Está en la página 1de 122

“PROYECTO HIDROSANITARIO,

PLUVIAL Y PROTECCIÓN CONTRA


INCENDIOS PARA CONSTRUCCIÓN
DE LA UNIDAD MEDICA FAMILIAR
(UNIMEF “LOS OLIVOS”) DEL IPEJAL
EN ZAPOPAN, JALISCO.”
MEMORIA DESCRIPTIVA

INFRAESTRUCTURA HIDRÁULICA Y SERVICIOS S.A. DE C.V.

ABRIL DEL 2022

0
Tabla de contenido
1 INTRODUCCIÓN GENERAL. ............................................................................................... 5
2 PROYECTO DE AGUA POTABLE........................................................................................ 6
2.1 INTRODUCCIÓN .................................................................................................................. 6
2.2 OBJETIVO DE PROYECTO DE AGUA POTABLE ............................................................... 6
2.3 DESCRIPCIÓN GENERAL DEL PROYECTO HIDRÁULICO ............................................... 6
2.4 DOTACIÓN DE AGUA POTABLE ......................................................................................... 7
2.5 GASTO MEDIO DIARIO........................................................................................................ 8
2.6 GASTO MÁXIMO DIARIO ..................................................................................................... 8
2.7 GASTO MÁXIMO HORARIO ................................................................................................ 9
2.8 CALCULO DE LA TOMA DOMICILIARIA ........................................................................... 10
2.9 CALCULO DE VOLUMEN DE CISTERNA.......................................................................... 11
2.10 CALCULO DE CAPACIDAD DE HIDRONEUMÁTICO ................................................. 11
2.11 DETERMINACIÓN DE LA CARGA TOTAL DE BOMBEO............................................ 12
2.12 RED DE DISTRIBUCIÓN.............................................................................................. 12
2.13 CÁLCULO Y DISEÑO DE LA RED DE AGUA POTABLE ............................................ 41
2.14 CALCULO DE LA CARGA DISPONIBLE EN CADA TRAMO....................................... 41
2.15 AGUA CALIENTE PARA REGADERAS ....................................................................... 54
2.16 ESPECIFICACIONES DE MATERIALES ..................................................................... 54
2.17 NORMATIVIDAD APLICABLE ...................................................................................... 54
3 PROYECTO DE DRENAJE SANITARIO. ........................................................................... 54
3.1 INTRODUCCIÓN ................................................................................................................ 55
3.2 OBJETIVO .......................................................................................................................... 55
3.3 FORMULA DE MANNING ................................................................................................... 55
3.4 COEFICCIENTE DE FRICCIÓN DE MANNING.................................................................. 57
3.5 VELOCIDADES PERMISIBLES .......................................................................................... 58
3.5.1 Velocidad mínima. ........................................................................................................ 58
3.5.2 Velocidad máxima. ....................................................................................................... 58
3.6 PENDIENTES PERMITIDAS EN INTERIORES .................................................................. 59
3.7 PENDIENTES PERMITIDAS EN EXTERIORES ................................................................ 60
3.7.1 PENDIENTE MÍNIMA ................................................................................................... 60
3.7.2 PENDIENTE MÁXIMA .................................................................................................. 60
3.8 REGISTROS Y ESTRUCTURAS ........................................................................................ 60
3.8.1 Separación entre registros ............................................................................................ 61
3.8.2 Profundidad máxima de registros ................................................................................. 61
3.9 GASTO DE DISEÑO ........................................................................................................... 61
3.10 DETERMINACION DEL GASTO DE DESCARGA ....................................................... 64
3.11 CÁLCULO Y DIMENCIONAMIENTO DE LA RED SANITARIA. ................................... 70
3.12 DIMENCIONAMIENTO DE CARCAMO DE BOMBEO ................................................. 87

1
3.13 ESPECIFICACIONES DE MATERIALES ..................................................................... 90
3.14 NORMATIVIDAD APLICABLE ...................................................................................... 91
4 PROYECTO PLUVIAL. ....................................................................................................... 92
4.1 HIDROLOGÍA EN LA ZONA DE ESTUDIO ......................................................................... 92
4.1.1 CURVAS I-D-TR. .......................................................................................................... 92
4.1.2 MORFOLOGÍA DEL PREDIO ....................................................................................... 93
4.1.3 MÉTODO RACIONAL AMERICANO ............................................................................ 95
4.2 DISEÑO DE SISTEMA PLUVIAL ........................................................................................ 96
4.2.1 BAJANTES DE AGUAS PLUVIALES ........................................................................... 96
4.2.2 CÁLCULO Y DIMENSIONAMIENTO DE LA RED PLUVIAL INTERNA ........................ 98
4.2.3 CÁLCULO Y DIMENSIONAMIENTO DE BOCAS DE TORMENTA ........................... 101
4.2.4 CÁLCULO Y DIMENSIONAMIENTO DE DEPÓSITO DE REGULACIÓN .................. 106
5 PROYECTO DE INSTALACION DE PROTECCIÓN CONTRA INCENDIOS .................... 109
5.1 OBJETIVO ........................................................................................................................ 109
5.2 ALCANCE ......................................................................................................................... 109
5.3 INSTALACIÓN SISTEMA DE PROTECCIÓN CONTRA INCENDIOS .............................. 110
5.3.1 DESCRIPCIÓN DEL SISTEMA. ................................................................................. 110
5.4 VOLUMEN DE ALMACENAMIENTO DE RESERVA CONTRA INCENDIO. .................... 110
5.5 REDES GENERALES DE ALIMENTACIÓN ..................................................................... 111
5.6 ALIMENTACIÓN A HIDRANTES ...................................................................................... 111
5.7 CALCULO HIDRÁULICO DEL SISTEMA DE HIDRANTES. ............................................. 113
5.7.1 CARGA DINÁMICA TOTAL ........................................................................................ 114
5.7.2 CALCULO NPSH DISPONIBLE ................................................................................. 115
5.7.3 REDUCTORES DE PRESION .................................................................................... 115
5.7.4 CURVA DE RENDIMIENTO BOMBA ELECTRICA .................................................... 117
5.7.5 CURVA DE RENDIMIENTO BOMBA COMBUSTION INTERNA ............................... 118
5.7.6 CURVA DE RENDIMIENTO BOMBA JOCKEY .......................................................... 119
5.7.7 MATERIALES ............................................................................................................. 120
5.7.8 SOPORTERÍA ............................................................................................................ 120
5.7.9 PRUEBA DE HERMETICIDAD (PRESIÓN DE PRUEBA, FORMATO DE REGISTRO).
120
5.8 NORMAS Y REGLAMENTOS ........................................................................................... 121

ÍNDICE DE FIGURAS
Figura 1. Localización del proyecto.............................................................................................. 5
Figura 2. Dotaciones mínimas de agua. ...................................................................................... 7
Figura 3. Cálculo de Unidades Mueble en Clínicas y Hospitales. .............................................. 14
Figura 4. Gasto en función de unidades mueble, Método Hunter – Nielsen. ............................. 15

2
Figura 5. Elementos geométricos de secciones de canal. ......................................................... 56
Figura 6. Características geométricas para un tubo parcialmente lleno. ................................... 57
Figura 7. Coeficiente de rugosidad de Manning para diferentes materiales. ............................. 58
Figura 8. Velocidades máximas y mínimas permisibles en tuberías para alcantarillado sanitario.
................................................................................................................................................... 59
Figura 9. Ramales horizontales y bajadas. ................................................................................ 59
Figura 10. Líneas principales horizontales................................................................................. 60
Figura 11. Separación entre registros con respecto al diámetro................................................ 61
Figura 12. Unidades mueble para sanitario. .............................................................................. 63
Figura 13. Detalle de cárcamo de bombeo vista en planta. ....................................................... 89
Figura 14. Detalle de cárcamo de bombeo vista en corte. ......................................................... 89
Figura 15. Curvas Intensidad - Duración - Periodo de Retorno (i-d-Tr) ..................................... 93
Figura 16. Coeficiente de escurrimientos del IMSS. .................................................................. 94
Figura 17. Delimitación de áreas para escurrimiento pluvial...................................................... 96
Figura 18. Esquema isométrico de la red pluvial. ...................................................................... 98
Figura 19. Bocas de tormenta.................................................................................................. 101
Figura 20. Detalle de rejilla. ..................................................................................................... 102
Figura 21. Hidrograma de ingreso y salidas del cárcamo de bombeo. .................................... 105
Figura 22. Tirante máximo del cárcamo de bombeo................................................................ 105
Figura 23. Hidrograma de ingreso y salidas del depósito de regulación.................................. 108
Figura 24. Tirante máximo del depósito de regulación. ........................................................... 108
Figura 25. Selección de hidrantes simultáneos. ...................................................................... 111
Figura 26. Curva de rendimiento de bomba eléctrica Marca Barmesa, Modelo IA2EH. .......... 117
Figura 27. Curva de rendimiento de bomba de combustión interna, Marca Mejorada, Modelo 2P-
61MDP. .................................................................................................................................... 118
Figura 28. Curva de rendimiento de bomba Jokeyc, Marca Altamira serie TX, Modelo T0.6 X20-
17. ............................................................................................................................................ 119

ÍNDICE DE TABLAS
Tabla 1. Dotación diaria de agua potable. ................................................................................... 8
Tabla 2. Datos básicos del proyecto de agua potable. ................................................................ 9
Tabla 3. Cálculo de la capacidad de almacenamiento de la cisterna. ....................................... 11
Tabla 4. Cálculo de la capacidad del tanque hidroneumático. ................................................... 12
Tabla 5. Cálculo de carga total y potencia de la bomba. ........................................................... 12
Tabla 6. Sumatoria de unidades mueble, determinación de gasto probable. ............................ 16
Tabla 7. Cálculo hidráulico de la red de agua potable. .............................................................. 42
Tabla 8. Cálculo del gasto de descarga por mueble. ................................................................. 64
Tabla 9. Cálculo de gastos y velocidades de la red principal del edificio. .................................. 71
Tabla 10. Dimensionamiento del cárcamo ................................................................................. 88

3
Tabla 11. Cálculo de línea de bombeo. ..................................................................................... 90
Tabla 12. Intensidad - Duración - Periodo de Retorno de la cuenca Atemajac (i-d-Tr).............. 92
Tabla 13. Ponderación de coeficientes de escurrimiento........................................................... 94
Tabla 14. Cálculo de características físicas. .............................................................................. 95
Tabla 15. Cálculo de gastos pluviales con el método Racional Americano. .............................. 95
Tabla 16. Ponderación de los gastos pluviales de las áreas de proyecto. ................................. 97
Tabla 17. Cálculo del diámetro comercial para los bajantes. ..................................................... 97
Tabla 18. Cálculo de la red pluvial. .......................................................................................... 100
Tabla 19. Bocas de Tormentas. ............................................................................................... 102
Tabla 20. Cálculo de tubería de descarga de boca de tormenta. ............................................ 102
Tabla 21. Dimensionamiento y selección de bomba pluvial..................................................... 102
Tabla 22. Tránsito de cárcamo de bombeo en estacionamiento del sótano. ........................... 103
Tabla 23. Tránsito de depósito de regulación. ......................................................................... 106
Tabla 24. Cálculo de perdida de carga, tubería de succión e impulsión. ................................. 113
Tabla 25. Cálculo de diámetro de la placa orificio ................................................................... 116

4
1 INTRODUCCIÓN GENERAL.

Como parte del proyecto de construcción de la unidad médica familiar (UNIMEF) del instituto de
pensiones del estado de Jalisco (IPEJAL). Se presenta los proyectos de redes de agua potable,
drenaje sanitario, drenaje pluvial, instalación contra incendios que servirán para atender a las
necesidades diarias de servicios básicos del personal y usuarios de la unidad.

El predio en estudio se encuentra ubicado ubicada en Av. Federalistas, esquina con la calle
Trafalgar, colonia Colinas del Rey en el municipio de Zapopan, Jalisco. El predio se encuentra
aproximadamente en las coordenadas UTM:

665,966.00 m E y 2,295,517.67 m N

Figura 1. Localización del proyecto.

5
2 PROYECTO DE AGUA POTABLE.

2.1 INTRODUCCIÓN

Para el diseño de la red de agua potable se tienen que considerar que el predio se alimentará
con la conexión a la red pública del SIAPA.

El diseño de la red de agua potable del edificio será dividido en tres niveles: Sótano, Planta Baja
y Planta Alta. El suministro de agua potable de la unidad médica será por sistema de presión
variable (hidroneumático) y depósito de almacenamiento.

Para el diseño de la red de agua potable se utilizará el método de Hunter, que es uno de los más
utilizados en el mundo, el cual define que para el dimensionamiento de las tuberías se tiene en
cuenta que todos los aparatos instalados no funcionan simultáneamente; por esta razón se deben
distinguir varios tipos de caudal.

El método pretende evaluar el caudal máximo probable y se basa en el concepto de que


únicamente unos pocos aparatos, de todos los que están conectados al sistema, entrarán en
operación simultánea en un instante de tiempo dado.

2.2 OBJETIVO DE PROYECTO DE AGUA POTABLE

El objetivo de la instalación hidráulica es suministrar agua fría y caliente a los muebles sanitarios,
de los baños, consultorios, área de hemodiálisis, aseo, cocinas, jardines y de toda aquellas áreas
que requiera de agua potable dentro la unidad médica, de acuerdo a los criterios de diseño y
normatividad tanto del Instituto Mexicano del Seguro Social (IMSS) y del Sistema Intermunicipal
de los Servicios de Agua Potable y Alcantarillado (SIAPA) expuesto en los alcances del proyecto
antes mencionados.

2.3 DESCRIPCIÓN GENERAL DEL PROYECTO HIDRÁULICO

Cada equipo que requiera servicio en conjunto será alimentado por el equipo de bombeo de
velocidad variable el cual se encuentra en el cuarto de máquinas junto a la cisterna destinada
para uso de servicios de agua potable (dos celdas), el agua que abastecerá a las celdas proviene
de la red de distribución de agua potable municipal.

El abastecimiento a los servicios se realizará a partir de la Red de Agua Potable Interna, esta red
será abastecida en cantidad suficiente y dotará de la presión al sistema por medio de equipos de
velocidad variable.

El sistema de Bombeo que se implementara en el proyecto, tendrá la capacidad de abastecer de


agua a los muebles sanitarios para que se logre el correcto suministro del líquido y tenga la
capacidad de dar la presión necesaria mínima al mueble más crítico o más lejano de la unidad,

6
así como la demanda de gasto requerido por cada mueble en consideración de un gasto
simultaneo.

2.4 DOTACIÓN DE AGUA POTABLE

Por ser catalogado como hospital la dotación se divide en diferentes usos que serán obtenidos
con base en la tabla 4.1 Dotaciones mínimas de agua de las normas de diseño de ingeniería del
IMSS, los usos encontrados son: Camas/equipos de hemodiálisis, consultorios, lavanderías,
áreas de oficina, áreas verdes y áreas de estacionamientos.

Figura 2. Dotaciones mínimas de agua.

En la siguiente tabla se presenta el cálculo del volumen diario que requiere la unidad medica

7
Tabla 1. Dotación diaria de agua potable.
Tipo de uso Dotación Unidad Cantidad Volumen total
Camas/eq de hemodialísis 1250 l/día 22 27500
Consultorios 500 l/día 18 9000
Lavanderia 200 cama/día 30 6000
Oficinas 20 m2/día 263.08 5261.6
Área verdes 5 l/m2/d 367 1835
Área de estacionamiento 2 l/m2/d 1116 2232
TOTAL 51828.6 l/día
51.8286 m3/día

Para el proyecto se propuso una dotación promedio de 329.5 l/día que da como resultado un
volumen de 51,829 l/día (Ver Tabla 1). para este proyecto se propone instalar un sistema central
de presión variable que comprende la implementación de dos bombas con capacidad del 100%
del gasto máximo de la red, trabajando en forma alternada y en casos excepcionales en forma
simultánea y de un tanque hidroneumático que trabaje para mantener una presión regulada en
la línea interna del edificio.

2.5 GASTO MEDIO DIARIO

Este gasto se define como la cantidad de agua requerida, para satisfacer las necesidades de una
población en un día de consumo promedio, y se calcula con la ecuación:

Qmed 
P.P.Dot
86,400s

Donde:

Qmed = Gasto medio diario en (l/s)

P.p. = Población de Proyecto en (hab)

Dot = Dotación diaria (l/emp*día) (definida por el organismo operador)

86,400= Cantidad de segundos en un día. (s)

2.6 GASTO MÁXIMO DIARIO

Este gasto se define como el gasto medio que se representa en el día de máximo consumo a lo
largo del año y se obtiene multiplicando el gasto medio diario por un factor llamado coeficiente
de variación diaria, el cual de acuerdo a los criterios técnicos del SIAPA este coeficiente varía
entre 1.20 y 1.50.

En este caso se considera el valor de 1.40, por lo que tenemos:

8
Q max .diario  Qmed * C .V .D .

Donde:

Qmax diario = Gasto máximo diario en (l/s)

Qmed = Gasto medio diario en (l/s)

C.V.D. = Coeficiente de Variación Diaria (adm)

2.7 GASTO MÁXIMO HORARIO

Este gasto se define como el mayor caudal que se presenta durante la hora de máximo consumo
del día de máximo consumo durante el año y se calcula afectando al gasto máximo diario por un
coeficiente de variación horaria, el cual tiene un valor entre 1.50 y 2.0.

En este caso se considera el valor de 1.50, por lo que tenemos:

Q max .horario  Q max .diario * C .V . H .

Donde:

Qmax horario = Gasto máximo horario en (l/s)

Qmax diario = Gasto máximo diario en (l/s)

C.V.H. = Coeficiente de Variación Horaria (adm)

En la siguiente tabla se presentan los cálculos antes mencionados


Tabla 2. Datos básicos del proyecto de agua potable.
DATOS BÁSICOS
Material TUBOPLUS
Rugosidad 0.007 mm
Qmed (l/s) 3.36
CvD 1.40
Qm axD (l/s) 4.71
CvH 1.50
Qm axH (l/s) 7.06
QmaxH (l/min) 423.60

9
2.8 CALCULO DE LA TOMA DOMICILIARIA

El cálculo de la toma domiciliaria está sujeto al cálculo del gasto Máximo Horario y para su
obtención se recurre a los conceptos de gastos medio diario, máximo diario y máximo horario
establecidos por parte de la CONAGUA y presentados en el tema anterior.

A partir de la ecuación de continuidad:

= ∗

Donde:

Q= Gasto máximo diario en (m3/s)

V= Velocidad media en (m/s)

A= Área hidráulica del conducto (m2)

Aplicando las fórmulas anteriores tenemos:

Sabiendo que: = ∗

Entonces:

4 * Q max .diario
Ø
v *

Donde:

4= Constante geométrica

Ø= Diámetro interior del conducto del diámetro económico en (m)

Proponiendo un caudal de 3 l/s y una velocidad de 1.50 m/s, se obtienen los siguientes resultados
para el diámetro teórico de la tubería:

4 ∗ 0.003( 3/ )
∅= = 0.05 ≈ 2.00
1.50 ∗

Por lo que se propone un diámetro comercial de la toma domiciliaria de 2” de diámetro.

10
2.9 CALCULO DE VOLUMEN DE CISTERNA

El primer paso es, calcular el volumen de almacenamiento necesario para dotar de agua a la
unidad médica, para esto se propone que la cisterna deberá de almacenar el volumen de agua
necesario para satisfacer dos días, sumado al volumen de agua que requiere el sistema de
protección contra incendios (PCI). La cisterna contara con dos celdas las cuales servirán de
manera conjunta y que solo deberán ser vaciadas para su limpieza.

El cálculo arroja que es necesario contar con un volumen de 104 m3 para agua potable y de
33.50 m3 para la red de protección contra incendios. Se pretende construir una cisterna de
concreto dividida en dos celdas la primera celda con capacidad de 71.60 m3 y la segunda con
capacidad de 74.00 m3, considerando un tirante de 1.80m, que sumados dan un volumen de
almacenamiento de 145.6 m3 con lo que se cumple el objetivo de dotar de agua al edificio por al
menos 2 días y de almacenar el volumen para utilizar en caso de incendio, según la normativa
del organismo operador y del IMSS.

En la siguiente tabla se presenta el cálculo del volumen requerido para este fin y las dimensiones
propuestas de la cisterna.
Tabla 3. Cálculo de la capacidad de almacenamiento de la cisterna.
VOLUMEN DE CISTERNA
2 días del consumo díario+ Vol PCI
Vol requerido AP (m3) 103.66
Vol requerido PCI (m3) 33.50
Celda 1 (m2) 39.78
Celda 2 (m2) 41.10
Alto (m) 1.80
Vol almacenado en celda 1 (m3) 71.60
Vol almacenado en celda 2 (m3) 73.98
Volumen total (m3) 145.58

2.10 CALCULO DE CAPACIDAD DE HIDRONEUMÁTICO

Para el cálculo del volumen del equipo hidroneumático se propone un tanque de 480 litros con
la consideración que la bomba tendrá un número de arranques de 4 veces por hora y el tanque
un tiempo de vaciado de 13.3 minutos. También el sistema funcionará con una presión mínima
de 3.65 Kg/cm2 y presión máxima de 4.65 Kg/cm2 (ver Tabla 7).

11
Tabla 4. Cálculo de la capacidad del tanque hidroneumático.

CAPACIDAD DE HIDRONEUMÁTICO

Numero de Arranques
4
(bomba)
Presión Mínima 36.52
Presión Máxima 46.52
Volumen propuesto
de Hidroneumático 480
(litros)
Tiempo vaciado (min) 13.3

2.11 DETERMINACIÓN DE LA CARGA TOTAL DE BOMBEO

Para determinar la carga total de bombeo se suman las alturas topográficas de bombeo, las
pérdidas en succión y descarga, altura del edificio, las pérdidas y presión mínima hasta el mueble
más desfavorable. Después con el gasto a bombear y la potencia requerida, buscar entre los
proveedores una bomba que cumpla con las características calculadas.

Con los resultados se obtiene que los requerimientos son una carga total de 46.52 m y un gasto
de 7.00 l/s. Por lo tanto, la bomba seleccionada/propuesta tiene una capacidad para alcanzar a
operar hasta una altura óptima de 48.00 m y un gasto óptimo de 7.00 l/s.
Tabla 5. Cálculo de carga total y potencia de la bomba.
CARGA DE LA BOMBA (H) EN METROS

ALTURA DE DESCARGA (hs) (DEPÓSITO BAJO LA BOMBA) 3.00


ALTURA DE EDIFICIO (h) (NIVEL BOMBA A NIVEL DE TECHO) 7.40
PÉRDIDA EN SUCCIÓN Y DESCARGA DE BOMBA (hfs) 3.00
SUMATORIA DE PÉRDIDAS DESDE HIDRONEUMÁTICO AL MUEBLE MAS DESFAVORABLE (hfd) 8.12
PRESIÓN MÍNIMA (1.5 KG/CM2.) EN LA PIEZA MENOS FAVORECIDA 15.00
PRESIÓN MÍNIMA DE ARRANQUE DE LA BOMBA (H min) 36.52
PRESIÓN DIFERENCIAL ENTRE EL ARRANQUE EL PARO DE LA BOMBA 10.00
PRESIÓN MÁXIMA DE PARO DE LA BOMBA 46.52
CARGA TOTAL (H) (m) 46.52

2.12 RED DE DISTRIBUCIÓN

Una red de distribución se define como el conjunto de tuberías, accesorios y estructuras que
conducen el agua potable desde los tanques de regulación y/o almacenamiento, o desde el punto
de conexión con alguna red ya existente, hasta las tomas domiciliarias, cisternas de
almacenamiento o hidrantes públicos. De acuerdo a su función, la red de distribución puede
dividirse en red primaria o red secundaria.

12
En este caso la red de distribución se considera como del tipo secundaria ya que es para uso
interno y exclusivo de la unidad médica.

Debido a que la distribución será por medio de bombeo directo a la red a partir de la cisterna de
almacenamiento de agua potable, la operación consistirá en un sistema que garantice la carga
hidráulica adecuada para el suministro, considerando equipos que puedan trabajar bajo un
variado régimen de la demanda que pueda presentarse durante las 24 horas de un día normal
garantizando que la presión sea constante en la red y que el gasto sea de acuerdo a la
demandada.

Para la red interna se calculan para cada tramo la cantidad de Unidades Mueble (U.M.) que
abastecerán y que dependerá del tipo de mueble que se tenga instalado en la red. Por ejemplo,
un WC equivale a 1 U.M., los lavabos 1.5 U.M., los mingitorios 3 U.M. y fregaderos y llaves 2
U.M., los WC con fluxómetro a 3 U.M. y las regaderas a 2 U.M. en la siguiente figura se presenta
la tabla 5.2 de las normas de diseño de ingeniería del IMSS, donde se obtienen las unidades
muebles para clínicas y hospitales

13
Figura 3. Cálculo de Unidades Mueble en Clínicas y Hospitales.

14
Aplicando la metodología de Hunter se calcula el gasto probable que conducirá cada tramo con
base en el acumulado de unidades mueble y su gasto equivalente, estos datos se obtiene de la
tabla 5.4 de las normas de diseño de ingeniería del IMSS

Figura 4. Gasto en función de unidades mueble, Método Hunter – Nielsen.

En la siguiente tabla se presentan los tramos de toda la red, el mueble al que darán
servicio y en su caso el acumulado de unidades mueble y su respectivo gasto probable,
obtenido de la tabla anterior, esto considerando que existen baños con fluxómetro.

15
Tabla 6. Sumatoria de unidades mueble, determinación de gasto probable.
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
R H22  EQ. HEMO 1.0
R - H22 SUMA 1.0 0.10
S H21  EQ. HEMO 1.0
S - H21 SUMA 1.0 0.10
S H20  EQ. HEMO 1.0
S - H20 SUMA 1.0 0.10
R S  S - H21 1.0
S - H20 1.0
R-S SUMA 2.0 0.18
Q R  R - H22 1.0
R-S 2.0
Q-R SUMA 3.0 0.25
Q H19  EQ. HEMO 1.0
Q - H19 SUMA 1.0 0.10
Ñ Q  Q-R 3.0
Q - H19 1.0
Ñ-Q SUMA 4.0 0.31
P H18  EQ. HEMO 1.0
P - H18 SUMA 1.0 0.10
P H17  EQ. HEMO 1.0
P - H17 SUMA 1.0 0.10
O P  P - H18 1.0
P - H17 1.0
O-P SUMA 2.0 0.18
O H16  EQ. HEMO 1.0
O - H16 SUMA 1.0 0.10
Ñ O  O-P 2.0
O - H16 1.0
Ñ-O SUMA 3.0 0.25
N Ñ  Ñ-Q 4.0
Ñ-O 3.0
N-Ñ SUMA 7.0 1.48
N H15  EQ. HEMO 1.0
N - H15 SUMA 1.0 0.10
M N  N-Ñ 7.0
N - H15 1.0
M-N SUMA 8.0 1.56
M H14  EQ. HEMO 1.0
M - H14 SUMA 1.0 0.10
L M  M-N 8.0
M - H14 1.0
L-M SUMA 9.0 1.63

16
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
L H13  EQ. HEMO 1.0
L - H13 SUMA 1.0 0.10
I L  L-M 9.0
L - H13 1.0
I-L SUMA 10.0 1.70
K H10  EQ. HEMO 1.0
K - H10 SUMA 1.0 0.10
K H11  EQ. HEMO 1.0
K - H11 SUMA 1.0 0.10
J K  K - H10 1.0
K - H11 1.0
J-K SUMA 2.0 0.18
J H12  EQ. HEMO 1.0
J - H12 SUMA 1.0 0.10
I J  J-K 2.0
J - H12 1.0
I-J SUMA 3.0 0.25
H I  I-L 10.0
I-J 3.0
H-I SUMA 13.0 1.88
H H5  EQ. HEMO 1.0
H - H5 SUMA 1.0 0.10
G H  H-I 13.0
H - H5 1.0
G-H SUMA 14.0 1.93
G H4  EQ. HEMO 1.0
G - H4 SUMA 1.0 0.10
A G  G-H 14.0
G - H4 1.0
A-G SUMA 15.0 1.98
F H6  EQ. HEMO 1.0
F - H6 SUMA 1.0 0.10
F H7  EQ. HEMO 1.0
F - H7 SUMA 1.0 0.10
E F  F - H6 1.0
F - H7 1.0
E-F SUMA 2.0 0.18
E H8  EQ. HEMO 1.0
E - H8 SUMA 1.0 0.10

17
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
D E  E-F 2.0
E - H8 1.0
D -E SUMA 3.0 0.25
D H9  EQ. HEMO 1.0
D - H9 SUMA 1.0 0.10
A D  D-E 3.0
D - H9 1.0
A-D SUMA 4.0 0.31
C H1  EQ. HEMO 1.0
C - H1 SUMA 1.0 0.10
C H2  EQ. HEMO 1.0
C - H2 SUMA 1.0 0.10
B C  C - H1 1.0
C - H2 1.0
B-C SUMA 2.0 0.18
B H3  EQ. HEMO 1.0
B - H3 SUMA 1.0 0.10
A B  B-C 2.0
B - H3 1.0
A-B SUMA 3.0 0.25
EQ. OI A  A-G 15.0
A-D 4.0
A-B 3.0
EQ. OI - A SUMA 22.0 2.29
164 EQ. OI  EQ. OI - A 22.0
164 - EQ. OI SUMA 22.0 2.29
164 WC-F  WC-FLUX 3.0
164 - WC-F SUMA 3.0 0.25
163 164  164 - EQ. OI 22.0
164 - WC-F 3.0
163 - 164 SUMA 25.0 2.41
163 L  LAVABO 1.0
163 - L SUMA 1.0 0.10
162 163  163 - 164 25.0
163 - L 1.0
162 - 163 SUMA 26.0 2.45
167 L1  LAVABO 1.0
167 - L1 SUMA 1.0 0.10
167 L2  LAVABO 1.0
167 - L2 SUMA 1.0 0.10
166 167  167 - L1 1.0
 167 - L2 1.0
166 - 167 SUMA 2.0 0.18

