PROCEDIMIENTO DE COMISIONAMIENTO Y
PÚESTA EN SERVICIO DE ESTACION SG3125HV-MV-V30 SUNGROW
ÍNDICE
1 OBJETIVO.............................................................................................................................. 5
2 ALCANCE............................................................................................................................... 5
3 RESPONSABILIDADES. ......................................................................................................... 5
10.5 Jefe de Comisionamiento ................................................................................................. 5
10.6 Encargado de Calidad QA/QC ......................................................................................... 5
10.7 Supervisor HSE/MA ........................................................................................................ 6
10.8 Personal Ejecutor ............................................................................................................. 6
4 DEFINICIONES ...................................................................................................................... 7
5 NORMATIVA Y DOCUMENTOS APLICABLE........................................................................ 8
10.9 Planos y documentos asociados ........................................................................................ 8
10.10 Procedimientos precedentes ......................................................................................... 8
10.11 Normativa aplicable ...................................................................................................... 9
6 RECURSOS, EQUIPOS Y HERRAMIENTAS PARA EL DESARROLLO DE LA ACTIVIDAD ...10
10.12 ELEMENTOS DE PROTECCIÓN PERSONAL.............................................................10
10.13 EQUIPOS Y HERRAMIENTAS ...................................................................................10
10.14 MEDIDAS PREVENTIVAS GENERALES ....................................................................11
7 IMPACTO AL MEDIO AMBIENTE ........................................................................................11
8 DOCUMENTACIÓN PREVIA A LA EJECUCIÓN DE LOS TRABAJOS ..................................11
9 PAUTAS GENERAL Y PROHIBICIONES ...............................................................................12
10 Comisionamiento y puesta en servicio SG6250HV-MV/SG6800HV-MV ...............................12
10.1 Consideraciones previas al inicio de los trabajos. ..............................................................12
10.2 Trabajos rutinarios y traslado de materiales. .....................................................................13
10.3 Identificación de componentes de estación inversor SG6250HV-MV/SG6800HV-MV .......14
10.3.1 Vista exterior de estación de media tensión. ..............................................................14
10.3.2 Ventana de control y monitoreo................................................................................14
10.3.3 Diseño de ventilación. ..............................................................................................16
10.3.4 Diseño Interno de los Componentes internos en Estación MT ...................................16
Proyecto Planta Solar CEME-1
1 OBJETIVO.
El presente documento tiene por objeto describir el proceso de ejecución de COMISIONAMIENTO Y
PUESTA EN MARCHA en el Proyecto del Parque Fotovoltaico CEME1. Establecer las directrices para
dar cumplimiento a las exigencias establecidas en las Bases Administrativas del Proyecto, con el fin de
minimizar y controlar los riesgos asociados a la actividad de COMISIONAMIENTO Y PUESTA EN
SERVICIO. Este documento será utilizado como medio de control y verificación de cumplimiento de
estándares de seguridad, calidad, medio ambiente tanto de POWER CHINA como de sus subcontratas
y a su vez para dar cumplimiento a lo establecido en la Ley 16.744 y en el Decreto Supremo Nº
40, artículo 21 sobre la obligación de informar de los riesgos laborales, para todas las actividades
realizadas por power china y empresas subcontratistas en el proyecto indicado en la correcta ejecución
de los trabajos de COMISIONAMIENTO Y PUESTA EN SERVICIO.
2 ALCANCE.
Este documento proporciona la metodología general para la ejecución de COMISIONAMIENTO Y
PUESTA EN MARCHA en los trabajos que se ejecutarán en el área de proyecto PARQUE
FOTOVOLTAICO ceme1, ubicado en la localidad de María Elena, región de Antofagasta de Chile.
3 RESPONSABILIDADES.
10.5 Jefe de Comisionamiento
• Gestionar el proceso completo del comisionamiento del parque en sitio.
• Gestionar los recursos, el personal y las necesidades para el desarrollo de las actividades de
comisionamiento y puesta en servicio del parque.
• Generar y gestionar la información requerida para suministrar al Coordinador Eléctrico
Nacional.
• Supervisor de Comisionamiento
• Instruir a todos los trabajadores en el presente procedimiento.
• Impartir las instrucciones directas de terreno.
• Reporta al jefe de Comisionamiento todas las actividades desarrolladas en terreno y las
anomalías que se detecten en la ejecución de las actividades.
• Velar por que las diferentes actividades programadas sean ejecutadas de forma correcta y
segura.
4 DEFINICIONES
Tablero eléctrico que permite conectar en paralelo las cadenas (strings) de un campo
fotovoltaico y, al mismo tiempo, protegerlas electrónicamente o a través de fusibles
String Box
destinados a tal fin. El cuadro incorpora un sistema de medida que permite conocer
el estado de cada uno de los string
Proceso mediante el cual se reconoce que existe un peligro y se definen sus
Capacitación
características
CC / DC Corriente continua.
Corriente alterna.
CA / AC
Un multímetro, también denominado polímetro o tester, es un instrumento eléctrico
Multímetro portátil para medir directamente magnitudes eléctricas activas, como corrientes y
potenciales, o pasivas, como resistencias, capacidades y otras
Todos los residuos que se generen en los trabajos serán depositados en los recipientes dispuestos en el
sector de acuerdo con normas del cliente
Además, se debe verificar el cierre perimetral de las áreas a intervenir implementando la señalización y
letreros adecuados de advertencia (trabajos eléctricos, prohibido pasar personal no autorizado, etc).
Coordinar previamente con el cliente los pasos (cronograma de actividades donde se contempla orden
de equipos y/o anillos), los bloqueos correspondientes y la verificación de ausencia de tensión con
equipo multitester (multímetro) o detector de ausencia de tensión.
En todo momento la cuadrilla ejecutora de los trabajos debe mantener el kit de rescate eléctrico
dispuesto por el cliente generalmente el cual debe contar como mínimo con pértiga de rescate, guantes
dieléctricos en función a tensión máxima de trabajo, cuello ortopédico, tabla cervical, entre otros.
10.1 Consideraciones previas al inicio de los trabajos.
• Antes de iniciar, verificar que las condiciones alrededor del inversor son optimas y no se encuentran
zanjas abiertas o intervención con área de construcción.
• Todos los trabajadores deberán estar instruidos en el procedimiento de trabajo seguro
correspondiente, AST o ART y charla diaria previamente antes de acudir al lugar de trabajo.
• Se deja establecido y comunicado que ningún trabajador podrá ejecutar la tarea de forma individual,
siempre debe existir un compañero de trabajo.
• Antes de realizar los trabajos, el supervisor en conjunto con los trabajadores chequeará todas las
herramientas y equipos asegurándose de que no existan fallas y que se presenten en buenas condiciones.
• Los trabajadores deben evaluar la situación antes de que el trabajo se lleve a cabo en o cuando se
encuentren cerca de equipos.
• Segregar y señalización del área de trabajo.
Proyecto Planta Solar CEME-1
• En el evento que ocurra una descarga eléctrica durante la conexión o desconexión de suministro
eléctrico se deberá realizar una acción rápida por los participantes para dar asistencia, por tanto,
generalmente será necesario estar acompañado por alguien que será competente para hacer el sistema
seguro y evitar heridas. La persona acompañante debe estar formada para reconocer el peligro, para
cortar tensión y si es necesario, para dar asistencia en el caso de una emergencia.
• El supervisor o bien el trabajador a cargo de SUMGROW, debe asegurarse que todos los trabajadores
que van a ejecutar cualquier trabajo lleven adecuadamente colocados obligatoriamente los Equipos de
Protección Personal.
• El supervisor o trabajador se debe asegurar que hay espacio, acceso y alumbrado adecuado para
trabajar de forma segura y que toda evacuación existente está despejada.
• Equipos provisionales siempre deben ser de 220 v en lo posible, siendo diseñados, construidos,
instalados y mantenidos según la normativa chilena para evitar el peligro.
• No conectar la alimentación cuando las puertas estén abiertas. Manteniendo todas las puertas cerradas
durante la operación del inversor.
• Seguir todas las instrucciones de seguridad antes de abrir las puertas, podría quedar energía
almacenada en los condensadores. Si no, podría recibir una descarga eléctrica debido a que hay partes
accesibles en tensión.
• No energizar un inversor dañado o que le falten partes, incluso aunque la instalación esté completa.
De lo contrario, podría sufrir una descarga eléctrica. Ya que podría tener acceso a partes energizadas.
•Se debe operar siempre los interruptores con las manos secas y utilizando los EPP apropiados.
Cumpliendo las normativas de seguridad y salud.
• Cualquier tarea en el inversor deben realizarlas, al menos, dos técnicos autorizados.
• En caso de que el inversor sufra una parada debido a una falta en el suministro, no realice ninguna
tarea en él. El inversor podría arrancar automáticamente y recibir una descarga.
• Todos los trabajos que son ejecutados en instalaciones de almacenaje tienen que ser realizados con
casco de seguridad, chaleco reflectante de alta visibilidad, tapones y/o fonos auditivos (si aplica), zapatos
de seguridad dieléctricos, guantes mecánicos de cabritilla, lentes de seguridad, careta facial (si aplica),
mascarillas o respiradores con filtros y todos los EPP necesarios para cada tarea.
• Realizar conducción a la defensiva, respetando los límites de velocidad establecidos en el proyecto
para evitar cualquier choque, colisión, atropello o volcamiento.
• Toda elevación y técnicas de traslado de materiales deben ser emprendidas siguiendo los
procedimientos adecuados de manipulación manual. Malas técnicas de elevación y traslado de
materiales pueden generar molestias y aumentar el riesgo de lesiones las que pueden tener efectos
permanentes. Por lo tanto, se deben implementar las siguientes técnicas para reducir estos riesgos:
• Hay que asegurar que los sistemas de trabajo cumplen con lo establecido para la actividad del trabajo
para la que han sido diseñados.
• Hacer un uso pleno y adecuado de ayudas para el traslado de materiales, tales como carros y/o
equipos de elevación (cuando se requiera).
Proyecto Planta Solar CEME-1
• Conserve los artículos pesados entre el hombro y la altura de la cadera. Siempre que sea posible se
debe sólo, almacenar objetos pequeños, ligeros por encima de los hombros o por debajo de la altura de
la rodilla.
• Use las piernas y las rodillas para agacharse y levantarse – no pararse o doblar la espalda.
• Evitar las tareas, las cuales requieran estiramientos o torsión.
• Asegurarse de que se toman descansos regulares donde las actividades de manipulación manual son
repetitivas para prevenir la aparición de la fatiga.
• Asegurarse que no hay bordes tanto afilados como calientes o fríos, que puedan causar lesiones.
• Asegurarse que las pasarelas o pasillos están libres de obstáculos. De todas maneras, los trabajadores
siempre deberán tener una conducta y actitud ligada al autocuidado tanto personal como el de su equipo
de trabajo.
• Todos los trabajadores reportarán cualquier problema o preocupación asociado con operaciones de
manipulación manual a la línea de mando y el Encargado de Seguridad y Salud.
•Se deberá de respetar la velocidad máxima de conducción dentro de proyecto CEME1 (30km/h
vehículos livianos y 20Km/h maquinaria pesada)
Estación SG6250HV-MV/SG6800HV-MV
•La ventana de Control y Monitoreo está ubicada en la puerta frontal del inversor.
•Como se muestra en la figura siguiente, los indicadores LED están en la parte superior, la pantalla táctil
de cristal líquido (LCD) en color está en la parte media y el botón de parada de emergencia está en la
parte inferior.
Proyecto Planta Solar CEME-1
▪ La interfaz de mantenimiento
La tapa de la pantalla LCD sólo se puede abrir con la llave. Retire la llave y guárdela adecuadamente
después de su uso.
Proyecto Planta Solar CEME-1
Para facilitar la conexión y revisión de cables en sitio, todos los cables entre los dispositivos internos se
han conectado antes de la entrega.
Todos los cables entre la estación MT y el exterior pasan por la parte inferior de la estación MT. Todos
los cables que entran o salen de la estación MT deben estar protegidos adecuadamente (por ejemplo,
utilice un tubo/ducto para cables y evitar daños causados por roedores). Después de las conexiones del
cable, todas las entradas de cables deben sellarse con espuma ignífugo u otros materiales apropiados.
10.3.6 Inversor
10.4 PRE-COMISIONAMIENTO
Para llevar a cabo el pre comisionamiento, asegúrese primero de que el inversor está completamente
aislado y de que se han seguido todos los pasos del procedimiento LOTO.
Para llevar a cabo la puesta en servicio, asegúrese primero de que el inversor está completamente
aislado y de que se han seguido todos los pasos del procedimiento LOTO.
El cliente debe estar en posesión de un documento que certifique que el circuito DC ha sido probado en
cuanto a polaridad, fallos de fuga a tierra, pares de apriete.
! PELIGRO ¡
Cuando el cliente indique que tiene el campo fotovoltaico listo y chequeado, procederemos a revisar en
nuestro armario DC (cada MPPT) que las tensiones y polaridades son correctas canal por canal.
Los trabajos se deberán de realizar en pareja y utilizar radios de comunicación portátiles para establecer
las instrucciones necesarias entre el personal y evitar un malentendido.
• Solicitar a cliente Power china por medio de comunicación radial que nos cierre la primera caja
de string, indicando mediante comunicación radial el numero o TAG de la string box la que será
medida, además de indicar cuando se realiza el cierre y apertura del seccionador de la string
box. El especialista sungrow que se encuentra en el inversor midiendo será quien ordenará las
indicaciones al personal de apoyo por el EPC, en apoyo del supervisor de la actividad.
Proyecto Planta Solar CEME-1
• Indicar el cierre de la string box y medir polaridad y tensión en el canal correspondiente, entre
positivo-tierra, negativo-tierra y entre polo positivo y negativo. Si la polaridad de un cable de
DC es incorrecta, los arreglos fotovoltaicos pueden dañarse.
• Al medir los polos positivo o negativo con respecto a tierra este deberá de indicar una valor
cercano al 50% de la fuente, quiere decir mas menos un 50% de los 1300 o 1500vdc, que
suministre el campo solar, reflejando como ejemplo +650vdc en positivo con respecto a tierra
y -650 vdc en negativo con respecto a tierra, verificando que la tensión se mantenga en
descenso, de lo contrario podríamos identificar que el canal que se encuentra en medición pueda
encontrarse derivado, por lo que habría que indicar abrir el seccionador de la string box, bloquear
y que el EPC verifique la condición de la derivación. De estar en correcta medición continue
con el siguiente punto.
• Comprobamos que la medida es correcta y solicitamos que abran dicha caja de string y cierren
la siguiente.
• Este proceso lo repetiremos con todos los canales del equipo y en cada MPPT. comprobando
así que no hay ningún canal mal conectado o derivado a tierra. La tensión continua (Vdc) no
debe ser superior a los 1500Vdc.
• La tensión de cada entrada de DC de cada string box debe ser la misma y no más del máximo
permisible de tensión DC admisible por el equipo.
• Completar protocolo de comisionamiento inversor (anexo).
! ADVERTENCIA ¡
La tensión del lado DC no debe ser superior a los 1500VDC admisibles en la entrada del inversor. Una
tensión DC demasiada alta puede causar daños a las personas y a los equipos.
Proyecto Planta Solar CEME-1
• Si no hay problemas con la comprobación DC (sección anterior), coordine el cierre de una string
box del MPPT 1.1 y una string box del MPPT 1.2 y cierre los interruptores DC del inversor para
poder energizarlo.
• En la pantalla HMI, verifique que la protección de la puerta esté desactivada (Parameters >
Password 1111 -> Pro-Parameter -> Page 13).
• Programe todas las protecciones (Tensión, Frecuencia, Tiempo, Factor de potencia, etc.) Estos
valores deben ser provistos por EPC. Registre la información en el reporte de comisionamiento
provisto en este documento.
• Ejecute la prueba de Open Loop.
• En la pantalla HMI, tome una fotografía de los valores de corriente y tensión de los IGBT durante
la prueba de Open Loop.
• Compruebe y registre la versión de firmware (password 2222). Registre la información en el
reporte de comisionamiento provisto en este documento.
• Repita prueba para inversor 2 MPPT 2.1 y MPPT2.2
! ADVERTENCIA ¡
Por seguridad, asegúrese de desconectar la comunicación con el sistema SCADA durante las
siguientes pruebas. El inversor puede arrancar sin previo aviso.
Cambiador de TAP
Proyecto Planta Solar CEME-1
El indicador de temperatura del aceite del transformador está cerca de la temperatura ambiente.
• La cubierta del medidor de temperatura de aceite se instala de forma segura, la superficie está
limpia y el vidrio está intacto.
• El bucle de medición de temperatura está completo e intacto.
• Alarma 85 °C; Disparo 95 °C
• El anillo de sellado no tiene fugas
Termómetro de aceite
Deshidratador de aceite
Proyecto Planta Solar CEME-1
Las celdas SafeRing/SafePlus contienen gas SF6 a una presión nominal de 1,4 bar a 20°C.
Las celdas SafeRing/SafePlus están selladas de por vida y disponen de un indicador de presión
(manómetro) compensado a variaciones de la temperatura ambiente. Este dispositivo, bajo demanda,
puede ser suministrado con un accesorio que emite una señal eléctrica cuando la presión cae por debajo
de los valores nominales. Indicador en zona verde - presión correcta. Indicador en zona roja - presión
baja.
Antes de cualquier maniobra sobre los mecanismos, comprobar y asegurar que las tapas frontales se
encuentran montadas y cerradas. Todas las maniobras de los accionamientos de los mandos se realizan
con la palanca de maniobra suministrada (una sola palanca). Todos los mecanismos se encuentran
diseñados y fabricados de forma que las tres fases se maniobran de forma simultánea. La velocidad de
maniobra es independiente de la acción del operador.
Proyecto Planta Solar CEME-1
Antes de la conexión con la red de media tensión, debe realizarse el siguiente trabajo durante la
preparación para la puesta en servicio:
Energice los alimentadores de suministro de alimentación. Conecte la RMU paso a paso, observando
las señales e indicadores. Cuando resulte necesario, compruebe que los conductores están en fase
cuando haya varios cables de alimentadores de entrada y secciones de RMU. Realice todas las
mediciones y compruebe que todas las funciones que dependen del suministro de alimentación de media
tensión están conectadas. Compruebe que no existen irregularidades de ninguna clase.
9.6.5 Operación
Todos los interruptores pueden manejarse con la palanca de operación incluida. El enclavamiento
mecánico interno entre el interruptor-seccionador/aislador y los seccionadores de puesta a tierra
asociados evita cualquier operación incorrecta. Para obtener una descripción detallada del
enclavamiento, consulte la descripción general para cada módulo en el manual CCV/CV ABB en anexo.
Proyecto Planta Solar CEME-1
! ADVERTENCIA ¡
! ADVERTENCIA ¡
Delimite el área y espere autorización del cliente para operar los Interruptor/seecionador de
la RMU.
ATENCIÓN
9.6.6 Desenergizacion
Paso 1: Maniobra de desenergizacion segura de la celda de protección del transformador.
Proyecto Planta Solar CEME-1
9.6.7 Energización
Paso 1: Operación segura de energización de celdas de línea.
Proyecto Planta Solar CEME-1
Recuerde de utilizar los siguientes elementos de seguridad para realizar las operaciones con energía
eléctrica:
Proyecto Planta Solar CEME-1
• Antes de la energización, verifique que se encuentran todas las protecciones de acrílico del
inversor instaladas y limpias.
• Abra las puertas frontales del inversor, en donde se encuentra posicionado el HMI de
operación.
• Cierre el breaker (QS25; QS2) de control de ambos inversores (Posición ON).
• Solo una string box de DC será usado para chequear las condiciones de trabajo de los módulos,
la más próxima al inversor y debe ser posible su visión desde el mismo. En esta string box, el
instalador deberá dejar el mínimo número de fusibles durante el testeo de módulos
individualmente (generalmente 1, 2 o 3 fusibles será suficiente).
• Cerrar una string box en cada MPPT para inversor 1 y 2.
• A posterior asegure de cerrar todas las puertas de la estación SG6250HV-MV/SG6800HV-MV
Proyecto Planta Solar CEME-1
ATENCIÓN!
• Durante las pruebas de operación del inversor, asegúrese que no existan materiales
inflamables o peligrosos al menos 5 metros alrededor del sitio de instalación.
• Normas locales / nacionales sobre la distancia mínima se deben respetar alrededor del
inversor.
• Usando la pantalla HMI, primero ajuste el límite de potencia al 10%. Presione el botón Start y
compruebe que el inversor arranca normalmente y que la potencia es limitada a un 10%. Espere
90 segundos.
• Usando la pantalla HMI, primero ajuste el límite de potencia al 25%. Presione el botón Start y
compruebe que el inversor arranca normalmente y que la potencia es limitada a un 25%. Espere
90 segundos.
• Usando la pantalla HMI, primero ajuste el límite de potencia al 50%. Presione el botón Start y
compruebe que el inversor arranca normalmente y que la potencia es limitada a un 50%. Espere
90 segundos.
• Usando la pantalla HMI, primero ajuste el límite de potencia al 75%. Presione el botón Start y
compruebe que el inversor arranca normalmente y que la potencia es limitada a un 75%. Espere
90 segundos.
• Usando la pantalla HMI, primero ajuste el límite de potencia al 100%. Presione el botón Start y
compruebe que el inversor arranca normalmente y que la potencia es limitada a un 100%. Espere
90 segundos.
Proyecto Planta Solar CEME-1
Jerarquiza Jerarquizació
Tipo Evaluación de Riesgo
Personal Potencial Evaluación de Riesgo Inicial ción n Medidas de
Tarea Residual
Medidas Control
E=Eliminación E=Eliminación del
Rutina Magnitu Magnitu
del Peligro Peligro
rio (R) Daño o d del d del
Nº Tarea Peligro Incidente Toleranc Medidas de Control Actual S=Sustitución Probabi Toleran Medidas de Control a Implementar S=Sustitución Cuerpo Legal Aplicable
No Enfer Consecuencia Probabili Graveda riesgo CI=Control de Graved Riesgo CI=Control de
D I Lesión ia lidad cia
Rutina medad dad (P) d (G) Inicial ingeniería ad (G) Inicial ingeniería
(NA / A) (rediseñar o (P) (NA / A) (rediseñar o
ria (MR=P x MR=P x
separar) separar)
(NR) G) G
CA=Controles CA=Controles
Actividad 1: PROCEDIMIENTO DE COMISIONAMIENTO Y PUESTA EN SERVICIO DE ESTACION SG3125HV-MV-V30 SUNGROW
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
Lesiones, CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
R D Superficies irregulares Caida mismo nivel, golpes X 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
traumatismo trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC- PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
Traumatismol
R D choque, volcamientos X 8 4 32 NA trabajo. Instrucción específica sobre procedimiento de trabajo, CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
lesiones, muerte
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado, Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
normas del transito, velocidades, condciiones del terreno HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
Traslado de personal, Laceración, CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
1 R D caidas mismo nivel X 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
materiale sy equipos traumatismo trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
R D Golpes X Laceración 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
FFVVV Proyecto Planta Solar CEME-1
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
Lesiones, CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
R D Superficies irregulares Caida mismo nivel, golpes X 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
traumatismo trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
R D Golpes X Laceración 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
Cold comissioning trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
2 (inspección visual Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
interior y exterior)
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
Lesiones, CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
R D Superficies irregulares Caida mismo nivel, golpes X 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
traumatismo trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
Contacto con objeto CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
R D X Traumatismo 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
cortante o punzante trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
R D Golpes X Laceración 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
Lesiones, CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
R D Superficies irregulares Caida mismo nivel, golpes X 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
traumatismo trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
Contacto con objeto CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
R D X Traumatismo 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
cortante o punzante trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
PC-CEME1-HSEC-M002 - Manual de Seguridad PC-CEME1-HSEC- Ley 16.744 sobre Accidentes del Trabajo y Enfermedades
Inducción Hombre Nuevo, sobre la obligación de informar ODI,PC-
IT004_0 Instructivo de Análisis de Riesgos en el Trabajo Estandares Profesionales, Decreto Supremo N° 594, Sobre la Condiciones
CEME1-EL-P011 y matriz de los riesgos inherentes y asociados al
R D Golpes X Laceración 8 4 32 NA CA - EPP 8 2 16 A establecidos por Proyecto - Protocolos Asociados Uso de EPP CI - CA - EPP Básicas en los lugares de trabajo, Reglamentos internos de
trabajo. Instrucción específica sobre procedimiento de trabajo,
Especifico- Capacitacion y entrenamiento del personal- difusion de cada empresa, Ley 19.300 sobre bases medio ambientales, ley
Acreditacion de personal, confeccion de ART, Uso de EPP adecuado
HDS que apliquen, Examen de competencias asociados, 17288, guia técnica Radiación UV solar,
Frente a cualquier situación de emergencia, debe seguir Protocolo de Comunicaciones. Dar aviso de
inmediato, comunicando el lugar, el tipo de emergencia, personal herido o evacuación del área a la
guardia.
Hacer uso de los conocimientos de primeros auxilios sólo si está capacitado para dar la ayuda que
corresponda. No mover los heridos a no ser que exista riesgo inminente. Esperar al personal
especializado.
En caso de amago de incendio, activar el sistema contra incendios en forma inmediata o extintores
manuales y evacuar el área.
En caso de accidente grave o fatal seguir el compendio de la SUSESO Libro IV Prestaciones Preventivas.
11 ANEXOS
11.1 Protocolización
Protocolo de pre-comisionamiento inversor
Protocolo de comisionamiento inversor
Protocolo de comisionamiento MV station
Protocolo de pre comisionamiento de MV station
11.2 Diagramas eléctricos sungrow estacion SG3125HV-MV-V30
A-SJ-02772 SG6250HV-MV-V1240 Distribution and MV(1)
A-SJ-02772 SG6250HV-MV-V1240 Inverter(A-ST-03703)
A-SJ-02773 SG6250HV-MV-V1241 Distribution and MV
CEME1-ID-PV-ES-DWG-008-0 Diagrama eléctrico de equipamiento de comunicación en estación
transformadora
CEME1-ID-PV-ES-DWG-009-0 Detalles de Equipamiento de Comunicaciones en Estacion
Transformadora
TI_20230103_SG3125HV-30 Series_Communication Protocal_V19_EN(1)
11.3 RMU ABB 36kV
1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601
1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601
PROTOCOLO DE PRECOMISIONAMIENTO INVERSOR
PROYECTO: PFV CEME1
REVISION 00
DOCUMENTO DE REFERENCA:
CÓDIGO DOC.: Diseñado: Revisado: Aprobado:
M. Mora J. Cabrera J. Cabrera
3.0 CABLEADO AC y DC
6.0 OBSERVACIONES:
Confirmar que las polaridades sean correctas y los valores de tensión en circuito abierto sean similares para todos los strings
Tag combiner
Actividad Pos / Neg (VDC) Pos / Gnd (VDC) Neg / Gnd (VDC)
box
SCB # 1
SCB # 2
SCB # 3
SCB # 4
SCB # 5
SCB # 6
SCB # 7
SCB # 8
SCB # 9
SCB # 10
1.1 El inversor
SG3125HV tiene un SCB # 11
bus comun.
Compruebe las SCB # 12
derivaciones en DC SCB # 13
del inversor antes SCB # 14
de ser energizado
SCB # 15
SCB # 16
SCB # 17
SCB # 18
SCB # 19
SCB # 20
SCB # 21
SCB # 22
SCB # 23
SCB # 24
3
3,1 Presionar el botón “Stop” del inversor a través de la HMI para asegurarse de que el equipo no arrancará automáticamente.
3,2 Solicitar a cliente el cierre de las cajas combinadoras (SCB)
3,3 Ajustar el limite de potencia al 10%
3,4 Colocar AC Switch en posicion ON y cerrar manualmente breaker AC. En workstate en la pantalla principal debe aparecer como keypad
3,5 Colocar DC Switch en posicion ON y verificar que breaker DC permanecen en estado abierto
3,6 Dar partida al inversor por medio del boton start en display y verificar el ciere de los breaker DC
3,7 Verificar y registrar los valores de tensión y frecuencia de la red. La medición no debe exceder el valor permisible de la red.
Verifique con multímetro y registre la tensión fase-fase L1-L2, L1-L3 y L2-L3 y Fase a tierra
VL1-L2 VL1-GND
3,8
VL1-L3 VL2-GND
Registro de
tensión AC .
VL2-L3 VL3-GND
Frecuencia
TOUCH Fm Ver.
Logger Fm Ver.
IDM-AC Fm Ver
DSP 1 Fm Ver. DSP2 Fm Ver.
INV1
INV2
5,3
6 AJUSTES PROTECCIONES
6,1 Verificar ajustes de protecciones
Ajustar el límite de potencia al 10%. Presionar el botón Start y comprobar que el inversor arranca normalmente y que la potencia es limitada a un 10%.
7,1
Espere 90 segundos y repita los pasos gradualmente hasta llegar al 100% de la potencia nomial del inversor.
Curva de Potencia
Actividad Potencia limitada Observaciones:
1,2 110%
10% 100%
1
25%
0,8 75%
0,2 10%
110%
0
0
1 2 3 4 5 6 7
REVISION 00
DOCUMENTO DE REFERENCA:
CÓDIGO DOC.:
Diseñado: Revisado: Aprobado:
M. Mora J. Cabrera J. Cabrera
1,1 Asegúrese de que los interruptores de CC y los interruptores de CA de cada unidad de inversor están en posicion OFF VISUAL
1,2 Asegúrese de que el transformador de media tensión no recibe alimentación de CA y de que su interruptor de aguas abajo está desconectado. VISUAL
En el caso de una red en anillo, asegúrese de que cada operación del switchgear. No encienda dos equipos al mismo tiempo. Encienda cada
1,3 VISUAL
equipo de maniobra y su transformador de uno en uno.
Aplique la tensión nominal a los terminales HV del transformador y deje la unidad en estado de reposo (sin carga) durante 8 horas. A
1,5 VISUAL
continuación, el transformador puede cargarse hasta un valor máximo.
Si se activa la operación de trip en alguno de los dispositivos de protección, el transformador no deberá volver a encenderse antes de que se
1,6 VISUAL/MANUAL
determine la causa de la activación del trip.
Inicie la prueba en la red sólo después de comprobar las conexiones de los cables y la tensión de entrada y salida y de no encontrar ningún
1,8 MANUAL
error.
Mida con precisión la tensión trifásica de línea a línea de la red: L1-L2, L1-L3 y L2-L3. Los datos medidos no deben superar la tensión admisible
1,9 MANUAL
de la red y las tres fases deben estar equilibradas.
2 OPERACION SWITCHGEAR
Cierre los interruptores del gabinete de distribución de energía después de encender el lado de CA del inversor. A continuación, compruebe si la
3,1 MANUAL
tensión de salida del gabinete de distribución de energía es normal.
3,4 Compruebe si la comunicación RS485 y la función de comunicación de red son correctas. VISUAL/MANUAL
1.0 COMPARTIMIENTO MT
Criterios de aceptación
Ítem Actividad Cumple OBSERVACIONES
Verificación Medida Fecha
Si No N/A
Medida con
Tierra: Compruebe si la conexión a tierra está hecha correctamente y la
1.1 multimetro 4Ω.
resistencia a tierra es inferior a 4Ω.
