Está en la página 1de 26

ÍNDICE

1. OBJETIVO. ............................................................................................................................... 2
2. INTRODUCCIÓN. ........................................................................................................................ 2
3. CALIDAD DE LA ENERGÍA. .......................................................................................................... 2
4. FACTOR DE POTENCIA .............................................................................................................. 3
5. ARMÓNICAS. ............................................................................................................................ 3
6. DESCRIPCIÓN DE ACTIVIDADES. ................................................................................................ 4
7. DIAGRAMA UNIFILAR. ................................................................................................................ 6

8. TABLA DE LOS PARÁMETROS ELÉCTRICOS ................................................................................. 8


8.1 PARÁMETROS EN EL INTERRUPTOR GENERAL DE LA ESTACIÓN (SECUNDARIO DEL TRANSFORMADOR 13800/480 V) ................ 8
8.2 PARÁMETROS EN EL INTERRUPTOR PRINCIPAL DEL CCM 480” OLEO 24” CADEREYTA...................................................... 123

9. TABLA DE LA DISTORSIÓN ARMÓNICA TOTAL (THD) EN %, CON RESPECTO A LA FUNDAMENTAL. 14


9.1 INTERRUPTOR GENERAL DE LA ESTACIÓN (SECUNDARIO DEL TRANSFORMADOR 13800/480 V) ............................................ 14
9.2 INTERRUPTOR PRINCIPAL DEL CCM 480” OLEO 24” CADEREYTA. .................................................................................... 15

10. GRÁFICAS DEL COMPORTAMIENTO DE LOS PARÁMETROS ELÉCTRICOS. ..................................... 16


10.1 FORMAS DE ONDA DE LAS TENSIONES (V) Y CORRIENTES (I) DE LAS TRES FASES. ............................................................. 167
10.2 COMPORTAMIENTO EN EL TIEMPO DE LAS TENSIONES (V) Y CORRIENTES (I) DE LAS TRES FASES. ....................................... 167
10.3 COMPORTAMIENTO EN EL TIEMPO DE LA POTENCIA REAL DE LAS TRES FASES. .................................................................. 178
10.4 COMPORTAMIENTO EN EL TIEMPO DE LA POTENCIA REACTIVA DE LAS TRES FASES. ........................................................... 178
10.5 COMPORTAMIENTO EN EL TIEMPO DE LA POTENCIA APARENTE DE LAS TRES FASES. .......................................................... 189
10.6 COMPORTAMIENTO EN EL TIEMPO DEL FACTOR DE POTENCIA DE LAS TRES FASES. .............................................................. 20

11. GRÁFICAS DEL COMPORTAMIENTO DEL THD EN TENSIÓN (V) Y CORRIENTE(I). ........................ 219
11.1 COMPORTAMIENTO DE LA DISTORSIÓN ARMÓNICA TOTAL DE TENSIÓN DE LAS 3 FASES. ...................................................... 21
11.2 COMPORTAMIENTO DE LA DISTORSIÓN ARMÓNICA TOTAL DE CORRIENTE DE LAS 3 FASES. ................................................. 22

12. PORCENTAJE DE LAS ARMÓNICAS EN CORRIENTE DE MAYOR IMPACTO CONTRA LA FUNDAMENTAL


PARA CADA UNA DE LAS FASES. ........................................................................................................ 22
12.1 INTERRUPTOR GENERAL DE LA ESTACIÓN (SECUNDARIO DEL TRANSFORMADOR 13800/480 V) ............................................ 20

13. SISTEMA. ................................................................................................................................ 21


13.1 5º ARMÓNICA DE LA TENSIÓN......................................................................................................................................... 23
13.2 5º ARMÓNICA DE LA CORRIENTE..................................................................................................................................... 24
13.3 CONTENIDO ARMÓNICO DE TENSIÓN, 3ª , 5ª, 7ª ,9ª, 11ª,13ª, 15ª,17ª Y 19ª ........................................................................ 24
13.4 CONTENIDO ARMÓNICO DE CORRIENTE, 3ª , 5ª, 7ª ,9ª, 11ª,13ª, 15ª Y 17ª. ......................................................................... 25

14. DETERMINACIÓN DE DISTORSIÓN ARMÓNICA DE VOLTAJE Y CORRIENTE ..................................... 23

15. RESUMEN EJECUTIVO ............................................................................................................. 24

16. COMENTARIOS Y RECOMENDACIONES ..................................................................................... 25

1
1. Objetivo.
Medir parámetros eléctricos en estado estable en la Estación de Bombeo El Tejar como son:
voltaje, corriente, potencia real, potencia aparente, potencia reactiva, factor de potencia, así como
transitorios, (sags, swell, etc.) y armónicas circulantes en la red para poder evaluar el efecto en su
sistema eléctrico.

El objetivo se puede resumir en determinar la mejor alternativa dirigida a mejorar el uso y distribución
de la energía eléctrica en este sitio, con el reflejo del ahorro de la energía en el sistema eléctrico y
prevención de problemas graves provocados por mala calidad de la energía eléctrica.

2. Introducción.
En todo sistema eléctrico ocurren perturbaciones y en algunos casos inevitables, causados por
fenómenos naturales, accidentes o por la operación misma de la red, lo cual provoca variaciones en
los parámetros eléctricos, afectando la calidad de la energía eléctrica. Esta situación afecta la
continuidad de las actividades productivas, en particular de las industriales que emplean equipos
electrónicos cada vez más avanzados y sensibles.

Dentro de los problemas que suelen presentarse se encuentran: interrupciones del servicio eléctrico,
depresiones o impulsos de voltaje, variaciones en la frecuencia y la generación de armónicas. Otro
problema que en últimas fechas ha causado gran atención y preocupación, es el problema del bajo
factor de potencia. Por lo cual los usuarios requieren la instalación de bancos de capacitores,
pasando éstos a ser equipo necesario e indispensable, que en forma independiente proporciona
beneficios económicos muy interesantes a los usuarios, además de lograr el uso más eficiente y
racional de la energía eléctrica en sus instalaciones.

Por otro lado, la distorsión armónica en los sistemas eléctricos de distribución, ocasionada por el
incremento en la utilización de la electrónica de potencia, presenta un problema creciente tanto para
las empresas suministradoras de energía eléctrica como para sus usuarios.

Idealmente, los generadores de energía eléctrica suministran a la red eléctrica formas de voltaje casi
senoidales. En consecuencia, esperaríamos que la forma de onda de la corriente resultante de
alimentar los diferentes tipos de carga fuera también senoidal pura. Sin embargo, en la práctica las
condiciones de generación, transmisión y utilización de la electricidad no son ideales, es común que
se obtengan formas de onda distorsionadas. La distorsión de las formas de onda reales se expresa
usualmente en términos de la distorsión “armónica” de las formas de onda de la corriente y la tensión.

El fenómeno de la distorsión armónica no es nuevo; la implantación de procedimientos para su control


constituye una preocupación permanente de los ingenieros comprometidos en las diversas etapas de
la utilización de la energía eléctrica desde los primeros sistemas eléctricos. En éstos, la única fuente
de distorsión de las formas de onda de las señales de voltaje lo constituía la saturación del núcleo
magnético de transformadores o de máquinas rotatorias. Sin embargo, más adelante comenzaron a
aparecer algunas cargas no lineales, tales como hornos de arco eléctrico, soldadores eléctricos,
rectificadores, controladores de velocidad de motores, lámparas fluorescentes, computadoras, UPS,
etc. Lo cual trajo como consecuencia una deficiencia en la calidad de la energía eléctrica.

