MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

MUNICIPALIDAD DEL CALLAO

CALLAO - ABRIL
2023
ELABORACION DEL EXPEDIENTE TECNICO EN LA
ESPECIALIDAD DE INSTALACIONES ELETRICAS DEL
PROYECTO “MEJORAMIENTO DE LOS SERVICIOS DE
TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV.
SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO
‐ DEPARTAMENTO DE CALLAO CON CUI N° 2486138.

Consultor:
ICSCI EIRL
067
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

Contenido|
1. GENERALIDADES..................................................................................................................3
1.1. Introducción ...................................................................................................................3
1.2. Código y reglamento ....................................................................................................3
2. DEMANDA MAXIMA DE POTENCIA .................................................................................4
3. DATOS GENERALES DE LA AVENIDA A INTERVENIR .................................................4
3.1. Ubicación del Proyecto ................................................................................................4
3.2. Plano de Ubicación Geográfica ..................................................................................5
4. CALCULOS DE INGENIERIA ELECTRICA.........................................................................5
4.1. Cálculo de caída de tensión. .......................................................................................5
4.2. Cálculo de la intensidad de corriente admisible .......................................................6
4.3. Calculo potencia (W) ....................................................................................................6
4.4. Calculo factor de la demanda (F.D.) ..........................................................................6
4.5. Cálculo del conductor (S).............................................................................................7
4.6. Cálculo de sistema puesta a tierra .............................................................................7
4.7. Separación entre luminarias (d)..................................................................................8
5. MAXIMA DEMANDA ............................................................................................................9
6. ANEXOS ................................................................................................................................12
5.1. Procedimiento del cálculo de caída de tensión..................................................12
5.2. Procedimiento del cálculo de caída de tensión..................................................12
5.3. Procedimiento del cálculo de Calculo potencia (W) ..........................................12
5.4. Procedimiento del cálculo de factor de la demanda (F.D.). .............................13
5.5. Procedimiento del cálculo del conductor (S). .....................................................13
5.6. Procedimiento del cálculo de sistema puesta a tierra.......................................13
5.7. Procedimiento del cálculo de separación entre luminarias (d) ........................13
7. TABLAS .................................................................................................................................14

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
066
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

1. GENERALIDADES
1.1. Introducción
La presente memoria de cálculo corresponde al desarrollo del expediente
técnico de instalaciones Eléctricas destinadas al proyecto
“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD
VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ
SOLDAN Y LA AV. GUARDIA CHALACA, DISTRITO DE CALLAO -
PROVINCIA DE CALLAO - DEPARTAMENTO DE CALLAO. CON CUI N°
2486138.
El proyecto fue desarrollado de acuerdo con los planos de Arquitectura
existente y contemplado con la distribución de carga eléctrica de los
equipos suministrado por el concedente.
Está formado por:
 Cálculo de la Máxima demanda y Potencia contratada.
 Cálculo de la caída de tensión de los alimentadores.
 Calculo de la capacidad de interruptores termomagnéticos
principales y derivados.
 Calculo de sistema a tierra.
 Cálculo de separación de luminarias.

1.2. Código y reglamento

 CNE - Utilización 2006: "Código Nacional de Electricidad-


Utilización".
 CNE - Suministro 2011: "Código Nacional de Electricidad-
Suministro".
 RNE - "Reglamento Nacional de Edificaciones".
 NTP - "Norma Técnica Peruana".

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
065
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

2. DEMANDA MAXIMA DE POTENCIA


Para él cálculo de la máxima demanda se consideró:
 Cargas normalizadas para la salida eléctricas de alumbrado.
Para él cálculo de la demanda máxima y red de servicio público, se tomó en
cuenta el Código Nacional de Electricidad utilización 2009 y las Normas del
Ministerio de Energía y Minas y el reglamento de la ley de electricidad No
23406. El cuadro de cargas se adjunta en el Anexo del documento.

3. DATOS GENERALES DE LA AVENIDA A INTERVENIR


3.1. Ubicación del Proyecto
Departamento : Lima.
Provincia : Callao.
Distritos : Callao.
Localización : En la Av. Saenz Peña, tramo Ca. Paz Soldan - Av.
Guardia Chalaca - distrito de Callao - Provincia Constitucional del Callao
- Departamento de Callao.
Imagen N° 1 : En la Av. Sáenz peña, tramo Ca. Paz Soldán - Av. Guardia Chalaca-
distrito de Callao - Provincia Constitucional del Callao - Departamento de Callao.

UBICACIÓN
DEL
PROYECTO

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
064
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

3.2. Plano de Ubicación Geográfica

IMAGEN N° 2: Ubicación geográfica con limites distritales

4. CALCULOS DE INGENIERIA ELECTRICA.


4.1. Cálculo de caída de tensión.
Los parámetros considerados para el cálculo son los siguientes.

a) Caída máxima permisible de tensión igual a 2,5% de la tensión nominal.

b) Factor de potencia igual a 0.85 para alimentadores

c) Factor de potencia igual a 0.85 para equipos de fuerza. Se considera


necesario acotar el estado de la vía, a fin de conocer el comportamiento del
tránsito vehicular frente a estas variables.

Donde:

%ΔV = Caída de tensión en porcentaje

S = sección del conductor

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
063
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

In = Corriente en Amp. nominal

L = Longitud en metros.

Vn = Tensión de operación

P = 0.01786

4.2. Cálculo de la intensidad de corriente admisible

4.3. Calculo potencia (W)

4.4. Calculo factor de la demanda (F.D.)


Es la relación entre la suma de la demanda máxima de un sistema (o parte
de un sistema) y la carga total conectada en el sistema (o parte del sistema)
bajo consideración. El factor de demanda es siempre menor o igual a uno.

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
062
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

4.5. Cálculo del conductor (S)

4.6. Cálculo de sistema puesta a tierra


Para el cálculo de la puesta a tierra, se está considerando un sistema
que sirva y proteja a los circuitos y equipos de alumbrado.
En principio, el sistema de puesta a tierra estará constituidaau por un
electrodo de cobre dentro de una zanja rellena y compactada con tierra
de chacra. Se está considerándola siguiente expresión de H. B. Dwight,
específica para el caso de una varilla vertical con relleno de cemento
conductivo y tierra de cutltivo
Resistencia de terreno =

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
061
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

De acuerdo al cuadro, para nuestro caso corresponde la resistividad de


600 ohm-m. Debido a la naturaleza del terreno se ha considerado
reemplazar la tierra del terreno por tierra de cultivo cuya resistividad está
alrededor de los 50 ohm-m.

Ρ= 500 ohm-m
L= 2.4m
R1= 0.5m
P1= 0.5 ohm-m
R=0.15m

RJ = 13.003 Ohm

4.7. Separación entre luminarias (d)


Una vez fijados los datos de entrada, podemos proceder al cálculo de la
separación (d) entre las luminarias utilizando la expresión de la iluminancia
media.