18
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
166 WC-F  WC-FLUX 3.0
166 - WC-F SUMA 3.0 0.25
165 166  166 - 167 2.0
 166 - WC-F 3.0
165 - 166 SUMA 5.0 1.30
165 L  LAVABO 1.0
165 - L SUMA 1.0 0.10
162 165  165 - 166 5.0
Nota 1  165 - L 1.0
162 - 165 SUMA 5.0 1.30
161 162  162 - 163 26.0
 162 - 165 5.0
161 - 162 SUMA 31.0 2.64
161 L  LAVABO 1.0
161 - L SUMA 1.0 0.10
156 161  161 - 162 31.0
 161 - L 1.0
156 - 161 SUMA 32.0 2.67
160 L  LAVABO 1.0
160 - L SUMA 1.0 0.10
160 WC-F  WC-FLUX 3.0
160 - WC-F SUMA 3.0 0.25
159 160  160 - L 1.0
Nota 1  160 - WC-F 3.0
159 - 160 SUMA 3.0 0.25
159 T  MEZCLADORA 2.0
159 - T SUMA 2.0 0.18
158 159  159 - 160 3.0
 159 - T 2.0
158 - 159 SUMA 5.0 1.30
158 T  MEZCLADORA 2.0
158 - T SUMA 2.0 0.18
157 158  158 - 159 5.0
 158 - T 2.0
157 - 158 SUMA 7.0 1.48
157 T  MEZCLADORA 2.0
157 - T SUMA 2.0 0.18
156 157  157 - 158 7.0
 157 - T 2.0
156 - 157 SUMA 9.0 1.63
155 156  156 - 161 32.0
 156 - 157 9.0
155 - 156 SUMA 41.0 2.94
155 T  MEZCLADORA 2.0
155 - T SUMA 2.0 0.18

19
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
154 155  155 - 156 41.0
 155 - T 2.0
154 - 155 SUMA 43.0 3.00
154 T  MEZCLADORA 2.0
154 - T SUMA 2.0 0.18
150 154  154 - 155 43.0
 154 - T 2.0
150 - 154 SUMA 45.0 3.06
153 L1  LAVABO 1.0
153 - L1 SUMA 1.0 0.10
153 L2  LAVABO 1.0
153 - L2 SUMA 1.0 0.10
152 153  153 - L1 1.0
153 - L2 1.0
152 - 153 SUMA 2.0 0.18
152 WC-F  WC-FLUX 3.0
152 - WC-F SUMA 3.0 0.25
151 152  152 - 153 2.0
152 - WC-F 3.0
151 - 152 SUMA 5.0 1.30
151 WC-F  WC-FLUX 3.0
151 - WC-F SUMA 3.0 0.25
150 151  151 - 152 5.0
151 - WC-F 3.0
150 - 151 SUMA 8.0 1.56
124 150  150 - 154 45.0
150 - 151 8.0
124 - 150 SUMA 53.0 3.27
149 L1  LAVABO 1.0
149 - L1 SUMA 1.0 0.10
149 L2  LAVABO 1.0
149 - L2 SUMA 1.0 0.10
148 149  149 - L1 1.0
149 - L2 1.0
148 - 149 SUMA 1.0 0.10
148 WC-F  WC-FLUX 3.0
148 - WC-F SUMA 3.0 0.25
147 148  148 - 149 1.0
 148 - WC-F 3.0
147 - 148 SUMA 4.0 0.31
147 WC-F  WC-FLUX 3.0
147 - WC-F SUMA 3.0 0.25
146 147  147 - 148 4.0
 147 - WC-F 3.0
146 - 147 SUMA 7.0 1.48
146 T  VERTEDERO 2.0
146 - T SUMA 2.0 0.18

20
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
145 146  146 - 147 7.0
146 - T 2.0
145 - 146 SUMA 9.0 1.63
145 WC-F  WC-FLUX 3.0
145 - WC-F SUMA 3.0 0.25
144 145  145 - 146 9.0
145 - WC-F 3.0
144 - 145 SUMA 12.0 1.82
144 LL  LLAVE 1.0
144 - LL SUMA 1.0 0.10
139 144  144 - 145 12.0
 144 - LL 1.0
139 - 144 SUMA 13.0 1.88
143 L1  LAVABO 1.0
143 - L1 SUMA 1.0 0.10
143 L2  LAVABO 1.0
143 - L2 SUMA 1.0 0.10
142 143  143 - L1 1.0
 143 - L2 1.0
142 - 143 SUMA 2.0 0.18
142 L  LAVABO 1.0
142 - L SUMA 1.0 0.10
141 142  142 - 143 2.0
142 - L 1.0
141 - 142 SUMA 3.0 0.25
141 L  LAVABO 1.0
141 - L SUMA 1.0 0.10
140 141  141 - 142 3.0
 141 - L 1.0
140 - 141 SUMA 4.0 0.31
140 L  LAVABO 1.0
140 - L SUMA 1.0 0.10
139 140  140 - 141 4.0
 140 - L 1.0
139 - 140 SUMA 5.0 1.30
138 139  139 - 144 13.0
 139 - 140 5.0
138 - 139 SUMA 18.0 2.13
138 LL  LAVABO 1.0
138 - LL SUMA 1.0 0.10
130 138  138 - 139 18.0
138 - LL 1.0
130 - 138 SUMA 19.0 2.17

21
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
137 WC-F1  WC FLUX 3.0
137 - WC-F1 SUMA 3.0 0.25
137 WC-F2  WC FLUX 3.0
137 - WC-F2 SUMA 3.0 0.25
136 137  137 - WC-F1 3.0
 137 - WC-F2 3.0
136 - 137 SUMA 6.0 1.39
136 WC-F  WC FLUX 3.0
136 - WC-F SUMA 3.0 0.25
135 136  136 - 137 6.0
 136 - WC-F 3.0
135 - 136 SUMA 9.0 1.63
135 WC-F  WC FLUX 3.0
135 - WC-F SUMA 3.0 0.25
134 135  135 - 136 9.0
 135 - WC-F 3.0
134 - 135 SUMA 12.0 1.82
134 WC-F  WC FLUX 3.0
134 - WC-F SUMA 3.0 0.25
133 134  134 - 135 12.0
 134 - WC-F 3.0
133 - 134 SUMA 15.0 1.98
133 M  MINGITORIO 2.0
133 - M SUMA 2.0 0.18
132 133  133 - 134 15.0
 133 - M 2.0
132 - 133 SUMA 17.0 2.08
132 WC-F  WC FLUX 3.0
132 - WC-F SUMA 3.0 0.25
131 132  132 - 133 17.0
132 - WC-F 3.0
131 - 132 SUMA 20.0 2.21
131 M  MINGITORIO 2.0
131 - M SUMA 2.0 0.18
130 131  131 - 132 20.0
 131 - M 2.0
130 - 131 SUMA 22.0 2.29
125 130  130 - 138 19.0
 130 - 131 22.0
125 - 130 SUMA 41.0 2.94
129 L1  LAVABO 1.0
129 - L1 SUMA 1.0 0.10

22
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
129 L2  LAVABO 1.0
129 - L2 SUMA 1.0 0.10
128 129  129 - L1 1.0
 129 - L2 1.0
128 - 129 SUMA 2.0 0.18
128 L  LAVABO 1.0
128 - L SUMA 1.0 0.10
127 128  128 - 129 2.0
 128 - L 1.0
127 - 128 SUMA 3.0 0.25
127 L  LAVABO 1.0
127 - L SUMA 1.0 0.10
126 127  127 - 128 3.0
 127 - L 1.0
126 - 127 SUMA 4.0 0.31
126 L  LAVABO 1.0
126 - L SUMA 1.0 0.10
125 126  126 - 127 4.0
 126 - L 1.0
125 - 126 SUMA 5.0 1.30
124 125  125 - 130 41.0
 125 - 126 5.0
124 - 125 SUMA 46.0 3.09
123 124  124 - 150 53.0
 124 - 125 46.0
123 - 124 SUMA 99.0 4.18
123 L  LAVABO 1.0
123 - L SUMA 1.0 0.10
122 123  123 - 124 99.0
123 - L 1.0
122 - 123 SUMA 100.0 4.20
122 WC  WC 1.0
122 - WC SUMA 1.0 0.10
121 122  122 - 123 100.0
 122 - WC 1.0
121 - 122 SUMA 101.0 4.22
121 WC  WC 1.0
121 - WC SUMA 1.0 0.10
120 121  121 - 122 101.0
 121 - WC 1.0
120 - 121 SUMA 102.0 4.23

23
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
120 L  LAVABO 1.0
120 - L SUMA 1.0 0.10
119A 120  120 - 121 102.0
 120 - L 1.0
119A - 120 SUMA 103.0 4.25
119D L-1 LAVABO 1.0
119D - L-1 SUMA 1.0 0.10
119D L-2 LAVABO 1.0
119D - L-2 SUMA 1.0 0.10
119C 119D  119D - L-1 1.0
 119D - L-2 1.0
119C - 119D SUMA 2.0 0.18
119C WC-F WC FLUX 3.0
119C - WC-F SUMA 3.0 0.25
119B 119C 119C - 119D 2.0
119C - WC-F 3.0
119B - 119C SUMA 5.0 1.30
119B WC-F WC FLUX 3.0
119B - WC-F SUMA 3.0 0.25
119A 119B 119B - 119C 5.0
119B - WC-F 3.0
119A - 119B SUMA 8.0 1.56
119 119A 119A - 120 103.0
119A - 119B 8.0
119 - 119A SUMA 111.0 4.38
119 T  VERTEDERO 2.0
119 - T SUMA 2.0 0.18
118 119  119 - 119A 111.0
 119 - T 2.0
118 - 119 SUMA 113.0 4.41
118 T  VERTEDERO 2.0
118 - T SUMA 2.0 0.18
SIST BOM 118  118 - 119 113.0
 118 - T 2.0
SIST BOM - 118 SUMA 115.0 4.44
117 LL  LLAVE 1.0
117 - LL SUMA 1.0 0.10
117 WC-F  WC FLUX 3.0
117 - WC-F SUMA 3.0 0.25
116 117  117 - LL 1.0
 117 - WC-F 3.0
116 - 117 SUMA 4.0 0.31

24
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
116 L  LAVABO 1.0
116 - L SUMA 1.0 0.10
115 116  116 - 117 4.0
NOTA 1  116 - L 1.0
115 - 116 SUMA 4.0 0.31
115 L  LAVABO 1.0
115 - L SUMA 1.0 0.10
114 115  115 - 116 4.0
 115 - L 1.0
114 - 115 SUMA 5.0 1.30
114 WC-F  WC FLUX 3.0
114 - WC-F SUMA 3.0 0.25
113 114  114 - 115 5.0
 114 - WC-F 3.0
113 - 114 SUMA 8.0 1.56
113 LL  LLAVE 1.0
113 - LL SUMA 1.0 0.10
112 113  113 - 114 8.0
 113 - LL 1.0
112 - 113 SUMA 9.0 1.63

25
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
112 WC-F  WC FLUX 3.0
112 - WC-F SUMA 3.0 0.25
111 112  112 - 113 9.0
 112 - WC-F 3.0
111 - 112 SUMA 12.0 1.82
111 L  LAVABO 1.0
111 - L SUMA 1.0 0.10
110 111  111 - 112 12.0
 111 - L 1.0
110 - 111 SUMA 13.0 1.88
110 L  LAVABO 1.0
110 - L SUMA 1.0 0.10
109 110  110 - 111 13.0
 110 - L 1.0
109 - 110 SUMA 14.0 1.93
109 WC-F  WC FLUX 3.0
109 - WC-F SUMA 3.0 0.25
108 109  109 - 110 14.0
 109 - WC-F 3.0
108 - 109 SUMA 17.0 2.08
108 T  VERTEDERO 2.0
108 - T SUMA 2.0 0.18
106 108  108 - 109 17.0
 108 - T 2.0
106 - 108 SUMA 19.0 2.17
107 WC-F  WC FLUX 3.0
107 - WC-F SUMA 3.0 0.25
107 L  LAVABO 1.0
107 - L SUMA 1.0 0.10
106 107  107 - WC-F 3.0
NOTA 1  107 - L 1.0
106 - 107 SUMA 3.0 0.25
105 106  106 - 108 19.0
 106 - 107 3.0
105 - 106 SUMA 22.0 2.29
105 T  VERTEDERO 2.0
105 - T SUMA 2.0 0.18
99 105  105 - 106 22.0
 105 - T 2.0
99 - 105 SUMA 24.0 2.37
104 LL1  LLAVE 1.0
104 - LL1 SUMA 1.0 0.10

26
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
104 LL2  LLAVE 1.0
104 - LL2 SUMA 1.0 0.10
103 104  104 - LL1 1.0
 104 - LL2 1.0
103 - 104 SUMA 2.0 0.18
103 T  VERTEDERO 2.0
103 - T SUMA 2.0 0.18
101 103  103 - 104 2.0
 103 - T 2.0
101 - 103 SUMA 4.0 0.31
102 T1  VERTEDERO 2.0
102 - T1 SUMA 2.0 0.18
102 T2  VERTEDERO 2.0
102 - T2 SUMA 2.0 0.18
101 102  102 - T1 2.0
 102 - T2 2.0
101 - 102 SUMA 4.0 0.31
100 101  101 - 103 4.0
 101 - 102 4.0
100 - 101 SUMA 8.0 1.56
100 REG  REGADERA 2.0
100 - REG SUMA 2.0 0.18
99 100  100 - 101 8.0
 100 - REG 2.0
99 - 100 SUMA 10.0 1.70
94 99  99 - 105 24.0
 99 - 100 10.0
94 - 99 SUMA 34.0 2.73
98 WC-F  WC FLUX 3.0
98 - WC-F SUMA 3.0 0.25
98 T  VERTEDERO 2.0
98 - T SUMA 2.0 0.18
97 98  98 - WC-F 3.0
 98 - T 2.0
97 - 98 SUMA 5.0 1.30
97 L  LAVABO 1.0
97 - L SUMA 1.0 0.10
96 97  97 - 98 5.0
NOTA 1  97 - L 1.0
96 - 97 SUMA 5.0 1.30
96 L  LAVABO 1.0
96 - L SUMA 1.0 0.10

27
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
95 96  96 - 97 5.0
 96 - L 1.0
95 - 96 SUMA 6.0 1.39
95 WC-F  WC FLUX 3.0
95 - WC-F SUMA 3.0 0.25
94 95  95 - 96 6.0
NOTA 1  95 - WC-F 3.0
94 - 95 SUMA 8.0 1.56
93 94  94 - 99 34.0
 94 - 95 8.0
93 - 94 SUMA 42.0 2.97
93 T  VERTEDERO 2.0
93 - T SUMA 2.0 0.18
91 93  93 - 94 42.0
 93 - T 2.0
91 - 93 SUMA 44.0 3.03
92 T1  VERTEDERO 2.0
92 - T1 SUMA 2.0 0.18
92 T2  VERTEDERO 2.0
92 - T2 SUMA 2.0 0.18
91 92  92 - T1 2.0
 92 - T2 2.0
91 - 92 SUMA 4.0 0.31
90 91  91 - 93 44.0
 91 - 92 4.0
90 - 91 SUMA 48.0 3.15
90 T  VERTEDERO 2.0
90 - T SUMA 2.0 0.18
87 90  90 - 91 48.0
90 - T 2.0
87 - 90 SUMA 50.0 3.20
89 L  LLAVE 1.0
89 - L SUMA 1.0 0.10
89 WC-F  WC FLUX 3.0
89 - WC-F SUMA 3.0 0.25
88 89  89 - L 1.0
89 - WC-F 3.0
88 - 89 SUMA 4.0 0.31
88 L  LAVABO 1.0
88 - L SUMA 1.0 0.10

28
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
87 88  88 - 89 4.0
 88 - L 1.0
87 - 88 SUMA 5.0 1.30
SIST BOM 87  87 - 90 50.0
 87 - 88 5.0
SIST BOM - 87 SUMA 55.0 3.30
86 WC  WC 1.0
86 - WC SUMA 1.0 0.10
86 L  LAVABO 1.0
86 - L SUMA 1.0 0.10
85 86  86 - WC 1.0
NOTA 1  86 - L 1.0
85 - 86 SUMA 1.0 0.10
85 LL  LLAVE 1.0
85 - LL SUMA 1.0 0.10
84 85  85 - 86 1.0
 85 - LL 1.0
84 - 85 SUMA 2.0 0.18
84 T  VERTEDERO 2.0
84 - T SUMA 2.0 0.18
83 84  84 - 85 2.0
 84 - T 2.0
83 - 84 SUMA 4.0 0.31
83 T  VERTEDERO 2.0
83 - T SUMA 2.0 0.18
82 83  83 - 84 4.0
 83 - T 2.0
82 - 83 SUMA 6.0 1.39
82 T  VERTEDERO 2.0
82 - T SUMA 2.0 0.18
81A 82  82 - 83 6.0
 82 - T 2.0
81A - 82 SUMA 8.0 1.56
81D L  LAVABO 1.0
81D - L SUMA 1.0 0.10
81D WC-F  WC FLUX 3.0
81D - WC-F SUMA 3.0 0.25
81B 81D  81D - L 1.0
 81D - WC-F 3.0
81B - 81D SUMA 4.0 0.31
81C L  LAVABO 1.0
81C - L SUMA 1.0 0.10
81C WC-F  WC FLUX 3.0
81C - WC-F SUMA 3.0 0.25
81B 81C  81C - L 1.0
 81C - WC-F 3.0
81B - 81C SUMA 4.0 0.31

29
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
81A 81B  81B - 81D 4.0
 81B - 81C 4.0
81A - 81B SUMA 8.0 1.56
81 81A  81A - 82 8.0
 81A - 81B 8.0
81 - 81A SUMA 16.0 2.03
81 T  VERTEDERO 2.0
81 - T SUMA 2.0 0.18
79 81  81 - 81A 16.0
 81 - T 2.0
79 - 81 SUMA 18.0 2.13
80 LL1  LLAVE 1.0
80 - LL1 SUMA 1.0 0.10
80 LL2  LLAVE 1.0
80 - LL2 SUMA 1.0 0.10
79 80  80 - LL1 1.0
 80 - LL2 1.0
79 - 80 SUMA 2.0 0.18
78 79  79 - 81 18.0
 79 - 80 2.0
78 - 79 SUMA 20.0 2.21
78 T  VERTEDERO 2.0
78 - T SUMA 2.0 0.18
77 78  78 - 79 20.0
 78 - T 2.0
77 - 78 SUMA 22.0 2.29
77 T  VERTEDERO 2.0
77 - T SUMA 2.0 0.18
76 77  77 - 78 22.0
 77 - T 2.0
76 - 77 SUMA 24.0 2.37
76 D  EQ. ODONT 1.0
76 - D SUMA 1.0 0.10
75 76  76 - 77 24.0
 76 - D 1.0
75 - 76 SUMA 25.0 2.41
75 T  VERTEDERO 2.0
75 - T SUMA 2.0 0.18
74 75  75 - 76 25.0
 75 - T 2.0
74 - 75 SUMA 27.0 2.49
74 T  VERTEDERO 2.0
74 - T SUMA 2.0 0.18
28 74  74 - 75 27.0
 74 - T 2.0
28 - 74 SUMA 29.0 2.57

30
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
73 L  LAVABO 1.0
73 - L SUMA 1.0 0.10
73 WC-F  WC FLUX 3.0
73 - WC-F SUMA 3.0 0.25
71 73  73 - L 1.0
NOTA 1  73 - WC-F 3.0
71 - 73 SUMA 3.0 0.25
72 L  LAVABO 1.0
72 - L SUMA 1.0 0.10
72 WC-F  WC FLUX 3.0
72 - WC-F SUMA 3.0 0.25

31
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
71 72  72 - L 1.0
NOTA 1  72 - WC-F 3.0
71 - 72 SUMA 3.0 0.25
70 71  71 - 73 3.0
 71 - 72 3.0
70 - 71 SUMA 6.0 1.39
70 T  VERTEDERO 2.0
70 - T SUMA 2.0 0.18
64 70  70 - 71 6.0
 70 - T 2.0
64 - 70 SUMA 8.0 1.56
69 T  VERTEDERO 2.0
69 - T SUMA 2.0 0.18
69 WC-F  WC FLUX 3.0
69 - WC-F SUMA 3.0 0.25
68 69  69 - T 2.0
 69 - WC-F 3.0
68 - 69 SUMA 5.0 1.30
68 T  VERTEDERO 2.0
68 - T SUMA 2.0 0.18
67 68  68 - 69 5.0
 68 - T 2.0
67 - 68 SUMA 7.0 1.48
67 WC-F  WC FLUX 3.0
67 - WC-F SUMA 3.0 0.25
66 67  67 - 68 7.0
 67 - WC-F 3.0
66 - 67 SUMA 10.0 1.70
66 T  VERTEDERO 2.0
66 - T SUMA 2.0 0.18
65 66  66 - 67 10.0
 66 - T 2.0
65 - 66 SUMA 12.0 1.82
65 T  VERTEDERO 2.0
65 - T SUMA 2.0 0.18
64 65  65 - 66 12.0
 65 - T 2.0
64 - 65 SUMA 14.0 1.93
56 64  64 - 70 8.0
 64 - 65 14.0
56 - 64 SUMA 22.0 2.29

32
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
63 LL  LLAVE 1.0
63 - LL SUMA 1.0 0.10
63 WC-F  WC FLUX 3.0
63 - WC-F SUMA 3.0 0.25
61 63  63 - LL 1.0
 63 - WC-F 3.0
61 - 63 SUMA 4.0 0.31
62 L1  LAVABO 1.0
62 - L1 SUMA 1.0 0.10
62 L2  LAVABO 1.0
62 - L2 SUMA 1.0 0.10
61 62  62 - L1 1.0
 62 - L2 1.0
61 - 62 SUMA 2.0 0.18
60 61  61 - 63 4.0
 61 - 62 2.0
60 - 61 SUMA 6.0 1.39
60 LL  LLAVE 1.0
60 - LL SUMA 1.0 0.10
58 60  60 - 61 6.0
 60 - LL 1.0
58 - 60 SUMA 7.0 1.48
59 LL  LLAVE 1.0
59 - LL SUMA 1.0 0.10
59 T  VERTEDERO 2.0
59 - T SUMA 2.0 0.18
58 59  59 - LL 1.0
 59 - T 2.0
58 - 59 SUMA 3.0 0.25
57 58  58 - 60 7.0
 58 - 59 3.0
57 - 58 SUMA 10.0 1.70
57 L  LAVABO 1.0
57 - L SUMA 1.0 0.10
56 57  57 - 58 10.0
 57 - L 1.0
56 - 57 SUMA 11.0 1.76
50 56  56 - 64 22.0
 56 - 57 11.0
50 - 56 SUMA 33.0 2.70
54 T  VERTEDERO 2.0
54 - T SUMA 2.0 0.18

33
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
54 LL  LLAVE 1.0
54 - LL SUMA 1.0 0.10
53 54  54 - T 2.0
 54 - LL 1.0
53 - 54 SUMA 3.0 0.25
55 L  LAVABO 1.0
55 - L SUMA 1.0 0.10
55 WC-F  WC FLUX 3.0
55 - WC-F SUMA 3.0 0.25
53 55  55 - L 1.0
NOTA 1  55 - WC-F 3.0
53 - 55 SUMA 3.0 0.25
51 53  53 - 54 3.0
 53 - 55 3.0
51 - 53 SUMA 6.0 1.39
52 LL  LLAVE 1.0
52 - LL SUMA 1.0 0.10
52 WC-F  WC FLUX 3.0
52 - WC-F SUMA 3.0 0.25
51 52  52 - LL 1.0
NOTA 1  52 - WC-F 3.0
51 - 52 SUMA 3.0 0.25
50 51  51 - 53 6.0
 51 - 52 3.0
50 - 51 SUMA 9.0 1.63
42 50  50 - 56 33.0
 50 - 51 9.0
42 - 50 SUMA 42.0 2.97
49 LL  LLAVE 1.0
49 - LL SUMA 1.0 0.10
49 L  LAVABO 1.0
49 - L SUMA 1.0 0.10
48 49  49 - LL 1.0
 49 - L 1.0
48 - 49 SUMA 2.0 0.18
48 L  LAVABO 1.0
48 - L SUMA 1.0 0.10
47 48  48 - 49 2.0
 48 - L 1.0
47 - 48 SUMA 3.0 0.25
47 L  LAVABO 1.0
47 - L SUMA 1.0 0.10

34
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
46 47  47 - 48 3.0
 47 - L 1.0
46 - 47 SUMA 4.0 0.31
46 WC-F  WC FLUX 3.0
46 - WC-F SUMA 3.0 0.25
45 46  46 - 47 4.0
 46 - WC-F 3.0
45 - 46 SUMA 7.0 1.48
45 L  LAVABO 1.0
45 - L SUMA 1.0 0.10
44 45  45 - 46 7.0
 45 - L 1.0
44 - 45 SUMA 8.0 1.56
44 L  LAVABO 1.0
44 - L SUMA 1.0 0.10
43 44  44 - 45 8.0
 44 - L 1.0
43 - 44 SUMA 9.0 1.63
43 WC-F  WC FLUX 3.0
43 - WC-F SUMA 3.0 0.25
42 43  43 - 44 9.0
 43 - WC-F 3.0
42 - 43 SUMA 12.0 1.82
39 42  42 - 50 42.0
 42 - 43 12.0
39 - 42 SUMA 54.0 3.28
41 L1  LAVABO 1.0
41 - L1 SUMA 1.0 0.10
41 L2  LAVABO 1.0
41 - L2 SUMA 1.0 0.10
40 41  41 - L1 1.0
 41 - L2 1.0
40 - 41 SUMA 2.0 0.18
40 L  LAVABO 1.0
40 - L SUMA 1.0 0.10
39 40  40 - 41 2.0
40 - L 1.0
39 - 40 SUMA 3.0 0.25
33 39  39 - 42 54.0
 39 - 40 3.0
33 - 39 SUMA 57.0 3.34

35
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
38 WC-F  WC FLUX 3.0
38 - WC-F SUMA 3.0 0.25
38 M  MINGITORIO 2.0
38 - M SUMA 2.0 0.18
37 38  38 - WC-F 3.0
 38 - M 2.0
37 - 38 SUMA 5.0 1.30
37 WC-F  WC FLUX 3.0
37 - WC-F SUMA 3.0 0.25
36 37  37 - 38 5.0
 37 - WC-F 3.0
36 - 37 SUMA 8.0 1.56
36 WC-F  WC FLUX 3.0
36 - WC-F SUMA 3.0 0.25
35 36  36 - 37 8.0
 36 - WC-F 3.0
35 - 36 SUMA 11.0 1.76
35 WC-F  WC FLUX 3.0
35 - WC-F SUMA 3.0 0.25
34 35  35 - 36 11.0
 35 - WC-F 3.0
34 - 35 SUMA 14.0 1.93
34 WC-F  WC FLUX 3.0
34 - WC-F SUMA 3.0 0.25
33 34  34 - 35 14.0
 34 - WC-F 3.0
33 - 34 SUMA 17.0 2.08
31 33  33 - 39 57.0
 33 - 34 17.0
31 - 33 SUMA 74.0 3.68
32 T1  VERTEDERO 2.0
32 - T1 SUMA 2.0 0.18
32 T2  VERTEDERO 2.0
32 - T2 SUMA 2.0 0.18
31 32  32 - T1 2.0
 32 - T2 2.0
31 - 32 SUMA 4.0 0.31
29 31  31 - 33 74.0
 31 - 32 4.0
29 - 31 SUMA 78.0 3.68
30 T1  VERTEDERO 2.0
30 - T1 SUMA 2.0 0.18

36
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
30 T2  VERTEDERO 2.0
30 - T2 SUMA 2.0 0.18
29 30  30 - T1 2.0
 30 - T2 2.0
29 - 30 SUMA 4.0 0.31
28 29  29 - 31 78.0
 29 - 30 4.0
28 - 29 SUMA 82.0 3.84
SIST BOM 28  28 - 74 21.0
 28 - 29 82.0
SIST BOM - 28 SUMA 103.0 4.24
27 R1  REGADERA 1.5
27 - R1 SUMA 1.5 0.18
27 R2  REGADERA 1.5
27 - R2 SUMA 1.5 0.18
26 27  27 - R1 1.5
 27 - R2 1.5
26 - 27 SUMA 3.0 0.25
26 REG  REGADERA 1.5
26 - REG SUMA 1.5 0.18
CAL 26  26 - 27 3.0
 26 - REG 1.5
CAL - 26 SUMA 4.5 1.30
25 CAL  CAL - 26 4.5
25 - CAL SUMA 4.5 1.30
25 REG  REGADERA 1.5
25 - REG SUMA 1.5 0.18
24 25  25 - CAL 4.5
 25 - REG 1.5
24 - 25 SUMA 6.0 1.39
24 REG  REGADERA 1.5
24 - REG SUMA 1.5 0.18
23 24  24 - 25 6.0
 24 - REG 1.5
23 - 24 SUMA 7.5 1.56
23 REG  REGADERA 1.5
23 - REG SUMA 1.5 0.18
19 23  23 - 24 7.5
 23 - REG 1.5
19 - 23 SUMA 9.0 1.63
22 L1  LAVABO 1.0
22 - L1 SUMA 1.0 0.10