4Ω
Exterior del contenedor: Compruebe si hay daños mecánicos, daños en la
1.2 Visual
pintura, oxidación, etc.
2.0 SWITCHGEAR MT
Conexión por cable: Compruebe si los cables del interior del armario
2.5 C(R) están firmemente fijados a los terminales y si los manguitos Visual
aislantes están bajo tensión.
2.6 Conexión por cable: Compruebe la secuencia de fases de las conexiones. Visual
Puertas: Compruebe si las puertas retiradas del armario RMU se han vuelto
2.9 Visual
a instalar.
1 de 2
PROTOCOLO DE PRE COMISIONAMIENTO DE PROYECTO: PFV CEME1
MV STATION REVISION 00
DOCUMENTO DE REFERENCA:
EECL-21-1-CM-PRT-001
6.0 OBSERVACIONES:
2 de 2
1 2 3 4 5 6 7 8
Confidential
A A
阳光电源股份有限公司
Sungrow Power Supply Co., Ltd.
B B
客户名称
Customer name
C 产品名称 户外型中压一体机 C
Product name Outdoor Inverter Of Medium Voltage
产品型号 SG6250HV-MV-V1240 Distribution & MV
Product model
项目名称
D Project name D
电气标准 IEC/GB
Electrical standard
防护等级 IP54
Level of protection
主电路电压 3PH 600VAC
Main circuit voltage
E
辅助电源电压 400/230VAC E
AUX power voltage
控制电源电压 24VDC/200VDC
Control supply voltage
F F
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
目录Contents A-SJ-02772 SG6250HV-MV-V1240英文目录表格
C C
D D
E E
F F
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
S2 S1
-T1
5 1 7 3
3 1 2
P2 P1
6 2 8 4
3+PE
4turns 3 4
1 5 8
1 2
630 PF 486 SF NET_A NET_B NET_C
L
13 23 2
3 4 位号(XX)
600V PT
N 14 24 功能单元(XXX)
5 6
0V PS 0V SS
C 7 8 系统单元(XXXX) C
D GND -GND2 -T 2
D
Θ
常规接地 外壳地
Chassis ground 3 3
Functional ground
1
160℃
Θ
A 600V 2 箱变变压器(单线图) 温控继电器
main transformer temperature relay
400V a
B 600V
400V b
E E
400V c 3 2
C 600V
+ - S G
0V n L
-GND
保护接地 电流传感器
Protective ground Current sensor
配电三相变压器 温控开关 网口
Three phases transformer
thermal control Ethernet
F F
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
2 3 L 棕 N
1 4
M
LDE2 1~
PE
B B
烟感 单相轴流风机 负荷开关 带底座熔丝 指示灯 接触器主触点
Smoke detector Single-phase axial fan Load break switch Fuse-disconnector Signal light Contactor main contact
3
C C
2
D D
SG6250HV-MV-V1240一体机布局简图 SG6250HV-MV-V1240 Outdoor Inverter of medium voltage location map :
E E
箱变
Oil transformer
逆变器N2
逆变器N1
环网柜
Inverter N2 Inverter N1 RMU
配电柜
Distribution
F F
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
配电柜 Power Distribution Cabinet Confidential
RMU_NA_36KV_SAFE36_20220520
C C v -QS4 -FU102~FU104 -T3 -QF3C63A/4P
-QF4
3 3 3 C32A/4P/30mA
3 3 4
N1:L1/L2/L3
4 4
A M 逆变器交流输出铜排 熔丝fuse:690V/63A -QF5 A
Inverter AC output 1000V/50A 底座hoder:690V/125A C32A/4P/30mA
copper bar 600Vac/400Vac/20KVA 4
4
-QF6
C16A/4P/30mA
4
3 -FU100 4
熔丝Fuse:3*1000V/40A -QF7
底座Holder:1000V/40A C16A/4P/30mA
REF601 4
4
BR
XK1:230V配电端子
3 -SPD4 230V distribution terminal
3 SPD -QF8
B C32A/2P/30mA B
2
AHY10WZ(36)-45/129.5 2
S1 S1 S1
2 2 2 -QF9
C32A/2P/30mA
2
S2 S2 S2 GND 2
C
2
C
2
C
2
-QF10
C16A/2P/30mA
2
2
D D D
-QF11
SAFE36
GNYE C10A/2P
2AWG 2
2
-QF14
C10A/2P
2
GND 2
2
HV_Transf_6250kVA_NA_50℃
等电位连接铜排,或平板箱、集装箱就近接地
Equipotential connection copper bar 36kV屏蔽前接头-70 IN
AQT3-36/630K/70
Tier1_33/0.6-0.6kV_S
2KVA
UPS
D D
3
OUT -QF15
C16A/2P/30mA
2
配电柜插座
SFL-6250/33
2
-T Power Distribution Cabinet socket
-QF16
C10A/2P
GNYE 2
欧变
2AWG
3 3 2
-QF17
C10A/2P
GND 2
等电位连接铜排,或平板箱、集装箱就近接地 2
Equipotential connection copper bar 2
E 逆变器N1端子XB11
XK3:220V配电端子(UPS) E
220V distribution terminal(UPS)
Inverter N1 terminal XB11
2
N1-XB11:5b/6b XK2:24V配电端子
24V distribution terminal
SG3125HV-V33
SG3125HV-V33
逆变器N2端子XB11
N1 3 N2 3 Inverter N2 terminal XB11 2
N2-XB11:5b/6b XK4:24V配电端子
3 3 ★备注Notice: 24V distribution terminal
RS485
COM8 COM9
SLD MLD
2 2 SPD4 PN3 or FL4
GNYE
GNYE GNYE 2AWG
2AWG 2AWG
1 2 3 4 5 6 7 8
F
E
D
C
B
A
1
1
-XSG
BK
11.7:B / XSG-1/XK3-1c 001 15AWG RMU 220Vac-L
1
BK
11.8:B / XSG-2/XK3-3c 002 15AWG RMU 220Vac-N
2
3
RMU +/L
2
2
4
RMU -/N
BK
3b
/ XSG-5/XB12-3b
DO2
123 17AWG
5
RMU VCB remote closing-NO
control
operation
N1-XB12:
BK
4b
RMU closing
/ XSG-6/XB12-4b 124 17AWG RMU VCB remote closing-COM
6
BK
DO3
1b
/ XSG-7/XB12-1b 68 17AWG RMU VCB Tripping-NO
BK 7
control
/ N2-XB12-1b/N1-XB12-1b
1b
DO3
77 17AWG
operation
N1-XB12:
BK
RMU Tripping
2b
control
/ XSG-8/XB12-2b 69 17AWG RMU VCB Tripping-COM
8
operation
N2-XB12:
/ N2-XB12-2b/N1-XB12-2b BK
2b
78 17AWG
RMU Tripping
BK
/ XSG-9/XZ3-11b 119 17AWG RMU Load Switch1 state-NO
11b
9
MV Load
Switch 1
N1-XZ3:
BK
3
3
10
BK
/ XSG-11/N2-XZ3-19b 123 17AWG RMU Earthing Switch1 state-NO
19b
11
Switch 1
N2-XZ3:
BK
/ XSG-12/N2-XZ3-20b 124 17AWG RMU Earthing Switch1 state-COM
20b
12
MV Earthing
BK
/ XSG-13/XZ3-13b 119 17AWG RMU Load Switch2 state-NO
13b
13
MV Load
Switch 2
N1-XZ3:
BK
/ XSG-14/XZ3-14b 120 17AWG RMU Load Switch2 state-COM
14b
14
BK
/ XSG-15/N2-XZ2-15b
15b
15
Switch 2
N2-XZ2:
BK
/ XSG-16/N2-XZ2-16b
4
4
16b
16
MV Earthing
MV
BK
/ XSG-17/XZ2-11b 121 17AWG RMU Disconnector state-NO
11b
17
Switch
N1-XZ2:
BK
/ XSG-18/XZ2-12b 122 17AWG RMU Disconnector state-COM
Disconnector
12b
18
BK
/ XSG-19/XZ3-17b 123 17AWG RMU Earthing Switch3 state-NO
17b
19
Switch 3
N1-XZ3:
BK
/ XSG-20/XZ3-18b 124 17AWG RMU Earthing Switch3 state-COM
18b
20
MV Earthing
BK
/ XSG-21/XZ3-15b 123 17AWG RMU VCB state-NO
15b
21
N1-XZ3:
MV Vacuum
BK
/ XSG-22/XZ3-16b 124 17AWG RMU VCB state-COM
16b
22
Circuit-Breaker
5
5
BK
9b
BK
HV Remote
124 17AWG
24
Drawn by
RD
Checked by
13.4:B / XSG-25/XB13-17b 20AWG RMU RS485-A+
Approved by
RS485
17b
25
Internal
N1-XB13:
BK
13.4:B / XSG-26/XB13-18b 20AWG RMU RS485-B-
Communication
18b
26
XUWT
Jochen
Maggie
27
RMU RS485-GND
Date
Date
Date
28
RMU VCB remote opening-NO
6
6
29
RMU VCB remote opening-COM
30
RMU Low Gas Pressure state-NO
2022/8/18
2022/8/18
2022/8/18
31
RMU Low Gas Pressure state-COM
32
33
Drawing NO.
Drawing Name
Product Model
34
7
7
35
A-SJ-02772-JL-A
8
8
Page 6
A A
FA11-N/XK1-4a /11.5:B
SQ3-21/XK1-1d /11.4:D
SW3-1/XK4-3b / 12.8:C
SW3-2/XK4-1b / 12.7:C
J1-11/XK1-2a / 11.5:B
H4-N/XK1-3d / 11.5:D
B B
BK RD
20AWG 20AWG
-W53
2x20AWG
012 014
004 009 BK BK
BK BK 17AWG 17AWG
17AWG 17AWG
BK RD
20AWG 20AWG
-W54
2x20AWG
003 007
C BK
17AWG
BK
19AWG
C
1 1 2 1 2 -X6 017
-B6 019
-B5 020
-B4 021
-B3 022
-B2 023
-B1 018
- R
- R
LDE2
- Y
LDE2
- Y
LDE1
LDE1
-SW3 -SW4
+
+
+
4 3 4 3 BK BK BK BK BK BK BK
-TK01 P-D-000282 P-D-000282
+ 9AWG 9AWG 9AWG 9AWG 9AWG 9AWG 9AWG
2 -10~+50℃可设定 + - + - + - + - + - + -
11 41 P-D-000234 V3 P-D-000234 V3
011
-J1 BK -
19AWG
/7.2:C 14 44 6节12V铅酸蓄电池
A1 13 6 12V lead-acid batteries
/7.2:D 21
-J1 220VAC
-SQ3
015
A2
-SQ3 BK
17AWG UPS安装在配电柜
240VAC/3A 240VAC/3A 14 UPS installed in power distribution cabinet
006 22 016
BK 008 /7.4:D /7.3:D
BK
17AWG BK
17AWG
19AWG
D 005 013
D
BK BK 112 111 061 058
17AWG 17AWG BK BK BK BK
17AWG 17AWG 17AWG 17AWG
L BU N BK
-FA11
M
L
1~ 5b 6b 13b 14b
-H4
PE GNYE 220V N1-XZ3: N1-XZ2:
230V N
010 SY-1*18-A HV Room HV Room
GNYE Door Smoke
19AWG
-GND2
E E
/ SQ3-14/XZ3-5b
/ SQ3-13/XZ3-6b
/ SW3-4/XZ2-13b
/ SW3-3/XZ2-14b
11 14 /7.1:C
41 44 /7.2:C
接至逆变器N1
A1 A2 /7.2:D To the inverter N1
F F
Checked by Maggie Date 2022/8/18 Drawing Name 环网柜接线图2 Wiring diagram of RMU 2
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
FU100-5/N1-L3
FU100-3/N1-L2
FU100-1/N1-L1
Confidential
N2-XZ3:
Auxiliary transformer
temperature alarm
17AWG
A T3-1/XZ3-17b / A
17b
1
160℃
030
Θ BK
17AWG
T3-2/XZ3-18b / C63A/4P
18b
014 015 016 A 600V 2
BK BK BK
036
BK
-QF3
5AWG 5AWG 5AWG
072 -QS4 030 033 7AWG 蓝色套管 061
-FU102
Blue sleeve
400V a BK
BK BK BK 1 2
9AWG 蓝色套管 1
Blue sleeve
2 9AWG 蓝色套管
Blue sleeve
1 2 9AWG 蓝色套管
Blue sleeve
9AWG 蓝色套管
Blue sleeve
QF3-2/QF8-1 / 10.1:B
037 063
073 031 034
BK BK -FU103 BK B 600V
BK
3 4
BK
9AWG 3 4 9AWG 1 2 9AWG
7AWG 9AWG
QF3-4/QF9-1 / 10.2:B
400V b 065
074 032 035
BK BK -FU104 BK 039 5 6
BK
9AWG 红色套管 5
Red sleeve
6 9AWG 红色套管
Red sleeve
1 2 9AWG 红色套管
Red sleeve BK
9AWG 红色套管
Red sleeve
QF3-6/QF12-1 / 10.5:B
7AWG 红色套管 067
熔丝fuse:690V/63A Red sleeve
050 19AWG
053 19AWG
056 19AWG
BK
1000V/50A 底座hoder:690V/125A 400V c 7 8
C 600V 9AWG 白色套管
QF3-8/QF8-3
BK
BK
BK
White sleeve
/ 10.2:B
B N B
0V n
-QF4
安规电容
060 062 064 066 C32A/4P/30mA
BK BK BK BK
-C83
-C84
-C85
9AWG 9AWG 9AWG 9AWG
040 038 041
5 3 1 GNYE BK BK
蓝色套管
Blue sleeve
红色套管
Red sleeve
白色套管
White sleeve
051 19AWG
054 19AWG
057 19AWG
GNYE
5AWG
BK
BK
BK
熔丝Fuse:3*1000V/40A
6 4 2
-GND
底座Holder:1000V/40A 042
FL4 -GND2 BK 1 2
7AWG
接FU100-2
接FU100-4
接FU100-6
白色套管
043 3 4
接GND
-RT1
PN3
GNYE
1 2
PE 15AWG
T3-n/XK1-5a / 11.6:B 5 6
C C
Θ
L/N L/N L/N L/N 045 044 046
7 8
-PN3 BK
17AWG
BK
17AWG
BK
17AWG
026
BK
5AWG
J1 L3 -RT2
1 2
交直流输入 AC/DC input
028
BK 12 11 12 11 12 11 12 11 L BU BN N BK
5AWG
J3
D
DC+/L2 M D
防雷板 SPD board
-FA10
029
1~ 1 2
GNYE 230V PE GNYE
5AWG 047
J4 GROUND GNYE 3 4
导轨防雷接线图1 15AWG或自带线
Guide SPD attachment figure1
5 6
4 GND FL4
RAC -GND2
接FU100-2
接FU100-4
接FU100-6
068 7 8
节点输出 Node output
049 048 BK
069
接GND
BK BK 9AWG
蓝色套管 BK
11AWG 蓝色套管
RDC 11.4:B / QF7-1/XK1-1a 15AWG 蓝色套管 Blue sleeve
Blue sleeve Blue sleeve 9AWG 070
052 BK 071
J5 BK 9AWG
红色套管
BK
11AWG Red sleeve 9AWG
L/N L/N L/N L/N 白色套管
E 230V配电端子XK1 055
White sleeve
E
BK
11AWG 红色套管
Red sleeve
059 058
SGND BK BK
1 11.5:B / QF7-7/XK1-3a 15AWG 白色套管
White sleeve 11AWG 白色套管
White sleeve
-QF7 1 3 5 7 -QF6 1 3 5 7
C16A/4P/30mA 2 4 6 8 C16A/4P/30mA 2 4 6 8
F F
导轨防雷接线图2 Drawn by XUWT Date 2022/8/18 Drawing NO. A-SJ-02772-JL-A Page 9 of 14
Guide SPD attachment figure2
Checked by Maggie Date 2022/8/18 Drawing Name 配电柜接线图1Wiring diagram of distribution cabinet1
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
/ 9.8:B
QF12-1/QF3-6 / 9.8:B
QF8-1/QF3-2 /9.8:A
QF8-3/QF3-8 /9.8:B
QF9-1/QF3-4
B B
078
BK
11AWG
C 076
BK
083
BK
087
BK
089
BK
C
11AWG 蓝色套管 11AWG 红色套管 11AWG 红色套管 13AWG 红色套管
077
Blue sleeve
088
Red sleeve
090
Red sleeve
QF14-1/X1-L/ 11.2:B
BK BK BK BK BK BK BK
9AWG 白色套管 9AWG 白色套管 9AWG 白色套管 9AWG 白色套管 11AWG 白色套管 11AWG 白色套管 13AWG 白色套管
White sleeve White sleeve White sleeve White sleeve White sleeve White sleeve White sleeve
QF14-3/X1-N/ 11.2:B
-QF8 1 3
-QF9 1 3
-QF10 1 3
-QF11 1 3
-QF12 1 3 1 3 1 3 UPS输入供电
-QF13 -QF14
C10A/2P 2 4 C10A/2P 2 4
D D
-GND PE L N
-X3
250V/16A
欧式插座
E 配电柜插座 E
F F
Checked by Maggie Date 2022/8/18 Drawing Name 配电柜接线图2Wiring diagram of distribution cabinet2
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
X1-N/QF14-3/10.7:C
X1-L/QF14-1/10.7:C
接至N2逆变器
To the inverter N2
UPS-DB9-1/XZ2-13b /
UPS-DB9-5/XZ2-14b /
XK3-1a/QF17-1 /11.4:E
XK3-3a/QF17-3 /11.4:E
XK1-4a/FA11-N /7.2:B
XK1-1a/QF7-1 / 9.5:E
XK1-3a/QF7-7 / 9.5:E
XK1-2a/J1-11/7.1:B
XK3-1c/XSG-1/6.2:C
XK3-3c/XSG-2/6.2:C
XK1-5a/T3-n / 9.6:C
090 089
BK BK
13AWG 13AWG
094
B GNYE B
15AWG
N L PE
058 058
-X1 BK
17AWG
BK
17AWG
模数化插座
004 17AWG
009 17AWG
-GND
BK
BK
102 13AWG
001 15AWG
103 13AWG
002 15AWG
13b 14b
049 15AWG
059 15AWG
043 15AWG
GNYE
BK
BK
BK
BK
BK
BK
N2-XZ2:
配电柜UPS输出220V
UPS fault
alarm
配电柜230V供电
-XK1
-XK3
1d1c
2b2a
2d2c
3b3a
3d3c
4b4a
4d4c
5b5a
5d5c
6b6a
6d6c
1d1c
2b2a
2d2c
3b3a
3d3c
4b4a
4d4c
1b1a
1b1a
IN:N IN:L IN:GND
RelayI/O
DC:+
UPS DB9 1
012 17AWG
024 15AWG
014 17AWG
025 15AWG
105 17AWG
106 17AWG
107 17AWG
108 17AWG
104 15AWG
BK
BK
BK
BK
BK
BK
BK
BK
GNYE
-X2 -X5
插头 N L PE 插头 N L PE
(若孔太细用15AWG)
(若孔太细用15AWG)
7.3:B / XK1-1d/SQ3-21
8.6:D / XK1-2b/XT1-24
8.6:D / XK1-4b/XT1-25
12.2:B / XK3-1b/PE5-J1-3
12.6:B / XK3-2d/PE6-J1-3
12.2:B / XK3-3b/PE5-J1-1
12.6:B / XK3-4d/PE6-J1-1
7.3:B / XK1-3d/H4-N
091
BK
093
BK
095
GNYE
★注意:备用插头,插在UPS输出口
13AWG 13AWG 19AWG -GND
D -GND 配电柜就近接地 D
Distribution cabinet
grounding in close proximity
1 3
-QF15 1 3 1 3
-QF16 -QF17
11.7:B / QF17-1/XK3-1a
11.8:B / QF17-3/XK3-3a
C10A/2P 2 4 C10A/2P 2 4
E E
C16A/2P/30mA 2 4
092 097 099
GNYE BK BK
15AWG 11AWG 11AWG
-GND PE L N
-X4
250V/16A 至UPS输出端子XK3
欧式插座
配电柜插座
F F
UPS附近贴如下标签:
The UPS operation panel is at the rear of this location. Drawn by XUWT Date 2022/8/18 Drawing NO. A-SJ-02772-JL-A Page 11 of 14
Facing the operation panel, Checked by Maggie Date 2022/8/18 Drawing Name 配电柜接线图3Wiring diagram of distribution cabinet3
the" "button is on the left and the TEST button is on the right.
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
引至逆变器 N1 引至逆变器 N2
From the inverter N1 From the inverte N2
XK2-1a/XB11-5b /
XK2-3a/XB11-6b /
XK4-1a/XB11-5b /
XK4-3a/XB11-6b /
A A
PE5 PE6
078 17AWG
079 17AWG
082 17AWG
085 17AWG
BK
BK
BK
BK
107 108
BK BK
配电柜24VDC供电(N1)
配电柜24VDC供电(N2)
-PE5 AC1-N 1
17AWG
PE5-J1-1/XK3-3b/11.8:D -PE6 AC1-N 1
17AWG
PE6-J1-1/XK3-4d/11.8:D
B B
-XK2
-XK4
1d1c
2b2a
2d2c
3b3a
3d3c
4b4a
4d4c
1d1c
2b2a
2d2c
3b3a
3d3c
4b4a
4d4c
1b1a
1b1a
105 106
P-E-000282 P-E-000282
2 BK 2 BK
17AWG 17AWG
交 AC1-L 3 PE5-J1-3/XK3-1b/11.7:D 交 AC1-L 3 PE6-J1-3/XK3-2d/11.7:D
流 J1 4 流 J1 4
输 +24V +24V 0V 0V 输 +24V +24V 0V 0V
入 AC2-L 5 入 AC2-L 5
6 1b、1c、1d、 3b、3c、3d、 6 1b、1c、1d、 3b、3c、3d、
2a、2b、2c、2d: 4a、4b、4c、4d: 2a、2b、2c、2d: 4a、4b、4c、4d:
AC2-N 7 109
BK
+24V 0V
AC2-N 7 113
BK
+24V 0V
电 17AWG 电 17AWG
源 1 PE5-J2-1/XK2-2b/12.4:C 源 1 PE6-J2-1/XK4-2b/12.7:C
对 +22V 2 对 +22V 2
顶 顶
109 17AWG
110 17AWG
20AWG
113 17AWG
20AWG
114 17AWG
110 114
板 3 BK 板 3 BK
BK
BK
RD
BK
BK
BK
17AWG 17AWG
4 PE5-J2-4/XK2-4b/12.4:C 4 PE6-J2-4/XK4-4b/12.8:C
C 直 SGND 5 直 SGND 5 C
流
J2 6 流
J2 6
输 输
7.5:B / XK4-1b/SW3-2
7.4:B / XK4-3b/SW3-1
7 7
12.2:C / XK2-2b/PE5-J2-1
12.2:C / XK2-4b/PE5-J2-4
12.6:C / XK4-2b/PE6-J2-1
12.6:C / XK4-4b/PE6-J2-4
出 出
+24V 8 +24V 8
9 9
NO 10 NO 10
C 11 C 11
NC 12 NC 12
D D
至逆变器N1 1
network cable
-EDS
111
BK
1 3 5 Optical fiber 2
E 17AWG
24V E
112
BK
17AWG Optical fiber
OV 2 4 6
3
network cable
交换机
Switch
4
23
至逆变器N2
To the inverter N2 24
F F
Checked by Maggie Date 2022/8/18 Drawing Name 配电柜接线图4Wiring diagram of distribution cabinet4
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
逆变器 N1和N2之间RS485通讯接线The RS485 communication between inverter N1 and N2
逆变器 N1端子 inverter N1 terminal 逆变器 N2端子 inverter N2 terminal
A A
-XB13
-XB13
10b10a
11b11a
12b12a
13b13a
14b14a
15b15a
16b16a
17b17a
18b18a
10b10a
11b11a
12b12a
13b13a
14b14a
15b15a
16b16a
17b17a
18b18a
2b2a
3b3a
4b4a
5b5a
6b6a
7b7a
8b8a
9b9a
2b2a
3b3a
4b4a
5b5a
6b6a
7b7a
8b8a
9b9a
1b1a
1b1a
H L GND GND A B A B GND GND A B A B GND GND A B H L GND GND A B A B GND GND A B A B GND GND A B
1b、2b、3b: 4b、5b、6b: 7b、8b、9b: 10b、11b、12b: 13b、14b、15b: 16b、17b、18b: 1b、2b、3b: 4b、5b、6b: 7b、8b、9b: 10b、11b、12b: 13b、14b、15b: 16b、17b、18b:
Reserved CAN Data Forwarding Reserved RS485 Reserved RS485 Internal Communication Internal Communication Reserved CAN Data Forwarding Reserved RS485 Reserved RS485 Internal Communication Internal Communication
to Background RS485 RS485 to Background RS485 RS485
RS485 RS485
COM5 COM6 COM7 COM8 COM9 COM5 COM6 COM7 COM8 COM9
RD BK
20AWG 20AWG
B -W2 UL2661 20AWG×2C/2×0.519mm²/黑/双绞
UL2661 20AWG×2C/2×0.519mm²/black/twisted-pair cable
B
2x20AWG
6.5:C / XB13-17b/XSG-25
6.6:C / XB13-18b/XSG-26
C C
-W1
2x20AWG
BK 20AWG
RD 20AWG
UL2661 20AWG×2C/2×0.519mm²/黑/双绞
UL2661 20AWG×2C/2×0.519mm²/black/twisted-pair cable
D D
-XB12
-XB12
2b2a
3b3a
4b4a
2b2a
3b3a
4b4a
1b1a
1b1a
7 8
E E
NO COM NO COM NO COM NO COM
1b、2b: 3b、4b: 1b、2b: 3b、4b:
DO3 DO2 DO3 DO2
RMU Tripping RMU closing RMU Tripping RMU closing
operation operation operation operation
control control control control
69 078
BK BK
17AWG 17AWG
68 077
BK BK
17AWG 17AWG
F F
Checked by Maggie Date 2022/8/18 Drawing Name 逆变器N1和N2之间接线Wiring diagram of Inverter N1&N2
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
Terminal Terminal
排 排
=SG+-XK1 =SG+-XK3
A A
POS Ext Target Short Int Target POS POS Ext Target Short Int Target POS
放置 外部目标 短接 内部目标 放置 放置 外部目标 短接 内部目标 放置
049 105 102
1b1a -QF7:1 /9.6:F /12.2:B -PE5:J1-3 1b1a -QF17:1 /11.4:E
012 001
/7.3:D -SQ3:21 1d1c 1d1c -XSG:1 /6.2:B
024 004
/8.6:D -XT1:24 2b2a -J1:11 /7.1:C 2b2a
106
2d2c /12.6:B -PE6:J1-3 2d2c
059 107 103
B 3b3a -QF7:7 /9.6:F /12.2:B -PE5:J1-1 3b3a -QF17:3 /11.4:E B
014 002
/7.3:D -H4:N 3d3c 3d3c -XSG:2 /6.2:B
025 009
/8.6:D -XT1:25 4b4a -FA11:N BK /7.1:D 4b4a
108
4d4c /12.6:B -PE6:J1-1 4d4c
043
5b5a -T3:0V n /9.4:B
5d5c
C 6b6a C
104
/11.6:D -GND 6d6c
Terminal Terminal
排 排
D D
=SG+-XK2 =SG+-XK4
POS Ext Target Short Int Target POS POS Ext Target Short Int Target POS
放置 外部目标 短接 内部目标 放置 放置 外部目标 短接 内部目标 放置
1b1a /7.5:C -SW3:2 1b1a
111
/12.5:E -EDS-24V 1d1c 1d1c
109 113
/12.2:C -PE5:J2-1 2b2a /12.6:C -PE6:J2-1 2b2a
2d2c 2d2c
E E
3b3a /7.4:C -SW3:1 3b3a
112
/12.5:E -EDS-OV 3d3c 3d3c
110 114
/12.2:C -PE5:J2-4 4b4a /12.6:C -PE6:J2-4 4b4a
4d4c 4d4c
F F
Approved by Jochen Date 2022/8/18 Product Model A-SJ-02772 SG6250HV-MV-V1240 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
阳光电源股份有限公司
Sungrow Power Supply Co., Ltd.