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
060
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

5. MAXIMA DEMANDA

PROYECTO DE ILUMINACIÓN AV SAENZ PEÑA

MAXIMA DEMANDA TABLERO GENERAL (TG ‐01)

ITEM USOS CANT. P.I(W) F.D.(%) M.D.(W)


LUMINARIA,
LED DE 55W IP66 IK08 10KV
1 57 3135 1 3135
TC4000K 6050LM

9 OTROS/RESERVA 1 500 1 500


TOTAL (M.D) 3635
TOTAL, POTENCIA CONTRATADA M.D 3635 1.2 4362

POTENCIA A CONTRATAR 5KW

CARGA INSTALADA(KW): 3.64


MAXIMA DEMANDA (KW): 3.64

MAXIMA DEMANDA TABLERO GENERAL (TG ‐02)

ITEM USOS CANT. P.I(W) F.D.(%) M.D.(W)


LUMINARIA,
LED DE 55W IP66 IK08 10KV
1 59 3245 1 3245
TC4000K 6050LM

9 OTROS/RESERVA 1 500 1 500


TOTAL (M.D) 3,745
TOTAL, POTENCIA CONTRATADA M.D 3,745 1.2 4,494

POTENCIA A CONTRATAR 5KW

CARGA INSTALADA(KW): 3.75


MAXIMA DEMANDA (KW): 3.75

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
059
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

MAXIMA DEMANDA TABLERO GENERAL (TG ‐03)

ITEM USOS CANT. P.I(W) F.D.(%) M.D.(W)


LUMINARIA,
LED DE 55W IP66 IK08 10KV
1 55 3025 1 3,025
TC4000K 6050LM

9 OTROS/RESERVA 1 500 1 500


TOTAL (M.D) 3,525
TOTAL, POTENCIA CONTRATADA M.D 3,525 1.2 4,230

POTENCIA A CONTRATAR 5KW

CARGA INSTALADA(KW): 3.53


MAXIMA DEMANDA (KW): 3.53

MAXIMA DEMANDA TABLERO GENERAL (TG ‐04)

ITEM USOS CANT. P.I(W) F.D.(%) M.D.(W)


LUMINARIA, LED DE 55W IP66
IK08 10KV TC4000K 6050LM
1 56 3080 1 3,080

9 OTROS/RESERVA 1 500 1 500


TOTAL (M.D) 3,580
TOTAL, POTENCIA CONTRATADA M.D 3,580 1.2 4,296

POTENCIA A CONTRATAR 5KW

CARGA INSTALADA(KW): 3.58


MAXIMA DEMANDA (KW): 3.58

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
058
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

MAXIMA DEMANDA TABLERO GENERAL (TG ‐05)

ITEM USOS CANT. P.I(W) F.D.(%) M.D.(W)


LUMINARIA,
LED DE 55W IP66 IK08 10KV
1 58 3190 1 3,190
TC4000K 6050LM

9 OTROS/RESERVA 1 500 1 500


TOTAL (M.D) 3,690
TOTAL, POTENCIA CONTRATADA M.D 3,690 1.2 4,428

POTENCIA A CONTRATAR 5KW

CARGA INSTALADA(KW): 3.69


MAXIMA DEMANDA (KW): 3.69

MAXIMA DEMANDA TABLERO GENERAL (TG ‐06)

F.D.
ITEM USOS CANT. P.I(W) M.D.(W)
(%)
LUMINARIAS LED 120W
1 15600LM IP66 TC6500K 83 9960 1 9960

9 OTROS/RESERVA 1 500 1 500


TOTAL (M.D) 10,460
TOTAL, POTENCIA CONTRATADA M.D 10,460 1.2 12,552

POTENCIA A CONTRATAR 13KW

CARGA INSTALADA(KW): 10.46


MAXIMA DEMANDA (KW): 10.46

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
057
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

6. ANEXOS
5.1. Procedimiento del cálculo de caída de tensión
La caida de tension se evalua en cada circuito acorde a las normas vigentes.

5.3. Procedimiento del cálculo de Calculo potencia (W)

• Ya sea un Sistema monofasico o trifasico, la potencia electrica total es


la suma algebraica de las potencias individuales

5.4. Procedimiento del cálculo de factor de la demanda (F.D.).

• El factor de demanda es la relacion entre la potencia instalada y la


demanda utilizada en un determinado momento del dia.

5.5. Procedimiento del cálculo del conductor (S).

• Una vez realizado el calculod e la caida de tension se procede a


verificar la capacidad de corriente admissible y de esta manera se
selecciona el conductor que sera utilizado

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
056
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

7. TABLAS
CÁLCULOS ELÉCTRICOS DE ALIMENTADOR Y TABLERO /CAIDA DE TENSIÓN (TG‐1)

CANTID CARGA
ITEM UBICACIÓN TABLERO CIRCUITOS P.I(W) F.D M.D.(W) In(A) Id(A) TIPO L(m) S(mm2) ΔV (v) ΔV(v)%
AD UNITARIA

C‐1 28 55 1540 1
TG‐01 3135 9.14 11.43 3Ø 12 10 0.30 0.14
1 JR. PEDRO RUIZ
C‐2 29 55 1595 1

TG‐01 3135 9.14 11.43 3Ø 16 10 0.40 0.18

TOTAL DE POTENCIA CONTRATADA (KW) M.D(KW) 3.135 1.2 3.762

POTENCIA A CONTRATAR 5KW

CARGA INSTALADA(KW): 3.14 CARGA INSTALADA(W): 3135

MAXIMA DEMANDA (KW): 3.14 3135


MAXIMA DEMANDA (W):

1.‐ CALCULO DEL CABLE ALIMENTADOR POR CAPACIDAD DE CORRIENTE

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 3.14 Kw
Fa ctor de res erva FR= 1.25
Factor de Potencia Cos Ø= 0.9
Tens ión nomina l V= 220 V, 3Ø
Eva luando:
In= 9.1414 A
Id= 11.43 A
SELECCIÓN DEL CONDUCTOR
El conductor a propia do pa ra es ta
corriente nomina l es: 3‐1x10 mm2 N2XOH

2.‐ CALCULO DEL CABLE ALIMENTADOR POR CAIDA DE TENSIÓN

ΔV= k * ρ * I x(L/S )*cos Ø


Donde:
Longi tud en metros L= 10 m
Corriente nomina l I= 9.14 A
Sección del conductor en mm2 S= 10 mm2
Factor de potencia CosØ= 0.9
Coefi ci ente res istividad del cobre ρ= 0.0175 ohm‐mm2/m
Consta nte que depende del s is tema K= 1.732 K= 1.732 Trifa s ico
Tens ión del s is tema V= 220 V K= 2 Monofa s i co
ΔV= 0.25 V
ΔV= 0.11 % ca i da de tens ión a cepta ble inferior a 1.5%
Má xima Ca ída de tensi ón permitida : 3.3 vol ti os ó 1.5%

SELECCIÓN DEL CONDUCTOR


El conductor que cumple con la
máxima ca ida de tens ion es: 3‐1x10 mm2 N2X0H

A. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐1)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 1540.00 w
Fa ctor de res erva FR= 1.25
Factor de Potencia Cos Ø= 0.9
Tens ión nomina l V= 220 V, 3Ø
Eva luando:
In= 4.4905 A
Id= 5.61 A
SELECCIÓN DEL CONDUCTOR
El conductor a propia do pa ra es ta
corriente nomina l es: 3‐1x10 mm2 N2XOH

B. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐2)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 1595.00 W
Fa ctor de res erva FR= 1.25
Factor de Potencia Cos Ø= 0.9
Tens ión nomina l V= 220 V, 3Ø
Eva luando:
In= 4.6509 A
Id= 5.81 A
SELECCIÓN DEL CONDUCTOR
El conductor a propia do pa ra es ta
corriente nomina l es: 3‐1x10 mm2 N2XOH