37
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
22 L2  LAVABO 1.0
22 - L2 SUMA 1.0 0.10
21 22  22 - L1 1.0
 22 - L2 1.0
21 - 22 SUMA 2.0 0.18
21 L  LAVABO 1.0
21 - L SUMA 1.0 0.10
20 21  21 - 22 2.0
 21 - L 1.0
20 - 21 SUMA 3.0 0.25
20 L  LAVABO 1.0
20 - L SUMA 1.0 0.10
19 20  20 - 21 3.0
 20 - L 1.0
19 - 20 SUMA 4.0 0.31
18 19  19 - 23 9.0
 19 - 20 4.0
18 - 19 SUMA 13.0 1.88
18 LL  LLAVE 1.0
18 - LL SUMA 1.0 0.10
12 18  18 - 19 13.0
 18 - LL 1.0
12 - 18 SUMA 14.0 1.93
17 WC/F1  WC FLUX 3.0
17 - WC/F1 SUMA 3.0 0.25
17 WC/F2  WC FLUX 3.0
17 - WC/F2 SUMA 3.0 0.25
16 17  17 - WC/F1 3.0
 17 - WC/F2 3.0
16 - 17 SUMA 6.0 1.39
16 WC-F  WC FLUX 3.0
16 - WC-F SUMA 3.0 0.25
15 16  16 - 17 6.0
 16 - WC-F 3.0
15 - 16 SUMA 9.0 1.63
15 WC-F  WC FLUX 3.0
15 - WC-F SUMA 3.0 0.25
14 15  15 - 16 9.0
 15 - WC-F 3.0
14 - 15 SUMA 12.0 1.82
14 WC-F  WC FLUX 3.0
14 - WC-F SUMA 3.0 0.25

38
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
13 14  14 - 15 12.0
 14 - WC-F 3.0
13 - 14 SUMA 15.0 1.98
13 WC-F  WC FLUX 3.0
13 - WC-F SUMA 3.0 0.25
12 13  13 - 14 15.0
 13 - WC-F 3.0
12 - 13 SUMA 18.0 2.13
11 12  12 - 18 14.0
 12 - 13 18.0
11 - 12 SUMA 32.0 2.67
11 LL  LLAVE 1.0
11 - LL SUMA 1.0 0.10
7 11  11 - 12 32.0
 11 - LL 1.0
7 - 11 SUMA 33.0 2.70
10 L1  LAVABO 1.0
10 - L1 SUMA 1.0 0.10
10 L2  LAVABO 1.0
10 - L2 SUMA 1.0 0.10
9 10  10 - L1 1.0
 10 - L2 1.0
9 - 10 SUMA 2.0 0.18
9 L  LAVABO 1.0
9-L SUMA 1.0 0.10
8 9  9 - 10 2.0
 9-L 1.0
8-9 SUMA 3.0 0.25
8 L  LAVABO 1.0
8-L SUMA 1.0 0.10
7 8  8-9 3.0
 8-L 1.0
7-8 SUMA 4.0 0.31
1 7  7 - 11 33.0
 7-8 4.0
1-7 SUMA 37.0 2.82
6 REG1  REGADERA 1.5
6 - REG1 SUMA 1.5 0.18
6 REG2  REGADERA 1.5
6 - REG2 SUMA 1.5 0.18

39
CÁLCULO DE TUBERÍAS DE DISTRIBUCIÓN CON SISTEMA DE CISTERNA MÁS TANQUE
HIDRONEUMÁTICO
SUMA DE GASTO
TRAMO DE TRAMO O PIEZA
FRIA CALIENTE GASTOS EN PROBABLE
TUBERIA SANITARIA
CADA TRAMO Q (l/s)
5 6  6 - REG1 1.5
 6 - REG2 1.5
5-6 SUMA 3.0 0.25
5 REG  REGADERA 1.5
5 - REG SUMA 1.5 0.18
C 5  5-6 3.0
 5 - REG 1.5
C-5 SUMA 4.5 1.30
4 C  C-5 4.5
4-C SUMA 4.5 1.30
4 REG  REGADERA 1.5
4 - REG SUMA 1.5 0.18
3 4  4-C 4.5
 4 - REG 1.5
3-4 SUMA 6.0 1.39
3 REG  REGADERA 1.5
3 - REG SUMA 1.5 0.18
2 3  3-4 6.0
 3 - REG 1.5
2-3 SUMA 7.5 1.56
2 REG  REGADERA 1.5
2 - REG SUMA 1.5 0.18
1 2  2-3 7.5
 2 - REG 1.5
1-2 SUMA 9.0 1.63
SIST BOM 1  1-7 37.0
 1-2 9.0
SIST BOM - 1 SUMA 46.0 3.09
SIST BOM AP  SIST BOM - 118 107.0
 SIST BOM - 87 55.0
 SIST BOM - 28 103.0
 SIST BOM - 1 46.0
SIST BOM - AP SUMA 311.0 7.06

40
2.13 CÁLCULO Y DISEÑO DE LA RED DE AGUA POTABLE

Las siguientes tablas de cálculo presentan el cálculo de la instalación hidráulica desde el cuarto
de máquinas ubicado en la planta baja hasta el sótano y planta alta respectivamente,
basándose en las consideraciones anteriores y en los alcances del proyecto antes descritos,
esto aunado a que se tendrá que llegar con la carga de presión suficiente para que el mueble
más desfavorable de cada instalación en particular tenga la carga de presión mínima necesaria
para su buen funcionamiento.

2.14 CALCULO DE LA CARGA DISPONIBLE EN CADA TRAMO

Teniendo calculados, gastos probables, la longitud de cada tramo y las pérdidas de fricción y
locales se procede a calcular la carga disponible de cada tramo. Para esto se toma como
referencia la presión mínima de arranque de la bomba y por lo tanto de operación del sistema.
Esta se obtiene como la suma de las alturas y pérdidas desde el nivel inferior de la
cisterna/cárcamo, hasta la altura a nivel de techo del edificio, agregando también a esta altura
las perdidas presentadas en la succión y descarga de la bomba y pérdidas desde el tanque
hidroneumático hasta el mueble más desfavorable por su ubicación. Utilizando esta presión
mínima de arranque de la bomba como punto inicial del análisis se calcula la carga disponible en
cada tramo, restando de la presión máxima en cada tramo las perdidas por longitud de la tubería,
por longitud equivalente de las conexiones y cota de piso. Para el mueble más desfavorable se
tiene una carga de 8.12 m.c.a., este cálculo se presenta en la tabla de determinación de la carga
total de bombeo.

Esta carga disponible nos mostrará si el sistema en el escenario desfavorable o conservador no


presenta presiones por debajo de las mínimas requeridas en los muebles más importantes, por
ejemplo, los inodoros con fluxómetro que requieren una presión mínima de 2.0 Kg/cm2 si tiene
un gasto máximo de 3.5 litros por descarga y de 1.0 Kg/cm2 si dicho gasto es de 4.8 litros por
descarga, por lo tanto, se cumple.

La presión máxima o de paro de la bomba se determina utilizando la mínima y sumándole un


diferencial entre arranque y paro de la bomba igual de 10 m.c.a., que resulta en 46.52 m.c.a.

41
Tabla 7. Cálculo hidráulico de la red de agua potable.
CÁLCULO DE RED DE AGUA POTABLE INTERNA
CÁLCULO Y DISEÑO DE LA RED DE AGUA POTABLE PARA LA UNIDAD MEDICA Visc. Cinemática: 1.02E-06 m²/seg.
OBRA:
FAMILIAR UNIMEF IV LOS OLIVOS EN ZAPOPAN, JALISCO. Tubería de: TUBOPLUS (PCC)
Rugosidad ε: 0.007 mm
UBICACIÓN: ZAPOPAN, JALISCO
Fórmula empleada: Darcy-Weisbach
Velocidades máxima y mínima
FECHA: MARZO DEL 2022
0.50 m/s 2.50 m/s

TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH


COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pérdidas Pérdidas COTA CARGA
f (adm .) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (m m ) (m m ) (m /s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m ) DISPONIBLE (m )
DE A (m )
SIST BOMBEO 41.30 4.30 37.00
SIST BOM - 1 57.50 3.09 75 54.40 1.3294 2,482,936 0.01322 1.259 16.55 1.491 2.750 38.55 0.00 38.55
1-2 0.25 1.63 50 36.20 1.5837 1,971,897 0.01424 0.013 5.85 0.748 0.761 37.79 0.00 37.79
2 - REG 2.10 0.18 20 14.40 1.1052 550,454 0.01760 0.160 9.05 0.564 0.723 37.07 1.90 35.17
2-3 1.00 1.56 50 36.20 1.5157 1,887,214 0.01426 0.046 5.00 0.586 0.632 37.16 0.00 37.16
3 - REG 2.10 0.18 20 14.40 1.1052 550,454 0.01760 0.160 9.05 0.564 0.723 36.43 1.90 34.53
3-4 1.00 1.39 50 36.20 1.3505 1,681,556 0.01432 0.037 5.00 0.465 0.502 36.66 0.00 36.66
4 - REG 2.10 0.18 20 14.40 1.1052 550,454 0.01760 0.160 9.05 0.564 0.723 35.93 1.90 34.03
4 - CAL 3.10 1.30 50 36.20 1.2631 1,572,678 0.01436 0.100 9.25 0.752 0.852 35.80 0.90 34.90
CAL - 5 3.30 1.30 50 36.20 1.2631 1,572,678 0.01436 0.106 18.25 1.484 1.591 34.21 0.00 34.21
5 - REG 2.10 0.18 20 14.40 1.1052 550,454 0.01760 0.160 2.65 0.165 0.325 33.89 1.90 31.99
5-6 1.00 0.25 32 23.20 0.5914 471,257 0.01645 0.013 4.45 0.079 0.092 34.12 0.00 34.12
6 - REG2 2.10 0.18 20 14.40 1.1052 550,454 0.01760 0.160 1.80 0.112 0.272 33.85 1.90 31.95
6 - REG1 3.10 0.18 20 14.40 1.1052 550,454 0.01760 0.236 3.80 0.237 0.473 33.65 1.90 31.75
1-7 4.05 2.82 75 54.40 1.2133 2,265,981 0.01327 0.074 5.25 0.394 0.468 38.08 0.00 38.08
7-8 0.45 0.31 32 23.20 0.7333 584,359 0.01621 0.009 5.85 0.160 0.169 37.91 0.00 37.91
8-L 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 37.85 0.60 37.25
8-9 0.90 0.25 32 23.20 0.5914 471,257 0.01645 0.011 5.00 0.089 0.101 37.81 0.00 37.81
9-L 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 37.75 0.60 37.15
9 - 10 0.90 0.18 25 18.00 0.7074 440,363 0.01716 0.022 4.15 0.106 0.128 37.68 0.00 37.68
10 - L2 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 37.62 0.60 37.02
10 - L1 1.60 0.10 20 14.40 0.6140 305,808 0.01822 0.039 4.40 0.085 0.123 37.56 0.60 36.96
7 - 11 0.20 2.70 75 54.40 1.1617 2,169,556 0.01329 0.003 5.00 0.344 0.347 37.73 0.00 37.73
11 - LL 0.95 0.10 25 18.00 0.3930 244,646 0.01796 0.007 6.10 0.048 0.055 37.68 0.60 37.08
11 - 12 3.00 2.67 75 54.40 1.1487 2,145,450 0.01330 0.049 3.60 0.242 0.292 37.44 0.00 37.44
12 - 13 0.20 2.13 63 45.80 1.2929 2,028,303 0.01369 0.005 3.60 0.307 0.312 37.13 0.00 37.13
13 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 37.11 0.60 36.51

42
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pé rdidas Pérdidas COTA CARGA
f (adm.) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (m m) (mm) (m/s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m) DISPONIBLE (m)
DE A (m )
13 - 14 0.30 1.98 63 45.80 1.2018 1,885,465 0.01373 0.007 3.60 0.265 0.272 36.86 0.00 36.86
14 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 36.84 0.60 36.24
14 - 15 0.75 1.82 50 36.20 1.7683 2,201,750 0.01418 0.047 4.15 0.662 0.708 36.15 0.00 36.15
15 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 36.13 0.60 35.53
15 - 16 0.30 1.63 50 36.20 1.5837 1,971,897 0.01424 0.015 3.60 0.460 0.475 35.68 0.00 35.68
16 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 35.66 0.60 35.06
16 - 17 0.75 1.39 50 36.20 1.3505 1,681,556 0.01432 0.028 3.60 0.335 0.362 35.31 0.00 35.31
17 - WC/F2 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 1.80 0.013 0.016 35.30 0.60 34.70
17 - WC/F1 1.10 0.25 40 29.00 0.3785 377,005 0.01626 0.005 2.90 0.021 0.026 35.29 0.60 34.69
12 - 18 3.10 1.93 63 45.80 1.1715 1,837,852 0.01375 0.065 4.15 0.290 0.355 37.09 0.00 37.09
18 - LL 0.95 0.10 25 18.00 0.3930 244,646 0.01796 0.007 5.80 0.046 0.053 37.03 0.60 36.43
18 - 19 0.20 1.88 63 45.80 1.1411 1,790,239 0.01376 0.004 3.60 0.239 0.243 36.84 0.00 36.84
19 - 20 0.45 0.31 25 18.00 1.2182 758,404 0.01667 0.032 4.45 0.337 0.368 36.48 0.00 36.48
20 - L 0.90 0.10 20 14.40 0.6140 305,808 0.01822 0.022 2.40 0.046 0.068 36.41 0.60 35.81
20 - 21 0.90 0.25 25 18.00 0.9824 611,616 0.01684 0.041 3.60 0.177 0.219 36.26 0.00 36.26
21 - L 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 36.19 0.60 35.59
21 - 22 0.90 0.18 25 18.00 0.7074 440,363 0.01716 0.022 3.60 0.092 0.114 36.14 0.00 36.14
22 - L2 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 36.08 0.60 35.48
22 - L1 1.60 0.10 20 14.40 0.6140 305,808 0.01822 0.039 4.40 0.085 0.123 36.02 0.60 35.42
19 - 23 4.30 1.63 50 36.20 1.5837 1,971,897 0.01424 0.216 7.55 0.965 1.182 35.66 0.00 35.66
23 - REG 2.10 0.18 20 14.40 1.1052 550,454 0.01760 0.160 9.05 0.564 0.723 34.94 1.90 33.04
23 - 24 1.00 1.56 50 36.20 1.5157 1,887,214 0.01426 0.046 5.00 0.586 0.632 35.03 0.00 35.03
24 - REG 2.10 0.18 20 14.40 1.1052 550,454 0.01760 0.160 9.05 0.564 0.723 34.31 1.90 32.41
24 - 25 1.00 1.39 50 36.20 1.3505 1,681,556 0.01432 0.037 5.00 0.465 0.502 34.53 0.00 34.53
25 - REG 2.10 0.18 20 14.40 1.1052 550,454 0.01760 0.160 9.05 0.564 0.723 33.81 1.90 31.91
25 - CAL 3.35 1.30 50 36.20 1.2631 1,572,678 0.01436 0.108 9.25 0.752 0.860 33.67 0.90 32.77
CAL - 26 3.10 1.30 50 36.20 1.2631 1,572,678 0.01436 0.100 18.25 1.484 1.584 32.08 0.00 32.08
26 - REG 2.10 0.18 20 14.40 1.1052 550,454 0.01760 0.160 2.65 0.165 0.325 31.76 1.90 29.86
26 - 27 1.00 0.25 25 18.00 0.9824 611,616 0.01684 0.046 5.00 0.246 0.292 31.79 0.00 31.79
27 - REG2 2.10 0.18 20 14.40 1.1052 550,454 0.01760 0.160 1.80 0.112 0.272 31.52 1.90 29.62
27 - REG1 3.10 0.18 20 14.40 1.1052 550,454 0.01760 0.236 3.80 0.237 0.473 31.32 1.90 29.42
SIST BOM - 28 6.10 4.24 90 65.40 1.2622 2,828,763 0.01278 0.097 4.05 0.329 0.426 40.87 3.30 37.57
28 - 29 3.05 3.84 90 65.40 1.1431 2,561,898 0.01284 0.040 3.60 0.240 0.280 40.59 3.30 37.29
29 - 30 1.43 0.31 40 29.00 0.4693 467,487 0.01597 0.009 4.45 0.050 0.059 40.54 3.30 37.24

43
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pé rdidas Pérdidas COTA CARGA
f (adm.) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (m m) (mm) (m/s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m) DISPONIBLE (m)
DE A (m )
30 - T2 0.70 0.18 25 18.00 0.7074 440,363 0.01716 0.017 4.60 0.117 0.134 40.40 3.90 36.50
30 - T1 2.10 0.18 25 18.00 0.7074 440,363 0.01716 0.051 7.45 0.190 0.241 40.29 3.90 36.39
29 - 31 10.25 3.68 90 65.40 1.0955 2,455,153 0.01286 0.123 4.10 0.251 0.374 40.22 3.30 36.92
31 - 32 1.25 0.31 40 29.00 0.4693 467,487 0.01597 0.008 4.45 0.050 0.058 40.16 3.30 36.86
32 - T2 0.70 0.18 25 18.00 0.7074 440,363 0.01716 0.017 2.40 0.061 0.078 40.08 3.90 36.18
32 - T1 2.10 0.18 25 18.00 0.7074 440,363 0.01716 0.051 5.25 0.134 0.185 39.98 3.90 36.08
31 - 33 23.20 3.68 90 65.40 1.0955 2,455,153 0.01286 0.279 9.10 0.557 0.836 39.38 3.30 36.08
33 - 34 5.10 2.08 50 36.20 2.0210 2,516,285 0.01412 0.414 6.40 1.333 1.747 37.64 3.30 34.34
34 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 37.62 3.90 33.72
34 - 35 0.20 1.93 50 36.20 1.8752 2,334,822 0.01416 0.014 3.60 0.645 0.659 36.98 3.30 33.68
35 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 36.96 3.90 33.06
35 - 36 0.85 1.76 50 36.20 1.7100 2,129,164 0.01420 0.050 3.60 0.537 0.586 36.39 3.30 33.09
36 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 36.37 3.90 32.47
36 - 37 0.25 1.56 50 36.20 1.5157 1,887,214 0.01426 0.012 3.60 0.422 0.433 35.96 3.30 32.66
37 - M 0.70 0.18 40 29.00 0.2725 271,444 0.01680 0.002 1.80 0.007 0.008 35.95 3.90 32.05
37 - 38 0.75 1.30 40 29.00 1.9681 1,960,429 0.01480 0.076 2.35 0.464 0.540 35.42 3.30 32.12
38 - M 1.80 0.18 40 29.00 0.2725 271,444 0.01680 0.004 4.35 0.016 0.020 35.40 4.80 30.60
38 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 35.40 3.90 31.50
33 - 39 1.50 3.34 90 65.40 0.9943 2,228,318 0.01292 0.015 3.60 0.181 0.196 39.19 3.30 35.89
39 - 40 0.65 0.25 32 23.20 0.5914 471,257 0.01645 0.008 4.70 0.084 0.092 39.10 3.30 35.80
40 - L 1.10 0.10 20 14.40 0.6140 305,808 0.01822 0.027 4.40 0.085 0.111 38.98 3.90 35.08
40 - 41 0.40 0.18 20 14.40 1.1052 550,454 0.01760 0.030 2.65 0.165 0.195 38.90 3.30 35.60
41 - L2 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 38.84 3.90 34.94
41 - L1 1.50 0.10 20 14.40 0.6140 305,808 0.01822 0.036 4.40 0.085 0.121 38.78 3.90 34.88
39 - 42 1.80 3.28 90 65.40 0.9764 2,188,288 0.01293 0.017 3.60 0.175 0.192 39.00 3.30 35.70
42 - 43 2.70 1.82 50 36.20 1.7683 2,201,750 0.01418 0.169 4.15 0.662 0.830 38.17 3.30 34.87
43 - WC-F 1.25 0.25 40 29.00 0.3785 377,005 0.01626 0.005 4.35 0.032 0.037 38.13 3.90 34.23
43 - 44 1.40 1.63 50 36.20 1.5837 1,971,897 0.01424 0.070 5.00 0.639 0.710 37.46 3.30 34.16
44 - L 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 3.25 0.062 0.079 37.38 3.90 33.48
44 - 45 0.90 1.56 50 36.20 1.5157 1,887,214 0.01426 0.042 5.00 0.586 0.627 36.83 3.30 33.53
45 - L 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 3.25 0.062 0.079 36.75 3.90 32.85
45 - 46 1.40 1.48 50 36.20 1.4380 1,790,434 0.01429 0.058 3.60 0.380 0.438 36.39 3.30 33.09
46 - WC-F 1.25 0.25 40 29.00 0.3785 377,005 0.01626 0.005 4.35 0.032 0.037 36.35 3.90 32.45
46 - 47 2.60 0.31 32 23.20 0.7333 584,359 0.01621 0.050 7.85 0.215 0.265 36.13 3.30 32.83

44
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pé rdidas Pérdidas COTA CARGA
f (adm.) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (m m) (mm) (m/s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m) DISPONIBLE (m)
DE A (m )
47 - L 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 36.06 3.90 32.16
47 - 48 0.80 0.25 32 23.20 0.5914 471,257 0.01645 0.010 5.00 0.089 0.099 36.03 3.30 32.73
48 - L 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 35.96 3.90 32.06
48 - 49 0.80 0.18 32 23.20 0.4258 339,305 0.01688 0.005 5.00 0.046 0.052 35.97 3.30 32.67
49 - L 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 35.91 3.90 32.01
49 - LL 2.20 0.10 25 18.00 0.3930 244,646 0.01796 0.017 8.95 0.070 0.088 35.89 3.90 31.99
42 - 50 5.40 2.97 63 45.80 1.8028 2,828,197 0.01352 0.264 4.45 0.737 1.001 37.99 3.30 34.69
50 - 51 0.70 1.63 40 29.00 2.4678 2,458,076 0.01470 0.110 1.80 0.559 0.669 37.33 3.30 34.03
51 - 52 0.15 0.25 40 29.00 0.3785 377,005 0.01626 0.001 1.80 0.013 0.014 37.31 3.30 34.01
52 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 1.80 0.013 0.016 37.30 3.90 33.40
52 - L 1.70 0.10 20 14.40 0.6140 305,808 0.01822 0.041 5.80 0.111 0.153 37.16 3.90 33.26
51 - 53 2.85 1.39 40 29.00 2.1044 2,096,150 0.01477 0.328 1.80 0.406 0.734 36.59 3.30 33.29
53 - 55 0.15 0.25 32 23.20 0.5914 471,257 0.01645 0.002 1.80 0.032 0.034 36.56 3.30 33.26
55 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 36.54 3.90 32.64
55 - L 1.50 0.10 20 14.40 0.6140 305,808 0.01822 0.036 5.80 0.111 0.148 36.41 3.90 32.51
53 - 54 0.90 0.25 25 18.00 0.9824 611,616 0.01684 0.041 2.65 0.130 0.172 36.42 3.30 33.12
54 - LL 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 36.36 3.90 32.46
54 - T 0.90 0.18 25 18.00 0.7074 440,363 0.01716 0.022 4.40 0.112 0.134 36.29 3.90 32.39
50 - 56 9.85 2.70 63 45.80 1.6389 2,571,088 0.01357 0.399 4.30 0.589 0.988 37.01 3.30 33.71
56 - 57 6.00 1.76 63 45.80 1.0683 1,675,969 0.01381 0.105 3.60 0.209 0.315 36.69 3.30 33.39
57 - L 3.40 0.10 20 14.40 0.6140 305,808 0.01822 0.083 7.80 0.150 0.233 36.46 3.90 32.56
57 - 58 2.55 1.70 50 36.20 1.6517 2,056,579 0.01422 0.139 2.35 0.327 0.466 36.23 3.30 32.93
58 - 59 0.40 0.25 25 18.00 0.9824 611,616 0.01684 0.018 3.20 0.157 0.176 36.05 3.30 32.75
59 - T 1.50 0.18 25 18.00 0.7074 440,363 0.01716 0.036 4.40 0.112 0.149 35.90 3.90 32.00
59 - LL 4.05 0.10 25 18.00 0.3930 244,646 0.01796 0.032 4.40 0.035 0.066 35.98 3.90 32.08
58 - 60 11.85 1.48 50 36.20 1.4380 1,790,434 0.01429 0.493 4.35 0.459 0.952 35.27 3.30 31.97
60 - LL 2.40 0.10 25 18.00 0.3930 244,646 0.01796 0.019 5.80 0.046 0.065 35.21 3.90 31.31
60 - 61 1.85 1.39 40 29.00 2.1044 2,096,150 0.01477 0.213 1.80 0.406 0.619 34.65 3.30 31.35
61 - 62 0.50 0.18 25 18.00 0.7074 440,363 0.01716 0.012 4.45 0.114 0.126 34.53 3.30 31.23
62 - L2 0.70 0.10 20 14.40 0.6140 305,808 0.01822 0.017 2.40 0.046 0.063 34.47 3.90 30.57
62 - L1 1.15 0.10 20 14.40 0.6140 305,808 0.01822 0.028 4.40 0.085 0.113 34.35 3.90 30.45
61 - 63 0.50 0.31 32 23.20 0.7333 584,359 0.01621 0.010 1.80 0.049 0.059 34.60 3.30 31.30
63 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 34.58 3.90 30.68
63 - LL 1.20 0.10 25 18.00 0.3930 244,646 0.01796 0.009 5.25 0.041 0.051 34.55 3.90 30.65

45
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pé rdidas Pérdidas COTA CARGA
f (adm.) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (m m) (mm) (m/s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m) DISPONIBLE (m)
DE A (m )
56 - 64 3.80 2.29 63 45.80 1.3900 2,180,664 0.01365 0.112 3.60 0.355 0.466 36.54 3.30 33.24
64 - 65 0.20 1.93 50 36.20 1.8752 2,334,822 0.01416 0.014 5.00 0.896 0.910 35.63 3.30 32.33
65 - T 2.05 0.18 25 18.00 0.7074 440,363 0.01716 0.050 4.95 0.126 0.176 35.45 3.90 31.55
65 - 66 0.45 1.82 50 36.20 1.7683 2,201,750 0.01418 0.028 5.00 0.797 0.825 34.80 3.30 31.50
66 - T 0.70 0.18 25 18.00 0.7074 440,363 0.01716 0.017 2.95 0.075 0.092 34.71 3.90 30.81
66 - 67 3.15 1.70 50 36.20 1.6517 2,056,579 0.01422 0.172 5.60 0.779 0.951 33.85 3.30 30.55
67 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 33.83 3.90 29.93
67 - 68 0.35 1.48 50 36.20 1.4380 1,790,434 0.01429 0.015 5.00 0.527 0.542 33.31 3.30 30.01
68 - T 0.70 0.18 25 18.00 0.7074 440,363 0.01716 0.017 2.95 0.075 0.092 33.22 3.90 29.32
68 - 69 0.40 1.30 50 36.20 1.2631 1,572,678 0.01436 0.013 3.60 0.293 0.306 33.01 3.30 29.71
69 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 1.80 0.013 0.016 32.99 3.90 29.09
69 - T 0.80 0.18 25 18.00 0.7074 440,363 0.01716 0.019 5.80 0.148 0.167 32.84 3.90 28.94
64 - 70 9.15 1.56 63 45.80 0.9469 1,485,518 0.01389 0.127 6.10 0.279 0.406 36.13 3.30 32.83
70 - T 0.70 0.18 25 18.00 0.7074 440,363 0.01716 0.017 3.25 0.083 0.100 36.03 3.90 32.13
70 - 71 0.85 1.39 63 45.80 0.8437 1,323,634 0.01398 0.009 1.80 0.065 0.075 36.06 3.30 32.76
71 - 72 1.25 0.25 32 23.20 0.5914 471,257 0.01645 0.016 2.65 0.047 0.063 36.00 3.30 32.70
72 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 35.98 3.90 32.08
72 - L 2.70 0.10 20 14.40 0.6140 305,808 0.01822 0.066 7.80 0.150 0.216 35.78 3.90 31.88
71 - 73 1.45 0.25 32 23.20 0.5914 471,257 0.01645 0.018 2.65 0.047 0.066 35.99 3.30 32.69
73 - WC-F 0.70 0.25 40 29.00 0.3785 377,005 0.01626 0.003 2.35 0.017 0.020 35.97 3.90 32.07
73 - L 2.60 0.10 20 14.40 0.6140 305,808 0.01822 0.063 7.80 0.150 0.213 35.78 3.90 31.88
28 - 74 3.30 2.25 75 54.40 0.9680 1,807,963 0.01341 0.039 5.55 0.265 0.304 40.57 3.30 37.27
74 - T 5.65 0.18 25 18.00 0.7074 440,363 0.01716 0.137 6.05 0.154 0.292 40.28 3.90 36.38
74 - 75 5.35 2.17 63 45.80 1.3172 2,066,393 0.01368 0.141 4.15 0.367 0.508 40.06 3.30 36.76
75 - T 3.80 0.18 25 18.00 0.7074 440,363 0.01716 0.092 7.50 0.191 0.284 39.78 3.90 35.88
75 - 76 4.95 2.08 63 45.80 1.2625 1,980,690 0.01370 0.120 3.60 0.293 0.413 39.65 3.30 36.35
76 - D 3.40 0.10 20 14.40 0.6140 305,808 0.01822 0.083 8.65 0.166 0.249 39.40 3.60 35.80
76 - 77 0.65 2.03 50 36.20 1.9724 2,455,798 0.01414 0.050 5.00 0.992 1.042 38.61 3.30 35.31
77 - T 0.70 0.18 25 18.00 0.7074 440,363 0.01716 0.017 2.95 0.075 0.092 38.51 3.90 34.61
77 - 78 1.40 1.93 50 36.20 1.8752 2,334,822 0.01416 0.098 5.00 0.896 0.995 37.61 3.30 34.31
78 - T 0.70 0.18 25 18.00 0.7074 440,363 0.01716 0.017 2.95 0.075 0.092 37.52 3.90 33.62
78 - 79 1.35 1.82 50 36.20 1.7683 2,201,750 0.01418 0.084 5.00 0.797 0.881 36.73 3.30 33.43
79 - 80 2.80 0.18 32 23.20 0.4258 339,305 0.01688 0.019 3.60 0.033 0.052 36.68 3.30 33.38
80 - LL2 0.70 0.10 25 18.00 0.3930 244,646 0.01796 0.005 2.40 0.019 0.024 36.65 3.90 32.75