3. Calidad de la energía.
Aunque se tienen muchas definiciones de calidad de la energía el estándar del IEEE define un alto
nivel de calidad de la energía cuando tenemos un bajo nivel de disturbios, entendiéndose por
disturbio como cualquier anormalidad en la forma de onda de voltaje o de corriente.
2
En otras palabras podríamos decir que se tiene calidad de la energía eléctrica cuando hay ausencia
de fallas, producto de sobre tensiones, interrupciones, variaciones de voltaje, contenido armónico,
etc. Estas fallas traen como consecuencia altos costos de reparación de los equipos dañados,
cuantiosas pérdidas por interrupciones en los procesos industriales.

Observamos como día con día como con el incremento masivo que ha tenido la utilización de equipo
basado en electrónica de potencia se ha creado un doble problema en primer lugar, estos equipos al
igual que todos los equipos que incorporan electrónica de potencia son muy sensibles a las
variaciones rápidas de voltaje. En segundo lugar este equipo genera distorsión armónica y bajo
ciertas condiciones puede deteriorar la magnitud y la forma de onda del voltaje suministrado a tal
grado que sea inadecuado de utilizar por la mayoría de los usuarios que comparten la misma fuente
de suministro.

4. Factor de Potencia
El Factor de Potencia es el coseno del ángulo formado entre el vector tensión y el vector corriente,
cuyo valor es expresado en centésimas (0.60, 0.80, 0.90, etc.), en realidad representa el tanto por
ciento que se aprovecha de la energía que se proporciona por la compañía suministradora, por lo que
se considera como un índice para evaluar la eficiencia con la que se utiliza la energía eléctrica en una
instalación. Por tal razón cuando el factor de potencia es bajo se penaliza.

Es importante mantener el Factor de Potencia en un valor superior a 0.90 para evitar las multas que
aplica Comisión Federal de Electricidad y obtener las bonificaciones correspondientes.

En general los beneficios que se obtiene al corregir el Factor de Potencia son:

 Liberación de carga del transformador.


 Reducción de corrientes en alimentadores.
 Reducción de pérdidas en alimentadores.
 Disminución de caída de tensión.
 Evitar pago de multas.
 Obtener bonificaciones.

5. Armónicas.
Frecuencia armónica: frecuencia equivalente a un múltiplo entero de la frecuencia fundamental de la
red de alimentación, en este caso 60 Hz.

Orden de la armónica: relación de la frecuencia armónica con la frecuencia fundamental.

Significa simplemente que la forma de onda de la tensión o corriente no es una senoidal pura, esto
resulta de la adición de una o más ondas armónicas que se sobreponen a la onda fundamental o de
60 Hz. Las armónicas pueden conceptualizarse entonces como voltajes y/o corrientes que existen en
un sistema eléctrico para algunos múltiplos de la frecuencia fundamental.

A continuación se incluyen curvas, en donde se pueden apreciar las formas de onda a frecuencia
fundamental y las armónicas que son señales senoidales a diferentes frecuencias múltiplos de 60 Hz.

3
1.5

0.5

60 Hz
180 Hz
0 0.0 0.3 0.6 0.9 1.2 1.5 1.8 2.1 2.5 2.8 3.1 3.4 3.7 4.0 4.3 4.7 5.0 5.3 5.6 5.9 6.2
300 Hz
00 14 28 43 57 71 85 99 14 28 42 56 70 85 99 13 27 41 56 70 84
Resultante

-0.5

-1

-1.5

Efectos de las Armónicas.

La distorsión armónica incrementa las pérdidas y la temperatura de prácticamente todas las


componentes de las redes eléctricas. El efecto es el incremento en los valores RMS del voltaje y la
corriente, pero sin el desarrollo de trabajo útil alguno.

Los efectos que producen las armónicas en una instalación pueden resumirse en:

 Problemas de funcionamiento en dispositivos de regulación tanto de potencia como de control.


 Mal funcionamiento de los dispositivos de protección y medición.
 Interferencia en sistemas de telecomunicación.
 Sobrecalentamiento de los equipos eléctricos (motores, transformadores, generadores, etc.) y
el cableado de potencia, con la disminución consecuente de vida media en los mismos e
incremento considerable de pérdidas de energía en forma de calor.
 Efectos de resonancia que amplifican los problemas anteriores.
 Daños irreparables a bancos de capacitores.

6. Descripción de Actividades.
Las mediciones eléctricas en campo fueron tomadas: El 10 y 11 de Noviembre del 2009, con un
analizador de redes eléctricas marca DRANETZ-BMI, modelo PP4300.

La mediciones eléctricas realizadas corresponden al Interruptor principal del secundario del


transformador de 13800/480 V y al bus principal del CCM de 480 V correspondiente al sistema
eléctrico del Oleo Ducto de 24”.

4
HORARIOS DE MEDICIÓN

Capacidad del
CIRCUITO
transformador

INTERRUPTOR
1 GENERAL DE 750 KVA
ESTACIÓN
INT. PRINCIPAL
2 CCM 24” 750 KVA

Los parámetros medidos en campo fueron: corriente por fase, voltaje de fase a neutro, potencia real
trifásica, potencia aparente trifásica, potencia reactiva trifásica, factor de potencia, porcentaje de
distorsión armónica de tensión y corriente.

Se registraron todos los eventos anormales que se presentan en el transcurso del tiempo
mencionado, También se obtuvieron las formas de onda características.

5
7. Diagrama unifilar.

28-LV-28C45

28-TR-28C21

28-LV-28C41M

POWER LOGIC

CCM-L-30"

28-LV-28C41A 28-LV-28C41B

30 125 100

POWER LOGIC

CCM-220 VCA
DISPONIBLE

6
CCM-101

7
Conexión del analizador de redes eléctricas en las barras del Interruptor
principal del secundario del transformador.

8. Tabla de los parámetros eléctricos

8.1 Parámetros en el Interruptor general de la estación (secundario del transformador


13800/480 V)