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
055
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

CAIDA DE TENSION - ILUMINACION AV. SAENZ PEÑA


ΔV = K.I.L/1000

ΔV: CAIDA DE TENSION (V) K= √3(r.cosφ+x.senφ) TRIFASICO


K: FACTOR DE CAIDA DE TENSION K= 2(r.cosφ+x.senφ) MONOFASICO
L= LONGITUD (m)

M.D.(W) U (V) F.P. I (A) Id (A) S(mm²) L(m) r(ohm/km) x(ohm/km) K ΔV(V) ΔV(%)
TABLERO TG-01 CIRCUITO 1

LP-1 825 220 0.90 2.41 3.01 10 46.40 1.995 0.166 3.235 0.45 0.21%
LP-2 770 220 0.90 2.25 2.81 10 9.11 1.995 0.166 3.235 0.08 0.04%
LP-3 715 220 0.90 2.08 2.61 10 8.00 1.995 0.166 3.235 0.07 0.03%
LP-4 660 220 0.90 1.92 2.41 10 9.06 1.995 0.166 3.235 0.07 0.03%
LP-5 605 220 0.90 1.76 2.21 10 11.11 1.995 0.166 3.235 0.08 0.04%
LP-6 550 220 0.90 1.60 2.00 10 11.07 1.995 0.166 3.235 0.07 0.03%
LP-7 495 220 0.90 1.44 1.80 10 12.70 1.995 0.166 3.235 0.07 0.03%
LP-8 440 220 0.90 1.28 1.60 10 11.56 1.995 0.166 3.235 0.06 0.03%
LP-9 385 220 0.90 1.12 1.40 10 12.64 1.995 0.166 3.235 0.06 0.03%
LP-10 330 220 0.90 0.96 1.20 10 11.11 1.995 0.166 3.235 0.04 0.02%
LP-11 275 220 0.90 0.80 1.00 10 9.93 1.995 0.166 3.235 0.03 0.01%
LP-12 220 220 0.90 0.64 0.80 10 10.03 1.995 0.166 3.235 0.03 0.01%
LP-13 165 220 0.90 0.48 0.60 10 9.97 1.995 0.166 3.235 0.02 0.01%
LP-14 110 220 0.90 0.32 0.40 10 10.00 1.995 0.166 3.235 0.01 0.01%
LP-15 55 220 0.90 0.16 0.20 10 10.00 1.995 0.166 3.235 0.01 0.00%
L(m) ΔV(V) ΔV(%)
TOTAL 193 1.15 0.52%

M.D.(W) U (V) F.P. I (A) Id (A) S(mm²) L(m) r(ohm/km) x(ohm/km) K ΔV(V) ΔV(%)
TABLERO TG-01 CIRCUITO 2

LP-1 880 220 0.90 2.57 3.21 10 10.00 1.995 0.166 3.235 0.10 0.05%
LP-2 825 220 0.90 2.41 3.01 10 27.98 1.995 0.166 3.235 0.27 0.12%
LP-3 770 220 0.90 2.25 2.81 10 10.00 1.995 0.166 3.235 0.09 0.04%
LP-4 715 220 0.90 2.08 2.61 10 10.00 1.995 0.166 3.235 0.08 0.04%
LP-5 660 220 0.90 1.92 2.41 10 10.00 1.995 0.166 3.235 0.08 0.04%
LP-6 605 220 0.90 1.76 2.21 10 10.00 1.995 0.166 3.235 0.07 0.03%
LP-7 550 220 0.90 1.60 2.00 10 10.00 1.995 0.166 3.235 0.06 0.03%
LP-8 495 220 0.90 1.44 1.80 10 10.00 1.995 0.166 3.235 0.06 0.03%
LP-9 440 220 0.90 1.28 1.60 10 10.00 1.995 0.166 3.235 0.05 0.02%
LP-10 385 220 0.90 1.12 1.40 10 10.00 1.995 0.166 3.235 0.05 0.02%
LP-11 330 220 0.90 0.96 1.20 10 10.00 1.995 0.166 3.235 0.04 0.02%
LP-12 275 220 0.90 0.80 1.00 10 10.00 1.995 0.166 3.235 0.03 0.01%
LP-13 220 220 0.90 0.64 0.80 10 10.00 1.995 0.166 3.235 0.03 0.01%
LP-14 165 220 0.90 0.48 0.60 10 10.00 1.995 0.166 3.235 0.02 0.01%
LP-15 110 220 0.90 0.32 0.40 10 10.00 1.995 0.166 3.235 0.01 0.01%
LP-16 55 220 0.90 0.16 0.20 10 10.00 1.995 0.166 3.235 0.01 0.00%
L(m) ΔV(V) ΔV(%)
TOTAL 177.98 1.06 0.48%

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
054
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

CÁLCULOS ELÉCTRICOS DE ALIMENTADOR Y TABLERO /CAIDA DE TENSIÓN (TG‐2)

CARGA
ITEM UBICACIÓN TABLERO CIRCUITOS CANTIDAD P.I(W) F.D M.D.(W) In(A) Id(A) TIPO L(m) S(mm2) ΔV(v) ΔV(v)%
UNITARI
A

C‐1 26 55 1430 1
TG‐01 3245 9.46 11.83 3Ø 12 10 0.31 0.14
1 JR. MARCO POLO
C‐2 33 55 1815 1

TG‐01 3245 9.46 11.83 3Ø 16 10 0.41 0.19

TOTAL DE POTENCIA
CONTRATADA (KW) M.D(KW) 3.245 1.2 3.894

POTENCIA A CONTRATAR 5KW

CARGA INSTALADA(KW): 3.25 CARGA INSTALADA(W): 3245

MAXIMA DEMANDA (KW): 3.25 MAXIMA DEMANDA (W): 3245

1.‐ CALCULO DEL CABLE ALIMENTADOR POR CAPACIDAD DE CORRIENTE

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 3.25 Kw
Factor de reserva FR= 1.25
Factor de Potencia CosØ= 0.9
Tensión nominal V= 220 V, 3Ø
Evaluando:
In= 9.4621A
Id= 11.83 A
SELECCIÓN DEL CONDUCTOR
El conductor
apropiado para esta 3‐1x10 mm2 N2XOH

2.‐ CALCULO DEL CABLE ALIMENTADOR POR CAIDA DE TENSIÓN

ΔV= k * ρ * I x(L/S )*cos Ø


Donde:
Longitud en metros L= 9m
Corriente nominal I= 9.46 A
Sección del conductor en m S= 10 mm2
Factor de potencia CosØ= 0.9
Coeficiente resistividad del c ρ= 0.0175 ohm‐mm2/m
Constante que depende del sis K= 1.732 K= 1.732 Trifasico
Tensión del sistema V= 220 V K= 2 Monofasico
ΔV= 0.23 V
ΔV= 0.11 % caida de tensión aceptable inferior a 1.5%
Máxima Caída de tensión permitida: 3.3 voltios ó 1.5%

SELECCIÓN DEL CONDUCTOR


cumple con la máxima
caida de tension es: 3‐1x10 mm2 N2X0H

A. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐1)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 1430.00 w
Factor de reserva FR= 1.25
Factor de Potencia CosØ= 0.9
Tensión nominal V= 220 V, 3Ø
Evaluando:
In= 4.1698A
Id= 5.21 A
SELECCIÓN DEL CONDUCTOR
apropiado para esta
corriente nominal es 3‐1x10 mm2 N2XOH
:

B. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐2)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 1815.00 W
Factor de reserva FR= 1.25
Factor de Potencia CosØ= 0.9
Tensión nominal V= 220 V, 3Ø
Evaluando:
In= 5.2924A
Id= 6.62 A
SELECCIÓN DEL CONDUCTOR
El conductor
apropiado para esta
corriente nominal es 3‐1x10 mm2 N2XOH
:

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
053
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

M.D.(W) U (V) F.P. I (A) Id (A) S(mm²) L(m) r(ohm/km) x(ohm/km) K ΔV(V) ΔV(%)
TABLERO TG-02 CIRCUITO 1

LP-1 880 220 0.90 2.57 3.21 10 3.73 1.995 0.166 3.235 0.04 0.02%
LP-2 825 220 0.90 2.41 3.01 10 19.36 1.995 0.166 3.235 0.19 0.09%
LP-3 770 220 0.90 2.25 2.81 10 22.51 1.995 0.166 3.235 0.20 0.09%
LP-4 715 220 0.90 2.08 2.61 10 10.00 1.995 0.166 3.235 0.08 0.04%
LP-5 660 220 0.90 1.92 2.41 10 9.75 1.995 0.166 3.235 0.08 0.03%
LP-6 605 220 0.90 1.76 2.21 10 9.50 1.995 0.166 3.235 0.07 0.03%
LP-7 550 220 0.90 1.60 2.00 10 9.76 1.995 0.166 3.235 0.06 0.03%
LP-8 495 220 0.90 1.44 1.80 10 10.00 1.995 0.166 3.235 0.06 0.03%
LP-9 440 220 0.90 1.28 1.60 10 9.75 1.995 0.166 3.235 0.05 0.02%
LP-10 385 220 0.90 1.12 1.40 10 9.52 1.995 0.166 3.235 0.04 0.02%
LP-11 330 220 0.90 0.96 1.20 10 9.18 1.995 0.166 3.235 0.04 0.02%
LP-12 275 220 0.90 0.80 1.00 10 9.04 1.995 0.166 3.235 0.03 0.01%
LP-13 220 220 0.90 0.64 0.80 10 9.04 1.995 0.166 3.235 0.02 0.01%
LP-14 165 220 0.90 0.48 0.60 10 9.04 1.995 0.166 3.235 0.02 0.01%
LP-15 110 220 0.90 0.32 0.40 10 9.72 1.995 0.166 3.235 0.01 0.01%
LP-16 55 220 0.90 0.16 0.20 10 10.00 1.995 0.166 3.235 0.01 0.00%
L(m) ΔV(V) ΔV(%)
TOTAL 169.92 1.00 0.45%

M.D.(W) U (V) F.P. I (A) Id (A) S(mm²) L(m) r(ohm/km) x(ohm/km) K ΔV(V) ΔV(%)
TABLERO TG-02 CIRCUITO 2

LP-1 880 220 0.90 2.57 3.21 10 5.11 1.995 0.166 3.235 0.05 0.02%
LP-2 825 220 0.90 2.41 3.01 10 25.96 1.995 0.166 3.235 0.25 0.11%
LP-3 770 220 0.90 2.25 2.81 10 10.99 1.995 0.166 3.235 0.10 0.05%
LP-4 715 220 0.90 2.08 2.61 10 10.55 1.995 0.166 3.235 0.09 0.04%
LP-5 660 220 0.90 1.92 2.41 10 10.44 1.995 0.166 3.235 0.08 0.04%
LP-6 605 220 0.90 1.76 2.21 10 12.63 1.995 0.166 3.235 0.09 0.04%
LP-7 550 220 0.90 1.60 2.00 10 12.41 1.995 0.166 3.235 0.08 0.04%
LP-8 495 220 0.90 1.44 1.80 10 11.08 1.995 0.166 3.235 0.06 0.03%
LP-9 440 220 0.90 1.28 1.60 10 10.95 1.995 0.166 3.235 0.06 0.03%
LP-10 385 220 0.90 1.12 1.40 10 11.07 1.995 0.166 3.235 0.05 0.02%
LP-11 330 220 0.90 0.96 1.20 10 10.00 1.995 0.166 3.235 0.04 0.02%
LP-12 275 220 0.90 0.80 1.00 10 10.00 1.995 0.166 3.235 0.03 0.01%
LP-13 220 220 0.90 0.64 0.80 10 20.00 1.995 0.166 3.235 0.05 0.02%
LP-14 165 220 0.90 0.48 0.60 10 10.00 1.995 0.166 3.235 0.02 0.01%
LP-15 110 220 0.90 0.32 0.40 10 10.00 1.995 0.166 3.235 0.01 0.01%
LP-16 55 220 0.90 0.16 0.20 10 10.00 1.995 0.166 3.235 0.01 0.00%
L(m) ΔV(V) ΔV(%)
TOTAL 191.18 1.08 0.49%

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
052
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

CÁLCULOS ELÉCTRICOS DE ALIMENTADOR Y TABLERO /CAIDA DE TENSIÓN (TG‐3)

CARGA
ITEM UBICACIÓN TABLERO CIRCUITOS CANTIDAD P.I(W) F.D M.D.(W) In(A) Id(A) TIPO L(m) S(mm2) ΔV(v) ΔV(v)%
UNITARIA

C‐1 33 55 1815 1
TG‐01 3025 8.82 11.03 3Ø 12 10 0.29 0.13
1 JR. PUNO
C‐2 22 55 1210 1

TG‐01 3025 8.82 11.03 3Ø 16 10 0.38 0.17

TOTAL DE POTENCIA CONTRATADA


(KW) M.D(KW) 3.025 1.2 3.63

POTENCIA A CONTRATAR 5KW

CARGA INSTALADA(KW): 3.03 CARGA INSTALADA(W): 3025

MAXIMA DEMANDA (KW): 3.03 3025


MAXIMA DEMANDA (W):

1.‐ CALCULO DEL CABLE ALIMENTADOR POR CAPACIDAD DE CORRIENTE

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 3.03 Kw
Factor de reserva FR= 1.25
Factor de Potenci a CosØ= 0.9
Tensi ón nominal V= 220 V, 3Ø
Evaluando:
In= 8.8206 A
Id= 11.03 A
SELECCIÓN DEL CONDUCTOR
El conductor apropi ado
para esta corri ente 3‐1x10 mm2 N2XOH

2.‐ CALCULO DEL CABLE ALIMENTADOR POR CAIDA DE TENSIÓN

ΔV= k * ρ * I x(L/S )*cos Ø


Donde:
Longitud en metros L= 9 m
Corriente nominal I= 8.82 A
Sección del conductor en mm S= 10 mm2
Factor de potenci a CosØ= 0.9
Coefi ciente resistividad del co ρ= 0.0175 ohm‐mm2/m
Constante que depende del si ste K= 1.732 K= 1.732 Trifasico
Tensi ón del s istema V= 220 V K= 2 Monofasi co
ΔV= 0.22 V
ΔV= 0.10 % caida de tensión aceptabl e i nferior a 1.5%
Máxima Caída de tens ión permi ti da: 3.3 volti os ó 1.5%

