Electrical
GCP-1001-01-CS-0136A
26148-226-V32-EZL0-00364 008
GCP-1001-01-CS-0136A-0740-E-ES-00001
Nº Documento 7813-02-ES-IF-001
Fecha Revisión
25-10-2023 10
06-09-2023 9
Aprobó
www.sdi-ingenieria.cl
7813-02-ES-IF-001
Índice
1 Introducción ............................................................................................................ 5
2 Alcance .................................................................................................................. 5
3 Objetivo .................................................................................................................. 5
3.1 Objetivos Específicos ............................................................................................. 5
4 Antecedentes ......................................................................................................... 6
5 Sistema Eléctrico .................................................................................................... 7
6 Escenarios de Operación ....................................................................................... 7
7 Sistema Equivalente S/E Quillota 220 kV ............................................................... 8
8 Criterios de Ajuste de Protecciones ........................................................................ 9
8.1 Criterios Generales................................................................................................. 9
8.2 Protección de Alimentadores de Media Tensión ..................................................... 9
8.2.1 Protección de Sobre corriente (50/51) .................................................................. 10
8.2.2 Protección de Falla a Tierra (50G/51G) ................................................................ 10
8.2.3 Protección Sub/Sobre Tensión (27/59) ................................................................. 10
8.3 Protección de transformadores de Media Tensión ................................................ 10
8.3.1 Protección de Sobre corriente (50/51) .................................................................. 10
8.3.2 Protección de Falla a Tierra (50G/51G) ................................................................ 11
8.3.3 Protección Sub/Sobre Tensión (27/59) ................................................................. 11
8.3.4 Protección diferencial de transformadores ............................................................ 11
8.4 Protección de Motores de Media Tensión............................................................. 11
8.4.1 Protección de Imagen Térmica por Sobre carga (49M) ........................................ 12
8.4.2 Protección de Rotor Bloqueado (51LR) ................................................................ 12
8.4.3 Protección de Cortocircuito (50M) ........................................................................ 12
8.4.4 Protección de Desbalance de Corriente (46M) ..................................................... 12
8.4.5 Protección Bajo/Sobre tensión (27M/59M) ........................................................... 12
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
1 Introducción
2 Alcance
Cabe destacar que sólo se analizan los alimentadores del switchgear principal 740-SG-001
que se dirigen a la planta MLP_INCO, y no el resto de los alimentadores del switchgear.
3 Objetivo
www.sdi-ingenieria.cl
4 Antecedentes
5 Sistema Eléctrico
Para la realización de este estudio se cuenta con la base de datos en el Software ETAP 20,
en donde se modelaron las protecciones de sobrecorriente de fase y tierra, en los
switchgears correspondientes que se observa en la Figura 1.
6 Escenarios de Operación
Los casos de operación que se consideran en este estudio, para verificar la coordinación
de protecciones eléctricas correspondientes al sistema eléctrico se indican a continuación:
Caso de operación normal: Este caso operacional consiste en que todas las
cargas correspondientes de MLP_INCO se encuentran activas.
www.sdi-ingenieria.cl
Fallas trifásicas
Monofásica a tierra sin resistencia de falla
Para el cálculo de las corrientes de cortocircuito trifásico y monofásico del SEP del proyecto
MLP_INCO, se considera lo siguiente:
Quillota 220
www.sdi-ingenieria.cl
El criterio se ha basado en el Standard IEEE 242-2001 (Buff Book) IEEE C37.91 Y C37.96,
los que han sido aplicados al proyecto.
Para motores de características similares que estén alimentados desde una misma barra,
se mostrará la coordinación de protección de uno de ellos, siendo sus ajustes válidos para
los demás motores. En el caso de existir conflictos en los criterios protección y coordinación,
siempre prevalecerá el concepto de protección de las personas y de los equipos por sobre
la coordinación o selectividad.
Los alimentadores de media tensión serán protegidos mediante relés de protección General
Electric modelo Multilin 850.
www.sdi-ingenieria.cl
Las características de retardo de tiempo serán del tipo “tiempo extremadamente inverso”.
La característica instantánea se excluirá de requerirse. Los rangos de ajuste deberán estar
entre el 50% y el 200% de la corriente nominal; para la característica de retardo de tiempo
con un ajuste de retardo de tiempo de 0.1 a 10 segundos, y 700% a 3000% de la corriente
nominal para operación instantánea.
El rango de ajuste deberá estar entre 5% a 50% de la corriente de falla de tierra, con un
retardo de tiempo de 0.1 a 2 seg. para la función de sobre corriente y de 50% a 500% para
la función instantánea.
La función de bajo voltaje ANSI 27 es regulado a 75% del voltaje nominal con un tiempo de
retardo de 3 seg y curva de tiempo definido.
La función de sobre tensión ANSI 59 es regulado a 115% del voltaje nominal con un tiempo
de retardo de 3 seg y curva de tiempo definido.
La regulación de cortocircuito del lado primario será al menos 10 veces la corriente nominal,
con un factor de asimetría de 1,6 veces la corriente de “pickup” o disparo del lado
secundario.
www.sdi-ingenieria.cl
Rango de ajuste deberá estar entre 5% a 50% de la corriente de falla de tierra, con un
retardo de tiempo de 0.1 a 2 seg. para la función de sobre corriente y de 50% a 500% para
la función instantánea.
La función de bajo voltaje ANSI 27 es regulado a 75% del voltaje nominal con un tiempo de
retardo de 3 seg y curva de tiempo definido.
La función de sobre tensión ANSI 59 es regulado a 115% del voltaje nominal con un tiempo
de retardo de 3 seg y curva de tiempo definido.
Los transformadores de potencia superior o igual a 7.5 MVA se protegerán con un esquema
de protección diferencial de transformador de acuerdo con la siguiente tabla.
Los Motores de media tensión serán protegidos mediante relés de protección General
Electric modelo Multilin 869.
www.sdi-ingenieria.cl
Para Motores de Media tensión el ajuste por sobrecarga térmica considera lo siguiente:
Para este caso se considerará un rango de ajuste de 10 a 20 veces la corriente nominal del
motor si la protección es sensible a las corrientes transitorias en el rotor del motor; de lo
contrario, el rango de configuración podrá reducirse de 5 a 10 veces la corriente nominal
del motor. No se configurará protección por sobre corriente cuando el partidor del motor
está equipado con fusibles.
La función de bajo voltaje ANSI 27 es regulado a 75% del voltaje nominal con un tiempo de
retardo de 3 s y curva de tiempo definido.
La función de sobre tensión ANSI 59 es regulado a 115% del voltaje nominal con un tiempo
de retardo de 3 s y curva de tiempo definido.
Para fijar los límites de alarma y disparo de las RTDs de los descansos de los motores,
cuando no estén definidos por el fabricante, se tendrá lo siguiente:
www.sdi-ingenieria.cl
Para fijar los límites de alarma y disparo de las RTD de enrollados, se definen los
siguientes criterios, según la clase de aislación del motor.
La función 50BF evalúa si el interruptor principal que recibe la señal de apertura operó
correctamente. Se sugiere utilizar los siguientes ajustes para corriente mínima de
operación:
Nota: Se recomienda para las protecciones asociadas al transformador (GE 845) incluir
arranque externo, disparo de las protecciones mecánicas del transformador.
Para motores de baja tensión el ajuste por sobrecarga térmica considera lo siguiente:
www.sdi-ingenieria.cl
Los tiempos de pasos entre las protecciones aguas abajo y aguas arriba será de 150 ms.
La protección de falla a tierra será ajustada a un pickup de 1 Amp, con un tiempo de disparo
instantáneo.
Nota: Se considera una eficiencia de motores en baja tensión IE2, según lo indicado por el
cliente.
www.sdi-ingenieria.cl
En esta sección se muestran los ajustes actuales del switchgear la planta MLP_INCO, en
23 kV.
Tabla 6: Ajustes actuales de las protecciones del Switchgear principal 740-SG-001.
TOC IOC
Device Trip
Relay ID Manufacturer Model CT Ratio Curve Tap Prim. Tap Prim. Inst.
Function Element TMD
(Pickup) Amps (Pickup) Amps Delay
740-SG-001-1_52-8_Relay GE Multilin 750/760 3000:5 Overcurrent Phase ANSI - Extremely Inverse 0,87 2610 3,5 - - -
740-SG-001-1_52-8_Relay GE Multilin 750/760 200:5 Overcurrent Ground ANSI - Extremely Inverse 0,20 40 1,95 - - -
Rele 52_22 GE Multilin 750/760 3000:5 Overcurrent Phase ANSI - Extremely Inverse 0,87 2610 3,50 - - -
Rele 52_22 GE Multilin 750/760 200:5 Overcurrent Ground ANSI - Extremely Inverse 0,20 40 1,95 - - -
740-SG-001_52-42_Relay GE Multilin 750/760 3000:5 Overcurrent Phase ANSI - Extremely Inverse 0,30 900 13,86 3,08 9240 0,2 s
740-SG-001_52-42_Relay GE Multilin 750/760 50:5 Overcurrent Ground - - - - 4,02 201 0,1 s
740-SG-001_52-17_Relay GE Multilin 750/760 3000:5 Overcurrent Phase ANSI - Extremely Inverse 0,30 900 13,86 3,08 9240 0,2 s
740-SG-001_52-17_Relay GE Multilin 750/760 50:5 Overcurrent Ground - - - - 4,02 201 0,1 s
Rele 52_37 GE Multilin 750/760 1200:5 Overcurrent Phase ANSI - Extremely Inverse 0,53 636 3,50 10,00 12000 0,06 s
Rele 52_37 GE Multilin 750/760 50:5 Overcurrent Ground ANSI - Extremely Inverse 0,75 37,5 2,00 - - -
Rele 52-25 GE Multilin 750/760 800:5 Overcurrent Phase ANSI - Extremely Inverse 0,80 640 5,00 4,90 3920 0,08 s
Rele 52-25 GE Multilin 750/760 50:5 Overcurrent Ground ANSI - Extremely Inverse 0,25 12,5 1,00 0,40 20 0,01 s
0740-SG-5002_52-501_Relay GE Multilin 850 (50Hz) 3000:1 Overcurrent Phase ANSI Extremely Inverse 0,40 1200 3,61 2,931 8793 0,084 s
0740-SG-5002_52-104_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,16 192 4,00 2,300 2760 0,04 s
0740-SG-5002_52-104_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,701 70,1 0,043 s
0740-SG-5002_52-105_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Phase ANSI Extremely Inverse 0,16 16 4,48 2,410 241 0,04 s
0740-SG-5002_52-105_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,701 70,1 0,043 s
0740-SG-5002_52-106_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,80 960 3,98 6,648 7978 0,075 s
0740-SG-5002_52-106_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,713 71,3 0,043 s
0740-SG-5002_52-107_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,35 420 7,02 4,500 5400 0,04 s
0740-SG-5002_52-107_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,701 70,1 0,044 s
0740-SG-5002_52-108_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,30 360 2,99 2,500 3000 0,04 s
0740-SG-5002_52-108_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,713 71,3 0,045 s
0740-SG-5002_52-201_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,16 192 4,00 2,300 2760 0,035 s
0740-SG-5002_52-201_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,600 60 0,067 s
0740-SG-5002_52-202_Relay GE Multilin 850 (50Hz) 600:5 Overcurrent Phase ANSI - Extremely Inverse 0,33 198 2,10 1,660 996 0,05 s
0740-SG-5002_52-202_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 1,130 113 0,08 s
0740-SG-5002_52-203_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,70 840 4,11 6,052 7262 0,064 s
0740-SG-5002_52-203_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 1,100 110 0,065 s
0740-SG-5002_52-204_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,30 360 2,99 2,500 3000 0,035 s
0740-SG-5002_52-204_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,679 67,9 0,066 s
0740-SG-5002_52-205_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Phase ANSI Extremely Inverse 0,16 16 4,48 2,410 241 0,036 s
0740-SG-5002_52-205_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,600 60 0,065 s
0740-SG-5002_52-206_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,33 396 7,02 4,300 5160 0,034 s
0740-SG-5002_52-206_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,600 60 0,068 s
0740-SG-5002_52-502_Relay GE Multilin 850 (50Hz) 3000:1 Overcurrent Phase ANSI Extremely Inverse 0,40 1200 3,13 2,758 8274 0,073 s
GE Multilin 350 (50Hz) 3000:1 Overcurrent Phase ANSI Extremely Inverse 0,40 1200 3,61 2,931 8793 0,084 s
52-601_Relay
GE Multilin 850 (50Hz) 3000:1 Overcurrent Phase ANSI Extremely Inverse 0,40 1200 3,61 2,931 8793 0,084 s
www.sdi-ingenieria.cl
TOC IOC
Device Trip
Relay ID Manufacturer Model CT Ratio Curve Tap Prim. Tap Prim. Inst.
Function Element TMD
(Pickup) Amps (Pickup) Amps Delay
0320-MC-5002_52-501_Relay GE Multilin 845 2000:5 Overcurrent Phase ANSI - Extremely Inverse 0,88 1760 3,29 5,38 10760 0,04 s
0320-MC-5002_52-501_Relay GE Multilin 845 50:5 Overcurrent Ground - - - - 3,92 196 0,048 s
0320-XF-5021-CB_Relay GE Multilin 845 400:5 Overcurrent Phase ANSI - Extremely Inverse 0,69 276 3,86 6,048 2419 0,04 s
0320-MC-5002_52-104_Relay GE Multilin 850 (50Hz) 800:5 Overcurrent Phase ANSI Extremely Inverse 0,30 240 8,27 6 4800 0,016 s
0320-MC-5002_52-104_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 2,621 131,1 0,014 s
0320-MC-5002_52-105_Relay GE Multilin 850 (50Hz) 800:5 Overcurrent Phase ANSI Extremely Inverse 0,55 440 8,91 6,8 5440 0,016 s
0320-MC-5002_52-105_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 2,621 131,1 0,015 s
0320-MC-5002_52-502_Relay GE Multilin 845 2000:5 Overcurrent Phase ANSI - Extremely Inverse 0,88 1760 3,68 5,535 11070 0,04 s
0320-MC-5002_52-502_Relay GE Multilin 845 50:5 Overcurrent Ground - - - - 0,654 32,7 0,059 s
0320-XF-5022-CB_Relay GE Multilin 845 400:5 Overcurrent Phase ANSI - Extremely Inverse 0,69 276 3,99 5,337 2135 0,049 s
0320-MC-5002_52-201_Relay GE Multilin 850 (50Hz) 800:5 Overcurrent Phase ANSI Extremely Inverse 0,20 160 5,00 1,8 1440 0,015 s
0320-MC-5002_52-201_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 0,4 20 0,014 s
0320-MC-5002_52-202_Relay GE Multilin 850 (50Hz) 800:5 Overcurrent Phase ANSI Extremely Inverse 0,55 440 7,00 6,8 5440 0,015 s
0320-MC-5002_52-202_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 0,4 20 0,014 s
0320-MC-5002_52-203_Relay GE Multilin 850 (50Hz) 800:5 Overcurrent Phase ANSI Extremely Inverse 0,15 120 7,00 1,3 1040 0,015 s
0320-MC-5002_52-203_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 0,4 20 0,024 s
0320-MC-5002_52-601_Relay GE Multilin 350 1200/5 Overcurrent Phase ANSI - Extremely Inverse - - - - - -
TOC IOC
Device Trip
Relay ID Manufacturer Model CT Ratio Curve Tap Prim. Tap Prim. Inst.