B B
客户名称
Customer name
C 产品名称 户外型中压一体机 C
Product name Outdoor Inverter Of Medium Voltage
产品型号 SG6250HV-MV-V1240 Inverter
Product model
项目名称
D Project name D
电气标准 IEC/GB
Electrical standard
防护等级 IP65
Level of protection
主电路电压 3PH 600VAC
Main circuit voltage
E
辅助电源电压 400/230VAC E
AUX power voltage
控制电源电压 24VDC/200VDC
Control supply voltage
F F
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
目录Contents A-SJ-02772 SG6250HV-MV-V1240英文目录表格
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
l1
l2
l3
PE
S2 S1
-T1 1L1 2T1
I>>
I>
5 1 7 3
P2 P1 M 3L2 4T2
I>>
I>
6 2 8 4
3+PE
4turns
3
5L3 6T3
I>>
I>
A
B
电流互感器 磁环W523绕4匝
Current transformer Magnet ring W523
三相离心风机 旋转开关 配电三相变压器(单线图) 交流断路器
Three-phase centrifugal fan Rotary switch Three-phase transformer AC ACB
B B
P-D-000507
A a 1 5 8
1 2
630 PF 486 SF NET_A NET_B NET_C
L
13 23 B b 3 4 位号(XX)
600V PT
N 14 24 C c 功能单元(XXX)
5 6
0V PS 0V SS
7 8 系统单元(XXXX)
C C
A1 660V
A2 630V 486V P1
A3 600V 0V P2
A4 550V 600Vac/486Vac
0.15KVA
486V L1
B1 660V
0V L2
B2 630V
600Vac/486Vac
GND -GND2 B3 600V 0.15KVA
D B4 550V 400V a D
外壳地 C1 660V 400V b
常规接地
Functional ground Chassis ground C2 630V
C3 600V 400V c
C4 550V
0V n
600Vac/400Vac
5.7KVA
配电三相变压器
Three-phase transformer
E E
+ - S G
-GND
保护接地
Protective ground
电流传感器
Current sensor
LCD
+24V - FG COM1 RS232 COM2 RS485/422 ETHERNET USB-A
液晶屏
LCD screen
F F
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
LDE1
~ +
2 3 L BU BN N BK
1 4
M
LDE2 1~ ~ -
PE
C C
控制线圈 行程开关 电阻 熔断器 热敏电阻NTC
Control coil Limit switch IGBT Resistance Fuse Thermistor
3 2
D 3 D
L
E E
B F X
M
F F
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
B B
XB9:400V配电端子
XB9:400V Adaptor terminal
-T1
-QS25 -FU41,-FU42,-FU43 -KM20 -FU25,-FU26,-FU27
3 3
3
3 3
3
4
XB8:400V配电端子
6.8:C/600V配电输入 XB8:400V Adaptor terminal
3+PE
600V AC input 690V/50A
熔丝Fuse:690V/20A
690V/25A
熔丝Fuse:690V/20A
底座Holder:1000VAC/20A IEC 底座Holder:1000VAC/20A IEC
600Vac/400Vac/5.70KVA
600Vac/486Vac/0.15KVA -FU40
600Vac/486Vac/0.15KVA 至开关电源板PE2
1
2
C To switch power supply PE2 C
熔丝Fuse:1000V/8A
底座Holder:1000VAC/20A IEC
-FU101
至开关电源板PE1
1
2
To switch power supply PE1
熔丝Fuse:1000V/8A
底座Holder:1000VAC/20A IEC
D D
-FU39 -T4
至开关电源板PE
1
2 2 2
2+PE
熔丝Fuse:1000V/1A
底座Holder:1000VAC/20A IEC
600Vac/486Vac/150VA
E E
F F
Checked by taonl Date 2022/7/29 Drawing Name (N1.N2)配电单线图(N1.N2)Distribution single line diagram
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
-储能接口1
Energy storage interface 1 熔丝Fuse:600V/4A或1000V/8A
整流桥 300W/10Ω 690V/25A 底座Holder:与熔丝品牌相同
Rectifier
-TA1
+ - S G 2
2
-DC_IN1 -FU1 2
2
500A/4V
1500V/315A 2
-TA2
+ - S G 2
2 -QF1
B -TA29 -N1 model -T30,-TA31,-TA32 -TA36,-TA38 B
-DC_IN2 -FU2 -QS1 -L1
500A/4V + - S G + - S G S2 S1
1500V/315A 2 3
3
I>>
I>
P2 P1
3 3
-TA9 001
2
3 3
2 1500V/2500A 2000A/4V 2000A/4V 70uH/1654A 690V/2000A 2000A/0.4A
+ - S G 2 Pac=1562.5kW
2 Umppt:DC 875-1300V
Uo:AC 600V
-DC_IN9 -FU9 Io:AC 1503A
3
500A/4V
1500V/315A DC Input:12-14路 -C1,-C2,-C3,-C4
-FU29,-FU30 2 850VAC/3*55.8uF
C 熔断器Fuse:1500V/20A 600V配电输出 / 5.1:C C
底座Holder:1500V/63A
600V AC power output
2 3
SPD1
-GND -L1/-L2/-L3
-D2
-R12,-R16 -KM11 -FU94,-FU95
D 2 3 -FU96,-FU97,-FU98 D
-储能接口2 2
Energy storage interface 2 熔断器Fuse:1000V/40A
底座Holder:1000V/40A
熔丝Fuse:600V/4A或1000V/8A
-TA41 整流桥 300W/10Ω 690V/25A 底座Holder:与熔丝品牌相同
+ - S G 2
Rectifier
2
-DC_IN1 -FU61
500A/4V 2 -SPD3 3
1500V/315A 2 3
-TA42 2
+ - S G 2
2
-TA69 -QF2
-N2 model -TA71,-TA72,-TA73 -TA76,-TA78
-DC_IN2 -FU62 -QS3 -L2
E 500A/4V + - S G + - S G S2 S1 E
1500V/315A 2 3
3
I>>
-GND
I>
P2 P1
3 3
-TA49 3 3
2 2 1500V/2500A 2000A/4V 2000A/4V 70uH/1654A 690V/2000A 2000A/0.4A
+ - S G 2 Pac=1562.5kW
2 Umppt:DC 875-1300V
Uo:AC 600V
-DC_IN9 -FU69 Io:AC 1503A
500A/4V
1500V/315A DC Input:12-14路 -C5,-C6,-C7,-C8
-FU81,-FU82 2
熔断器Fuse:1500V/20A 850VAC/3*55.8uF
底座Holder:1500V/63A
F 2 F
SPD2 ★备注Notice:
SLD MLD Drawn by xuwt Date 2022/7/29 Drawing NO. A-SJ-02772-JL-A Page 6 of 38
-GND SPD1 PN1 or FL2 (N1.N2)主电路单线图(N1.N2)Main circuit single line
Checked by taonl Date 2022/7/29 Drawing Name
SPD2 PN2 or FL3 diagram
SPD3 PN or FL1 Approved by zhangjin Date 2022/7/29 Product Model A-SJ-02772 SG6250HV-MV-V1240 Inverter(A-ST-03703)
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
L1 Copper bar
L1汇总铜条
L2 Copper bar
L2汇总铜条
A A
L3 Copper bar
L3汇总铜条
L1 L2 L3 L1 L2 L3 020 021 022
AC AC AC AC AC AC
-逆变器N1 -逆变器N2 BK BK BK
3 3 11AWG 11AWG 11AWG
L/N L/N L/N L/N
Inverter N1 Inverter N2
- + - +
B B
NC COM NC COM NC COM NC COM
2 2 2
PN
5AWG 5AWG 5AWG
C C
018
GNYE
5AWG L3
J1
接FU96-1
交直流输入 AC & DC input
J2 DC-/L1
接FU97-1
12 11 12 11 12 11 12 11
011 014 017
BK BK BK -GND2 J3 DC+/L2
接FU98-1
19AWG 19AWG 19AWG
004 019
BK BK
19AWG 19AWG
D D
J4 GROUND
接GND2
9.1:A / L1/QS25:A
9.1:A / L2/QS25:B
9.1:A / L3/QS25:C
18.3:E / FL1-12/PD1-J5-8
18.3:E / FL1-11/PD1-J5-7
RAC
接PD1-J5-8
就近接地 RDC
-GND2 -W1 J5
4x24AWG
006 RD 24AWG
-TA28 + TA28+/PL1-J2-1/19.2:E
007 BN 24AWG
10A/10V - TA28-/PL1-J2-5/19.2:E
E S 008 BK 24AWG
TA28S/PL1-J2-9/19.2:D SGND E
接PD1-J5-7
009 OG 24AWG
G
003
TA28G/PL1-J2-3/19.2:E 1
shade BK
19AWG
TA28屏蔽层/PL1-J2-8/19.2:D 板载防雷器接线图
Board SPD attachment figure
002
BK
5AWG 1#DC柜(FUSE侧)等电位连接铜排(使用绝缘子安装) AC柜 等电位连接铜排(使用绝缘子安装) 2#DC柜(FUSE侧)等电位连接铜排(使用绝缘子安装)
1#DC cabinet (FUSE side)Equipotential connection copper bar AC Equipotential connection copper bar 2#DC cabinet (FUSE side)Equipotential connection copper bar
GND GND GND GND
GND 023 032
BK 黄绿
5AWG 5AWG
F F
Checked by taonl Date 2022/7/29 Drawing Name (N1.N2)交流侧电气图 Ac side electrical diagram
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
-PI1 GND 4
212 BK 19AWG
PI1-J1-4/PA1-J12-14/14.7:D -PI2 GND 4
212 BK 19AWG
PI2-J1-4/PA2-J12-14/23.7:D
P-C-000319 P-C-000319
PI1
sensor board
sensor board
PI2
传感器板
传感器板
212 BK 19AWG 212 BK 19AWG
M 3 PI1-J1-3/PA1-J12-16/14.7:C M 3 PI2-J1-3/PA2-J12-16/23.7:D
J1 J1
A 212 BK 19AWG 212 BK 19AWG A
-VCC 2 PI1-J1-2/PA1-J12-18/14.7:C -VCC 2 PI2-J1-2/PA2-J12-18/23.7:C
212 BK 19AWG 212 BK 19AWG
+VCC 1 PI1-J1-1/PA1-J12-20/14.7:C +VCC 1 PI2-J1-1/PA2-J12-20/23.7:C
替代:新PB电路板接线(J1和J2端子接线方式有变)
-PB1 4 -PB2 4
/8.2:D /8.5:D
P-E-000553 P-E-000553
PV+ 3 穿过P-C-000319漏电流传感器 PV+ 3
J2 J2 穿过P-C-000319漏电流传感器
2021/02/07 2 (安装方向箭头指向直流侧负极) 2021/02/07 2 (安装方向箭头指向直流侧负极)
188 BK 19AWG 188 BK 19AWG
PV- 1 PB1-J2-1/N1-DC-/12.5:C PV- 1 PB2-J2-1/N2-DC-/21.5:B
B B
562 BK 19AWG 562 BK 19AWG
EN 6 PB1-J4-6/PG1-J2-11/14.2:E EN 6 PB2-J4-6/PG2-J2-11/23.2:E
PID power supply board
直流PID电源板
PB1
563 BK 19AWG 563 BK 19AWG
J4
REPAIR 4
GND 3
563 BK 19AWG
PB1-J4-4/PG1-J2-8/14.2:D
PB1-J4-3/PG1-J2-7/14.2:D PB2 J4
REPAIR 4
GND 3
563 BK 19AWG
PB2-J4-4/PG2-J2-8/23.2:D
PB2-J4-3/PG2-J2-7/23.2:D
2 2
GND 1 GND 1
C 4 4 C
082 BK 19AWG 076 BK 19AWG
AC 3 PB1-J1-3/XB8:6a/9.7:D AC 3 PB2-J1-3/XB8:6b/9.7:E
J1 J1
2 2
082 BK 19AWG 081 BK 19AWG
AC 1 PB1-J1-1/XB8:9a/9.8:D AC 1 PB2-J1-1/XB8:9b/9.8:E
-PB1 4
188 BK 19AWG
PB1-J2-4/N1-DC-/ -PB2 4
188 BK 19AWG
PB2-J2-4/N2-DC-/
PV- PV-
/8.2:A /8.5:A
D P-E-000553 P-E-000553 D
3 3
J2 穿过P-C-000319漏电流传感器 J2 穿过P-C-000319漏电流传感器
2020/08/22 2 2020/08/22 2 (安装方向箭头指向直流侧负极)
PV+ (安装方向箭头指向直流侧负极) PV+
1 1
562 BK 19AWG 562 BK 19AWG
EN 6 PB1-J4-6/PG1-J2-11/ EN 6 PB2-J4-6/PG2-J2-11/
PID power supply board
直流PID电源板
PB1 J4
REPAIR 4
GND 3
563 BK 19AWG
563 BK 19AWG
PB1-J4-4/PG1-J2-8/
PB1-J4-3/PG1-J2-7/
PB2 J4
REPAIR 4
GND 3
563 BK 19AWG
563 BK 19AWG
PB2-J4-4/PG2-J2-8/
PB2-J4-3/PG2-J2-7/
E E
2 2
GND 1 GND 1
082 BK 19AWG 076 BK 19AWG
AC 4 PB1-J1-4/XB8:6a/ AC 4 PB2-J1-4/XB8:6b/
3 3
J1 J1
082 BK 19AWG 081 BK 19AWG
AC 2 PB1-J1-2/XB8:9a/ AC 2 PB2-J1-2/XB8:9b/
1 1
F F
★通过电路板日期丝印,确定新旧板 Drawn by xuwt Date 2022/7/29 Drawing NO. A-SJ-02772-JL-A Page 8 of 38
Checked by taonl Date 2022/7/29 Drawing Name (N1.N2)直流PID电气图 Dc side PID electrical diagram
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
QS25:A/L1 / 7.3:D
QS25:B/L2 / 7.3:D
QS25:C/L3 / 7.4:D
Confidential
熔丝Fuse:1000V/1A
-T4
底座Holder:1000VAC/20A IEC 630 PF 486 SF 089 BK 17AWG
T4-486V/PE-J7-1/30.2:E
-FU39 082
A 2 1
BK
600V PT
A
17AWG
0V PS 0V SS 090 BK 17AWG
073
T4-0V/PE-J7-3/30.2:E
BK 074 600Vac/486Vac/150VA
A B C N 17AWG BK
17AWG
-GND2
-QS25
690V/50A
a b c n
600Vac/400Vac/5.70KVA
600Vac/486Vac/0.15KVA
-T1 600Vac/486Vac/0.15KVA
A1 660V 052
BK
-FU101 熔丝Fuse:1000V/8A
A2 630V 486V P1 1 2 底座Holder:1000VAC/20A IEC
B 17AWG 062 BK 17AWG
FU101-2/PE1-J7-1/15.3:E B
A3 600V 0V P2 053 BK 17AWG
熔丝Fuse:690V/20A 690VAC/25A 600Vac/486Vac
T1-P2/PE1-J7-3/15.3:E
底座Holder:1000VAC/20A IEC A4 550V
0.15KVA 091 -FU40 熔丝Fuse:1000V/8A
060
BK -FU41
076
BK
-KM20 083
BK 486V L1
BK
1 2 底座Holder:1000VAC/20A IEC
17AWG 099 BK 17AWG
11AWG 2 1 11AWG 1 2 11AWG B1 660V
0V L2
FU40:2/PE2-J7-1/24.3:E
092 BK 17AWG
063
BK -FU421
077
BK
084
BK
B2 630V
600Vac/486Vac
T1-L2/PE2-J7-3/24.3:D
2 3 4 B3 600V 0.15KVA 093
11AWG 11AWG 11AWG
BK -FU25 熔丝Fuse:690V/20A
064 078 086 B4 550V 400V a 1 2 底座Holder:1000VAC/20A IEC
BK -FU43 BK BK
11AWG 101 BK 13AWG
FU25:2/XB9:1a/10.1:D
2 1 5 6 094
11AWG 11AWG 11AWG
BK -FU26
C1 660V 400V b 11AWG 1 2 103 BK 13AWG
FU26:2/XB9:3a/10.2:D
C2 630V 095
BK -FU27
C3 600V 400V c 11AWG 1 2 105 BK 13AWG
C +A1 -A2 /31.6:D FU27:2/XB9:5a/10.2:D C
059 062 065 C4 550V
BK BK BK 1 2 /9.3:B
19AWG 19AWG 19AWG 0V n 096 098 BK 13AWG
3 4 /9.3:C
600Vac/400Vac
GNYE T1:n/XB9:7a/10.3:D
5 6 /9.3:C 15AWG
5.7KVA
100 102 104 097
BK BK BK BK
13AWG 13AWG 13AWG 13AWG
XB8:6a/PB1-J1-3 /8.3:C
XB8:8a/QS1-M:31/17.1:E
-GND2
XB8:9a/PB1-J1-1 /8.3:C
变压器N线保护接地,
XB8:1c/KM17:1 / 10.1:A
XB8:3c/KM17:3 / 10.1:A
XB8:6c/KM17:5 / 10.1:A
/ 10.1:B
-GND 有两处位置可供选择,
XB8:4c/KM6-1/17.4:B
067
以工艺实际操作为准。
066
旧板接PB1-J1-4
旧板接PB1-J1-2
BK
BK
19AWG
19AWG
XB8:7c/FA3:N
071
070
BK
BK
19AWG 080
19AWG 079
BK
BK
D 600V转接端子 19AWG
19AWG D
600V terminal blocks
-PD1 -PG1
1 5 8 1 7 1 7
1b1a
1d1c
2b2a
3b3a
3d3c
4b4a
5b5a
5d5c
6b6a
1b1a
1d1c
2b2a
2d2c
3b3a
3d3c
4b4a
4d4c
5b5a
5d5c
6b6a
6d6c
7b7a
7d7c
8b8a
8d8c
9b9a
9d9c
AC voltage sampling AC voltage sampling -XB8 L1 L2 L3 N
9.2:F / XB3:1b/PG2-J34-7
9.3:F/ XB3:2b/PD2-J6-1
9.3:F/ XB3:3b/PG2-J4-1
9.4:F/ XB3:4b/PD2-J6-5
9.3:F/ XB3:5b/PG2-J4-7
9.4:F/ XB3:6b/PD2-J6-8
DSP转接板 计量板
DSP adaptor board 109 110 112 113 115 116 054 118 121 055
Measuring Board BK BK BK BK BK BK BK BK BK BK
PG2-J34-7/XB3:1b/9.1:E
PG2-J4-7/XB3:5b /9.2:E
XB3:2b/PD2-J6-1 /9.1:E
XB3:4b/PD2-J6-5 /9.2:E
XB3:6b/PD2-J6-8 /9.2:E
17AWG 17AWG
E E
旧板接PB2-J1-4
旧板接PB2-J1-2
10.7:D/ XB8:1d/MF2-L1
10.6:D/ XB8:2d/MF1-L1
10.7:D/ XB8:3d/MF2-L2
10.6:D/ XB8:4d/MF1-L2
10.7:D/ XB8:5d/MF2-L3
10.6:D/ XB8:6d/MF1-L3
17.1:B / XB8:4b/QS1-M:30
17.4:E / XB8:7d/QF1-X:38
8.7:C / XB8:6b/PB2-J1-3
8.7:C / XB8:9b/PB2-J1-1
-PG2 -PD2
/23.1:C 1 7 1 7 /23.3:D 1 5 8
/29.5:B B A N C /25.5:A NET_A NET_B NET_C
F P-A-001084 /27.1:C F
/27.5:C
J34 J4 J6
P-D-000507
电网电压采样 电网电压采样 Drawn by xuwt Date 2022/7/29 Drawing NO. A-SJ-02772-JL-A Page 9 of 38
AC voltage sampling AC voltage sampling
Checked by taonl Date 2022/7/29 Drawing Name (N1.N2)供电图(N1.N2) Power supply diagram
计量板 DSP转接板
Measuring Board DSP adaptor board Approved by zhangjin Date 2022/7/29 Product Model A-SJ-02772 SG6250HV-MV-V1240 Inverter(A-ST-03703)
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
143 Confidential
BK
126 BK 17AWG 17AWG
-KM17 136
BK
1 2 125 BK 17AWG 17AWG
9.5:D / KM17:1/XB8:1c
A 3 4
A
127 BK 17AWG
9.6:D / KM17:3/XB8:3c
151
BK
5 6 128 BK 17AWG 17AWG
9.7:D / KM17:5/XB8:6c
160
690VAC/25A BK
129 BK 17AWG 17AWG
144
BK
120 BK 17AWG 19AWG
140
BK
119 BK 17AWG 19AWG
9.7:D / FA3:N/XB8:7c
135 BK 17AWG
10.3:E / FA9:N/XB9:8b
B 155
BK
B
137 BK 17AWG 19AWG
10.4:D / FA5:N/XB9:8c
161
BK
A1 A2 /16.7:E 138 BK 17AWG 19AWG
1 2 /10.2:A ★无外置电容风扇接线: 有外置电容风扇接线: C83 C84 C85 C86 C87 C88 C89 C90 C91
3 4 /10.2:A Cx
L BU N BK
5 6 /10.2:A L BU BN N BK L BU BN N BK L BU BN N BK L BU BN N BK L BU BN N BK L BU BN N BK L BU BN N BK L BU BN N BK L BU BN N BK
M L BU BN N BK
M M M M M M M M M
1~ M -FA1 -FA2 -FA3 -FA4 -FA9 -FA5 -FA6 -FA7 -FA8
1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~
PE GYNE 1~ PE GNYE PE GNYE PE GNYE PE GNYE PE GNYE PE GNYE PE GNYE PE GNYE PE GNYE
230VAC 230VAC 230VAC 230VAC 230VAC 230VAC 230VAC 230VAC 230VAC
PE GYNE 轴流风机 141 轴流风机 142 轴流风机 145 轴流风机 146 轴流风机 148 轴流风机 157 轴流风机 159 轴流风机 162 轴流风机 164
XB9:1a/FU25:2 /9.8:C
XB9:3a/FU26:2 /9.8:C
XB9:5a/FU27:2 /9.8:C
C Axial floe fan GNYE Axial floe fan GNYE Axial floe fan GNYE Axial floe fan GNYE Axial floe fan GNYE Axial floe fan GNYE Axial floe fan GNYE Axial floe fan GNYE Axial floe fan GNYE C
XB9:7a/T1:n / 9.8:C
15AWG 15AWG 15AWG 15AWG 15AWG 15AWG 15AWG 15AWG 15AWG
XB9:8a/QS3-M:31/26.1:E
Internal spoiler
/ 10.1:B
MF3-L1/XB9:2d /10.1:E
MF3-L2/XB9:4d /10.2:E
MF3-L3/XB9:6d /10.3:E
MF1-L1/XB8:2d /9.6:E
MF1-L2/XB8:4d /9.6:E
MF1-L3/XB8:6d /9.7:E
MF2-L1/XB8:1d /9.5:E
MF2-L2/XB8:3d /9.6:E
MF2-L3/XB8:5d /9.7:E
XB9:8c/FA5:N
D D
147
158 163
GNYE
GNYE GNYE
101 103 105 098 134 15AWG
110 115 118 109 112 116 15AWG 123 131 132 15AWG
BK BK BK BK BK BK BK BK BK BK BK BK BK BK
13AWG 13AWG 13AWG 13AWG 19AWG 15AWG 15AWG 15AWG 15AWG 15AWG 15AWG 15AWG 15AWG 15AWG
-GND2 -GND2 -GND2
-MF1 就近外壳接地 -MF2 就近外壳接地 -MF3 就近外壳接地
L1
L2
L3
PE
L1
L2
L3
PE
L1
L2
L3
PE
1b1a
1d1c
2b2a
2d2c
3b3a
3d3c
4b4a
4d4c
5b5a
5d5c
6b6a
6d6c
7b7a
7d7c
8b8a
8d8c
9b9a
9d9c
K3G250-PR17-W9产品自带线:
-XB9 L1 L2 L3 N
L1
L2
L3
PE
A
B
黄绿线(GNYE)
E M M M E
黑色线(BK)
黑色线(BK)
黑色线(BK)
白色线(WH)
棕色线(BN)
123 124 130 131 132 133 135 139
BK
15AWG
BK
19AWG
BK
17AWG
BK
15AWG
BK
15AWG
BK
17AWG
BK
17AWG
BK
15AWG
3 400VAC 3 400VAC 3 400VAC
离心风机 离心风机 离心风机
Centrifugal fan Centrifugal fan Centrifugal fan
B
-W2 RD BK -W3 RD BK -W4 RD BK
2x20AWG 20AWG 20AWG 2x20AWG 20AWG 20AWG 2x20AWG 20AWG 20AWG
26.3:B / XB9:4b/KM9-1
26.1:B/ XB9:3d/QS3-M:30
26.4:E/ XB9:7d/QF2-X:38
10.8:D / XB9:2d/MF3-L1
10.8:D / XB9:4d/MF3-L2
10.8:D / XB9:6d/MF3-L3
Checked by taonl Date 2022/7/29 Drawing Name (N1.N2)风扇(N1.N2) Fan supply diagram
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
-DC+:1 -DC+:2 -DC+:3 -DC+:4 -DC+:5 -DC+:6 -DC+:7 -DC+:8 -DC+:9
500A/4V
-TA1 500A/4V
-TA2 500A/4V
-TA3 500A/4V
-TA4 500A/4V
-TA5 500A/4V
-TA6 500A/4V
-TA7 500A/4V
-TA8 500A/4V
-TA9
+ + + + + + + + +
- - - - - - - - -
A A
S S S S S S S S S
G G G G G G G G G
RD 24AWG
BN 24AWG
BK 24AWG
OG 24AWG
-W5
4x24AWG
19.3:B / PL1-J2-23
19.3:B / PL1-J2-24
19.3:B / PL1-J2-21
19.3:B / PL1-J2-22
19.3:B / PL1-J2-19
19.3:B / PL1-J2-20
19.2:B / PL1-J2-17
19.2:B / PL1-J2-18
19.2:B / PL1-J2-15
19.4:E/XB20:1a
19.6:E/XB20:3a
19.7:E/XB20:5a
19.5:E/XB20:1a
19.6:E/XB20:3a
19.7:E/XB20:5a
19.5:E/XB20:1a
19.6:E/XB20:3a
19.7:E/XB20:5a
19.5:E/XB20:1a
19.6:E/XB20:3a
19.7:E/XB20:5a
19.5:E/XB20:1b
19.6:E/XB20:3b
19.7:E/XB20:5b
19.5:E/XB20:1b
19.6:E/XB20:3b
19.7:E/XB20:5b
19.5:E/XB20:1b
19.6:E/XB20:3b
19.7:E/XB20:5b
19.5:E/XB20:1b
19.6:E/XB20:3b
19.8:E/XB20:5b
19.5:E/XB20:2a
19.6:E/XB20:4a
19.8:E/XB20:6a
B 1 1 1 1 1 1 1 1 1 B
-FU1 1500V/315A -FU2 1500V/315A -FU3 1500V/315A -FU4 1500V/315A -FU5 1500V/315A -FU6 1500V/315A -FU7 1500V/315A -FU8 1500V/315A -FU9 1500V/315A
2 2 2 2 2 2 2 2 2
N1-DC+/12.1:A
N1-DC-/12.1:A
2 2 2 2 2 2 2 2 2
-FU10 1500V/315A -FU11 1500V/315A -FU12 1500V/315A -FU13 1500V/315A -FU14 1500V/315A -FU15 1500V/315A -FU16 1500V/315A -FU17 1500V/315A -FU18 1500V/315A
1 1 1 1 1 1 1 1 1
500A/4V
-TA41 500A/4V
-TA42 500A/4V
-TA43 500A/4V
-TA44 500A/4V
-TA45 500A/4V
-TA46 500A/4V
-TA47 500A/4V
-TA48 500A/4V
-TA49
+ + + + + + + + +
- - - - - - - - -
S S S S S S S S S
G G G G G G G G G
D D
RD 24AWG
BN 24AWG
BK 24AWG
OG 24AWG
-W17
4x24AWG
28.3:B / PL2-J2-23
28.3:B / PL2-J2-24
28.3:B / PL2-J2-21
28.3:B / PL2-J2-22
28.3:B / PL2-J2-19
28.3:B / PL2-J2-20
28.3:B / PL2-J2-17
28.3:B / PL2-J2-18
28.2:B / PL2-J2-15
28.5:E / XB40:1c
28.6:E / XB40:3c
28.7:E / XB40:5c
28.5:E / XB40:1c
28.6:E / XB40:3c
28.7:E / XB40:5c
28.5:E / XB40:1c
28.6:E / XB40:3c
28.7:E / XB40:5c
28.5:E / XB40:1c
28.6:E / XB40:3c
28.7:E / XB40:5c
28.5:E / XB40:1d
28.6:E / XB40:3d
28.7:E / XB40:5d
28.5:E / XB40:1d
28.6:E / XB40:3d
28.7:E / XB40:5d
28.5:E / XB40:1d
28.6:E / XB40:3d
28.8:E / XB40:5d
28.5:E / XB40:1d
28.6:E / XB40:3d
28.8:E / XB40:5d
28.5:E / XB40:2c
28.7:E / XB40:4c
28.8:E / XB40:6c
1 1 1 1 1 1 1 1 1
-FU61 1500V/315A -FU62 1500V/315A -FU63 1500V/315A -FU64 1500V/315A -FU65 1500V/315A -FU66 1500V/315A -FU67 1500V/315A -FU68 1500V/315A -FU69 1500V/315A
2 2 2 2 2 2 2 2 2
E E
N2-DC+/21.1:A
N2-DC-/21.1:A
2 2 2 2 2 2 2 2 2
-FU70 1500V/315A -FU71 1500V/315A -FU72 1500V/315A -FU73 1500V/315A -FU74 1500V/315A -FU75 1500V/315A -FU76 1500V/315A -FU77 1500V/315A -FU78 1500V/315A
1 1 1 1 1 1 1 1 1
F F
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
-MODEL 1#
-QS1
1 2 -N1:DC+
A N1-DC+ 1 U1 /13.1:A A
3 4
11.7:B / N1-DC+ -TA29
5 6
2000A/4V -C11 -C26
11.7:B / N1-DC- G OG 24AWG
TA29G/PA1-J12-13/14.7:E 750uF/800VDC 750uF/800VDC
BK 24AWG
7 8
S TA29S/PA1-J12-15/14.7:D
BN 24AWG -N1:N
- TA29-/PA1-J12-17/14.7:D 2 V1 /13.1:B
1500V/2500A RD 24AWG N1-NEUTRAL
213
BK
215
BK
+ TA29+/PA1-J12-19/14.7:D
5AWG 5AWG
-W29
4x24AWG -C27 -C42
750uF/800VDC 750uF/800VDC
1 1
B -N1:DC- B
N1-DC- 3 W1 /13.1:C
-FU29 -FU30
QS2:2+/QS3:1 /21.3:C
QS2:2-/QS3:5 /21.3:C
熔断器Fuse:1500V/20A 188
底座Holder:1500V/63A 2 2 BK
19AWG Pac=1562.5kW
214 216 Umppt:DC 875-1300V
BK BK Uo:AC 600V
5AWG 5AWG Io:AC 1503A
DC Input:12-14路
储能1:(+)
储能1:(-)
FL2 +/- -/+
BAT1+
BAT1-
236 237 -PM1
8.3:B / PB1-J2-1/N1-DC-
BK BK
旧板接PB1-J2-4
218 BK 19AWG 11AWG 11AWG
11
FL2-11/PL1-J12-2/18.3:A
219 BK 19AWG 224 226
C 12 BK BK
230 232
PM1 C
FL2-12/PL1-J12-1/18.3:A 19AWG 19AWG
BK
19AWG
BK
19AWG
14
1+ 1- 2+ 2-
3+
3-
PE PE -QS2 MZ1 MZ2 MZ3
1500V/16A 1+
3+
3-
1- 2+ 2-
225 227 231 233
PM2
BK BK BK BK
217 19AWG 19AWG 19AWG 19AWG
黄绿
5AWG 单元1模组
Unit 1 module
19.2:E / QS2-1-/PL1-J11-6
28.2:F / QS2-2+/PL2-J11-1
28.2:E / QS2-2-/PL2-J11-6
D 35
D
F 36 开关分闸
Open coil
33
F 34 开关分闸
Open coil
14.1:A/ N1-DC+
14.1:A/ N1-DC-
N1 slow start of SVG
N1-N
Rectifier
13NO 14NO
21NC 22NC
14.1:A /
+A1 -A2 /16.6:E
F 1 2 /12.3:E F
3 4 /12.3:E
Drawn by xuwt Date 2022/7/29 Drawing NO. A-SJ-02772-JL-A Page 12 of 38
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
-W30
4x24AWG
RD24AWG
A TA30+/PA1-J12-11/14.7:E TA36-S2/PG1-J40-1/14.2:F QF1:2/FU47:1/12.1:E A
BN24AWG
TA30-/PA1-J12-9/14.7:E TA36-S1/PG1-J40-2/14.2:F
BK24AWG -L1-R /18.7:D 276 278 QF1:4/FU48:1/12.1:E
TA30S/PA1-J12-3/14.7:F BK BK
OG24AWG
TA30G/PA1-J12-1/14.7:F 1 2 19AWG 19AWG
TA31+/PA1-J12-11/14.7:E -QF1
TA31-/PA1-J12-9/14.7:E
TA31S/PA1-J12-5/14.7:E
TA31G/PA1-J12-1/14.7:F A
-L1 a 1L1 2T1
L1 Copper bar
B B
I>>
I>
-TA31
L1铜条
+ - S G L2 Copper bar
2000A/4V B b 3L2 4T2
12.8:B / V1
I>>
I>
L2铜条
L3 Copper bar
C c 5L3 6T3
I>>
I>
TA32+/PA1-J12-19/14.7:D TA38-S2/PG1-J40-5/14.2:E
L3铜条
TA32-/PA1-J12-17/14.7:D 70uH/1654A
690V/2000A TA38-S1/PG1-J40-6/14.2:E Grounding copper bar
277 279
TA32S/PA1-J12-7/14.7:E -QF1:R /17.7:C
接地铜条
BK BK
TA32G/PA1-J12-13/14.7:D 19AWG 19AWG
1 2 控制器单元
-TA32 -TA38 Controller unit
+ - S G S2 S1
2000A/4V 2000A/0.4A
12.8:B / W1 P2 P1 -QF1:M /17.6:C -QF1:M-CW1 /17.6:D
30
C SA M 31 储能控制 33
SA M 34 储能控制 C
272 273 274
Energy storage Energy storage
BK BK BK
1AWG 1AWG 1AWG -QF1:Q /17.6:C -QF1:Q-CW1 /17.6:D
PN1 33
Q 34 欠压断开
Under voltage trip
27
Q 28 欠压断开
Under voltage trip
-QF1:F /17.5:C -QF1:F-CW1 /17.5:D