8
Pot. Pot. Pot. Factor
Voltaje de Fase Corriente por fase Real Apar. React de
Hora a Neutro (Volts) (Amp) (KW) KVA KVAR Potencia
VA VB VC VABC IA IB IC In P3f S3f Q3f FP3f
17:08:42 276.1 273.4 273.7 475.2 47.730 42.73 39.40 0.35 28.52 35.513 21.17 0.80
17:10:43 276.0 273.2 273.3 474.9 47.760 42.63 39.30 0.39 28.45 35.441 21.14 0.80
17:12:43 275.8 272.9 272.8 474.3 47.780 42.51 39.25 0.35 28.42 35.356 21.04 0.80
17:14:42 275.6 272.6 272.7 473.9 48.090 42.70 39.20 0.31 28.42 35.447 21.19 0.80
17:16:42 276.0 273.0 273.1 474.6 47.450 42.24 39.37 0.38 28.29 35.257 21.04 0.80
17:18:42 275.9 273.2 273.2 474.7 47.610 42.53 39.33 0.41 28.37 35.375 21.14 0.80
17:20:43 276.1 273.6 273.7 475.4 47.540 42.68 39.40 0.35 28.42 35.460 21.22 0.80
17:22:43 276.2 273.6 273.7 475.4 47.850 42.95 39.47 0.34 28.57 35.643 21.32 0.80
17:24:42 275.9 273.6 273.4 475.1 42.590 40.77 38.48 0.35 26.53 33.399 20.29 0.79
17:26:42 275.9 273.2 272.9 474.6 42.950 40.75 38.38 0.29 26.56 33.426 20.28 0.79
17:28:42 275.7 273.0 272.9 474.3 47.450 42.53 39.30 0.38 28.25 35.297 21.17 0.80
17:30:42 275.7 272.9 272.9 474.3 47.830 42.65 39.28 0.44 28.40 35.414 21.15 0.80
17:32:42 275.7 273.0 272.9 474.4 47.570 42.51 39.20 0.30 28.35 35.297 21.03 0.80
17:34:42 275.7 273.2 273.1 474.5 47.730 42.80 39.23 0.30 28.42 35.428 21.17 0.80
17:36:43 275.2 272.6 272.6 473.7 47.280 42.19 39.18 0.33 28.23 35.074 20.82 0.80
17:38:42 275.6 272.9 273.2 474.4 47.280 42.09 39.23 0.37 28.23 35.120 20.89 0.80
18:02:42 275.4 272.5 272.0 473.4 39.800 41.14 32.74 0.42 23.64 30.959 19.99 0.76
18:04:42 275.1 272.1 271.6 472.8 39.770 40.97 32.67 0.43 23.58 30.848 19.88 0.76
18:06:42 274.7 271.8 271.2 472.0 44.220 42.87 33.30 0.33 25.18 32.627 20.75 0.77
18:08:42 274.3 271.4 270.9 471.5 44.850 43.22 33.40 0.30 25.56 32.863 20.65 0.78
18:10:43 273.8 270.8 270.4 470.5 44.630 42.95 33.32 0.42 25.43 32.647 20.48 0.78
18:12:42 273.4 270.3 270.1 469.8 44.700 42.95 33.20 0.31 25.42 32.582 20.39 0.78
18:14:43 273.2 270.1 269.9 469.5 44.370 42.61 33.23 0.40 25.31 32.392 20.22 0.78
18:16:42 272.8 270.0 269.4 468.9 44.130 42.41 32.94 0.38 25.15 32.150 20.03 0.78
18:52:42 272.1 268.7 268.5 467.3 47.280 46.62 33.06 0.36 27.21 33.936 20.29 0.80
18:54:42 272.6 269.1 269.0 468.0 46.720 46.08 33.15 0.45 27.06 33.746 20.16 0.80
18:56:43 272.0 268.9 268.7 467.4 44.130 42.26 32.99 0.47 25.17 32.032 19.81 0.79
18:58:43 272.0 269.0 268.8 467.5 46.220 45.86 33.11 0.40 26.88 33.511 20.01 0.80
19:00:43 272.8 269.7 269.4 468.7 44.320 42.51 33.18 0.39 25.32 32.287 20.03 0.78
19:02:42 273.1 270.0 269.6 469.2 44.340 42.58 33.06 0.41 25.32 32.307 20.07 0.78
12:47:49 267.8 267.5 269.8 464.8 45.950 33.02 46.97 0.47 33.02 33.210 -3.55 -0.99
12:49:11 267.8 267.7 269.8 464.9 47.300 34.73 51.50 0.50 35.04 35.140 -2.60 -1.00
12:50:40 267.8 267.5 269.6 464.7 46.990 35.85 51.96 0.48 35.37 35.493 -2.93 -1.00
12:52:10 267.6 267.6 269.6 464.7 47.760 34.63 52.18 0.48 35.26 35.349 -2.54 -1.00
12:53:41 267.6 267.4 269.8 464.7 47.180 36.54 53.07 0.48 35.91 36.010 -2.73 -1.00
12:55:11 267.2 267.1 269.4 464.0 48.840 37.49 57.65 0.47 37.61 37.645 -1.60 1.00
12:56:40 267.4 267.1 269.4 464.1 52.090 47.57 58.73 0.49 42.03 42.042 -1.00 1.00
13:05:41 267.5 267.1 269.2 464.1 44.510 43.56 50.63 0.49 36.77 36.860 -2.57 -1.00
13:07:10 267.7 267.1 269.1 464.1 43.360 44.54 50.07 0.48 36.60 36.697 -2.69 -1.00
13:08:41 268.1 267.6 269.6 464.9 42.520 40.75 43.90 0.49 33.76 34.119 -4.94 -0.99
13:10:11 267.9 267.5 269.5 464.7 42.060 35.44 44.77 0.48 32.21 32.398 -3.48 -0.99
13:11:41 265.7 265.6 267.2 461.0 131.950 131.29 139.93 0.50 100.07 107.185 38.41 0.93
13:13:11 267.8 267.9 269.6 464.9 50.670 45.91 62.51 0.49 41.57 42.016 -6.08 -0.99
13:13:13 262.0 262.3 263.8 455.0 231.340 217.11 239.05 0.86
13:13:14 267.1 266.8 268.5 463.3 93.450 86.60 102.61 0.86
13:13:47 262.0 262.3 263.7 454.9 245.640 269.96 243.84 0.86
13:13:48 267.1 266.6 268.4 463.1 87.080 80.17 96.61 0.86
13:14:41 267.7 267.6 269.5 464.6 53.460 48.43 65.46 0.49 43.76 44.208 -6.28 -0.99
13:16:10 267.2 267.1 269.2 463.9 60.310 50.60 70.08 0.50 47.53 47.767 -4.72 -1.00

