Gateway Profibus address mapping for Mk5 controller

GA75_08 gen. 5 , API526134 Mk5 controller must be in Mk5 CAN profil


1900525592 - FS Graphic 2.0.21.0 Fixed Speed
21-12-2020 13:34:24 Register Address Bytes = B2B3

Analog Inputs Data Record


Name Type Unit B2B3 (reg) B4B5 (W1) B6B7 (W2) Value Interpretation
Salida del compresor Pressure (mB mBar 0
Salida Elemento Temperature 0.1 °C 2 Value StatusValues are S16. 32767 = Sensor error.
Aire ambiente Temperature 0.1 °C 4

Digital Inputs Data Record


Name B2B3 (reg) B4B5 (W1) B6B7 (W2) Functional Interpretation 0/1
Parada de emergencia 500 Abierto / Cerrado
Sobrec motor/motor ventilador 501 Abierto / Cerrado
Value Status
Purga Electrónica 503 Abierto / Cerrado
Selección de ajuste de Presión 509 Banda de Presión 1 / Banda de Presión 2
Bit Description (1/0)
0 PreWarning
1 Warning
2 ShutdownWarning
3 Shutdown
4 Service
5 Permissive
6 Sensor Error
7 Set/Not set
8 SPM valid measurement
13 PrePermissive

Digital Outputs Data Record


Name B2B3 (reg) B6B7 (W2) Functional Interpretation 0/1
Contactor de línea 2550 Abierto / Cerrado
Contactor de estrella 2551 Abierto / Cerrado
Contactor de triángulo 2552 Abierto / Cerrado
Carga/Descarga 2553 Value Abierto / Cerrado
Parada por alarma general 2554 Abierto / Cerrado
Operación automática 2556 Abierto / Cerrado
Aviso general 2557 Abierto / Cerrado

Counters Data Record


Name Unit B2B3 (reg) B4B5B6B7 (W1W2) Reference counters for % calculation
Horas de marcha s 1000

Value
Horas en carga s 1001
Arranques de motor Count 1002 Value
Relé de carga Count 1003
Horas del módulo s 1006

Special Alarms Data Record


Name B2B3 (reg) B6B7 (W2)
Protección de giro del motor 2700
Presión de control no válida 2702 Status
Comunicación Módulo Expansión 2741
Bit Description (1/0)
0 PreWarning
1 Warning
3 Shutdown

Machine Control Mode


Register 700 - B2B3
Name Value - B5
2a - Local Start/Stop & Pressure Sensing 0
3a - Remote Start/Stop, Local Pressure 1
4a - Communication Start/stop, Local Pr 2
2b - Local Start/Stop, Digital Contact Pr 16
3b - Remote Start/Stop, Digital Contact 17
4b - Communication Start/Stop & SPS Co 18
4c - Communication Start/Stop & Speed 34
4d - ES/EQ Controlled 50
2e - Local Start/Stop & 4-20mA Speed Co 64
3e - Remote Start/Stop & 4-20mA Speed 65
4e - Communication Start/Stop & 4-20m 66

Machine Mechanical State


Register 700 - B2B3
Name Value - B6
Stop 1
Unload 2
Loaded 4

General Status
Register 701 - B2B3
Name Bit - B6B7(W2)
PreWarning 0
General Warning 1
General Shutdown Warning 2
General Shutdown 3
General Service 4
General Start Failure 5
Emergency Stop 6
Manual/Automatic 7
Local/Remote 8
Week Timer 9
PreWarning Service Running Hours 10
- 11
PreWarning Service Analog Input 12
PrePermissive 13
Test Mode 14

ESi/EQi Status
Register 704 - B2B3
Name Value - B6B7(W2)
PowerUp ES/EQ 8209
Local Operation ES/EQ 8225
Central Stop ES/EQ 8242
Shutdown ES/EQ 8337
Automatic Operation ES/EQ 24594

Regulation Parameters B4B5B6B7-W1W2-


Name B2B3 (reg) Value Read Value Write Info
Pressure Band Selection 860 PB1=>1, PB2=>2
PB1=>1, PB2=>2 used in local pressure sensing mode
Pressure Band 1 - Load 861 mBar n/a
Pressure Band 1 - Unload 862 mBar n/a
Pressure Band 2 - Load 863 mBar n/a
Pressure Band 2 - Unload 864 mBar n/a
External Load Pressure 874 mBar n/a
External Unload Pressure 875 mBar n/a

ES(i) Pressure Band Selection 880 PB1=>1, PB2=>2


PB1=>1, PB2=>2 used in local pressure sensing mode
ES(i) Pressure Band 1 - Load 881 mBar n/a
ES(i) Pressure Band 1 - UnLoad 882 mBar n/a
ES(i) Pressure Band 2 - Load 883 mBar n/a
ES(i) Pressure Band 2 - UnLoad 884 mBar n/a

Commands - LAN mode B4B5B6B7-W1W2-


Name Register Value Read Value Write Info
Start 2000 n/a 1 Start the main machine
Stop 2000 n/a 2 stop the main machine
Load 2000 n/a 3
Unload 2000 n/a 4
StartES 2000 n/a 5
StopES 2000 n/a 6
LocalES 2000 n/a 7
Load50 2000 n/a 8

Change4A4B_TO4C 2001 n/a 3


/ Banda de Presión 2

rs for % calculation