46
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pérdidas Pérdidas COTA CARGA
f (adm .) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (mm ) (m m ) (m /s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m ) DISPONIBLE (m )
DE A (m )
80 - LL1 10.60 0.10 25 18.00 0.3930 176,145 0.01856 0.086 5.15 0.041 0.127 36.54 3.90 32.64
79 - 81 4.20 1.70 50 36.20 1.6517 1,488,963 0.01440 0.232 5.00 0.695 0.928 35.79 3.30 32.49
81 - T 0.70 0.18 25 18.00 0.7074 317,062 0.01757 0.017 2.95 0.075 0.093 35.70 3.90 31.80
81 - 81A 0.72 2.03 50 36.20 1.9724 1,777,997 0.01429 0.056 1.80 0.357 0.413 35.38 3.30 32.08
81A - 81B 2.20 1.56 50 36.20 1.5157 1,366,343 0.01445 0.103 3.60 0.422 0.525 34.86 3.30 31.56
81B - 81C 0.45 0.31 40 29.00 0.4693 338,928 0.01643 0.003 2.35 0.026 0.029 34.83 3.30 31.53
81C - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 34.81 3.90 30.91
81C - L 2.35 0.10 20 14.40 0.6140 220,182 0.01869 0.059 5.80 0.111 0.170 34.66 3.90 30.76
81B - 81D 2.55 0.31 40 29.00 0.4693 338,928 0.01643 0.016 3.80 0.043 0.059 34.80 3.30 31.50
81D - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 34.78 3.90 30.88
81D - L 2.35 0.10 20 14.40 0.6140 220,182 0.01869 0.059 5.80 0.111 0.170 34.63 3.90 30.73
81A - 82 0.68 1.56 50 36.20 1.5157 1,366,343 0.01445 0.032 5.00 0.586 0.617 34.76 3.30 31.46
82 - T 0.70 0.18 25 18.00 0.7074 317,062 0.01757 0.017 2.95 0.075 0.093 34.67 3.90 30.77
82 - 83 3.70 1.39 50 36.20 1.3505 1,217,447 0.01454 0.138 5.00 0.465 0.603 34.16 3.30 30.86
83 - T 4.40 0.18 25 18.00 0.7074 317,062 0.01757 0.110 5.20 0.133 0.242 33.92 3.90 30.02
83 - 84 2.30 0.31 25 18.00 1.2182 546,051 0.01695 0.164 3.20 0.242 0.406 33.75 3.30 30.45
84 - T 0.70 0.18 25 18.00 0.7074 317,062 0.01757 0.017 2.40 0.061 0.079 33.68 3.90 29.78
84 - 85 0.70 0.18 25 18.00 0.7074 317,062 0.01757 0.017 1.80 0.046 0.063 33.69 3.30 30.39
85 - LL 2.70 0.10 25 18.00 0.3930 176,145 0.01856 0.022 4.40 0.035 0.057 33.63 3.90 29.73
85 - 86 19.70 0.10 25 18.00 0.3930 176,145 0.01856 0.160 8.05 0.063 0.223 33.47 3.30 30.17
86 - L 3.20 0.10 20 14.40 0.6140 220,182 0.01869 0.080 6.40 0.123 0.203 33.27 3.90 29.37
86 - WC 0.30 0.10 20 14.40 0.6140 220,182 0.01869 0.007 2.40 0.046 0.054 33.41 3.50 29.91
SIST BOM - 87 1.50 3.30 75 54.40 1.4198 1,923,352 0.01337 0.038 1.80 0.185 0.223 41.08 3.30 37.78
87 - 88 1.95 1.30 40 29.00 1.9681 1,421,311 0.01496 0.199 7.00 1.382 1.581 39.50 3.30 36.20
88 - L 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 3.25 0.062 0.080 39.42 3.90 35.52
88 - 89 0.75 0.31 40 29.00 0.4693 338,928 0.01643 0.005 1.80 0.020 0.025 39.47 3.30 36.17
89 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 1.80 0.013 0.016 39.45 3.90 35.55
89 - LL 10.95 0.10 25 18.00 0.3930 176,145 0.01856 0.089 7.75 0.061 0.150 39.32 3.90 35.42
87 - 90 6.15 3.20 75 54.40 1.3768 1,865,068 0.01339 0.146 7.00 0.676 0.823 40.25 3.30 36.95
90 - T 3.00 0.18 25 18.00 0.7074 317,062 0.01757 0.075 5.80 0.148 0.223 40.03 3.90 36.13
90 - 91 4.20 3.15 75 54.40 1.3553 1,835,927 0.01340 0.097 5.25 0.492 0.588 39.67 3.30 36.37
91 - 92 5.10 0.31 32 23.20 0.7333 423,660 0.01658 0.100 3.15 0.086 0.186 39.48 3.30 36.18
92 - T2 2.70 0.18 25 18.00 0.7074 317,062 0.01757 0.067 4.95 0.126 0.193 39.29 3.90 35.39
92 - T1 4.35 0.18 25 18.00 0.7074 317,062 0.01757 0.108 5.20 0.133 0.241 39.24 3.90 35.34
91 - 93 6.10 3.03 75 54.40 1.3036 1,765,987 0.01342 0.130 5.50 0.477 0.607 39.06 3.30 35.76

47
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pérdidas Pérdidas COTA CARGA
f (adm .) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (mm ) (m m ) (m /s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m ) DISPONIBLE (m )
DE A (m )
93 - T 3.20 0.18 25 18.00 0.7074 317,062 0.01757 0.080 5.80 0.148 0.228 38.83 3.90 34.93
93 - 94 12.60 2.97 75 54.40 1.2778 1,731,017 0.01344 0.259 6.00 0.499 0.759 38.30 3.30 35.00
94 - 95 0.65 1.56 50 36.20 1.5157 1,366,343 0.01445 0.030 1.80 0.211 0.241 38.06 3.30 34.76
95 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 1.80 0.013 0.016 38.04 3.90 34.14
95 - 96 1.60 1.39 50 36.20 1.3505 1,217,447 0.01454 0.060 5.00 0.465 0.525 37.53 3.30 34.23
96 - L 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 3.25 0.062 0.080 37.45 3.90 33.55
96 - 97 0.70 1.30 40 29.00 1.9681 1,421,311 0.01496 0.071 4.35 0.859 0.930 36.60 3.30 33.30
97 - L 0.95 0.10 20 14.40 0.6140 220,182 0.01869 0.024 5.80 0.111 0.135 36.47 3.90 32.57
97 - 98 1.10 1.30 40 29.00 1.9681 1,421,311 0.01496 0.112 3.60 0.711 0.823 35.78 3.30 32.48
98 - T 3.55 0.18 25 18.00 0.7074 317,062 0.01757 0.088 4.40 0.112 0.201 35.58 3.90 31.68
98 - WC-F 2.20 0.25 40 29.00 0.3785 273,329 0.01679 0.009 2.35 0.017 0.026 35.75 3.90 31.85
94 - 99 8.55 2.73 75 54.40 1.1746 1,591,136 0.01350 0.149 4.35 0.306 0.455 37.85 3.30 34.55
99 - 100 2.85 1.70 63 45.80 1.0319 1,176,866 0.01407 0.048 3.60 0.195 0.243 37.60 3.30 34.30
100 - REG 4.20 0.18 20 14.40 1.1052 396,327 0.01791 0.325 3.40 0.212 0.537 37.07 5.20 31.87
100 - 101 2.30 1.56 50 36.20 1.5157 1,366,343 0.01445 0.108 2.35 0.275 0.383 37.22 3.30 33.92
101 - 102 1.55 0.31 32 23.20 0.7333 423,660 0.01658 0.030 6.45 0.177 0.207 37.01 3.30 33.71
102 - T2 0.70 0.18 25 18.00 0.7074 317,062 0.01757 0.017 2.40 0.061 0.079 36.93 3.90 33.03
102 - T1 1.00 0.18 25 18.00 0.7074 317,062 0.01757 0.025 4.40 0.112 0.137 36.88 3.90 32.98
101 - 103 1.20 0.31 32 23.20 0.7333 423,660 0.01658 0.024 7.85 0.215 0.239 36.98 3.30 33.68
103 - T 0.70 0.18 25 18.00 0.7074 317,062 0.01757 0.017 2.40 0.061 0.079 36.90 3.90 33.00
103 - 104 8.70 0.18 25 18.00 0.7074 317,062 0.01757 0.217 2.30 0.059 0.275 36.71 3.30 33.41
104 - LL2 17.40 0.10 25 18.00 0.3930 176,145 0.01856 0.141 5.65 0.044 0.186 36.52 3.90 32.62
104 - LL1 9.05 0.10 25 18.00 0.3930 176,145 0.01856 0.073 5.15 0.041 0.114 36.59 3.90 32.69
99 - 105 4.20 2.37 75 54.40 1.0197 1,381,316 0.01361 0.056 5.25 0.278 0.334 37.51 3.30 34.21
105 - T 1.05 0.18 25 18.00 0.7074 317,062 0.01757 0.026 5.80 0.148 0.174 37.34 3.90 33.44
105 - 106 5.15 2.29 75 54.40 0.9853 1,334,690 0.01364 0.064 5.25 0.260 0.324 37.19 3.30 33.89
106 - 107 2.25 0.25 32 23.20 0.5914 341,661 0.01687 0.029 2.35 0.042 0.071 37.12 3.30 33.82
107 - L 1.05 0.10 20 14.40 0.6140 220,182 0.01869 0.026 5.25 0.101 0.127 36.99 3.90 33.09
107 - WC-F 1.05 0.25 40 29.00 0.3785 273,329 0.01679 0.004 2.35 0.017 0.022 37.09 3.90 33.19
106 - 108 7.80 2.17 63 45.80 1.3172 1,502,235 0.01388 0.209 2.60 0.230 0.439 36.75 3.30 33.45
108 - T 1.20 0.18 25 18.00 0.7074 317,062 0.01757 0.030 6.10 0.156 0.185 36.56 3.90 32.66
108 - 109 2.95 2.08 63 45.80 1.2625 1,439,930 0.01391 0.073 3.60 0.293 0.365 36.38 3.30 33.08
109 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 1.80 0.013 0.016 36.37 3.90 32.47
109 - 110 0.45 1.93 50 36.20 1.8752 1,690,411 0.01432 0.032 2.35 0.421 0.453 35.93 3.30 32.63
110 - L 1.20 0.10 20 14.40 0.6140 220,182 0.01869 0.030 6.10 0.117 0.147 35.78 3.90 31.88
110 - 111 1.75 1.88 50 36.20 1.8266 1,646,618 0.01434 0.118 1.80 0.306 0.424 35.51 3.30 32.21
111 - L 1.30 0.10 20 14.40 0.6140 220,182 0.01869 0.032 6.10 0.117 0.150 35.36 3.90 31.46

48
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pérdidas Pérdidas COTA CARGA
f (adm .) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (mm ) (m m ) (m /s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m ) DISPONIBLE (m )
DE A (m )
111 - 112 0.70 1.82 50 36.20 1.7683 1,594,067 0.01436 0.044 3.60 0.574 0.618 34.89 3.30 31.59
112 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 1.80 0.013 0.016 34.87 3.90 30.97
112 - 113 4.25 1.63 50 36.20 1.5837 1,427,653 0.01443 0.217 9.25 1.183 1.399 33.49 3.30 30.19
113 - LL 0.70 0.10 25 18.00 0.3930 176,145 0.01856 0.006 2.95 0.023 0.029 33.46 3.90 29.56
113 - 114 0.10 1.56 50 36.20 1.5157 1,366,343 0.01445 0.005 3.60 0.422 0.426 33.06 3.30 29.76
114 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 33.04 3.90 29.14
114 - 115 0.70 1.30 50 36.20 1.2631 1,138,619 0.01459 0.023 3.60 0.293 0.316 32.75 3.30 29.45
115 - L 1.15 0.10 20 14.40 0.6140 220,182 0.01869 0.029 6.10 0.117 0.146 32.60 3.90 28.70
115 - 116 2.85 0.31 40 29.00 0.4693 338,928 0.01643 0.018 1.80 0.020 0.038 32.71 3.30 29.41
116 - L 1.00 0.10 20 14.40 0.6140 220,182 0.01869 0.025 5.80 0.111 0.136 32.57 3.90 28.67
116 - 117 0.70 0.31 40 29.00 0.4693 338,928 0.01643 0.004 1.80 0.020 0.025 32.68 3.30 29.38
117 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 32.66 3.90 28.76
117 - LL 11.45 0.10 25 18.00 0.3930 176,145 0.01856 0.093 9.75 0.077 0.170 32.51 3.90 28.61
SIST BOM - 168 14.25 4.44 90 65.40 1.3217 2,152,528 0.01295 0.251 11.85 1.055 1.307 39.99 7.00 32.99
168-LL 8.70 0.10 25 18.00 0.3930 176,145 0.01856 0.071 8.10 0.064 0.134 39.86 7.00 32.86
168-118 7.45 4.44 90 65.40 1.3217 2,152,528 0.01295 0.131 6.10 0.543 0.675 39.32 7.00 32.32
118 - T 3.55 0.18 25 18.00 0.7074 317,062 0.01757 0.088 6.35 0.162 0.250 39.07 7.60 31.47
118 - 119 7.30 4.41 90 65.40 1.3128 2,137,984 0.01295 0.127 4.10 0.360 0.487 38.83 7.00 31.83
119 - T 3.55 0.18 25 18.00 0.7074 317,062 0.01757 0.088 6.35 0.162 0.250 38.58 7.60 30.98
119 - 119A 0.10 4.38 90 65.40 1.3039 2,123,440 0.01295 0.002 3.60 0.312 0.314 38.52 7.00 31.52
119A - 119B 14.48 1.56 40 29.00 2.3618 1,705,573 0.01486 2.110 7.15 2.033 4.143 34.37 7.00 27.37
119B - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 34.35 7.60 26.75
119B - 119C 0.25 1.30 40 29.00 1.9681 1,421,311 0.01496 0.025 1.80 0.355 0.381 33.99 7.00 26.99
119C - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 33.97 7.60 26.37
119C - 119D 1.35 0.18 25 18.00 0.7074 317,062 0.01757 0.034 4.45 0.114 0.147 33.85 7.00 26.85
119D - L-1 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 6.00 0.115 0.133 33.71 7.60 26.11
119D - L-2 0.90 0.10 20 14.40 0.6140 220,182 0.01869 0.022 4.40 0.085 0.107 33.74 7.60 26.14
119A - 120 13.00 4.25 90 65.40 1.2652 2,060,416 0.01297 0.210 3.60 0.294 0.504 38.01 7.00 31.01
120 - L 0.90 0.10 20 14.40 0.6140 220,182 0.01869 0.022 6.65 0.128 0.150 38.37 7.60 30.77
120 - 121 3.10 4.23 90 65.40 1.2592 2,050,720 0.01298 0.050 5.60 0.453 0.502 38.02 7.00 31.02
121 - WC 0.90 0.10 20 14.40 0.6140 220,182 0.01869 0.022 7.50 0.144 0.167 37.85 7.20 30.65
121 - 122 5.50 4.22 90 65.40 1.2562 2,045,872 0.01298 0.088 3.85 0.310 0.398 37.62 7.00 30.62
122 - WC 0.90 0.10 20 14.40 0.6140 220,182 0.01869 0.022 7.50 0.144 0.167 37.45 7.20 30.25
122 - 123 1.00 4.20 75 54.40 1.8070 2,447,902 0.01323 0.040 5.55 0.924 0.964 36.65 7.00 29.65
123 - L 2.55 0.10 20 14.40 0.6140 220,182 0.01869 0.064 6.10 0.117 0.181 36.47 7.60 28.87
123 - 124 12.55 4.18 75 54.40 1.7984 2,436,245 0.01323 0.503 2.80 0.462 0.965 35.69 7.00 28.69
124 - 125 6.50 3.09 75 54.40 1.3294 1,800,957 0.01341 0.144 5.00 0.451 0.595 35.09 7.00 28.09

49
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pérdidas Pérdidas COTA CARGA
f (adm .) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (mm ) (m m ) (m /s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m ) DISPONIBLE (m )
DE A (m )
125 - 126 1.70 1.30 40 29.00 1.9681 1,421,311 0.01496 0.173 4.15 0.820 0.993 34.10 7.00 27.10
126 - L 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 3.25 0.062 0.080 34.02 7.60 26.42
126 - 127 0.85 0.31 25 18.00 1.2182 546,051 0.01695 0.061 4.45 0.337 0.397 33.70 7.00 26.70
127 - L 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 2.40 0.046 0.064 33.64 7.60 26.04
127 - 128 0.90 0.25 25 18.00 0.9824 440,363 0.01716 0.042 3.60 0.177 0.219 33.48 7.00 26.48
128 - L 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 2.40 0.046 0.064 33.42 7.60 25.82
128 - 129 0.85 0.18 25 18.00 0.7074 317,062 0.01757 0.021 3.60 0.092 0.113 33.37 7.00 26.37
129 - L2 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 2.40 0.046 0.064 33.31 7.60 25.71
129 - L1 1.60 0.10 20 14.40 0.6140 220,182 0.01869 0.040 4.40 0.085 0.124 33.25 7.60 25.65
125 - 130 3.35 2.94 75 54.40 1.2649 1,713,532 0.01345 0.068 3.60 0.294 0.361 34.73 7.00 27.73
130 - 131 2.70 2.29 63 45.80 1.3900 1,585,308 0.01384 0.080 3.60 0.355 0.435 34.30 7.00 27.30
131 - M 1.80 0.18 40 29.00 0.2725 196,797 0.01744 0.004 4.35 0.016 0.021 34.28 8.50 25.78
131 - 132 0.15 2.21 63 45.80 1.3414 1,529,926 0.01387 0.004 3.60 0.330 0.334 33.96 7.00 26.96
132 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 33.94 7.60 26.34
132 - 133 0.90 2.08 50 36.20 2.0210 1,821,790 0.01428 0.074 4.15 0.864 0.938 33.03 7.00 26.03
133 - M 1.80 0.18 40 29.00 0.2725 196,797 0.01744 0.004 4.35 0.016 0.021 33.00 8.50 24.50
133 - 134 0.15 1.98 50 36.20 1.9238 1,734,204 0.01431 0.011 3.60 0.679 0.690 32.33 7.00 25.33
134 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 32.31 7.60 24.71
134 - 135 0.80 1.82 50 36.20 1.7683 1,594,067 0.01436 0.051 3.60 0.574 0.625 31.71 7.00 24.71
135 - WC-F 0.90 0.25 40 29.00 0.3785 273,329 0.01679 0.004 2.35 0.017 0.021 31.69 7.60 24.09
135 - 136 0.25 1.63 40 29.00 2.4678 1,782,105 0.01484 0.040 2.35 0.730 0.769 30.94 7.00 23.94
136 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 1.80 0.013 0.016 30.92 7.60 23.32
136 - 137 0.75 1.39 40 29.00 2.1044 1,519,709 0.01492 0.087 1.80 0.406 0.494 30.45 7.00 23.45
137 - WC-F2 0.90 0.25 40 29.00 0.3785 273,329 0.01679 0.004 2.35 0.017 0.021 30.43 7.60 22.83
137 - WC-F1 0.95 0.25 40 29.00 0.3785 273,329 0.01679 0.004 4.35 0.032 0.036 30.41 7.60 22.81
130 - 138 2.35 2.17 63 45.80 1.3172 1,502,235 0.01388 0.063 4.15 0.367 0.430 34.30 7.00 27.30
138 - LL 1.40 0.10 25 18.00 0.3930 176,145 0.01856 0.011 5.25 0.041 0.053 34.25 7.60 26.65
138 - 139 1.20 2.13 63 45.80 1.2929 1,474,544 0.01389 0.031 1.80 0.153 0.184 34.12 7.00 27.12
139 - 140 1.75 1.30 40 29.00 1.9681 1,421,311 0.01496 0.178 4.45 0.879 1.057 33.06 7.00 26.06
140 - L 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 3.25 0.062 0.080 32.98 7.60 25.38
140 - 141 0.85 0.31 32 23.20 0.7333 423,660 0.01658 0.017 5.55 0.152 0.169 32.89 7.00 25.89
141 - L 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 2.40 0.046 0.064 32.83 7.60 25.23
141 - 142 0.90 0.25 32 23.20 0.5914 341,661 0.01687 0.012 5.00 0.089 0.101 32.79 7.00 25.79
142 - L 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 2.40 0.046 0.064 32.73 7.60 25.13
142 - 143 0.85 0.18 32 23.20 0.4258 245,996 0.01740 0.006 3.60 0.033 0.039 32.75 7.00 25.75
143 - L2 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 2.40 0.046 0.064 32.69 7.60 25.09
143 - L1 1.60 0.10 20 14.40 0.6140 220,182 0.01869 0.040 4.40 0.085 0.124 32.63 7.60 25.03

50
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pérdidas Pérdidas COTA CARGA
f (adm .) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (mm ) (m m ) (m /s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m ) DISPONIBLE (m )
DE A (m )
139 - 144 1.80 1.88 63 45.80 1.1411 1,301,476 0.01399 0.036 3.60 0.239 0.275 33.84 7.00 26.84
144 - LL 0.70 0.10 25 18.00 0.3930 176,145 0.01856 0.006 3.25 0.026 0.031 33.81 7.60 26.21
144 - 145 0.80 1.82 63 45.80 1.1047 1,259,939 0.01401 0.015 3.60 0.224 0.239 33.60 7.00 26.60
145 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 4.35 0.032 0.035 33.57 7.60 25.97
145 - 146 0.45 1.63 50 36.20 1.5837 1,427,653 0.01443 0.023 5.55 0.710 0.733 32.87 7.00 25.87
146 - T 3.05 0.18 25 18.00 0.7074 317,062 0.01757 0.076 6.95 0.177 0.253 32.62 7.60 25.02
146 - 169 3.15 1.48 50 36.20 1.4380 1,296,274 0.01449 0.133 1.80 0.190 0.323 32.55 7.00 25.55
169 - LL 7.75 0.10 25 18.00 0.3930 176,145 0.01856 0.063 12.05 0.095 0.158 32.39 7.60 24.79
169 - 147 0.30 1.48 50 36.20 1.4380 1,296,274 0.01449 0.013 3.60 0.380 0.392 32.16 7.00 25.16
147 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 32.14 7.60 24.54
147 - 148 0.30 0.31 40 29.00 0.4693 338,928 0.01643 0.002 2.35 0.026 0.028 32.13 7.00 25.13
148 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 32.11 7.60 24.51
148 - 149 0.50 0.10 32 23.20 0.2366 136,664 0.01865 0.001 4.15 0.012 0.013 32.11 7.00 25.11
149 - L2 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 2.40 0.046 0.064 32.05 7.60 24.45
149 - L1 1.00 0.10 20 14.40 0.6140 220,182 0.01869 0.025 4.40 0.085 0.110 32.01 7.60 24.41
124 - 150 1.95 3.27 75 54.40 1.4069 1,905,867 0.01337 0.048 5.00 0.505 0.553 35.14 7.00 28.14
150 - 151 1.45 1.56 50 36.20 1.5157 1,366,343 0.01445 0.068 3.60 0.422 0.489 34.65 7.00 27.65
151 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 34.63 7.60 27.03
151 - 152 0.30 1.30 40 29.00 1.9681 1,421,311 0.01496 0.031 2.35 0.464 0.495 34.15 7.00 27.15
152 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 34.13 7.60 26.53
152 - 153 0.80 0.18 25 18.00 0.7074 317,062 0.01757 0.020 4.45 0.114 0.133 34.02 7.00 27.02
153 - L2 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 2.40 0.046 0.064 33.95 7.60 26.35
153 - L1 0.80 0.10 20 14.40 0.6140 220,182 0.01869 0.020 4.40 0.085 0.105 33.91 7.60 26.31
150 - 154 2.30 3.06 75 54.40 1.3165 1,783,472 0.01342 0.050 5.00 0.442 0.492 34.64 7.00 27.64
154 - T 4.00 0.18 25 18.00 0.7074 317,062 0.01757 0.100 5.80 0.148 0.248 34.40 7.60 26.80
154 - 155 1.50 3.00 75 54.40 1.2907 1,748,502 0.01343 0.031 5.00 0.425 0.456 34.19 7.00 27.19
155 - T 2.40 0.18 25 18.00 0.7074 317,062 0.01757 0.060 5.80 0.148 0.208 33.98 7.60 26.38
155 - 156 5.85 2.94 75 54.40 1.2649 1,713,532 0.01345 0.118 3.85 0.314 0.432 33.76 7.00 26.76
156 - 157 3.75 1.63 63 45.80 0.9894 1,128,407 0.01411 0.058 3.60 0.180 0.237 33.52 7.00 26.52
157 - T 2.10 0.18 25 18.00 0.7074 317,062 0.01757 0.052 5.25 0.134 0.186 33.33 7.60 25.73
157 - 158 3.00 1.48 50 36.20 1.4380 1,296,274 0.01449 0.127 5.55 0.585 0.712 32.81 7.00 25.81
158 - T 0.70 0.18 25 18.00 0.7074 317,062 0.01757 0.017 2.40 0.061 0.079 32.73 7.60 25.13
158 - 159 0.30 1.30 40 29.00 1.9681 1,421,311 0.01496 0.031 2.35 0.464 0.495 32.31 7.00 25.31
159 - T 1.10 0.18 25 18.00 0.7074 317,062 0.01757 0.027 5.25 0.134 0.161 32.15 7.60 24.55
159 - 160 5.15 0.25 40 29.00 0.3785 273,329 0.01679 0.022 6.05 0.044 0.066 32.25 7.00 25.25
160 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 32.23 7.60 24.63
160 - L 2.50 0.10 20 14.40 0.6140 220,182 0.01869 0.062 5.25 0.101 0.163 32.08 7.60 24.48

51
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pérdidas Pérdidas COTA CARGA
f (adm .) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (mm ) (m m ) (m /s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m ) DISPONIBLE (m )
DE A (m )
156 - 161 2.20 2.67 63 45.80 1.6207 1,848,372 0.01374 0.088 4.15 0.556 0.644 33.11 7.00 26.11
161 - L 5.60 0.10 20 14.40 0.6140 220,182 0.01869 0.140 6.05 0.116 0.256 32.86 7.60 25.26
161 - 162 2.80 2.64 63 45.80 1.6024 1,827,604 0.01375 0.110 1.80 0.236 0.346 32.77 7.00 25.77
162 - 165 0.50 1.30 50 36.20 1.2631 1,138,619 0.01459 0.016 5.55 0.451 0.468 32.30 7.00 25.30
165 - L 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 3.25 0.062 0.080 32.22 7.60 24.62
165 - 166 1.55 1.30 50 36.20 1.2631 1,138,619 0.01459 0.051 3.60 0.293 0.344 31.95 7.00 24.95
166 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 2.35 0.017 0.020 31.93 7.60 24.33
166 - 167 1.65 0.18 20 14.40 1.1052 396,327 0.01791 0.128 5.50 0.343 0.470 31.48 7.00 24.48
167 - L2 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 4.20 0.081 0.098 31.39 7.60 23.79
167 - L1 1.15 0.10 20 14.40 0.6140 220,182 0.01869 0.029 4.40 0.085 0.113 31.37 7.60 23.77
162 - 163 0.95 2.45 63 45.80 1.4871 1,696,072 0.01380 0.032 3.60 0.406 0.438 32.33 7.00 25.33
163 - L 0.70 0.10 20 14.40 0.6140 220,182 0.01869 0.017 3.80 0.073 0.091 32.24 7.60 24.64
163 - 164 1.55 2.41 63 45.80 1.4628 1,668,381 0.01381 0.051 3.60 0.393 0.444 31.88 7.00 24.88
164 - WC-F 0.70 0.25 40 29.00 0.3785 273,329 0.01679 0.003 1.80 0.013 0.016 31.87 7.60 24.27
164 - EQ. OI 3.95 2.29 63 45.80 1.3900 1,585,308 0.01384 0.118 7.80 0.768 0.886 31.00 7.60 23.40
EQ. OI 39.00 7.00 32.00
EQ. OI - A 2.10 2.29 50 36.20 2.2250 2,770,333 0.01409 0.206 5.00 1.262 1.468 37.53 7.00 30.53
A-B 0.90 0.25 25 18.00 0.9824 611,616 0.01684 0.041 2.35 0.116 0.157 37.37 7.00 30.37
B - H3 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 0.95 0.007 0.010 37.36 7.00 30.36
B-C 2.00 0.18 25 18.00 0.7074 440,363 0.01716 0.049 1.80 0.046 0.095 37.28 7.00 30.28
C - H2 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 0.95 0.007 0.010 37.27 7.00 30.27
C - H1 2.30 0.10 25 18.00 0.3930 244,646 0.01796 0.018 2.95 0.023 0.041 37.24 7.00 30.24
A-D 5.45 0.31 25 18.00 1.2182 758,404 0.01667 0.382 5.00 0.378 0.760 36.77 7.00 29.77
D - H9 2.90 0.10 25 18.00 0.3930 244,646 0.01796 0.023 6.95 0.055 0.077 36.69 7.00 29.69
D- E 1.05 0.25 25 18.00 0.9824 611,616 0.01684 0.048 3.80 0.187 0.235 36.54 7.00 29.54
E - H8 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 0.95 0.007 0.010 36.53 7.00 29.53
E- F 2.00 0.18 25 18.00 0.7074 440,363 0.01716 0.049 1.80 0.046 0.095 36.44 7.00 29.44
F - H7 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 0.95 0.007 0.010 36.43 7.00 29.43
F - H6 2.30 0.10 25 18.00 0.3930 244,646 0.01796 0.018 2.95 0.023 0.041 36.40 7.00 29.40
A-G 1.15 1.98 50 36.20 1.9238 2,395,310 0.01415 0.085 5.00 0.943 1.028 36.50 7.00 29.50
G - H4 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 1.50 0.012 0.014 36.49 7.00 29.49
G- H 2.00 1.93 50 36.20 1.8752 2,334,822 0.01416 0.140 5.00 0.896 1.037 35.47 7.00 28.47
H - H5 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 1.50 0.012 0.014 35.45 7.00 28.45
H- I 4.25 1.88 50 36.20 1.8266 2,274,335 0.01417 0.283 1.80 0.306 0.589 34.88 7.00 27.88
I- J 0.75 0.25 25 18.00 0.9824 611,616 0.01684 0.035 3.20 0.157 0.192 34.69 7.00 27.69
J - H12 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 0.95 0.007 0.010 34.68 7.00 27.68
J- K 2.00 0.18 25 18.00 0.7074 440,363 0.01716 0.049 1.80 0.046 0.095 34.59 7.00 27.59

52
TABLA DE CALCULO HIDRAULICO, MÉTODO DARCY-WEISBACH
COTA DE
CRUCERO LONG. GASTO DIAM EXT DIAM INT VELOCIDAD NUMERO DE k (pérdidas Pérdidas COTA CARGA
f (adm .) hf (m ) ha (m ) NODO/MUEBLE
(m ) (l/s) (mm ) (m m ) (m /s) REYNOLDS locales) totales (m ) PIEZOMÉTRICA. (m ) DISPONIBLE (m )
DE A (m )
K - H11 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 0.95 0.007 0.010 34.58 7.00 27.58
K - H10 2.30 0.10 25 18.00 0.3930 244,646 0.01796 0.018 2.95 0.023 0.041 34.55 7.00 27.55
I- L 2.70 1.70 50 36.20 1.6517 2,056,579 0.01422 0.147 13.00 1.808 1.956 32.92 7.00 25.92
L - H13 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 1.50 0.012 0.014 32.91 7.00 25.91
L-M 2.00 1.63 50 36.20 1.5837 1,971,897 0.01424 0.101 5.00 0.639 0.740 32.18 7.00 25.18
M - H14 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 1.50 0.012 0.014 32.17 7.00 25.17
M- N 2.00 1.56 50 36.20 1.5157 1,887,214 0.01426 0.092 5.00 0.586 0.678 31.50 7.00 24.50
N - H15 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 1.50 0.012 0.014 31.49 7.00 24.49
N- Ñ 1.50 1.48 50 36.20 1.4380 1,790,434 0.01429 0.062 1.80 0.190 0.252 31.25 7.00 24.25
Ñ- O 1.95 0.25 25 18.00 0.9824 611,616 0.01684 0.090 9.20 0.453 0.542 30.71 7.00 23.71
O - H16 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 0.95 0.007 0.010 30.70 7.00 23.70
O- P 2.00 0.18 25 18.00 0.7074 440,363 0.01716 0.049 1.80 0.046 0.095 30.62 7.00 23.62
P - H17 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 0.95 0.007 0.010 30.61 7.00 23.61
P - H18 2.30 0.10 25 18.00 0.3930 244,646 0.01796 0.018 2.95 0.023 0.041 30.57 7.00 23.57
Ñ- Q 5.35 1.48 50 36.20 1.4380 1,790,434 0.01429 0.223 9.00 0.949 1.171 30.08 7.00 23.08
Q - H19 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 1.50 0.012 0.014 30.07 7.00 23.07
Q- R 2.05 0.25 32 23.20 0.5914 471,257 0.01645 0.026 6.45 0.115 0.141 29.94 7.00 22.94
R- S 0.40 0.18 25 18.00 0.7074 440,363 0.01716 0.010 1.80 0.046 0.056 29.88 7.00 22.88
S - H20 0.30 0.10 25 18.00 0.3930 244,646 0.01796 0.002 0.95 0.007 0.010 29.87 7.00 22.87
S - H21 2.70 0.10 25 18.00 0.3930 244,646 0.01796 0.021 6.95 0.055 0.076 29.81 7.00 22.81
R - H22 4.25 0.10 25 18.00 0.3930 244,646 0.01796 0.033 3.20 0.025 0.059 29.88 7.00 22.88

53
2.15 AGUA CALIENTE PARA REGADERAS

Para los dos vestidores cada uno con 3 regaderas se proyecta una línea de agua caliente de
diámetro variable y se propone instalar un calentador eléctrico Marca Rheem que funciona para
1 hasta 3 servicios para cada uno de los vestidores.