9
13:17:41 267.8 267.4 269.4 464.5 61.800 53.39 71.17 0.48 49.21 49.363 -3.94 -1.00
13:19:10 267.6 267.2 268.9 464.0 62.260 60.90 68.87 0.49 51.12 51.188 -2.63 1.00
13:20:41 268.0 267.5 269.1 464.6 63.610 57.11 66.50 0.50 49.79 49.906 -3.40 -1.00
13:22:11 267.4 266.8 269.0 463.8 62.040 53.71 61.32 0.48 46.97 47.093 -3.52 -1.00
13:23:41 267.7 267.1 269.5 464.3 63.820 54.52 62.41 0.49 48.00 48.140 -3.57 -1.00
13:25:11 267.9 267.3 269.7 464.7 62.430 53.71 60.31 0.50 46.84 46.995 -3.83 -1.00
13:26:40 267.3 266.7 269.0 463.6 62.450 54.81 61.93 0.50 47.53 47.655 -3.43 -1.00
14:02:40 268.0 267.9 270.1 465.3 40.330 29.10 40.66 0.49 28.37 29.350 -7.51 -0.97
14:04:11 268.1 267.9 270.0 465.4 35.010 31.21 37.27 0.50 26.50 27.701 -8.06 -0.96
14:05:40 268.1 267.6 269.9 465.1 34.840 28.18 32.69 0.49 23.98 25.561 -8.85 -0.94
14:07:10 269.0 268.7 270.8 466.8 35.930 31.01 38.38 0.49 27.08 28.257 -8.09 -0.96
14:08:41 268.8 268.4 270.7 466.4 31.380 26.27 33.15 0.51 22.59 24.312 -8.99 -0.93
14:10:11 268.8 268.2 270.5 466.2 31.410 26.29 32.72 0.49 22.39 24.201 -9.17 -0.93
14:11:40 268.5 268.1 270.5 466.0 31.600 29.25 37.17 0.51 24.78 26.216 -8.56 -0.95
14:13:10 269.1 269.1 271.4 467.4 39.440 24.19 47.34 0.49 28.13 28.551 -4.87 -0.99
14:14:41 270.0 269.7 272.2 468.7 35.950 23.16 40.58 0.48 24.96 25.882 -6.84 -0.96
14:16:11 269.7 269.3 271.7 468.1 35.850 23.04 40.41 0.49 24.84 25.745 -6.78 -0.96
14:31:10 269.7 269.5 271.5 468.0 39.050 31.62 45.18 0.50 30.11 30.612 -5.55 -0.98
14:32:40 269.4 269.1 271.4 467.6 38.930 31.53 45.21 0.49 30.00 30.508 -5.58 -0.98
14:34:10 269.0 268.7 271.0 466.9 38.550 31.75 44.92 0.49 29.80 30.357 -5.79 -0.98
14:35:41 269.6 269.1 271.2 467.6 38.640 31.72 44.89 0.49 29.87 30.409 -5.73 -0.98
14:43:10 269.5 269.4 271.6 467.9 36.940 23.43 41.72 0.48 25.49 26.412 -6.92 -0.97
14:44:41 269.5 269.2 271.3 467.7 36.960 23.33 41.72 0.50 25.42 26.353 -6.98 -0.96
14:46:11 269.6 269.4 271.5 467.9 37.780 24.02 41.60 0.49 25.93 26.824 -6.88 -0.97
14:47:41 269.8 269.2 271.5 467.9 38.480 25.85 36.76 0.50 25.52 26.968 -8.71 -0.95
14:49:11 269.6 269.0 271.4 467.6 44.170 33.51 44.29 0.50 32.34 32.438 -2.55 -1.00
14:50:40 269.1 268.6 270.9 466.8 43.690 33.19 43.56 0.50 31.88 31.993 -2.71 -1.00
14:53:40 269.1 268.7 270.9 466.9 44.050 33.19 43.90 0.51 32.08 32.176 -2.54 -1.00
14:55:10 269.3 269.1 271.1 467.4 45.060 35.71 48.98 0.50 34.43 34.466 -1.74 1.00
14:56:20 260.9 260.0 262.0 452.0 323.580 360.97 315.19 0.81
14:56:21 266.5 266.2 268.1 462.4 138.340 135.98 137.94 1.30
14:56:41 268.8 268.6 270.7 466.5 52.540 42.95 55.13 0.49
14:56:41 268.6 268.6 270.6 466.4 56.780 47.84 59.75 0.49 42.83 44.037 10.24 0.97
14:58:11 268.8 268.7 270.8 466.7 55.260 47.20 58.64 0.51 41.97 43.207 10.27 0.97
Máximo 276.16 273.62 273.68 475.41 323.58 360.97 315.19 1.30 100.07 107.19 38.41 1.00
Mínimo 260.91 260.03 261.97 452.01 31.38 23.04 32.67 0.29 22.39 24.20 -9.17 -1.00
Promedio 270.35 269.13 270.41 467.59 57.03 51.69 56.07 0.48 32.42 35.60 6.14 1.00