SELECCIÓN DEL CONDUCTOR


con l a máxima caida de
tension es: 3‐1x10 mm2 N2X0H

A. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐1)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 1815.00 w
Factor de reserva FR= 1.25
Factor de Potenci a CosØ= 0.9
Tensi ón nominal V= 220 V, 3Ø
Evaluando:
In= 5.2924 A
Id= 6.62 A
SELECCIÓN DEL CONDUCTOR
para esta corri ente
nomi nal es: 3‐1x10 mm2 N2XOH

B. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐2)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 1210.00 W
Factor de reserva FR= 1.25
Factor de Potenci a CosØ= 0.9
Tensi ón nominal V= 220 V, 3Ø
Evaluando:
In= 3.5283 A
Id= 4.41 A
SELECCIÓN DEL CONDUCTOR
El conductor apropi ado
para esta corri ente
nomi nal es: 3‐1x10 mm2 N2XOH

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
051
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

CÁLCULOS ELÉCTRICOS DE ALIMENTADOR Y TABLERO /CAIDA DE TENSIÓN (TG‐4)

CARGA
ITEM UBICACIÓN TABLERO CIRCUITOS CANTIDAD P.I(W) F.D M.D.(W) In(A) Id(A) TIPO L(m) S(mm2) ΔV(v) ΔV(v)%
UNITARI
A

C‐1 33 55 1815 1
TG‐01 3025 8.82 11.03 3Ø 12 10 0.29 0.13
1 JR. VILLAR
C‐2 22 55 1210 1

TG‐01 3025 8.82 11.03 3Ø 16 10 0.38 0.17

TOTAL DE POTENCIA CONTRATADA


(KW) M.D(KW) 3.025 1.2 3.63

POTENCIA A CONTRATAR 5KW

CARGA INSTALADA(KW): 3.03 CARGA INSTALADA(W): 3025

MAXIMA DEMANDA (KW): 3.03 MAXIMA DEMANDA (W): 3025

1.‐ CALCULO DEL CABLE ALIMENTADOR POR CAPACIDAD DE CORRIENTE

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 3.03 Kw
Factor de reserva FR= 1.25
Factor de Potencia CosØ= 0.9
Tensión nominal V= 220 V, 3Ø
Evaluando:
In= 8.8206A
Id= 11.03 A
SELECCIÓN DEL CONDUCTOR
El conductor apropiado
para esta corriente 3‐1x10 mm2 N2XOH

2.‐ CALCULO DEL CABLE ALIMENTADOR POR CAIDA DE TENSIÓN

ΔV= k * ρ * I x(L/S )*cos Ø


Donde:
Longitud en metros L= 11 m
Corriente nominal I= 8.82 A
Sección del conductor en mm S= 10 mm2
Factor de potencia CosØ= 0.9
Coeficiente resistividad del co ρ= 0.0175 ohm‐mm2/m
Constante que depende del sist K= 1.732 K= 1.732 Trifasico
Tensión del sistema V= 220 V K= 2 Monofasico
ΔV= 0.26 V
ΔV= 0.12 % caida de tensión aceptable inferior a 1.5%
Máxima Caída de tensión permitida: 3.3 voltios ó 1.5%

SELECCIÓN DEL CONDUCTOR


con la máxima caida de
tension es: 3‐1x10 mm2 N2X0H

A. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐1)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 1815.00 w
Factor de reserva FR= 1.25
Factor de Potencia CosØ= 0.9
Tensión nominal V= 220 V, 3Ø
Evaluando:
In= 5.2924A
Id= 6.62 A
SELECCIÓN DEL CONDUCTOR
para esta corriente
nominal es: 3‐1x10 mm2 N2XOH

B. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐2)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 1210.00 W
Factor de reserva FR= 1.25
Factor de Potencia CosØ= 0.9
Tensión nominal V= 220 V, 3Ø
Evaluando:
In= 3.5283A
Id= 4.41 A
SELECCIÓN DEL CONDUCTOR
El conductor apropiado
para esta corriente
nominal es: 3‐1x10 mm2 N2XOH

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
050
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

M.D.(W) U (V) F.P. I (A) Id (A) S(mm²) L(m) r(ohm/km) x(ohm/km) K ΔV(V) ΔV(%)
TABLERO TG-04 CIRCUITO 1

LP-1 770 220 0.90 2.25 2.81 10 42.32 1.995 0.166 3.235 0.38 0.17%
LP-2 715 220 0.90 2.08 2.61 10 10.05 1.995 0.166 3.235 0.08 0.04%
LP-3 660 220 0.90 1.92 2.41 10 9.96 1.995 0.166 3.235 0.08 0.04%
LP-4 605 220 0.90 1.76 2.21 10 11.09 1.995 0.166 3.235 0.08 0.04%
LP-5 550 220 0.90 1.60 2.00 10 12.53 1.995 0.166 3.235 0.08 0.04%
LP-6 495 220 0.90 1.44 1.80 10 12.60 1.995 0.166 3.235 0.07 0.03%
LP-7 440 220 0.90 1.28 1.60 10 10.51 1.995 0.166 3.235 0.05 0.02%
LP-8 385 220 0.90 1.12 1.40 10 10.62 1.995 0.166 3.235 0.05 0.02%
LP-9 330 220 0.90 0.96 1.20 10 12.00 1.995 0.166 3.235 0.05 0.02%
LP-10 275 220 0.90 0.80 1.00 10 12.16 1.995 0.166 3.235 0.04 0.02%
LP-11 220 220 0.90 0.64 0.80 10 10.41 1.995 0.166 3.235 0.03 0.01%
LP-12 165 220 0.90 0.48 0.60 10 10.73 1.995 0.166 3.235 0.02 0.01%
LP-13 110 220 0.90 0.32 0.40 10 12.05 1.995 0.166 3.235 0.02 0.01%
LP-14 55 220 0.90 0.16 0.20 10 11.02 1.995 0.166 3.235 0.01 0.00%
L(m) ΔV(V) ΔV(%)
TOTAL 188.03 1.04 0.47%

M.D.(W) U (V) F.P. I (A) Id (A) S(mm²) L(m) r(ohm/km) x(ohm/km) K ΔV(V) ΔV(%)
TABLERO TG-04 CIRCUITO 2

LP-1 715 220 0.90 2.08 2.61 10 36.33 1.995 0.166 3.235 0.31 0.14%
LP-2 660 220 0.90 1.92 2.41 10 10.525 1.995 0.166 3.235 0.08 0.04%
LP-3 605 220 0.90 1.76 2.21 10 10.464 1.995 0.166 3.235 0.07 0.03%
LP-4 550 220 0.90 1.60 2.00 10 10.395 1.995 0.166 3.235 0.07 0.03%
LP-5 495 220 0.90 1.44 1.80 10 10.452 1.995 0.166 3.235 0.06 0.03%
LP-6 440 220 0.90 1.28 1.60 10 10.629 1.995 0.166 3.235 0.06 0.03%
LP-7 385 220 0.90 1.12 1.40 10 10.656 1.995 0.166 3.235 0.05 0.02%
LP-8 330 220 0.90 0.96 1.20 10 10.281 1.995 0.166 3.235 0.04 0.02%
LP-9 275 220 0.90 0.80 1.00 10 9.194 1.995 0.166 3.235 0.03 0.01%
LP-10 220 220 0.90 0.64 0.80 10 10.253 1.995 0.166 3.235 0.03 0.01%
LP-11 165 220 0.90 0.48 0.60 10 11.147 1.995 0.166 3.235 0.02 0.01%
LP-12 110 220 0.90 0.32 0.40 10 9.99 1.995 0.166 3.235 0.01 0.01%
LP-13 55 220 0.90 0.16 0.20 10 9.996 1.995 0.166 3.235 0.01 0.00%
L(m) ΔV(V) ΔV(%)
TOTAL 160.31 0.83 0.38%