El calentador funciona con ajuste de temperatura termostático, tiene un módulo electrónico de


control y no utiliza piloto. Se puede instalar tanto en exteriores como interiores.

La tubería se proyecta de PP-R termofusionable marca tuboplus o similar por su buena


resistencia a la temperatura.

2.16 ESPECIFICACIONES DE MATERIALES

Tuberías agua fría: La tubería será de PP-R Termofusionable marcar Tuboplus o similar

Tuberías agua caliente: La tubería será de PP-R Termofusionable marcar Tuboplus o similar

Muebles: las coladeras a instalar será de marca Helvex o similar.

Conexiones: Las conexiones serán de PP-R marca Tuboplus o similar y se realizarán mediante
el proceso de termofusión.

Materiales de unión agua caliente: Termofusión

2.17 NORMATIVIDAD APLICABLE

 Criterios y lineamientos técnicos para factibilidades, SIAPA. CAP. 1 CRITERIOS


BÁSICOS DE DISEÑO. Febrero 2014.

 Criterios y lineamientos técnicos para factibilidades, SIAPA. CAP. 2 SISTEMAS DE


AGUA POTABLE. Febrero 2014.

 Normas de diseño de ingeniería en instalaciones hidráulicas, sanitarias y especiales


del IMSS 1997

 Normas técnicas complementarias para el diseño y la ejecución de obras e


instalaciones hidráulicas sección 2.

 Lineamientos Comisión Nacional del Agua (CONAGUA).

 Manual de productos Tuboplus. Ed. 2021PROYECTO DE DRENAJE SANITARIO.

54
2.18 INTRODUCCIÓN

El propósito del presente trabajo es, elaborar el diseño de la red de drenaje Sanitario, que tenga
la capacidad de cubrir las aportaciones presentes, por lo que se hace una revisión de las
características del proyecto.

Se realizará un informe amplio y detallado de todos los elementos utilizados para el desalojo de
las aguas negras, utilizando procedimientos de cálculo aprobados por los organismos
supervisores.

La red sanitaria será calculada con el método de Hunter con la diferencia que la unidad de diseño
se le denominará Unidad de Descarga (U.D.) esta equivale a la descarga del agua residual de
un lavado común en uso doméstico y que es igual a un caudal de 28 litros por minuto.

Para el cálculo se designan áreas donde se ubiquen los muebles a utilizar como lo son baños,
cocinas, cuartos de lavado, etc, como la mayoría de los muebles tiene un diámetro estándar de
descarga el proceso del cálculo solo se realizará en la red interna que une a todos los muebles
y se presentara la tabla de los tramos con las características hidráulicas que permitan el flujo del
gasto de diseño para cada tramo, en las consideraciones de la red sanitaria se tiene que la
velocidad mínima será de 0.5 m/s y la máxima de 5.0 m/s que es la velocidad permisible del PVC
sanitario de norma y con la velocidad mínima permite que los desechos no se queden atorados
en la red.

2.19 OBJETIVO

El propósito del presente trabajo es, elaborar el diseño de la red de drenaje Sanitario, que tenga
la capacidad de conducir las descargas sanitarias para descargarlas a la red sanitaria del
municipio.

2.20 FORMULA DE MANNING

Aunque la fórmula de Manning es empleada para cualquier tipo de geometría de canal, como lo
muestra la siguiente tabla, es normal emplearla para secciones circulares ya que dicha sección
es la más eficiente desde el punto de vista hidráulico y es por ello que se fabrican tuberías en
lugar de alguna otra geometría.

55
Figura 5. Elementos geométricos de secciones de canal.

La fórmula de Manning aplicada a tubos totalmente llenos es como sigue:

Donde:

V = Velocidad del flujo en (m/s)

n = Coeficiente de Manning (0.009 para PVC)

s = pendiente de la tuberia en (m/m)

Rh = Radio hidráulico en (m)

A = Área de la tuberia en (m2)

Pm = Perímetro mojado en (m)

Sin embargo, cuando el tubo es parcialmente lleno (en todos los casos cuando se habla de redes
sanitarias), la fórmula es un poco más compleja. Para el cálculo de los elementos geométricos
en tuberías que trabajan parcialmente llenas se emplearan las siguientes expresiones:

Radio hidráulico, perímetro mojado, diámetro de tubo totalmente lleno y parcialmente lleno.

56
Figura 6. Características geométricas para un tubo parcialmente lleno.

θ= 2 Cos -1(1-2d / D)

d= D/2 (1-Cos θ/2)

Pm = π D x θ/180

Rh = D/4 (1- 360/2 π θ x Sen θ)

A= D2/4 (π θ/360 - ½ Sen θ)

Donde:

d Tirante hidráulico en m.

D Diámetro interior del tubo en m

A Área transversal del flujo en m2

Pm perímetro mojado en m

Rh Radio Hidráulico en m

θ Angulo en grados

2.21 COEFICCIENTE DE FRICCIÓN DE MANNING

El coeficiente de rugosidad de Manning es un índice el cual determina la resistencia de un flujo


en un canal o conducción, la siguiente tabla presenta el rango de los coeficientes para diferentes

57
materiales, para este proyecto se diseñará con el coeficiente que presenta el proveedor de la
tubería que será de 0.009, el cual se ubica dentro del rango presentado en la tabla.

Figura 7. Coeficiente de rugosidad de Manning para diferentes materiales.

2.22 VELOCIDADES PERMISIBLES

2.22.1 Velocidad mínima.

La velocidad mínima se considera aquella con la cual no se permite depósito de sólidos en las
atarjeas que provoquen azolves y taponamientos. La velocidad mínima permisible para cualquier
tipo de material es de 0.6 m/s, considerando el gasto mínimo calculado. Adicionalmente, debe
asegurarse que el tirante calculado bajo estas condiciones tenga un valor mínimo de 1.0 cm en
casos de pendientes fuertes y de 1.5 cm en casos normales.

2.22.2 Velocidad máxima.

La velocidad máxima es el límite superior de diseño con el cual se trata de evitar la erosión de
las paredes de las tuberías y estructuras. La velocidad máxima permisible para los diferentes
tipos de material se muestra en la Tabla siguiente. Para su revisión se utiliza el gasto máximo
extraordinario calculado.

58
Figura 8. Velocidades máximas y mínimas permisibles en tuberías para alcantarillado sanitario.

2.23 PENDIENTES PERMITIDAS EN INTERIORES

Las tuberías horizontales con diámetros de 75 mm o menores se proyectarán con una pendiente
mínima del 2%.

Las tuberías horizontales con diámetro de 100 mm o mayor se proyectarán con una pendiente
mínima del 1.5%, pero se recomienda que se proyecten con una pendiente del 2% siempre que
sea posible.

Sin embargo, dichos datos ya se encuentran normalizados y para trazos en interiores se hará de
acuerdo con las TABLAS 10.2 y 10.3 que indican el máximo número de unidades mueble que
se permite conectar a un ramal, bajada o línea principal, esto se encuentra reglamentado en las
normas del instituto mexicano del seguro Social en su capítulo 10 “Eliminación de Aguas
Residuales” en su sección 10.6.4. Selección de Diámetros Sanitarios.

Figura 9. Ramales horizontales y bajadas.

59
Figura 10. Líneas principales horizontales.

El método general para el análisis de tuberías de alcantarillado sanitario está basado en la


ecuación de Manning y lo correcto es que una vez definido el trazo, el diseño hidráulico se realiza
tramo por tramo, iniciando en los muebles sanitarios y/o las cabezas de atarjea y finalizado en
los entronques de tuberías. Con las expresiones anteriores se calculan los gastos de diseño para
cada tramo, tomando en consideración, la aportación del gasto de cada salida que corresponda.

2.24 PENDIENTES PERMITIDAS EN EXTERIORES

Las pendientes de las tuberías deben ser tan semejantes como sea posible a las del terreno con
objeto de tener excavaciones mínimas, pero siempre teniendo en cuenta lo siguiente:

2.24.1 PENDIENTE MÍNIMA

Para aguas claras será la que produzca una velocidad de 0.3 m/s a tubo lleno y para aguas
negras la que produzca una velocidad de 0.6 m/s a tubo lleno.

2.24.2 PENDIENTE MÁXIMA

Será aquella que produzca una velocidad de 3.0 m/s con el gasto máximo probable.

2.25 REGISTROS Y ESTRUCTURAS

Cada salida de aguas claras o negras del edificio deberá desfogar en un registro cuyas
dimensiones mínimas serán las siguientes:

* Para profundidades hasta de un metro: 40 x 60 cm

* Para profundidades de 1.01 a 1.50 m: 50 x 70 cm

60
* Para profundidades de 1.51 a 1.80 m: 60 x 80 cm

En todos los casos las dimensiones mínimas de la tapa serán de 40 x 60 cm. Esto viene
fundamentado, en la norma del IMSS en su capítulo 10 “Eliminación de Aguas Residuales” en
su parte 10.8.11.a. Registros.

2.25.1 Separación entre registros

La separación máxima de los registros estará de acuerdo con el diámetro del tubo según se
indica:

Figura 11. Separación entre registros con respecto al diámetro.

Esto viene fundamentado, en la norma del IMSS en su capítulo 10 “Eliminación de Aguas


Residuales” en su parte 10.8.11.b. Registros.

2.25.2 Profundidad máxima de registros

La profundidad máxima de los registros será de 1.80 metros. A partir de la profundidad de 1.80
m y todavía se tengan registros por conectar, se proyectará una red paralela y secundaria para
evitar registros con mayor profundidad.

Esto viene fundamentado, en la norma del IMSS en su capítulo 10 “Eliminación de Aguas


Residuales” en su parte 10.8.11.c. Registros.

2.26 GASTO DE DISEÑO

Para el dimensionamiento de las tuberías y asignación de gastos en cada una de ellas se emplea
el gasto máximo instantáneo que está basado en el método probabilístico del Dr. Roy Hunter; en
el cual el gasto se obtiene a partir de la suma de las unidades-mueble (UM) de los equipos y/o
aparatos que requieren agua.

Sin embargo, la valorización en unidades-mueble de los diferentes muebles sanitarios varia en


cambio con la valorización de las unidades-mueble de distribución de agua potable y esta se

61
hará con base en la TABLA 10.1. De las normas del Instituto Mexicano del Seguro Social, en su
capítulo 10 “Eliminación de Aguas Residuales” en su sección 10.6.3. Unidades Mueble
Sanitarias.

Una vez determinado el número de unidades mueble, se procede a realizar el cálculo de los
tramos de la red sanitaria recurre a la tabla 5.4 en las que se muestra el gasto en función de las
unidades mueble.

Esto se encuentra reglamentado en las Normas de diseño de Ingeniería del Instituto Mexicano
del seguro Social en su capítulo 5. Distribución de agua fría, en su apartado 5.13. Cálculo de los
gastos en una red de distribución de agua a muebles sanitarios.

62
Figura 12. Unidades mueble para sanitario.

63
2.27 DETERMINACION DEL GASTO DE DESCARGA

Es imperativo conocer el número de muebles sanitarios a servir, para aplicar el método antes
descrito, por lo que se hace el conteo de los muebles sanitarios, asignándoles un valor mueble
de acuerdo a la tabla 10.1. Por lo que para esta unidad médica se tendrá el mínimo de muebles
operando, de acuerdo a la siguiente tabla obteniendo el siguiente resultado.

Para determinar el gasto total de descarga se supondrá que solo se dotara en caudal a las
unidades mueble indicadas en la tabla debajo y se suponen los WC y mingitorios son con
fluxómetro en todos los servicios con algunas excepciones, obteniendo el caudal siguiente.
Tabla 8. Cálculo del gasto de descarga por mueble.
PLANTA BAJA
Gasto DIAM. MÍNIMO DIAM. DISEÑO
MUEBLE U.D.
(l/s) mm(pulg.) mm(pulg.)
71 TARJA 2 0.18 38 1.50 50 2.00
72 TARJA 2 0.18 38 1.50 50 2.00
73 TARJA 2 0.18 38 1.50 50 2.00
74 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
75 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
76 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
77 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
78 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
79 TARJA 2 0.18 38 1.50 50 2.00
80 TARJA 2 0.18 38 1.50 50 2.00
81 TARJA 2 0.18 38 1.50 50 2.00
82 TARJA 2 0.18 38 1.50 50 2.00
83 TARJA 2 0.18 38 1.50 50 2.00
84 TARJA 2 0.18 38 1.50 50 2.00
85 TARJA 2 0.18 38 1.50 50 2.00
86 TARJA 2 0.18 38 1.50 50 2.00
87 TARJA 2 0.18 38 1.50 50 2.00
88 LAVABO 2 0.18 32 1.25 50 2.00
89 W.C. FLUX. 5 1.30 75 3.00 100 4.00
90 TARJA 2 0.18 38 1.50 50 2.00
91 TARJA 2 0.18 38 1.50 50 2.00
92 TARJA 2 0.18 38 1.50 50 2.00
93 TARJA 2 0.18 38 1.50 50 2.00
94 W.C. FLUX. 5 1.30 75 3.00 100 4.00
95 LAVABO 2 0.18 32 1.25 50 2.00
96 LAVABO 2 0.18 32 1.25 50 2.00

64
PLANTA BAJA
Gasto DIAM. MÍNIMO DIAM. DISEÑO
MUEBLE U.D.
(l/s) mm(pulg.) mm(pulg.)
97 W.C. FLUX. 5 1.30 75 3.00 100 4.00
98 TARJA 2 0.18 38 1.50 50 2.00
99 TARJA 2 0.18 38 1.50 50 2.00
100 TARJA 2 0.18 38 1.50 50 2.00
101 REGADERA 3 0.25 50 2.00 50 2.00
102 TARJA 2 0.18 38 1.50 50 2.00
103 LAVABO 2 0.18 32 1.25 50 2.00
104 LAVABO 2 0.18 32 1.25 50 2.00
105 LAVABO 2 0.18 32 1.25 50 2.00
106 TARJA 2 0.18 38 1.50 50 2.00
107 LAVABO 2 0.18 32 1.25 50 2.00
108 W.C. FLUX. 5 1.30 75 3.00 100 4.00
109 TARJA 2 0.18 38 1.50 50 2.00
110 W.C. FLUX. 5 1.30 75 3.00 100 4.00
111 LAVABO 2 0.18 32 1.25 50 2.00
112 LAVABO 2 0.18 32 1.25 50 2.00
113 W.C. FLUX. 5 1.30 75 3.00 100 4.00
114 W.C. FLUX. 5 1.30 75 3.00 100 4.00
115 LAVABO 2 0.18 32 1.25 50 2.00
116 W.C. FLUX. 5 1.30 75 3.00 100 4.00
117 LAVABO 2 0.18 32 1.25 50 2.00
118 URINARIO SUSPENDIDO 2 0.18 32 1.25 50 2.00
119 LAVABO 2 0.18 32 1.25 50 2.00
120 W.C. FLUX. 5 1.30 75 3.00 100 4.00
121 W.C. FLUX. 5 1.30 75 3.00 100 4.00
122 W.C. FLUX. 5 1.30 75 3.00 100 4.00
123 LAVABO 2 0.18 32 1.25 50 2.00
124 W.C. FLUX. 5 1.30 75 3.00 100 4.00
125 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
126 TARJA 2 0.18 38 1.50 50 2.00
127 TARJA 2 0.18 38 1.50 50 2.00
128 W.C. FLUX. 5 1.30 75 3.00 100 4.00
129 LAVABO 2 0.18 32 1.25 50 2.00
130 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
131 LAVABO 2 0.18 32 1.25 50 2.00
132 W.C. FLUX. 5 1.30 75 3.00 100 4.00
133 LAVABO 2 0.18 32 1.25 50 2.00
134 W.C. FLUX. 5 1.30 75 3.00 100 4.00
135 LAVABO 2 0.18 32 1.25 50 2.00
136 W.C. FLUX. 5 1.30 75 3.00 100 4.00
137 LAVABO 2 0.18 32 1.25 50 2.00

65
PLANTA BAJA
Gasto DIAM. MÍNIMO DIAM. DISEÑO
MUEBLE U.D.
(l/s) mm(pulg.) mm(pulg.)
138 LAVABO 2 0.18 32 1.25 50 2.00
139 W.C. FLUX. 5 1.30 75 3.00 100 4.00
140 TARJA DOBLE 4 0.31 50 2.00 50 2.00
141 W.C. FLUX. 5 1.30 75 3.00 100 4.00
142 TARJA 2 0.18 38 1.50 50 2.00
143 TARJA 2 0.18 38 1.50 50 2.00
144 W.C. FLUX. 5 1.30 75 3.00 100 4.00
145 LAVABO 2 0.18 32 1.25 50 2.00
146 W.C. FLUX. 5 1.30 75 3.00 100 4.00
147 LAVABO 2 0.18 32 1.25 50 2.00
148 LAVABO 2 0.18 32 1.25 50 2.00
149 W.C. FLUX. 5 1.30 75 3.00 100 4.00
150 LAVABO 2 0.18 32 1.25 50 2.00
151 W.C. FLUX. 5 1.30 75 3.00 100 4.00
152 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
153 TARJA 2 0.18 38 1.50 50 2.00
AC-20 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-21 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-22 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-23 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-24 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-25 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-26 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-27 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-28 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-29 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-30 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-31 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-32 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-33 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-34 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-35 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-36 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-37 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-38 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-39 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-40 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-41 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-42 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-43 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-44 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50

66
PLANTA BAJA
Gasto DIAM. MÍNIMO DIAM. DISEÑO
MUEBLE U.D.
(l/s) mm(pulg.) mm(pulg.)
AC-45 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-46 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-47 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
184 W.C. FLUX. 5 1.30 75 3.00 100 4.00
185 W.C. FLUX. 5 1.30 75 3.00 100 4.00
186 LAVABO 2 0.18 32 1.25 50 2.00
187 LAVABO 2 0.18 32 1.25 50 2.00
249.04 42.76 75 3.00 100 4.00
PLANTA ALTA
Gasto DIAM. MÍNIMO DIAM. DISEÑO
MUEBLE U.D.
(l/s) mm(pulg.) mm(pulg.)
1 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
2 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
3 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
4 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
5 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
6 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
7 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
8 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
9 TARJA 2 0.18 38 1.50 50 2.00
10 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
11 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
12 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
13 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
14 TARJA 2 0.18 38 1.50 50 2.00
15 LAVABO 2 0.18 32 1.25 50 2.00
16 W.C. 5 1.30 75 3.00 100 4.00
17 W.C. 5 1.30 75 3.00 100 4.00
18 LAVABO 2 0.18 32 1.25 50 2.00
19 TARJA 2 0.18 38 1.50 50 2.00
20 TARJA 2 0.18 38 1.50 50 2.00
21 LAVABO 2 0.18 32 1.25 50 2.00
22 W.C. FLUX. 5 1.30 75 3.00 100 4.00
23 TARJA 2 0.18 38 1.50 50 2.00
24 TARJA 2 0.18 38 1.50 50 2.00
25 TARJA 2 0.18 38 1.50 50 2.00
26 W.C. FLUX. 5 1.30 75 3.00 100 4.00
27 LAVABO 2 0.18 32 1.25 50 2.00
28 LAVABO 2 0.18 32 1.25 50 2.00
29 W.C. FLUX. 5 1.30 75 3.00 100 4.00
30 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
31 LAVADERO (ROPA) 3 0.25 75 3.00 75 3.00
32 W.C. FLUX. 5 1.30 75 3.00 100 4.00
33 W.C. FLUX. 5 1.30 75 3.00 100 4.00
34 LAVABO 2 0.18 32 1.25 50 2.00
35 W.C. FLUX. 5 1.30 75 3.00 100 4.00
36 LAVABO 2 0.18 32 1.25 50 2.00

67
PLANTA ALTA
Gasto DIAM. MÍNIMO DIAM. DISEÑO
MUEBLE U.D.
(l/s) mm(pulg.) mm(pulg.)
37 TARJA 2 0.18 38 1.50 50 2.00
38 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
39 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
40 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
41 SALIDA 2 0.18 32 1.25 50 2.00
42 SALIDA 2 0.18 32 1.25 50 2.00
43 SALIDA 2 0.18 32 1.25 50 2.00
44 SALIDA 2 0.18 32 1.25 50 2.00
45 SALIDA 2 0.18 32 1.25 50 2.00
46 SALIDA 2 0.18 32 1.25 50 2.00
47 TARJA DOBLE 4 0.31 50 2.00 50 2.00
48 LAVABO 2 0.18 32 1.25 50 2.00
49 LAVABO 2 0.18 32 1.25 50 2.00
50 W.C. FLUX. 5 1.30 75 3.00 100 4.00
51 LAVABO 2 0.18 32 1.25 50 2.00
52 W.C. FLUX. 5 1.30 75 3.00 100 4.00
53 LAVABO 2 0.18 32 1.25 50 2.00
54 LAVABO 2 0.18 32 1.25 50 2.00
55 W.C. FLUX. 5 1.30 75 3.00 100 4.00
56 LAVABO 2 0.18 32 1.25 50 2.00
57 W.C. FLUX. 5 1.30 75 3.00 100 4.00
58 LAVABO 2 0.18 32 1.25 50 2.00
59 W.C. FLUX. 5 1.30 75 3.00 100 4.00
60 LAVABO 2 0.18 32 1.25 50 2.00
61 W.C. FLUX. 5 1.30 75 3.00 100 4.00
62 LAVABO 2 0.18 32 1.25 50 2.00
63 LAVABO 2 0.18 32 1.25 50 2.00
64 URINARIO SUSPENDIDO 2 0.18 32 1.25 50 2.00
65 LAVABO 2 0.18 32 1.25 50 2.00
66 URINARIO SUSPENDIDO 2 0.18 32 1.25 50 2.00
67 LAVABO 2 0.18 32 1.25 50 2.00
68 W.C. FLUX. 5 1.30 75 3.00 100 4.00
69 LAVABO 2 0.18 32 1.25 50 2.00
70 W.C. FLUX. 5 1.30 75 3.00 100 4.00
176 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
177 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
178 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
179 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
AC-1 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-2 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-3 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-4 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50

68
PLANTA ALTA
Gasto DIAM. MÍNIMO DIAM. DISEÑO
MUEBLE U.D.
(l/s) mm(pulg.) mm(pulg.)
AC-5 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-6 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-7 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-8 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-9 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-10 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-11 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-12 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-13 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-14 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-15 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-16 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-17 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-18 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
AC-19 AIRE ACONDICIONADO 1.4E-03 0.001 13 0.50 13 0.50
183 30.00 75 3.00 100 4.00
SÓTANO
Gasto DIAM. MÍNIMO DIAM. DISEÑO
MUEBLE U.D.
(l/s) mm(pulg.) mm(pulg.)
154 REGADERA 3 0.25 50 2.00 50 2.00
155 REGADERA 3 0.25 50 2.00 50 2.00
156 REGADERA 3 0.25 50 2.00 50 2.00
157 LAVABO 2 0.18 32 1.25 50 2.00
158 W.C. FLUX. 5 1.30 75 3.00 100 4.00
159 LAVABO 2 0.18 32 1.25 50 2.00
160 LAVABO 2 0.18 32 1.25 50 2.00
161 W.C. FLUX. 5 1.30 75 3.00 100 4.00
162 LAVABO 2 0.18 32 1.25 50 2.00
163 W.C. FLUX. 5 1.30 75 3.00 100 4.00
164 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
165 LAVABO 2 0.18 32 1.25 50 2.00
166 W.C. FLUX. 5 1.30 75 3.00 100 4.00
167 LAVABO 2 0.18 32 1.25 50 2.00
168 LAVABO 2 0.18 32 1.25 50 2.00
169 W.C. FLUX. 5 1.30 75 3.00 100 4.00
170 LAVABO 2 0.18 32 1.25 50 2.00
171 W.C. FLUX. 5 1.30 75 3.00 100 4.00
172 COLADERA DE PISO 2 0.18 38 1.50 50 2.00
173 REGADERA 3 0.25 50 2.00 50 2.00
174 REGADERA 3 0.25 50 2.00 50 2.00
175 REGADERA 3 0.25 50 2.00 50 2.00

69
HEMODIÁLISIS
Gasto DIAM. MÍNIMO DIAM. DISEÑO
MUEBLE U.D.
(l/s) mm(pulg.) mm(pulg.)
H1 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H2 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H3 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H4 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H5 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H6 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H7 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H8 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H9 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H10 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H11 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H12 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H13 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H14 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H15 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H16 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H17 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H18 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H19 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H20 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H21 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50
H22 HEMODIÁLISIS 0.06 0.03 38 1.50 38 1.50

2.28 CÁLCULO Y DIMENCIONAMIENTO DE LA RED SANITARIA.

Una vez calculado los gastos para cada tramo se procede a seleccionar diámetro y pendiente
para la revisión del funcionamiento hidráulico, tomando en consideración que se debe de
aprovechar al máximo la capacidad hidráulica del tubo trabajando a superficie libre como ya se
indicó.

Para poder dimensionar la red de alcantarillado sanitario que permita desalojar las aguas
residuales producidas, será necesario efectuar el cálculo de los gastos para cada tramo

Se tomo en consideración que los tramos iniciales que conectan con muebles se iniciaran con
los diámetros iguales a los de la descarga del mueble y no podrá ser reducido a un diámetro
menor, para los muebles como mingitorios, fregaderos y lavabos la descarga estándar será de
2”, para las unidades de hemodiálisis será de 1.5” de diámetro y para los baños será de 4”.