Function Element TMD
(Pickup) Amps (Pickup) Amps Delay
330MC331-CB15A-Relay GE Multilin 745 4000:5 Overcurrent Phase ANSI - Extremely Inverse 0,88 3520 4 2,5 10000 0,04 s
330MC331-CB15A-Relay GE Multilin 745 100:5 Overcurrent Ground ANSI - Extremely Inverse 0,20 20 5 - - -
330XF331B-Relay GE Multilin 745 800:5 Overcurrent Phase ANSI - Extremely Inverse 0,85 680 3,5 3,17 2536 0,05 s
Tabla 10: Ajustes actuales Fusibles de media tensión del Switchgear 330-MC-331.
Max
FUSE ID Manufacturer Model Speed Size Cont. Amp
Voltage
Fuse78 Cutler-Hammer CLS 5,5 kV Other 18R 390
www.sdi-ingenieria.cl
TOC IOC
Device Trip
Relay ID Manufacturer Model CT Ratio Curve Tap Prim. Tap Prim. Inst.
Function Element TMD
(Pickup) Amps (Pickup) Amps Delay
330-XF-380Relay ABB RET 541 400:5 Overcurrent Phase Extremely Inverse 0,52 208 1 6,23 2492 0,05 s
330-MC-380Relay ABB RET 541 3000:5 Overcurrent Phase Extremely Inverse 0,44 1320 0,7 4,38 13140 0,05 s
330-MC-380Relay ABB RET 541 100:5 Overcurrent Ground - - - - 0,4 40 0,06 s
330-MC-380-1_CT01_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-1_CT01_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
330-MC-380-2_CT02_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-2_CT02_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
330-MC-380-3_CT03_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-3_CT03_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
330-MC-380-4_CT04_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-4_CT04_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
330-MC-380-5_CT05_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-5_CT05_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
330-MC-380-6_CT06_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-6_CT06_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
Tabla 12: Ajustes actuales Fusibles de media tensión del Switchgear 330-MC-380.
Max
FUSE ID Manufacturer Model Speed Size Cont. Amp
Voltage
FU2 Cutler-Hammer CLS 5,5 kV Other 6R 170
FU4 Cutler-Hammer CLS 5,5 kV Other 6R 170
FU5 Cutler-Hammer CLS 5,5 kV Other 6R 170
FU6 Cutler-Hammer CLS 5,5 kV Other 6R 170
FU7 Cutler-Hammer CLS 5,5 kV Other 6R 170
FU8 Cutler-Hammer CLS 5,5 kV Other 6R 170
Tabla 14: Ajustes actuales Fusibles de media tensión del Switchgear 0320-SG-5001.
Max Cont.
FUSE ID Manufacturer Model Speed Size
Voltage Amp
FUS-5013 Cutler-Hammer BA-200 25 Other 200E 600
FUS-5014 Cutler-Hammer BA-200 25 Other 200E 600
www.sdi-ingenieria.cl
Tabla 16: Ajustes actuales Fusibles de media tensión del Switchgear 0320-SG-5002.
Max Cont.
FUSE ID Manufacturer Model Speed Size
Voltage Amp
FUS-5023 Cutler-Hammer BA-200 25 Other 200E 600
FUS-5024 Cutler-Hammer BA-200 25 Other 200E 600
www.sdi-ingenieria.cl
11 Verificación de Coordinación
Para verificar si los ajustes actuales de los alimentadores coordinan con el sistema bajo
estudio, se realiza una verificación de coordinación por tiempos de operación. Esta consiste
en modelar toda la instalación existente y simular fallas transitorias, las fallas que se
estudiarán serán las siguientes:
Fallas trifásicas
Monofásica a tierra sin resistencia de falla
Se simulará las fallas anteriormente descritas, en las instalaciones en forma separada, con
el objetivo de mostrar la coordinación de las protecciones.
Los tiempos de operación mostrados en el anexo I están coloreadas según los rangos de
tiempo de operación de cada función de protección, tal como se define a continuación:
www.sdi-ingenieria.cl
En esta sección se muestran los ajustes propuestos del switchgear de la planta MLP_INCO,
en 23 kV.
Tabla 18: Ajustes propuestos de las protecciones del Switchgear principal 740-SG-001.
IOC
Device Trip
Relay ID Manufacturer Model CT Ratio Curve Tap Prim. Tap Prim. Inst.
Function Element TMD
(Pickup) Amps (Pickup) Amps Delay
740-SG-001_52-08_Relay GE Multilin 750/760 3000:5 Overcurrent Phase Define Time - - - 0,880 2640 0,6 s
740-SG-001_52-08_Relay GE Multilin 750/760 200:5 Overcurrent Ground IAC Extreme Inverse 0,24 48 2,00 - - -
740-SG-001_52-08_Relay GE Multilin T60 200:5 Overcurrent Ground IAC Extreme Inverse 0,24 48 2 - - -
Rele 52_22 GE Multilin 750/760 3000:5 Overcurrent Phase Define Time - - - 0,880 2640 0,6 s
Rele 52_22 GE Multilin 750/760 200:5 Overcurrent Ground IAC Extreme Inverse 0,24 48 2 - - -
Rele 52_22 GE Multilin T60 200:5 Overcurrent Ground IAC Extreme Inverse 0,24 48 2,00 - - -
Rele 52_31 GE Multilin 750/760 3000:5 Overcurrent Phase Define Time - - - 0,880 2640 0,6 s
Rele 52_31 GE Multilin 750/760 200:5 Overcurrent Ground IAC Extreme Inverse 0,24 48 2,00 - - -
Rele 52_31 GE Multilin T60 200:5 Overcurrent Ground IAC Extreme Inverse 0,24 48 2,00 - - -
740-SG-001_52-42_Relay GE Multilin 750/760 3000:5 Overcurrent Phase ANSI - Extremely Inverse 0,30 900 13,86 3,080 9240 0,42 s
740-SG-001_52-42_Relay GE Multilin 750/760 50:5 Overcurrent Ground - - - - 4,020 201 0,2 s
740-SG-001_52-17_Relay GE Multilin 750/760 3000:5 Overcurrent Phase ANSI - Extremely Inverse 0,30 900 13,86 3,080 9240 0,42 s
740-SG-001_52-17_Relay GE Multilin 750/760 50:5 Overcurrent Ground - - - - 4,020 201 0,2 s
740-SG-001_52-38_Relay GE Multilin 750/760 100:5 Overcurrent Phase ANSI - Extremely Inverse 2,00 200 2,1 10 1000 0s
740-SG-001_52-38_Relay GE Multilin 750/760 50:5 Overcurrent Ground ANSI - Extremely Inverse 0,64 32 2,70 - - -
Rele 52_37 GE Multilin 750/760 1200:5 Overcurrent Phase ANSI - Extremely Inverse 0,53 636 3,50 10 12000 0,4 s
Rele 52_37 GE Multilin 750/760 50:5 Overcurrent Ground ANSI - Extremely Inverse 0,75 37,5 2,00 6 300 0,4 s
Rele 52-25 GE Multilin 750/760 800:5 Overcurrent Phase ANSI - Extremely Inverse 0,80 640 5,00 4,9 3920 0,4 s
Rele 52-25 GE Multilin 750/760 50:5 Overcurrent Ground ANSI - Extremely Inverse 0,25 13 1,00 0,4 20 0,3 s
www.sdi-ingenieria.cl
IOC
Device Trip
Relay ID Manufacturer Model CT Ratio Curve Tap Prim. Tap Prim. Inst.
Function Element TMD
(Pickup) Amps (Pickup) Amps Delay
0740-SG-5002_52-501_Relay GE Multilin 850 (50Hz) 3000:1 Overcurrent Phase ANSI Extremely Inverse 0,40 1200 3,61 2,931 8793 0,4 s
0740-SG-5002_52-101_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,20 240 4,00 2,300 2760 0,2 s
0740-SG-5002_52-101_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,043 s
0740-SG-5002_52-101_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,701 70,1 0,043 s
0740-SG-5002_52-102_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,20 240 4,00 2,300 2760 0,2 s
0740-SG-5002_52-102_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,043 s
0740-SG-5002_52-102_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,701 70,1 0,043 s
0740-SG-5002_52-103_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,20 240 4,00 2,300 2760 0,2 s
0740-SG-5002_52-103_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,043 s
0740-SG-5002_52-103_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,701 70,1 0,043 s
0740-SG-5002_52-104_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,20 240 4,00 2,300 2760 0,2 s
0740-SG-5002_52-104_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,043 s
0740-SG-5002_52-104_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,701 70,1 0,043 s
0740-SG-5002_52-105_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Phase ANSI Extremely Inverse 0,20 240 4,48 2,410 241 0,04 s
0740-SG-5002_52-105_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Neutral - - - - 0,701 70,1 0,043 s
0740-SG-5002_52-105_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,701 70,1 0,043 s
0740-SG-5002_52-106_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,80 960 3,98 6,648 7977,6 0,075 s
0740-SG-5002_52-106_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,043 s
0740-SG-5002_52-106_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,713 71,3 0,043 s
0740-SG-5002_52-107_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,35 420 7,02 4,500 5400 0,04 s
0740-SG-5002_52-107_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,044 s
0740-SG-5002_52-107_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,701 70,1 0,044 s
0740-SG-5002_52-108_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,30 360 2,99 2,500 3000 0,3 s
0740-SG-5002_52-108_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,045 s
0740-SG-5002_52-108_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,713 71,3 0,045 s
0740-SG-5002_52-201_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,20 240 4,00 2,300 2760 0,2 s
0740-SG-5002_52-201_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,067 s
0740-SG-5002_52-201_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,600 60 0,067 s
0740-SG-5002_52-202_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI - Extremely Inverse 0,20 240 2,10 1,660 1992 0,05 s
0740-SG-5002_52-202_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 1,13 113 0,08 s
0740-SG-5002_52-203_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,70 840 4,11 6,052 7262,4 0,064 s
0740-SG-5002_52-203_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,065 s
0740-SG-5002_52-203_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 1,100 110 0,065 s
0740-SG-5002_52-204_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,30 360 2,99 2,500 3000 0,3 s
0740-SG-5002_52-204_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,066 s
0740-SG-5002_52-204_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,679 67,9 0,066 s
0740-SG-5002_52-205_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Phase ANSI Extremely Inverse 0,20 20 4,48 2,41 241 0,036 s
0740-SG-5002_52-205_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Neutral - - - - 0,600 60 0,065 s
0740-SG-5002_52-205_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,6 60 0,065 s
0740-SG-5002_52-206_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Phase ANSI Extremely Inverse 0,33 396 7,02 4,300 5160 0,034 s
0740-SG-5002_52-206_Relay GE Multilin 850 (50Hz) 1200:1 Overcurrent Neutral - - - - 0,100 120 0,068 s
0740-SG-5002_52-206_Relay GE Multilin 850 (50Hz) 100:1 Overcurrent Ground - - - - 0,600 60 0,068 s
0740-SG-5002_52-502_Relay GE Multilin 850 (50Hz) 3000:1 Overcurrent Phase ANSI Extremely Inverse 0,40 1200 3,13 2,758 8274 0,4 s
GE Multilin 850 (50Hz) 3000:1 Overcurrent Phase ANSI Extremely Inverse 0,40 1200 3,61 2,931 8793 0,4 s
52-601_Relay
GE Multilin 350 (50Hz) 3000:1 Overcurrent Phase ANSI Extremely Inverse 0,40 1200 3,61 2,931 8793 0,4 s
www.sdi-ingenieria.cl
IOC
Device Trip
Relay ID Manufacturer Model CT Ratio Curve Tap Prim. Tap Prim. Inst.
Function Element TMD
(Pickup) Amps (Pickup) Amps Delay
0320-MC-5002_52-501_Relay GE Multilin 845 2000:5 Overcurrent Phase ANSI - Extremely Inverse 0,88 1760 3,29 5,380 10760 0,2 s
0320-MC-5002_52-501_Relay GE Multilin 845 50:5 Overcurrent Ground - - - - 3,920 196 0,3 s
0320-XF-5021-CB_Relay GE Multilin 845 400:5 Overcurrent Phase ANSI - Extremely Inverse 0,69 276 3,86 5,337 2134,8 0,2 s
0320-MC-5002_52-101_Relay GE Multilin 850 (50Hz) 150:5 Overcurrent Phase ANSI Extremely Inverse 0,15 22,5 7,00 1,300 195 0,015 s
0320-MC-5002_52-101_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 0,400 20 0,024 s
0320-MC-5002_52-102_Relay GE Multilin 850 (50Hz) 800:5 Overcurrent Phase ANSI Extremely Inverse 0,55 440,0 7,00 6,800 5440 0,015 s
0320-MC-5002_52-102_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 0,400 20 0,014 s
0320-MC-5002_52-103_Relay GE Multilin 850 (50Hz) 150:5 Overcurrent Phase ANSI Extremely Inverse 0,40 60,0 5,00 9,600 1440 0,015 s
0320-MC-5002_52-103_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 0,400 20 0,014 s
0320-MC-5002_52-104_Relay GE Multilin 850 (50Hz) 150:5 Overcurrent Phase ANSI Extremely Inverse 0,65 97,5 8,27 30 4500 0,016 s
0320-MC-5002_52-104_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 2,621 131,05 0,014 s
0320-MC-5002_52-105_Relay GE Multilin 850 (50Hz) 800:5 Overcurrent Phase ANSI Extremely Inverse 0,65 520 7 6,800 5440 0,016 s
0320-MC-5002_52-105_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 1,000 50 0,1 s
0320-MC-5002_52-502_Relay GE Multilin 845 2000:5 Overcurrent Phase ANSI - Extremely Inverse 0,88 1760 3,29 5,380 10760 0,2 s
0320-MC-5002_52-502_Relay GE Multilin 845 50:5 Overcurrent Ground - - - - 3,920 196 0,3 s
0320-XF-5022-CB_Relay GE Multilin 845 400:5 Overcurrent Phase ANSI - Extremely Inverse 0,69 276 3,86 5,337 2134,8 0,2 s
0320-MC-5002_52-201_Relay GE Multilin 850 (50Hz) 150:5 Overcurrent Phase ANSI Extremely Inverse 0,40 60 5 9,6 1440 0,015 s
0320-MC-5002_52-201_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 0,400 20 0,014 s
0320-MC-5002_52-202_Relay GE Multilin 850 (50Hz) 800:5 Overcurrent Phase ANSI Extremely Inverse 0,65 520 7 6,800 5440 0,016 s
0320-MC-5002_52-202_Relay GE Multilin 850 (50Hz) 50:5 Overcurrent Ground - - - - 1,000 50 0,1 s
0320-MC-5002_52-203_Relay GE Multilin 845 150:5 Overcurrent Phase ANSI Extremely Inverse 0,80 120 7 6,935 1040 0,015 s
0320-MC-5002_52-203_Relay GE Multilin 845 50:5 Overcurrent Ground - - - - 0,400 20 0,024 s
0320-MC-5002_52-601_Relay GE Multilin 350 1200:5 Overcurrent Phase ANSI - Extremely Inverse 0,70 840 3,29 8,970 10764 0,2 s
TOC IOC
Device Trip
Relay ID Manufacturer Model CT Ratio Curve Tap Prim. Tap Prim. Inst.