10
11
8.2 Parámetros en el Interruptor principal del CCM 480” Oleo 24” Cadereyta.
Voltaje de Fase Corriente por fase Pot. Real Pot. Apar. Pot. React Factor de
Hora a Neutro (Volts) (Amp) (KW) KVA KVAR Potencia
VA VB VC VABC IA IB IC In P3f S3f Q3f FP3f
14:56:41 268.6 268.6 270.6 466.4 56.770 47.83 59.75 0.49 42.83 44.037 10.24 0.97
14:58:11 268.8 268.7 270.8 466.7 55.260 47.19 58.64 0.51 41.97 43.205 10.27 0.97
16:00:41 271.8 269.2 269.3 467.8 28.880 32.92 29.57 0.22 17.43 24.629 17.40 0.71
16:01:12 271.9 269.0 269.6 467.9 26.130 33.14 24.93 0.25 14.85 22.493 16.90 0.66
16:01:42 272.0 269.2 269.6 468.2 26.170 33.20 24.89 0.22 14.84 22.525 16.95 0.66
16:02:11 272.1 269.1 269.6 468.1 26.230 33.25 24.93 0.23 14.89 22.557 16.95 0.66
16:05:12 272.2 269.5 270.0 468.6 25.660 32.83 25.05 0.24 14.75 22.352 16.80 0.66
16:05:42 272.3 269.3 269.9 468.5 25.720 32.56 24.66 0.21 14.57 22.191 16.74 0.66
16:09:12 271.9 269.6 269.6 468.3 27.080 31.04 28.90 0.24 16.33 23.474 16.87 0.70
16:12:42 271.3 268.8 268.9 467.0 45.700 47.66 45.44 0.21 22.96 37.418 29.55 0.61
16:13:11 271.2 268.7 269.0 467.0 49.400 50.92 49.02 0.21 27.05 40.260 29.82 0.67
16:13:42 271.6 269.0 269.2 467.5 49.460 50.89 48.86 0.24 26.93 40.278 29.95 0.67
16:14:12 271.0 269.2 267.8 466.5 49.770 51.44 47.31 0.22 26.79 39.990 29.69 0.67
16:14:41 271.0 268.5 268.7 466.6 49.020 50.52 48.59 0.23 26.63 39.900 29.71 0.67
16:15:12 271.2 268.4 268.8 466.7 49.120 50.28 48.56 0.21 26.60 39.864 29.69 0.67
16:15:42 271.4 268.7 268.7 466.9 49.300 50.19 48.17 0.24 26.49 39.812 29.72 0.67
16:16:12 271.1 268.6 268.6 466.7 49.120 50.30 48.15 0.23 26.46 39.765 29.69 0.67
16:16:41 271.5 268.7 268.8 467.1 49.560 51.27 48.29 0.23 26.99 40.207 29.80 0.67
16:17:12 271.1 268.6 268.8 466.8 49.480 51.73 48.36 0.26 27.07 40.292 29.84 0.67
16:17:42 271.5 268.8 269.0 467.2 49.690 51.75 48.46 0.22 27.18 40.427 29.93 0.67
16:18:12 271.4 268.7 269.0 467.1 49.620 51.64 48.54 0.26 27.15 40.383 29.90 0.67
16:18:41 271.3 268.9 269.0 467.2 49.280 50.78 48.50 0.24 26.66 40.064 29.91 0.67
16:19:12 271.4 268.7 269.0 467.1 49.300 50.59 48.52 0.25 26.63 40.017 29.88 0.67
16:19:41 271.6 269.0 269.1 467.5 48.940 50.32 48.40 0.23 26.44 39.856 29.82 0.66
16:27:42 271.7 269.0 269.2 467.6 48.590 49.29 48.56 0.21 26.10 39.536 29.70 0.66
16:28:12 271.6 268.9 269.3 467.5 48.470 49.26 48.75 0.22 26.15 39.548 29.66 0.66
16:28:42 271.5 269.1 269.4 467.6 48.290 49.44 48.61 0.23 26.13 39.510 29.63 0.66
16:29:11 271.4 268.8 269.1 467.3 48.370 49.40 48.69 0.21 26.18 39.516 29.60 0.66
16:29:42 271.4 268.9 269.0 467.3 48.550 49.42 48.54 0.24 26.15 39.527 29.64 0.66
16:30:12 271.5 269.1 269.2 467.5 48.450 49.53 48.48 0.24 26.10 39.527 29.69 0.66
16:30:42 271.5 268.9 269.1 467.4 48.610 49.35 48.58 0.20 26.11 39.545 29.70 0.66
16:31:11 271.7 269.1 269.4 467.7 49.750 51.89 48.79 0.22 27.33 40.609 30.04 0.67
16:31:42 271.5 268.9 269.3 467.5 49.710 51.93 48.90 0.23 27.28 40.620 30.09 0.67
16:32:12 271.6 268.9 269.3 467.5 49.670 51.80 48.85 0.22 27.28 40.568 30.02 0.67
16:32:41 271.6 269.1 269.4 467.7 49.730 51.97 48.83 0.24 27.34 40.629 30.06 0.67
16:39:41 272.6 270.2 270.3 469.4 28.880 32.56 29.36 0.22 17.20 24.564 17.53 0.70
16:40:12 272.6 270.3 270.3 469.5 28.900 32.65 29.38 0.22 17.26 24.597 17.53 0.70
16:40:42 272.6 270.3 270.4 469.5 28.780 32.67 29.41 0.24 17.27 24.579 17.49 0.70
16:41:11 272.7 270.1 270.4 469.5 28.880 32.65 29.51 0.25 17.28 24.632 17.55 0.70
16:47:42 273.3 270.5 271.2 470.5 26.370 33.20 24.86 0.23 14.84 22.686 17.16 0.65
16:48:12 273.0 270.2 270.8 470.0 26.330 33.18 24.78 0.20 14.84 22.616 17.07 0.66
16:48:41 273.2 270.6 270.9 470.3 29.590 32.98 30.51 0.23 17.98 25.247 17.73 0.71
16:49:12 273.2 270.5 270.9 470.4 28.800 32.96 29.11 0.25 17.23 24.614 17.58 0.70
16:55:42 273.4 270.7 270.9 470.5 29.010 33.47 29.40 0.25 17.69 24.895 17.51 0.71
16:56:12 273.4 270.9 271.0 470.8 28.680 32.52 29.43 0.23 17.21 24.588 17.56 0.70
16:56:42 273.0 270.8 270.9 470.3 28.560 32.56 29.45 0.22 17.23 24.550 17.49 0.70
17:14:41 274.0 271.3 271.4 471.5 29.110 32.67 29.45 0.22 17.31 24.802 17.77 0.70
17:15:11 274.0 271.5 271.5 471.7 29.130 32.76 29.47 0.26 17.35 24.837 17.78 0.70
17:15:42 274.1 271.4 271.7 471.8 29.110 32.81 29.55 0.23 17.36 24.869 17.80 0.70
17:16:12 274.4 271.7 271.8 472.2 29.170 32.83 29.57 0.23 17.39 24.919 17.84 0.70
12
17:29:41 274.1 271.2 271.3 471.4 33.890 38.16 33.51 0.22 19.87 28.675 20.68 0.69
17:30:12 274.2 271.3 271.4 471.7 33.380 37.17 32.72 0.21 19.68 28.072 20.02 0.70
17:30:42 273.9 271.1 271.4 471.4 33.280 37.21 32.78 0.23 19.67 28.057 20.01 0.70
17:31:12 274.2 271.4 271.6 471.8 33.060 36.26 32.86 0.24 19.20 27.802 20.11 0.69
17:42:42 274.2 271.3 271.5 471.7 29.110 32.59 29.40 0.24 17.27 24.770 17.75 0.70
17:43:12 274.4 271.4 271.6 471.9 29.670 33.09 29.40 0.23 17.48 25.062 17.96 0.70
17:43:42 274.4 271.3 271.6 471.9 29.690 33.07 29.43 0.22 17.47 25.071 17.99 0.70
17:44:11 274.3 271.3 271.4 471.7 29.670 32.96 29.34 0.23 17.40 25.001 17.95 0.70
17:44:42 274.6 271.6 271.8 472.3 29.610 32.98 29.41 0.23 17.42 25.045 18.00 0.70
17:45:12 274.6 271.5 271.8 472.2 29.630 33.00 29.43 0.23 17.43 25.057 18.00 0.70
17:45:42 274.0 271.1 271.4 471.4 29.470 32.92 29.34 0.24 17.37 24.916 17.87 0.70
17:46:12 273.8 270.9 271.3 471.1 29.510 32.98 29.41 0.22 17.41 24.957 17.88 0.70
17:46:42 273.9 270.9 271.3 471.1 29.510 32.92 29.40 0.25 17.39 24.931 17.86 0.70
17:47:11 274.0 271.1 271.4 471.4 29.880 34.04 29.43 0.20 17.95 25.341 17.89 0.71
17:47:41 274.1 271.5 271.7 471.8 29.860 34.24 29.45 0.24 17.98 25.411 17.96 0.71
17:59:41 281.3 278.3 278.4 483.8 30.540 37.45 33.17 0.20 20.80 28.124 18.93 0.74
18:00:11 281.4 278.2 278.3 483.8 30.750 37.72 33.45 0.27 20.94 28.332 19.08 0.74
18:59:42 277.1 274.3 274.0 476.5 29.030 36.66 31.84 0.23 20.02 26.671 17.62 0.75
19:00:12 277.1 274.2 273.9 476.4 28.980 36.60 31.82 0.25 20.02 26.627 17.56 0.75
19:00:41 277.2 274.4 274.1 476.7 28.940 36.62 31.82 0.23 20.02 26.639 17.57 0.75
19:06:44 265.7 265.1 262.3 457.9 322.180 276.70 302.82 0.76
19:06:45 271.5 268.5 268.5 466.8 176.020 183.11 185.09 0.92
19:06:45 276.6 273.4 273.1 475.2 50.700 55.63 53.87 0.70
19:07:12 276.3 273.6 273.1 475.2 56.490 60.24 57.52 0.22 33.61 47.772 33.95 0.70
19:07:42 276.5 273.7 273.4 475.4 56.780 60.65 57.54 0.23 33.70 48.001 34.19 0.70
19:08:12 276.3 273.5 273.2 475.1 56.610 60.41 57.37 0.24 33.51 47.813 34.10 0.70
19:08:42 276.3 273.6 273.3 475.3 56.550 60.37 57.37 0.22 33.50 47.796 34.09 0.70
19:09:11 275.8 273.0 272.8 474.4 56.230 60.19 57.23 0.22 33.34 47.535 33.88 0.70
19:09:41 276.1 273.2 273.1 474.8 53.620 60.30 52.56 0.20 30.86 45.534 33.48 0.68
19:12:41 276.6 273.6 273.3 475.5 53.980 60.50 52.40 0.22 30.92 45.698 33.65 0.68
19:13:11 276.4 273.3 273.1 475.0 54.380 61.29 52.50 0.24 31.45 45.988 33.56 0.68
19:13:42 276.5 273.5 273.2 475.3 54.280 61.40 52.38 0.22 31.41 45.979 33.58 0.68
19:14:11 276.4 273.7 273.4 475.4 54.080 61.60 52.44 0.22 31.43 46.006 33.60 0.68
19:14:42 276.3 273.6 273.4 475.3 53.740 60.61 52.52 0.22 30.90 45.686 33.65 0.68
19:15:11 276.6 273.8 273.6 475.8 53.700 60.41 52.46 0.34 30.85 45.642 33.64 0.68
19:15:42 276.4 273.7 273.5 475.5 53.700 60.50 52.48 0.21 30.89 45.648 33.61 0.68
19:16:12 276.5 273.7 273.6 475.7 53.700 60.48 52.67 0.21 30.92 45.715 33.67 0.68
19:19:12 276.4 273.8 273.7 475.6 55.640 59.93 57.54 0.21 33.18 47.509 34.00 0.70
19:19:42 276.4 273.8 273.7 475.7 55.760 59.97 57.44 0.22 33.18 47.532 34.04 0.70
19:20:12 276.4 273.6 273.6 475.5 55.660 59.66 57.56 0.23 33.14 47.432 33.94 0.70
19:20:42 276.5 273.7 273.6 475.6 55.700 59.68 57.44 0.22 33.17 47.432 33.91 0.70
19:21:12 276.5 273.6 273.5 475.5 55.760 59.57 57.48 0.24 33.16 47.418 33.89 0.70
19:25:42 277.0 274.1 273.8 476.2 35.530 42.48 37.69 0.24 23.79 31.696 20.94 0.75
Máximo 281.39 278.26 278.38 483.78 322.18 276.70 302.82 0.92 42.83 48.00 34.19 0.97
Mínimo 265.72 265.09 262.28 457.89 25.66 31.04 24.66 0.20 14.57 22.19 10.24 0.61
Promedio 273.61 270.97 271.08 470.92 45.60 48.76 45.56 0.25 23.86 34.41 24.55 0.69

