Instruction Leaflet IL01216001E Effective May 2010

Instruction leaflet for ground fault


protector/earth leakage protector
for LG circuit breakers and motor
circuit protectors
El protector de fallas a tierra y escapes a tierra
para interruptores de circuito y protectores
de circuito de motores
m CAUTION m ADVERTENCIA
DO NOT ATTEMPT TO INSTALL OR PERFORM NO INTENTE INSTALAR O LLEVAR A CABO TRABAJOS
MAINTENANCE ON EQUIPMENT WHILE IT IS DE MANTENIMIENTO EN EL EQUIPOMIENTRAS
ENERGIZED. DEATH OR SEVERE PERSONAL INJURY TENGA ENERGIA. EL CONTACTO CON EQUIPO CON
CAN RESULT FROM CONTACT WITH ENERGIZED ENERGIA PUEDE PROVOCAR LA MUERTE O LESIONES
EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PERSONALES SEVERAS. ANTES DE PROCEDER,
PRESENT BEFORE PROCEEDING. VERIFIQUE SIEMPRE QUE NO HAYA VOLTAJE PRESENTE.

Attach Endcap. Push Down.


Coloque el cubrefalta. Presione hacia abajo.
SCALE 2.000

Figure 1. Figure 3.

Breaker Must Be in OFF Position for Assembly. Insert Screws in Retainers.


Antes de conectar el Interruptor debe a Reset Coloque los tornillos en los
estar en la posicion de apagado (OFF). Unit. retenedores.
b Insert Unit Into Breaker. Restablecer
Coloque la unidad en el interruptor. la unidad.

Figure 2. Figure 4.
Instruction Leaflet IL01216001E Instruction leaflet for ground fault protector/earth 
Effective May 2010 leakage protector for LG circuit breakers 
and motor circuit protectors

Tighten Breaker Screws and Reset Unit and Latch Breaker.


Attach Cover.
Reinicie la unidad y cierre el interruptor.
Apriete los tornillos del ruptor y 3
coloquela tapa.
275.00 in-lb
(31.0 N.m)

1
. 2
0.38 in.
(9.5 mm)

Figure 5. Figure 8.

Reset Unit and Latch Breaker. Attach Accessories.


Reinicie la unidad y cierre el interruptor.
Coloque los accesorios.
2

From Accessories
Proviene de los
accesorios 4-Pole
Cuatro-polos

Figure 6. Figure 9.

Test by Pushing Push-To-Trip Button.


Pruebe la unidad presionado el boton de disparo.
3
1

To Accessory
Hacia los 3-Pole
accesorios Tres-polos

Figure 7. Figure 10.

2 eaton corporation www.eaton.com


Instruction leaflet for ground fault protector/earth  Instruction Leaflet IL01216001E
leakage protector for LG circuit breakers  Effective May 2010
and motor circuit protectors

50% lG (or 50% l n)


(Indicates 50% of Leakage Value Has Been Reached)

Test Button 50% lG (o 50% l n)


(Indica que 50% del valor de escape fue alcanzado)
Botón de prueba

Push-To-Trip Button
Botón de disparo
Push to Trip

Reset
50% l G STATUS
Test
Status Light Reset Button
(Flashes to Indicate T (s) l G (A)
0.3 0.5 2 Botón de reinicio
Proper Operation) 0.15
0.06 0.5 0.10 6
Inst. 1 0.03 30
Luz para indicación
0.03 Inst.
del estado
(Parpadea para
indicar operación lG (or l n )
apropiada) Adjustment
Ajuste del lG
(o l n)
t (s) o t
Adjustment
Ajuster de
t(seg.) (o t)

Figure 11.

Table 1a. LG-Frame Line and Load Terminations


Wire Size Torque
Terminal Catalog
Frame Type Wire Type AWG mm2 Materials Number Lb In Nm
LG-Frame Cu/Al 500–750 a 240–380 a Aluminum TA631L b 550 62
LG-Frame Cu 500–750 a 240–380 a Copper T631L b 500 57
LG-Frame Cu/Al 2–500 b 35–240 b Aluminum TA632L a b 375 42
LG-Frame Cu 2–500 b 35–240 b Copper T632L b 375 42
LG-Frame Cu/Al 2–500 a 35–240 a Aluminum TA350L 375 42
LG-Frame Cu 2–500 a 35–240 a Copper T350L 375 42
a Standard collars mounted on line and load end.
b Terminal shield required for TA631L, T631L, TA632L AND T632L.

Table 1b. Terminaciones de linea y carga del marco LG


Tamano de alambre Torsion
Materials de la Numero de
Tipo de marco Tipo de alambre AWG mm2 terminal catalogo Lb In Nm
Marco LG Cu/Al 500–750 a 240–380 a Aluminio TA631L b 550 62
Marco LG Cu 500–750 a 240–380 a Cobre T631L b 500 57
Marco LG Cu/Al 2–500 b 35–240 b Aluminio TA632L a b 375 42
Marco LG Cu 2–500 b 35–240 b Cobre T632L b 375 42
Marco LG Cu/Al 2–500 a 35–240 a Aluminio TA350L 375 42
Marco LG Cu 2–500 a 35–240 a Cobre T350L 375 42
a Lleva terminales estandar montados en los extremos de linea y carga.
b Protector de terminales son requeridos para TA631L, T631L, TA632L and T632L.

eaton corporation www.eaton.com 3


Instruction Leaflet IL01216001E Instruction leaflet for ground fault protector/earth 
Effective May 2010 leakage protector for LG circuit breakers 
and motor circuit protectors

5.16 4.31 3.44


(131.1) (109.5) (87.4)
3.44 1.72
4.06
(87.4) (43.7)
(103.1)
1.72 3.98 0.86
(43.7) (101.1) (21.8)

4.73 5.58 5.58


(141.7) (141.7) 4.73
(120.1)
(120.1)

8.44
(214.4) 8.44
10.13 (214.4)
(257.3)
15.38
(390.7)

13.69 13.68
(347.7) (347.5)
15.38
(390.7)

3.97
2.75 (69.9) 4-Pole (100.8) 2.75 (69.9) 4-Pole
4.30
7.22 (183.4) 4-Pole 2.74 (69.6) 3-Pole 2.74 (69.6) 3-Pole
(109.2) 7.22 (183.4) 4-Pole
5.48 (139.2) 3-Pole 4.55 5.48 (139.2) 3-Pole
5.43 (115.6) Scale 0.50
(137.9)

Figure 12.

Phase N A B C NOTICE
Fase
BEFORE PERFORMING ANY HIGH VOLTAGE
INSULATION TEST, REFER TO THE FOLLOWING:
ANTES DE REALIZAR CUALQUIER PRUEBA DE AISLAMIENTO
USANDOALTA TENSION, FAVOR HACER REFERENCIA
Push to Trip LO SIGUIENTE:
Reset
50% IG STATUS Trip unit using PUSH-TO-TRIP button prior to any
Test
high voltage test.
T (s) lG (A)
0.15 0.3 0.5 2
0.06 0.5 0.10 6
Inst. 1 0.03 30
Dispare la unidad usando el botón de disparo
antes de ejecutar cualquier prueba de
0.03 Inst.

alto tensión.

Do not apply voltage higher than the unit's rated


voltage on Phase C.
Phase
Nunca aplique un voltaje mús alto por el cual
Fase N A B C esté capacitada la unidad en la fase C.

Figure 13.

Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com

© 2010 Eaton Corporation PowerChain Management is a registered


All Rights Reserved trademark of Eaton Corporation.
Printed in USA
Publication No. IL01216001E / Z9925 All other trademarks are property of their
May 2010 respective owners.