Function Element TMD
(Pickup) Amps (Pickup) Amps Delay
330MC331-CB15A-Relay GE Multilin 745 4000:5 Overcurrent Phase ANSI - Extremely Inverse 0,88 3520 4 2,5 10000 0,2 s
330MC331-CB15A-Relay GE Multilin 745 100:5 Overcurrent Ground ANSI - Extremely Inverse 0,20 20 5 - - -
330XF331B-Relay GE Multilin 745 800:5 Overcurrent Phase ANSI - Extremely Inverse 0,85 680 3,5 3,17 2536 0,2 s
Tabla 22: Ajustes propuestos Fusibles de media tensión del Switchgear 330-MC-331.
www.sdi-ingenieria.cl
TOC IOC
Device Trip
Relay ID Manufacturer Model CT Ratio Curve Tap Prim. Tap Prim. Inst.
Function Element TMD
(Pickup) Amps (Pickup) Amps Delay
330-XF-380Relay ABB RET 541 400:5 Overcurrent Phase Extremely Inverse 0,52 208 1 6,23 2492 0,2 s
330-MC-380Relay ABB RET 541 3000:5 Overcurrent Phase Extremely Inverse 0,44 1320 0,7 4,38 13140 0,2 s
330-MC-380Relay ABB RET 541 100:5 Overcurrent Ground - - - - 0,4 40 0,2 s
330-MC-380-1_CT01_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-1_CT01_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
330-MC-380-2_CT02_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-2_CT02_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
330-MC-380-3_CT03_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-3_CT03_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
330-MC-380-4_CT04_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-4_CT04_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
330-MC-380-5_CT05_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-5_CT05_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
330-MC-380-6_CT06_Relay GE Multilin 869 100:5 Overcurrent Phase ANSI Extremely Inverse 0,8 80 39,62 5,763 576,3 0,028 s
330-MC-380-6_CT06_Relay GE Multilin 869 50:5 Overcurrent Ground - - - - 0,4 20 0,03 s
Tabla 24: Ajustes propuestos Fusibles de media tensión del Switchgear 330-MC-380.
Max
FUSE ID Manufacturer Model Speed Size Cont. Amp
Voltage
FU2 Cutler-Hammer CLS 5,5 kV Other 6R 170
FU4 Cutler-Hammer CLS 5,5 kV Other 6R 170
FU5 Cutler-Hammer CLS 5,5 kV Other 6R 170
FU6 Cutler-Hammer CLS 5,5 kV Other 6R 170
FU7 Cutler-Hammer CLS 5,5 kV Other 6R 170
FU8 Cutler-Hammer CLS 5,5 kV Other 6R 170
Tabla 26: Ajustes propuestos Fusibles de media tensión del Switchgear 0320-SG-5001.
Max Cont.
FUSE ID Manufacturer Model Speed Size
Voltage Amp
FUS-5013 Cutler-Hammer BA-200 25 Other 200E 600
FUS-5014 Cutler-Hammer BA-200 25 Other 200E 600
www.sdi-ingenieria.cl
0320-SG-5002_CB01_Relay EATON 1150 2x2000/5 Overcurrent Phase 0,790 3160 6,0 5 15800 0,5 - - -
0320-SG-5002_CB02_Relay EATON 1150 2x2000/5 Overcurrent Phase 0,790 3160 6,0 5 15800 0,5 - - -
0320-SG-5002_CB12_Relay EATON 1150 2000/5 Overcurrent Phase 0,675 1350 5,0 8 10800 0,3 - - -
0320-SG-5002_CB13_Relay EATON 1150 2000/5 Overcurrent Phase 0,700 1400 5,0 7,5 10500 0,3 - - -
0320-SG-5002_CB21_Relay EATON 1150 2000/5 Overcurrent Phase 0,800 1600 5,0 8,5 13600 0,3 - - -
0320-SG-5002_CB22_Relay EATON 1150 2000/5 Overcurrent Phase 0,625 1250 5,0 8,5 10625 0,3 - - -
Tabla 28: Ajustes propuestos Fusibles de media tensión del Switchgear 0320-SG-5002.
Max Cont.
FUSE ID Manufacturer Model Speed Size
Voltage Amp
FUS-5023 Cutler-Hammer BA-200 25 Other 200E 600
FUS-5024 Cutler-Hammer BA-200 25 Other 200E 600
www.sdi-ingenieria.cl
Tabla 31: Ajustes propuestos de las protecciones de motores del CCM 0320-MC-5011.
CCM 0320-MC-
MOTOR MOTOR PROTECCION DE CORTO CIRCUITO ( MCP ) RELÉ DE SOBRECARGA FALLA A TIERRA 50G
5011
Eficienc CORRIENT REG. Trip
kW HP F.S CosFi TRIP-AMP
Ubicac ia E NOM. Número CAT AMPS RECOMEN N° de Catalogo Unidad de Trip Amps Unidad de Trip Delay
TAG TAG Descripción Type
ión MCP Fram RANGO(A PO Relé Medida Range Medida (A) (s) (*3)
(1) Amp AMPS SF=1.15
e ) S.
Motor bomba de piso E300 Electronic 193-EIOGP-43-
15,00 20,11 1,15 0,82 0,90 29,34 HMCP050K2C 50 150 - 500 350 E 6-60A 29,34 Class 10
MCP1 2CD 0310-PP-5091A recirculación pebbles Overload Relay 120
Motor bomba booster para E300 Electronic 193-EIOGP-43-
5,00 6,70 1,15 0,77 0,87 10,77 HMCPS030H1C 30 90-300 120 B 0,5-30A 10,77 Class 10
MCP2 2EF 0320-PP-5028A agua fresca Overload Relay 120
Motor bomba impulsión 1250- E300 Electronic
75,00 100,54 1,15 0,91 0,94 126,55 HMCP250W5C 250 2500 I 193-EIOGP-22-12020-200A 126,55 Class 10 0,5 - 5 A 1 0s
MCP3 3AF 0320-PP-5025A trommel molino SAG 2500 Overload Relay
Motor bomba lavado trommel 1250- E300 Electronic
75,00 100,54 1,15 0,91 0,94 126,55 HMCP250W5C 250 2500 I 193-EIOGP-22-12020-200A 126,55 Class 10 0,5 - 5 A 1 0s
MCP4 3GM 0320-PP-5024A molino SAG 2500 Overload Relay
Motor bomba booster para E300 Electronic 193-EIOGP-43-
5,00 6,70 1,15 0,77 0,87 10,77 HMCPS030H1C 30 90-300 120 B 0,5-30A 10,77 Class 10 0,5 - 5 A 1 0s
MCP6 4GH 0320-PP-5026A agua fresca Overload Relay 120
Motor ventilador sala de E300 Electronic 193-EIOGP-43-
2,30 3,08 1,15 0,74 0,83 5,41 HMCPS015EOC 15 45 - 150 60 B 0,5-30A 5,41 Class 10
MCP7 4JK 0320-FA-5001A lubricación molino SAG Overload Relay 120
CB2 5CD 0320-CN-5071-C01 Tecle y carro 3,40 1,00 1,00 4,91
CB3 5EF 0320-CN-5070-C01 Tecle y carro 3,40 1,00 1,00 4,91
CB4 5GH 0320-CN-5064-C01 Tecle y carro 3,40 1,00 1,00 4,91
CB5 5JK 0320-CN-5059-C01 Tecle y carro 3,40 1,00 1,00 4,91
CB6 6AB 0320-CN-5058-C01 Tecle y carro 3,40 1,00 1,00 4,91
CB7 6CD 0320-CN-5038-C01 Tecle y carro 3,40 1,00 1,00 4,91
CB8 6EF 0320-CN-5037-C01 Tecle y carro 3,40 1,00 1,00 4,91
CB9 6GH 0320-CN-5034-C01 Puente grúa 4,00 1,00 1,00 5,77
CB10 6JK 0310-CN-5063-C01 Caja terminal 3,40 1,00 1,00 4,91
CB11 6LM 0310-CN-5062-C01 Caja terminal 3,60 1,00 1,00 5,20
CB12 7AB 0310-CN-5061-C01 Caja terminal 3,60 1,00 1,00 5,20
Estación make-up servicio
37,00 1,00 1,00 53,40
CB13 7CD 0320-ZM-5005-01 molino SAG y bolas
Panel local unidad de
54,00 1,00 1,00 77,94
CB14 7EF 0320-ZM-5005-03 enfriamiento
CB15 7GH 0320-ZM-5005-02 Barra de control chiller SAG 54,00 1,00 1,00 77,94
Caja con terminales tipo TBC
0,25 - 2,5
CB16 7JK 0320-TB-5010 12P (Para enchufes 0320-WR- 40,00 1,00 1,00 57,74 1 0,02 s
A
5001 y WR-3002)
Electroiman autolimpiante para
1,00 1,00 0,00
CB17 7LM 0310-MA-5001 correa 0320-CV-5011
Sistema variador motor 0,25 - 2,5
250,00 1,00 1,00 360,84 1 0,02 s
CB18 8AE 0320-CP-5001-C01 compresor de aire A
CB20 8LM 0320-CN-5039-C01 Tecle y carro 15,70 1,00 1,00 22,66
0,25 - 2,5
Puente grúa nave molino SAG 155,00 1,00 1,00 223,72 1 0,02 s
CB21 9AD 0320-CN-5001-C01 A
www.sdi-ingenieria.cl
Tabla 33: Ajustes propuestos de las protecciones de motores del CCM 0280-MC-5011.
CCM 0280-MC-
MOTOR MOTOR PROTECCION DE CORTO CIRCUITO ( MCP ) RELÉ DE SOBRECARGA FALLA A TIERRA 50G
5011
Eficienc CORRIEN REG. Trip
kW HP F.S CosFi TRIP-AMP
Ubicac ia TE NOM. Número CAT AMPS RECOMEN N° de Catalogo Unidad de Trip Amps Unidad de Trip Delay
TAG TAG Descripción Type
ión MCP Fram RANGO(A PO Relé Medida Range Medida (A) (s) (*3)
(1) Amp AMPS SF=1.15
e ) S.