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
049
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

CÁLCULOS ELÉCTRICOS DE ALIMENTADOR Y TABLERO /CAIDA DE TENSIÓN (TG‐5)

CARGA
ITEM UBICACIÓN TABLERO CIRCUITOS CANTIDAD P.I(W) F.D M.D.(W) In(A) Id(A) TIPO L(m) S(mm2) ΔV(v) ΔV(v)%
UNITARIA

C‐1 24 55 1320 1
TG‐01 3190 9.30 11.63 3Ø 12 10 0.30 0.14
1 JR. VIGIL
C‐2 34 55 1870 1

TG‐01 3190 9.30 11.63 3Ø 16 10 0.41 0.18

TOTAL DE POTENCIA
M.D(KW) 3.19 1.2 3.828
CONTRATADA (KW)

POTENCIA A CONTRATAR 5KW

CARGA INSTALADA(KW): 3.19 3190


CARGA IN STALADA(W):
MAXIMA DEMANDA (KW): 3.19 3190
MAXIMA DEMANDA (W):

1.‐ CALCULO DEL CABLE ALIMENTADOR POR CAPACIDAD DE CORRIENTE

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demand MD= 3.19 Kw
Factor de reserv FR= 1.25
Factor de Potenc CosØ= 0.9
Tens i ón nomi na V= 220 V, 3Ø
Eval uando:
In= 9.3018 A
Id= 11.63 A
SELECCIÓN DEL CONDUCTOR
El conductor
apropi ado 3‐1x10 mm2 N2XOH

2.‐ CALCULO DEL CABLE ALIMENTADOR POR CAIDA DE TENSIÓN

ΔV= k * ρ * I x(L/S )*cos Ø


Donde:
Longi tud en metr L= 12 m
Corri ente nomi n I= 9.30 A
Secci ón del conductor S= 10 mm2
Factor de potenc CosØ= 0.9
Coefi ci ente resi sti vi dad ρ= 0.0175 ohm‐mm2/m
Cons tante que depende d K= 1.732 K= 1.732 Tri fasi co
Tens i ón del si ste V= 220 V K= 2 Monofa si co
ΔV= 0.30 V
ΔV= 0.14 % cai da de tens i ón acepta bl e inferi or a 1.5%
Máxima Caída de tens ión permi ti da : 3.3 volti os ó 1.5%

SELECCIÓN DEL CONDUCTOR


que cumpl e
con l a 3‐1x10 mm2 N2X0H

A. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐1)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demand MD= 1320.00 w
Factor de reserv FR= 1.25
Factor de Potenc CosØ= 0.9
Tens i ón nomi na V= 220 V, 3Ø
Eval uando:
In= 3.8490 A
Id= 4.81 A
SELECCIÓN DEL CONDUCTOR
apropi ado
para esta 3‐1x10 mm2 N2XOH

B. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐2)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demand MD= 1870.00 W
Factor de reserv FR= 1.25
Factor de Potenc CosØ= 0.9
Tens i ón nomi na V= 220 V, 3Ø
Eval uando:
In= 5.4528 A
Id= 6.82 A
SELECCIÓN DEL CONDUCTOR
El conductor
apropi ado
para esta
corri ente
nomi nal es: 3‐1x10 mm2 N2XOH

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
048
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

M.D.(W) U (V) F.P. I (A) Id (A) S(mm²) L(m) r(ohm/km) x(ohm/km) K ΔV(V) ΔV(%)
TABLERO TG-05 CIRCUITO 1

LP-1 770 220 0.90 2.25 2.81 10 5.41 1.995 0.166 3.235 0.05 0.02%
LP-2 715 220 0.90 2.08 2.61 10 19.17 1.995 0.166 3.235 0.16 0.07%
LP-3 660 220 0.90 1.92 2.41 10 10.00 1.995 0.166 3.235 0.08 0.04%
LP-4 605 220 0.90 1.76 2.21 10 10.00 1.995 0.166 3.235 0.07 0.03%
LP-5 550 220 0.90 1.60 2.00 10 37.35 1.995 0.166 3.235 0.24 0.11%
LP-6 495 220 0.90 1.44 1.80 10 12.65 1.995 0.166 3.235 0.07 0.03%
LP-7 440 220 0.90 1.28 1.60 10 11.08 1.995 0.166 3.235 0.06 0.03%
LP-8 385 220 0.90 1.12 1.40 10 11.07 1.995 0.166 3.235 0.05 0.02%
LP-9 330 220 0.90 0.96 1.20 10 11.58 1.995 0.166 3.235 0.05 0.02%
LP-10 275 220 0.90 0.80 1.00 10 11.54 1.995 0.166 3.235 0.04 0.02%
LP-11 220 220 0.90 0.64 0.80 10 11.59 1.995 0.166 3.235 0.03 0.01%
LP-12 165 220 0.90 0.48 0.60 10 11.55 1.995 0.166 3.235 0.02 0.01%
LP-13 110 220 0.90 0.32 0.40 10 11.08 1.995 0.166 3.235 0.01 0.01%
LP-14 55 220 0.90 0.16 0.20 10 10.00 1.995 0.166 3.235 0.01 0.00%
L(m) ΔV(V) ΔV(%)
TOTAL 184.05 0.94 0.43%

M.D.(W) U (V) F.P. I (A) Id (A) S(mm²) L(m) r(ohm/km) x(ohm/km) K ΔV(V) ΔV(%)
TABLERO TG-05 CIRCUITO 2

LP-1 770 220 0.90 2.25 2.81 10 2.17 1.995 0.166 3.235 0.02 0.01%
LP-2 715 220 0.90 2.08 2.61 10 35.29 1.995 0.166 3.235 0.30 0.14%
LP-3 660 220 0.90 1.92 2.41 10 10.85 1.995 0.166 3.235 0.08 0.04%
LP-4 605 220 0.90 1.76 2.21 10 13.11 1.995 0.166 3.235 0.09 0.04%
LP-5 550 220 0.90 1.60 2.00 10 13.01 1.995 0.166 3.235 0.08 0.04%
LP-6 495 220 0.90 1.44 1.80 10 11.22 1.995 0.166 3.235 0.07 0.03%
LP-7 440 220 0.90 1.28 1.60 10 31.93 1.995 0.166 3.235 0.17 0.08%
LP-8 385 220 0.90 1.12 1.40 10 11.38 1.995 0.166 3.235 0.05 0.02%
LP-9 330 220 0.90 0.96 1.20 10 11.22 1.995 0.166 3.235 0.04 0.02%
LP-10 275 220 0.90 0.80 1.00 10 12.85 1.995 0.166 3.235 0.04 0.02%
LP-11 220 220 0.90 0.64 0.80 10 11.77 1.995 0.166 3.235 0.03 0.01%
LP-12 165 220 0.90 0.48 0.60 10 11.77 1.995 0.166 3.235 0.02 0.01%
LP-13 110 220 0.90 0.32 0.40 10 12.82 1.995 0.166 3.235 0.02 0.01%
LP-14 55 220 0.90 0.16 0.20 10 11.02 1.995 0.166 3.235 0.01 0.00%
L(m) ΔV(V) ΔV(%)
TOTAL 200.41 1.02 0.47%

