Está en la página 1de 3

4.

0 ELECTRICAL
4.4.6.6 Ramp Control unloading, a compressor is taken off
Another feature of the controller is line when the computer determines that
ramp control, which is the ability to the remaining compressors can control
vary load time of the machine from water temperature.
start. Often when the machine is started,
the water in the chilled water circuit is 4.4.6.8 Modmotor Setback Control
warm, and the unit will go to full load A computer contact and a resistor are
quickly. With ramp control, the user wired in parallel in the modmotor
can program the computer so that it control circuit. The contact is controller
loads at a predetermined rate. This is a controlled to open under light load
valuable tool, since it can help reduce conditions. This lowers liquid level
power consumption and demand slightly, preventing excessive liquid
charges. Two variables are used to level in the evaporator.
define the ramp profile: Ramp rate and
start point. Ramp rate defines the length 4.4.6.9 Evaporator Pressure Control
of time the unit takes to load from start This control function seeks to prevent a
point to full load. Start point is the low differential pressure alarm. It
percent of full load at which the ramp monitors the difference between
begins. The ramp rate setpoint can be condenser and evaporator pressure. If
set anywhere from 0.1 to 0.4, smaller this difference is less than 30 psig
values producing slower loading rates. [2.1BAR] for more than 60 seconds,
The ramp start setpoint can be set and evaporator pressure is above 75
anywhere between 10 and 50%. The psig [5.1BAR], the computer will open
compressor will load quickly to this a set of contacts in the modmotor
value and then follow the ramp slope circuit, causing valves to travel in the
from there. See Table 4.4.6.6 for ramp closed direction. This starves the
evaporator, which increases pressure
rates at various settings.
difference. When this difference
exceeds 30 psig [2.1BAR], modmotor
TABLE 4.4.6.6 Ramp Rates for Several control returns to normal.
Setpoints (In Minutes) CAUTION: Do not start compressor
manually more than once every 15
Ramp 1 Comp. 2 Comp. 3 Comp
minutes. Verify that chilled water flow
Rate Start Point Start Point Start Point
Setpoint Setpoint Setpoint switch is closed.
Setpoint 25% 50% 75% 25% 50% 75% 25% 50% 75%

0.1 25 17 8 58 50 42 91 83 75
4.4.6.10 Sump Heater Control
0.2 13 8 4 29 25 21 46 42 37 Each compressor is fitted with an oil
0.3 8 6 3 19 17 14 30 28 25 sump heater. The heater is energized at
0.4 6 4 2 15 12 10 23 21 19 all times when compressor is off and
de-energized when the compressor is
running.
4.4.6.7 Staging Control
Its purpose is to prevent refrigerant
On multiple-compressor machines, migration into the oil during shut down.
when the controller determines that a For this reason, it is essential that
compressor is fully loaded and heaters be energized for 24 hours
temperature is not being maintained, before starting a compressor.
another compressor is added. When