450 - E300 Electronic 193-EIOGP-22- Class
Motor unidad hidráulica 56,00 75,07 1,15 0,87 0,93 99,90 HMCP150T4C 150 1200 F 10-100A 99,9 0,5 - 5 A 1 0s
MCP1 2CF 0280-FE-5004-01A 1500 Overload Relay 120 10
E300 Electronic
Motor unidad hidráulica 56,00 75,07 1,15 0,87 0,93 99,90 HMCP150T4C 150 450 - 1500 1200 F 120-EIOGP-22-1 10-100A 99,9 Class 10 0,5 - 5 A 1 0s
MCP2 3AD 0280-FE-5003-01A Overload Relay
E300 Electronic
Motor unidad hidráulica 56,00 75,07 1,15 0,87 0,93 99,90 HMCP150T4C 150 450 - 1500 1200 F 120-EIOGP-22-1 10-100A 99,9 Class 10 0,5 - 5 A 1 0s
MCP3 3EH 0280-FE-5002-01A Overload Relay
E300 Electronic
Motor unidad hidráulica 56,00 75,07 1,15 0,87 0,93 99,90 HMCP150T4C 150 450 - 1500 1200 F 120-EIOGP-22-1 10-100A 99,9 Class 10 0,5 - 5 A 1 0s
MCP4 3JM 0280-FE-5001-01A Overload Relay
Motor bomba de piso tunel E300 Electronic
11,00 14,75 1,15 0,80 0,89 22,30 HMCP050G2 50 80-120 80 A 193-EIO-43-120 0.5-30A 22,3 Class 10
recuperación stockpile Overload Relay
MCP5 4AB 0280-PP-5090A
Motor ventilador tunel de E300 Electronic
15,00 20,11 1,15 0,82 0,90 29,34 HMCP050K2C 50 150 - 500 350 E 193-EIO-43-120 6-60A 29,3 Class 10
MCP6 4CD 0280-FA-5001A recuperación Overload Relay
E300 Electronic
Enfriador unidad hidraulica 0,75 1,01 1,15 0,69 0,79 1,99 HMCPS003A0C 3 9 - 30 24 F 193-EIO-43-120 0.5-30A 2,0 Class 10
MCP8 4GH 0280-FE-5004-01B Overload Relay
E300 Electronic
Enfriador unidad hidraulica 0,75 1,01 1,15 0,69 0,79 1,99 HMCPS003A0C 3 9 - 30 24 F 193-EIO-43-120 0.5-30A 2,0 Class 10
MCP10 5AB 0280-FE-5003-01B Overload Relay
E300 Electronic
Enfriador unidad hidraulica 0,75 1,01 1,15 0,69 0,79 1,99 HMCPS003A0C 3 9 - 30 24 F 193-EIO-43-120 0.5-30A 2,0 Class 10
MCP11 5CD 0280-FE-5002-01B Overload Relay
E300 Electronic
Enfriador unidad hidraulica 0,75 1,01 1,15 0,69 0,79 1,99 HMCPS003A0C 3 9 - 30 24 F 193-EIO-43-120 0.5-30A 2,0 Class 10
MCP12 5EF 0280-FE-5001-01B Overload Relay
CB1 5JK 0280-SL-5001-C01 Pesometro 3,00 1,00 1,00 4,33
CB2 5LM 0280-CN-5050-C01 Tablero fuerza puente grua 5,50 1,00 1,00 7,94
CB3 6AB 0280-CN-5049-C01 Tablero fuerza puente grua 6,80 1,00 1,00 9,81
CB4 6CD 0280-CN-5047-C01 Tablero fuerza puente grua 6,80 1,00 1,00 9,81
CB5 6EF 0280-CN-5045-C01 Tablero fuerza puente grua 6,80 1,00 1,00 9,81
CB7 6JK 0280-CN-5043-C01 Tablero fuerza puente grua 6,80 1,00 1,00 9,81
CB8 6LM 0280-CN-5004-C01 Tablero fuerza puente grua 10,50 1,00 1,00 15,16
CB9 7AB 0280-CN-5060-C01 Tablero fuerza puente grua 10,50 1,00 1,00 15,16
CB10 7CD 0320-ZM-5021-C01 Unidad hidráulica 15,00 1,00 1,00 21,65
CB11 7EF 0320-ZM-5020-C01 Unidad hidráulica 15,00 1,00 1,00 21,65
Transformador de
instrumentación tipo seco 10,00 1,00 1,00 14,43
CB12 7GH 0320-JX-1308 400-120V, NEMA 2
Transformador de
instrumentación tipo seco 5,00 1,00 1,00 7,22
CB13 7JK 0320-JX-1306 400-120V
Huinche mantencion
7,45 1,00 1,00 10,75
CB14 7LM 0280-ZM-5034-C01 contrapeso
CB15 8AB 0280-ZM-5033-C01 Unidad hidráulica 7,45 1,00 1,00 10,75
CB16 8CD 0280-ZM-5032-C01 Unidad hidráulica 7,45 1,00 1,00 10,75
CB17 8EF 0280-ZM-5031-C01 Unidad hidráulica 7,45 1,00 1,00 10,75
CB18 8GH 0280-ZM-5030-C01 Unidad hidráulica 7,45 1,00 1,00 10,75
Caja terminales tipo TBC36
40,00 1,00 1,00 57,74 0,25 - 2,5 A 1 0,02 s
CB20 8LM 0280-TB-5010 (para enchufes WR)
Caja terminales tipo TBC36
40,00 1,00 1,00 57,74 0,25 - 2,5 A 1 0,02 s
CB21 9AB 0280-TB-5013 (para enchufes WR)
Caja terminales tipo TBC36
40,00 1,00 1,00 57,74 0,25 - 2,5 A 1 0,02 s
CB22 9CD 0330-TB-5011 (para enchufes WR)
Caja terminales tipo TBC36
40,00 1,00 1,00 57,74 0,25 - 2,5 A 1 0,02 s
CB23 9EF 0330-TB-5012 (para enchufes WR)
Transformador de
distribución alumbrado tipo 75,00 1,00 1,00 108,25
CB24 9GH 0320-LX-5401 seco 400-400/231V
Transformador de
distribución alumbrado tipo 75,00 1,00 1,00 108,25
CB25 9JK 0320-LX-5001 seco 400-400/231V
Transformador de servicios
auxiliares tipo seco 400- 150,00 1,00 1,00 216,51 0,25 - 2,5 A 1 0,02 s
400/231V 150kVA
CB27 10AD 0320-DX-5201
UPS instrumentación 20kVA 20,00 1,00 1,00 28,87
CB29 10JK 0320-UP-1301
Tranformador de
instrumentación tipo seco 15,00 1,00 1,00 21,65
CB30 10LM 0320-JX-1304 400-120V
Tranformador de
instrumentación tipo seco 15,00 1,00 1,00 21,65
CB31 11AB 0280-JX-1302 400-120V
Tranformador de
instrumentación tipo seco 15,00 1,00 1,00 21,65
CB32 11CD 0280-JX-1301 400-120V
Transformador de
distribución de alumbrado 30,00 1,00 1,00 43,30
CB34 11GH 0330-LX-5001 tipo seco 400-400/231V
Transformador de servicios
auxiliares tipo seco 400- 45,00 1,00 1,00 64,95
CB35 11JK 0320-DX-5001 400/231V
Transformador de
distribución de alumbrado 30,00 1,00 1,00 43,30
CB36 11LM 0310-LX-5001 tipo seco 400-400/231V
Transformador de
distribución de alumbrado 30,00 1,00 1,00 43,30
CB37 12AB 0280-LX-5001 tipo seco 400-400/231V
Transformador de servicios
auxiliares tipo seco 400- 100,00 1,00 1,00 144,34 0,25 - 2,5 A 1 0,02 s
CB38 12CE 0320-DX-5501 400/231V
Huinche mantencion
3,00 1,00 1,00 4,33
CB40 12JK 0280-ZM-5053-C01 contrapeso
www.sdi-ingenieria.cl
Tabla 35: Ajustes propuestos de las protecciones de motores del CCM 0320-MC-5012.
CCM 0320-MC-
MOTOR MOTOR PROTECCION DE CORTO CIRCUITO ( MCP ) RELÉ DE SOBRECARGA FALLA A TIERRA 50G
5012
Eficienc CORRIEN REG. Trip
kW HP F.S CosFi TRIP-AMP
Ubicac ia TE NOM. Número CAT AMPS RECOMEN N° de Catalogo Unidad de Trip Amps Unidad de Trip Delay
TAG TAG Descripción Type
ión MCP Fram RANGO(A PO Relé Medida Range Medida (A) (s) (*3)
(1) Amp AMPS SF=1.15
e ) S.
Motor alimentador de E300 Electronic
0,80 1,07 1,15 0,70 0,79 2,09 HMCPS003A0C 3 9 - 30 24 F 193-EIO-43-120 0,5-30A 2,09 Class 10
MCP2 2GH 0320-FE-5012A bolas a molino de bolas Overload Relay
Motor alimentador de E300 Electronic
0,80 1,07 1,15 0,70 0,79 2,09 HMCPS003A0C 3 9 - 30 24 F 193-EIO-43-120 0,5-30A 2,09 Class 10
MCP3 2JK 0320-FE-5011A bolas a molino de bolas Overload Relay
Motor correa alta
E300 Electronic
pendiente alim. Bolas a 3,70 4,96 1,15 0,76 0,85 8,27 HMCPS015EOC 15 45 - 150 105 E 193-EIO-43-120 0,5-30A 8,27 Class 10
Overload Relay
MCP4 2LM 0320-CV-5005A molino bolas SAG
Motor correa alta
E300 Electronic
pendiente alim. Bolas a 3,70 4,96 1,15 0,76 0,85 8,27 HMCPS015EOC 15 45 - 150 105 E 193-EIO-43-120 0,5-30A 8,27 Class 10
Overload Relay
MCP5 3CD 0320-CV-5004A molino bolas
Motor bomba de piso E300 Electronic
75,00 100,54 1,15 0,91 0,94 126,55 HMCP400X5W 400 2000-4000 4000 I 193-EIOGP-22-12020-200A 126,55 Class 10 0,5 - 5 A 1 0s
MCP7 3GM 0320-PP-5014A molienda Overload Relay
Motor bomba de piso E300 Electronic
75,00 100,54 1,15 0,91 0,94 126,55 HMCP400X5W 400 2000-4000 4000 I 193-EIOGP-22-12020-200A 126,55 Class 10 0,5 - 5 A 1 0s
MCP9 4GM 0320-PP-5013A molienda Overload Relay
Computación chute
3,00 1,00 1,00 4,33
CB1 5AB 0320-ST-5223 alimentación SAG
CB2 5CD 0310-SL-5010-C01 Pesometro 3,00 1,00 1,00 4,33
CB3 5EF 0310-CN-5028-SW1 Switch para tecle y carro 3,40 1,00 1,00 4,91
CB4 5GH 0310-CN-5027-SW1 Switch para tecle y carro 4,40 1,00 1,00 6,35
CB5 5JK 0310-CN-5022-SW1 Switch para tecle y carro 5,40 1,00 1,00 7,79
Maquina twin
37,00 1,00 1,00 53,40
CB6 5LM 0320-ME-5005 enlainadora molino SAG
Maquina enlainadora
37,00 1,00 1,00 53,40
CB7 6AB 0320-ME-5002 molino bolas
Carro porta chute molino
22,00 1,00 1,00 31,75
CB8 6CD 0320-ME-5004 bolas
Carro porta chute molino
22,00 1,00 1,00 31,75
CB9 6EF 0320-ME-5003 SAG
Maquina twin
37,00 1,00 1,00 53,40
CB10 6GJ 0320-ME-5001 enlainadora molino SAG
CB11 6KL 0310-ZM-5042-C01 Unidad hidráulica 15,00 1,00 1,00 21,65
CB12 7AB 0310-ZM-5041-C01 Unidad hidráulica 15,00 1,00 1,00 21,65
CB13 7CD 0310-ZM-5040-C01 Unidad hidráulica 15,00 1,00 1,00 21,65
CB14 7EG 0310-CV-5013-AF Variador de frecuencia 75,00 1,00 1,00 108,25 0,25 - 2,5 A 1 0,02 s
CB15 7HK 0310-CV-5012-AF Variador de frecuencia 75,00 1,00 1,00 108,25 0,25 - 2,5 A 1 0,02 s
CB16 7LM 0310-CV-5011-AF Variador de frecuencia 30,00 1,00 1,00 43,30
CB17 8AC 0310-CV-5010-AF Variador de frecuencia 75,00 1,00 1,00 108,25 0,25 - 2,5 A 1 0,02 s
Caja terminales tipo
TBC12P (Para enchufes 40,00 1,00 1,00 57,74 0,25 - 2,5 A 1 0,02 s
CB20 8JK 0310-TB-5010 WR)
Caja terminales tipo
TBC12P (Para enchufes 40,00 1,00 1,00 57,74 0,25 - 2,5 A 1 0,02 s
CB21 8LM 0320-TB-5013 WR)
Huinche mantencion
7,45 1,00 1,00 10,75
CB22 9AB 0310-ZM-5038-C01 contrapeso
Huinche mantencion
7,45 1,00 1,00 10,75
CB23 9CD 0310-ZM-5037-C01 contrapeso
Huinche mantencion
7,45 1,00 1,00 10,75
CB24 9EF 0310-ZM-5036-C01 contrapeso
Huinche mantencion
7,45 1,00 1,00 10,75
CB25 9GH 0310-ZM-5035-C01 contrapeso
Sistema variador motor
250,00 1,00 1,00 360,84 0,25 - 2,5 A 1 0,02 s
CB26 9JM 0320-CP-5002-C01 compresor de aire
www.sdi-ingenieria.cl
Tabla 37: Ajustes propuestos de las protecciones de motores del CCM 0320-MC-5013.
CCM 0320-MC-
MOTOR MOTOR PROTECCION DE CORTO CIRCUITO ( MCP ) RELÉ DE SOBRECARGA FALLA A TIERRA 50G
5013
Eficienc CORRIEN REG. Trip
kW HP F.S CosFi TRIP-AMP
Ubicac ia TE NOM. Número CAT AMPS RECOMEN N° de Catalogo Unidad de Trip Amps Unidad de Trip Delay
TAG TAG Descripción Type
ión MCP Fram RANGO(A PO Relé Medida Range Medida (A) (s) (*3)
(1) Amp AMPS SF=1.15
e ) S.
CB1 2CD 0320-CN-5040-C01 Tecle y carro 5,30 1,00 1,00 7,65 HFD3015L 15
Motor correa alimentación bolas E300 Electronic 193-EIOGP-43-
MCP1 2EF 0320-CV-5003A 3,70 4,96 1,15 0,76 0,85 8,27 HMCPS015EOC 15 45 - 150 105 E 0,5-30A 8,27 Class 10
a molinos de bolas #1 Overload Relay 120
www.sdi-ingenieria.cl
Tabla 39: Ajustes propuestos de las protecciones de motores del CCM 0320-MC-5021.
CCM 0320-MC-
MOTOR MOTOR PROTECCION DE CORTO CIRCUITO ( MCP ) RELÉ DE SOBRECARGA FALLA A TIERRA 50G
5021
Eficienc CORRIEN REG. Trip
kW HP F.S CosFi TRIP-AMP
Ubicac ia TE NOM. Número CAT AMPS RECOMEN N° de Catalogo Unidad de Trip Amps Unidad de Trip Delay
TAG TAG Descripción Type
ión MCP Fram RANGO(A PO Relé Medida Range Medida (A) (s) (*3)
(1) Amp AMPS SF=1.15
e ) S.
CB1 2CD 0320-CN-5065-C01 Tecle y carro 3,40 1,00 1,00 4,91 HFD3015L 15
CB4 3AB 0320-CN-5057-C01 Tecle y carro 8,20 1,00 1,00 11,84 HFD3020L 20
CB5 3CD 0320-CN-5056-C01 Tecle y carro 8,60 1,00 1,00 12,41 HFD3020L 20
CB7 3GH 0320-UP-1300 UPS Instrumentación 20,00 1,00 1,00 28,87 HFD3040L 40
Transformador de
CB8 3JK 0320-JX-1307 instrumentación tipo seco 400- 15,00 1,00 1,00 21,65 HFD3050L 50
120V, NEMA 3R
Transformador de
CB9 3LM 0320-JX-1305 instrumentación tipo seco 400- 15,00 1,00 1,00 21,65 HFD3050L 50
120V, NEMA 3R
Cargador de baterías 400V, 3F
CB10 4AB 0320-BA-5012 10,00 1,00 1,00 14,43 HFD3020L 30
para banco de baterías 125Vcc
Transformador de servicios
0,25 - 2,5
CB23 5KLM 0320-DX-5521 auxiliares tipo seco 400- 100,00 1,00 1,00 144,34 H50-2350F 250 5-10 10 1 0,02 s
A
400/231V, Nema 3R
Transformador de servicios
0,25 - 2,5
CB24 13CD 0320-DX-5221 auxiliares tipo seco 400- 150,00 1,00 1,00 216,51 HKD-3400F 400 5-10 10 1 0,02 s
A
400/231V, Nema 2
Motor ventilador de motor E300 Electronic 193-EIO-43-
MCP2 7JK 0320-PP-5001B 4,00 5,36 1,15 0,76 0,86 8,83 HMCPS030H1C 30 90-300 120 B 0,5-30A 8,8 Class 10 0,5 - 5 A 1 0s
principal 0320-PP-5001A Overload Relay 120
Motor ventilador de motor E300 Electronic 193-EIO-43-
MCP1 7LM 0320-PP-5001C 4,00 5,36 1,15 0,76 0,86 8,83 HMCPS030H1C 30 90-300 120 B 0,5-30A 8,8 Class 10 0,5 - 5 A 1 0s
principal 0320-PP-5001A Overload Relay 120
Motor ventilador de motor E300 Electronic 193-EIO-43-
MCP3 8AB 0320-PP-5001D 2,80 3,75 1,15 0,75 0,84 6,42 HMCPS015EOC 15 45 - 150 75 C 0,5-30A 6,4 Class 10 0,5 - 5 A 1 0s
principal 0320-PP-5001A Overload Relay 120
Motor ventilador de motor E300 Electronic 193-EIO-43-
MCP4 8CD 0320-PP-5003B 4,00 5,36 1,15 0,76 0,86 8,83 HMCPS030H1C 30 90-300 120 B 0,5-30A 8,8 Class 10 0,5 - 5 A 1 0s
principal 0320-PP-5003A Overload Relay 120
Motor ventilador de motor E300 Electronic 193-EIO-43-
MCP5 8EF 0320-PP-5003C 4,00 5,36 1,15 0,76 0,86 8,83 HMCPS030H1C 30 90-300 120 B 0,5-30A 8,8 Class 10 0,5 - 5 A 1 0s
principal 0320-PP-5003A Overload Relay 120
Motor ventilador de motor E300 Electronic 193-EIO-43-
MCP6 8GH 0320-PP-5003D 2,80 3,75 1,15 0,75 0,84 6,42 HMCPS015EOC 15 45 - 150 75 C 0,5-30A 6,4 Class 10 0,5 - 5 A 1 0s
principal 0320-PP-5003A Overload Relay 120
CB6 3EF 0320-MC-5021-RE6 0320-MC-5021-RE6
www.sdi-ingenieria.cl
Tabla 41: Ajustes propuestos de las protecciones de motores del CCM 0330-MC-5001.