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
047
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

CÁLCULOS ELÉCTRICOS DE ALIMENTADOR Y TABLERO /CAIDA DE TENSIÓN (TG‐6)

CARGA
ITEM UBICACIÓN TABLERO CIRCUITOS CANTIDAD P.I(W) F.D M.D.(W) In(A) Id(A) TIPO L(m) S(mm2) ΔV(v) ΔV(v)%
UNITARI
A

C‐1 35 120 4200 1


TG‐01 9960 29.04 36.30 3Ø 12 10 0.95 0.43
1 JR. PALACIOS
C‐2 48 120 5760 1

TG‐01 9960 29.04 36.30 3Ø 16 10 1.27 0.58

TOTAL DE POTENCIA
CONTRATADA (KW) M.D(KW) 9.96 1.2 11.952

POTENCIA A CONTRATAR 13KW

CARGA INSTALADA(KW): 9.96 9960


CARGA INSTALADA(W):

MAXIMA DEMANDA (KW): 9.96 9960


MAXIMA DEMANDA (W):

1.‐ CALCULO DEL CABLE ALIMENTADOR POR CAPACIDAD DE CORRIENTE

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 9.96 Kw
Factor de reserva FR= 1.25
Factor de Potenci a Cos Ø= 0.9
Tensión nomi nal V= 220 V, 3Ø
Evaluando:
In= 29.0425 A
Id= 36.30 A
SELECCIÓN DEL CONDUCTOR
El conductor
apropi ado para 3‐1x35 mm2 N2XOH

2.‐ CALCULO DEL CABLE ALIMENTADOR POR CAIDA DE TENSIÓN

ΔV= k * ρ * I x(L/S )*cos Ø


Donde:
Longitud en metros L= 11 m
Corriente nomi nal I= 29.04 A
Secci ón del conductor en S= 35 mm2
Factor de potenci a Cos Ø= 0.9
Coefi ciente resis ti vi dad del ρ= 0.0175 ohm‐mm2/m
Constante que depende del s K= 1.732 K= 1.732 Trifas ico
Tensión del sistema V= 220 V K= 2 Monofasico
ΔV= 0.25 V
ΔV= 0.11 % cai da de tens i ón aceptable i nferi or a 1.5%
Máxima Caída de tens i ón permi tida: 3.3 vol ti os ó 1.5%

SELECCIÓN DEL CONDUCTOR


cumpl e con l a
máxima caida de 3‐1x35 mm2 N2X0H

A. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐1)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 4200.00 w
Factor de reserva FR= 1.25
Factor de Potenci a Cos Ø= 0.9
Tensión nomi nal V= 220 V, 3Ø
Evaluando:
In= 12.2468 A
Id= 15.31 A
SELECCIÓN DEL CONDUCTOR
apropi ado para
esta corriente 3‐1x35 mm2 N2XOH

B. CALCULO DEL CABLE DEL CIRCUITO DERIVADO POR CAPACIDAD DE CORRIENTE (C‐2)

In=MD/(√3*Vn*CosØ)
Donde:
Máxima Demanda MD= 5760.00 W
Factor de reserva FR= 1.25
Factor de Potenci a Cos Ø= 0.9
Tensión nomi nal V= 220 V, 3Ø
Evaluando:
In= 16.7956 A
Id= 20.99 A
SELECCIÓN DEL CONDUCTOR
El conductor
apropi ado para
esta corriente
nomi nal es: 3‐1x35 mm2 N2XOH

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138
046
MEMORIA DE CÁLCULO
MUNICIPALIDAD DEL CALLAO INSTALACIONES ELÉCTRICAS

M.D.(W) U (V) F.P. I (A) Id (A) S(mm²) L(m) r(ohm/km) x(ohm/km) K ΔV(V) ΔV(%)
TABLERO TG-06 CIRCUITO 1

LP-1 4200 220 0.90 12.25 15.31 35 22.43 0.798 0.152 1.359 0.47 0.21%
LP-2 4080 220 0.90 11.90 14.87 35 9.97 0.081 0.074 0.182 0.03 0.01%
LP-3 3960 220 0.90 11.55 14.43 35 9.68 0.081 0.074 0.182 0.03 0.01%
LP-4 3840 220 0.90 11.20 14.00 35 9.40 0.081 0.074 0.182 0.02 0.01%
LP-5 3720 220 0.90 10.85 13.56 35 12.19 0.081 0.074 0.182 0.03 0.01%
LP-6 3600 220 0.90 10.50 13.12 35 8.69 0.081 0.074 0.182 0.02 0.01%
LP-7 3480 220 0.90 10.15 12.68 35 8.69 0.081 0.074 0.182 0.02 0.01%
LP-8 3360 220 0.90 9.80 12.25 35 11.19 0.081 0.074 0.182 0.02 0.01%
LP-9 3240 220 0.90 9.45 11.81 35 10.19 0.081 0.074 0.182 0.02 0.01%
LP-10 3120 220 0.90 9.10 11.37 35 21.56 0.081 0.074 0.182 0.04 0.02%
LP-11 3000 220 0.90 8.75 10.93 35 9.97 0.081 0.074 0.182 0.02 0.01%
LP-12 2880 220 0.90 8.40 10.50 35 24.65 0.081 0.074 0.182 0.05 0.02%
LP-13 2760 220 0.90 8.05 10.06 35 10.19 0.081 0.074 0.182 0.02 0.01%
LP-14 2640 220 0.90 7.70 9.62 35 10.19 0.081 0.074 0.182 0.02 0.01%
LP-15 2520 220 0.90 7.35 9.19 35 10.19 0.081 0.074 0.182 0.02 0.01%
LP-16 2400 220 0.90 7.00 8.75 35 10.19 0.081 0.074 0.182 0.02 0.01%
LP-17 2280 220 0.90 6.65 8.31 35 10.19 0.081 0.074 0.182 0.02 0.01%
LP-18 2160 220 0.90 6.30 7.87 35 10.19 0.081 0.074 0.182 0.01 0.01%
LP-19 2040 220 0.90 5.95 7.44 35 10.19 0.081 0.074 0.182 0.01 0.01%
LP-20 1920 220 0.90 5.60 7.00 35 10.19 0.081 0.074 0.182 0.01 0.01%
LP-21 1800 220 0.90 5.25 6.56 35 19.13 0.081 0.074 0.182 0.02 0.01%
LP-22 1680 220 0.90 4.90 6.12 35 9.97 0.081 0.074 0.182 0.01 0.01%
LP-23 1560 220 0.90 4.55 5.69 35 9.97 0.081 0.074 0.182 0.01 0.00%
LP-24 1440 220 0.90 4.20 5.25 35 9.97 0.081 0.074 0.182 0.01 0.00%
LP-25 1320 220 0.90 3.85 4.81 35 9.97 0.081 0.074 0.182 0.01 0.00%
LP-26 1200 220 0.90 3.50 4.37 35 9.97 0.081 0.074 0.182 0.01 0.00%
LP-27 1080 220 0.90 3.15 3.94 35 9.97 0.081 0.074 0.182 0.01 0.00%
LP-28 960 220 0.90 2.80 3.50 35 9.97 0.081 0.074 0.182 0.01 0.00%
LP-29 840 220 0.90 2.45 3.06 35 9.97 0.081 0.074 0.182 0.01 0.00%
LP-30 720 220 0.90 2.10 2.62 35 9.97 0.081 0.074 0.182 0.00 0.00%
LP-31 600 220 0.90 1.75 2.19 35 9.97 0.081 0.074 0.182 0.00 0.00%
LP-32 480 220 0.90 1.40 1.75 35 9.97 0.081 0.074 0.182 0.00 0.00%
LP-33 360 220 0.90 1.05 1.31 35 9.97 0.081 0.074 0.182 0.00 0.00%
LP-34 240 220 0.90 0.70 0.87 35 9.97 0.081 0.074 0.182 0.00 0.00%
LP-35 120 220 0.90 0.35 0.44 35 9.97 0.081 0.074 0.182 0.00 0.00%
L(m) ΔV(V) ΔV(%)
TOT AL 398.84 1.01 0.46%