N1-copper-bar-A 7 6 5 4 3 2 1
35
F 36 电动断开 29
F 30 电动断开
Open coil Open coil
J1 L3
N1-copper-bar-B 7 6 5 4 3 2 1 -QF1:X /17.4:C -QF1:X-CW1 /17.4:D
37
X 38 电动闭合 31
X 32 电动闭合
接FU30-2
47 48 辅助触点 42 43 辅助触点
AUX node AUX node
J3 DC+/L2 -QF1:NO1 /18.3:D -QF1:NO1-CW1 /18.3:C 280
接FU29-2
250 251 254 259 262 263 264 265 266 267 268 269 270 271 275 BK
BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK 49 50 辅助触点 37 38 辅助触点 5AWG
7AWG 7AWG 7AWG 7AWG 7AWG 7AWG 7AWG 7AWG 7AWG 7AWG 7AWG 7AWG 19AWG 19AWG 19AWG
AUX node AUX node
J4 GROUND -QF1:NC2
GND1
接GND2
51 52 辅助触点
AUX node
+/- -/+ 4 -QF1:NO2
RAC
14.5:E / N1bar-B3/PD1-J3-5
14.5:D / N1bar-C3/PD1-J3-8
接PL1-J12-2
850VAC/3*55.8uF 850VAC/3*55.8uF 850VAC/3*55.8uF 850VAC/3*55.8uF NC J5 55 56 辅助触点
AUX node
NO
-QF1:NO3
57 58 辅助触点
SGND
PE PE AUX node
接PL1-J12-1
1
PTG 防雷接线图 板载防雷器接线图 NDW1框架接线图 CW1 框架接线图
PTG SPD attachment figure Board SPD attachment figure NDW1 ACB attachment figure CW1 ACB attachment figure
F F
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
12.6:E / N1-DC+
A 12.6:E / N1-N A
12.6:E / N1-DC-
PX1
15.3:F / N1-DC+/PE1-J2-1
15.3:E / N1-DC-/PE1-J4-1
30.2:F / N1-DC+/PE-J2-1
30.2:F / N1-DC-/PE-J4-1
B B
-PX1 2
P-N-001014
直流电压 DC voltage
2
J1 1500V+ 240 BK 17AWG
PG1 J2
1
2
244 BK 17AWG
1500V_M
-PG1 RD -LB1 1
C 4 20AWG C
24V power supply
PA1
BK 026 24AWG
20AWG PA1-J12-20/PI1-J1-1/8.3:A
+24VGND PG1-J46-1/XB10:7a/30.8:D 025 24AWG
PA1-J12-18/PI1-J1-2/8.3:A
1 024 24AWG
PA1-J12-16/PI1-J1-3/8.3:A
1 -W33
4turns
023 24AWG
COM4
2x20AWG PA1-J12-14/PI1-J1-4/8.3:A
-PA1
NO4 /20.1:B 19 20 4turns
P-A-000776 +15VA +15VA
NC4
DO输出口 DO output node
253 24AWG
PA1-J12-19/TA32+/13.2:B
COM3 304 24AWG
PA1-J12-19/TA29+/12.5:B
PD1
D -15VA -15VA D
NO3 256 24AWG
PA1-J12-17/TA32-/13.2:B
303 24AWG
NC3 PA1-J12-17/TA29-/12.5:B
J2 030 BK 19AWG I-DC I-LEAK
COM2 PG1-J2-7/PB1-J4-3/8.3:C
BK
/9.3:D
8 19AWG AGND AGND
PD1-J3-8/N1bar-C3/13.3:E
301 24AWG
COM1 PG1-J2-10/PB1-J4-5/8.3:B /18.2:C PA1-J12-13/TA29G/12.5:A
逆变电压采样
BK
/18.5:C 19AWG +15VA +15VA
NO1
027 BK 19AWG
PG1-J2-11/PB1-J4-6/8.3:B INV_B PD1-J3-5/N1bar-B3/13.3:E 335 24AWG
PA1-J12-11/TA30+/13.2:A
DSP转接板 DSP adapter board
P-D-000507 J3 J12
252 24AWG
NC1 270
BK
PA1-J12-11/TA31+/13.2:B
-15VA -15VA
12 19AWG 338 24AWG
PA1-J12-9/TA30-/13.2:A
INV_A PD1-J3-1/N1bar-A3/13.3:E
E 6 1 281 255 24AWG E
PA1-J12-9/TA31-/13.2:B
AC current sampling
279 BK 19AWG BK
IC2 PG1-J40-6/TA38-S1/13.5:B 10 19AWG I-C1 I-C2
277 BK 19AWG FUSE_GND
PG1-J40-5/TA38-S2/13.5:B
DC voltage sampling
IC1 246
BK -GND2 258 24AWG
PA1-J12-7/TA32S/13.2:C
IB2 19AWG I-B1 I-B2
J40 J2 BUS-
电流采样
直流电压采样
IB1 243
BK 中性线:两根线并行走线 257 24AWG
278 BK 19AWG Neutral line:Two wires in parallel PA1-J12-5/TA31S/13.2:B
IA2 PG1-J40-2/TA36-S1/13.5:A BUS_N
19AWG*2
I-A1 I-A2
276 BK 19AWG 239
IA1 PG1-J40-1/TA36-S2/13.5:A BK
341 24AWG
1 BUS+
19AWG PA1-J12-3/TA30S/13.2:A
AGND AGND
DC voltage sampling
J12 1 2
F 238 BK 19AWG F
PV+
1 Drawn by xuwt Date 2022/7/29 Drawing NO. A-SJ-02772-JL-A Page 14 of 38
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
287
-LB2 BK
15AWG
15.2:D/XB1:5a/PE1-J6-3
磁环靠近电路板安装
289
BK
15AWG
15.2:D/XB1:1a/PE1-J6-1
4turns
B B
LVRT电源盒
PE1 LVRT power supply
XB1:1c/PD1-J17-2 /18.7:F
XB1:2a/PD1-J1-13 /16.7:B
XB1:2c/PD1-J1-11 /16.7:B
XB1:5c/PD1-J18-2 /18.7:E
XB1:6a/PL1-J7-1 / 18.7:B
-PE1 -PE
4
Capacitance energy storage
282
A-ST-01143 BK /30.1:C
17AWG A-ST-01143
250VIN-
284
BK
17AWG
3
250VIN+
J1 + 285 J1
BK
17AWG
1
LVRT电源板 LVRT power supply board
24GND 3 0V
DC24V输出
1d1c
2b2a
2d2c
3b3a
3d3c
5b5a
5d5c
6b6a
6d6c
17AWG
1b1a
D
24VA
290
22V -XB1 D
BK
RELAY- 3 17AWG
PE1-J3-3/QS1-36/17.2:E DC+:24V DC-:0V
DC200V输出
L2 3 17AWG
PE1-J7-3/T1-P2/9.8:B
交流输入
J7
16.2:D / XB1:1d/KM18:1
XB1:1b/PD1-J1-7
XB1:2b/PL1-J6-1
106
BK
16.6:E / XB1:5b/KM8:A2
16.5:E / XB1:5d/KM7-A2
16.1:E / XB1:6b/KM1:A2
L1 1 17AWG
PE1-J7-1/FU101-2/9.8:B
E 3 E
直流输入 DC voltage input
J4 BUS- 248
BK
1 17AWG
PE1-J4-1/N1-DC-/14.8:B
16.7:C /
18.7:B /
3
J2 BUS+ 241
BK
1 17AWG
PE1-J2-1/N1-DC+/14.8:B
F F
Checked by taonl Date 2022/7/29 Drawing Name (N1)单机供电图(N1) Unit Internal Power Supply
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
-PL1 -PD1 23 24
2 /9.3:D
COM1 318 BK19AWG
/18.2:A J4 NO1 /14.3:D
PD1-J1-23/PD2-J1-23/25.7:A
/18.5:A 1 308 BK19AWG
PL1-J4-1/XB10:4b/30.7:E 317 BK19AWG 风扇控制 Fan control
DO node output
NO3 2 294 BK19AWG
J9 PD1-J1-13/XB1:2a/15.6:C
B COM3 1
COM4 2
PD1 J1 ON4 COM4 316 BK19AWG
296 BK19AWG
断路器电动断开 ACB remote open
PD1-J1-12/KM7-A1/16.5:D
PD1-J1-11/XB1:2c/15.6:C
B
COM6 2
J21
1 IOLED2
NO6
IOLED3
C C
NO7 2 310 BK19AWG
PL1-J22-2/PL1-J6-2 /18.7:B +24V IOLED4
J22 直流负荷开关分闸
COM7 1 Open DC LBS
305 BK19AWG
PL1-J22-1/KM1-A1 /16.1:D
1 2
D D
305 293 309 313 316 323 317
BK BK BK BK BK BK BK
19AWG 17AWG 19AWG 19AWG 19AWG 19AWG 19AWG
1 3
306 -KM18 +A1 315 -KM18
BK /31.4:D BK /31.4:D
2 4
19AWG KM3 24VDC 19AWG
-A2
312
BK
+A1 19AWG +A1 +A1 +A1 A1
E KM1 24VDC 21NC KM6 24VDC KM7 24VDC KM8 24VDC KM17 24VDC E
-A2 -KM1 -A2 -A2 -A2 A2
/16.1:E 22NC 314
300 324
BK 297
BK BK
307 19AWG 298 BK
19AWG 19AWG
BK BK 19AWG
19AWG 17AWG
KM1-A2/XB1:6b / 15.8:E KM1-22NC/XB10:8b /30.8:E KM7-A2/XB1:5d / 15.8:E KM8:A2/XB1:5b /15.7:E KM17-A2/XB10:6a / 30.7:D
+A1 -A2 /16.1:E +A1 -A2 /16.3:E +A1 -A2 /16.4:E +A1 -A2 /16.5:E +A1 -A2 /16.6:E 1 2 /10.2:A
3 4 /10.2:A
1 2 /17.2:B 1 2 /17.3:B 1 2 /17.4:B 1 2 /17.5:B 1 2 /12.3:E
5 6 /10.2:A
3 4 /17.2:B 3 4 /17.3:B 3 4 /17.4:B 3 4 /17.5:B 3 4 /12.3:E
F 5 6 /17.2:B 5 6 /17.3:B 5 6 /17.4:B 5 6 /17.5:B F
21NC 22NC /16.3:E
Drawn by xuwt Date 2022/7/29 Drawing NO. A-SJ-02772-JL-A Page 16 of 38
Checked by taonl Date 2022/7/29 Drawing Name (N1)单机控制图(一)(N1) Unit controlling diagram 1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
负荷开关 负荷开关 直流负荷 直流负荷 断路器 断路器 断路器 断路器 断路器 断路器
常开触点 电机储能 开关分闸 开关合闸 电动闭合 电动断开 储能控制 欠压断开 控制供电 常开触点
LBS NO node LBS Energy storage LBS open LBS Close ACB remote close ACB remote open ACB Energy storage ACB under voltage trip ACB power supply unit ACB NO node
B -KM1 327
BK
-KM3 331
BK
-KM6 336
BK
-KM7 343
BK
B
1 2 19AWG 1 2 19AWG 1 2 19AWG 1 2 19AWG
5 6 5 6 5 6 5 6
C C
NDW2GZ负荷开关接线图 NDW2GZ LBS attachment figure NDW1框架接线图 NDW1 ACB attachment figure
30
49 30 35 37 37 35 33 1
49
SA
-QS1:NO M -QS1:M /12.7:E F -QS1:F /12.7:D B -QS1:B /12.7:D X -QF1:X /13.6:D F -QF1:F /13.6:C -QF1:M /13.6:C Q -QF1:Q /13.6:C -QF1:R /13.6:C -QF1:NO1
/17.3:A M /17.3:D
50 31 36 38 38 36 34
2 50
31
CW3G负荷开关接线图 CW3G LBS attachment figure CW1框架接线图 CW1 ACB attachment figure
33
D 70 37 33 35 31 29 27 37
D
SA
-QS1:NO-CW
/17.3:B
M -QS1:M-CW F -QS1:F-CW B -QS1:B-CW X -QF1:X-CW1 F -QF1:F-CW1 M
-QF1:M-CW1 Q -QF1:Q-CW1 -QF1:NO1-CW1
/12.8:E /12.8:D /12.8:D /13.7:D /13.7:C /13.7:C /13.7:C /17.3:C
71 38 34 36 32 30 28
38
34
122
BK
19AWG
F F
Checked by taonl Date 2022/7/29 Drawing Name (N1)单机控制图(二)(N1) Unit controlling diagram 2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
N1直流防雷干节点 -PL1
N1 DC SPD node /16.1:A AN4+ 2
-PL1 J13
Temperature sampling
/19.1:A 0V1 1 219 BK19AWG
PL1-J12-1/FL2-12/12.2:C P-D-000508
A AN3+ 2 A
P-D-000508 J16
ST1 2 362 BK19AWG
跳线2
short
J26
AN3- 1
0V1 1 NDW2GZ负荷开关节点
环温采样
支路电流与绝缘监测板
370BK19AWG
NDW2GZ DC LBS node AN2+ 2
DI输入 DI input
J5 1单元直流负荷开关散热器或铜排附近
ST2 2 363 BK19AWG
371BK19AWG 2 1 NTC4
J27
AN2- 1 Unit 1 near DC LBS copper bar
PL1
372BK19AWG
AN1+ 2
ST3 2 365 BK19AWG -QS1:NO/12.7:E J10
373BK19AWG 2 1 NTC5 1单元直流侧风机进风口
跳线3
short
J25
AN1- 1 Unit 1 DC air inlet
CW3G负荷开关节点
0V1 1
支路电流与绝缘监测板
CW3G DC LBS node 310BK19AWG
2 PL1-J6-2/PL1-J22-2 /16.3:C
Power supply
J6 +24V 295BK19AWG
ST4 2 366 BK19AWG
1 PL1-J6-1/XB1:2b/15.6:E
跳线4
short
B J24 70 71 B
0V1 1
2
供电
-QS1:NO-CW/12.8:E J7 0V
ST5 2 367 BK19AWG
299BK17AWG
PL1-J7-1/XB1:6a/15.8:C
跳线5
short
J23 1
0V1 1 -LB3
Communication
BK20AWG
B2 2 PL1-J1-2/PA1-J13-20/20.3:C
通讯
J1
RD20AWG
A2 1 PL1-J1-1/PA1-J13-19/20.3:C
-PD1 -W34 4turns
23 24 磁环靠近电路板安装
/9.3:D 0V2 IN12 353 BK19AWG
2x20AWG
跳线6
short
/14.3:D UL2661 20AWG×2C/2×0.519mm²/黑/双绞
/16.5:A 374
/18.5:C 0V2 IN11 BK
354 BK19AWG -PD1 19AWG
跳线7
short
C P-D-000507 PTA+ C
2
/9.3:D 2
/14.3:D
0V2 IN10 355 BK19AWG
CW1主断路器触点 /16.5:A J16 375
BK
NTC1 模组风机进风口
CW1 ACB node /18.2:C
跳线9 跳线8
short short 19AWG
1 Module air inlet
PTA-
1
37 38 P-D-000507
0V2 IN9 356 BK19AWG
-QF1:NO1-CW1 /13.7:D 376
环温采样Temperature sampling
BK
19AWG
NDW1主断路器触点
PTB-
2
0V2 IN8 NDW1 ACB node 2
DSP转接板 DSP adapter board
368 BK19AWG
J15 377
BK
NTC2 直流电容风扇进风口
357 BK19AWG 49 50 19AWG DC capacitor air inlet
-QF1:NO1 /13.6:D PTB+ 1
1
DSP转接板 DSP adapter board
378
BK
19AWG
跳线10.1
D PTC+ D
2
0V2 IN7 358 BK19AWG 2
short
DI input
J14 379
BK
-L1-R 电抗器温度
/13.3:A Reactor temperature
PD1
19AWG
1
PTC-
1
J5
PD1 380
跳线11 跳线10.2
0V2 IN6 BK
351 BK19AWG 19AWG
short short
PTD-
2
2
电容池与模组之间
0V2 IN5 352 BK19AWG J13 381
BK
NTC3 Between capacitor pool and module
19AWG
1
1
PTD+
交流防雷触点
AC SPD node
0V2 IN4
E 004 BK19AWG
PD1-J5-8/FL1-12/7.5:D
BK
20AWG E
0V PD1-J18-2/XB1:5c /15.8:C
2
供电Power supply
019 BK19AWG
PD1-J5-7/FL1-11/7.6:D
0V2 IN3 359 BK19AWG J18
跳线13 跳线12
short
1
0V2 IN2 360 BK19AWG 电抗器触点
RD
short
2
0V2 IN1 369 BK19AWG 4 3
J17 -W35
1 2 2x20AWG
160℃常闭 UL2661 20AWG×2C/2×0.519mm²/黑/双绞
1
361 BK19AWG
F F
Checked by taonl Date 2022/7/29 Drawing Name (N1)单机DI温度板(N1) Unit DI temprture board
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
PA1
-W36
-PA1 2x20AWG
2
RD 20AWG
/14.6:D
J7
CANHB PA1-J7-2/PA2-J7-2/29.3:B
PG1
P-A-000776
1
BK 20AWG
CANLB PA1-J7-1/PA2-J7-1/29.3:B
CAN通讯 CAN communication
B J6 FGB B
-W38
2x20AWG -PG1 10
short14
389 BK 19AWG
跳线14
-W37 RD 20AWG
PA1-J5-2/PT-J3-7/32.7:B
/9.4:D IN5
2x20AWG /14.1:C
P-A-001084 0V
2
RD 20AWG
CANHA PA1-J5-2/PA2-J5-2/29.3:B IN4
J5
BK 20AWG
CANLA PA1-J5-1/PA2-J5-1/29.3:B 0V
BK 20AWG IN3
PA1-J5-1/PT-J3-5/32.7:B J6
0V
J4 FGA -GND2 IN2
0V
C 19 20 C
442 BK 20AWG IN1
A2 B2 PA1-J13-20/PL1-J1-2/18.7:B
0V
435 RD 20AWG
PA1-J13-19/PL1-J1-1/18.7:C 1
J14
RS485通讯 RS485 communication
1 2
Carrier synchronization
386 BK 光纤
J10 TX PA1-J10/PA2-J11/29.3:E
载波同步
388 BK 光纤
J11 RX PA1-J11/PA2-J10/29.3:E
光纤环网通讯
Optical fiber ring network communication
F F
Checked by taonl Date 2022/7/29 Drawing Name (N1)单机通讯板(N1) Unit communication board
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
-MODEL 2#
-QS3
1 2 -N2:DC+
N2-DC+ 1 U2 /22.1:A
A A
3 4
11.6:E / N2-DC+ -TA69
5 6
2000A/4V -C51 -C66
11.6:E / N2-DC- G OG 24AWG
TA69G/PA2-J12-13/23.7:E 750uF/800VDC 750uF/800VDC
BK 24AWG
7 8
S TA69S/PA2-J12-15/23.7:D
BN 24AWG -N2:N
- TA69-/PA2-J12-17/23.7:D 2 V2 /22.1:B
1500V/2500A RD 24AWG N2-NEUTRAL
390 392 + TA69+/PA2-J12-19/23.7:D
BK BK
5AWG 5AWG -W42
4x24AWG -C67 -C82
750uF/800VDC 750uF/800VDC
1 1 -N2:DC-
B N2-DC- 3 W2 /22.1:C B
-FU81 -FU82 230 232
188
熔断器Fuse:1500V/20A BK
BK BK
2 2 19AWG
底座Holder:1500V/63A 19AWG 19AWG Pac=1562.5kW
Umppt:DC 875-1300V
391 393
BK BK
Uo:AC 600V
5AWG 5AWG Io:AC 1503A
DC Input:12-14路
储能2:(+)
储能2:(-)
FL3 +/- -/+
BAT2+
BAT2-
8.7:B / PB2-J2-1/N2-DC-
旧板接PB2-J2-4
399 BK 19AWG
11
FL3-11/PL2-J12-2/27.3:A
400 BK 19AWG
12 405 406
C FL3-12/PL2-J12-1/27.3:A BK BK -PM2 C
11AWG 11AWG
14
PE PE
PM1
12.3:C / QS3:1/QS2:2+
12.3:C / QS3:5/QS2:2-
394
GNYE
5AWG
MZ1 MZ2 MZ3
PM2
单元2模组
D Unit 2 module D
23.1:A/ N2-DC+
23.1:A/ N2-DC-
~ -
N2-N
SVG控制N2缓启 5 6
整流桥
N2 slow start of SVG Rectifier
13NO
23.1:A/
14NO
21NC 22NC
F F
+A1 -A2 /25.7:E
1 2 /21.3:E Drawn by xuwt Date 2022/7/29 Drawing NO. A-SJ-02772-JL-A Page 21 of 38
3 4 /21.3:F Checked by taonl Date 2022/7/29 Drawing Name (N2)逆变模组单元(N2) Invert module unit
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
21.6:F / N2-DC+
A 21.6:F / N2-N A
21.6:F / N2-DC-
410 416
BK BK
17AWG 17AWG
PX2
24.3:F / N2-DC+/PE2-J2-1
24.3:E / N2-DC-/PE2-J4-1
B B
-PX2 2 415
直流电压 DC voltage
2 409
BK
J1 1500V+ 17AWG
PG2 J2 1500V_M
1
2 412
BK
17AWG
-PG2 RD -LB6 1
4
24V power supply
C /9.2:F +24V
20AWG
PG2-J46-4/XB10:2a/30.6:D C
/29.5:B
24V供电输入
磁环靠近电路板安装
P-A-001084 J46 磁环靠近电路板安装
BK
-LB15
PA2
20AWG
+24VGND PG2-J46-1/XB10:5b/30.7:E 044 24AWG
PA2-J12-20/PI2-J1-1/8.7:A
1 043 24AWG
-W46 4turns PA2-J12-18/PI2-J1-2/8.7:A
COM4
1 2x20AWG 042 24AWG
PA2-J12-16/PI2-J1-3/8.7:A
041 24AWG
PA2-J12-14/PI2-J1-4/8.7:A
NO4 -PA2
NC4 /29.2:B 19 20 4turns
P-A-000776 +15VA +15VA
COM3 420 24AWG
PA2-J12-19/TA73+/22.2:B
D D
DO输出口 DO output node
516 24AWG
NO3
-15VA -15VA PA2-J12-19/TA69+/21.5:B
423 24AWG
PA2-J12-17/TA73-/22.2:B
PD2
NC3
J2 515 24AWG
COM2
048 BK 19AWG
PG2-J2-7/PB2-J4-3/8.7:C PA2-J12-17/TA69-/21.5:A
I-DC I-LEAK
047 BK 19AWG
NO2 PG2-J2-8/PB2-J4-4/8.7:B
8 BK
计量板 Measuring Board
513 24AWG
NO1
045 BK 19AWG
PG2-J2-11/PB2-J4-6/8.7:B /25.5:A 439 PA2-J12-13/TA69G/21.5:A
/27.1:C BK +15VA +15VA 542 24AWG
NC1 /27.5:C INV_B
19AWG
PD2-J3-5/N2bar-B3/22.3:E J12 PA2-J12-11/TA71+/22.2:A
DSP转接板 DSP adapter board
422 24AWG
446 BK 19AWG 1 450 PA2-J12-9/TA72-/22.2:B
IC1 PG2-J40-5/TA78-S2/22.5:B 10 BK
19AWG
I-C1 I-C2
IB2 FUSE_GND
DC voltage sampling
425 24AWG
J40 414
BK
PA2-J12-7/TA73S/22.2:C
IB1 -GND2 I-B1 I-B2
电流采样
19AWG
447 BK 19AWG J2 BUS-
IA2 PG2-J40-2/TA76-S1/22.5:A
直流电压采样
19AWG
PV- BUS+ 552 24AWG
PA2-J12-1/TA71G/22.2:A
1
直流采样
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
-LB7 609
BK
15AWG
24.2:D/XB5:5a/PE2-J6-3
磁环靠近电路板安装
611
BK
15AWG
24.2:D/XB5:1a/PE2-J6-1
4turns
LVRT电源盒
PE2
/27.7:F
/25.7:B
/25.7:B
B B
XB5:5c/PD2-J18-2 / 27.7:E
/ 27.7:B
LVRT power supply
XB5:3a/KM18:5 / 25.2:D
XB5:1c/PD2-J17-2
XB5:2a/PD2-J1-13
XB5:2c/PD2-J1-11
XB5:6a/PL2-J7-1
-PE2 -PE2
4
Capacitance energy storage
451
/24.3:B BK /24.1:B
250VIN-
A-ST-01143 17AWG A-ST-01143
453
BK
C 3
17AWG C
250VIN+
594 460 461 462 601 466
J1 + 454 J1 RD BK BK BK BK BK
BK 20AWG 19AWG 19AWG 17AWG 20AWG 17AWG
17AWG
1 455
BK
17AWG
24GND 3 0V
DC200V output DC24V output
LVRT电源板 LVRT power supply board
PE2-J6-3/XB5:5a/24.4:A
DC24V输出
1d1c
2b2a
2d2c
3b3a
3d3c
5b5a
5d5c
6b6a
6d6c
1b1a
J6 456 CON1 -XB5
PE2-J6-1/XB5:1a/24.4:B BK
17AWG
(J3)
24VA 1 22V
457
BK
DC+:24V DC-:0V
17AWG 459 463 464 465 467
RELAY- 3 PE2-J3-3/QS3-36/26.2:E BK BK BK BK BK
DC200V输出
17AWG
L2 3 PE2-J7-3/T1-L2/9.8:B
27.7:B / XB5:3b/PL2-J6-1
交流输入
25.7:E / XB5:5b/KM11-A2
25.5:E / XB5:5d/KM10-A2
25.1:E / XB5:6b/KM12-A2
25.7:C / XB5:1b/PD2-J1-7
J7 099
BK
17AWG
L1 1 PE2-J7-1/FU40:2/9.8:B
3
直流输入 DC voltage input
J4 BUS- 416
BK
E 17AWG E
1 PE2-J4-1/N2-DC-/23.7:B
3
J2 BUS+ 410
BK
17AWG
1 PE2-J2-1/N2-DC+/23.7:B
F F
Checked by taonl Date 2022/7/29 Drawing Name (N2)单机供电图(N2) Unit Internal Power Supply
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
负荷开关 负荷开关 直流负荷 直流负荷 断路器 断路器 断路器 断路器 断路器 断路器
常开触点 电机储能 开关分闸 开关合闸 电动闭合 电动断开 储能控制 欠压断开 控制供电 常开触点
LBS NO node LBS Energy storage LBS open LBS Close ACB remote close ACB remote open ACB Energy storage ACB under voltage trip ACB power supply unit ACB NO node
C C
NDW2GZ负荷开关接线图 NDW2GZ LBS attachment figure NDW1框架接线图 NDW1 ACB attachment figure
30
49 30 35 37 37 35 33 1 49
SA
-QS3:NO -QS3:F/21.7:D -QS3:B /21.7:E -QF2:M /22.6:C -QF2:R /22.6:C -QF2:NO1
/26.3:B
M -QS3:M /21.7:E F B X -QF2:X /22.6:D F -QF2:F/22.6:D M Q -QF2:Q /22.6:C /26.3:D
50 31 36 38 38 36 34 50
2
31
CW3G负荷开关接线图 CW3G LBS attachment figure CW1框架接线图 CW1 ACB attachment figure
33
D 70 37 33 35 31 29 27 37 D
SA
-QS3:NO-CW M -QS3:M-CW /21.8:E F -QS3:F-CW/21.8:D B -QS3:B-CW X -QF2:X-CW1/22.7:D F -QF2:F-CW1 /22.7:D M
-QF2:M-CW1/22.7:C Q -QF2:Q-CW1/22.7:C -QF2:NO1-CW1
/26.3:B /26.3:C
71 38 34 36 /21.8:E 32 30 28
38
34
134
BK
19AWG
E N DC-:0V N E
/25.1:E +A1 -A2 /25.3:E +A1 -A2 /25.4:E +A1 -A2 /25.5:E +A1 -A2
/26.2:B 1 2 /26.3:B 1 2 /26.4:B 1 2 /26.5:B 1 2
/26.2:C 3 4 /26.3:C 3 4 /26.4:C 3 4 /26.5:C 3 4
/26.2:C 5 6 /26.3:C 5 6 /26.4:C 5 6 /26.5:C 5 6
/25.3:E 21NC 22NC
F F
Checked by taonl Date 2022/7/29 Drawing Name (N2)单机控制图(二)(N2) Unit controlling diagram 2
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
-PL2
N1直流防雷干节点 /25.1:A AN4+ 2
N1 DC SPD node J13
Temperature sampling
A /25.1:A A
/27.5:A J12 P-D-000508
400 BK 19AWG
/28.1:A 0V1 1 PL2-J12-1/FL3-12/21.2:C AN3+ 2
J16
P-D-000508
2
520 BK 19AWG AN3- 1
跳线16
ST1
short
J26
环温采样
528 BK 19AWG
支路电流与绝缘监测板
0V1 1 NDW2GZ负荷开关节点 AN2+ 2
NDW2GZ DC LBS node J5 2单元直流负荷开关散热器或铜排附近
521 BK 19AWG AN2- 1
529 BK 19AWG 2 1 NTC9 Unit 2 near DC LBS copper bar
DI输入 DI input ST2 2
J27
PL2
522 BK 19AWG 49 50 530 BK 19AWG
0V1 1 AN1+ 2
PL2
J10 2单元直流侧风机进风口
523 BK 19AWG -QS3:NO /21.7:E AN1- 1
531 BK 19AWG 2 1 NTC10 Unit 2 DC air inlet
2
跳线17
ST3
支路电流与绝缘监测板
short
J25 CW3G负荷开关节点 474 BK 19AWG
0V1 1 CW3G DC LBS node 2 PL2-J6-2/PL2-J22-2/25.3:C
Power supply
B J6 463 BK 19AWG
B
524 BK 19AWG
+24V 1 PL2-J6-1/XB5:3b/24.6:D
2
跳线18
ST4 70 71
short
J24
1 2
供电
0V1
-QS3:NO-CW /21.8:E J7 0V 466 BK 17AWG
2
525 BK 19AWG
1 PL2-J7-1/XB5:6a/24.7:C
跳线19
ST5
-LB8
short
J23
Communication
0V1 1 B2 2 BK20AWG
PL2-J1-2/PA2-J13-20/29.3:C
通讯
J1
A2 1 RD20AWG
PL2-J1-1/PA2-J13-19/29.3:C
-W47 4turns
-PD2 23 24 2x20AWG 磁环靠近电路板安装
/9.3:F 0V2 IN12 504 BK 19AWG UL2661 20AWG×2C/2×0.519mm²/黑/双绞
跳线23 跳线22 跳线21 跳线20
short short short short
/23.3:D
/25.5:A -PD2 532 BK 19AWG
PTA+
2
C /27.5:C 0V2 IN11 505 BK 19AWG
/9.3:F 2 C
/23.3:D 模组风机进风口
P-D-000507 /25.5:A J16 NTC6 Module air inlet
/27.1:C 533 BK 19AWG
0V2 IN10 1
PTA-
1
506 BK 19AWG
P-D-000507
CW1主断路器触点
环温采样Temperature sampling
CW1 ACB node
0V2 IN9 507 BK 19AWG 534 BK 19AWG
PTB-
2
37 38 2
-QF2:NO1-CW1 /22.7:D J15 NTC7 直流电容风扇进风口
DC capacitor air inlet
1
0V2 IN8 NDW1 ACB node
526 BK 19AWG
508 BK 19AWG 49 50
DSP转接板 DSP adapter board
536 BK 19AWG
-QF2:NO1 /22.6:D PTC+
2
D 2 D
电抗器温度
J14 -L2-R Reactor temperature
1 /22.3:A
DI input
537 BK 19AWG
PTC-
1
跳线24.1
J5
PD2
0V2 IN7 509 BK 19AWG
PD2
short
538 BK 19AWG
PTD-
2
2
跳线25 跳线24.2
电容池与模组之间
0V2 IN6 510 BK 19AWG J13 NTC8 Between capacitor pool and module
short short
539 BK 19AWG 1
PTD+
1
0V2 IN5 511 BK 19AWG
BK
E 20AWG E
0V PD2-J18-2/XB5:5c/24.7:C
2
0V2 IN4 512 BK 19AWG
跳线28 跳线27 跳线26
供电Power supply
short short short
J18
0V2 IN3
1
517 BK 19AWG
RD
20AWG
电抗器触点
0V2 IN2 24V PD2-J17-2/XB5:1c/24.5:C
2
518 BK 19AWG
Reactor node
-L2-T /22.3:B J17 -W48
2x20AWG
0V2 IN1 527 BK 19AWG 4 3
UL2661 20AWG×2C/2×0.519mm²/黑/双绞
1
1 2
160℃常闭
519 BK 19AWG
F F
Checked by taonl Date 2022/7/29 Drawing Name (N2)单机DI温度板(N2) Unit DI temprture board
1 2 3 4 5 6 7 8
F
E
D
C
B
A
P-D-000508
/27.5:A
/27.1:A
/25.1:A
-PL2
1
1
J2
J11
PL2
GND
M32
+15V
AGND
-15V
DC+
DC-
J17 EARTH2
1
2
1
6
M12 M13
J2-13 J2-14
J2-15 J2-16
J2-17 J2-18
J2-19 J2-20
J2-21 J2-22
J2-23 J2-24
AGND
AGND
23 24
2
+15V
AGND
-15V
544 GNYE
2
2
19AWG
231 BK 19AWG
233 BK 19AWG
543 BK 19AWG
541 BK 19AWG
540 BK 19AWG
11.6:D/ PL2-J2-15/TA49-S
11.5:D/ PL2-J2-18/TA48-S
11.4:D/ PL2-J2-17/TA47-S
11.4:D/ PL2-J2-20/TA46-S
11.3:D/ PL2-J2-19/TA45-S
-LB9
4turns
11.3:D/ PL2-J2-22/TA44-S
-GND2
3
3
11.2:D/ PL2-J2-21/TA43-S
就近接机壳
磁环靠近电路板安装
PL2-J11-1/QS2-2+/12.3:D
PL2-J11-6/QS2-2-/12.3:D
11.1:D/ PL2-J2-24/TA42-S
11.1:D/ PL2-J2-23/TA41-S
PL2-J2-2/XB40:1a/28.4:B
PL2-J2-4/XB40:5a/28.7:B
PL2-J2-6/XB40:3a/28.6:B
4
4
-XB40
1b1a
XB40:1a/PL2-J2-2 / 28.3:E
5
5
186 24AWG
Drawn by
11.6:D/ TA49:+ 210 24AWG TA49:+/XB40:2c /28.5:B
Checked by
Approved by
3b3a
XB40:3a/PL2-J2-6 / 28.3:E
xuwt
taonl
11.1:D/ TA41:- 154 24AWG TA41:-/XB40:3c /28.6:B
11.1:D/ TA42:- 169 24AWG 28.6:D / XB40:3d/TA45:- XB40:3c/TA41:-/28.6:D
zhangjin Date
Date
Date
3d3c
11.2:D/ TA43:-
6
6
175 24AWG
193 24AWG
Drawing NO.