13
9. Tabla de la distorsión Armónica Total (THD) en %, con respecto a la
fundamental.
9.1 Interruptor general de la estación (secundario del transformador 13800/480 V)
Distorsión Armónica Distorsión Armónica
Hora Total de Voltaje Total de Corriente
Vb
Va (%) (%) Vc (%) Ia (%) Ib (%) Ic (%)
17:08:42 1.34 1.14 1.27 10.37 10.89 8.15
17:10:43 1.22 1.13 1.19 10.31 11.00 8.16
17:12:43 1.29 1.12 1.20 10.34 11.03 8.24
17:40:42 1.09 1.05 1.05 10.16 10.67 8.24
17:51:58 1.09 1.16 1.01 10.81 10.58 10.01
17:52:05 1.11 1.17 1.02 10.99 10.82 9.60
18:06:42 0.97 1.01 0.96 11.29 10.71 9.76
18:08:42 0.89 0.96 0.86 10.55 10.51 9.19
18:36:42 0.83 0.96 0.76 10.62 10.69 9.06
12:49:50 0.91 1.09 1.10 8.87 14.44 10.03
13:32:48 0.89 1.00 1.07 9.46 14.22 13.57
13:34:10 0.90 1.04 1.12 9.58 14.71 13.05
13:34:38 0.92 1.04 1.13 10.18 14.72 14.13
13:40:34 0.93 1.05 1.11 9.73 15.82 11.17
13:41:40 0.94 1.05 1.11 9.37 15.72 10.95
13:42:38 0.91 1.03 1.10 10.01 18.09 12.49
13:43:11 0.94 1.07 1.14 10.53 20.73 14.64
13:44:40 0.93 1.08 1.14 10.79 21.26 15.83
13:46:10 0.93 1.09 1.13 10.73 21.31 15.84
13:46:40 0.89 1.06 1.13 9.23 19.81 15.76
13:47:41 0.92 1.06 1.12 9.17 17.38 13.29
13:49:11 0.94 1.07 1.15 8.72 15.47 15.72
14:01:11 0.92 1.09 1.12 9.16 16.26 13.91
14:07:10 0.97 1.12 1.15 11.25 16.52 14.20
14:20:41 0.92 1.10 1.15 11.05 17.54 14.37
14:22:10 0.93 1.10 1.17 11.23 19.79 16.55
14:22:32 0.94 1.10 1.17 9.80 18.67 16.00
14:23:40 0.94 1.08 1.15 9.67 16.43 14.10
14:25:50 1.01 1.12 1.23 11.35 19.74 16.86
14:28:11 0.99 1.12 1.22 11.29 19.60 16.71
14:43:10 0.95 1.16 1.20 11.61 22.62 14.24
14:44:41 0.98 1.17 1.20 11.77 22.82 14.16
14:46:11 1.02 1.17 1.23 11.54 22.08 14.40
14:47:41 1.01 1.13 1.18 10.56 17.36 13.55
14:53:08 1.04 1.13 1.22 9.62 14.53 12.88
14:58:11 0.98 1.06 1.14 6.45 8.95 8.43
Máximo 1.338 1.173 1.269 11.772 22.818 16.861
Mínimo 0.833 0.960 0.757 6.451 8.952 8.146
Promedio 1.085 1.067 1.013 9.111 15.885 12.504

14
9.2 Interruptor principal del CCM 480” Oleo 24” Cadereyta.

Distorsión Armónica Distorsión Armónica


Hora Total de Voltaje Total de Corriente
Vb
Va (%) (%) Vc (%) Ia (%) Ib (%) Ic (%)
13:37:10 0.90 1.05 1.11 9.75 14.74 13.81
13:38:09 0.89 1.03 1.09 10.34 18.35 12.95
13:38:41 0.88 1.02 1.09 10.18 18.42 12.86
13:40:34 0.93 1.05 1.11 9.73 15.82 11.17
13:41:40 0.94 1.05 1.11 9.37 15.72 10.95
13:43:11 0.94 1.07 1.14 10.53 20.73 14.64
13:44:40 0.93 1.08 1.14 10.79 21.26 15.83
13:50:22 0.95 1.07 1.14 10.11 16.28 16.42
13:51:38 0.92 1.05 1.12 9.93 15.22 13.96
13:52:11 0.92 1.04 1.09 9.60 15.07 13.73
13:53:40 0.91 1.05 1.12 9.06 13.35 12.26
13:54:54 0.95 1.08 1.16 10.32 15.44 14.34
14:02:30 0.89 1.08 1.12 9.88 16.30 13.67
14:04:04 0.93 1.12 1.15 11.47 16.61 15.52
14:05:40 0.93 1.13 1.16 11.56 19.06 18.31
14:07:27 0.92 1.09 1.12 12.66 16.94 14.63
14:10:11 1.00 1.12 1.18 13.40 19.25 17.73
14:11:40 0.97 1.11 1.15 13.22 16.82 15.11
14:20:41 0.92 1.10 1.15 11.05 17.54 14.37
14:22:10 0.93 1.10 1.17 11.23 19.79 16.55
14:35:41 0.99 1.10 1.19 10.55 15.20 12.35
14:37:11 1.03 1.17 1.25 11.13 16.06 13.25
14:38:41 1.00 1.15 1.15 10.56 15.93 12.43
14:40:11 1.01 1.16 1.25 12.40 22.63 14.90
14:53:08 1.04 1.13 1.22 9.62 14.53 12.88
14:53:40 0.98 1.10 1.18 9.57 14.63 12.85
14:55:10 1.01 1.10 1.17 9.03 13.22 11.04
16:44:12 1.24 1.07 1.23 11.76 9.22 9.18
16:45:11 1.24 1.04 1.23 11.81 9.22 9.23
17:07:42 1.47 1.28 1.50 10.17 8.63 6.21
19:22:43 1.45 1.21 1.36 8.88 6.34 4.68
19:23:42 1.41 1.17 1.32 8.83 6.29 4.72
19:26:04 1.43 1.17 1.37 8.69 6.25 4.64
Máximo 1.469 1.279 1.502 13.403 22.632 18.309
Mínimo 0.879 1.023 1.089 8.690 6.253 4.641
Promedio 1.174 1.151 1.295 11.046 14.443 11.475