M.D.(W) U (V) F.P. I (A) Id (A) S(mm²) L(m) r(ohm/km) x(ohm/km) K ΔV(V) ΔV(%)
TABLERO TG-06 CIRCUITO 2

LP-1 5760 220 0.90 16.80 20.99 35 7.49 0.798 0.152 1.359 0.21 0.10%
LP-2 5640 220 0.90 16.45 20.56 35 9.97 0.081 0.074 0.182 0.04 0.02%
LP-3 5520 220 0.90 16.10 20.12 35 9.97 0.081 0.074 0.182 0.04 0.02%
LP-4 5400 220 0.90 15.75 19.68 35 9.97 0.081 0.074 0.182 0.04 0.02%
LP-5 5280 220 0.90 15.40 19.25 35 9.97 0.081 0.074 0.182 0.03 0.02%
LP-6 5160 220 0.90 15.05 18.81 35 9.97 0.081 0.074 0.182 0.03 0.02%
LP-7 5040 220 0.90 14.70 18.37 35 9.97 0.081 0.074 0.182 0.03 0.02%
LP-8 4920 220 0.90 14.35 17.93 35 9.97 0.081 0.074 0.182 0.03 0.01%
LP-9 4800 220 0.90 14.00 17.50 35 9.97 0.081 0.074 0.182 0.03 0.01%
LP-10 4680 220 0.90 13.65 17.06 35 9.96 0.081 0.074 0.182 0.03 0.01%
LP-11 4560 220 0.90 13.30 16.62 35 10.47 0.081 0.074 0.182 0.03 0.01%
LP-12 4440 220 0.90 12.95 16.18 35 11.56 0.081 0.074 0.182 0.03 0.02%
LP-13 4320 220 0.90 12.60 15.75 35 12.21 0.081 0.074 0.182 0.04 0.02%
LP-14 4200 220 0.90 12.25 15.31 35 10.04 0.081 0.074 0.182 0.03 0.01%
LP-15 4080 220 0.90 11.90 14.87 35 10.03 0.081 0.074 0.182 0.03 0.01%
LP-16 3960 220 0.90 11.55 14.43 35 19.03 0.081 0.074 0.182 0.05 0.02%
LP-17 3840 220 0.90 11.20 14.00 35 11.08 0.081 0.074 0.182 0.03 0.01%
LP-18 3720 220 0.90 10.85 13.56 35 10.03 0.081 0.074 0.182 0.02 0.01%
LP-19 3600 220 0.90 10.50 13.12 35 10.03 0.081 0.074 0.182 0.02 0.01%
LP-20 3480 220 0.90 10.15 12.68 35 10.03 0.081 0.074 0.182 0.02 0.01%
LP-21 3360 220 0.90 9.80 12.25 35 10.04 0.081 0.074 0.182 0.02 0.01%
LP-22 3240 220 0.90 9.45 11.81 35 9.53 0.081 0.074 0.182 0.02 0.01%
LP-23 3120 220 0.90 9.10 11.37 35 10.54 0.081 0.074 0.182 0.02 0.01%
LP-24 3000 220 0.90 8.75 10.93 35 10.03 0.081 0.074 0.182 0.02 0.01%
LP-25 2880 220 0.90 8.40 10.50 35 10.03 0.081 0.074 0.182 0.02 0.01%
LP-26 2760 220 0.90 8.05 10.06 35 10.03 0.081 0.074 0.182 0.02 0.01%
LP-27 2640 220 0.90 7.70 9.62 35 9.04 0.081 0.074 0.182 0.02 0.01%
LP-28 2520 220 0.90 7.35 9.19 35 11.00 0.081 0.074 0.182 0.02 0.01%
LP-29 2400 220 0.90 7.00 8.75 35 10.00 0.081 0.074 0.182 0.02 0.01%
LP-30 2280 220 0.90 6.65 8.31 35 10.00 0.081 0.074 0.182 0.02 0.01%
LP-31 2160 220 0.90 6.30 7.87 35 10.00 0.081 0.074 0.182 0.01 0.01%
LP-32 2040 220 0.90 5.95 7.44 35 34.24 0.081 0.074 0.182 0.05 0.02%
LP-33 1920 220 0.90 5.60 7.00 35 13.06 0.081 0.074 0.182 0.02 0.01%
LP-34 1800 220 0.90 5.25 6.56 35 17.00 0.081 0.074 0.182 0.02 0.01%
LP-35 1680 220 0.90 4.90 6.12 35 10.03 0.081 0.074 0.182 0.01 0.01%
LP-36 1560 220 0.90 4.55 5.69 35 10.03 0.081 0.074 0.182 0.01 0.00%
LP-37 1440 220 0.90 4.20 5.25 35 12.43 0.081 0.074 0.182 0.01 0.01%
LP-38 1320 220 0.90 3.85 4.81 35 7.64 0.081 0.074 0.182 0.01 0.00%
LP-39 1200 220 0.90 3.50 4.37 35 10.03 0.081 0.074 0.182 0.01 0.00%
LP-40 1080 220 0.90 3.15 3.94 35 10.03 0.081 0.074 0.182 0.01 0.00%
LP-41 960 220 0.90 2.80 3.50 35 10.03 0.081 0.074 0.182 0.01 0.00%
LP-42 840 220 0.90 2.45 3.06 35 10.04 0.081 0.074 0.182 0.01 0.00%
LP-43 720 220 0.90 2.10 2.62 35 10.03 0.081 0.074 0.182 0.00 0.00%
LP-44 600 220 0.90 1.75 2.19 35 10.04 0.081 0.074 0.182 0.00 0.00%
LP-45 480 220 0.90 1.40 1.75 35 10.03 0.081 0.074 0.182 0.00 0.00%
LP-46 360 220 0.90 1.05 1.31 35 10.03 0.081 0.074 0.182 0.00 0.00%
LP-47 240 220 0.90 0.70 0.87 35 10.03 0.081 0.074 0.182 0.00 0.00%
LP-48 180 220 0.90 0.52 0.66 35 10.03 0.081 0.074 0.182 0.00 0.00%
L(m) ΔV(V) ΔV(%)
TOT AL 526.70 1.20 0.54%

“MEJORAMIENTO DE LOS SERVICIOS DE TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA AV. SAENZ PEÑA, ENTRE JR. PAZ SOLDAN Y LA AV. GUARDIA
CHALACA, DISTRITO DE CALLAO ‐ PROVINCIA DE CALLAO ‐ DEPARTAMENTO DE CALLAO” con Código Único N° 2486138