CCM 0330-MC-
MOTOR MOTOR PROTECCION DE CORTO CIRCUITO ( MCP ) RELÉ DE SOBRECARGA FALLA A TIERRA 50G
5001
Eficienc CORRIEN REG. Trip
kW HP F.S CosFi TRIP-AMP
Ubicac ia TE NOM. AMPS RECOMEN N° de Catalogo Unidad de Trip Amps Unidad de Trip Delay
TAG TAG Descripción Número CAT MCP Type
ión Fram RANGO(A PO Relé Medida Range Medida (A) (s) (*3)
(1) Amp AMPS SF=1.15
e ) S.
Ventilador reductor celda E300 Electronic 193-EIOGP-22-
MCP1 2CD 0330-FT-5001B 0,75 1,01 1,15 0,69 0,79 1,99 HMCPS007C0C 7 21 - 70 28 B 0,5-30A 1,99 Class 10 0,5 - 5 A 1 0s
flotación rougher Overload Relay 120
Ventilador reductor celda E300 Electronic 193-EIOGP-22-
MCP2 2EF 0330-FT-5002B 0,75 1,01 1,15 0,69 0,79 1,99 HMCPS007C0C 7 21 - 70 28 B 0,5-30A 1,99 Class 10 0,5 - 5 A 1 0s
flotación rougher Overload Relay 120
Ventilador reductor celda E300 Electronic 193-EIOGP-22-
MCP3 3AB 0330-FT-5003B 0,75 1,01 1,15 0,69 0,79 1,99 HMCPS007C0C 7 21 - 70 28 B 0,5-30A 1,99 Class 10 0,5 - 5 A 1 0s
flotación rougher Overload Relay 120
Ventilador reductor celda E300 Electronic 193-EIOGP-22-
MCP4 3CD 0330-FT-5004B 0,75 1,01 1,15 0,69 0,79 1,99 HMCPS007C0C 7 21 - 70 28 B 0,5-30A 1,99 Class 10 0,5 - 5 A 1 0s
flotación rougher Overload Relay 120
Ventilador reductor celda E300 Electronic 193-EIOGP-22-
MCP5 3EF 0330-FT-5005B 0,75 1,01 1,15 0,69 0,79 1,99 HMCPS007C0C 7 21 - 70 28 B 0,5-30A 1,99 Class 10 0,5 - 5 A 1 0s
flotación rougher Overload Relay 120
Ventilador reductor celda E300 Electronic 193-EIOGP-22-
MCP6 3GH 0330-FT-5006B 0,75 1,01 1,15 0,69 0,79 1,99 HMCPS007C0C 7 21 - 70 28 B 0,5-30A 1,99 Class 10 0,5 - 5 A 1 0s
flotación rougher Overload Relay 120
www.sdi-ingenieria.cl
Para verificar si los ajustes propuestos de los interruptores coordinan con el sistema bajo
estudio, se realiza una verificación de coordinación por tiempos de operación. Esta sección
consiste en revisar la operación de la planta MLP_INCO; simulando fallas transitorias. Las
fallas que se estudiarán serán las siguientes:
Fallas trifásicas
Monofásica a tierra sin resistencia de falla
Se simulará las fallas anteriormente descritas, en las instalaciones en forma separada, con
el objetivo de mostrar la coordinación de las protecciones.
Los tiempos de operación mostrados en el anexo II están coloreadas según los rangos de
tiempo de operación de cada función de protección, tal como se define a continuación:
14 Explicación Anexos
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
15 Conclusiones
En el anexo I, se muestran las tablas de tiempo de operación para cada uno de los
escenarios de operación indicados en la sección 8, en el cual se verifican la coordinación
de protecciones de las instalaciones, con los ajustes indicados en la sección 10 (ajustes
existentes), esta verificación se realizó reproduciendo las siguientes fallas: Trifásica y
monofásica franca a tierra.
En el Anexo III, se encuentran las gráficas tiempo v/s corriente de los ajustes de
protecciones propuesto; en el Anexo IV la Base de datos ETAP y en el Anexo V los print
out de los relés de protección.
En el Anexo VIII se realiza una verificación de los ajustes de protecciones propuestos a los
centros de control de motores 0390- MC- 5011 (Planta de Reactivos) y 0391-MC-5011
(Planta de Cal).
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Transformador Transformador
0320-XF-5021 0320-XF-5022 Barra 1
(Lado 23kV) (Lado 23kV)
Relé ID ETAP Interruptor
0320-MC-5002-1 0320-MC-5002-2 0320-MC-5002-1
If Top If Top If Top
kA ms kA ms kA ms
0740-SG-5002-52-501_Relay 52-501 15,034 99,0 15,034 99,0 - -
0740-SG-5002-52-502_Relay 52-502 15,034 88,0 15,034 88,0 - -
0740-SG-5002-52-108_Relay 52-104 30,210 55,0 - - - -
0740-SG-5002-52-204_Relay 52-204 - - 30,216 50,0 - -
0320-XF-5021-CB_Relay 0320-XF-5021-CB 30,226 40,0 - - - -
0320-XF-5022-CB_Relay 0320-XF-5022-CB - - 30,227 49,0 - -
0320-MC-5002_52-501_Relay 0320-MC-5002-52-501 - - - - 24,11 40,0
0320-MC-5002_52-502_Relay 0320-MC-5002-52-502 - - - - - -
0320-MC-5002_52-104_Relay 0320-MC-5002-52-104 - - - - - -
0320-MC-5002_52-105_Relay 0320-MC-5002-52-105 - - - - - -
0320-MC-5002_52-201_Relay 0320-MC-5002-52-201 - - - - - -
0320-MC-5002_52-202_Relay 0320-MC-5002-52-202 - - - - - -
0320-MC-5002_52-203_Relay 0320-MC-5002-52-203 - - - - - -
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
330-SW37XA01 Transformador
Barra
(52-37) 330-XF-380
Relé ID ETAP Interruptor
330-MC-380 330-MC-380 330-MC-380
If Top If Top If Top
kA ms kA ms kA ms
Rele 52_31 52-31 - - - - - -
Rele 52_22 52-22 0,198 492,0 - - - -
Rele 52_37 52-37 0,767 119,0 - - - -
330-XF-380Relay 330CB380CB - - 0,746 6753,0 - -
330-MC-380Relay 330-MC-380-CB01 - - - - 0,398 60,0
330-MC-380-1_CTO1_Relay - - - - - -
FU2 - - - - - - -
330-MC-380-2_CTO2_Relay - - - - - -
FU4 - - - - - - -
330-MC-380-3_CTO3_Relay - - - - - -
FU5 - - - - - - -
330-MC-380-4_CTO4_Relay - - - - - -
FU6 - - - - - - -
330-MC-380-5_CTO5_Relay - - - - - -
FU7 - - - - - - -
330-MC-380-6_CTO6_Relay - - - - - -
FU8 - - - - - - -
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Transformador Transformador
Barra 1
0320-XF-5013 0320-XF-5014
Relé ID ETAP Interruptor
0320-SG-5001-1 0320-SG-5001-2 0320-SG-5001-1
If Top If Top If Top
kA ms kA ms kA ms
0740-SG-5002-52-501_Relay 52-501 15,263 99,0 15,264 99,0 - -
0740-SG-5002-52-502_Relay 52-502 15,263 88,0 15,264 99,0 - -
0740-SG-5002-52-104_Relay 52-104 30,673 55,0 - - - -
0740-SG-5002-52-201_Relay 52-201 - - 30,662 50,0 - -
FUS-5013 - 30,673 13,0 - - 0,849 2733,0
FUS-5014 - - - 30,662 13,0 - -
0320-SG-5001_CB01_Relay SG5001-CB-01 - - - - 48,817 10,0
0320-SG-5001_CB02_Relay SG5001-CB-02 - - - - - -
0320-SG-5001_CB12_Relay SG5001-CB-12 - - - - - -
0320-SG-5001_CB13_Relay SG5001-CB-13 - - - - - -
0320-SG-5001_CB21_Relay SG5001-CB-21 - - - - - -
0320-SG-5001_CB22_Relay SG5001-CB-22 - - - - - -
0320-SG-5001_CB23_Relay SG5001-CB-23 - - - - - -
0320-MC-5011 0320-ML-5001-MC1
Barra 2
(CB-12) (CB-13)
Relé ID ETAP Interruptor
0320-SG-5001-1 0320-SG-5001-1 0320-SG-5001-2
If Top If Top If Top
kA ms kA ms kA ms
0740-SG-5002-52-501_Relay 52-501 - - - - - -
0740-SG-5002-52-502_Relay 52-502 - - - - - -
0740-SG-5002-52-104_Relay 52-104 - - - - - -
0740-SG-5002-52-201_Relay 52-201 - - - - - -
FUS-5013 - - - - - - -
FUS-5014 - - - - - 0,849 2734,0
0320-SG-5001_CB01_Relay SG5001-CB-01 43,393 40,0 35,19 10,0 - -
0320-SG-5001_CB02_Relay SG5001-CB-02 - - - - 48,816 10,0
0320-SG-5001_CB12_Relay SG5001-CB-12 43,987 31,0 - - - -
0320-SG-5001_CB13_Relay SG5001-CB-13 - - 35,657 10,0 - -
0320-SG-5001_CB21_Relay SG5001-CB-21 - - - - - -
0320-SG-5001_CB22_Relay SG5001-CB-22 - - - - - -
0320-SG-5001_CB23_Relay SG5001-CB-23 - - - - - -
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Transformador 0320-ML-5002-MC1
Barra 1
0320-XF-5024 (CB-12)
Relé ID ETAP Interruptor
0320-SG-5002-2 0320-SG-5002-1 0320-SG-5002-1
If Top If Top If Top
kA ms kA ms kA ms
0740-SG-5002-52-501_Relay 52-501 - - - - - -
0740-SG-5002-52-502_Relay 52-502 - - - - - -
0740-SG-5002-52-108_Relay 52-108 - - - - - -
0740-SG-5002-52-204_Relay 52-204 - - - - - -
FUS-5023 - - - 0,848 2742,0 - -
FUS-5024 - 29,555 13,0 - - - -
0320-SG-5002_CB01_Relay SG5002-CB-01 - - 48,777 10,0 35,263 10,0
0320-SG-5002_CB02_Relay SG5002-CB-02 - - - - - -
0320-SG-5002_CB12_Relay SG5002-CB-12 - - - - 35,432 10,0
0320-SG-5002_CB13_Relay SG5001-CB-13 - - - - - -
0320-SG-5002_CB21_Relay SG5001-CB-21 - - - - - -
0320-SG-5002_CB22_Relay SG5001-CB-22 - - - - - -
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Transformador 0320-ML-5002-MC1
Barra 1
0320-XF-5024 (CB-12)
Relé ID ETAP Interruptor
0320-SG-5002-2 0320-SG-5002-1 0320-SG-5002-1
If Top If Top If Top
kA ms kA ms kA ms
0740-SG-5002-52-501_Relay 52-501 - - - - - -
0740-SG-5002-52-502_Relay 52-502 - - - - - -
0740-SG-5002-52-108_Relay 52-108 - - - - - -
0740-SG-5002-52-204_Relay 52-204 - - - - - -
FUS-5023 - - - 0,491 97262,0 - -
FUS-5024 - 0,759 4266,0 - - - -
0320-SG-5002_CB01_Relay SG5002-CB-01 - - 49,253 10,0 31,421 10,0
0320-SG-5002_CB02_Relay SG5002-CB-02 - - - - - -
0320-SG-5002_CB12_Relay SG5002-CB-12 - - - - 31,521 10,0
0320-SG-5002_CB13_Relay SG5001-CB-13 - - - - - -
0320-SG-5002_CB21_Relay SG5001-CB-21 - - - - - -
0320-SG-5002_CB22_Relay SG5001-CB-22 - - - - - -
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Carga Carga
Relé ID ETAP Interruptor 0320-DX-5501 0280-ZM-5053-C01
If Top If Top
kA ms kA ms
SG-5001-CB-02 CB-02 41,403 420,0 41,403 420,0
SG-5001-CB-22 CB-22 42,587 220,0 42,587 220,0
INC_0280-MC-5011 Incoming MC 42,587 220,0 42,587 220,0
MCP1_0280MC5011 MCP1 - - - -
OL_0280-FE-5004-01A - - - -
MCP2_0280MC5011 MCP2 - - - -
OL_0280-FE-5003-01A - - - -
MCP3_0280MC5011 MCP3 - - - -
OL_0280-FE-5002-01A - - - -
MCP4_0280MC5011 MCP4 - - - -
OL_0280-FE-5001-01A - - - -
MCP5_0280MC5011 MCP5 - - - -
OL_0280-PP-5090A - - - -
MCP6_0280MC5011 MCP6 - - - -
OL_0280-FA-5001A - - - -
MCP8_0280MC5011 MCP8 - - - -
OL_0280-FE-5004-01B - - - -
MCP10_0280MC5011 MCP10 - - - -
OL_0280-FE-5003-01B - - - -
MCP11_0280MC5011 MCP11 - - - -
OL_0280-FE-5002-01B - - - -
MCP12_0280MC5011 MCP12 - - - -
OL_0280-FE-5001-01B - - - -
CB1_0280MC5011 CB1 - - - -
CB2_0280MC5011 CB2 - - - -
CB3_0280MC5011 CB3 - - - -
CB4_0280MC5011 CB4 - - - -
CB5_0280MC5011 CB5 - - - -
CB7_0280MC5011 CB7 - - - -
CB8_0280MC5011 CB8 - - - -
CB9_0280MC5011 CB9 - - - -
CB10_0280MC5011 CB10 - - - -
CB11_0280MC5011 CB11 - - - -
CB12_0280MC5011 CB12 - - - -
CB13_0280MC5011 CB13 - - - -
CB14_0280MC5011 CB14 - - - -
CB15_0280MC5011 CB15 - - - -
CB16_0280MC5011 CB16 - - - -
CB17_0280MC5011 CB17 - - - -
CB18_0280MC5011 CB18 - - - -
CB20_0280MC5011 CB20 - - - -
50G_0280-TB-5010 CB20 - - - -
CB21_0280MC5011 CB21 - - - -
50G_0280-TB-5013 CB21 - - - -
CB22_0280MC5011 CB22 - - - -
50G_0330-TB-5011 CB22 - - - -
CB23_0280MC5011 CB23 - - - -
50G_0330-TB-5012 CB23 - - - -
CB24_0280MC5011 CB24 - - - -
CB25_0280MC5011 CB25 - - - -
CB27_0280MC5011 CB27 - - - -
50G_0320-DX-5201 CB27 - - - -
CB29_0280MC5011 CB29 - - - -
CB30_0280MC5011 CB30 - - - -
CB31_0280MC5011 CB31 - - - -
CB32_0280MC5011 CB32 - - - -
CB34_0280MC5011 CB34 - - - -
CB35_0280MC5011 CB35 - - - -
CB36_0280MC5011 CB36 - - - -
CB37_0280MC5011 CB37 - - - -
CB38_0280MC5011 CB38 43,925 0,0 - -
50G_0320-DX-5501 CB38 43,925 50,0 - -
CB40_0280MC5011 CB40 - - 43,925 0,0
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
740-SG-001
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
740-SG-5002
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5002
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0330-MC-331
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0330-MC-380
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-SG-5001
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-SG-5002
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5011
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5012
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5013
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5021
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0330-MC-5001
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5011 – MCP1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5011 – MCP2
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5011 – MCP3
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5011 – MCP4
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Voltage
Imbalance Over Limit - - Enabled
Warning in History
368 VIBWarningLevel 10%
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Enable Warning on
Consumed Reactive - - Disable
Power Under Limit
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5011 – MCP6
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Voltage
Imbalance Over Limit - - Enabled
Warning in History
368 VIBWarningLevel 10%
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Enable Warning on
Consumed Reactive - - Disable
Power Under Limit
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5011 – MCP7
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Voltage
Imbalance Over Limit - - Enabled
Warning in History
368 VIBWarningLevel 10%
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Enable Warning on
Consumed Reactive - - Disable
Power Under Limit
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5011 – CB-16
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5011 – CB-18
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5011 – CB-21
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011 – MCP1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0280-MC-5011 – MCP2
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Voltage
Imbalance Over Limit - - Enabled
Warning in History
368 VIBWarningLevel 10%
