Documentos de Académico
Documentos de Profesional
Documentos de Cultura
MacBAT 5
ModBUS map (type ENRON)
(Ds6.13)
Document edition: 03
April 2021
Default byte order is 1-2-3-4 (configurable in parameters MBOrdIntCOMX – for integer and
MBOrdFpCOMX – for floating point numbers; X – number of configured COM port).
Current data
1 2 3 4 5 6 7 8 9
0 DTStamp 7001 R ^float 0 0 Date Stamp 32 bit float MMDDYY
1 TMStamp 7002 R ^float 0 0 Time Stamp 32 bit float HHMMSS
2 p1abs 7003 kPa R ^float 0 0 91 Pressure p1 (absolute)
3 p1g 7004 kPa WR ^float 0 7 92 Pressure p1 (overpressure); Values: 0 - Zeroing
4 p2 7005 kPa R ^float 0 7 Pressure p2
5 t 7006 'C R ^float 0 0 131 Temperature t
6 Qm 7007 m3/h R ^float 0 0 57 Flow rate at measurement conditions
7 Qb 7008 m3/h R ^float 0 0 56 Flow rate at base conditions