70
Tabla 9. Cálculo de gastos y velocidades de la red principal del edificio.
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA ALTA
RAMAL 1
1 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
2 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 1 0.36 50 20 P 1.66 0.85 OK
RAMAL 2,3
RAMAL 1 0.36 50 20 P 1.66 0.85 OK
3 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
4 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 2,3 0.72 50 20 P 1.66 0.85 OK
RAMAL 4
5 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
6 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 4 0.36 50 20 P 1.66 0.85 OK
RAMAL 5,6
RAMAL 4 0.36 50 20 P 1.66 0.85 OK
7 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
8 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 5,6 0.72 50 20 P 1.66 0.85 OK
RAMAL 7
RAMAL 2,3 0.72 50 20 P 1.66 0.85 OK
RAMAL 5,6 0.72 50 20 P 1.66 0.85 OK
RAMAL 7 1.44 50 20 P 1.66 0.85 OK
RAMAL 8
RAMAL 7 1.44 50 20 P 1.66 0.85 OK
9 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 8 1.62 50 20 P 1.66 0.85 OK
RAMAL 9
10 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
11 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 9 0.36 50 20 P 1.66 0.85 OK
RAMAL 174
180 LAVABO 0.18 50 20 P 1.66 0.85 OK
181 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 174 0.36 50 20 P 1.66 0.85 OK
RAMAL 175
RAMAL 9 0.36 50 20 P 1.66 0.85 OK
RAMAL 174 0.36 50 20 P 1.66 0.85 OK
RAMAL 175 0.72 50 20 P 1.66 0.85 OK
RAMAL 176
182 W.C. FLUX. 1.30 100 20 P 10.55 1.34 OK
183 W.C. FLUX. 1.30 100 20 P 10.55 1.34 OK
RAMAL 176 2.60 100 20 P 10.55 1.34 OK
RAMAL 177
RAMAL 175 0.72 50 20 P 1.66 0.85 OK
RAMAL 176 2.60 100 20 P 10.55 1.34 OK
RAMAL 177 3.32 100 20 P 10.55 1.34 OK

71
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA ALTA
RAMAL 1-AC
AC-1 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
AC-2 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
RAMAL 1-AC 0.001 13 61 P 0.08 0.60 OK
RAMAL 2,3-AC
RAMAL 1-AC 0.001 13 61 P 0.08 0.60 OK
AC-3 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
AC-4 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
RAMAL 2,3-AC 0.003 13 61 P 0.08 0.60 OK
RAMAL 10,11
RAMAL 177 3.32 100 20 P 10.55 1.34 OK
12 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
13 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 2,3-AC 0.003 13 61 P 0.08 0.60 OK
RAMAL 10,11 3.68 100 20 P 10.55 1.34 OK
RAMAL 12
RAMAL 8 1.62 50 20 P 1.66 0.85 OK
RAMAL 10,11 3.68 100 20 P 10.55 1.34 OK
RAMAL 12 5.30 100 20 P 10.55 1.34 OK
RAMAL 13,14,15,16,17
RAMAL 12 5.30 100 20 P 10.55 1.34 OK
14 TARJA 0.18 50 20 P 1.66 0.85 OK
15 LAVABO 0.18 50 20 P 1.66 0.85 OK
16 W.C. 1.30 100 15 P 9.14 1.16 OK
17 W.C. 1.30 100 15 P 9.14 1.16 OK
18 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 13,14,15,16,17 8.44 100 15 P 9.14 1.16 OK
RAMAL 18
19 TARJA 0.18 50 20 P 1.66 0.85 OK
20 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 18 0.36 50 30 P 2.04 1.04 OK
RAMAL 19
21 LAVABO 0.18 50 20 P 1.66 0.85 OK
22 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 19 1.48 100 15 P 9.14 1.16 OK
RAMAL 20
RAMAL 18 0.36 50 30 P 2.04 1.04 OK
RAMAL 19 1.48 100 15 P 9.14 1.16 OK
AC-5 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
RAMAL 20 1.84 100 15 P 9.14 1.16 OK
RAMAL 21
RAMAL 20 1.84 100 15 P 9.14 1.16 OK
23 TARJA 0.18 50 20 P 1.66 0.85 OK
AC-6 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
RAMAL 21 2.02 100 15 P 9.14 1.16 OK
RAMAL 22
RAMAL 21 2.02 100 15 P 9.14 1.16 OK
24 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 22 2.20 100 15 P 9.14 1.16 OK
RAMAL 23
RAMAL 22 2.20 100 15 P 9.14 1.16 OK
25 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 23 2.38 100 15 P 9.14 1.16 OK
RAMAL 24
26 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
27 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 24 1.48 100 15 P 9.14 1.16 OK

72
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA ALTA
RAMAL 25
RAMAL 23 2.38 100 15 P 9.14 1.16 OK
RAMAL 24 1.48 100 15 P 9.14 1.16 OK
AC-7 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
RAMAL 25 3.86 100 15 P 9.14 1.16 OK
RAMAL 26
28 LAVABO 0.18 50 20 P 1.66 0.85 OK
29 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 26 1.48 100 15 P 9.14 1.16 OK
RAMAL 4-AC
AC-10 AIRE ACONDICIONADO 0.00 13 61 P 0.08 0.60 OK
AC-11 AIRE ACONDICIONADO 0.00 13 61 P 0.08 0.60 OK
RAMAL 4-AC 0.001 13 61 P 0.08 0.60 OK
RAMAL 5-AC
RAMAL 4-AC 0.001 13 61 P 0.08 0.60 OK
AC-12 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
RAMAL 5-AC 0.002 13 61 P 0.08 0.60 OK
RAMAL 27
RAMAL 25 3.86 100 15 P 9.14 1.16 OK
RAMAL 26 1.48 100 15 P 9.14 1.16 OK
AC-8 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
AC-9 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
RAMAL 5-AC 0.002 13 61 P 0.08 0.60
RAMAL 27 5.35 100 15 P 9.14 1.16 OK
RAMAL 28
30 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
31 LAVADERO (ROPA) 0.25 75 20 P 4.90 1.11 OK
RAMAL 28 0.43 75 20 P 4.90 1.11 OK
RAMAL 29
RAMAL 28 0.43 75 20 P 4.90 1.11 OK
32 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 29 1.73 100 15 P 9.14 1.16 OK
RAMAL 30
33 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
34 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 30 1.48 100 15 P 9.14 1.16 OK
RAMAL 31
35 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
36 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 31 1.48 100 15 P 9.14 1.16 OK
RAMAL 32
RAMAL 30 1.48 100 15 P 9.14 1.16 OK
RAMAL 31 1.48 100 15 P 9.14 1.16 OK
RAMAL 32 2.96 100 15 P 9.14 1.16 OK
RAMAL 33
RAMAL 32 2.96 100 15 P 9.14 1.16 OK
37 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 33 3.14 100 15 P 9.14 1.16 OK

73
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA ALTA
RAMAL 34
RAMAL 29 1.73 100 15 P 9.14 1.16 OK
RAMAL 33 3.14 100 15 P 9.14 1.16 OK
RAMAL 34 4.87 100 15 P 9.14 1.16 OK
RAMAL 35
RAMAL 34 4.87 100 15 P 9.14 1.16 OK
38 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 35 5.05 100 15 P 9.14 1.16 OK
RAMAL 7,8-AC
AC-15 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
AC-16 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
AC-17 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
RAMAL 7,8-AC 0.002 13 61 P 0.08 0.60 OK
RAMAL 1 TERRAZA
RAMAL 7,8-AC 0.002 13 61 P 0.08 0.60 OK
176 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
177 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 1 TERRAZA 0.36 50 20 P 1.66 0.85 OK
RAMAL 2 TERRAZA
RAMAL 1 TERRAZA 0.36 50 20 P 1.66 0.85 OK
178 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 2 TERRAZA 0.54 50 20 P 1.66 0.85 OK
RAMAL 3 TERRAZA
RAMAL 2 TERRAZA 0.54 50 20 P 1.66 0.85 OK
179 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 3 TERRAZA 0.72 50 20 P 1.66 0.85 OK
RAMAL 4 TERRAZA
RAMAL 3 TERRAZA 0.72 50 20 P 1.66 0.85 OK
RAMAL 35 5.05 100 15 P 9.14 1.16 OK
RAMAL 4 TERRAZA 5.77 100 15 P 9.14 1.16 OK
RAMAL 6-AC
AC-13 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
AC-14 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
RAMAL 6-AC 0.001 13 61 P 0.08 0.60 OK
RAMAL 36
RAMAL 6-AC 0.001 13 61 P 0.08 0.60 OK
39 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
40 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 36 0.36 50 20 P 1.66 0.85 OK
RAMAL 37
41 SALIDA 0.18 50 20 P 1.66 0.85 OK
42 SALIDA 0.18 50 20 P 1.66 0.85 OK
RAMAL 37 0.36 50 20 P 1.66 0.85 OK
RAMAL 38
RAMAL 37 0.36 50 20 P 1.66 0.85 OK
43 SALIDA 0.18 50 20 P 1.66 0.85 OK
RAMAL 38 0.54 50 20 P 1.66 0.85 OK

74
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA ALTA
RAMAL 39,40
RAMAL 38 0.54 50 20 P 1.66 0.85 OK
44 SALIDA 0.18 50 20 P 1.66 0.85 OK
45 SALIDA 0.18 50 20 P 1.66 0.85 OK
RAMAL 39,40 0.90 50 20 P 1.66 0.85 OK
RAMAL 41
RAMAL 39,40 0.90 50 20 P 1.66 0.85 OK
46 SALIDA 0.18 50 20 P 1.66 0.85 OK
RAMAL 41 1.08 50 20 P 1.66 0.85 OK
RAMAL 42
RAMAL 36 0.36 50 20 P 1.66 0.85 OK
RAMAL 41 1.08 50 20 P 1.66 0.85 OK
RAMAL 42 1.44 50 20 P 1.66 0.85 OK
RAMAL 43
RAMAL 42 1.44 50 20 P 1.66 0.85 OK
47 TARJA DOBLE 0.31 50 20 P 1.66 0.85 OK
RAMAL 43 1.75 75 20 P 4.90 1.11 OK
RAMAL 44
RAMAL 43 1.75 75 20 P 4.90 1.11 OK
48 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 44 1.93 75 20 P 4.90 1.11 OK
RAMAL 45
49 LAVABO 0.18 50 20 P 1.66 0.85 OK
50 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 45 1.48 100 15 P 9.14 1.16 OK
RAMAL 46
RAMAL 44 1.93 75 20 P 4.90 1.11 OK
RAMAL 45 1.48 100 15 P 9.14 1.16 OK
RAMAL 46 3.41 100 15 P 9.14 1.16 OK
RAMAL 47
51 LAVABO 0.18 50 20 P 1.66 0.85 OK
52 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 47 1.48 100 15 P 9.14 1.16 OK
RAMAL 48
RAMAL 46 3.41 100 15 P 9.14 1.16 OK
RAMAL 47 1.48 100 15 P 9.14 1.16 OK
RAMAL 48 4.89 100 15 P 9.14 1.16 OK
RAMAL 49
RAMAL 4 TERRAZA 5.77 100 15 P 9.14 1.16 OK
RAMAL 48 4.89 100 15 P 9.14 1.16 OK
AC-18 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
AC-19 AIRE ACONDICIONADO 0.001 13 61 P 0.08 0.60 OK
RAMAL 49 10.66 152 15 P 27.91 1.54 OK
RAMAL 50
RAMAL 13,14,15,16,17 8.44 100 15 P 9.14 1.16 OK
RAMAL 27 5.35 100 15 P 9.14 1.16 OK
RAMAL 50 13.79 152 15 P 27.91 1.54 OK

75
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA ALTA
RAMAL 51
RAMAL 49 10.66 152 15 P 27.91 1.54 OK
RAMAL 50 13.79 152 15 P 27.91 1.54 OK
RAMAL 51 24.45 152 15 P 27.91 1.54 OK
RAMAL 52
53 LAVABO 0.18 50 20 P 1.66 0.85 OK
54 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 52 0.36 50 20 P 1.66 0.85 OK
RAMAL 53
RAMAL 52 0.36 50 20 P 1.66 0.85 OK
55 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 53 1.66 100 15 P 9.14 1.16 OK
RAMAL 54
RAMAL 53 1.66 100 15 P 9.14 1.16 OK
56 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 54 1.84 100 15 P 9.14 1.16 OK
RAMAL 55
RAMAL 54 1.84 100 15 P 9.14 1.16 OK
57 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 55 3.14 100 15 P 9.14 1.16 OK
RAMAL 56,57,58,59
RAMAL 55 3.14 100 15 P 9.14 1.16 OK
58 LAVABO 0.18 50 20 P 1.66 0.85 OK
59 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
60 LAVABO 0.18 50 20 P 1.66 0.85 OK
61 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 56,57,58,59 6.10 100 15 P 9.14 1.16 OK
RAMAL 60
62 LAVABO 0.18 50 20 P 1.66 0.85 OK
63 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 60 0.36 50 20 P 1.66 0.85 OK
RAMAL 61
RAMAL 60 0.36 50 20 P 1.66 0.85 OK
64 URINARIO SUSPENDIDO 0.18 50 20 P 1.66 0.85 OK
RAMAL 61 0.54 50 20 P 1.66 0.85 OK
RAMAL 62,63
RAMAL 61 0.54 50 20 P 1.66 0.85 OK
65 LAVABO 0.18 50 20 P 1.66 0.85 OK
66 URINARIO SUSPENDIDO 0.18 50 20 P 1.66 0.85 OK
RAMAL 62,63 0.90 50 20 P 1.66 0.85 OK
RAMAL 64
RAMAL 62,63 0.90 50 20 P 1.66 0.85 OK
67 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 64 1.08 50 20 P 1.66 0.85 OK
RAMAL 65
RAMAL 64 1.08 50 20 P 1.66 0.85 OK
68 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 65 2.38 100 15 P 9.14 1.16 OK

76
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA ALTA
RAMAL 66,67
RAMAL 65 2.38 100 15 P 9.14 1.16 OK
69 LAVABO 0.18 50 20 P 1.66 0.85 OK
70 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 66,67 3.86 100 15 P 9.14 1.16 OK
RAMAL 68
RAMAL 56,57,58,59 6.10 100 15 P 9.14 1.16 OK
RAMAL 66,67 3.86 100 15 P 9.14 1.16 OK
RAMAL 68 9.96 100 20 P 10.55 1.34 OK
RAMAL 69
RAMAL 51 24.45 152 15 P 27.91 1.54 OK
RAMAL 68 9.96 100 20 P 10.55 1.34 OK
RAMAL 69 34.41 203 20 P 69.71 2.15 OK
PLANTA BAJA
RAMAL 71
71 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 70 0.36 50 20 P 1.66 0.85 OK
RAMAL 71 0.54 50 20 P 1.66 0.85 OK
RAMAL 70
72 TARJA 0.18 50 20 P 1.66 0.85 OK
73 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 70 0.36 50 20 P 1.66 0.85 OK
RAMAL 72
74 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
75 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 72 0.36 50 20 P 1.66 0.85 OK
RAMAL 73
RAMAL 72 0.36 50 20 P 1.66 0.85 OK
76 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 73 0.54 50 20 P 1.66 0.85 OK
RAMAL 74,75
RAMAL 73 0.54 50 20 P 1.66 0.85 OK
77 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
78 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 74,75 0.90 50 20 P 1.66 0.85 OK
RAMAL 76
RAMAL 74,75 0.90 50 20 P 1.66 0.85 OK
79 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 76 1.08 50 20 P 1.66 0.85 OK
RAMAL 77,78,79
RAMAL 76 1.08 50 20 P 1.66 0.85 OK
80 TARJA 0.18 50 20 P 1.66 0.85 OK
81 TARJA 0.18 50 20 P 1.66 0.85 OK
82 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 77,78,79 1.62 50 20 P 1.66 0.85 OK
RAMAL 178
RAMAL 77,78,79 1.62 50 20 P 1.66 0.85 OK
184 W.C. FLUX. 1.30 100 20 P 10.55 1.34 OK
RAMAL 178 2.92 100 20 P 10.55 1.34 OK

77
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA BAJA
RAMAL 80
RAMAL 178 2.92 100 20 P 10.55 1.34 OK
83 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 80 3.10 100 20 P 10.55 1.34 OK
RAMAL 179
RAMAL 80 3.10 100 20 P 10.55 1.34 OK
185 W.C. FLUX. 1.30 100 20 P 10.55 1.34 OK
RAMAL 179 4.40 100 20 P 10.55 1.34 OK
RAMAL 81,82
RAMAL 179 4.40 100 20 P 10.55 1.34 OK
84 TARJA 0.18 50 20 P 1.66 0.85 OK
85 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 81,82 4.76 100 15 P 9.14 1.16 OK
RAMAL 180
186 LAVABO 0.18 50 20 P 1.66 0.85 OK
187 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 180 0.36 50 20 P 1.66 0.85 OK
RAMAL 181
RAMAL 81,82 4.76 100 15 P 9.14 1.16 OK
RAMAL 180 0.36 50 20 P 1.66 0.85 OK
RAMAL 181 5.12 100 15 P 9.14 1.16 OK
RAMAL 83
RAMAL 181 5.12 100 15 P 9.14 1.16 OK
86 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 83 5.30 100 15 P 9.14 1.16 OK
RAMAL 84
RAMAL 71 0.54 50 20 P 1.66 0.85 OK
RAMAL 83 5.30 100 15 P 9.14 1.16 OK
RAMAL 84 5.84 100 15 P 9.14 1.16 OK
RAMAL 85
RAMAL 84 5.84 100 15 P 9.14 1.16 OK
87 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 85 6.02 100 15 P 9.14 1.16 OK
RAMAL 86
88 LAVABO 0.18 50 20 P 1.66 0.85 OK
89 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 86 1.48 100 15 P 9.14 1.16 OK
RAMAL 87,88,89
RAMAL 86 1.48 100 15 P 9.14 1.16 OK
90 TARJA 0.18 50 20 P 1.66 0.85 OK
91 TARJA 0.18 50 20 P 1.66 0.85 OK
92 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 87,88,89 2.02 100 15 P 9.14 1.16 OK
RAMAL 90
RAMAL 87,88,89 2.02 100 15 P 9.14 1.16 OK
93 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 90 2.20 100 15 P 9.14 1.16 OK

78
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA BAJA
RAMAL 91
RAMAL 85 6.02 100 15 P 9.14 1.16 OK
RAMAL 90 2.20 100 15 P 9.14 1.16 OK
RAMAL 91 8.22 100 15 P 9.14 1.16 OK
RAMAL 92
94 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
95 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 92 1.48 100 15 P 9.14 1.16 OK
RAMAL 93
RAMAL 92 1.48 100 15 P 9.14 1.16 OK
96 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 93 1.66 100 15 P 9.14 1.16 OK
RAMAL 94
RAMAL 93 1.66 100 15 P 9.14 1.16 OK
97 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 94 2.96 100 15 P 9.14 1.16 OK
RAMAL 95
RAMAL 91 8.22 100 15 P 9.14 1.16 OK
RAMAL 94 2.96 100 15 P 9.14 1.16 OK
RAMAL 95 11.18 152 15 P 27.91 1.54 OK
RAMAL 96
RAMAL 95 11.18 152 15 P 27.91 1.54 OK
98 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 96 11.36 152 15 P 27.91 1.54 OK
RAMAL 97
RAMAL 69 34.41 203 20 P 69.71 2.15 OK
RAMAL 96 11.36 152 15 P 27.91 1.54 OK
RAMAL 97 45.77 203 15 P 60.37 1.87 OK
RAMAL 98
99 TARJA 0.18 50 20 P 1.66 0.85 OK
100 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 98 0.36 50 20 P 1.66 0.85 OK
RAMAL 99
RAMAL 98 0.36 50 20 P 1.66 0.85 OK
101 REGADERA 0.25 50 20 P 1.66 0.85 OK
RAMAL 99 0.61 50 20 P 1.66 0.85 OK
RAMAL 100
RAMAL 99 0.61 50 20 P 1.66 0.85 OK
102 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 100 0.79 50 20 P 1.66 0.85 OK
RAMAL 101
RAMAL 97 45.77 203 15 P 60.37 1.87 OK
RAMAL 100 0.79 50 20 P 1.66 0.85 OK
RAMAL 101 46.56 203 15 P 60.37 1.87 OK
RAMAL 102
103 LAVABO 0.18 50 20 P 1.66 0.85 OK
104 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 102 0.36 50 20 P 1.66 0.85 OK

79
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA BAJA
RAMAL 103
RAMAL 102 0.36 50 20 P 1.66 0.85 OK
105 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 103 0.54 50 30 P 2.04 1.04 OK
RAMAL 104
RAMAL 101 46.56 203 15 P 60.37 1.87 OK
RAMAL 103 0.54 50 30 P 2.04 1.04 OK
RAMAL 104 47.10 203 15 P 60.37 1.87 OK
RAMAL 105
RAMAL 104 47.10 203 15 P 60.37 1.87 OK
106 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 105 47.28 203 15 P 60.37 1.87 OK
RAMAL 106
107 LAVABO 0.18 50 20 P 1.66 0.85 OK
108 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 106 1.48 100 15 P 9.14 1.16 OK
RAMAL 107
RAMAL 105 47.28 203 15 P 60.37 1.87 OK
RAMAL 106 1.48 100 15 P 9.14 1.16 OK
RAMAL 107 48.76 203 15 P 60.37 1.87 OK
RAMAL 108
RAMAL 107 48.76 203 15 P 60.37 1.87 OK
109 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 108 48.94 203 15 P 60.37 1.87 OK
RAMAL 109
110 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
111 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 109 1.48 100 15 P 9.14 1.16 OK
RAMAL 110
RAMAL 108 48.94 203 15 P 60.37 1.87 OK
RAMAL 109 1.48 100 15 P 9.14 1.16 OK
RAMAL 110 50.42 203 20 P 69.71 2.15 OK
RAMAL 111
112 LAVABO 0.18 50 20 P 1.66 0.85 OK
113 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 111 1.48 100 15 P 9.14 1.16 OK
RAMAL 112
114 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
115 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 112 1.48 100 15 P 9.14 1.16 OK
RAMAL 113
RAMAL 112 1.48 100 15 P 9.14 1.16 OK
116 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 113 2.78 100 15 P 9.14 1.16 OK

80
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA BAJA
RAMAL 114,115,116,117
RAMAL 113 2.78 100 15 P 9.14 1.16 OK
117 LAVABO 0.18 50 20 P 1.66 0.85 OK
118 URINARIO SUSPENDIDO 0.18 50 20 P 1.66 0.85 OK
119 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 111 1.48 100 15 P 9.14 1.16 OK
RAMAL 114,115,116,117 4.80 100 15 P 9.14 1.16 OK
RAMAL 118
120 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
121 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 118 2.60 100 15 P 9.14 1.16 OK
RAMAL 119,120,121,122
RAMAL 118 2.60 100 15 P 9.14 1.16 OK
122 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
123 LAVABO 0.18 50 20 P 1.66 0.85 OK
124 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
125 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 119,120,121,122 5.56 100 15 P 9.14 1.16 OK
RAMAL 123
RAMAL 114,115,116,117 4.80 100 15 P 9.14 1.16 OK
RAMAL 119,120,121,122 5.56 100 15 P 9.14 1.16 OK
RAMAL 123 10.36 100 20 P 10.55 1.34 OK
RAMAL 124
RAMAL 123 10.36 100 15 P 10.55 1.34 OK
126 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 124 10.54 100 20 P 10.55 1.34 OK
RAMAL 125
127 TARJA 0.18 50 20 P 1.66 0.85 OK
128 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 125 1.48 100 15 P 9.14 1.16 OK
RAMAL 126
RAMAL 125 1.48 100 15 P 9.14 1.16 OK
129 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 126 1.66 100 15 P 9.14 1.16 OK
RAMAL 127
RAMAL 124 10.54 100 20 P 10.55 1.34 OK
RAMAL 126 1.66 100 15 P 9.14 1.16 OK
RAMAL 127 12.20 152 15 P 27.91 1.54 OK
RAMAL 128
RAMAL 110 50.42 203 20 P 69.71 2.15 OK
RAMAL 127 12.20 152 15 P 27.91 1.54 OK
RAMAL 128 62.62 203 20 P 69.71 2.15 OK
RAMAL 129
130 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
131 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 129 0.36 50 20 P 1.66 0.85 OK

81
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA BAJA
RAMAL 130
132 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
133 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 130 1.48 100 15 P 9.14 1.16 OK
RAMAL 131
RAMAL 129 0.36 50 20 P 1.66 0.85 OK
RAMAL 130 1.48 100 15 P 9.14 1.16 OK
RAMAL 131 1.84 100 15 P 9.14 1.16 OK
RAMAL 132
134 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
135 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 132 1.48 100 15 P 9.14 1.16 OK
RAMAL 133
RAMAL 131 1.84 100 15 P 9.14 1.16 OK
RAMAL 132 1.48 100 15 P 9.14 1.16 OK
RAMAL 133 3.32 100 15 P 9.14 1.16 OK
RAMAL 134
136 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
137 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 134 1.48 100 15 P 9.14 1.16 OK
RAMAL 135
RAMAL 133 3.32 100 15 P 9.14 1.16 OK
RAMAL 134 1.48 100 15 P 9.14 1.16 OK
RAMAL 135 4.80 100 15 P 9.14 1.16 OK
RAMAL 136
RAMAL 135 4.80 100 15 P 9.14 1.16 OK
138 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 136 4.98 100 15 P 9.14 1.16 OK
RAMAL 137
139 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
140 TARJA DOBLE 0.31 50 30 P 2.04 1.04 OK
RAMAL 137 1.61 100 15 P 9.14 1.16 OK
RAMAL 138
RAMAL 136 4.98 100 15 P 9.14 1.16 OK
RAMAL 137 1.61 100 15 P 9.14 1.16 OK
RAMAL 138 6.59 100 15 P 9.14 1.16 OK
RAMAL 139
RAMAL 138 6.59 100 15 P 9.14 1.16 OK
141 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 139 7.89 100 15 P 9.14 1.16 OK
RAMAL 140
142 TARJA 0.18 50 20 P 1.66 0.85 OK
143 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 140 0.36 50 20 P 1.66 0.85 OK
RAMAL 141
RAMAL 139 7.89 100 15 P 9.14 1.16 OK
RAMAL 140 0.36 50 20 P 1.66 0.85 OK
RAMAL 141 8.25 100 15 P 9.14 1.16 OK

82
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
PLANTA BAJA
RAMAL 142
RAMAL 128 62.62 203 20 P 69.71 2.15 OK
RAMAL 141 8.25 100 15 P 9.14 1.16 OK
RAMAL 142 70.87 203 21 P 71.43 2.21 OK
RAMAL 143
144 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
145 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 143 1.48 100 15 P 9.14 1.16 OK
RAMAL 144
RAMAL 143 1.48 100 15 P 9.14 1.16 OK
146 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 144 2.78 100 15 P 9.14 1.16 OK
RAMAL 145
RAMAL 144 2.78 100 15 P 9.14 1.16 OK
147 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 145 2.96 100 15 P 9.14 1.16 OK
RAMAL 146
148 LAVABO 0.18 50 20 P 1.66 0.85 OK
149 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 146 1.48 100 15 P 9.14 1.16 OK
RAMAL 147
150 LAVABO 0.18 50 20 P 1.66 0.85 OK
151 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 147 1.48 100 15 P 9.14 1.16 OK
RAMAL 148
RAMAL 146 1.48 100 15 P 9.14 1.16 OK
RAMAL 147 1.48 100 15 P 9.14 1.16 OK
RAMAL 148 2.96 100 15 P 9.14 1.16 OK
RAMAL 149
RAMAL 148 2.96 100 15 P 9.14 1.16 OK
152 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 149 3.14 100 15 P 9.14 1.16 OK
RAMAL 150
RAMAL 145 2.96 100 15 P 9.14 1.16 OK
RAMAL 149 3.14 100 15 P 9.14 1.16 OK
RAMAL 150 6.10 100 15 P 9.14 1.16 OK
RAMAL 151
RAMAL 142 70.87 203 21 P 71.43 2.21 OK
RAMAL 150 6.10 100 15 P 9.14 1.16 OK
RAMAL 151 76.97 254 20 P 126.73 2.50 OK
RAMAL 152
RAMAL 151 76.97 254 20 P 126.73 2.50 OK
153 TARJA 0.18 50 20 P 1.66 0.85 OK
RAMAL 152 77.15 254 20 P 126.73 2.50 OK

83
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
SÓTANO
RAMAL 153
154 REGADERA 0.25 50 20 P 1.66 0.85 OK
155 REGADERA 0.25 50 20 P 1.66 0.85 OK
RAMAL 153 0.50 50 20 P 1.66 0.85 OK
RAMAL 154
RAMAL 153 0.50 50 20 P 1.66 0.85 OK
156 REGADERA 0.25 50 20 P 1.66 0.85 OK
RAMAL 154 0.75 50 20 P 1.66 0.85 OK
RAMAL 155
157 LAVABO 0.18 50 20 P 1.66 0.85 OK
158 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 155 1.48 100 15 P 9.14 1.16 OK
RAMAL 156,157
RAMAL 155 1.48 100 15 P 9.14 1.16 OK
159 LAVABO 0.18 50 20 P 1.66 0.85 OK
160 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 156,157 1.84 100 15 P 9.14 1.16 OK
RAMAL 158
RAMAL 156,157 1.84 100 15 P 9.14 1.16 OK
161 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 158 3.14 100 15 P 9.14 1.16 OK
RAMAL 159,160,161
RAMAL 158 3.14 100 15 P 9.14 1.16 OK
162 LAVABO 0.18 50 20 P 1.66 0.85 OK
163 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
164 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 159,160,161 4.80 100 15 P 9.14 1.16 OK
RAMAL 162
RAMAL 154 0.75 50 20 P 1.66 0.85 OK
RAMAL 159,160,161 4.80 100 15 P 9.14 1.16 OK
RAMAL 162 5.55 100 15 P 9.14 1.16 OK
RAMAL 163
165 LAVABO 0.18 50 20 P 1.66 0.85 OK
166 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 163 1.48 100 15 P 9.14 1.16 OK
RAMAL 164,165
RAMAL 163 1.48 100 15 P 9.14 1.16 OK
167 LAVABO 0.18 50 20 P 1.66 0.85 OK
168 LAVABO 0.18 50 20 P 1.66 0.85 OK
RAMAL 164,165 1.84 100 15 P 9.14 1.16 OK