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Enable Warning on
Consumed Reactive - - Disable
Power Under Limit
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011 – MCP3
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Voltage
Imbalance Over Limit - - Enabled
Warning in History
368 VIBWarningLevel 10%
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Enable Warning on
Consumed Reactive - - Disable
Power Under Limit
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011 – MCP4
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Voltage
Imbalance Over Limit - - Enabled
Warning in History
368 VIBWarningLevel 10%
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Enable Warning on
Consumed Reactive - - Disable
Power Under Limit
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011 – MCP5
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0280-MC-5011 – MCP6
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0280-MC-5011 – MCP8
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0280-MC-5011 – MCP10
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0280-MC-5011 – MCP11
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Voltage
Imbalance Over Limit - - Enabled
Warning in History
368 VIBWarningLevel 10%
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Enable Warning on
Consumed Reactive - - Disable
Power Under Limit
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011 – MCP12
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0280-MC-5011 – CB-20
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011 – CB-21
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011 – CB-22
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011 – CB-23
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011 – CB-27
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0280-MC-5011 – CB-38
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5012 – MCP2
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
Enable Warning on L1
- - Disable
Line Loss
Include L1 Line Loss
- - Enabled
Warning in History
L2 LINE LOSS
Assign L2 Line Loss
- - Disable
Detection Enable
Enable Trip on L2 Line
- - Disable
Loss
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Delay 287 L2LossTripDelay 1.0 s
Enable Warning on L2
- - Disable
Line Loss
Include L2 Line Loss
- - Enabled
Warning in History
L3 LINE LOSS
Assign L3 Line Loss
- - Disable
Detection Enable
Enable Trip on L3 Line
- - Disable
Loss
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Delay 288 L3LossTripDelay 1.0 s
Enable Warning on L3
- - Disable
Line Loss
Include L3 Line Loss
- - Enabled
Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5012 – MCP3
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5012 – MCP4
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
Enable Warning on L1
- - Disable
Line Loss
Include L1 Line Loss
- - Enabled
Warning in History
L2 LINE LOSS
Assign L2 Line Loss
- - Disable
Detection Enable
Enable Trip on L2 Line
- - Disable
Loss
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Delay 287 L2LossTripDelay 1.0 s
Enable Warning on L2
- - Disable
Line Loss
Include L2 Line Loss
- - Enabled
Warning in History
L3 LINE LOSS
Assign L3 Line Loss
- - Disable
Detection Enable
Enable Trip on L3 Line
- - Disable
Loss
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Delay 288 L3LossTripDelay 1.0 s
Enable Warning on L3
- - Disable
Line Loss
Include L3 Line Loss
- - Enabled
Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5012 – MCP5
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
Enable Warning on L1
- - Disable
Line Loss
Include L1 Line Loss
- - Enabled
Warning in History
L2 LINE LOSS
Assign L2 Line Loss
- - Disable
Detection Enable
Enable Trip on L2 Line
- - Disable
Loss
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Delay 287 L2LossTripDelay 1.0 s
Enable Warning on L2
- - Disable
Line Loss
Include L2 Line Loss
- - Enabled
Warning in History
L3 LINE LOSS
Assign L3 Line Loss
- - Disable
Detection Enable
Enable Trip on L3 Line
- - Disable
Loss
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Delay 288 L3LossTripDelay 1.0 s
Enable Warning on L3
- - Disable
Line Loss
Include L3 Line Loss
- - Enabled
Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5012 – MCP7
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
Enable Warning on L1
- - Disable
Line Loss
Include L1 Line Loss
- - Enabled
Warning in History
L2 LINE LOSS
Assign L2 Line Loss
- - Disable
Detection Enable
Enable Trip on L2 Line
- - Disable
Loss
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Delay 287 L2LossTripDelay 1.0 s
Enable Warning on L2
- - Disable
Line Loss
Include L2 Line Loss
- - Enabled
Warning in History
L3 LINE LOSS
Assign L3 Line Loss
- - Disable
Detection Enable
Enable Trip on L3 Line
- - Disable
Loss
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Delay 288 L3LossTripDelay 1.0 s
Enable Warning on L3
- - Disable
Line Loss
Include L3 Line Loss
- - Enabled
Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5012 – MCP9
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Enable Warning on L1
- - Disable
Line Loss
Include L1 Line Loss
- - Enabled
Warning in History
L2 LINE LOSS
Assign L2 Line Loss
- - Disable
Detection Enable
Enable Trip on L2 Line
- - Disable
Loss
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Delay 287 L2LossTripDelay 1.0 s
Enable Warning on L2
- - Disable
Line Loss
Include L2 Line Loss
- - Enabled
Warning in History
L3 LINE LOSS
Assign L3 Line Loss
- - Disable
Detection Enable
Enable Trip on L3 Line
- - Disable
Loss
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Delay 288 L3LossTripDelay 1.0 s
Enable Warning on L3
- - Disable
Line Loss
Include L3 Line Loss
- - Enabled
Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5012 – CB-14
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5012 – CB-15
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5012 – CB-17
ELRC-1/110
CENTRO CONTROL MOTORES 0320-MC-5012 CB-17
POTENCIOMETRO TIEMPO DE DISPARO
AJUSTE RANGO DE AJUSTE PARAMETER
t (sec) 0.02 s; 0.05 s; 0.1 s; 0.2 s; 0.3 s; 0.4 s; 0.5 s 0.02 s (1)
POTENCIOMETRO CORRIENTE DE DISPARO
I∆n (A) 0.25 A; 0.5 A; 1 A; 1.5 A; 2 A; 2.5 A 1.00 A
MICROSWICTH CONSTANTE DE TIEMPO
2 tx10 ; tx1 tx1
MICROSWICTH CONSTANTE DE CORRIENTE
3-4 I∆x1; I∆10; I∆x0.1 I∆x1
www.sdi-ingenieria.cl
0320-MC-5012 – CB-20
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5012 – CB-21
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5012 – CB-26
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5013 – MCP-1
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5013 – MCP-2
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
Enable Warning on L1
- - Disable
Line Loss
Include L1 Line Loss
- - Enabled
Warning in History
L2 LINE LOSS
Assign L2 Line Loss
- - Disable
Detection Enable
Enable Trip on L2 Line
- - Disable
Loss
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Delay 287 L2LossTripDelay 1.0 s
Enable Warning on L2
- - Disable
Line Loss
Include L2 Line Loss
- - Enabled
Warning in History
L3 LINE LOSS
Assign L3 Line Loss
- - Disable
Detection Enable
Enable Trip on L3 Line
- - Disable
Loss
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Delay 288 L3LossTripDelay 1.0 s
Enable Warning on L3
- - Disable
Line Loss
Include L3 Line Loss
- - Enabled
Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5013 – CB-3
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5013 – CB-7
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5013 – MCP-5
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
Enable Warning on L1
- - Disable
Line Loss
Include L1 Line Loss
- - Enabled
Warning in History
L2 LINE LOSS
Assign L2 Line Loss
- - Disable
Detection Enable
Enable Trip on L2 Line
- - Disable
Loss
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Delay 287 L2LossTripDelay 1.0 s
Enable Warning on L2
- - Disable
Line Loss
Include L2 Line Loss
- - Enabled
Warning in History
L3 LINE LOSS
Assign L3 Line Loss
- - Disable
Detection Enable
Enable Trip on L3 Line
- - Disable
Loss
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Delay 288 L3LossTripDelay 1.0 s
Enable Warning on L3
- - Disable
Line Loss
Include L3 Line Loss
- - Enabled
Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5013 – MCP-6
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5013 – MCP-7
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5013 – MCP-8
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5013 – MCP-9
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Voltage
Imbalance Over Limit - - Enabled
Warning in History
368 VIBWarningLevel 10%
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Enable Warning on
Consumed Reactive - - Disable
Power Under Limit
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5021 – CP-21
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5021 – CP-23
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5021 – CP-24
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5021 – MCP-1
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
Enable Warning on L1
- - Disable
Line Loss
Include L1 Line Loss
- - Enabled
Warning in History
L2 LINE LOSS
Assign L2 Line Loss
- - Disable
Detection Enable
Enable Trip on L2 Line
- - Disable
Loss
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Delay 287 L2LossTripDelay 1.0 s
Enable Warning on L2
- - Disable
Line Loss
Include L2 Line Loss
- - Enabled
Warning in History
L3 LINE LOSS
Assign L3 Line Loss
- - Disable
Detection Enable
Enable Trip on L3 Line
- - Disable
Loss
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Delay 288 L3LossTripDelay 1.0 s
Enable Warning on L3
- - Disable
Line Loss
Include L3 Line Loss
- - Enabled
Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5021 – MCP-2
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5021 – MCP-3
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5021 – MCP-4
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5021 – MCP-5
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0320-MC-5021 – MCP-6
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Voltage
Imbalance Over Limit - - Enabled
Warning in History
368 VIBWarningLevel 10%
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Enable Warning on
Consumed Reactive - - Disable
Power Under Limit
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0330-MC-5001 – MCP-1
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0330-MC-5001 – MCP-2
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0330-MC-5001 – MCP-3
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0330-MC-5001 – MCP-4
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0330-MC-5001 – MCP-5
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0330-MC-5001 – MCP-6
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0330-MC-5001 – MCP-7
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
Enable Warning on L1
- - Disable
Line Loss
Include L1 Line Loss
- - Enabled
Warning in History
L2 LINE LOSS
Assign L2 Line Loss
- - Disable
Detection Enable
Enable Trip on L2 Line
- - Disable
Loss
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Delay 287 L2LossTripDelay 1.0 s
Enable Warning on L2
- - Disable
Line Loss
Include L2 Line Loss
- - Enabled
Warning in History
L3 LINE LOSS
Assign L3 Line Loss
- - Disable
Detection Enable
Enable Trip on L3 Line
- - Disable
Loss
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Delay 288 L3LossTripDelay 1.0 s
Enable Warning on L3
- - Disable
Line Loss
Include L3 Line Loss
- - Enabled
Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0330-MC-5001 – MCP-10
www.sdi-ingenieria.cl
PHASE LOSS
N°
PARAMETER NAME VALUE
PARAMETER
Delay Monitoring Time 239 PLInhibitTime 0s
Phase Loss Duration for
240 PLTripDelay 1s
Trip
STALL PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Trip Limit 250 StallTripLevel 600 %FLA
Monitoring Duration Time 249 StallEnabledTime 10 s
JAM PROTECTION
Trip Limit 253 JamTripLevel 250 %FLA
Delay Monitoring Time 251 JamInhibitTime 10 s
Jam Duration Requered
252 JamTripDelay 5.0 s
for Trip
Warning Limit 254 JamWarningLevel 150 %FLA
www.sdi-ingenieria.cl
CURRENT IMBALANCE
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Current
- - Disable
Imbalance Over Limit
Include Current
Imbalance Over Limit Trip - - Enable
In History
Trip Limit 261 CITripLevel 35%
Delay Monitoring Time 259 CIInhibitTime 10 s
Current Imbalance
Duration Required for 260 CITripDelay 5.0 s
Trip
Enable Warning on
Current Imbalance Over - - Disable
Limit
Include Current
Imbalance Over Limit - - Enabled
Warning in History
Warning Limit 262 CIWarningLevel 20%
www.sdi-ingenieria.cl