Drawing Name
Product Model
5b5a
XB40:5a/PL2-J2-4 / 28.3:E
11.1:D/ TA41:G TA41:G/XB40:5c /28.7:B
7
7
156 24AWG
F
E
D
C
B
A
1 2 3 4 5 6 7 8
Confidential
A A
PA2
-PA2
2
718 RD 20AWG
/23.6:D CANHB PA2-J7-2/PA1-J7-2 /20.3:B
P-A-000776
1
719 BK 20AWG
CANLB PA2-J7-1/PA1-J7-1 /20.3:B
B J6 FGB PG2 B
2
718 RD 20AWG
J5
CANHA PA2-J5-2/PA1-J5-2 /20.3:B
-PG2 10
1
719 BK 20AWG 546 BK 19AWG
跳线29
CANLA PA2-J5-1/PA1-J5-1/20.3:C /9.2:F IN5
short
/23.1:C
P-A-001084 0V
J4 FGA
0V
SHELL2 1
A1 B1
B1 PG2-J14-2/PG1-J14-2/20.7:D
716 BK 20AWG
A1 PG2-J14-1/PG1-J14-1/20.7:D
PA2-J13-6/PG2-J3-3/29.7:E 1 -W49
4turns
A1 B1 713 RD 20AWG
PA2-J13-5/PG2-J3-2/29.7:E 2x20AWG
RD 20AWG
-LB11 磁环靠近电路板安装
4 PG2-J14-1/PT-J4-5/32.7:C
BK 20AWG
PG2-J14-2/PT-J4-7/32.7:B
4turns
SHELL1
BK 20AWG
B0 PG2-J3-3/PA2-J13-6/29.3:D
1 2 J3
RD 20AWG
E A0 PG2-J3-2/PA2-J13-5/29.3:D E
Carrier synchronization
388 BK 光纤
J10 TX PA2-J10/PA1-J11 /20.3:F
载波同步
-W50
386 BK 光纤
-GND2 2x20AWG
F F
Checked by taonl Date 2022/7/29 Drawing Name (N2)单机通讯板(N2) Unit communication board
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
告警指示 运行指示 故障指示
Warning light Running light Fault light -PP
A
H2:X3/XB10:2d
549
BK
/30.6:E
547
BK
554
BK
LCD A
17AWG 19AWG 19AWG
+24V - FG COM1 RS232 COM2 RS485/422 ETHERNET USB-A
-PC
液晶屏
X3 X3 X1 A B GND
1 2 3 4
H2 H2 H3 -W51 RD BK
2x20AWG 20AWG 20AWG
黄色 X1 绿色 X2 红色 X2 -W52 RD BK
550 555 557 2x20AWG 20AWG 20AWG
BK
19AWG
BK
19AWG
BK
19AWG
30.4:D/ PP_DC24V+/PE4-J2-2 32.7:C/PC-J1-1/PT-J17-1
30.4:D/ PP_DC24V-/PE4-J2-1 32.7:C/PC-J1-2/PT-J17-5
553 BK 15AWG
30.2:D/XB10:1a/PE-J6-1
4turns
PE PE4 24V电源灯
磁环靠近电路板安装 24VDC Power light
XB10:7a/PG1-J46-1 / 14.2:C
XB10:2a/PG2-J46-4 /23.2:C
XB10:2c/PD1-J1-22 / 16.7:A
/32.5:A
/32.5:B
-H1
XB10:5c/KM20:A2 /31.6:D
XB10:6a/KM17-A2 /16.7:E
1 -LB12
558 566
-PE4
Voltage input
BK BK
C -PE 绿色 C
XB10:3a/H1-X1 / 30.5:C
XB10:7c/SW1:1 / 31.2:B
XB10:3c/SW1:2 /31.2:B
17AWG 17AWG
P-E-000515 0V_IN H1-X2/XB10:6d/30.8:E
/15.3:C X2
Capacitance energy storage
XB10:4c/PW-J1-3
XB10:8c/PW-J1-1
559 567
P-E-000230 J1 BK BK
X1
-
输入
17AWG 17AWG
J5 24V_IN H1-X1/XB10:3a/30.6:D
2 4turns
Voltage output
1
1
722 BK 20AWG
电容板储能
0V_OUT PE4-J2-1/PP_DC24V-/30.4:B
J2
3
723 BK 20AWG
24V_OUT PE4-J2-2/PP_DC24V+/30.4:B
输出
J1 + 2
1
551
BK
D 15AWG D
DC24V output
24GND 3 PE-J6-3/XB10:5a/30.5:B
LVRT电源板 LVRT power supply board
RD BK BK BK RD BK BK BK BK BK
J6 20AWG 19AWG 17AWG 20AWG 20AWG 19AWG 19AWG 20AWG 19AWG 20AWG
PE3
553
BK
15AWG
24VA 1 PE-J6-1/XB10:1a/30.5:B
5d5c
6b6a
6d6c
7b7a
8b8a
8d8c
7d7c
3d3c
4d4c
1b1a
1d1c
2b2a
2d2c
3b3a
4b4a
5b5a
-XB10
AC voltage input DC200V output
RELAY- 3
DC200V输出
P-E-000464 470
734 561 549 568 308 472 734 570 566 560 307
RELAY+ 1 090
RD
20AWG
BK
17AWG
BK
17AWG
BK
19AWG
BK
19AWG
BK
19AWG
BK
20AWG
BK
19AWG
BK
17AWG
BK
17AWG
BK
19AWG
BK
19AWG
J1
Voltage input
BK
17AWG 561 BK 17AWG
L2 3 PE-J7-3/T4-0V/9.8:A 24V1 1 PE3-J1-1/XB10:2b/30.6:E
交流输入
电源输入
E J7 089
E
BK
17AWG
GND 3
1 PE-J7-1/T4-486V/9.8:A
30.4:E/ XB10:2b/PE3-J1-1
16.3:A / XB10:4b/PL1-J4-1
25.3:A / XB10:4d/PL2-J4-1
L1
32.5:E / XB10:3b/PT-J12-16
30.1:A / XB10:2d/H2:X3
30.5:C / XB10:6d/H1-X2
25.3:E / XB10:8d/KM12-22NC
14.2:C / XB10:1b/PG1-J46-4
23.2:C / XB10:5b/PG2-J46-1
30.4:E / XB10:7d/PE3-J1-3
16.3:E / XB10:8b/KM1-22NC
XB10:6b/PT-J2-1
J2
24V2 1
直流输入 DC voltage input
3
J4 BUS- 249 4 562 BK 19AWG
BK PE3-J3-4/PT-J7-6 /32.2:A
17AWG 24V
1 PE-J4-1/N1-DC-/14.7:B 563 BK 19AWG
DC24V output
J3 PE3-J3-3/XB11:5a/33.2:B
DC24V输出
564 BK 19AWG
PE3-J3-2/PT-J7-2/32.2:A
3
32.5:D /
GND 565 BK 19AWG
PE3-J3-1/XB11:6a/33.2:B
F
J2 BUS+ 242
BK 1 F
17AWG
1 PE-J2-1/N1-DC+/14.7:B
Drawn by xuwt Date 2022/7/29 Drawing NO. A-SJ-02772-JL-A Page 30 of 38
Checked by taonl Date 2022/7/29 Drawing Name 智能配电供电图Intelligent distribution and power supply
diagram
Approved by zhangjin Date 2022/7/29 Product Model A-SJ-02772 SG6250HV-MV-V1240 Inverter(A-ST-03703)
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
KM20-A1/PD1-J1-16 /16.7:B
/32.5:B
/ 32.2:D
SW1:2/XB10:3c / 30.7:D
SW1:1/XB10:7c / 30.8:D
S1:13/PT-J5-2 / 32.2:E
S1:23/XB11:5a /33.2:B
KM35-A1/PT-J2-21
SQ1:13/PT-J5-3
B B
RD BK
20AWG 20AWG
C -W53 C
2x20AWG
572
BK
-SW1 19AWG 13 23
+
Y -
-S1
LDE1 14 24
2 3 13
-SQ1 580
BK
537
BK
1 4 14 19AWG 19AWG
+
R - 576
LDE2 BK
RD BK 573 19AWG
20AWG 20AWG BK +A1 +A1 +A1 +A1
-W54 19AWG
2x20AWG
13 -KM18 24VDC -KM36 24VDC -KM20 24VDC -KM35 24VDC
-SW2
D +
-SQ2 -A2 538
-A2 -A2 -A2
D
Y - BK
LDE1 14 19AWG
2 3
577 579 571 569 582
BK BK BK BK BK
19AWG 19AWG 19AWG 19AWG 19AWG
1 4
+
R -
LDE2 574
BK
32.2:D / S1:14/PT-J5-12
32.2:D / SQ2:14/PT-J5-11
33.2:B / KM18:A2/XB11:6a
30.7:D / KM20:A2/XB10:5c
32.2:A / KM35-A2/PT-J7-4
19AWG
32.2:C /SW2-4/PT-J5-14
E E
23 24 /31.4:C
13 14 /31.4:C
+A1 -A2 /31.4:D +A1 -A2 /31.5:D +A1 -A2 /31.6:D +A1 -A2 /31.8:D
1 2 /16.2:E 11 14 /33.4:A 1 2 /9.3:B 11 14 /33.4:A
3 4 /16.5:E 41 44 /33.4:A 3 4 /9.3:C 41 44 /33.4:A
5 6 /25.2:D 5 6 /9.3:C
13NO 14NO /25.5:D
F F
Checked by taonl Date 2022/7/29 Drawing Name 智能配电控制图Intelligent distribution control diagram
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
/32.2:E
/32.2:E
/32.2:E
XB11:7a/PT-J15-11 /32.2:E
/32.2:E
/32.2:F
/32.2:F
/32.7:B
/32.7:B
/32.7:D
/32.7:D
/32.7:D
/32.7:D
/32.7:D
/32.7:D
/32.7:E
/32.7:E
/32.7:E
/32.7:E
/ 32.5:E
/ 32.5:F
/32.2:F
/32.2:F
XB11:5a/PE3-J3-3 /30.4:F
XB11:6a/PE3-J3-1 /30.4:F
/32.2:F
581 585 587
BK BK BK
XB11:6a/KM18:A2 /31.4:D
19AWG 19AWG 19AWG
-KM35/31.8:D
-KM36/31.5:D
XB11:5a/S1:23 /31.4:B
XB11:10a/PT-J15-15
XB11:11a/PT-J15-16
XB11:12a/PT-J15-13
XB11:8a/PT-J15-12
XB11:13a/PT-J15-8
XB11:14a/PT-J15-6
XB13:11a/PT-J18-1
XB13:12a/PT-J18-3
XB13:13a/PT-J20-5
XB13:14a/PT-J20-7
XB13:17a/PT-J20-1
XB13:18a/PT-J20-3
XB11:9a/PT-J15-9
XB13:1a/PT-J19-5
XB13:2a/PT-J19-3
XB13:5a/PT-J11-3
XB13:6a/PT-J11-5
XB13:7a/PT-J18-5
XB13:8a/PT-J18-7
XB12:3a/PT-J12-6
XB12:4a/PT-J12-2
XB11:1a/PT-J15-4
XB11:2a/PT-J15-2
A 14 44 14 44
A
11 41 11 41
623 19AWG
622 19AWG
619 19AWG
620 19AWG
615 19AWG
616 19AWG
563 19AWG
535 19AWG
565 19AWG
539 19AWG
596 19AWG
612 19AWG
597 19AWG
593 19AWG
611 19AWG
595 19AWG
613 19AWG
614 19AWG
800 20AWG
801 20AWG
803 20AWG
802 20AWG
805 20AWG
804 20AWG
807 20AWG
806 20AWG
809 20AWG
808 20AWG
811 20AWG
810 20AWG
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
RD
BK
RD
BK
RD
BK
RD
BK
RD
BK
RD
BK
B B
10b10a
11b11a
12b12a
13b13a
14b14a
10b10a
11b11a
12b12a
13b13a
14b14a
15b15a
16b16a
17b17a
18b18a
2b2a
3b3a
4b4a
5b5a
6b6a
7b7a
8b8a
9b9a
2b2a
3b3a
4b4a
2b2a
3b3a
4b4a
5b5a
6b6a
7b7a
8b8a
9b9a
1b1a
1b1a
1b1a
-XB11 -XB12 -XB13
V1A+ V1A- 24VOUT GND1 PT1- PT1+ GND PT2- PT2+ GND V2A+ V2A- NO COM NO COM H L GND GND A B A B GND GND A B A B GND GND A B
1b、2b: 3b、4b: 5b、6b: 7b、8b、9b: 10b、11b、12b: 13b、14b: 1b、2b: 3b、4b: 1b、2b、3b: 4b、5b、6b: 7b、8b、9b: 10b、11b、12b: 13b、14b、15b: 16b、17b、18b:
4~20mA spare 24V(OUT) PT100 PT100 4~20mA DO3 DO2 Reserved CAN Data Forwarding Reserved RS485 Reserved RS485 Internal Communication Internal Communication
Transformer spare Transformer spare RMU Tripping RMU closing to Background RS485 RS485
Winding oil operation operation
control control RS485
Temperature temperature COM5 COM6 COM7 COM8 COM9
V1A 24V输出 PT2 DO3 DO2
变压器绕组温度 变压器油温 环网柜跳闸 环网柜合闸
C C
XZ2:10a/PT-J5-15 / 32.2:C
/ 32.2:B
XZ3:10a/PT-J9-14 / 32.2:B
XZ3:12a/PT-J9-13 / 32.2:B
XZ3:14a/PT-J9-16 / 32.2:B
XZ3:16a/PT-J9-15 / 32.2:B
XZ2:6a/PT-J5-13 / 32.2:D
XZ2:8a/PT-J5-16 / 32.2:C
XZ2:12a/PT-J5-7 / 32.2:D
XZ2:14a/PT-J5-8 / 32.2:D
XZ2:16a/PT-J5-5 / 32.2:D
/ 32.2:C
XZ3:2a/PT-J9-10 / 32.2:B
/ 32.2:C
/ 32.2:B
XZ3:8a/PT-J9-11 / 32.2:B
XZ3:18a/PT-J9-7 / 32.2:B
XZ3:20a/PT-J9-8 / 32.2:B
XZ2:1a/PT-J5-4 / 32.2:D
XZ3:6a/PT-J9-12
XZ3:1a/PT-J9-4
XZ3:3a/PT-J9-6
XZ3:4a/PT-J9-9
D D
610 19AWG
589 19AWG
608 19AWG
588 19AWG
590 19AWG
609 19AWG
591 19AWG
607 19AWG
604 19AWG
606 19AWG
586 19AWG
602 19AWG
585 19AWG
600 19AWG
584 19AWG
599 19AWG
583 19AWG
587 19AWG
605 19AWG
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG 603 BK 22AWG
603 BK 22AWG
10b10a
11b11a
12b12a
13b13a
14b14a
15b15a
16b16a
10b10a
11b11a
12b12a
13b13a
14b14a
15b15a
16b16a
17b17a
18b18a
19b19a
20b20a
1b1a
2b2a
3b3a
4b4a
5b5a
6b6a
7b7a
8b8a
9b9a
1b1a
2b2a
3b3a
4b4a
5b5a
6b6a
7b7a
8b8a
9b9a
-XZ2 -XZ3
E E
+24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI +24V DI
1b、2b: 3b、4b: 5b、6b: 7b、8b: 9b、10b: 11b、12b: 13b、14b: 15b、16b: 1b、2b: 3b、4b: 5b、6b: 7b、8b: 9b、10b: 11b、12b: 13b、14b: 17b、18b: 19b、20b:
15b、16b:
spare spare DI6 DI7 DI8 DI17 DI19 DI21 DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16 DI18 DI20
Gas Relay Gas Relay Oil MV N1:HV Room Smoke N1:Winding
Oil Low Oil HV Room Pressure HV Remote MV Load MV Load MV Vacuum N1:MV Earthing N1:Winding
Circuit-Breaker Switch 3
Trip Alarm Temperature Disconnector N2:UPS Fault Alarm Temperature trip Temperature Alarm
Switch N2:MV Earthing Temperature Level Trip Door Relief Trip Control Switch 1 Switch 2 N2:Auxiliary
transformer N2:MV Earthing
Alarm Switch 2 Trip temperature alarm Switch 1
DI6 DI7 DI8 DI17 DI19 DI21 DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16 DI18 DI20
瓦斯跳闸 瓦斯报警 油温报警 中压隔离开关 N1高压室烟感 N1绕组温度跳闸 油温跳闸 低油位跳闸 高压室门禁 油压跳闸 高压远程控制 中压负荷开关1 中压负荷开关2 中压断路器 N1中压接地开关3
N2辅变温度报警
N1绕组温度报警
N2中压接地开关1
N2 UPS故障报警 N2中压接地开关2
F F
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
Terminal Terminal Terminal
排 排 排
A =SG+-XB1 =SG+-XB3 =SG+-XB5 A
POS Ext Target Short Int Target POS POS Ext Target Short Int Target POS POS Ext Target Short Int Target POS
放置 外部目标 短接 内部目标 放置 放置 外部目标 短接 内部目标 放置 放置 外部目标 短接 内部目标 放置
292 289 061 059 459
/16.6:B -PD1:J1-7 1b1a -PE1:J6-1 /15.2:D /9.2:F -PG2:J34-7 1b1a -QS25:a /9.1:A /25.5:B -PD2:J1-7 1b1a -PE2:J6-1 /24.2:D
B 463 462 B
3b3a 2d2c /27.6:B -PL2:J6-1 3b3a -KM18:5 /25.2:D
069 062
3d3c /9.3:F -PG2:J4-1 3b3a -QS25:b /9.1:A 3d3c
8d8c 8d8c
D D
E E
F F
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
109 108
/10.7:E -MF2-L1 1d1c -KM17: 1 /10.2:A 1d1c 1d1c
561 734
2b2a 2b2a /30.4:E -PE3:J1-1 2b2a -PG2:J46-4 /23.2:C
116 569
/10.7:E -MF2-L3 5d5c 5d5c 5d5c -KM20:-A2 /31.6:D
C C
076 082 570 324
/8.6:C -PB2:J1-3 6b6a -PB1:J1-3 /8.2:C 6b6a /32.4:D -PT:J2-1 6b6a -KM17:A2 /16.7:E
081 082
/8.6:C -PB2:J1-1 9b9a -PB1:J1-1 /8.2:C 9b9a
9d9c 9d9c
E E
F F
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
195 171
3b3a 3b3a /33.5:B /11.5:A -TA7:+ -TA3:+ /11.2:A
201 177
4b4a 4b4a /33.5:B /11.5:A -TA8:+ -TA4:+ /11.3:A
565 805
6b6a -PE3:J3-1 /30.4:F 7b7a -PT:J18-5 /32.7:D 2d2c
571 804 184 150
-KM18:-A2 /31.4:D 8b8a -PT:J18-7 /32.7:D /11.3:A -TA5:- 3b3a -TA1:- /11.1:A
595 808
12b12a -PT:J15-13 /32.2:E 14b14a -PT:J20-7 /32.7:E 4d4c
613 185 152
13b13a -PT:J15-8 /32.2:F 15b15a /33.7:B /11.3:A -TA5:G 5b5a -TA1:G /11.1:A
383
/19.2:E -PL1:J2-4 5d5c
209
6b6a -TA9:G /11.6:A
Terminal 6d6c
排
E =SG+-XB12 E
POS Ext Target Short Int Target POS
放置 外部目标 短接 内部目标 放置
623
1b1a -KM35:11 /33.4:A
622
2b2a -KM35:14 /33.4:A
619
3b3a -PT:J12-6 /32.4:E
620
4b4a -PT:J12-2 /32.4:F
F F
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
210
2d2c -TA49:+ /11.6:D 7b7a 7b7a
540 608 585
3b3a -PL2:J2-6 /28.2:E 8b8a -PT:J5-16 /32.2:C 8b8a -PT:J9-11 /32.2:B
187 154
/11.3:D -TA45:- 3d3c -TA41:- /11.1:D 9b9a 9b9a
193 169 588 600
/11.4:D -TA46:- -TA42:- /11.2:D 10b10a -PT:J5-15 /32.2:C 10b10a -PT:J9-14 /32.2:B
C C
199 175
/11.5:D -TA47:- -TA43:- /11.2:D 11b11a 11b11a
205 181 590 584
/11.5:D -TA48:- -TA44:- /11.3:D 12b12a -PT:J5-7 /32.2:D 12b12a -PT:J9-13 /32.2:B
541
5b5a -PL2:J2-4 /28.2:E 15b15a 15b15a
188 156 591 583
D /11.3:D -TA45:G 5d5c -TA41:G /11.1:D 16b16a -PT:J5-5 /32.2:D 16b16a -PT:J9-15 /32.2:B D
194 170
/11.4:D -TA46:G -TA42:G /11.2:D 17b17a
200 176 587
/11.5:D -TA47:G -TA43:G /11.2:D 18b18a -PT:J9-7 /32.2:B
206 182
/11.5:D -TA48:G -TA44:G /11.3:D 19b19a
605
6b6a 20b20a -PT:J9-8 /32.2:B
212
6d6c -TA49:G /11.6:D
E E
F F
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
P-D-000508 P-A-000776
B PL1 PA1 B
支路电流与绝缘监测板 微机板
Disconnect DC combiner box before maintaining PL1 board or fuse. Disconnect AC combiner box before maintaining PA1 board.
C C
D
P-D-000508 P-A-000776 D
PL2 PA2
支路电流与绝缘监测板 微机板
E Disconnect DC combiner box before maintaining PL2 board or fuse. Disconnect AC combiner box before maintaining PA2 board. E
F F
Checked by taonl Date 2022/7/29 Drawing Name 电路板安规标签示意PCB safety standards label
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
阳光电源股份有限公司
Sungrow Power Supply Co., Ltd.
B B
客户名称
Customer name
C 产品名称 户外型中压一体机 C
Product name Outdoor Inverter Of Medium Voltage
产品型号 SG6250HV-MV-V1241 Distribution & MV
Product model
项目名称
D Project name D
电气标准 IEC/GB
Electrical standard
防护等级 IP54
Level of protection
主电路电压 3PH 600VAC
Main circuit voltage
E
辅助电源电压 400/230VAC E
AUX power voltage
控制电源电压 24VDC/200VDC
Control supply voltage
F F
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
目录Contents A-SJ-02773 SG6250HV-MV-V1241英文目录表格
C C
D D
E E
F F
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
S2 S1
-T1
5 1 7 3
3 1 2
P2 P1
6 2 8 4
3+PE
4turns 3 4
1 5 8
1 2
630 PF 486 SF NET_A NET_B NET_C
L
13 23 2
3 4 位号(XX)
600V PT
N 14 24 功能单元(XXX)
5 6
0V PS 0V SS
C 7 8 系统单元(XXXX) C
D GND -GND2 -T 2
D
Θ
常规接地 外壳地
Chassis ground 3 3
Functional ground
1
160℃
Θ
A 600V 2 箱变变压器(单线图) 温控继电器
main transformer temperature relay
400V a
B 600V
400V b
E E
400V c 3 2
C 600V
+ - S G
0V n L
-GND
保护接地 电流传感器
Protective ground Current sensor
配电三相变压器 温控开关 网口
Three phases transformer
thermal control Ethernet
F F
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
2 3 L 棕 N
1 4
M
LDE2 1~
PE
B B
烟感 单相轴流风机 负荷开关 带底座熔丝 指示灯 接触器主触点
Smoke detector Single-phase axial fan Load break switch Fuse-disconnector Signal light Contactor main contact
3
C C
2
D D
SG6250HV-MV-V1241一体机布局简图 SG6250HV-MV-V1241 Outdoor Inverter of medium voltage location map :
E E
箱变
Oil transformer
逆变器N2
逆变器N1
环网柜
Inverter N2 Inverter N1 RMU
配电柜
Distribution
F F
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
配电柜 Power Distribution Cabinet Confidential
RMU_NA_36kV_SAFE36_20220523
C v -QS4 -FU102~FU104 -T3 -QF3C63A/4P
-QF4
3 3 3 C32A/4P/30mA
3 3 4
N1:L1/L2/L3
4 4
A M 逆变器交流输出铜排 熔丝fuse:690V/63A -QF5 A
Inverter AC output 1000V/50A 底座hoder:690V/125A C32A/4P/30mA
copper bar 600Vac/400Vac/20KVA 4
4
-QF6
C16A/4P/30mA
4
3 -FU100 4
熔丝Fuse:3*1000V/40A -QF7
底座Holder:1000V/40A C16A/4P/30mA
REF601 4
4
BR
XK1:230V配电端子
3 -SPD4 230V distribution terminal
3 SPD -QF8
B C32A/2P/30mA B
2
AHY10WZ(36)-45/129.5 2
S1 S1 S1
2 2 2 -QF9
C32A/2P/30mA
2
S2 S2 S2 GND 2
C
2
C
2
C
2
-QF10
C16A/2P/30mA
2
2
D D D
-QF11
SAFE36
GNYE C10A/2P
2AWG 2
2
-QF14
C10A/2P
2
GND 2
2
HV_Transf_6250kVA_NA_50℃
等电位连接铜排,或平板箱、集装箱就近接地
Equipotential connection copper bar 36kV屏蔽前接头-70 IN
AQT3-36/630K/70
Tier1_33/0.6-0.6kV_S
2KVA
UPS
D D
3
OUT -QF15
C16A/2P/30mA
2
配电柜插座
SFL-6250/33
2
-T Power Distribution Cabinet socket
-QF16
C10A/2P
GNYE 2
欧变
2AWG
3 3 2
-QF17
C10A/2P
GND 2
等电位连接铜排,或平板箱、集装箱就近接地 2
Equipotential connection copper bar 2
E 逆变器N1端子XB11
XK3:220V配电端子(UPS) E
220V distribution terminal(UPS)
Inverter N1 terminal XB11
2
N1-XB11:5b/6b XK2:24V配电端子
24V distribution terminal
SG3125HV-V33
SG3125HV-V33
逆变器N2端子XB11
N1 3 N2 3 Inverter N2 terminal XB11 2
N2-XB11:5b/6b XK4:24V配电端子
3 3 ★备注Notice: 24V distribution terminal
RS485
COM8 COM9
SLD MLD
2 2 SPD4 PN3 or FL4
GNYE
GNYE GNYE 2AWG
2AWG 2AWG
1 2 3 4 5 6 7 8
F
E
D
C
B
A
1
1
-XSG
BK
11.7:B / XSG-1/XK3-1c 001 15AWG RMU 220Vac-L
1
BK
11.8:B / XSG-2/XK3-3c 002 15AWG RMU 220Vac-N
2
3
RMU +/L
2
2
4
RMU -/N
BK
3b
/ XSG-5/XB12-3b
DO2
123 17AWG
5
RMU VCB remote closing-NO
control
operation
N1-XB12:
BK
4b
RMU closing
/ XSG-6/XB12-4b 124 17AWG RMU VCB remote closing-COM
6
BK
DO3
1b
/ XSG-7/XB12-1b 68 17AWG RMU VCB Tripping-NO
BK 7
control
/ N2-XB12-1b/N1-XB12-1b
1b
DO3
77 17AWG
operation
N1-XB12:
BK
RMU Tripping
2b
control
/ XSG-8/XB12-2b 69 17AWG RMU VCB Tripping-COM
8
operation
N2-XB12:
/ N2-XB12-2b/N1-XB12-2b BK
2b
78 17AWG
RMU Tripping
BK
/ XSG-9/XZ3-13b 119 17AWG RMU Load Switch1 state-NO
13b
9
MV Load
Switch 2
N1-XZ3:
BK
3
3
10
BK
/ XSG-11/N2-XZ2-15b 123 17AWG RMU Earthing Switch1 state-NO
15b
11
Switch 2
N2-XZ2:
BK
/ XSG-12/N2-XZ2-16b 124 17AWG RMU Earthing Switch1 state-COM
16b
12
MV Earthing
14
RMU Load Switch2 state-COM
15
RMU Earthing Switch2 state-NO
4
4
16
RMU Earthing Switch2 state-COM
MV
BK
/ XSG-17/XZ2-11b 121 17AWG RMU Disconnector state-NO
11b
17
Switch
N1-XZ2:
BK
/ XSG-18/XZ2-12b 122 17AWG RMU Disconnector state-COM
Disconnector
12b
18
BK
/ XSG-19/XZ3-17b 123 17AWG RMU Earthing Switch3 state-NO
17b
19
Switch 3
N1-XZ3:
BK
/ XSG-20/XZ3-18b 124 17AWG RMU Earthing Switch3 state-COM
18b
20
MV Earthing
BK
/ XSG-21/XZ3-15b 123 17AWG RMU VCB state-NO
15b
21
N1-XZ3:
MV Vacuum
BK
/ XSG-22/XZ3-16b 124 17AWG RMU VCB state-COM
16b
22
Circuit-Breaker
5
5
BK
9b
BK
HV Remote
124 17AWG
24
Drawn by
RD
Checked by
13.4:B / XSG-25/XB13-17b 20AWG RMU RS485-A+
Approved by
RS485
17b
25
Internal
N1-XB13:
BK
13.4:B / XSG-26/XB13-18b 20AWG RMU RS485-B-
Communication
18b
26
XUWT
Jochen
Maggie
27
RMU RS485-GND
Date
Date
Date
28
RMU VCB remote opening-NO
6
6
29
RMU VCB remote opening-COM
30
RMU Low Gas Pressure state-NO
2022/10/19
2022/10/19
2022/10/19
31
RMU Low Gas Pressure state-COM
32
33
Drawing NO.