84
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
SÓTANO
RAMAL 166
RAMAL 164,165 1.84 100 15 P 9.14 1.16 OK
169 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 166 3.14 100 15 P 9.14 1.16 OK
RAMAL 167,168
RAMAL 166 3.14 100 15 P 9.14 1.16 OK
170 LAVABO 0.18 50 20 P 1.66 0.85 OK
171 W.C. FLUX. 1.30 100 15 P 9.14 1.16 OK
RAMAL 167,168 4.62 100 15 P 9.14 1.16 OK
RAMAL 169
RAMAL 162 5.55 100 15 P 9.14 1.16 OK
RAMAL 167,168 4.62 100 15 P 9.14 1.16 OK
RAMAL 169 10.17 100 20 P 10.55 1.34 OK
RAMAL 170
RAMAL 169 10.17 100 15 P 10.55 1.34 OK
172 COLADERA DE PISO 0.18 50 20 P 1.66 0.85 OK
RAMAL 170 10.35 100 20 P 10.55 1.34 OK
RAMAL 171
173 REGADERA 0.25 50 20 P 1.66 0.85 OK
174 REGADERA 0.25 50 20 P 1.66 0.85 OK
RAMAL 171 0.50 50 20 P 1.66 0.85 OK
RAMAL 172
RAMAL 171 0.50 50 20 P 1.66 0.85 OK
175 REGADERA 0.25 50 20 P 1.66 0.85 OK
RAMAL 172 0.75 50 20 P 1.66 0.85 OK
RAMAL 173
RAMAL 170 10.35 100 20 P 10.55 1.34 OK
RAMAL 172 0.75 50 30 P 1.66 0.85 OK
RAMAL 173 11.10 152 15 P 27.91 1.54 OK
HEMODIÁLISIS
RAMAL 1 HEMODIÁLISIS
H1 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
H2 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 1 HEMODIÁLISIS 0.06 38 20 P 0.80 0.70 OK
RAMAL 2 HEMODIÁLISIS
RAMAL 1 HEMODIÁLISIS 0.06 38 20 P 0.80 0.70 OK
H3 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 2 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK
RAMAL 3 HEMODIÁLISIS
H4 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
H5 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 3 HEMODIÁLISIS 0.06 38 20 P 0.80 0.70 OK
RAMAL 4 HEMODIÁLISIS
RAMAL 3 HEMODIÁLISIS 0.06 38 20 P 0.80 0.70 OK
H6 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 4 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK

85
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
HEMODIÁLISIS
RAMAL 5 HEMODIÁLISIS
RAMAL 4 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK
H7 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 5 HEMODIÁLISIS 0.12 38 20 P 0.80 0.70 OK
RAMAL 6 HEMODIÁLISIS
RAMAL 4 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK
RAMAL 5 HEMODIÁLISIS 0.12 38 20 P 0.80 0.70 OK
RAMAL 6 HEMODIÁLISIS 0.21 38 20 P 0.80 0.70 OK
RAMAL 7 HEMODIÁLISIS
RAMAL 6 HEMODIÁLISIS 0.21 38 20 P 0.80 0.70 OK
H8 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 7 HEMODIÁLISIS 0.24 38 20 P 0.80 0.70 OK
RAMAL 8 HEMODIÁLISIS
RAMAL 7 HEMODIÁLISIS 0.24 38 20 P 0.80 0.70 OK
H9 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 8 HEMODIÁLISIS 0.27 38 20 P 0.80 0.70 OK
RAMAL 9 HEMODIÁLISIS
H10 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
H11 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 9 HEMODIÁLISIS 0.06 38 20 P 0.80 0.70 OK
RAMAL 10 HEMODIÁLISIS
RAMAL 9 HEMODIÁLISIS 0.06 38 20 P 0.80 0.70 OK
H12 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 10 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK
RAMAL 11 HEMODIÁLISIS
RAMAL 8 HEMODIÁLISIS 0.27 38 20 P 0.80 0.70 OK
RAMAL 10 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK
RAMAL 11 HEMODIÁLISIS 0.36 38 20 P 0.80 0.70 OK
RAMAL 12 HEMODIÁLISIS
H13 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
H14 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 12 HEMODIÁLISIS 0.06 38 20 P 0.80 0.70 OK
RAMAL 13 HEMODIÁLISIS
RAMAL 12 HEMODIÁLISIS 0.06 38 20 P 0.80 0.70 OK
H15 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 13 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK
RAMAL 14 HEMODIÁLISIS
RAMAL 13 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK
H16 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 14 HEMODIÁLISIS 0.12 38 20 P 0.80 0.70 OK
RAMAL 15 HEMODIÁLISIS
H17 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
H18 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 15 HEMODIÁLISIS 0.06 38 20 P 0.80 0.70 OK
RAMAL 16 HEMODIÁLISIS
RAMAL 15 HEMODIÁLISIS 0.06 38 20 P 0.80 0.70 OK
H19 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 16 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK

86
DIAM. GASTO A VELOCIDAD A
Gasto PENDIENTE
CODIGO MUEBLE DISEÑO MATERIAL TUBO LLENO TUBO LLENO GASTO (l/s)
(l/s) (al millar)
mm (l/s) (m/s)
HEMODIÁLISIS
RAMAL 17 HEMODIÁLISIS
RAMAL 13 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK
RAMAL 16 HEMODIÁLISIS 0.09 38 20 P 0.80 0.70 OK
RAMAL 17 HEMODIÁLISIS 0.18 38 20 P 0.80 0.70 OK
RAMAL 18 HEMODIÁLISIS
RAMAL 17 HEMODIÁLISIS 0.18 38 20 P 0.80 0.70 OK
H20 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 18 HEMODIÁLISIS 0.21 38 20 P 0.80 0.70 OK
RAMAL 19 HEMODIÁLISIS
RAMAL 18 HEMODIÁLISIS 0.21 38 20 P 0.80 0.70 OK
H21 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 19 HEMODIÁLISIS 0.24 38 20 P 0.80 0.70 OK
RAMAL 20 HEMODIÁLISIS
RAMAL 19 HEMODIÁLISIS 0.24 38 20 P 0.80 0.70 OK
H22 HEMODIÁLISIS 0.03 38 20 P 0.80 0.70 OK
RAMAL 20 HEMODIÁLISIS 0.27 38 20 P 0.80 0.70 OK
RAMAL 21 HEMODIÁLISIS
RAMAL 11 HEMODIÁLISIS 0.36 38 20 P 0.80 0.70 OK
RAMAL 20 HEMODIÁLISIS 0.27 38 20 P 0.80 0.70 OK
RAMAL 21 HEMODIÁLISIS 0.63 38 20 P 0.80 0.70 OK

En la

Tabla 9 de cálculo se observa que cada tramo cumple con su gasto de diseño acumulado y que
además se encuentra dentro del rango de velocidades mencionadas anteriormente para las
tuberías de PVC sanitario de norma. Por lo tanto, se da por valido el diseño propuesto de la red.

2.29 DIMENCIONAMIENTO DE CARCAMO DE BOMBEO

Primeramente, se proponen las dimensiones del cárcamo con base en el volumen a regular en
él, dando como resultado 1.53 m3 en un tiempo de 30 minutos, el cual es el tiempo máximo de
retención permitido de acuerdo a la normativa de la Conagua. Para este proyecto se presenta
un cárcamo rectangular de 3.80 m de largo y 2.30 m de ancho y una altura de 1.00 m y de 1.10
en la cámara de sedimentación, El cárcamo se construirá con una cámara de sedimentación,
una de transición y dos cámaras de bombeo.

87
Tabla 10. Dimensionamiento del cárcamo
DATOS DE ENTRADA
Qmed (lps)= 5.12
QmaxI (lps)= 11.10
Tiempo de retención (min)= 30.0
Tirante efectivo (del nivel max al min)(m)= 0.50
Largo de camara de sedimentos (m)= 0.40
Ancho de muro internos (m)= 0.30
Ancho de muro externos (m)= 0.30
Ancho de rejillas, nariz y pantalla (m)= 0.20
Bordo Libre (m)= 0.10

DIMENSIONAMIENTO DE LAS CAMARAS


Cálculado Proyectado
Ancho de camaras de bombeo(m)= 0.41 1.00
Longitud de camara de bombeo (m)= 1.22 1.25
Sumergencia (m)= 0.30 0.30
Dist. del eje de la bomba al muro posterior (m)= 0.41 0.45
Dist. De la campana al piso (m)= 0.10 0.10

CÁLCULO DEL VOLUMEN DE REGULACIÓN


Minutos Segundos
Tiempo de operación de las bombas= 5 300
Volumen de regulación (m3)= 1.53 6.32

CÁLCULO DE ÁREAS
Cantidad de camaras de bombeo= 2
Área de camaras de bombeo(m2)= 2.50
Ancho total interno de la camara de
2.30
sedimentación(m)=
Área de camara de sedimentos (m2)= 0.92
Ancho total interno de la camara(m)= 2.30 Cálculado
Longitud (m)= 4.01 1.05
Área de trancisión(m2)= 9.22

CÁLCULO DEL CICLO


Segundos Minutos
Tiempo de llenado (min)= 1235.53 21.00
Ciclo completo (min)= 1535.53 26.00
Revisión= OK

88
Figura 13. Detalle de cárcamo de bombeo vista en planta.

Figura 14. Detalle de cárcamo de bombeo vista en corte.

Posteriormente se propone un diámetro para la línea de impulsión, en este caso será de fierro
galvanizado de 3” de diámetro y mediante los métodos de Darcy-Weisbach y Manning se
calcularán las pérdidas de fricción y locales con el fin de obtener la carga dinámica total,
adicionando los desniveles topográficos a vencer, proponiendo una carga residual de columna
de agua de 5 m, tal y como se muestra en la tabla 11.

89
Como siguiente paso se busca una bomba en el mercado de acuerdo a esos requerimientos.
Para el proyecto se optó por una bomba marca NABOHI, modelo BCA-03-32-23/43 con 3 HP de
potencia, o se propone otra de similares características ya que cumple con los requerimientos
para bombear hasta la descarga.
Tabla 11. Cálculo de línea de bombeo.
Cálculo de diámetro y pérdidas de energía
Long V Q Diametro Diametro Area Radio
Viscosidad
n
ϵ
Hf
Hf
Piezométrica
Z Carga
Tramo nominal MATERIAL cinemátic Re (Rugosidad f (Darcy) k (Manning) (Elevación disponible
m m/s m 3/s m 2
m Hidráulico (Manning) (Darcy) (m.s.n.m)
Pulg a (m2/s) Absoluta) m m.s.n.m.) (m)

Bomba P1 9.23 -5.77 15.00


Bomba P1 A Brocal P1 2.68 1.12 0.005 0.0762 3.00 FoGo 0.005 0.0191 1.06E-06 80,785 0.011 0.1500 0.02561 1,144 0.0578 0.0802 9.17 -4.17 13.34
Brocal P1 A Registro 7.19 1.30 0.005 0.0700 3.00 FoGo 0.004 0.0175 1.06E-06 85,879 0.011 0.1500 0.02594 1,798 0.2292 0.3231 8.91 0.00 8.91

2.30 ESPECIFICACIONES DE MATERIALES

 Tuberías: La tubería será de P.V.C. Sanitario de norma tipo Anger y unión para
cementar Mca. Amanco Wavin o similar.

 Coladeras: las coladeras a instalar será de marca Helvex o similar.

 Conexiones: Las conexiones serán también de P.V.C. Sanitario de fabricación


nacional tipo cementar Mca. Amanco Wavin o similar.

 Materiales de unión: Para unir las tuberías de P.V.C. con sus respectivas
conexiones se utilizará cemento para P.V.C. Mca. Amanco Wavin o similar.

 Registros Sanitarios: Los registros sanitarios tendrán un firme de concreto con una
resistencia de f’c= 200 kg/cm2, de 10 cm de espesor, muros y tapa de concreto con una
resistencia de f’c= 200 kg/cm2, de 10 cm de espesor, reforzado con acero de 5/16 a cada
15 cm en ambos sentidos, cimbra, contramarco de 1/8" x 2" y contramarco de 1/8" x 1 1/2",
las medidas interiores y las profundidades serán las indicadas en el proyecto.

90
2.31 NORMATIVIDAD APLICABLE

 Criterios y lineamientos técnicos para factibilidades, SIAPA. CAP. 1 CRITERIOS


BÁSICOS DE DISEÑO. Febrero 2014.

 Criterios y lineamientos técnicos para factibilidades, SIAPA. CAP. 3


ALCANTARILLADO SANITARIO. Febrero 2014.

 Normas técnicas complementarias para el diseño y la ejecución de obras e


instalaciones hidráulicas sección 2.

 Lineamientos Comisión Nacional del Agua (CONAGUA)

 Catálogo de edificación de Amanco Wavin México Ed. 2021

91
3 PROYECTO PLUVIAL.

El propósito de este proyecto es diseñar la red pluvial tomando en consideración la superficie de


captación de azoteas y terrazas de la unidad médica, conduciendo estas aguas captadas a un
tanque de tormentas que servirá para contenerlas por un periodo determinado; posteriormente
se desalojaran a la red municipal.

3.1 HIDROLOGÍA EN LA ZONA DE ESTUDIO

En este capítulo, se explica de forma resumida el proceso realizado para obtener el gasto de
diseño que posteriormente se usará en el modelo hidráulico. Por lo que, se realizan una serie de
actividades, las que implica la recopilación de información y el análisis de datos para decretar
los valores útiles en el cálculo que se emplearán en los modelos matemáticos de lluvia-
escurrimiento.

3.1.1 CURVAS I-D-TR.

En el Área Metropolitana de Guadalajara (AMG) existen varias estaciones climatológicas que


tienen como finalidad cuantificar diversos eventos meteorológicos, tales como: temperaturas
diarias, velocidad y dirección del viento, precipitación diaria, entre otras. Para el cálculo del gasto
máximo presentado en la zona de estudio, primeramente, se analizan los datos de
precipitaciones registrados de cada estación y se seleccionan aquellas que mayor influyen.
Debido a la ubicación del predio y las estaciones se seleccionó las curvas de Intensidad-
Duración-Tr de la cuenca de Atemajac obtenidas del PROMIAP del SIAPA.

Con base a las precipitaciones diarias registradas, se determinan las Precipitaciones Máximas
Anuales (PMA). Dichos valores se analizan probabilísticamente para calcular las lluvias
asociadas a diferentes Periodos de Retorno (Tr) expresados en años. Por último, se generan las
curvas de Intensidad – Duración – Periodo de Retorno.
Tabla 12. Intensidad - Duración - Periodo de Retorno de la cuenca Atemajac (i-d-Tr)
CUENCA ATEMAJAC
INTENSIDADES ESTIMADAS (MM/H) PARA DIFERENTES DURACIONES (MIN) Y PERIODOS DE RETORNO (AÑOS)
Duración de la tormenta
Tr(años)
5 min 10 min 20 min 30 min 40 min 50 min 60 min 120 min 1440 min
2 153.58 114.94 80.16 63.58 53.57 46.75 41.74 26.79 2.71
5 202.70 151.71 105.80 83.92 70.70 61.70 55.09 35.36 3.35
10 239.86 179.52 125.19 99.30 83.66 73.01 65.19 41.84 3.68
25 288.98 216.29 150.83 119.64 100.80 87.96 78.55 50.41 4.14
50 326.14 244.10 170.23 135.02 113.76 99.27 88.65 56.89 4.31
100 363.31 271.91 189.62 150.41 126.72 110.58 98.75 63.37 4.56

92
Figura 15. Curvas Intensidad - Duración - Periodo de Retorno (i-d-Tr)

3.1.2 MORFOLOGÍA DEL PREDIO

El coeficiente de escurrimiento nos define la proporción de la lluvia que contribuye al


escurrimiento superficial; el cual se obtiene como un valor ponderado de los coeficientes típicos
de escurrimiento para diversas superficies en contacto con el agua de lluvia.

Una vez calculada las curvas i-d-Tr, se procede en delimitar el área de captación que para este
caso es el total del predio, debido a la normativa en el tema pluvial por parte del SIAPA, se
determinara el impacto hidrológico cero, por lo que es necesario determinar los caudales
pluviales que se generan en estado en breña y de proyecto, esto para poder diseñar un depósito
que regule los escurrimientos pluviales y evitar un incremento del flujo pluvial en la red municipal.

En la siguiente figura se tomaron los coeficientes de escurrimiento para el cálculo en este


proyecto, esta se encuentra reglamentado en las Normas de diseño de Ingeniería del Instituto
Mexicano del seguro Social en su capítulo 11. Eliminación de aguas pluviales, en su apartado
11.1. Coeficiente de escurrimiento.

93
Figura 16. Coeficiente de escurrimientos del IMSS.

Se procede a dividir las áreas o diferentes usos de suelo que se tienen dentro de la unidad
médica, donde se encontraron 5 usos diferentes, que son: área en breña, construcción,
estacionamientos de concreto, adopasto y áreas verdes, a cada una se le determina un
coeficiente de escurrimiento con base en la normativa oficial, en la siguiente tabla se presentan
los coeficientes de escurrimiento por uso de suelo y ponderado para su estado en breña y de
proyecto.
Tabla 13. Ponderación de coeficientes de escurrimiento.
COEFICIENTES DE ESCURRIMIENTO PONDERADOS DE LA CUENCA DE
ESTUDIO EN BREÑA
MC-01
2 SUPERFICIE EN
USO DE SUELO Ce AREA M % Ce ponderado
HECTAREAS
ÁREAS EN BREÑA 0.20 4,099.84 0.4100 100% 0.20
Total 4,099.84 0.4100 100% 0.20

COEFICIENTES DE ESCURRIMIENTO PONDERADOS DE LA CUENCA DE


ESTUDIO EN PROYECTO
MC-01
2 SUPERFICIE EN
USO DE SUELO Ce AREA M % Ce ponderado
HECTAREAS
CONSTRUCCIONES 0.95 2036.94 0.2037 50% 0.47
PATIOS Y
ESTACIONAMIENTOS:
0.95 1300.83 0.1301 32% 0.30
CONCRETO
HIDRÁULICO
CAJONES DE
ESTACIONAMIENTO: 0.35 373.87 0.0374 9% 0.03
ADOPASTO
AREAS VERDES 0.17 388.19 0.0388 9% 0.02
Total 4,099.84 0.4100 100% 0.82

Una vez determinado el coeficiente de escurrimiento, se procede en calcular el tiempo de


concentración (método Kirpich).

94
Tabla 14. Cálculo de características físicas.
CARACTERÍSTICAS FÍSICAS
SUPERFICIE LONG. MAYOR COTA MAYOR COTA MENOR
SUBCUENCA 2
(m ) (m) (m.s.n.m) (m.s.n.m)
MC-01 4099.84 136.38 7.40 -1.72
CARACTERÍSTICAS FÍSICAS CALCULADAS
PENDIENTE
SUPERFICIE TC (KIRPICH)
SUBCUENCA GOBERNADORA Ce
(Ha) (min)
(al millar)
MC-01 0.41 67.00 2.00 0.82

El cálculo arrojo un tiempo de concentración de 2 minutos y que, por normativa del IMSS, se
deberá diseñar para tiempos de concentración de 5 y 10 minutos para drenajes interiores y
exteriores respectivamente y un periodo de retorno de 10 años por lo que la intensidad que se
empleara es de 180.92 mm/hr y 147.64 mm/hr respectivamente.

3.1.3 MÉTODO RACIONAL AMERICANO

El método racional es el más empleado en el cálculo del gasto pico en cuencas urbanas, para la
determinación del caudal se fundamenta en las siguientes hipótesis (Gómez, 2007), la intensidad
de la precipitación es uniforme en el espacio y no varía en el tiempo; la duración de la
precipitación que produce el caudal máximo dada una intensidad, es igual al tiempo de
concentración; el tiempo de concentración es el tiempo que tarda toda el área de la cuenca en
contribuir al escurrimiento mismo en que se produce el gasto pico; el coeficiente de escurrimiento
se mantiene uniforme en el tiempo.

Campos-Aranda, 2010, recomienda el uso de este método para cuencas con un área no mayor
a 0.89 km2; por su cuenta López, 2007 menciona que puede ser aplicable en cuencas con en
áreas de hasta 12.59 km2 (5 mi2), es decir, este método es aplicable a microcuencas y
subcuencas.

En la siguiente tabla se presentan los gastos de escurrimiento obtenidos aplicando este método,
tanto para el estado en breña como de proyecto para las duraciones previamente mencionadas.
Tabla 15. Cálculo de gastos pluviales con el método Racional Americano.

ESTIMACION DE GASTOS PLUVIALES MÉTODO RACIONAL AM ERICANO

DURACIÓN Tr (años) = 10 BREÑA Tr (años) = 10 PROYECTO


SUBCUENCA TORMENTA INTENSIDAD GASTO INTENSIDAD GASTO
(min) (mm/hr) (l/s) (mm/hr) (l/s)
Drenajes interiores 5 180.92 20.490 180.92 97.327
Drenajes exteriores 10 147.64 16.934 147.64 58.801
∑ 37.424 ∑ 156.128

95
Con esto la red pluvial interna se diseñará con un gasto de 97.327 l/s y los drenajes externos al
edificio se diseñarán con un gasto de 58.80 l/s, teniendo un caudal de diseño al depósito de
tormenta de 156.13 l/s.

3.2 DISEÑO DE SISTEMA PLUVIAL

Para el manejo correcto de los escurrimientos pluviales, se proponen dos diferentes tipos de
sistemas pluviales para la protección de la unidad médica. El primero es instalar coladeras de
pretil en la azotea del edificio, segundo la instalación de bocas de tormenta conectadas mediante
una red pluvial ubicadas en la parte externa del edificio, ya que debido a la pendiente de proyecto
se provoca que los escurrimientos se acumulen en la zona, todos los escurrimientos se
mandaran a un depósito de regulación y este a su vez descargara a la red municipal de manera
regulada.

3.2.1 BAJANTES DE AGUAS PLUVIALES

El primer paso para el diseño pluvia es dividir la azotea en distintas áreas para así dirigir el
escurrimiento hacia los bajantes que se ubicarán en puntos específicos. Para el techado de la
unidad médica se proyectan varios parteaguas generando una descarga por cada área definida,

Una vez obtenido el área de cada superficie se calculan los gastos pluviales con base en la
ponderación del gasto pluvial calculado en la hidrología.

Figura 17. Delimitación de áreas para escurrimiento pluvial.

96
En los puntos más bajos proyectados en la azotea, se plantean instalar coladeras de azotea tipo
cúpula o de pretil donde se adapten mejor, conectadas a un tubo de descarga de PVC de 10cm
(4”) de diámetro.

Se delimitaron 13 áreas, de los cuales 10 son del edificio principal con sus respectivos bajantes,
estos en la mayoría de los casos se ubicarán por un costado de las columnas y descargando
hasta la parte baja de la losa de planta baja. y 3 son de las áreas de estacionamientos y jardines
que descargaran a bocas de tormenta ubicadas en zonas bajas,

En la siguiente tabla se presenta los escurrimientos ponderados en base a las áreas delimitadas
Tabla 16. Ponderación de los gastos pluviales de las áreas de proyecto.
SUPERFICIE GASTO
CLAVE 2
m lps
A01 140.17 6.70
A02 125.78 6.01
A03 185.04 8.84
A04 189.13 9.04
A05 221.13 10.57
A06 253.14 12.10
A07 13.16 0.63
A08 321.25 15.35
A09 588.14 28.10
A10 194.42 5.54
A11 38.74 1.85
A12 37.75 1.80
A13 38.74 1.85
A12 944.80 26.93
A13 808.47 23.04
TOTAL: 4099.86 158.35

Después se procede a calcular el diámetro calculado para conducir el gasto asignado a cada
área del edificio, en la siguiente tabla se presenta el cálculo de los bajantes y el diámetro
propuesto con base en diámetros comerciales.
Tabla 17. Cálculo del diámetro comercial para los bajantes.
CÁLCULO HIDRÁULICO DE BAJANTE DE AGUAS PLUVIALES
AREA DE GASTO DIÁMETRO (mm)
CLAVE 2
CAPTACIÓN (M ) lps CALCULADO PROPUESTO
BAP01 140.17 6.70 115.07 100
BAP02 125.78 6.01 110.20 100
BAP03 185.04 8.84 128.60 100
BAP04 189.13 9.04 129.73 100
BAP05 221.13 10.57 138.10 100
BAP06 266.30 12.72 148.76 150
BAP07 13.16 0.63 44.68 50
BAP08 321.25 15.35 160.35 150
BAP09 588.14 28.10 204.23 150
BAP10 115.23 5.51 106.40 150
2152.17 102.83

97
3.2.2 CÁLCULO Y DIMENSIONAMIENTO DE LA RED PLUVIAL INTERNA

Para los cálculos hidráulicos de tuberías existe gran diversidad de fórmulas, sin embargo en este
proyecto se aplicarán las fórmulas de Manning que por lo general se ha usado para el cálculo de
canales ya que son fáciles y con mayor grado de exactitud, esto último es debido a que como
condición indispensable los sistemas de tuberías sanitarios deben de trabajar como canales
abiertos a la atmosfera y en el caso de los sistemas de aguas pluviales en específico las tuberías
deberán ser diseñadas para conducir el 100% del volumen de la tubería, esto se encuentra
fundamentado en las normas del Instituto Mexicano del Seguro Social en su capítulo 11
“Eliminación de Aguas pluviales” en su sección 11.10.5 TIRANTE MÁXIMO.

Considerando tanto la pendiente natural, así como la pendiente propuesta para la construcción
de la unidad médica, el flujo escurriría en la azotea hasta los bajantes, por lo que se propone la
construcción de una red pluvial para proteger al edificio de probables encharcamientos que se
generen por efectos de las lluvias. En la parte trasera se proponen la construcción de bocas de
tormentas para captar el escurrimiento que pudiera ingresar por las rampas al estacionamiento
y con base a una red de tubería de PVC sanitario de norma de diferentes diámetros, donde se
conduce el flujo hacia el deposito de regulación que a su vez descarga a la res municipal. Ubicada
en la calle aledaña al edificio. En la siguiente figura se presenta un esquema isométrico de la red
pluvial.

Figura 18. Esquema isométrico de la red pluvial.

98
Para le diseño de la red pluvial se utilizarán las propiedades hidráulicas con las que cuentan las
tuberías de PVC. Las condiciones que debe de cumplir la red para su correcto funcionamiento
es que la velocidad mínima no sea menor a 0.60 m/s, esto con la finalidad de evitar sedimentos
en la tubería. Además, la velocidad máxima no debe ser mayor a 5.00 m/s para evitar el desgaste
interno del tubo. En la siguiente tabla se presenta el cálculo hidráulico de la red pluvial donde se
comprueba en cada tramo tenga la capacidad de conducir el gasto pluvial, y que cumpla con las
velocidades mínimas y máximas permitidas.

99
Tabla 18. Cálculo de la red pluvial.

CÁLCULO HIDRÁULICO DE RED PLUVIAL INTERNA PARA TORM ENTAS CON Tr 10 AÑOS

TUBERIA FUNCIONAMEINTO HIDRÁULICO


ÁREA DE GASTO DE
LONGITUD TIPO DE PENDIENTE A TUBO LLENO A GASTO MAX. EXT.
TRAMO CAPTACIÓN DISEÑO DIÁMETRO
m 2 DRENAJE millar MATERIAL GASTO VELOCIDAD VELOCIDAD TIR. EFECT.
m lps cm
lps m/s m/s cm
RAMAL 1 (Bajantes 10 y 05)
TRAMO 1 13.80 38.74 1.85 Interior 5 15 P 15.55 0.880 0.62 3.772
TRAMO 2 14.08 37.75 1.80 Interior 5 15 P 15.55 0.880 0.61 3.721
TRAMO 3 0.98 38.74 1.85 Interior 5 15 P 15.55 0.880 0.62 3.772
TRAMO 4 1.52 115.23 5.51 Interior 3 15 P 12.05 0.682 0.69 7.676
TRAMO 5 1.12 115.23 5.51 Interior 3 15 P 12.05 0.682 0.69 7.676
TRAMO 6 15.32 221.13 10.57 Interior 3 15 P 12.05 0.682 0.77 10.829
TRAMO 7 0.41 336.36 16.07 Interior 2 20 P 21.19 0.674 0.75 13.375
RAMAL 2 (Bajantes 08)
TRAMO 8 40.92 321.25 15.35 Interior 2 20 P 21.19 0.674 0.74 13.054
RAMAL 3 (Bajantes 09)
TRAMO 9 44.68 588.14 28.10 Interior 4 20 P 29.96 0.954 1.08 14.961
RAMAL 4 (Bajantes 04, 06 y 07)
TRAMO 10 21.90 266.30 12.72 Interior 4 15 P 13.91 0.787 0.89 11.072
TRAMO 11 15.23 189.13 9.04 Interior 2 15 P 9.84 0.557 0.63 11.098
TRAMO 12 5.13 455.44 21.76 Interior 3 20 P 25.95 0.826 0.93 14.103
RAMAL 5 (Bajante 01, 02 y 03)
TRAMO 13 14.65 125.78 6.01 Interior 3 15 P 12.05 0.682 0.70 8.039
TRAMO 14 2.30 140.17 6.70 Interior 3 15 P 12.05 0.682 0.72 8.512
TRAMO 15 5.97 265.94 12.71 Interior 4 15 P 13.91 0.787 0.89 11.064
TRAMO 16 0.62 185.04 8.84 Interior 2 15 P 9.84 0.557 0.63 10.970
TRAMO 17 1.59 450.98 21.55 Interior 3 20 P 25.95 0.826 0.93 14.030
RAMAL 6 (Boca de tormenta sótano)
TRAMO 18 0.89 194.42 5.54 Exterior 3 15 P 12.05 0.682 0.69 7.702

100
3.2.3 CÁLCULO Y DIMENSIONAMIENTO DE BOCAS DE TORMENTA

La boca de tormentas propuesta será construida con base en elementos estructurales de


concreto y cubiertas por una rejilla de acero. Las bocas de tormenta se propones de un ancho
de 0.50 m y de 5.35 m de largo que se ubicara en el acceso al estacionamiento del sótano que
tendrán la función de captar los escurrimientos que fluyan por las rampas de acceso a este, en
la

Tabla 19 se presentan el cálculo y dimensiones de la boca de tormenta, así como la profundidad


y diámetros de descarga propuestos.

Figura 19. Bocas de tormenta.

101
Figura 20. Detalle de rejilla.

Tabla 19. Bocas de Tormentas.