UNDERLOAD PROTECTION
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Underload
- - Disable
Under Limit
Include Underload Under
- - Enable
Limit Trip In History
Trip Limit 257 ULTripLevel 50 %FLA
Delay Monitoring Time 255 ULInhibitTime 10 s
Underload Duration
256 ULTripDelay 5.0 s
Required for Trip
Enable Warning on
- - Disable
Underload Under Limit
Include Underload Under
- - Enabled
Limit Warning in History
Warning Limit 258 ULWarningLevel 70 %FLA
www.sdi-ingenieria.cl
L2
Enable Trip on L2 Current
- - Disable
Over Limit
Include L2 Current Over
- - Enable
Limit Trip In History
Trip Limit 280 L2OCTripLevel 100%
L2 Over Current Duration
279 L2OCTripDelay 1.0 s
Required for Trip
Enable Warning on L2
- - Disable
Over Current Limit
Include L2 Over Current
- - Enabled
Limit Warning in History
Warning Limit 281 L2OCWarningLevel 90%
L3
Enable Trip on L3 Current
- - Disable
Over Limit
Include L3 Current Over
- - Enable
Limit Trip In History
Trip Limit 283 L3OCTripLevel 100%
L3 Over Current Duration
282 L3OCTripDelay 1.0 s
Required for Trip
Enable Warning on L3
- - Disable
Over Current Limit
Include L3 Over Current
- - Enabled
Limit Warning in History
Warning Limit 284 L3OCWarningLevel 90%
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
FREQUENCY (1)
OVER FREQUENCY
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Frequency
- - Disable
Over Limit
Include Frequency Over
- - Enable
Limit Trip In History
Trip Limit 375 OFTripLevel 63 Hz
Delay Monitoring Time 373 OFInhibitTime 10 s
Over Frequency Duration
374 OFTripDelay 1.0 s
Required for Trip
Enable Warning on
- - Disable
Frequency Over Limit
Include Frequency Over
- - Enabled
Limit Warning in History
Warning Limit 376 OFWarningLevel 62 Hz
UNDER FREQUENCY
Enable Trip on Frequency
- - Disable
Under Limit
Include Frequency Under
- - Enable
Limit Trip In History
Trip Limit 371 UFTripLevel 57 Hz
www.sdi-ingenieria.cl
POWER (1)
OVER REAL POWER
N°
PARAMETER NAME VALUE
PARAMETER
Enable Trip on Real Power
- - Disable
Over Limit
Include Real Power Over
- - Enable
Limit Trip In History
Trip Limit 384 OWTripLevel 0.000 kW
Delay Monitoring Time 382 OWInhibitTime 10 s
Over Real Power Duration
383 OWTripDelay 1.0 s
Required for Trip
Enable Warning on Real
- - Disable
Power Over Limit
Include Real Power Over
- - Enabled
Limit Warning in History
Warning Limit 385 OWWarningLevel 0.000 Kw
UNDER REAL POWER
Enable Trip on Real Power
- - Disable
Under Limit
Include Real Power Under
- - Enable
Limit Trip In History
Trip Limit 380 UWTripLevel 0.000 kW
Delay Monitoring Time 378 UWInhibitTime 10 s
Under Real Power
Duration Required for 379 UWTripDelay 1.0 s
Trip
Enable Warning on Real
- - Disable
Power Under Limit
Include Real Power Under
- - Enabled
Limit Warning in History
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Include Consumed
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 389 UVARCWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Generated Reactive - - Disable
Power Under Limit
Include Generated
Reactive Power Under - - Enabled
Limit Warning in History
Warning Limit 397 UVARGWarnLevel 0.000 kVar
www.sdi-ingenieria.cl
Enable Warning on
Apparent Power Under - - Disable
Limit
Include Apparent Power
Under Limit Warning in - - Enabled
History
Warning Limit 405 UVAWarningLevel 0.000 kVA
www.sdi-ingenieria.cl
Enable Warning on
Leading Power Factor - - Disable
Under Limit
Include Leading Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 421 UPFLeadWarnLevel 95%
www.sdi-ingenieria.cl
Enable Warning on
Lagging Power Factor - - Disable
Under Limit
Include Lagging Power
Factor Under Limit - - Enabled
Warning in History
Warning Limit 413 UPFLagWarnLevel -95 %
www.sdi-ingenieria.cl
0330-MC-5001 – CB-3
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-501)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
www.sdi-ingenieria.cl
Funciones
deshabilitadas
PROTECCIÓN - PHASE TOC (51)
PHASE TOC 2
SETTING SETTING RANGE STEP SIZE PARAMETER
Disabled, Trip, Alarm, Latched Alarm,
Function - Disabled
Configurable
Input Phasor, RMS - Phasor
Pickup 0.020 to 30.000 x CT 0.001 x CT 1.000 x CT
IEEE Extremely / Very / Moderately Inverse;
ANSI Extremely / Very / Normally /
Moderately Inverse; Definite time IEC A / B / IEEE Moderately
Curves -
C and Short Inverse; IAC Extremely / Very / Inverse
Inverse / Short Inverse; FlexCurve A / B / C /
D, I2t, I4t
TDM 0.05 to 600.00 0.01 1.00
RESET Instantaneous, Timed - Instantaneous
Direction Disabled, Ph Dir OC 1 FWD, Ph Dir OC 2 REV - Disabled
Voltage Restraint Disabled, Enabled - Disabled
Block Off, Any FlexLogic operand - OFF
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-502)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
www.sdi-ingenieria.cl
Funciones
deshabilitadas
PROTECCIÓN - PHASE TOC (51)
PHASE TOC 2
SETTING SETTING RANGE STEP SIZE PARAMETER
Disabled, Trip, Alarm, Latched Alarm,
Function - Disabled
Configurable
Input Phasor, RMS - Phasor
Pickup 0.020 to 30.000 x CT 0.001 x CT 1.000 x CT
IEEE Extremely / Very / Moderately Inverse;
ANSI Extremely / Very / Normally /
Moderately Inverse; Definite time IEC A / B / IEEE Moderately
Curves -
C and Short Inverse; IAC Extremely / Very / Inverse
Inverse / Short Inverse; FlexCurve A / B / C /
D, I2t, I4t
TDM 0.05 to 600.00 0.01 1.00
RESET Instantaneous, Timed - Instantaneous
Direction Disabled, Ph Dir OC 1 FWD, Ph Dir OC 2 REV - Disabled
Voltage Restraint Disabled, Enabled - Disabled
Block Off, Any FlexLogic operand - OFF
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-101)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Phases For Operation Any One, Any Two, All Three - Any One
Definite Time, Inverse Time, FlexCurves
Undervoltage Curves - Definite Time
A/B/C/D
Pickup Delay 0.000 to 6000.000 s 0.001 s 3.000 s
Block Off, Any FlexLogic operand - Flexlogic (1)
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
Nota (1): Por definir en terreno, en caso de requerir del bloqueo de la función de Baja Tensión por operación
ITM del TP ( Se debe disponer del estado de la señal ITM operado), en caso contrario ajustar el parámetro en
OFF.
PHASE OV 1
Relé GE-850-EP1NNG1HNNAANGASFB3ECNAN
BREAKER FAILURE: BF1 SETUP
SETTING SETTING RANGE STEP SIZE PARAMETER
Disabled, Retrip, Latched Alarm, Alarm,
Function - Retrip
Configurable
Use Seal-IN Yes, No - Yes
Ph Retrip Superv Pickup 0.050 to 30.000 x CT 0.001 x CT 1.200 x CT
Ntrl Retrip Superv Pickup 0.050 to 30.000 x CT 0.001 x CT 0.100 x CT
Retrip Pickup Delay 0.000 to 6000.000 s 0.001 s 0.050 s
Supervision Current, 52b & Current, 52b - 52b & Current
Breaker Closed Off, Any FlexLogic operand - Flexlogic (2)
T1 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
T2 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
T3 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
Phase Highset Pickup 0.050 to 30.000 x CT 0.001 x CT 1.200 x CT
Neutral Highset Pickup 0.050 to 30.000 x CT 0.001 x CT 0.100 x CT
Lowset Delay 0.000 to 6000.000 s 0.001 s 0.000 s
Phase Lowset Pickup 0.050 to 30.000 x CT 0.001 x CT 1.200 x CT
Neutral Lowset Pickup 0.050 to 30.000 x CT 0.001 x CT 0.100 x CT
Dropout Delay 0.000 to 6000.000 s 0.001 s 0.100 s
Block Off, Any FlexLogic operand - Off
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
BREAKER FAILURE: BF1 INITIATE
SETTING SETTING RANGE STEP SIZE PARAMETER
External Initiate Off, Any FlexLogic operand - Flexlogic (3)
Initiate IN1 Off, Any FlexLogic operand - Ph TOC 1 OP
Initiate IN2 Off, Any FlexLogic operand - Ph IOC 1 OP
Initiate IN3 Off, Any FlexLogic operand - GND IOC 1 OP
Initiate IN4 Off, Any FlexLogic operand - PH UV 1 OP
Initiate IN5 Off, Any FlexLogic operand - PH OV 1 OP
Initiate IN6 Off, Any FlexLogic operand - Off
Initiate IN7 Off, Any FlexLogic operand - Off
Initiate IN8 Off, Any FlexLogic operand - Off
Initiate IN9 Off, Any FlexLogic operand - Off
Initiate IN10 Off, Any FlexLogic operand - Off
Initiate IN11 Off, Any FlexLogic operand - Off
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-102)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Phases For Operation Any One, Any Two, All Three - Any One
Definite Time, Inverse Time, FlexCurves
Undervoltage Curves - Definite Time
A/B/C/D
Pickup Delay 0.000 to 6000.000 s 0.001 s 3.000 s
Block Off, Any FlexLogic operand - Flexlogic (1)
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
Nota (1): Por definir en terreno, en caso de requerir del bloqueo de la función de Baja Tensión por operación
ITM del TP ( Se debe disponer del estado de la señal ITM operado), en caso contrario ajustar el parámetro en
OFF.
PHASE OV 1
Relé GE-850-EP1NNG1HNNAANGASFB3ECNAN
BREAKER FAILURE: BF1 SETUP
SETTING SETTING RANGE STEP SIZE PARAMETER
Disabled, Retrip, Latched Alarm, Alarm,
Function - Retrip
Configurable
Use Seal-IN Yes, No - Yes
Ph Retrip Superv Pickup 0.050 to 30.000 x CT 0.001 x CT 1.200 x CT
Ntrl Retrip Superv Pickup 0.050 to 30.000 x CT 0.001 x CT 0.100 x CT
Retrip Pickup Delay 0.000 to 6000.000 s 0.001 s 0.050 s
Supervision Current, 52b & Current, 52b - 52b & Current
Breaker Closed Off, Any FlexLogic operand - Flexlogic (2)
T1 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
T2 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
T3 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
Phase Highset Pickup 0.050 to 30.000 x CT 0.001 x CT 1.200 x CT
Neutral Highset Pickup 0.050 to 30.000 x CT 0.001 x CT 0.100 x CT
Lowset Delay 0.000 to 6000.000 s 0.001 s 0.000 s
Phase Lowset Pickup 0.050 to 30.000 x CT 0.001 x CT 1.200 x CT
Neutral Lowset Pickup 0.050 to 30.000 x CT 0.001 x CT 0.100 x CT
Dropout Delay 0.000 to 6000.000 s 0.001 s 0.100 s
Block Off, Any FlexLogic operand - Off
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
BREAKER FAILURE: BF1 INITIATE
SETTING SETTING RANGE STEP SIZE PARAMETER
External Initiate Off, Any FlexLogic operand - Flexlogic (3)
Initiate IN1 Off, Any FlexLogic operand - Ph TOC 1 OP
Initiate IN2 Off, Any FlexLogic operand - Ph IOC 1 OP
Initiate IN3 Off, Any FlexLogic operand - GND IOC 1 OP
Initiate IN4 Off, Any FlexLogic operand - PH UV 1 OP
Initiate IN5 Off, Any FlexLogic operand - PH OV 1 OP
Initiate IN6 Off, Any FlexLogic operand - Off
Initiate IN7 Off, Any FlexLogic operand - Off
Initiate IN8 Off, Any FlexLogic operand - Off
Initiate IN9 Off, Any FlexLogic operand - Off
Initiate IN10 Off, Any FlexLogic operand - Off
Initiate IN11 Off, Any FlexLogic operand - Off
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-103)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Phases For Operation Any One, Any Two, All Three - Any One
Definite Time, Inverse Time, FlexCurves
Undervoltage Curves - Definite Time
A/B/C/D
Pickup Delay 0.000 to 6000.000 s 0.001 s 3.000 s
Block Off, Any FlexLogic operand - Flexlogic (1)
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
Nota (1): Por definir en terreno, en caso de requerir del bloqueo de la función de Baja Tensión por operación
ITM del TP ( Se debe disponer del estado de la señal ITM operado), en caso contrario ajustar el parámetro en
OFF.
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Heat Time Constant (tH) 3.0 to 600.0 min 0.1 min 6.0 min
Cool Time Constant (tC) 1.00 to 6.00 x τH 0.01 x τH 2.00 x τH
Block Off, Any FlexLogic operand - OFF
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-104)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Phases For Operation Any One, Any Two, All Three - Any One
Definite Time, Inverse Time, FlexCurves
Undervoltage Curves - Definite Time
A/B/C/D
Pickup Delay 0.000 to 6000.000 s 0.001 s 3.000 s
Block Off, Any FlexLogic operand - Flexlogic (1)
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
Nota (1): Por definir en terreno, en caso de requerir del bloqueo de la función de Baja Tensión por operación
ITM del TP ( Se debe disponer del estado de la señal ITM operado), en caso contrario ajustar el parámetro en
OFF.
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Heat Time Constant (tH) 3.0 to 600.0 min 0.1 min 6.0 min
Cool Time Constant (tC) 1.00 to 6.00 x τH 0.01 x τH 2.00 x τH
Block Off, Any FlexLogic operand - OFF
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-105)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Nota (1): Por definir en terreno, en caso de requerir del bloqueo de la función de Baja Tensión por operación
ITM del TP ( Se debe disponer del estado de la señal ITM operado), en caso contrario ajustar el parámetro en
OFF.
PHASE OV 1
www.sdi-ingenieria.cl
Nota (4): Por definir en terreno. Se debe vincular mediante lógica las variables BF1 Highset OP y BF1 Lowset OP
hacia la salida digital que activa el 86 B1 o 86B2.