Drawing Name
Product Model
34
7
7
35
A-SJ-02773-JL-A
8
8
Page 6
A A
FA11-N/XK1-4a /11.5:B
SQ3-21/XK1-1d /11.4:D
SW3-1/XK4-3b / 12.8:C
SW3-2/XK4-1b / 12.7:C
J1-11/XK1-2a / 11.5:B
H4-N/XK1-3d / 11.5:D
B B
BK RD
20AWG 20AWG
-W53
2x20AWG
012 014
004 009 BK BK
BK BK 17AWG 17AWG
17AWG 17AWG
BK RD
20AWG 20AWG
-W54
2x20AWG
003 007
C BK
17AWG
BK
19AWG
C
1 1 2 1 2 -X6 017
-B6 019
-B5 020
-B4 021
-B3 022
-B2 023
-B1 018
- R
- R
LDE2
- Y
LDE2
- Y
LDE1
LDE1
-SW3 -SW4
+
+
+
4 3 4 3 BK BK BK BK BK BK BK
-TK01 P-D-000282 P-D-000282
+ 9AWG 9AWG 9AWG 9AWG 9AWG 9AWG 9AWG
2 -10~+50℃可设定 + - + - + - + - + - + -
11 41 P-D-000234 V3 P-D-000234 V3
011
-J1 BK -
19AWG
/7.2:C 14 44 6节12V铅酸蓄电池
A1 13 6 12V lead-acid batteries
/7.2:D 21
-J1 220VAC
-SQ3
015
A2
-SQ3 BK
17AWG UPS安装在配电柜
240VAC/3A 240VAC/3A 14 UPS installed in power distribution cabinet
006 22 016
BK 008 /7.4:D /7.3:D
BK
17AWG BK
17AWG
19AWG
D 005 013
D
BK BK 112 111 061 058
17AWG 17AWG BK BK BK BK
17AWG 17AWG 17AWG 17AWG
L BU N BK
-FA11
M
L
1~ 5b 6b 13b 14b
-H4
PE GNYE 220V N1-XZ3: N1-XZ2:
230V N
010 SY-1*18-A HV Room HV Room
GNYE Door Smoke
19AWG
-GND2
E E
/ SQ3-14/XZ3-5b
/ SQ3-13/XZ3-6b
/ SW3-4/XZ2-13b
/ SW3-3/XZ2-14b
11 14 /7.1:C
41 44 /7.2:C
接至逆变器N1
A1 A2 /7.2:D To the inverter N1
F F
Checked by Maggie Date 2022/10/19 Drawing Name 环网柜接线图2 Wiring diagram of RMU 2
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
XT1-20/XB11-11b /
XT1-21/XB11-10b /
XT1-22/XB11-12b /
XT1-30/XZ3-19b /
/
XT1-17/XZ2-10b /
XT1-28/XB11-1b /
XT1-29/XB11-2b /
XT1-31/XZ3-20b /
XT1-32/XZ2-15b /
XT1-33/XZ2-16b /
XT1-13/XZ3-3b /
XT1-16/XZ2-9b /
/
/
XT1-1/XZ2-7b /
XT1-14/XZ3-4b
XT1-18/XZ3-1b
XT1-19/XZ3-2b
XT1-2/XZ2-8b
XT1-8/XZ3-7b
XT1-9/XZ3-8b
XT1-3/XZ2-5b
XT1-4/XZ2-6b
B B
RD BK
20AWG 20AWG
-W55
C 2x20AWG C
XT1-24/XK1-2b / 11.5:D
XT1-25/XK1-4b / 11.5:D
088 17AWG
089 17AWG
090 17AWG
091 17AWG
092 17AWG
093 17AWG
094 17AWG
095 17AWG
096 17AWG
097 17AWG
098 17AWG
099 17AWG
100 17AWG
101 17AWG
102 17AWG
024 15AWG
025 15AWG
582 17AWG
582 17AWG
067 17AWG
068 17AWG
D D
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
-XT1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 24 25 28 29 30 31 32 33
油温PT100信号
R3
4~20mA
4~20mA
高温报警
超温跳闸
火线L
零线N
-20℃~120℃
高温报警
超温跳闸
输出:+
输出:-
OTI-PT100
GR-K1
GR-K2
PR-K1
PR-K2
OL-K1
OL-K2
OTI-K2
OTI-K3
WTI-K1
WTI-K2
轻瓦斯
重瓦斯
跳闸1
跳闸2
跳闸1
跳闸2
100℃
alarm
105℃
120℃
trip
报警
跳闸
95℃
R2 68 69 85 86
AC220V 0℃~160℃
E R1 绕组温度计 E
气体继电器GR 压力释放阀PR 油位信号OL 油面温控器OTI 绕组温控器 WTI
gas relay GR pressure valve PR Oil level gauge Oil thermometer OTI winding thermometer WTI
F F
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
/ 9.8:B
QF12-1/QF3-6 / 9.8:B
QF8-1/QF3-2 /9.8:A
QF8-3/QF3-8 /9.8:B
QF9-1/QF3-4
B B
078
BK
11AWG
C 076
BK
083
BK
087
BK
089
BK
C
11AWG 蓝色套管 11AWG 红色套管 11AWG 红色套管 13AWG 红色套管
077
Blue sleeve
088
Red sleeve
090
Red sleeve
QF14-1/X1-L/ 11.2:B
BK BK BK BK BK BK BK
9AWG 白色套管 9AWG 白色套管 9AWG 白色套管 9AWG 白色套管 11AWG 白色套管 11AWG 白色套管 13AWG 白色套管
White sleeve White sleeve White sleeve White sleeve White sleeve White sleeve White sleeve
QF14-3/X1-N/ 11.2:B
-QF8 1 3
-QF9 1 3
-QF10 1 3
-QF11 1 3
-QF12 1 3 1 3 1 3 UPS输入供电
-QF13 -QF14
C10A/2P 2 4 C10A/2P 2 4
D D
-GND PE L N
-X3
250V/16A
欧式插座
E 配电柜插座 E
F F
Checked by Maggie Date 2022/10/19 Drawing Name 配电柜接线图2Wiring diagram of distribution cabinet2
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
A A
X1-N/QF14-3/10.7:C
X1-L/QF14-1/10.7:C
接至N2逆变器
To the inverter N2
UPS-DB9-1/XZ2-13b /
UPS-DB9-5/XZ2-14b /
XK3-1a/QF17-1 /11.4:E
XK3-3a/QF17-3 /11.4:E
XK1-4a/FA11-N /7.2:B
XK1-1a/QF7-1 / 9.5:E
XK1-3a/QF7-7 / 9.5:E
XK1-2a/J1-11/7.1:B
XK3-1c/XSG-1/6.2:C
XK3-3c/XSG-2/6.2:C
XK1-5a/T3-n / 9.6:C
090 089
BK BK
13AWG 13AWG
094
B GNYE B
15AWG
N L PE
058 058
-X1 BK
17AWG
BK
17AWG
模数化插座
004 17AWG
009 17AWG
-GND
BK
BK
102 13AWG
001 15AWG
103 13AWG
002 15AWG
13b 14b
049 15AWG
059 15AWG
043 15AWG
GNYE
BK
BK
BK
BK
BK
BK
N2-XZ2:
配电柜UPS输出220V
UPS fault
alarm
配电柜230V供电
-XK1
-XK3
1d1c
2b2a
2d2c
3b3a
3d3c
4b4a
4d4c
5b5a
5d5c
6b6a
6d6c
1d1c
2b2a
2d2c
3b3a
3d3c
4b4a
4d4c
1b1a
1b1a
IN:N IN:L IN:GND
RelayI/O
DC:+
UPS DB9 1
012 17AWG
024 15AWG
014 17AWG
025 15AWG
105 17AWG
106 17AWG
107 17AWG
108 17AWG
104 15AWG
BK
BK
BK
BK
BK
BK
BK
BK
GNYE
-X2 -X5
插头 N L PE 插头 N L PE
(若孔太细用15AWG)
(若孔太细用15AWG)
7.3:B / XK1-1d/SQ3-21
8.6:D / XK1-2b/XT1-24
8.6:D / XK1-4b/XT1-25
12.2:B / XK3-1b/PE5-J1-3
12.6:B / XK3-2d/PE6-J1-3
12.2:B / XK3-3b/PE5-J1-1
12.6:B / XK3-4d/PE6-J1-1
7.3:B / XK1-3d/H4-N
091
BK
093
BK
095
GNYE
★注意:备用插头,插在UPS输出口
13AWG 13AWG 19AWG -GND
D -GND 配电柜就近接地 D
Distribution cabinet
grounding in close proximity
1 3
-QF15 1 3 1 3
-QF16 -QF17
11.7:B / QF17-1/XK3-1a
11.8:B / QF17-3/XK3-3a
C10A/2P 2 4 C10A/2P 2 4
E E
C16A/2P/30mA 2 4
092 097 099
GNYE BK BK
15AWG 11AWG 11AWG
-GND PE L N
-X4
250V/16A 至UPS输出端子XK3
欧式插座
配电柜插座
F F
UPS附近贴如下标签:
The UPS operation panel is at the rear of this location. Drawn by XUWT Date 2022/10/19 Drawing NO. A-SJ-02773-JL-A Page 11 of 14
Facing the operation panel, Checked by Maggie Date 2022/10/19 Drawing Name 配电柜接线图3Wiring diagram of distribution cabinet3
the" "button is on the left and the TEST button is on the right.
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
引至逆变器 N1 引至逆变器 N2
From the inverter N1 From the inverte N2
XK2-1a/XB11-5b /
XK2-3a/XB11-6b /
XK4-1a/XB11-5b /
XK4-3a/XB11-6b /
A A
PE5 PE6
078 17AWG
079 17AWG
082 17AWG
085 17AWG
BK
BK
BK
BK
107 108
BK BK
配电柜24VDC供电(N1)
配电柜24VDC供电(N2)
-PE5 AC1-N 1
17AWG
PE5-J1-1/XK3-3b/11.8:D -PE6 AC1-N 1
17AWG
PE6-J1-1/XK3-4d/11.8:D
B B
-XK2
-XK4
1d1c
2b2a
2d2c
3b3a
3d3c
4b4a
4d4c
1d1c
2b2a
2d2c
3b3a
3d3c
4b4a
4d4c
1b1a
1b1a
105 106
P-E-000282 P-E-000282
2 BK 2 BK
17AWG 17AWG
交 AC1-L 3 PE5-J1-3/XK3-1b/11.7:D 交 AC1-L 3 PE6-J1-3/XK3-2d/11.7:D
流 J1 4 流 J1 4
输 +24V +24V 0V 0V 输 +24V +24V 0V 0V
入 AC2-L 5 入 AC2-L 5
6 1b、1c、1d、 3b、3c、3d、 6 1b、1c、1d、 3b、3c、3d、
2a、2b、2c、2d: 4a、4b、4c、4d: 2a、2b、2c、2d: 4a、4b、4c、4d:
AC2-N 7 109
BK
+24V 0V
AC2-N 7 113
BK
+24V 0V
电 17AWG 电 17AWG
源 1 PE5-J2-1/XK2-2b/12.4:C 源 1 PE6-J2-1/XK4-2b/12.7:C
对 +22V 2 对 +22V 2
顶 顶
109 17AWG
110 17AWG
20AWG
113 17AWG
20AWG
114 17AWG
110 114
板 3 BK 板 3 BK
BK
BK
RD
BK
BK
BK
17AWG 17AWG
4 PE5-J2-4/XK2-4b/12.4:C 4 PE6-J2-4/XK4-4b/12.8:C
C 直 SGND 5 直 SGND 5 C
流
J2 6 流
J2 6
输 输
7.5:B / XK4-1b/SW3-2
7.4:B / XK4-3b/SW3-1
7 7
12.2:C / XK2-2b/PE5-J2-1
12.2:C / XK2-4b/PE5-J2-4
12.6:C / XK4-2b/PE6-J2-1
12.6:C / XK4-4b/PE6-J2-4
出 出
+24V 8 +24V 8
9 9
NO 10 NO 10
C 11 C 11
NC 12 NC 12
D D
至逆变器N1 1
network cable
-EDS
111
BK
1 3 5 Optical fiber 2
E 17AWG
24V E
112
BK
17AWG Optical fiber
OV 2 4 6
3
network cable
交换机
Switch
4
23
至逆变器N2
To the inverter N2 24
F F
Checked by Maggie Date 2022/10/19 Drawing Name 配电柜接线图4Wiring diagram of distribution cabinet4
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
逆变器 N1和N2之间RS485通讯接线The RS485 communication between inverter N1 and N2
逆变器 N1端子 inverter N1 terminal 逆变器 N2端子 inverter N2 terminal
A A
-XB13
-XB13
10b10a
11b11a
12b12a
13b13a
14b14a
15b15a
16b16a
17b17a
18b18a
10b10a
11b11a
12b12a
13b13a
14b14a
15b15a
16b16a
17b17a
18b18a
2b2a
3b3a
4b4a
5b5a
6b6a
7b7a
8b8a
9b9a
2b2a
3b3a
4b4a
5b5a
6b6a
7b7a
8b8a
9b9a
1b1a
1b1a
H L GND GND A B A B GND GND A B A B GND GND A B H L GND GND A B A B GND GND A B A B GND GND A B
1b、2b、3b: 4b、5b、6b: 7b、8b、9b: 10b、11b、12b: 13b、14b、15b: 16b、17b、18b: 1b、2b、3b: 4b、5b、6b: 7b、8b、9b: 10b、11b、12b: 13b、14b、15b: 16b、17b、18b:
Reserved CAN Data Forwarding Reserved RS485 Reserved RS485 Internal Communication Internal Communication Reserved CAN Data Forwarding Reserved RS485 Reserved RS485 Internal Communication Internal Communication
to Background RS485 RS485 to Background RS485 RS485
RS485 RS485
COM5 COM6 COM7 COM8 COM9 COM5 COM6 COM7 COM8 COM9
RD BK
20AWG 20AWG
B -W2 UL2661 20AWG×2C/2×0.519mm²/黑/双绞
UL2661 20AWG×2C/2×0.519mm²/black/twisted-pair cable
B
2x20AWG
6.5:C / XB13-17b/XSG-25
6.6:C / XB13-18b/XSG-26
C C
-W1
2x20AWG
BK 20AWG
RD 20AWG
UL2661 20AWG×2C/2×0.519mm²/黑/双绞
UL2661 20AWG×2C/2×0.519mm²/black/twisted-pair cable
D D
-XB12
-XB12
2b2a
3b3a
4b4a
2b2a
3b3a
4b4a
1b1a
1b1a
7 8
E E
NO COM NO COM NO COM NO COM
1b、2b: 3b、4b: 1b、2b: 3b、4b:
DO3 DO2 DO3 DO2
RMU Tripping RMU closing RMU Tripping RMU closing
operation operation operation operation
control control control control
69 078
BK BK
17AWG 17AWG
68 077
BK BK
17AWG 17AWG
F F
Checked by Maggie Date 2022/10/19 Drawing Name 逆变器N1和N2之间接线Wiring diagram of Inverter N1&N2
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Confidential
Terminal Terminal
排 排
=SG+-XK1 =SG+-XK3
A A
POS Ext Target Short Int Target POS POS Ext Target Short Int Target POS
放置 外部目标 短接 内部目标 放置 放置 外部目标 短接 内部目标 放置
049 105 102
1b1a -QF7:1 /9.6:F /12.2:B -PE5:J1-3 1b1a -QF17:1 /11.4:E
012 001
/7.3:D -SQ3:21 1d1c 1d1c -XSG:1 /6.2:B
024 004
/8.6:D -XT1:24 2b2a -J1:11 /7.1:C 2b2a
106
2d2c /12.6:B -PE6:J1-3 2d2c
059 107 103
B 3b3a -QF7:7 /9.6:F /12.2:B -PE5:J1-1 3b3a -QF17:3 /11.4:E B
014 002
/7.3:D -H4:N 3d3c 3d3c -XSG:2 /6.2:B
025 009
/8.6:D -XT1:25 4b4a -FA11:N BK /7.1:D 4b4a
108
4d4c /12.6:B -PE6:J1-1 4d4c
043
5b5a -T3:0V n /9.4:B
5d5c
C 6b6a C
104
/11.6:D -GND 6d6c
Terminal Terminal
排 排
D D
=SG+-XK2 =SG+-XK4
POS Ext Target Short Int Target POS POS Ext Target Short Int Target POS
放置 外部目标 短接 内部目标 放置 放置 外部目标 短接 内部目标 放置
1b1a /7.5:C -SW3:2 1b1a
111
/12.5:E -EDS-24V 1d1c 1d1c
109 113
/12.2:C -PE5:J2-1 2b2a /12.6:C -PE6:J2-1 2b2a
2d2c 2d2c
E E
3b3a /7.4:C -SW3:1 3b3a
112
/12.5:E -EDS-OV 3d3c 3d3c
110 114
/12.2:C -PE5:J2-4 4b4a /12.6:C -PE6:J2-4 4b4a
4d4c 4d4c
F F
Approved by Jochen Date 2022/10/19 Product Model A-SJ-02773 SG6250HV-MV-V1241 Distribution & MV
1 2 3 4 5 6 7 8
Transformadores MT y unidad principal de anillo
XT1
Aclaración NOTA TER.NO NOTA
XT1-1
1
ALARMA XT1-2
2
GR XT1-3
RELÉ PRINCIPAL BUCHOLZ GR INDICADOR DE TEMPERATURA DE ACEITE OTI INDICADOR DE TEMPERATURA DE DEVANADO WTI 3
TRIP XT1-4
4
XT1-1 11 XT1-30 5
A1 K1 XT1-31 ALARMA XT1-6
ALARMA 14 6
GR-K1 K1 A2 XT1-32 TRIP1 XT1-7
XT1-2 21 7
XT1-16 K2 24 XT1-33 TRIP PR XT1-8
B1 XT1-34
8
31 TRIP2 XT1-9
XT1-3 K2 ALARMA B2 XT1-17 XT1-35 TRIP 9
K3 34 10
GR-K2 TRIP C1 XT1-18 41 XT1-11
XT1-4 K4 11
K3 TRIP C2 XT1-19 44 TRIP XT1-12
XT1-28 12
OL XT1-13
XT1-20 4~20mA XT1-29 4~20mA(0℃-160℃) 13
R3 TRIP XT1-14
XT1-24 14
PT100
R2 XT1-21 68
AC220V XT1-25 AC220V 15
DISPOSITIVO PRINCIPAL DE ALIVIO DE PRESIÓN PR R1 XT1-22 69 16 XT1-16
ALARMA XT1-17
17
XT1-6 91 B422 S1 S2
HCT2b OTI XT1-18
18
*
TRIP XT1-19
PR-K1 NO ( TRIP ) N422 0.5 19
XT1-7 92 20 XT1-20
21 XT1-21
PT100
XT1-8 22 XT1-22
23
PR-K2 NO ( TRIP ) XT1-9 XT1-24
L 24
AC220V XT1-25
N 25
26
PE 27
4~20mA(+) 28 XT1-28
4~20mA(-) 29 XT1-29
30 XT1-30
INDICADOR DE NIVEL DE ACEITE PRINCIPAL OL
ALARMA XT1-31
31
XT1-11 XT1-32
NOT A: WTI TRIP
32
XT1-33
OL-K1 33
NO ( TRIP ) XT1-12 Rango de medición de temperatura OTI: -20 ~ 120 ℃, interruptores: K2 = 95 ℃ (ALARMA); K3 = 100 ℃ XT1-34
34
TRIP XT1-35
(DISPARO). 35
XT1-13 Rango de medición de temperatura WTI: 0~160 ℃, interruptores: K1 = 105 ℃ (ALARMA); K2 = 120 ℃ 36
37
OL-K2 NO ( TRIP ) XT1-14 (DISPARO); K3 = 120 ℃ (DISPARO).
38
PT100, 4~20mA. El blindaje de la lista de señales debe conectarse a tierra en el lado del 39
dispositivo.
El contacto de protección en el archivo adjunto es normalmente un nodo abierto, que se cierra cuando
se activa la señal de protección.
Con ectado al INV SCU1
光伏总承
M E1 包
CE
项
智利
目
部
APROBADO PARA
C E M E1 P
C HI LE
CONSTRUCCIÓN
EN
RO
EC
CO
Y
TO AI
FOTOVOLT
Contacto en seco
RMU swtich de tierra2 estado-NO 15 (SCU-Entrada digital)
Interruptor de puesta a tierra2 cerrada cuando está cerrada RMU swtich de tierra2 estado-COM 16
RMU Estado del seccionador RMU desconectador estado-NO 17
Cierre del seccionador cuando está cerrado RMU desconectador estado-COM 18
RMU Estado del seccionador de puesta a tierra3 RMU swtich de tierra3 estado-NO 19
V Interruptor de puesta a tierra 3 cerrada cuando está cerrada RMU swtich de tierra3 estado-COM 20
(DI) RMU Estado VCB RMU VCB estado-NO 21
(SCU-DI)
(SCU-Entrada digital)
Contacto en seco VCB cerrada cuando está cerrada RMU VCB estado-COM 22
Estado del control remoto RMU RMU Control remoto estado-NC 23
Mando a distancia cuando está cerrado RMU Control remoto estado-COM 24
RMU RS485-A+ 25
(SCU-DI)
(RS485) Comunicación RMU RS485 RMU RS485-B- 26 (Puerto de entrada de com. SCU-RS485)
RMU RS485-GND 27
RMU Remota abierta RMU VCB apertura remota-NO 28
(DO) (SCU-DO)
VCB abierta cuando está cerrada RMU VCB apertura remota-COM 29 (SCU-Salida digital)
Contacto en seco
30
31
32
33
34
35
1 光 伏总 承包
ME
CE
项
智利
目
部
APROBADO PARA
C E M E1 P
C H I LE
CONSTRUCCIÓN
EN
RO
EC
CO
Y
TO AI
FOTOVOLT
enchufe de distribucion
1 光 伏总 承包
ME
CE
项
智利
目
部
APROBADO PARA
C E M E1 P
C H I LE
CONSTRUCCIÓN
EN
RO
EC
CO
Y
TO AI
FOTOVOLT
1 光 伏总 承包
ME
CE
项
智利
目
部
APROBADO PARA
C E M E1 P
C H I LE
CONSTRUCCIÓN
EN
RO
EC
CO
Y
TO AI
FOTOVOLT
项
智利
目
部
APROBADO PARA
C E M E1 P
C HI LE
CONSTRUCCIÓN
EN
RO
EC
CO
Y
TO AI
FOTOVOLT
A 20/10/2022 INICIAL / INITIAL D.V.E. P.J.L. E.P.L. PHOTOVOLTAIC PLANT DETALLES DE EQUIPAMIENTO DE COMUNICACIONES EN
ESTACION TRANSFORMADORA CEME1-ID-PV-ES-DWG-009
FECHA/ EJEC/ REV/ APR/ DIBUJO/EXECUTED PROYECTO/PROJECT CONTROLO/AUDITED APROBO/VALIDATED FECHA/DATE ESCALA/SCALE LAMINA/PAGE REV.
N° MODIFICACIONES/MODIFICATIONS D.V.E. M.M.R P.J.L. E.P.L. 25/01/2023 S.E./N.T.S 01 OF 04 0
DATE EXEC AUDI VALI
1 光 伏总 承包
ME
CE
项
智利
目
部
APROBADO PARA
C E M E1 P
C H I LE
CONSTRUCCIÓN
EN
RO
EC
CO
Y
TO AI
FOTOVOLT
A 20/10/2022 INICIAL / INITIAL D.V.E. P.J.L. E.P.L. PHOTOVOLTAIC PLANT DETALLES DE EQUIPAMIENTO DE COMUNICACIONES EN
ESTACION TRANSFORMADORA CEME1-ID-PV-ES-DWG-009
FECHA/ EJEC/ REV/ APR/ DIBUJO/EXECUTED PROYECTO/PROJECT CONTROLO/AUDITED APROBO/VALIDATED FECHA/DATE ESCALA/SCALE LAMINA/PAGE REV.
N° MODIFICACIONES/MODIFICATIONS D.V.E. M.M.R P.J.L. E.P.L. 25/01/2023 S.E./N.T.S 02 OF 04 0
DATE EXEC AUDI VALI
Transformador
de aceite
1 光 伏总 承包
ME
CE
项
智利
目
部
APROBADO PARA
C E M E1 P
C H I LE
CONSTRUCCIÓN
EN
RO
EC
CO
Y
TO AI
FOTOVOLT
A 20/10/2022 INICIAL / INITIAL D.V.E. P.J.L. E.P.L. PHOTOVOLTAIC PLANT DETALLES DE EQUIPAMIENTO DE COMUNICACIONES EN
ESTACION TRANSFORMADORA CEME1-ID-PV-ES-DWG-009
FECHA/ EJEC/ REV/ APR/ DIBUJO/EXECUTED PROYECTO/PROJECT CONTROLO/AUDITED APROBO/VALIDATED FECHA/DATE ESCALA/SCALE LAMINA/PAGE REV.
N° MODIFICACIONES/MODIFICATIONS D.V.E. M.M.R P.J.L. E.P.L. 25/01/2023 S.E./N.T.S 03 OF 04 0
DATE EXEC AUDI VALI
Transformador de corriente
1 光 伏总 承包
ME
CE
项
智利
目
部
APROBADO PARA
C E M E1 P
C H I LE
CONSTRUCCIÓN
EN
RO
EC
CO
Y
TO AI
FOTOVOLT
A 20/10/2022 INICIAL / INITIAL D.V.E. P.J.L. E.P.L. PHOTOVOLTAIC PLANT DETALLES DE EQUIPAMIENTO DE COMUNICACIONES EN
ESTACION TRANSFORMADORA CEME1-ID-PV-ES-DWG-009
FECHA/ EJEC/ REV/ APR/ DIBUJO/EXECUTED PROYECTO/PROJECT CONTROLO/AUDITED APROBO/VALIDATED FECHA/DATE ESCALA/SCALE LAMINA/PAGE REV.
N° MODIFICACIONES/MODIFICATIONS D.V.E. M.M.R P.J.L. E.P.L. 25/01/2023 S.E./N.T.S 04 OF 04 0
DATE EXEC AUDI VALI
Public
1/ 27
Public
state
V1.2.1 2022-11-7 Modified some measuring points in the overall alarm state
in the appendix, added BIT 15144 PMD_IO1DI input state,
BIT 15145 heartbeat count, BIT 15146 UPS inverter state
and the appendix, BIT 15147 UPS alarm state and the
appendix, BIT 15630 ISO fault state and the appendix, BIT
15631 ISO alarm state and the appendix, BIT 15632 AC
insulation resistance, BIT 15633 overall alarm state 2 and
the appendix. Added 15128 overall fault state, BIT 11 RMU
current protection fault, and BIT12 RMU relay protection
communication fault.
Valid for:
SG3125HV-30
SG3125HV-MV-30
SG6250HV-MV
1. Introduction
This protocol is for communications between the grid-connected inverter of Sungrow and the background
monitoring system. Modbus RTU/Modbus TCP (optional for Ethernet port) is used. According to this
protocol, running data and fault state of the inverter can be read in real time. This protocol complies with
the GB/T 19582-2008 standard.
2. Physical Interface
(1) RS485
Default setting
Address Inverter: 1 to 247
settable
PC: 1 to 247 settable
Broadcast Yes
Baud rate 9600bit/s
Check bit Null or settable
Data bit 8
Stop bit 1
Mode RTU
Electrical RS485-2W cable
port connection
(2). Ethernet: (optional, default IP: 192.168.13.127; subnet mask: 255.255.255.0; and port number: 502).
2/ 27
Public
3. Communication Description
(1). Data type:
U16---16-bit unsigned integer, big-endian
S16---16-bit signed integer, big-endian
U32---32-bit unsigned integer; little-endian for double-word data. Big-endian for byte data
U32---32-bit signed integer; little-endian for double-word data. Big-endian for byte data
For example: The transmission order of U16 data 0x0102 is 01, 02.
For example, the transmission order of U32 data 0x01020304 is 03, 04, 01, 02
The transmission order of multibyte data UTF-8: the high-byte data is in the front and the low-byte data
is at back.
For example, the transmission order of the UTF-8 data "ABCD" is A, B, C, D.
(2). Value descriptions
The decimal parameters are transmitted as integer after expansion. For example, 10.333KW is
transmitted as 10 333, and 800.5V is transmitted as 8005. Negative numbers are transmitted as
complements, for example, 0xFFFF signifying -1.