15
10. Gráficas del comportamiento de los parámetros eléctricos.
10.1 Formas de onda de las tensiones (V) y corrientes (I) de las tres fases.

10.2 Comportamiento en el tiempo de las tensiones (V) y corrientes (I) de las tres fases.

16
10.3 Comportamiento en el tiempo de la potencia real de las tres fases.

10.4 Comportamiento en el tiempo de la potencia reactiva de las tres fases.

17
10.5 Comportamiento en el tiempo de la potencia aparente de las tres fases.

10.6 Comportamiento en el tiempo del factor de potencia de las tres fases.

18
11. Gráficas del comportamiento del THD en Tensión (V) y
Corriente(I).
11.1 Comportamiento de la Distorsión Armónica Total de tensión de las 3 fases.

11.2 Comportamiento de la Distorsión Armónica Total de Corriente de las 3 fases.

19
12. Porcentaje de las armónicas en corriente de mayor impacto
contra la fundamental para cada una de las fases.

12.1 Interruptor general de la estación (secundario del transformador 13800/480 V)

FASE A FASE B FASE C

3a. 5a. 7a. 9a. 11a. 13a. 15a. 17a. 3a. 5a. 7a. 9a. 11a. 13a. 15a. 17a. 3a. 5a. 7a. 9a. 11a. 13a. 15a. 17a.
0.2 1.0 0.3 0.1 0.2 0.1 0.0 0.0 0.2 0.9 0.3 0.1 0.2 0.1 0.1 0.0 0.2 0.8 0.4 0.0 0.2 0.1 0.0 0.1

PORCENTAJE PARA CADA UNA DE LAS ARMONICAS ENCONTRADAS CON MAYOR THDI
FASE A FASE B FASE C

% del promedio de % del promedio de % del promedio de


ARMONICA ARMONICA ARMONICA
distorsión armónica distorsión armónica distorsión armónica

3a. ARMONICA 0.2 3a. ARMONICA 0.2 3a. ARMONICA 0.2


5a. ARMONICA 1.0 5a. ARMONICA 0.9 5a. ARMONICA 0.8
7a. ARMONICA 0.3 7a. ARMONICA 0.3 7a. ARMONICA 0.4
9a. ARMONICA 0.1 9a. ARMONICA 0.1 9a. ARMONICA 0.0
11a. ARMONICA 0.2 11a. ARMONICA 0.2 11a. ARMONICA 0.2
13a. ARMONICA 0.1 13a. ARMONICA 0.1 13a. ARMONICA 0.1
15a. ARMONICA 0.0 15a. ARMONICA 0.1 15a. ARMONICA 0.0
17a. ARMONICA 0.0 17a. ARMONICA 0.0 17a. ARMONICA 0.1

TOTAL DE DISTORSIÓN ARMÓNICA TRIFÁSICA PROMEDIO PARA CADA UNA DE LAS FASES DEL SISTEMA

3a. ARMONICA 0.203

5a. ARMONICA 0.872

7a. ARMONICA 0.332

9a. ARMONICA 0.055

11a. ARMONICA 0.189

13a. ARMONICA 0.115

15a. ARMONICA 0.025

17a. ARMONICA 0.043

20
13. sistema.
13.1 5º armónica de la tensión

13.2 5º armónica de la corriente

21
13.3 Contenido armónico de tensión, 3ª , 5ª, 7ª ,9ª, 11ª,13ª, 15ª,17ª y 19ª

13.4 Contenido armónico de corriente, 3ª , 5ª, 7ª ,9ª, 11ª,13ª, 15ª y 17ª.


Harmonic Tim eplot
%FND
10
M ax T i me
AI H03 6.57 17:55: 12
BI H03 5.08 17:57: 42
CI H03 5.60 17:57: 12
AI H05 10.22 18:43: 12
BI H05 7.84 16:44: 42
9
CI H05 8.30 17:57: 12
AI H07 4.35 18:48: 12
BI H07 2.48 18:11: 12
CI H07 3.98 17:57: 12
AI H09 1.53 18:43: 12
BI H09 0.98 18:43: 12
8 CI H09 0.98 18:29: 41
AI H11 2.22 18:35: 12
BI H11 1.66 17:46: 42
CI H11 1.40 18:34: 42
AI H13 1.83 18:43: 12
BI H13 0.94 16:10: 12
7 CI H13 1.27 18:46: 11
AI H15 1.20 18:46: 11
BI H15 0.56 16:01: 12
CI H15 0.61 18:16: 42
AI H17 1.53 18:18: 42
BI H17 0.74 16:49: 41
6 CI H17 1.22 18:31: 42

0
16:00 16:20 16:40 17:00 17:20 17:40 18:00 18:20 18:40 19:00 19:20
AI H03 BI H03 CI H03 AI H05 BI H05 CI H05 AI H07 BI H07 CI H07
AI H09 BI H09 CI H09 AI H11 BI H11 CI H11 AI H13 BI H13 CI H13
AI H15 BI H15 CI H15 AI H17 BI H17 CI H17

07/01/2010 16:00:00. 00 - 07/01/2010 19:20:00.00


Site: TEJAR

22
14. Determinación de distorsión armónica de voltaje y corriente
Calculo del valor máximo recomendado por la especificación CFE-L000045 Desviaciones Permisibles
en las Formas de Onda de Tensión y Corriente en el Suministro y Consumo de Energía Eléctrica y la
norma IEEE Std 519-1992 Recommended Practices and Requirements for Harmonic Control in
Electrical Power Systems, en distorsión armónica total (THD) y armónicas individuales.

LÍMITES DE DISTORSIÓN ARMÓNICA MÁXIMA PERMISIBLE EN VOLTAJE (%).