CÁLCULO DE LA CAPACIDAD DE CAPTACIÓN DE LAS BOCAS DE TORMENTA

Periodo de retorno para diseño (años) 10.00


Gasto máximo calculado Sótano (m3/s) 0.006
Superficie total de cuenca Sótano (m2) 194.42

Boca de Área de aport. Gasto pon. Dimensiones (m) Área eficiente Tirante sobre Gasto captado
% Ponderado Cr Cd
Tormenta (m2) (m3/s) Ancho Longitud (m2) vialidad (m) (m3/s)
BT-01 194.42 100.00% 0.00554 0.50 0.60 0.5 5.35 2.06 0.010 0.274

Tabla 20. Cálculo de tubería de descarga de boca de tormenta.


Elevación (msnm)
Diámetro Rasante BT Arrastre BT Profundidad Longitud Pendiente Gasto máximo
Material Rugosidad
(m) (msnm) (msnm) (m) Arrastre tubo Descarga tubo (m) (%) (m3/s)

0.15 -3.40 -4.45 1.05 -4.45 -4.45 0.89 0.30% PVC 0.009 0.0120

La descarga será con un tubo de PVC de diámetro de 150 mm, esta descargara a un cárcamo
de bombeo ubicado a un costado de la boca de tormenta, y de este se bombera al depósito, esto
debido a que el depósito se ubica por arriba del nivel de descarga y es imposible mandarlo por
gravedad hacia este.
Tabla 21. Dimensionamiento y selección de bomba pluvial.

102
Carga total

Carga total: 7.24 m


Carga estática: 4.45 m
Pérdidas por fricción: 2.49 m
Carga de velocidad: 0.30 m

Carga estática
Fondo del cárcamo: -5.40 m
Punto de descarga: -0.95 m
Carga estática: 4.45 m

Nivel Terreno -3.40 m


Arrastre llegada a cárcamo: -4.45 m
Profundidad total cárcamo: 2.00
Perdidas de carga
Pérdidas por fricción: 2.486
Coeficiente H-W PVC: 140
Longitud tubería de descarga: 11.489
Longitud con fricción: 16.53 m
Diámetro: 0.05 m 50.80 mm
Caudal: 0.0055 m³/s 332.50 LPM
5.54 l/s

Pérdidas por accesorios: 5.04


Codo 90° PVC: 3
Longitud equivalente: 1.68 m

El cárcamo de bombeo tendrá unas dimensiones de 1.00 m de ancho x 1.50 m de largo y 2.00
m de profundidad, el ancho de los muros y de losa se deberán de calcular estructuralmente
para soportar el paso de vehículos. La tubería de descarga de la bomba será de PVC hidráulico
de 3”, diámetro igual al de la descarga de la bomba y será conducida hasta la parte alta del
depósito de regulación. En la siguiente tabla se presenta el cálculo del cárcamo donde se verifica
que el volumen asegura que no exista un desbordamiento con el gasto de diseño considerado.
Tabla 22. Tránsito de cárcamo de bombeo en estacionamiento del sótano.

103
TRÁNSITO DEL CARCAMO DE BOMBEO
Datos del Tránsito de carcamo de bombeo en estacionamiento de sotano
DATOS GEOMÉTRICOS DEL DEPÓSITO DATOS HIDRÁULICOS
Altura Total: 2.00 m Qmáx ingreso: 5.54 l/s
Tirante libre: 0.65 m Qmáx breña: 1.77 l/s
Largo: 1.50 m Qmáx desfogue bomba: 5.50 l/s
Ancho: 1.00 m Tirante máx calculado: 1.35 m
Área del depósito: 1.50 2
m
3
Volumen Total: 2.02 m
Altura del desfogue: 2.00 m

Tirante Carga en Volumen


Tiempo Gasto breña Gasto entrada Gasto desfogue Tirante Real
teórico Desfogue almacenado
(min) (l/s) (l/s) (l/s) (m) 3
(m) (m) (m )
0 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1 0.03 0.09 0.00 0.00 0.00 0.00 0.00
2 0.06 0.18 0.01 0.00 0.00 0.01 0.01
3 0.09 0.28 0.02 0.00 0.00 0.02 0.02
4 0.12 0.37 0.03 0.00 0.00 0.03 0.04
5 0.15 0.46 0.05 0.00 0.00 0.05 0.07
6 0.18 0.55 0.07 0.00 0.00 0.07 0.10
7 0.21 0.65 0.09 0.00 0.00 0.09 0.14
8 0.24 0.74 0.12 0.00 0.00 0.12 0.18
9 0.27 0.83 0.15 0.00 0.00 0.15 0.22
10 0.30 0.92 0.18 0.00 0.00 0.18 0.28
11 0.33 1.02 0.22 0.00 0.00 0.22 0.34
12 0.35 1.11 0.27 0.00 0.00 0.27 0.40
13 0.38 1.20 0.31 0.00 0.00 0.31 0.47
14 0.41 1.29 0.36 0.00 0.00 0.36 0.54
15 0.44 1.39 0.42 0.00 0.00 0.42 0.62
16 0.47 1.48 0.47 0.00 0.00 0.47 0.71
17 0.50 1.57 0.53 0.00 0.00 0.53 0.80
18 0.53 1.66 0.60 0.00 0.00 0.60 0.90
19 0.56 1.75 0.67 0.00 0.00 0.67 1.00
20 0.59 1.85 0.74 0.00 0.00 0.74 1.11
21 0.62 1.94 0.81 0.00 0.00 0.81 1.22
22 0.65 2.03 0.89 0.00 0.00 0.89 1.34
23 0.68 2.12 0.98 0.00 0.00 0.98 1.47
24 0.71 2.22 1.06 0.00 0.00 1.06 1.60
25 0.74 2.31 1.15 0.00 0.00 1.15 1.73
26 0.77 2.40 1.25 0.00 0.00 1.25 1.87
27 0.80 2.49 1.35 0.00 0.00 1.35 2.02
28 0.83 2.59 1.45 0.00 5.50 1.34 2.01
29 0.86 2.68 1.44 0.00 5.50 1.22 1.84
30 0.89 2.77 1.33 0.00 5.50 1.11 1.67
40 1.18 3.69 0.43 0.00 5.50 0.21 0.31
50 1.48 4.62 -0.11 0.00 5.50 -0.33 -0.50
60 1.77 5.54 -0.28 0.00 5.50 -0.50 -0.75
70 1.48 4.62 -0.45 0.00 5.50 -0.67 -1.00
80 1.18 3.69 -0.99 0.00 5.50 -1.21 -1.81
90 0.89 2.77 -1.89 0.00 5.50 -2.11 -3.17
100 0.59 1.85 -3.17 0.00 5.50 -3.39 -5.08
110 0.30 0.92 -4.81 0.00 5.50 -5.03 -7.55
120 0.00 0.00 -6.83 0.00 5.50 -7.05 -10.58
Total 5.50 1.35 2.02

Tirante máximo (y): 1.35 m 38.10 mm


ᴓ Desfogue:
Altura de tanque: 2.00 m 1.50 in.
Volúmen a regular mínimo: 3 3
13.56 m Q desfogue 0.33 m /min
Volúmen a regular propuesto: 2.02 m
3 propuesto: 5.50 l/s
3
. Capacidad de tanque: 3.00 m Qm áx breña: 1.77 l/s

104
Figura 21. Hidrograma de ingreso y salidas del cárcamo de bombeo.

Figura 22. Tirante máximo del cárcamo de bombeo.

105
3.2.4 CÁLCULO Y DIMENSIONAMIENTO DE DEPÓSITO DE REGULACIÓN

Para el dimensionamiento del tanque de regulación o alguna estructura hidráulica de


almacenamiento, se compararon los gastos generados en estado de breña y en estado de
proyecto.

El gasto generado en estado en breña es de 4.91 l/s, mientras que el gasto calculado en estado
de proyecto es de 23.30 l/s. En la siguiente imagen se ilustran los hidrogramas en estado natural
o de breña y de proyecto.

Para el dimensionamiento de la obra hidráulica de detención se consideró la diferencia de los


dos gastos anteriores. Se obtuvo que el volumen a regular deberá ser de 83.88 m3 para una
duración de tormenta de 120 minutos.

Se propone un tanque de retención de 7.15 m de largo y 6.00 m de ancho. Deberá tener una
altura de 2.60 m para contener un tirante de 1.95 m y poder retener un volumen 111.54 m3. Cabe
mencionar que se considera una descarga del tanque a través de un sistema de bombeo donde
se deberá considerar la altura y el caudal de desfogue de 4.90 l/s.En la siguiente tabla se
presenta el cálculo de tránsito de dicho tanque.
Tabla 23. Tránsito de depósito de regulación.
TRÁNSITO DEL TANQUE DE DETENCIÓN
Datos del Tránsito de Depósito

DATOS GEOMÉTRICOS DEL DEPÓSITO DATOS HIDRÁULICOS


Altura Total: 2.60 m Qmáx ingreso: 23.30 l/s
Tirante libre: 0.64 m Qmáx breña: 4.91 l/s
Largo: 7.15 m Qmáx desfogue bomba: 4.90 l/s
Ancho: 6.00 m Tirante máx calculado: 1.96 m
2
Área del depósito : 42.90 m
3
Volumen Total: 83.88 m
Altura del desfogue: 3.50 m

Tirante Carga en Volumen


Tiempo Gasto breña Gasto entrada Gasto desfogue Tirante Real
teórico Desfogue almacenado
(min) (l/s) (l/s) (l/s) (m) 3
(m) (m) (m )
0 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1 0.08 0.39 0.00 0.00 0.00 0.00 0.01
2 0.16 0.78 0.00 0.00 0.00 0.00 0.05
3 0.25 1.17 0.00 0.00 0.00 0.00 0.10
4 0.33 1.55 0.00 0.00 0.00 0.00 0.19
5 0.41 1.94 0.01 0.00 0.00 0.01 0.29
6 0.49 2.33 0.01 0.00 0.00 0.01 0.42
7 0.57 2.72 0.01 0.00 0.00 0.01 0.57
8 0.65 3.11 0.02 0.00 0.00 0.02 0.75
9 0.74 3.50 0.02 0.00 0.00 0.02 0.94
10 0.82 3.88 0.03 0.00 0.00 0.03 1.17
11 0.90 4.27 0.03 0.00 0.00 0.03 1.41
12 0.98 4.66 0.03 0.00 0.00 0.04 1.68
13 1.06 5.05 0.04 0.00 0.00 0.05 1.97
14 1.14 5.44 0.05 0.00 0.00 0.05 2.28

106
Tirante Carga en Volumen
Tiempo Gasto breña Gasto entrada Gasto desfogue Tirante Real
teórico Desfogue almacenado
(min) (l/s) (l/s) (l/s) (m) 3
(m) (m) (m )
15 1.23 5.83 0.05 0.00 0.00 0.06 2.62
16 1.31 6.21 0.06 0.00 0.00 0.07 2.98
17 1.39 6.60 0.07 0.00 0.00 0.08 3.37
18 1.47 6.99 0.08 0.00 0.00 0.09 3.77
19 1.55 7.38 0.09 0.00 0.00 0.10 4.21
20 1.64 7.77 0.10 0.00 0.00 0.11 4.66
21 1.72 8.16 0.11 0.00 0.00 0.12 5.14
22 1.80 8.54 0.12 0.00 0.00 0.13 5.64
23 1.88 8.93 0.13 0.00 0.00 0.14 6.16
24 1.96 9.32 0.14 0.00 0.00 0.16 6.71
25 2.04 9.71 0.16 0.00 0.00 0.17 7.28
26 2.13 10.10 0.17 0.00 0.00 0.18 7.88
27 2.21 10.49 0.18 0.00 0.00 0.20 8.49
28 2.29 10.87 0.20 0.00 0.00 0.21 9.13
29 2.37 11.26 0.21 0.00 0.00 0.23 9.80
30 2.45 11.65 0.23 0.00 0.00 0.24 10.49
40 3.27 15.53 0.41 0.00 0.00 0.43 18.64
50 4.09 19.42 0.65 0.00 0.00 0.68 29.13
60 4.91 23.30 0.95 0.00 0.00 0.98 41.94
70 4.09 19.42 1.25 0.00 0.00 1.28 54.76
80 3.27 15.53 1.50 0.00 0.00 1.52 65.25
90 2.45 11.65 1.69 0.00 0.00 1.71 73.40
100 1.64 7.77 1.84 0.00 0.00 1.85 79.23
110 0.82 3.88 1.92 0.00 0.00 1.93 82.72
120 0.00 0.00 1.96 0.00 4.90 1.95 83.73
130 0.00 0.00 1.90 0.00 4.90 1.88 80.79
140 0.00 0.00 1.83 0.00 4.90 1.81 77.85
150 0.00 0.00 1.76 0.00 4.90 1.75 74.91
160 0.00 0.00 1.69 0.00 4.90 1.68 71.97
170 0.00 0.00 1.62 0.00 4.90 1.61 69.03
180 0.00 0.00 1.55 0.00 4.90 1.54 66.09
190 0.00 0.00 1.49 0.00 4.90 1.47 63.15
200 0.00 0.00 1.42 0.00 4.90 1.40 60.21
210 0.00 0.00 1.35 0.00 4.90 1.33 57.27
220 0.00 0.00 1.28 0.00 4.90 1.27 54.33
230 0.00 0.00 1.21 0.00 4.90 1.20 51.39
240 0.00 0.00 1.14 0.00 4.90 1.13 48.45
250 0.00 0.00 1.07 0.00 4.90 1.06 45.51
260 0.00 0.00 1.01 0.00 4.90 0.99 42.57
270 0.00 0.00 0.94 0.00 4.90 0.92 39.63
280 0.00 0.00 0.87 0.00 4.90 0.86 36.69
290 0.00 0.00 0.80 0.00 4.90 0.79 33.75
300 0.00 0.00 0.73 0.00 4.90 0.72 30.81
310 0.00 0.00 0.66 0.00 4.90 0.65 27.87
320 0.00 0.00 0.59 0.00 4.90 0.58 24.93
330 0.00 0.00 0.53 0.00 4.90 0.51 21.99
340 0.00 0.00 0.46 0.00 4.90 0.44 19.05
350 0.00 0.00 0.39 0.00 4.90 0.38 16.11
360 0.00 0.00 0.32 0.00 4.90 0.31 13.17
370 0.00 0.00 0.25 0.00 4.90 0.24 10.23
380 0.00 0.00 0.18 0.00 4.90 0.17 7.29
390 0.00 0.00 0.12 0.00 4.90 0.10 4.35
Total 4.90 1.95 83.88
Tirante máximo (y): 1.95 m 76.20 mm
ᴓ Desfogue:
Altura de tanque: 2.60 m 3.00 in.
3 3
Volúmen a regular mínimo: 66.23 m Q desfogue 0.29 m /min
Volúmen a regular propuesto: 83.88 m 3 propuesto: 4.90 l/s
Capacidad de tanque: 111.54 m3 Qm áx breña: 4.91 l/s
107
Figura 23. Hidrograma de ingreso y salidas del depósito de regulación.

Figura 24. Tirante máximo del depósito de regulación.

108
4 PROYECTO DE INSTALACION DE PROTECCIÓN CONTRA INCENDIOS

4.1 OBJETIVO

El objetivo de la presente, es establecer los requerimientos técnicos y de diseño para las


instalaciones del sistema de protección contra incendios, los cuales cubrirán las demandas del
proyecto “UNIMEF IV - Los Olivos”

 Instalación de protección contra incendios. Sistema para la protección contra incendios,


por medio de una red hidráulica para servicio a Hidrantes y tomas siamesas.

 Instalación de Diésel. Almacenamiento, distribución a motor de combustión interna de


bomba de PCI

El sistema se diseñará, a partir de la información de proyecto arquitectónico.

4.2 ALCANCE

La presente memoria técnico descriptiva complementa y justifica los planos de proyecto de


instalación del sistema de protección contra incendio, comprobando y fundamentando los
criterios de diseño utilizados para su posterior construcción.

Las Instalaciones del sistema de protección contra incendio por construir son el conjunto de
tuberías en diferentes materiales y diámetros, accesorios y equipamiento.

A) Instalación de Protección Contra Incendio

Comprende el Diseño a partir de la Reserva Contra Incendio en Cisterna de Agua Potable, a


cada uno de los Gabinetes Contra incendio distribuidos en planta baja, primer nivel y Azotea,
redes, columnas generales de distribución y tomas siamesas, criterio de alimentación a
Gabinetes, Interconexión de equipos en Cuarto de Máquinas.

B) Instalación Diésel

Interconexión entre tanque y bomba de combustión interna de PCI.

109
4.3 INSTALACIÓN SISTEMA DE PROTECCIÓN CONTRA INCENDIOS

4.3.1 DESCRIPCIÓN DEL SISTEMA.

La instalación del sistema de protección contra incendios será alimentada por un equipo de
bombeo tipo paquete (bomba eléctrica, bomba de combustión interna y bomba jockey) el cual se
encuentra en el cuarto de máquinas, este equipo será alimentado por medio de la conexión
directa a la cisterna de agua potable, este servirá exclusivamente para el uso del sistema de
protección contra incendios.

Como parte de los trabajos de ingeniería del proyecto ejecutivo. Se plantea un sistema de
protección contra incendio, lo cual se adopta como medio de prevención para evitar daños
irreparables tanto en vidas humanas como pérdidas materiales y medioambientales.

Este Sistema comienza con el agua de reserva contra incendio, que se alojará en la Cisterna de
Agua Potable.

En este sistema la finalidad es alimentar los gabinetes contra incendio distribuidos en cada uno
de los niveles de manera que se logre el 100% de cobertura de la UNIMEF IV.

La línea Principal del sistema de Protección Contra Incendio saldrá del Cuarto de Máquinas que
se ubica en planta baja, para posteriormente conectarse al Loop principal de distribución, que irá
por lecho bajo de losa de sótano.

A partir del Loop Principal se derivarán columnas de alimentación para alimentar los gabinetes
ubicados en sótano, planta baja, primer nivel y azotea.

4.4 VOLUMEN DE ALMACENAMIENTO DE RESERVA CONTRA INCENDIO.

La determinación de volumen de reserva contra incendio para el almacén se realiza con base en
las NORMAS DE DISEÑO DE INGENIERIA DEL INSTITUTO MEXICANO DEL SEGURO
SOCIAL (IMSS), CAPITULO 7. PROTECCION CONTRA INCENDIO, que considera un
abastecimiento de 5 litros por metro cuadrado construido con una capacidad de almacenamiento,
mínima de 20, 000 litros (20 m3), se tiene un área de construcción de 6,675 m2 por lo cual se
requiere un volumen de almacenamiento de 33,500 litros (33.5 m3)

Se considerará un gasto de 2.82 l/s por cada hidrante, suponiendo en función del área construida
del edificio, el número de hidrantes en uso simultáneo de acuerdo con la siguiente tabla obtenida
de las normas de diseño de ingeniería del IMSS.

110
Figura 25. Selección de hidrantes simultáneos.

El número de hidrantes que se consideraran en uso simultaneo será de 3 atendiendo los criterios
de diseño del IMSS y las normas técnicas complementarias del distrito federal.

Según la norma oficial mexicana NOM-002-STPS-2010 condiciones de seguridad-prevención y


protección contra incendios en los centros de trabajo, se debe de mantener una presión mínima
de 7 kg/cm2 en toda la red.

4.5 REDES GENERALES DE ALIMENTACIÓN

La línea Principal del sistema de Protección Contra Incendio saldrá del Cuarto de Máquinas que
se ubica en planta baja, con un diámetro de 100 mm en material Fierro Negro Fierro. Negro
Ranurado C-10, para conectarse al Loop principal de distribución, que irá por lecho bajo de losa
de sótano. El diámetro de este Loop que suministra agua a todos los hidrantes, será de 100 mm,
en Material Fierro. Negro Ranurado C-10.

Se consideran tres tomas siamesas una por cada fachada principal, estás serán de 100 mm de
diámetro y se conectarán al Loop Principal.

4.6 ALIMENTACIÓN A HIDRANTES

La alimentación a los hidrantes se realizará con un diámetro de 50 mm, puesto que la Instalación
se realiza con material Fierro Negro Ranurado C-10, se deben considerar colillas con un extremo
Ranurado y el otro Roscado, el segundo será necesario para la conexión a la Válvula de Globo
Angular Roscada de 50X38 mm de diámetro.

EL Criterio General para alimentar hidrantes es: 1 hidrante, 50 mm de diámetro, 2 hidrantes 64


mm de diámetro, 3 hidrantes 75 mm de diámetro, 4 hidrantes 100 mm de diámetro.

Se colocará un tipo de hidrante contra incendio: de sobreponer.

Independientemente del tipo de Gabinete, cada uno será de medidas 60X70X18 (frente, alto,
fondo); con cuna, jaladera y resbalón, pintura electrostática automotriz color Rojo y deberán
contener lo siguiente:

111
 Manguera Contra Incendio marca Key modelo Eco-Flex de 38 mm (1 1 /2") de diámetro
por 30 m de largo, con conexiones en bronce rosca ipt,

 Chiflón de neblina en bronce 38mm (1 1 /2") de diámetro, rosca ipt,

 Válvula de globo angular de 50 mm (2") de diámetro hembra a 38 mm (1 1 /2") de diámetro


macho.

 Llave universal para ajustar coples en bronce.

112
4.7 CALCULO HIDRÁULICO DEL SISTEMA DE HIDRANTES.
Tabla 24. Cálculo de perdida de carga, tubería de succión e impulsión.
PERDIDA DE CARGA POR FRICCION EN TUBERIAS, CONEXIONES Y VALVULAS EN LA RED HIDRAULICA DE HIDRANTES
Diametro Fierro Negro Ranurado C-10 Tuberias Fierro Negro Ranurado C-10 Conexiones Fierro Negro Ranurado C-10 y Valvulas
Diametro del Diametro del
Gasto por Gasto Total Velocidad Carga
Tramo o Coeficiente Perdida de Coeficiente Perdida de Orificio Orificio
Crucero Hidrante Hidrante Propuesta Teorico Nominal Interno Velocidad Perdida de Disponible
Derivacion Longitud (m) de Carga Hf Nombre Cantidad de Perdidas Carga Total Calibrado teorico Calibrado
(l/s) (l/s) (m/s) (mm) (mm) (mm) (m/s) Carga Hs (mca) (mca)
Rugocidad (mca) Singulares Hf+Hs (mca) (mm) comercial (mm)

IMPULSION
TEE 3.0 3.00
CODO 90° 2.0 1.50
A- B 1 2.82 2.82 2.00 42.371 50 54.800 1.20 4.50 0.010 0.19 0.87 1.07 70 . 0 0 14. 0 0 15 . 9 (5 / 8")
VAL. CHECK 0.0 0.00
VAL. COMP. 0.0 0.30
TEE 1.0 3.70
CODO 90° 2.0 1.80
B- C 2 2.82 5.64 2.00 59.921 64 66.900 1.60 3.70 0.010 0.22 0.96 1.18 71. 0 7 13. 9 2 15 . 9 (5 / 8")
VAL. CHECK 0.0 0.00
VAL. COMP. 0.0 0.30
TEE 1.0 4.60
CODO 90° 3.0 2.10
C- D 3 2.82 8.46 2.00 73.388 75 82.800 1.57 3.60 0.010 0.16 1.37 1.53 72 . 2 5 13. 8 3 15 . 9 (5 / 8")
VAL. CHECK 0.0 0.00
VAL. COMP. 0.0 0.30
TEE 12.0 6.10
CODO 90° 7.0 3.00
D- E 4 0 8.46 2.00 73.388 100 108.200 0.92 90.00 0.010 0.93 4.38 5.31 73 . 7 7 N/ A N/ A
VAL. CHECK 1.0 6.70
VAL. COMP. 1.0 0.60

SUCCION
TEE 12.0 9.10
CODO 90° 7.0 4.30
E- F 5 0 8.46 2.00 73.388 150 154.080 0.45 15.00 0.010 0.02 1.57 1.59 79 . 0 9 N/ A N/ A
VAL. CHECK 1.0 9.30
VAL. COMP. 1.0 0.90
Total: 10.68

113
4.7.1 CARGA DINÁMICA TOTAL

Para la selección del equipo de bombeo es necesario calcular la carga dinámica total del sistema,
la cual se representa en la siguiente ecuación:

CDT  He  hp  hv  himp

Donde:

CDT = Carga dinámica total (m)

He = Carga estática (m)

hp = Carga de presión (10m)

hv = Carga de velocidad (m)

himp= Perdida de carga en la impulsión (m)

= 15 ( ) + 70 ( ) + 10.68 ( ) = 95.68( . . . )

Se tiene el punto de operación del equipo de bombeo para protección contra incendios (CDT,
Qb), con los cuales se puede ingresar a la curva característica del equipo que cumpla con las
características mecánicas e hidráulicas necesarias.

= 95.68( . . . )

Qb  8.46l / s   507.60(l / m)

65% = 62.19( . . . )

150%Qb  761.4(l / m)

114
4.7.2 CALCULO NPSH DISPONIBLE

= + − −

= 8.6( ) + 3.5( ) − 0.24( ) − 1.59( ) = 3.27( )

Hs= Presión estática del fluido (m.c.a.)

Ha= Altura de succión (m)

Hvp= Presión de vapor (m.c.a.)

Hf= Perdidas tubería de succión (m.c.a.)

4.7.3 REDUCTORES DE PRESION

Cuando se tenga una presión del lado de la manguera del hidrante mayor a 25.5 m.c.a., se
utilizará un dispositivo de orificio calibrado para reducir la presión y dejar pasar 2.82 l/s.

El diámetro se calcula con la siguiente formula:

= 36.155/( − 25.5)^0.25

Donde:

d= Diámetro de la placa orificio

c= carga en la válvula angular del gabinete

La placa orificio debe tener las siguientes características

 El diámetro exterior de la placa debe ser igual a la rosca de la válvula angular

 El espesor será de 2.5 mm

 El material de construcción será de acero inoxidable (AISI-316)

115
Tabla 25. Cálculo de diámetro de la placa orificio
Diametro del Diametro del
Gasto por Gasto Total Carga
Tramo o Orificio Orificio
Crucero Hidrante Hidrante Disponible
Derivacion Calibrado teorico Calibrado
(l/s) (l/s) (mca)
(mm) comercial (mm)
A- B 1 2.82 2.82 70.00 14 . 0 0 15 . 9 (5 / 8 ")

B- C 2 2.82 5.64 7 1. 0 7 13 . 9 2 15 . 9 (5 / 8 ")

C- D 3 2.82 8.46 72.25 13 . 8 3 15 . 9 (5 / 8 ")

Nota: la placa orificio de 5/8" de diámetro deberá de instalarse en todos los hidrantes instalados
en sótano, planta baja, primer nivel y azotea de la UNIMEF IV, los Olivos.

116
4.7.4 CURVA DE RENDIMIENTO BOMBA ELECTRICA

Figura 26. Curva de rendimiento de bomba eléctrica Marca Barmesa, Modelo IA2EH.

Por lo tanto, se tiene una bomba centrifuga marca Barmesa, modelo IA2EH, diámetro de impulsor
9 1/4”, 480 Volts a 3500 RPM, con una potencia de 30 HP.

117
4.7.5 CURVA DE RENDIMIENTO BOMBA COMBUSTION INTERNA

Figura 27. Curva de rendimiento de bomba de combustión interna, Marca Mejorada, Modelo 2P-61MDP.

Por lo tanto, se tiene una bomba centrifuga marca Bombas mejorada, modelo 2P-61MDP,
diámetro de impulsor 10 1/8”, a 3050 RPM, con una potencia de 61 HP.

118
4.7.6 CURVA DE RENDIMIENTO BOMBA JOCKEY

Figura 28. Curva de rendimiento de bomba Jokeyc, Marca Altamira serie TX, Modelo T0.6 X20-17.

Por lo tanto, se tiene una bomba multietapas vertical marca Altamira serie TX, modelo T0.6 X20-
17 (2 HP) 220/440 Volts a 3500 RPM, con una potencia de 2 HP.

119
4.7.7 MATERIALES

La Instalación (tubería y conexiones) de protección Contra incendio en cuarto de bombas será


de acero negro roscado y soldable ced 40 en cuarto de bombas y acero Negro Ranurado C-10
en la red de hidrantes.

Las válvulas Check colocadas en el ramal de suministro de agua por tomas Siamesas, serán del
tipo Bridadas.

Las válvulas en Cuarto de Máquinas, y loop principal deberán ser del tipo Compuerta fabricada
en hierro fundido, clase 125#, extremos bridados según ANSI B16.1 y vástago ascendente.

Las tomas siamesas serán fabricadas en bronce, con acabado cromado y granallado, con
entrada hembra de 100 mm de diámetro rosca IPT, con dos entradas hembra de 64 mm de
diámetro rosca NSHT, Incluye: Tapones, cadena y Placa con la Leyenda “Bomberos”.

4.7.8 SOPORTERÍA

Toda la Instalación de protección contra incendios debe estar debidamente soportada de manera
que se eviten deformaciones en la tubería.

Así mismo la Instalación de protección contra incendios debe estar debidamente señalizada.

4.7.9 PRUEBA DE HERMETICIDAD (PRESIÓN DE PRUEBA, FORMATO DE


REGISTRO).

Se deberá realizar prueba de hermeticidad de todo el sistema de Protección Contra Incendio.


Para el procedimiento de la prueba, se debe apegar a lo establecido en la NOM-001-CONAGUA-
2011.

Para este caso, la presión a la que se deberá probar el sistema es de 14 Kg/cm2. Durante 24 hrs.
El sistema se considera hermético, si después de haber realizado la prueba de presión
hidrostática no se detecta ninguna fuga y la presión de prueba al finalizar, sea mayor o igual al
95% de la presión inicial.

120
4.8 NORMAS Y REGLAMENTOS

Las siguientes normas y reglamentos son aplicadas para la realización del proyecto ejecutivo del
sistema contra incendio de la “UNIMEF IV, Los Olivos”.

 Reglamento de Construcciones del Distrito Federal.

 Normas Técnicas Complementaria para el Diseño y Ejecución de Obras e Instalaciones


Hidráulicas.

 Normas de Instalaciones Sanitarias, Hidráulicas y Especiales del IMSS

 Norma Oficial Mexicana NOM-002-STPS-2010 condiciones de seguridad-Prevención y


protección contra incendios en los centros de trabajo.

121