"Reserved" or unavailable register cannot be viewed or set. The return of unsigned numbers is "F", for
example, "0xFFFF" is the return for U16, and "0xFFFFFFFF" is the return for U32; the return of signed
numbers is the max. positive number, for example, "0x7FFF" for S16, "0x7FFFFFFF" for S32; and
0x00 for UTF-8. UTF-8 occupies 1 byte. The length of odd number is complemented by 0x00.
(3). Address type
Address of 3x type is of read-only register, supporting the cmdcode inquiry of 0x04.
Address of 4x type is of holding register, supporting the cmdcode inquiry of 0x03, and cmdcodes write-
in of 0x10 and 0x06. Cmdcodes 0x10 and 0x06 support the broadcast address.
Support Modbus error code 02 (address error), 04 (setting failure).
Visit all registers by subtracting 1 from the register address. For example, if the address is 10000 to
10001, visit it using address 9999 10000. For example, "01 04 27 0F 00 02 + CRC" is used for
querying address data 10000 to 10001.
(4). Check type
CRC16 generates polynomial 0xA001, little-endian.
Regist
er Data Default
No. Item Factor Unit Note
addres type value
s
Overall running information
1 1 Protocol number 15000 U32
2 Protocol version 15002 U32
3/ 27
Public
4/ 27
Public
6/ 27
Public
7/ 27
Public
Register Default
No. Item Data type Factor Unit Note
address value
Zone Monitoring Overall running information
0:disable
1 16000 U16 1:self-study
zone monitor work state 2:fault detection
bit0~bit15:unit 1 branch
status(1~16);
bit16~bit31: unit 2 branch
2 16001 U32 1
status(1~16);
0:normal;1:open circuit
branch open circuit alarm fault
bit0~bit15: unit 1 branch
status(1~16);
bit16~bit31: unit 2 branch
3 16003 U32 1
status(1~16);
0:normal;1:string open
branch string alarm circuit fault
Zone Monitoring Running information of module 1
Warning number of strings
1 16005 U16 1
on branch 1 of unit 1
Warning number of strings
2 16006 U16 1
on branch 2 of unit 1
Warning number of strings
3 16007 U16 1
on branch 3 of unit 1
Warning number of strings
4 16008 U16 1
on branch 4 of unit 1
Warning number of strings
5 16009 U16 1
on branch 5 of unit 1
Warning number of strings
6 16010 U16 1
on branch 6 of unit 1
9/ 27
Public
10/ 27
Public
11/ 27
Public
12/ 27
Public
HV Remote Control 0 1 0
20 15026 U16 1
Trip
Reactive power
21 15027 U16 0.01 %/s 1 50000 1000
dispatch rise rate
Reactive power
22 dispatch decline 15028 U16 0.01 %/s 1 50000 1000
rate
Q(U) activation
23 15029 U16 0.1 % 0 1100 0
power point
0xA1: reactive
Genera power ratio mode;
l: 0xA1 0xA2: active power
24 QU operation mode 15030 U16 1 0xA1 0xA3
India: ratio mode: and
0xA3 0xA3: power factor
mode
0xB1: real-time
25 QU input voltage 15031 U16 1 0xB1 0xB2 0xB1 voltage; and 0xB2:
record voltage
Q(U) inductive
26 reactive power limit 15032 U16 0.1 % 0 1000 500
value
Q(U) capacitive
27 reactive power limit 15033 S16 0.1 % -1000 0 -500
value
Q(U) power factor
28 15034 U16 0.001 800 1000 900
end point
Q(U) power factor
29 15035 U16 0.001 800 1000 1000
start point
Q(U) voltage rise
30 15037 U16 0.1 % 1000 1100 1080
start point
Q(U) voltage rise
31 15038 U16 0.1 % 1000 1100 1100
end point
Q(U) voltage drop
32 15039 U16 0.1 % 900 1000 920
start point
Q(U) voltage drop
33 15040 U16 0.1 % 900 1000 900
end point
Automatic voltage
34 regulation 15043 U16 1 % 90 110 100
benchmark
Automatic voltage
35 regulation hystersis 15044 U16 1 % 0 10 1
(%)
13/ 27
Public
HV Remote Control 0 1 0
36 15049 U16 1
Closing
Actual Value Setting -2063 2063 0
KVa
37 of Reactive Power 15058 S16 1
r
Dispatching_Italy
DC switch 0xAA: open; 0x55:
38 15060 U16 1 0x55 0xAA 0x55
close/open control close
0xAA: enabled;
39 Night SVG switch 15061 U16 1 0x55 0xAA 0x55
0x55: disabled
40 Start waiting time 15062 U16 1 1s 0 600 60
Time for automatic
41 15063 U16 1 1s 20 1800 60
recovery from fault
42 DC starting voltage 15066 U16 0.1 V 8750 13000 9150
Frequency
0xAA: enabled;
43 modulation function 15073 U16 1 0x55 0xAA 0x55
0x55: disabled
switch
Frequency 0xA1: rated power;
44 regulation output 15074 U16 1 0xA1 0xA2 0xA1 0xA2: power before
change benchmark derating
50Hz grid
5000 5500 5020 Start point < end
Overfrequency point
45 15075 U16 0.01 Hz
derating start point 60Hz grid
6000 6500 6020 Start point < end
point
50Hz grid
5000 5500 5120 Start point < end
Overfrequency point
46 15076 U16 0.01 Hz
derating end point 60Hz grid
6000 6500 6120 Start point < end
point
Overfrequency
47 15077 U16 0.001 0 2000 400
derating factor
Overfrequency
48 15078 U16 0.1 % 0 1100 300
derating limit
0xB1: real-time
Frequency frequency
49 15079 U16 1 0xB1 0xB2 0xB2
regulation input type 0xB2: record
frequency
Frequency
50 regulation activation 15080 U16 0.1 % 0 1100 0
power
14/ 27
Public
50Hz grid
4500 5000 4980 End point < start
underfrequency point
51 15081 U16 0.01 Hz
rising start point 60Hz grid
5500 6000 5980 End point < start
point
50Hz grid
4500 5000 4880 End point < start
underfrequency point
52 15082 U16 0.01 Hz
rising end point 60Hz grid
5500 6000 5880 End point < start
point
underfrequency rise
53 15083 U16 0.001 0 2000 0
factor
Underfrequency
54 15084 U16 0.1 % 0 10000 300
rising limit
Leakage current U16 0.01 A 100 500 500
55 15088
protection value
0xAA: enabled;
56 Floating mode 15168 U16 1 0x55 0xAA 0x55
0x55: disabled
Active power control 0xAA: enabled;
57 15212 U16 1 0x55 0xAA 0xAA
closed-loop switch 0x55: disabled
Reactive power
0xAA: enabled;
58 control closed-loop 15213 U16 1 0x55 0xAA 0xAA
0x55: disabled
switch
59 Heartbeat 15246 U16 1 默认:0
Heartbeat time-out
60 15247 U16 1 0 3600 默认:0
period
61 QU_ExitPower 15251 U16 0,1 %
Power Recovery %/
62 15252 U16 1
Gradient min
Power Recovery %/
63 15253 U16 1
Gradient min
64 QP_EnterVoltage 15254 U16 0,1 %
65 QP_ExitVoltage 15255 U16 0,1 %
66 QP_ExitPower 15256 U16 0,1 %
Grid Connection
67 15257 U16 0,1 %
Maximum Voltage
Grid Connection
68 15258 U16 0,1 %
Minimum Voltage
15/ 27
Public
Grid Connection
60Hz range: 6002-
69 Maximum 15259 U16 0,01 Hz
6200
Frequency
Grid Connection
60Hz range: 5700-
70 Minimum 15260 U16 0,01 Hz
5998
Frequency
Grid Detection 0xAA: Enable;
71 15261 U16
Before Connection 0x55: Disable
72 Startup Wait Time 15262 U16 1 s
Active Power Soft 1: Enable; 0:
73 15263 U16 1
Start Disable
Reactive Power 1: Enable; 0:
74 15264 U16 1
Soft Start Disable
Regist
Defau
er Data Min. Max.
No. Item Factor Unit lt Note
addres type value value
value
s
Zone Monitoring Set Information
1:Enable; 0:
1 Zone monitoring 15800 U16 1 0 1
Disable
2 Sensitivity 15802 U16 1 1 7 5
3 Clear zone monitor data 15803 U16 1 0 1
4 Clear fault 15804 U16 1 0 1
Number of strings on
5 15805 U16 1 0 24 24
branch 1 of unit 1
Number of strings on
6 15806 U16 1 0 24 24
branch 2 of unit 1
Number of strings on
7 15807 U16 1 0 24 24
branch 3 of unit 1
Number of strings on
8 15808 U16 1 0 24 24
branch 4 of unit 1
Number of strings on
9 15809 U16 1 0 24 24
branch 5 of unit 1
Number of strings on
10 15810 U16 1 0 24 24
branch 6 of unit 1
Number of strings on
11 15811 U16 1 0 24 24
branch 7 of unit 1
Number of strings on
12 15812 U16 1 0 24 24
branch 8 of unit 1
Number of strings on
13 15813 U16 1 0 24 24
branch 9 of unit 1
16/ 27
Public
Number of strings on
14 15814 U16 1 0 24 24
branch 10 of unit 1
Number of strings on
15 15815 U16 1 0 24 24
branch 11 of unit 1
Number of strings on
16 15816 U16 1 0 24 24
branch 12 of unit 1
Number of strings on
17 15817 U16 1 0 24 24
branch 13 of unit 1
Number of strings on
18 15818 U16 1 0 24 24
branch 14 of unit 1
Number of strings on
19 15819 U16 1 0 24 24
branch 15 of unit 1
Number of strings on
20 15820 U16 1 0 24 24
branch 16 of unit 1
Number of strings on
21 15821 U16 1 0 24 24
branch 1 of unit 2
Number of strings on
22 15822 U16 1 0 24 24
branch 2 of unit 2
Number of strings on
23 15823 U16 1 0 24 24
branch 3 of unit 2
Number of strings on
24 15824 U16 1 0 24 24
branch 4 of unit 2
Number of strings on
25 15825 U16 1 0 24 24
branch 5 of unit 2
Number of strings on
26 15826 U16 1 0 24 24
branch 6 of unit 2
Number of strings on
27 15827 U16 1 0 24 24
branch 7 of unit 2
Number of strings on
28 15828 U16 1 0 24 24
branch 8 of unit 2
Number of strings on
29 15829 U16 1 0 24 24
branch 9 of unit 2
Number of strings on
30 15830 U16 1 0 24 24
branch 10 of unit 2
Number of strings on
31 15831 U16 1 0 24 24
branch 11 of unit 2
Number of strings on
32 15832 U16 1 0 24 24
branch 12 of unit 2
Number of strings on
33 15833 U16 1 0 24 24
branch 13 of unit 2
Number of strings on
34 15834 U16 1 0 24 24
branch 14 of unit 2
17/ 27
Public
Number of strings on
35 15835 U16 1 0 24 24
branch 15 of unit 2
Number of strings on
36 15836 U16 1 0 24 24
branch 16 of unit 2
5. Appendix
Overall work state
No. Item BIT Data range Note
1 Running BIT 0 1: Running
2 Stop BIT 1 1: Stop
Dry contact
3 BIT 2 0: normal; 1: protection
protection/External E-stop Reserved
4 Remote emergency stop BIT 3 0: normal; 1: protection
5 Door opening protection BIT 4 0: Disabled; 1: Enabled
6 Smoke protection BIT 5 0: normal; 1: protection
7 Local emergency stop BIT 6 0: normal; 1: protection
8 MV fault BIT 7 0: normal; 1: protection
9 Insulation failure BIT 8 0: normal/1: fault
10 DC Insulation Failure BIT 9 0: normal/1: fault
11 AC Insulation Fault BIT 10 0: normal/1: fault
12 Reserved BIT11~BIT32
Overall alarm state
No. Item BIT Data range Note
1 Reserved BIT0~BIT2
Abnormal communication of
2 BIT 3 0: normal; 1: abnormal
temperature board
3 Reserved BIT 4
4 Smoke Sensor Power Failure BIT 5 0: normal; 1: abnormal Apply Country: Spain
5 Insulation Alarm BIT 6 0: normal; 1: abnormal
6 M&S SCU com-state BIT7 0: normal; 1: abnormal
7 Heartbeat abnormal BIT8 0: normal; 1: abnormal
8 PMD IO Board Com-err BIT9 0: normal; 1: abnormal
9 Abnormal UPS AC ISO BIT10 0: normal; 1: abnormal
10 Inverter IO Board Com-err BIT11 0: normal; 1: abnormal
11 Reserved BIT12
12 Reserved BIT13
13 ISO-communication fault BIT14 0: normal; 1: abnormal
14 Reserved BIT15
Fault state 1
No. Item BIT Data range Note
1 DC undervoltage BIT 0 0: normal/1: fault
18/ 27
Public
Fault state 2
No. Item BIT Data range Note
1 Insulation impedance BIT 0 0: normal/1: fault
2 (AC) SPD fault BIT 1 0: normal/1: fault
3 Sampling fault BIT 2 0: normal/1: fault
4 (PV) polarity reversed BIT 3 0: normal/1: fault
Control power supply
5 BIT 4 0: normal/1: fault
abnormal
Backup power supply
6 BIT 5 0: normal/1: fault
abnormal
7 (AC) current unbalance BIT 6 0: normal/1: fault
19/ 27
Public
Alarm state 1
No. Item BIT Data range Note
1 Temperature abnormal alarm BIT 0 0: normal/1: alarm
2 Low insulation resistance BIT 1 0: normal/1: alarm
3 GFRT operation BIT 2 0: normal/1: alarm
4 CT unbalance BIT 3 0: normal/1: alarm
5 DC fuse abnormal BIT 4 0: normal/1: alarm
DSP-MDC communication Abnormal communication between
6 BIT 5 0: normal/1: alarm
abnormal DSP and meter plate
7 DC sensor abnormal BIT 6 0: normal/1: alarm
8 DC SPD alarm BIT 7 0: normal/1: alarm
9 AC SPD alarm BIT 8 0: normal/1: alarm
Bypass circuit breaker
10 BIT 9 0: normal/1: alarm
abnormal
20/ 27
Public
Node state
No. Item BIT Data range Note
0: disconnected/1:
1 AC circuit breaker state BIT 0
connected
0: disconnected/1:
2 AC main contactor state BIT 1
connected
3 ABC fault state BIT 12 0: normal/1: fault
4 ABC remote/local BIT 13 0: local/1: remote
Node state 2
No. Item BIT Data range Note
0: disconnected/1:
SPD node state BIT 12
1 connected
21/ 27
Public
0: disconnected/1:
DC switch state 1 BIT 20
2 connected
0: disconnected/1:
DC switch state 2 BIT 21
3 connected
0: disconnected/1:
DC switch state 3 BIT 22
4 connected
0: disconnected/1:
DC switch state 4 BIT 23
5 connected
22/ 27
Public
MV node state
No. Item BIT Data range Note
1 Gas Relay Trip BIT 0 0: open/1: close
2 Gas Relay Alarm BIT 1 0: normal/1: alarm
3 Oil Temperature Alarm BIT 2 0: normal/1: alarm
4 Oil Temperature Trip BIT 3 0: open/1: close
5 Low Oil Level Trip BIT 4 0: open/1: close
6 Reserved BIT 5
7 Pressure Relief Trip BIT 6 0: open/1: close
8 Reserved BIT 7
9 BIT 8 0: disconnected/1:
MV Load Switch 1 connected
10 BIT 9 0: disconnected/1:
MV Load Switch 2 connected
11 BIT 10 0: disconnected/1:
MV Vacuum Circuit-Breaker connected
12 BIT 11 0: disconnected/1:
MV Disconnector Switch connected
13 Reserved BIT 12
14 Reserved BIT 13
15 Winding Temperature Trip BIT 14 0: open/1: close
16 Winding Temperature Alarm BIT 15 0: normal/1: alarm
MV node state 1
No. Item BIT Data range Note
1 Reserved BIT 0
2 Reserved BIT 1
3 Reserved BIT 2
4 Reserved BIT 3
5 Reserved BIT 4
6 Reserved BIT 5
7 HV Room Door BIT 6 0: open/1: close
8 Reserved BIT 7
9 Reserved BIT 8
10 Reserved BIT 9
11 SF6 Low Pressure Alarm BIT 10 0: normal/1: alarm
12 External E-stop BIT 11 0: open/1: close AC Insulation Trip for RMU VCB
13 MV Fuse BIT 12 0: open/1: close
14 HV Room Smoke BIT 13 0: open/1: close
23/ 27
Public
DI input state
No Item BIT Data range Note
1 DI1 BIT 0 0: open/1: close
2 DI2 BIT 1 0: open/1: close
3 DI3 BIT 2 1: open/0: close
4 DI4 BIT 3 1: open/0: close
5 DI5 BIT 4 1: open/0: close
6 DI6 BIT 5 0: open/1: close
7 DI7 BIT 6 0: open/1: close
8 DI8 BIT 7 0: open/1: close
9 DI9 BIT 8 0: open/1: close
10 DI10 BIT 9 0: open/1: close
11 DI11 BIT 10 0: open/1: close
12 DI12 BIT 11 0: open/1: close
13 DI13 BIT 12 0: open/1: close
14 DI14 BIT 13 0: open/1: close
15 DI15 BIT 14 0: open/1: close
16 DI16 BIT 15 0: open/1: close
17 DI17 BIT 16 0: open/1: close
18 DI18 BIT 17 0: open/1: close
24/ 27
Public
25/ 27
Public
27/ 27
1 2 3 4 5 6 7 8
A A
Project Overview
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
B
Project name 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601
B
C
Order Number C
Product SafePlus 36
Rated voltage 36kV 25kA/20KA
Nominal voltage 33kV
D
Busbar rated current 630A/600Hz D
Beijing,100176,P.R.China
Telephone (8610) 8709 9199
Fax (8610) 8709 9299
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. =
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Project Overview +
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 1
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A Table of content A
Drawing Number Page Description Page Position Page NO. Pages Drawing Number Page Description Page Position Page NO. Pages
1 1YVS84000293 Project Overview 1 1 3 25 1YVS84000293 Terminal diagram MLD-A03-10 10 12
2 1YVS84000293 Table of contents 2 2 3 26 1YVS84000293 Terminal diagram MLD-A03-11 11 12
3 1YVS84000293 Out terminals for Sungrow 3 3 3 27 1YVS84000293 Part list MLD-A03-12 12 12
4 1YVS84000293 Circuit Diagram Overview for Saf MLD-A01-1 1 7
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
eRing/SafePlus 36_40.5kV C Mo
dule
B 5 1YVS84000293 Auxiliary Contacts for SafeRing/ MLD-A01-2 2 7 B
SafePlus 36_40.5kV C Module
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. =
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Table of contents +
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 2
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
UP上排 Down下排
环网柜源端 描述 RMU manufacturer XSG MV中压一体机目标端
Sungrow
RMU 220Vac-L 1
RMU 220Vac Control power circuit
RMU 220Vac-N 2
(Power电源) RMU +/L 3 (Distribution Cabinet 配电柜 )
RMU 24/48V dc/ac Control power circuit
RMU -/N 4
RMU Remote close 环网柜远方操作合闸 RMU VCB remote closing-NO 5
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
1备注:2-3、4-5、8-9、24-25、27-28、29-30之间需加挡板,RS485采用屏蔽型双绞线;
NOTE:Among 2-3、4-5、8-9、24-25、27-28、29-30 need to add dam-board,shielded twisted paie wire for RS485;
2备注:本端子排默认要求放在低压配电箱,具体以技术协议为准;
NOTE:This terminal strip is required to be placed in the low-voltage distribution box by default,the details shall be subject to the agreement ;
E 3备注:本端子列出的信号环网柜若没有,则将该端子位号空置,严禁它用; E
NOTE:If these signals listed are not present in this terminal strip ,leave the terminal tag empty,no other use;
4备注:继保带RJ45网口。
NOTE:If there are other signals (for example, relay protection with Ethernet Interface), please add them.
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. =
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Out terminals for Sungrow +
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 3
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Circuit Diagram Overview
-Main_Bus_Bar
L1 L2 L3
A A
/2.3:C
/2.3:C
/2.4:C
/2.4:C
1 3 1 3
Auxiliary Contact of Load Break Switch
-S7.1 2 4 -S7.2 2 4
-QBL
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
B B
-QC
/2.5:C
/2.5:C
/2.6:C
/2.6:C
1 3 1 3
Auxiliary Contact of Earthing Switch
-S10.1 2 4 -S10.2 2 4
C C
-PGVI
D D
L1
CK
-XB1 L2
CK
-XB2 L3
CK
-XB3
PE
E E
-Cable
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Circuit Diagram Overview for
Checked Moses-Ju Xing Approved Xiaolong Chen + A01
Sungrow Electrict Co Ltd Project name SafeRing/SafePlus 36_40.5kV C Module
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 1
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 7
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Load Break Switch Status Earthing Switch Status
A A
3.6:B 3.6:B
XSG9 XSG11
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
C C
1 3 1 3 1 3 1 3
-S7.1 -S7.1 -S7.2 -S7.2 -S10.1 -S10.1 -S10.2 -S10.2
/1.5:B 2 /1.5:B 4 /1.6:B 2 /1.6:B 4 /1.5:C 2 /1.5:C 4 /1.6:C 2 /1.6:C 4
D D
XSG10 XSG12
3.6:B 3.6:B
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Auxiliary Contacts for SafeRing/SafePlus
Checked Moses-Ju Xing Approved Xiaolong Chen + A01
Sungrow Electrict Co Ltd Project name 36_40.5kV C Module
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 2
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 7
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
XSG terminal
A A
-XSG 1
+A03/2.2:C / +A03-XSG1
-XSG 2
+A03/2.2:C / +A03-XSG2
-XSG 3
/ -XSG3
-XSG 4
/ -XSG4
-XSG 5
+A03/2.4:A / +A03-XSG5
-XSG 6
+A03/2.5:B / +A03-XSG6
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
-XSG 7
+A03/2.3:D / +A03-XSG7
-XSG 8
+A03/2.3:D / +A03-XSG8
B B
-XSG 9
2.3:B / XSG9
-XSG 10
2.3:E / XSG10
-XSG 11
2.5:B / XSG11
-XSG 12
2.5:E / XSG12
-XSG 13
+A02/2.3:B / +A02-XSG13
-XSG 14
+A02/2.3:E / +A02-XSG14
-XSG 15
+A02/2.5:B / +A02-XSG15
-XSG 16
+A02/2.5:E / +A02-XSG16
-XSG 17
+A03/3.2:B / +A03-XSG17
-XSG 18
C +A03/3.2:E / +A03-XSG18 C
-XSG 19
+A03/3.4:B / +A03-XSG19
-XSG 20
+A03/3.4:E / +A03-XSG20
-XSG 21
+A03/3.6:B / +A03-XSG21
-XSG 22
+A03/3.6:E / +A03-XSG22
-XSG 23
+A03/3.8:B / +A03-XSG23
-XSG 24
+A03/3.8:E / +A03-XSG24
-XSG 25
+A03/4.5:F / +A03-XSG25
-XSG 26
+A03/4.5:F / +A03-XSG26
-XSG 27
+A03/4.4:F / +A03-XSG27
D D
-XSG 28
+A03/2.4:A / +A03-XSG28
-XSG 29
+A03/2.3:B / +A03-XSG29
-XSG 30
/ -XSG30
-XSG 31
/ -XSG31
-XSG 32
/ -XSG32
-XSG 33
/ -XSG33
-XSG 34
/ -XSG34
-XSG 35
/ -XSG35
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen To customer out terminal XSG + A01
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 3
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 7
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
-QBL 2 -X1:34
3 -X1:3
B B
4 -X1:33
-S10.2
1 -X1:14
2 -X1:44
3 -X1:13
-QC 4 -X1:43
C C
-XB1
-XB2
-XB3 -XB1
-PGVI:L1
-QC
-XB2
D D
-S7.1 -PGVI:L2
1 -X1:2 -QC
2 -X1:32
3 -X1:1
4 -X1:31 -XB3
-PGVI:L3
-QC
-S7.2
E E
1 -X1:12
2 -X1:42
3 -X1:11
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Device connection diagram + A01
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 4
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 7
1 2 3 4 5 6 7 8
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A01-X1
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
Date
2 MA2.5/5 -S7.1:1 /2.3:B
Name
4 MA2.5/5 -S10.1:1 /2.5:B
2
2
Customer
Contract No.
13 MA2.5/5 -S10.2:3 /2.6:B
3
3
Checked
Prepared
43 MA2.5/5 -S10.2:4 /2.6:E
Project name
44 MA2.5/5 -S10.2:2 /2.6:E
Bingchun Han
Moses-Ju Xing
4
4
Date
Approved
2022.04.20
Xiaolong Chen
5
5
Title
6
6
Terminal diagram
7
7
1YVS84000293
=
+ A01
MLD
8
8
Page
Pages7
5
F
E
B
C
A
D
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A01-XSG
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
Date
2 MA2.5/5 +A03-X1:64 /3.6:A
3 MA2.5/5 /3.6:A
Name
4 MA2.5/5 /3.6:B
2
2
Customer
Contract No.
7 MA2.5/5 +A03-X1:88 /3.6:B
3
3
Checked
Prepared
15 MA2.5/5 +A02-X1:3 /3.6:C
Project name
16 MA2.5/5 +A02-X1:33 /3.6:C
Bingchun Han
Moses-Ju Xing
18 MA2.5/5 +A03-X1:31 /3.6:C
4
4
Date
21 MA2.5/5 +A03-X1:6 /3.6:C
Approved
22 MA2.5/5 +A03-X1:36 /3.6:C
2022.04.20
Xiaolong Chen
25 MA2.5/5 +A03-X4:70 /3.6:D
5
5
Title
28 MA2.5/5 +A03-X1:24 /3.6:D
30 MA2.5/5 /3.6:D
31 MA2.5/5 /3.6:D
32 MA2.5/5 /3.6:E
33 MA2.5/5 /3.6:E
6
6
34 MA2.5/5 /3.6:E
Terminal diagram
35 MA2.5/5 /3.6:E
ABB Beijing Switchgear Limited
Doc. No.
Order No.
7
7
1YVS84000293
=
+ A01
MLD
8
8
Page
Pages7
6
F
E
B
C
A
D
1 2 3 4 5 6 7 8
Parts List
A Name Description SUPPLIER SAP type Position A
1 -PGVI Voltage Indicator ANDAXING STD /1.5:D
B B
C C
D D
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Part list + A01
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 7
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 7
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Circuit Diagram Overview
-Main_Bus_Bar
L1 L2 L3
A A
/2.3:C
/2.3:C
/2.4:C
/2.4:C
1 3 1 3
Auxiliary Contact of Load Break Switch
-S7.1 2 4 -S7.2 2 4
-QBL
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
B B
-QC
/2.5:C
/2.5:C
/2.6:C
/2.6:C
1 3 1 3
Auxiliary Contact of Earthing Switch
-S10.1 2 4 -S10.2 2 4
C C
-PGVI
D D
L1
CK
-XB1 L2
CK
-XB2 L3
CK
-XB3
PE
E E
-Cable
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Circuit Diagram Overview for
Checked Moses-Ju Xing Approved Xiaolong Chen + A02
Sungrow Electrict Co Ltd Project name SafeRing/SafePlus 36_40.5kV C Module
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 1
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Load Break Switch Status Earthing Switch Status
A A
+A01/3.6:C +A01/3.6:C
XSG13 XSG15
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
C C
1 3 1 3 1 3 1 3
-S7.1 -S7.1 -S7.2 -S7.2 -S10.1 -S10.1 -S10.2 -S10.2
/1.5:B 2 /1.5:B 4 /1.6:B 2 /1.6:B 4 /1.5:C 2 /1.5:C 4 /1.6:C 2 /1.6:C 4
D D
XSG14 XSG16
+A01/3.6:C +A01/3.6:C
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Auxiliary Contacts for SafeRing/SafePlus
Checked Moses-Ju Xing Approved Xiaolong Chen + A02
Sungrow Electrict Co Ltd Project name 36_40.5kV C Module
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 2
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
-QBL 2 -X1:34
3 -X1:3
B B
4 -X1:33
-S10.2
1 -X1:14
2 -X1:44
3 -X1:13
-QC 4 -X1:43
C C
-XB1
-XB2
-XB3 -XB1
-PGVI:L1
-QC
-XB2
D D
-S7.1 -PGVI:L2
1 -X1:2 -QC
2 -X1:32
3 -X1:1
4 -X1:31 -XB3
-PGVI:L3
-QC
-S7.2
E E
1 -X1:12
2 -X1:42
3 -X1:11
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Device connection diagram + A02
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 3
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 5
1 2 3 4 5 6 7 8
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A02-X1
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
Date
2 MA2.5/5 -S7.1:1 /2.3:B
Name
4 MA2.5/5 -S10.1:1 /2.5:B
2
2
Customer
Contract No.