Funciones
deshabilitadas
PROTECCIÓN - PHASE TOC (51)
PHASE TOC 2
SETTING SETTING RANGE STEP SIZE PARAMETER
Function Disabled, Trip, Alarm, Latched Alarm, Configurable - Disabled
Input Phasor, RMS - Phasor
Pickup 0.020 to 30.000 x CT 0.001 x CT 1.000 x CT
IEEE Extremely / Very / Moderately Inverse; ANSI
Extremely / Very / Normally /
Moderately Inverse; Definite time IEC A / B / C and IEEE Moderately
Curves -
Short Inverse; IAC Extremely / Very / Inverse
Inverse / Short Inverse; FlexCurve A / B / C / D, I2t,
I4t
TDM 0.05 to 600.00 0.01 1.00
RESET Instantaneous, Timed - Instantaneous
Direction Disabled, Ph Dir OC 1 FWD, Ph Dir OC 2 REV - Disabled
Voltage Restraint Disabled, Enabled - Disabled
Block Off, Any FlexLogic operand - OFF
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
OVERFREQUENCY 2, 3, 4 ,5 y 6
SETTING SETTING RANGE STEP SIZE PARAMETER
Function Disabled, Trip, Alarm, Latched Alarm, Configurable - Disabled
Signal Input J2-3VT, J2-Vx - J2-3VT
Pickup 20.00 to 65.00 Hz 0.01 Hz 60.50 Hz
Pickup Delay 0.000 to 6000.000 s 0.001 s 5.000 s
Dropout Delay 0.000 to 6000.000 s 0.001 s 5.000 s
Minimum Voltage 0.000 to 1.250 x VT 0.001 x VT 0.300 x VT
Block Off, Any FlexLogic operand - Off
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-106)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
TTCC 100/1
Relé GE-850-EP1NNG1HNNAANGASFB3ECNAN
GROUND IOC 1
SETTING SETTING RANGE STEP SIZE PARAMETER
Function Disabled, Trip, Alarm, Latched Alarm, Configurable - Trip
Pickup 0.050 to 30.000 x CT 0.001 x CT 0.713 x CT
Direction Disabled, Forward, Reverse - Disabled
Pickup Delay 0.000 to 6000.000 0.001 0.043 s
Dropout Delay 0.000 to 6000.000 0.001 0.000 s
Block Off, Any FlexLogic operand - OFF
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
PHASE OV 1
www.sdi-ingenieria.cl
Funciones
deshabilitadas
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-107)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Nota (1): Por definir en terreno, en caso de requerir del bloqueo de la función de Baja Tensión por operación
ITM del TP ( Se debe disponer del estado de la señal ITM operado), en caso contrario ajustar el parámetro en
OFF.
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Funciones
deshabilitadas
PROTECCIÓN - PHASE TOC (51)
PHASE TOC 2
SETTING SETTING RANGE STEP SIZE PARAMETER
Function Disabled, Trip, Alarm, Latched Alarm, Configurable - Disabled
Input Phasor, RMS - Phasor
Pickup 0.020 to 30.000 x CT 0.001 x CT 1.000 x CT
IEEE Extremely / Very / Moderately Inverse; ANSI
Extremely / Very / Normally /
Moderately Inverse; Definite time IEC A / B / C IEEE Moderately
Curves -
and Short Inverse; IAC Extremely / Very / Inverse
Inverse / Short Inverse; FlexCurve A / B / C / D, I2t,
I4t
TDM 0.05 to 600.00 0.01 1.00
RESET Instantaneous, Timed - Instantaneous
Direction Disabled, Ph Dir OC 1 FWD, Ph Dir OC 2 REV - Disabled
Voltage Restraint Disabled, Enabled - Disabled
Block Off, Any FlexLogic operand - OFF
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
PHASE DIRECTIONAL
SETTING SETTING RANGE STEP SIZE PARAMETER
Function Disabled, Enabled - Disabled
ECA 0° to 359° 1° 30°
Polarizing V Threshold 0.050 to 3.000 x VT 0.001 x VT 0.700 x VT
REV When V Mem Exp No, Yes - No
Block Off, Any FlexLogic operand - OFF
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-108)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-201)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-202)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-203)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-204)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Relay:
Relays Relay, Disabled -
Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
BREAKER FAILURE: BF1 INITIATE Y BF2 INITIATE
SETTING SETTING RANGE STEP SIZE PARAMETER
External Initiate Off, Any FlexLogic operand - Off
Initiate IN1 Off, Any FlexLogic operand - Ph TOC 1 OP
Initiate IN2 Off, Any FlexLogic operand - Ph TOC 2 OP
Initiate IN3 Off, Any FlexLogic operand - Ph IOC 1 OP
Initiate IN4 Off, Any FlexLogic operand - Ph IOC 2 OP
Initiate IN5 Off, Any FlexLogic operand - Ntrl TOC 1 OP
Initiate IN6 Off, Any FlexLogic operand - Ntrl TOC 2 OP
Initiate IN7 Off, Any FlexLogic operand - Ntrl IOC 1 OP
Initiate IN8 Off, Any FlexLogic operand - Ntrl IOC 2 OP
Initiate IN9 Off, Any FlexLogic operand - GND TOC 1 OP
Initiate IN10 Off, Any FlexLogic operand - GND IOC 1 OP
Initiate IN11 Off, Any FlexLogic operand - Off
Initiate IN12 Off, Any FlexLogic operand - Off
Initiate IN13 Off, Any FlexLogic operand - Off
Initiate IN14 Off, Any FlexLogic operand - Off
Initiate IN15 Off, Any FlexLogic operand - Off
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-205)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
Relé GE-850-EP1NNG1HNNAANGASFB3ECNAN
BREAKER FAILURE: BF1 SETUP
SETTING SETTING RANGE STEP SIZE PARAMETER
Disabled, Retrip, Latched Alarm, Alarm,
Function - Retrip
Configurable
Use Seal-IN Yes, No - Yes
Ph Retrip Superv Pickup 0.050 to 30.000 x CT 0.001 x CT 1.200 x CT
Ntrl Retrip Superv Pickup 0.050 to 30.000 x CT 0.001 x CT 0.100 x CT
Retrip Pickup Delay 0.000 to 6000.000 s 0.001 s 0.050 s
Supervision Current, 52b & Current, 52b - 52b & Current
Breaker Closed Off, Any FlexLogic operand - Flexlogic (2)
T1 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
T2 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
T3 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
Phase Highset Pickup 0.050 to 30.000 x CT 0.001 x CT 1.200 x CT
Neutral Highset Pickup 0.050 to 30.000 x CT 0.001 x CT 0.100 x CT
Lowset Delay 0.000 to 6000.000 s 0.001 s 0.000 s
Phase Lowset Pickup 0.050 to 30.000 x CT 0.001 x CT 1.200 x CT
Neutral Lowset Pickup 0.050 to 30.000 x CT 0.001 x CT 0.100 x CT
Dropout Delay 0.000 to 6000.000 s 0.001 s 0.100 s
Block Off, Any FlexLogic operand - Off
Relay:
Relays Relay, Disabled -
Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
BREAKER FAILURE: BF1 INITIATE
SETTING SETTING RANGE STEP SIZE PARAMETER
External Initiate Off, Any FlexLogic operand - Flexlogic (3)
Initiate IN1 Off, Any FlexLogic operand - Ph TOC 1 OP
Initiate IN2 Off, Any FlexLogic operand - Ph IOC 1 OP
Initiate IN3 Off, Any FlexLogic operand - GND IOC 1 OP
Initiate IN4 Off, Any FlexLogic operand - PH UV 1 OP
Initiate IN5 Off, Any FlexLogic operand - PH OV 1 OP
Initiate IN6 Off, Any FlexLogic operand - Off
Initiate IN7 Off, Any FlexLogic operand - Off
Initiate IN8 Off, Any FlexLogic operand - Off
Initiate IN9 Off, Any FlexLogic operand - Off
Initiate IN10 Off, Any FlexLogic operand - Off
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Relay:
Relays Relay, Disabled -
Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Relay:
Relays Relay, Disabled -
Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Phase-
Mode Phase – Phase, Phase-Ground -
Ground
Pickup 0.00 to 1.50 x VT 0.01xVT 1.50 x VT
Phases For Operation Any One, Any Two, All Three - Any One
Curves Definite Time, Inverse Time, FlexCurves A/B/C/D - Definite Time
Pickup Delay 0.000 to 6000.000 s 0.001 s 1.000 s
Dropout Delay 0.000 to 6000.000 s 0.001 s 1.000 s
Block Off, Any FlexLogic operand - Off
Relay:
Relays Relay, Disabled -
Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-206)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Nota (1): Por definir en terreno, en caso de requerir del bloqueo de la función de Baja Tensión por operación
ITM del TP ( Se debe disponer del estado de la señal ITM operado), en caso contrario ajustar el parámetro en
OFF.
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Undervoltage Curves Definite Time, Inverse Time, FlexCurves A/B/C/D - Definite Time
Pickup Delay 0.000 to 6000.000 s 0.001 s 1.000 s
Block Off, Any FlexLogic operand - Off
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-601.1)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
www.sdi-ingenieria.cl
Funciones deshabilitadas
PROTECCIÓN - PHASE TOC (51)
PHASE TOC 2
SETTING SETTING RANGE STEP SIZE PARAMETER
Disabled, Trip, Alarm, Latched Alarm,
Function - Disabled
Configurable
Input Phasor, RMS - Phasor
Pickup 0.020 to 30.000 x CT 0.001 x CT 1.000 x CT
IEEE Extremely / Very / Moderately Inverse; ANSI
Extremely / Very / Normally /
IEEE
Moderately Inverse; Definite time IEC A / B / C
Curves - Moderately
and Short Inverse; IAC Extremely / Very /
Inverse
Inverse / Short Inverse; FlexCurve A / B / C / D,
I2t, I4t
TDM 0.05 to 600.00 0.01 1.00
RESET Instantaneous, Timed - Instantaneous
Direction Disabled, Ph Dir OC 1 FWD, Ph Dir OC 2 REV - Disabled
Voltage Restraint Disabled, Enabled - Disabled
Block Off, Any FlexLogic operand - OFF
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
AUXILIARY UV 1 y 2
SETTING SETTING RANGE STEP SIZE PARAMETER
Disabled, Trip, Alarm, Latched Alarm,
Function - Disabled
Configurable
Pickup 0.00 to 1.50 x VT 0.01 x VT 1.00 x VT
Minimum Voltage 0.00 to 1.50 x VT 0.01 x VT 0.20 x VT
Undervoltage Curves Definite Time, Inverse Time, FlexCurves A/B/C/D - Definite Time
Pickup Delay 0.000 to 6000.000 s 0.001 s 1.000 s
Block Off, Any FlexLogic operand - Off
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
OVERFREQUENCY 2, 3, 4 ,5 y 6
SETTING SETTING RANGE STEP SIZE PARAMETER
Disabled, Trip, Alarm, Latched Alarm,
Function - Disabled
Configurable
Signal Input J2-3VT, J2-Vx - J2-3VT
Pickup 20.00 to 65.00 Hz 0.01 Hz 60.50 Hz
Pickup Delay 0.000 to 6000.000 s 0.001 s 5.000 s
Dropout Delay 0.000 to 6000.000 s 0.001 s 5.000 s
Minimum Voltage 0.000 to 1.250 x VT 0.001 x VT 0.300 x VT
Block Off, Any FlexLogic operand - Off
Relays Relay, Disabled - Relay: Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0740-SG-5002 – (52-601.2)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Maximum Voltage
10 to 10000 V 1V 1000 V
Difference
Maximum Angle
2 to 80 degrees 1° 10 degrees
Difference
Maximum Frequency
0.05 to 5.00 Hz 0.01 0.05 Hz
Slip
Braker Closing Time 0.00 to 1.00 s 0.01 s 0.10 s
None, DL-DB (Dead Line-Dead Bus), LL-DB (Live
Line-Dead Bus), DL-LB (Dead Line-
Dead Source Live Bus), AL-DB (Any Line-Dead Bus), DL-AB (Dead - None
Line-Any Bus), OL-OD (One Live-Other
Dead), NBL (Not Both Live)
Off, On, Contact Input 1 to 10, Virtual Input 1 to
Synchrocheck Bypass 32, Remote Input 1 to 32, Logic - Off
Element 1 to 16
www.sdi-ingenieria.cl
0320-MC-5002 – (52-501)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0° , 30° Lag, 60° Lag, 90° Lag, 120° Lag, 150° Lag,
Angle With Respect To W1 180° Lag, 210° Lag, 240° Lag, 270° 30° 330° Lag
Lag, 300° Lag, 330° Lag
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
PHASE OV 1
Nota (3): Por definir en terreno.Se recomienda incluir la operación por las señales de protección mecánicas del
transformador (26Q,71Q,49, 63, 63x) como un arranque externo para la Función 50BF . En caso contrario dejar en OFF.
Nota (4): Por definir en terreno. Se debe vincular mediante lógica las variables BF1 Highset OP y BF1 Lowset OP hacia
la salida digital que activa el 86 B1 o 86B2.
CENTRO CONTROL DE MOTORES M.T. 3.45KV
CONTROL - BREAKER FAILURE (50BF)
CENTRO CONTROL MOTORES 0320-MC-5002 - 501
TTCC 2000/5
Relé GE-845-EP5H5G5HNNAANGSSFBSENNBN
BREAKER FAILURE: BF2 SETUP
SETTING SETTING RANGE STEP SIZE PARAMETER
Disabled, Retrip, Latched Alarm, Alarm,
Function - Retrip
Configurable
Signal Input J1, K1 - K1
Use Seal-IN Yes, No - Yes
Ph Retrip Superv Pickup 0.050 to 30.000 x CT 0.001 x CT 1.200 x CT
Ntrl Retrip Superv Pickup 0.050 to 30.000 x CT 0.001 x CT 0.100 x CT
Retrip Pickup Delay 0.000 to 6000.000 s 0.001 s 0.050 s
Supervision Current, 52b & Current, 52b - 52b & Current
Breaker Closed Off, Any FlexLogic operand - Flexlogic (2)
T1 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
T2 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
T3 Pickup Delay 0.000 to 6000.000 s 0.001 s 0.100 s
www.sdi-ingenieria.cl
Nota (3): Por definir en terreno.Se recomienda incluir la operación por las señales de protección mecánicas del
transformador (26Q,71Q,49, 63, 63x) como un arranque externo para la Función 50BF . En caso contrario dejar en OFF.
Nota (4): Por definir en terreno. Se debe vincular mediante lógica las variables BF1 Highset OP y BF1 Lowset OP hacia
la salida digital que activa el 86 B1 o 86B2.
Funciones deshabilitadas
PROTECCIÓN - OVERLOAD (49)
TRANSFORMER OVERLOAD
Function Disabled, Trip, Alarm, Latched Alarm, Configurable - Disabled
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
0320-MC-5002 – (52-101)
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Nota (1): Por definir en terreno, en caso de requerir del bloqueo de la función de Baja Tensión por operación
ITM del TP ( Se debe disponer del estado de la señal ITM operado), en caso contrario ajustar el parámetro en
OFF.
PHASE OV 1
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
www.sdi-ingenieria.cl
Relay:
Relays Relay, Disabled -
Disabled
Events Enabled, Disabled - Enabled
Targets Disabled, Self-reset, Latched - Self-reset
www.sdi-ingenieria.cl
0320-MC-5002 – (52-102)
www.sdi-ingenieria.cl
PHASE OV 1