TENSIÓN DEL BUS DISTORSIÓN DISTORSIÓN


(kV) INDIVIDUAL TOTAL
DE TENSIÓN (%) DE TENSIÓN (%)
MENOS DE 1 5.0 8.0
69 Y MENOS 3.0 5.0
69.000 A 161 1.5 2.5
161.001 Y MAYOR 1.0 1.5

En el caso de la distorsión en corriente los límites están determinados por el tamaño relativo
del sistema en cuestión contra el sistema del que se alimenta y se expresa como la relación
entre la corriente de corto circuito y la corriente de línea del sistema, como puede verse en la
siguiente tabla de la norma IEEE Std 519-1992 Recommended Practices and
Requirements for Harmonic Control in Electrical Power Systems.

I CC
Para aplicar la especificación se calcula la relación .
IL
Donde I CC : Corriente de cortocircuito en el punto de acometida
I L : Corriente máxima de carga

Cálculo de la I CC , se obtuvo de la corrida de corto circuito.

ICC  14,740 A

Cálculo de la I L , se toma la máxima registrada en el estudio.

I L  360.97 A
Por lo tanto

I CC 14,740
  40.83
I L 360.97

23
LÍMITES DE DISTORSIÓN ARMÓNICA MÁXIMA PERMISIBLE EN CORRIENTE (%).

PARA ARMÓNICAS IMPARES Y MENOS DE 69 DISTORSIÓN


Icc / IL kV ARMÓNICA
TOTAL (%)
h < 11 11 a 16 17 a 22 23 a 34 h > 34
Icc/Is < 20 4.0 2.0 1.5 0.6 0.3 5.0
20 < Icc/Is < 50 7.0 2.5 2.5 1.0 0.5 8.0
50 < Icc/Is < 10.0 4.0 4.0 1.5 0.7 12.0
100
100 < Icc/Is < 12.0 5.5 5.0 2.0 1.0 15.0
1000
Icc/Is > 1000 15.0 7.0 6.0 2.5 1.4 20.0

La relación Icc/IL cae dentro de la condición 20< Icc/IL<50 por lo tanto el limite de distorsión armónica
en corriente seria del 8% y en la mediciones no se registran corrientes armónicas superiores al límite
permitido.

15. Resumen Ejecutivo


A continuación se presentan una tabla resumen con los resultados de las mediciones realizadas en la
Estación De Bombeo El Tejar Veracruz.

TABLA RESUMEN
Pot. Pot. Pot. Factor
Voltaje de Fase Corriente por fase Real Apar. React de
SITIO DE
MEDICIÓN Hora a Neutro (Volts) (Amp) (KW) KVA KVAR Potencia
VA VB VC VABC IA IB IC In P3f S3f Q3f FP3f
Máximo 276.16 273.62 273.68 475.41 323.58 360.97 315.19 1.30 100.07 107.19 38.41 1.00
INT.
Mínimo 260.91 260.03 261.97 452.01 31.38 23.04 32.67 0.29 22.39 24.20 -9.17 -1.00
GENERAL
Promedio 270.35 269.13 270.41 467.59 57.03 51.69 56.07 0.48 32.42 35.60 6.14 1.00
Máximo 281.39 278.26 278.38 483.78 322.18 276.70 302.82 0.92 42.83 48.00 34.19 0.97
CCM 24" Mínimo 265.72 265.09 262.28 457.89 25.66 31.04 24.66 0.20 14.57 22.19 10.24 0.61
Promedio 273.61 270.97 271.08 470.92 45.60 48.76 45.56 0.25 23.86 34.41 24.55 0.69

DISTORSIÓN ARMONICA
SITIO DE Corrie
MEDICIÓN Hora Total de Voltaje Total de nte
Vb
Va (%) (%) Vc (%) Ia (%) Ib (%) Ic (%)
Máximo 1.338 1.173 1.269 11.772 22.818 16.861
INT.
GENERAL Mínimo 0.833 0.960 0.757 6.451 8.952 8.146
Promedio 1.085 1.067 1.013 9.111 15.885 12.504
Máximo 1.469 1.279 1.502 13.403 22.632 18.309
CCM 24" Mínimo 0.879 1.023 1.089 8.690 6.253 4.641
Promedio 1.174 1.151 1.295 11.046 14.443 11.475

24
RESUMEN
Sitio de la
Diagnóstico
Medición
El transformador de 750 KVA es de la capacidad adecuada para soportar la
carga instalada en la estación así como las capacidades de las plantas de
emergencia que corresponden a cada CCM 30” y CCM 24”.

Los valores nominales de la tensión real de operación (Max 483 V, Min. 452.1
V) cumplen con la tolerancia de -10%, +5% recomendada en la norma NMX-J-
098-ANCE-1999 “Sistemas Eléctricos de Potencia-Suministro-Tensiones
Eléctricas normalizadas”.

Con respecto a la especificación de CFE L0000-02 Tensiones de Sistemas de


Distribución, Subtransmisión y Transmisión, el valor también cumple, estando
por debajo del 10% permitido de variación de tensión en sus buses.

La distorsión armónica en voltaje se encuentra por debajo de los valores que


permite la especificación de CFE L0000-45 “Desviaciones Permisibles en las
Formas de Onda de Tensión y Corriente en el Suministro y Consumo de
INTERRUPTOR Energía Eléctrica” (6.5%) y la norma IEEE Std 519-1992 “Recommended
PRINCIPAL DEL Practices and Requirements for Harmonic Control in Electrical Power Systems”
SECUNDARIO DEL (5%):
TRANSFORMADOR
28-TR-28C21 La distorsión Armónica de Corriente promedio (THD-I) se encuentra por arriba
de los valores que permiten la especificación de CFE L0000-45 “Desviaciones
Permisibles en las Formas de Onda de Tensión y Corriente en el Suministro y
Consumo de Energía Eléctrica” (20%) y la norma IEEE Std 519-1992
“Recommended Practices and Requirements for Harmonic Control in Electrical
Power Systems”(12%). Se midieron valores de distorsión armónica de corriente
máximos de 22.632% los cuales corresponden al arranque de la bomba contra
incendio eléctrica.

Durante las mediciones se realizaron pruebas de operación para determinar la


demanda de corriente máxima de la estación obteniendo valores de 360.97
Amp. Operando con la bomba contra incendio eléctrica, el máximo valor
obtenido de corriente fue de 750 Amp. , el cuál se presento durante el arranque
del motor de la bomba contra incendilo.

Las mediciones se realizaron con la carga de cada transformador, trabajando


en condiciones normales de operación.

El Factor de Potencia promedio unitario


La Potencia Real Trifásica promedio 32.42 kW.
La Potencia Reactiva Trifásica promedio 35.60 kVAR.
La Potencia Aparente Trifásica Promedio 6.14 kVA.

25
16. Comentarios y Recomendaciones

RECOMENDACIONES

Se recomienda la Instalación de 1 supresor de transitorios clase “C” a la salida del


interruptor general en 480 Volts de 3 fases 4 hilos con interruptor Square D, QO de
100 A en gabinete para sobreponer.

Se recomienda la instalación de 1 TVSS clase B para protección del CCM en


220V 3 fases 4 hilos con interruptor de protección de 30 A en gabinete para
sobreponer.

La función de los supresores propuestos es la de atenuar los sobre voltajes que se


llegaran a presentar por descargas atmosféricas y la operación misma de la
estación (entrada y salida de motores, cierre y apertura de interruptores etc.) de
acuerdo a lo especificado en la NMX-J-549-ANCE-2004