13 MA2.5/5 -S10.2:3 /2.6:B
3
3
Checked
Prepared
43 MA2.5/5 -S10.2:4 /2.6:E
Project name
44 MA2.5/5 -S10.2:2 /2.6:E
Bingchun Han
Moses-Ju Xing
4
4
Date
Approved
2022.04.20
Xiaolong Chen
5
5
Title
6
6
Terminal diagram
7
7
1YVS84000293
=
+ A02
MLD
8
8
Page
Pages5
4
F
E
B
C
A
D
1 2 3 4 5 6 7 8
Parts List
A Name Description SUPPLIER SAP type Position A
1 -PGVI Voltage Indicator ANDAXING STD /1.5:D
B B
C C
D D
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Part list + A02
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 5
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Circuit Diagram Overview
-Main_Bus_Bar
L1 L2 L3
A A
-QA
/3.6:C
/3.6:C
/3.7:C
/3.7:C
/2.3:C
M
13 21 31 43 53 13 21 31 43 53
-S35.1 14 22 32 44 54 -S35.2 14 22 32 44 54
B B
a a
-MO1 -MC
/2.7:E b /2.6:E b
Open Coil Close Coil
-QBD
/3.2:C
/3.2:C
/3.3:C
/3.3:C
1 3 1 3
Auxiliary Contact of Disconnector
-S7.1 2 4 -S7.2 2 4
/3.4:C
/3.4:C
/3.5:C
/3.5:C
C C
1 3 1 3
-QC Auxiliary Contact of Earthing Switch
-S10.1 2 4 -S10.2 2 4
/2.5:C
1 3
Manual Operation of Disconnector/Earthing Switch
-S15 2 4
-PGVI
D D
L1
CK
-XB1 L2
CK
-XB2 L3
CK
-XB3 PE
E E
-Cable
/2.5:D
1 3
Cable Compartment Cover Status
-S13 2 4
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Circuit Diagram Overview for
Checked Moses-Ju Xing Approved Xiaolong Chen + A03
Sungrow Electrict Co Ltd Project name SafeRing/SafePlus 36_40.5kV V Module
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 1
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Open Control Circuit Close Control Circuit
Power Supply Close circuit Open circuit Motor
Local Remote Protection/External Trip Local Remote
XSG28 / +A01/3.6:D
A -F1 A
2 1
17F
2.2:D 4.2:A -PLUG8
19F 17M
L14 L10 -PLUG7 19M
+ 13
POS AC -X1 63 -X1 62 -X1 61 1
C AC
XSG1 / +A01/3.6:A -S35.2 C
-S15
-G1 Power Supply /1.6:B 14 /1.6:D
NEG AC -X1 66 -X1 65 -X1 64 2
AC
XSG2 / +A01/3.6:A
- 1F
-PLUG6 1M
20M
-PLUG7 3
20F
N14 N10
2.2:D 4.2:B -S13
/1.6:E 4
2M
2F
-K14
XB3:C2
XB3:C1
XB2:1
XB2:2
XB3:C12
XB3:C11
-F11
2 1 -X1 87 A1 A2 -X1 89 -X1 88
D XSG7 / +A01/3.6:B A1 A1
D
2A
外部跳闸信号 -K1 -V1 -K2 -V2
External trip signals A2 A2
-X1 86 -X1 85
XSG8 / +A01/3.6:B
-X1 67 -X1 68
-GN1
13 14 /2.2:B 1 2 /2.7:B 1 2 /2.6:B
3 1 3 1 21 22 3 4 /2.7:B 3 4 /2.6:B
Remote Local
31 32 5 6 /2.7:B 5 6 /2.7:B
-S01 -S02 43 44
/2.2:B /2.4:B 1 3 5 7 9 11 13 14 21 22
4 2 4 2
2 4 6 8 10 12
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Motorized Operation Schematic Diagram for
Checked Moses-Ju Xing Approved Xiaolong Chen + A03
Sungrow Electrict Co Ltd Project name SafeRing/SafePlus 36_40.5kV V Module
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 2
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Disconnector Status Earthing Switch Status Circuit Breaker Status Local Remote Switch Status
A A
-X1 2 -X1 1 -X1 12 -X1 11 -X1 4 -X1 3 -X1 14 -X1 13 -X1 6 -X1 7 -X1 17 -X1 16 -X1 8
B B
1F 3F 5F 7F
1F 3F 5F 7F 9F 11F 13F 15F
-PLUG8 -PLUG7 1M 3M 5M 7M
1M 3M 5M 7M 9M 11M 13M 15M
C C
1 3 1 3 1 3 1 3 13 21 31 43 12
-S7.1 -S7.1 -S7.2 -S7.2 -S10.1 -S10.1 -S10.2 -S10.2 -S35.1 -S35.1 -S35.1 -S35.1 -GN1
/1.6:C 2 /1.6:C 4 /1.6:C 2 /1.6:C 4 /1.6:C 2 /1.6:C 4 /1.6:C 2 /1.6:C 4 /1.6:B 14 /1.6:B 22 /1.6:B 32 /1.6:B 44 /2.3:F 11
D D
-X1 32 -X1 31 -X1 42 -X1 41 -X1 34 -X1 33 -X1 44 -X1 43 -X1 36 -X1 37 -X1 47 -X1 46 -X1 38
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Auxiliary Contacts for SafeRing/SafePlus
Checked Moses-Ju Xing Approved Xiaolong Chen + A03
Sungrow Electrict Co Ltd Project name 36_40.5kV V Module
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 3
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
2.2:C
4.8:B
L10
A DC3+ A
XK1
-X4 45
-F5 -X4 -X4 + BI1 1
2 1 41 42 1
~ 2
4A
-F6 XK9
2 1 -X4 68 -X4 69 2 - -X4 47
3
4A
BI2
4
DC3- XK4
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
4.6:B -X4 49
N10 External Trip Signal -X4 43
2.2:C BI3 1 DC3+ / 4.4:A
B 2 B
-X4 51
BI4 3
-X4 52
DC3- / 4.3:B
4
L1 L2 L3 XK10
-X4 53
XK8 TR1 / 2.5:A
BO1 1
-X4 66
TR2 / 2.3:B
2
-X2 9 1
S1 S1 S1 IL1 REF601 B D4 46 B B 1NH
-BBPR
GND
C 2 C
XK2
S2 S2 S2 -X4 55
3
BEPC1 BEPC2 BEPC3 BO6 1
IL2 -X4 56
-X2 10 2
4
-X2 11
-X4 57
-X2 12 5 BO5 3
-X4 58
IL3
4
6
-X4 59
D IRF_COM / D
5
7 BO4 -X4 60
Io 6
IRF /
8
-X4 61
7
BO3 -X4 62
8
-X4 63
9
BO2 -X4 64
E 10 E
XK3
D+
G
D-3 2 1
-X4 71
Remark:Red,Yellow,Blue,Black color wires should -X4 70
be used for A,B,C,N phases respecrively.
XSG27 XSG25
+A01/3.6:D +A01/3.6:D
XSG26
F +A01/3.6:D F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer SAFE40.5 V unit AC Operation Diagram
Checked Moses-Ju Xing Approved Xiaolong Chen + A03
Sungrow Electrict Co Ltd Project name REF601
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 4
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Device connection diagram + A03
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 5
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
32 2 1
43 3 -X1:23 2
B B
44 4 -GN1:5 3 -PLUG6:1M
-QBD 4 -PLUG6:2M
-QBD
-M3 -QBD -S7.1
XB2:1 -K1:1 1 -PLUG8:1M -S15
XB2:2 -K1:5 2 -PLUG8:2M 1 -PLUG8:17M
-QBD 3 -PLUG8:3M 2 -PLUG6:1F
-QA 4 -PLUG8:4M 3
C C
-MC -QA 4
XB3:C1 -K2:4 -QA
XB3:C2 -K2:6 -XB1 -S7.2
-XB2 1 -PLUG8:5M -S35.1
-QC 2 -PLUG8:6M 13 -PLUG7:1M
-MO1 3 -PLUG8:7M 14 -PLUG7:2M
XB3:C11 -K1:4 4 -PLUG8:8M 21 -PLUG7:3M
XB3:C12 -K1:6 -QC 22 -PLUG7:4M
D D
-XB1 31 -PLUG7:5M
-XB2 -S10.1 32 -PLUG7:6M
-PGVI -XB3 1 -PLUG8:9M 43 -PLUG7:7M
L1 -XB1 -QBD 2 -PLUG8:10M 44 -PLUG7:8M
L2 -XB2 3 -PLUG8:11M 53
L3 -XB3 4 -PLUG8:12M 54
-S01
1
E E
-PLUG6 2 -S10.2 -S35.2
1F -S15:2 3 -X1:26 1 -PLUG8:13M 13 -PLUG7:19M
1M -S13:3 2 -PLUG8:14M 14 -PLUG7:20M
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Device connection diagram + A03
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 6
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
44
53
B B
54
-V1
-K1:A1
-K1:A2
C C
-V2
-K2:A1
-K2:A2
-XB1
-PGVI:L1
-QBD
D D
-QC
-XB2
-PGVI:L2
-QBD
-QC
E E
-XB3
-PGVI:L3
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Device connection diagram + A03
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 7
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 12
1 2 3 4 5 6 7 8
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A03-X1
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
Date
2 MA2.5/5 -PLUG8:1F /3.2:B
Name
4 MA2.5/5 -PLUG8:9F /3.4:B
2
2
Customer
Contract No.
+A01-XSG:23 8 MA2.5/5 -GN1:12 /3.8:B
3
3
Checked
Prepared
+A01-XSG:29 19 MA2.5/5 /2.3:B
Project name
-GN1:8 20 MA2.5/5 /2.5:B
Bingchun Han
Moses-Ju Xing
-K2:1 22 MA2.5/5 -X4:53 /2.5:A
4
4
Date
25 MA2.5/5 -K14:13 /2.3:A
Approved
-F1:1 26 MA2.5/5 -S01:3 /2.2:A
2022.04.20
Xiaolong Chen
+A01-XSG:20 33 MA2.5/5 -PLUG8:12F /3.4:E
5
5
Title
37 MA2.5/5 -PLUG7:4F /3.6:E
6
6
7
7
62 MA2.5/5 /2.2:C
65 MA2.5/5 /2.2:C
=
Page
Pages12
8
F
E
B
C
A
D
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A03-X1
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
+A01-XSG:8 85 /2.2:D
Date
86 -X1:66 /2.2:D
Name
+A01-XSG:7 88 /2.2:D
2
2
89 -K14:A2 /2.2:D
Customer
Contract No.
Sungrow Electrict Co Ltd
3
3
Checked
Prepared
Project name
Bingchun Han
Moses-Ju Xing
4
4
Date
Approved
2022.04.20
Xiaolong Chen
5
5
Title
6
6
Terminal diagram
7
7
1YVS84000293
=
+ A03
MLD
8
8
Page
Pages12
9
F
E
B
C
A
D
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A03-X2
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
Date
-BBPR:XK8:1 10 -BEPC1:S2 /4.3:C
Name
-BBPR:XK8:5 12 -BEPC3:S2 /4.3:D
2
2
Customer
Contract No.
Sungrow Electrict Co Ltd
3
3
Checked
Prepared
Project name
Bingchun Han
Moses-Ju Xing
4
4
Date
Approved
2022.04.20
Xiaolong Chen
5
5
Title
6
6
Terminal diagram
7
7
1YVS84000293
=
+ A03
MLD
8
8
Page
Pages12
10
F
E
B
C
A
D
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A03-X4
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
41 -F5:1 /4.3:A
Date
-BBPR:XK9:1 42 /4.4:A
43 /4.8:B
Name
45 -BBPR:XK1:1 /4.6:A
2
2
47 -BBPR:XK1:3 /4.6:A
49 -BBPR:XK4:1 /4.7:B
Customer
Contract No.
51 -BBPR:XK4:3 /4.6:B
55 -BBPR:XK2:1 /4.6:C
3
3
57 -BBPR:XK2:3 /4.6:D
58 -BBPR:XK2:4 /4.6:D
59 -BBPR:XK2:5 /4.6:D
Checked
Prepared
60 -BBPR:XK2:6 /4.6:D
Project name
61 -BBPR:XK2:7 /4.6:D
62 -BBPR:XK2:8 /4.6:E
Bingchun Han
Moses-Ju Xing
63 -BBPR:XK2:9 /4.6:E
4
4
64 -BBPR:XK2:10 /4.6:E
Date
68 -F6:1 /4.3:A
Approved
-BBPR:XK9:2 69 -X4:52 /4.4:A
2022.04.20
Xiaolong Chen
5
5
Title
6
6
Terminal diagram
7
7
1YVS84000293
=
+ A03
MLD
8
8
Page
Pages12
11
F
E
B
C
A
D
1 2 3 4 5 6 7 8
Parts List
A Name Description SUPPLIER SAP type Position A
1 -BBPR Relay OBD OBD /4.4:A
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Part list + A03
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000293_ SAFE+DT CCV 36KV+Motor+REF601 Doc. No. Page 12
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000293 Pages 12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
Project Overview
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
B
Project name 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601
B
C
Order Number C
Product SafePlus 36
Rated voltage 36kV 25kA/20KA
Nominal voltage 33kV
D
Busbar rated current 630A/600Hz D
Beijing,100176,P.R.China
Telephone (8610) 8709 9199
Fax (8610) 8709 9299
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. =
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Project Overview +
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 1
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A Table of content A
eRing/SafePlus 36_40.5kV C Mo
dule
B 5 1YVS84000346 Auxiliary Contacts for SafeRing/ MLD-A01-2 2 7 B
SafePlus 36_40.5kV C Module
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. =
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Table of contents +
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 2
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
UP上排 Down下排
环网柜源端 描述 RMU manufacturer XSG MV中压一体机目标端
Sungrow
RMU 220Vac-L 1
RMU 220Vac Control power circuit
RMU 220Vac-N 2
(Power电源) RMU +/L 3 (Distribution Cabinet 配电柜 )
RMU 24/48V dc/ac Control power circuit
RMU -/N 4
RMU Remote close 环网柜远方操作合闸 RMU VCB remote closing-NO 5
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
1备注:2-3、4-5、8-9、24-25、27-28、29-30之间需加挡板,RS485采用屏蔽型双绞线;
NOTE:Among 2-3、4-5、8-9、24-25、27-28、29-30 need to add dam-board,shielded twisted paie wire for RS485;
2备注:本端子排默认要求放在低压配电箱,具体以技术协议为准;
NOTE:This terminal strip is required to be placed in the low-voltage distribution box by default,the details shall be subject to the agreement ;
E 3备注:本端子列出的信号环网柜若没有,则将该端子位号空置,严禁它用; E
NOTE:If these signals listed are not present in this terminal strip ,leave the terminal tag empty,no other use;
4备注:继保带RJ45网口。
NOTE:If there are other signals (for example, relay protection with Ethernet Interface), please add them.
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. =
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Out terminals for Sungrow +
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 3
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Circuit Diagram Overview
-Main_Bus_Bar
L1 L2 L3
A A
/2.3:C
/2.3:C
/2.4:C
/2.4:C
1 3 1 3
Auxiliary Contact of Load Break Switch
-S7.1 2 4 -S7.2 2 4
-QBL
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
B B
-QC
/2.5:C
/2.5:C
/2.6:C
/2.6:C
1 3 1 3
Auxiliary Contact of Earthing Switch
-S10.1 2 4 -S10.2 2 4
C C
-PGVI
D D
L1
CK
-XB1 L2
CK
-XB2 L3
CK
-XB3
PE
E E
-Cable
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Circuit Diagram Overview for
Checked Moses-Ju Xing Approved Xiaolong Chen + A01
Sungrow Electrict Co Ltd Project name SafeRing/SafePlus 36_40.5kV C Module
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 1
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 7
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Load Break Switch Status Earthing Switch Status
A A
3.6:B 3.6:B
XSG9 XSG11
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
C C
1 3 1 3 1 3 1 3
-S7.1 -S7.1 -S7.2 -S7.2 -S10.1 -S10.1 -S10.2 -S10.2
/1.5:B 2 /1.5:B 4 /1.6:B 2 /1.6:B 4 /1.5:C 2 /1.5:C 4 /1.6:C 2 /1.6:C 4
D D
XSG10 XSG12
3.6:B 3.6:B
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Auxiliary Contacts for SafeRing/SafePlus
Checked Moses-Ju Xing Approved Xiaolong Chen + A01
Sungrow Electrict Co Ltd Project name 36_40.5kV C Module
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 2
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 7
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
XSG terminal
A A
-XSG 1
+A02/2.2:C / +A02-XSG1
-XSG 2
+A02/2.2:C / +A02-XSG2
-XSG 3
/ -XSG3
-XSG 4
/ -XSG4
-XSG 5
+A02/2.4:A / +A02-XSG5
-XSG 6
+A02/2.5:B / +A02-XSG6
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
-XSG 7
+A02/2.3:D / +A02-XSG7
-XSG 8
+A02/2.3:D / +A02-XSG8
B B
-XSG 9
2.3:B / XSG9
-XSG 10
2.3:E / XSG10
-XSG 11
2.5:B / XSG11
-XSG 12
2.5:E / XSG12
-XSG 13
/ +A02-XSG13
-XSG 14
/ +A02-XSG14
-XSG 15
/ +A02-XSG15
-XSG 16
/ +A02-XSG16
-XSG 17
+A02/3.2:B / +A02-XSG17
-XSG 18
C +A02/3.2:E / +A02-XSG18 C
-XSG 19
+A02/3.4:B / +A02-XSG19
-XSG 20
+A02/3.4:E / +A02-XSG20
-XSG 21
+A02/3.6:B / +A02-XSG21
-XSG 22
+A02/3.6:E / +A02-XSG22
-XSG 23
+A02/3.8:B / +A02-XSG23
-XSG 24
+A02/3.8:E / +A02-XSG24
-XSG 25
+A02/4.5:F / +A02-XSG25
-XSG 26
+A02/4.5:F / +A02-XSG26
-XSG 27
+A02/4.4:F / +A02-XSG27
D D
-XSG 28
+A02/2.4:A / +A02-XSG28
-XSG 29
+A02/2.3:B / +A02-XSG29
-XSG 30
/ -XSG30
-XSG 31
/ -XSG31
-XSG 32
/ -XSG32
-XSG 33
/ -XSG33
-XSG 34
/ -XSG34
-XSG 35
/ -XSG35
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen To customer out terminal XSG + A01
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 3
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 7
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
-QBL 2 -X1:34
3 -X1:3
B B
4 -X1:33
-S10.2
1 -X1:14
2 -X1:44
3 -X1:13
-QC 4 -X1:43
C C
-XB1
-XB2
-XB3 -XB1
-PGVI:L1
-QC
-XB2
D D
-S7.1 -PGVI:L2
1 -X1:2 -QC
2 -X1:32
3 -X1:1
4 -X1:31 -XB3
-PGVI:L3
-QC
-S7.2
E E
1 -X1:12
2 -X1:42
3 -X1:11
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Device connection diagram + A01
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 4
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 7
1 2 3 4 5 6 7 8
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A01-X1
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
Date
2 MA2.5/5 -S7.1:1 /2.3:B
Name
4 MA2.5/5 -S10.1:1 /2.5:B
2
2
Customer
Contract No.
13 MA2.5/5 -S10.2:3 /2.6:B
3
3
Checked
Prepared
43 MA2.5/5 -S10.2:4 /2.6:E
Project name
44 MA2.5/5 -S10.2:2 /2.6:E
Bingchun Han
Moses-Ju Xing
4
4
Date
Approved
2022.04.20
Xiaolong Chen
5
5
Title
6
6
Terminal diagram
7
7
1YVS84000346
=
+ A01
MLD
8
8
Page
Pages7
5
F
E
B
C
A
D
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A01-XSG
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
Date
2 MA2.5/5 +A02-X1:64 /3.6:A
3 MA2.5/5 /3.6:A
Name
4 MA2.5/5 /3.6:B
2
2
Customer
Contract No.
7 MA2.5/5 +A02-X1:88 /3.6:B
3
3
13 MA2.5/5 /3.6:C
14 MA2.5/5 /3.6:C
Checked
Prepared
15 MA2.5/5 /3.6:C
Project name
16 MA2.5/5 /3.6:C
Bingchun Han
Moses-Ju Xing
18 MA2.5/5 +A02-X1:31 /3.6:C
4
4
Date
21 MA2.5/5 +A02-X1:6 /3.6:C
Approved
22 MA2.5/5 +A02-X1:36 /3.6:C
2022.04.20
Xiaolong Chen
5
5
Title
28 MA2.5/5 +A02-X1:24 /3.6:D
30 MA2.5/5 /3.6:D
31 MA2.5/5 /3.6:D
32 MA2.5/5 /3.6:E
33 MA2.5/5 /3.6:E
6
6
34 MA2.5/5 /3.6:E
Terminal diagram
35 MA2.5/5 /3.6:E
ABB Beijing Switchgear Limited
Doc. No.
Order No.
7
7
1YVS84000346
=
+ A01
MLD
8
8
Page
Pages7
6
F
E
B
C
A
D
1 2 3 4 5 6 7 8
Parts List
A Name Description SUPPLIER SAP type Position A
1 -PGVI Voltage Indicator ANDAXING STD /1.5:D
B B
C C
D D
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Part list + A01
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 7
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 7
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Circuit Diagram Overview
-Main_Bus_Bar
L1 L2 L3
A A
-QA
/3.6:C
/3.6:C
/3.7:C
/3.7:C
/2.3:C
M
13 21 31 43 53 13 21 31 43 53
-S35.1 14 22 32 44 54 -S35.2 14 22 32 44 54
B B
a a
-MO1 -MC
/2.7:E b /2.6:E b
Open Coil Close Coil
-QBD
/3.2:C
/3.2:C
/3.3:C
/3.3:C
1 3 1 3
Auxiliary Contact of Disconnector
-S7.1 2 4 -S7.2 2 4
/3.4:C
/3.4:C
/3.5:C
/3.5:C
C C
1 3 1 3
-QC Auxiliary Contact of Earthing Switch
-S10.1 2 4 -S10.2 2 4
/2.5:C
1 3
Manual Operation of Disconnector/Earthing Switch
-S15 2 4
-PGVI
D D
L1
CK
-XB1 L2
CK
-XB2 L3
CK
-XB3 PE
E E
-Cable
/2.5:D
1 3
Cable Compartment Cover Status
-S13 2 4
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Circuit Diagram Overview for
Checked Moses-Ju Xing Approved Xiaolong Chen + A02
Sungrow Electrict Co Ltd Project name SafeRing/SafePlus 36_40.5kV V Module
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 1
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 13
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Open Control Circuit Close Control Circuit
Power Supply Close circuit Open circuit Motor
Local Remote Protection/External Trip Local Remote
XSG28 / +A01/3.6:D
A -F1 A
2 1
17F
2.2:D 4.2:A -PLUG8
19F 17M
L14 L10 -PLUG7 19M
+ 13
POS AC -X1 63 -X1 62 -X1 61 1
C AC
XSG1 / +A01/3.6:A -S35.2 C
-S15
-G1 Power Supply /1.6:B 14 /1.6:D
NEG AC -X1 66 -X1 65 -X1 64 2
AC
XSG2 / +A01/3.6:A
- 1F
-PLUG6 1M
20M
-PLUG7 3
20F
N14 N10
2.2:D 4.2:B -S13
/1.6:E 4
2M
2F
-K14
XB3:C2
XB3:C1
XB2:1
XB2:2
XB3:C12
XB3:C11
-F11
2 1 -X1 87 A1 A2 -X1 89 -X1 88
D XSG7 / +A01/3.6:B A1 A1
D
2A
外部跳闸信号 -K1 -V1 -K2 -V2
External trip signals A2 A2
-X1 86 -X1 85
XSG8 / +A01/3.6:B
-X1 67 -X1 68
-GN1
13 14 /2.2:B 1 2 /2.7:B 1 2 /2.6:B
3 1 3 1 21 22 3 4 /2.7:B 3 4 /2.6:B
Remote Local
31 32 5 6 /2.7:B 5 6 /2.7:B
-S01 -S02 43 44
/2.2:B /2.4:B 1 3 5 7 9 11 13 14 21 22
4 2 4 2
2 4 6 8 10 12
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Motorized Operation Schematic Diagram for
Checked Moses-Ju Xing Approved Xiaolong Chen + A02
Sungrow Electrict Co Ltd Project name SafeRing/SafePlus 36_40.5kV V Module
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 2
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 13
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Disconnector Status Earthing Switch Status Circuit Breaker Status Local Remote Switch Status
A A
-X1 2 -X1 1 -X1 12 -X1 11 -X1 4 -X1 3 -X1 14 -X1 13 -X1 6 -X1 7 -X1 17 -X1 16 -X1 8
B B
1F 3F 5F 7F
1F 3F 5F 7F 9F 11F 13F 15F
-PLUG8 -PLUG7 1M 3M 5M 7M
1M 3M 5M 7M 9M 11M 13M 15M
C C
1 3 1 3 1 3 1 3 13 21 31 43 12
-S7.1 -S7.1 -S7.2 -S7.2 -S10.1 -S10.1 -S10.2 -S10.2 -S35.1 -S35.1 -S35.1 -S35.1 -GN1
/1.6:C 2 /1.6:C 4 /1.6:C 2 /1.6:C 4 /1.6:C 2 /1.6:C 4 /1.6:C 2 /1.6:C 4 /1.6:B 14 /1.6:B 22 /1.6:B 32 /1.6:B 44 /2.3:F 11
D D
-X1 32 -X1 31 -X1 42 -X1 41 -X1 34 -X1 33 -X1 44 -X1 43 -X1 36 -X1 37 -X1 47 -X1 46 -X1 38
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer Auxiliary Contacts for SafeRing/SafePlus
Checked Moses-Ju Xing Approved Xiaolong Chen + A02
Sungrow Electrict Co Ltd Project name 36_40.5kV V Module
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 3
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 13
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
2.2:C
4.8:B
L10
A DC3+ A
XK1
-X4 45
-F5 -X4 -X4 + BI1 1
2 1 41 42 1
~ 2
4A
-F6 XK9
2 1 -X4 68 -X4 69 2 - -X4 47
3
4A
BI2
4
DC3- XK4
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
4.6:B -X4 49
N10 External Trip Signal -X4 43
2.2:C BI3 1 DC3+ / 4.4:A
B 2 B
-X4 51
BI4 3
-X4 52
DC3- / 4.3:B
4
L1 L2 L3 XK10
-X4 53
XK8 TR1 / 2.5:A
BO1 1
-X4 66
TR2 / 2.3:B
2
-X2 9 1
S1 S1 S1 IL1 REF601 B D4 46 B B 1NH
-BBPR
GND
C 2 C
XK2
S2 S2 S2 -X4 55
3
BEPC1 BEPC2 BEPC3 BO6 1
IL2 -X4 56
-X2 10 2
4
-X2 11
-X4 57
-X2 12 5 BO5 3
-X4 58
IL3
4
6
-X4 59
D IRF_COM / D
5
7 BO4 -X4 60
Io 6
IRF /
8
-X4 61
7
BO3 -X4 62
8
-X4 63
9
BO2 -X4 64
E 10 E
XK3
D+
G
D-3 2 1
-X4 71
Remark:Red,Yellow,Blue,Black color wires should -X4 70
be used for A,B,C,N phases respecrively.
XSG27 XSG25
+A01/3.6:D +A01/3.6:D
XSG26
F +A01/3.6:D F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer SAFE40.5 V unit AC Operation Diagram
Checked Moses-Ju Xing Approved Xiaolong Chen + A02
Sungrow Electrict Co Ltd Project name REF601
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 4
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 13
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Device connection diagram + A02
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 5
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 13
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Device connection diagram + A02
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 6
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 13
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
2 1 44
3 -X1:23 2 53
B B
4 -GN1:5 3 -PLUG6:1M 54
-QBD 4 -PLUG6:2M
-QBD
-QBD -S7.1 -V1
1 -PLUG8:1M -S15 -K1:A1
2 -PLUG8:2M 1 -PLUG8:17M -K1:A2
-QBD 3 -PLUG8:3M 2 -PLUG6:1F
-QA 4 -PLUG8:4M 3
C C
-QA 4 -V2
-QA -K2:A1
-XB1 -S7.2 -K2:A2
-XB2 1 -PLUG8:5M -S35.1
-QC 2 -PLUG8:6M 13 -PLUG7:1M
3 -PLUG8:7M 14 -PLUG7:2M -XB1
4 -PLUG8:8M 21 -PLUG7:3M -PGVI:L1
-QC 22 -PLUG7:4M -QBD
D D
-XB1 31 -PLUG7:5M -QC
-XB2 -S10.1 32 -PLUG7:6M
-XB3 1 -PLUG8:9M 43 -PLUG7:7M
-QBD 2 -PLUG8:10M 44 -PLUG7:8M -XB2
3 -PLUG8:11M 53 -PGVI:L2
4 -PLUG8:12M 54 -QBD
-S01 -QC
1
E E
2 -S10.2 -S35.2
3 -X1:26 1 -PLUG8:13M 13 -PLUG7:19M -XB3
2 -PLUG8:14M 14 -PLUG7:20M -PGVI:L3
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Device connection diagram + A02
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 7
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 13
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
B B
C C
D D
E E
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Device connection diagram + A02
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 8
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 13
1 2 3 4 5 6 7 8
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A02-X1
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
Date
2 MA2.5/5 -PLUG8:1F /3.2:B
Name
4 MA2.5/5 -PLUG8:9F /3.4:B
2
2
Customer
Contract No.
+A01-XSG:23 8 MA2.5/5 -GN1:12 /3.8:B
3
3
Checked
Prepared
+A01-XSG:29 19 MA2.5/5 /2.3:B
Project name
-GN1:8 20 MA2.5/5 /2.5:B
Bingchun Han
Moses-Ju Xing
-K2:1 22 MA2.5/5 -X4:53 /2.5:A
4
4
Date
25 MA2.5/5 -K14:13 /2.3:A
Approved
-F1:1 26 MA2.5/5 -S01:3 /2.2:A
2022.04.20
Xiaolong Chen
5
5
Title
37 MA2.5/5 -PLUG7:4F /3.6:E
6
6
7
7
62 MA2.5/5 /2.2:C
65 MA2.5/5 /2.2:C
=
Page
Pages13
9
F
E
B
C
A
D
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A02-X1
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
+A01-XSG:8 85 /2.2:D
Date
86 -X1:66 /2.2:D
Name
+A01-XSG:7 88 /2.2:D
2
2
89 -K14:A2 /2.2:D
Customer
Contract No.
Sungrow Electrict Co Ltd
3
3
Checked
Prepared
Project name
Bingchun Han
Moses-Ju Xing
4
4
Date
Approved
2022.04.20
Xiaolong Chen
5
5
Title
6
6
Terminal diagram
7
7
1YVS84000346
=
+ A02
MLD
8
8
Page
Pages13
10
F
E
B
C
A
D
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A02-X2
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
Date
-BBPR:XK8:1 10 -BEPC1:S2 /4.3:C
Name
-BBPR:XK8:5 12 -BEPC3:S2 /4.3:D
2
2
Customer
Contract No.
Sungrow Electrict Co Ltd
3
3
Checked
Prepared
Project name
Bingchun Han
Moses-Ju Xing
4
4
Date
Approved
2022.04.20
Xiaolong Chen
5
5
Title
6
6
Terminal diagram
7
7
1YVS84000346
=
+ A02
MLD
8
8
Page
Pages13
11
F
E
B
C
A
D
F
E
B
C
A
D
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN.
Rev.
Terminal diagram Terminal Strip
1
1
=MLD+A02-X4
Description
Terminal
Cable number External Target Bridge Bar Terminal Type Internal Target Cable number Terminal position
Number
41 -F5:1 /4.3:A
Date
-BBPR:XK9:1 42 /4.4:A
43 /4.8:B
Name
45 -BBPR:XK1:1 /4.6:A
2
2
47 -BBPR:XK1:3 /4.6:A
49 -BBPR:XK4:1 /4.7:B
Customer
Contract No.
51 -BBPR:XK4:3 /4.6:B
55 -BBPR:XK2:1 /4.6:C
3
3
57 -BBPR:XK2:3 /4.6:D
58 -BBPR:XK2:4 /4.6:D
59 -BBPR:XK2:5 /4.6:D
Checked
Prepared
60 -BBPR:XK2:6 /4.6:D
Project name
61 -BBPR:XK2:7 /4.6:D
62 -BBPR:XK2:8 /4.6:E
Bingchun Han
Moses-Ju Xing
63 -BBPR:XK2:9 /4.6:E
4
4
64 -BBPR:XK2:10 /4.6:E
Date
68 -F6:1 /4.3:A
Approved
-BBPR:XK9:2 69 -X4:52 /4.4:A
2022.04.20
Xiaolong Chen
5
5
Title
6
6
Terminal diagram
7
7
1YVS84000346
=
+ A02
MLD
8
8
Page
Pages13
12
F
E
B
C
A
D
1 2 3 4 5 6 7 8
Parts List
A Name Description SUPPLIER SAP type Position A
1 -BBPR Relay OBD OBD /4.4:A
F F
Prepared Bingchun Han Date 2022.04.20 Title Order No. = MLD
Customer
Checked Moses-Ju Xing Approved Xiaolong Chen Part list + A02
Sungrow Electrict Co Ltd Project name
Contract No. 1YVS84000346_ SAFE+DT CV 36KV+Motor+REF601 Doc. No. Page 13
Rev. Description Date Name ABB Beijing Switchgear Limited 1YVS84000346 Pages 13
1 2 3 4 5 6 7 8