- 52 -
4.0 ELECTRICAL
4.4.6.11 Low Pressure Cut-off Failure is indicated on the alarm pilot
This function protects the unit from light. The low oil alarm will be
operating at abnormally low evaporator recorded by the controller.
refrigerant pressure. The controller will
shut down the compressor when cooler 4.4.6.15 High Oil Temperature
pressure falls below the low pressure Thermostat (12TAS)
setpoint and turn on the alarm pilot A thermostat is located in each
light. compressor which will open the
A low pressure alarm will be recorded compressor run circuit if oil
by the controller. Reset by pressing the temperature exceeds 203°F [95°C]. The
‘Reset Alarm’ on the controller. high oil temperature pilot light will
indicate an excessive oil temperature
Standard setpoint is 28 psig [1.9BAR]
and a No-Run error will be recorded by
for water-cooled systems.
the computer. Reset is activated by
pressing the ‘Reset Alarm’ button on
4.4.6.12 Evaporator Freeze Shutoff
microcomputer.
If the leaving chilled water temperature
drops below the freeze setpoint, the
4.4.6.16 Overload Protector (M2OL)
controller will shut down the unit and
store the freeze alarm. After solving the
A solid state overload protects each
compressor by three phase current
problem, press ‘Reset Alarm’ on the
monitoring to prevent high current
controller to clear the alarm.
draw. The trip setting is factory set and
is reset by pressing button on overload
4.4.6.13 High Pressure Cut-off
after correcting problem. The ‘Reset
This function protects the compressor Alarm’ button on controller must also
from operating at abnormally high be pressed to clear the alarm. A no-run
discharge refrigerant pressures. The error is stored in the controller.
controller will shut down the
compressor when condenser pressure 4.4.6.17 Phase Control Relay (PCR)
reaches the high pressure set point, and
The PCR protects the unit from the
turn on the alarm indicator lamp on the
following electric supply malfunctions:
control box. The high discharge Undervoltage, phase reversal and single
pressure alarm will be recorded by the phasing. If the PCR trips, a control
controller. Reset by pressing the ‘Reset relay (lCR) will de-energize and open
Alarm’ button on the micro-computer. the control circuit. A green LED
Setpoint for water-cooled system is 164 indicates presence of power supply.
psig [11.3BAR]. The yellow LED indicates a good
voltage supply. The power loss setpoint
4.4.6.14 Standard Oil Level Sensor (LS) is factory set to AUTO to allow
An standard oil level sensor is located automatic start after PCR failure.
in each compressor. If low oil Compressor will not start for 15
indication (digital input is OFF) persists minutes after failure. To select manual
for 60 seconds during compressor reset, set power loss setpoint to
operation, the controller will then shut MANUAL. In this case, a power loss
down the compressor. The status of the alarm will be stored by the
oil level sensor can be seen on the microcomputer and ‘Reset Alarm’ must
computer display. be pressed to start.

- 53
30 -
4.0 ELECTRICAL
4.4.6.18 Sensor Alarm etc.). All calibration on sensors shall be done
If the controller measures an analog in this step.
value (temperature, pressure.) that is far 2. Load the compressor to full load. If the amps
beyond normal operating values, the reading do not match with calculated FLA
associated compressors are shutdown. value within 2-3A, do this calculation: Amps
The controller then stores the alarm – FLA
code corresponding to the sensor alarm. For example, FLA = 150A, however the max
A sensor alarm indicates a problem in amps at full load is 130A, so, do the
the analog measurement system. calculation
130 – 150 = -20
4.4.6.19 No-Stop Alarm 3. Key in this value into “Max Percent Cal” of
If the controller turns off a compressor, the compressor in “COMPRESSOR FLA
but the compressor digital input does CALIBRATION” mask under technician key.
not turn off, a No-Stop alarm is 4. Therefore, the value of FLA will change.
generated. The controller will turn off Verify that amps and FLA now match closely.
the control power relay which disables 5. Manually unload the compressor all the way.
all compressor control circuits and will 6. Locate the minimum percentage of capacity
turn on the alarm light. This alarm for the compressor. If this value is 25% ± 3%,
indicates a wiring or hardware error. no change required. Else, enter this value into
“Min Percent Cal” in the same mask. The
4.4.6.20 Low Differential Pressure default value of “Min Percent Cal” is 25%.
Alarm
For example, the minimum percentage of
For proper lubrication, a compressor capacity for the compressor is 32.2%,
requires a 30 psig [2.1BAR] differential therefore, enter 32.2 at “Min Percent Cal”.
pressure between condenser and
7. Repeat this procedure for each compressor.
evaporator pressures. If the differential
pressure is less than 30 psig [2.1BAR]
for 3 minutes while a compressor is
operating, all compressors will be shut 4.6 Master/Slave Control
down. The controller will store the low
differential pressure alarm code and
Sequence
turn on the alarm light. The ‘Reset The optional master/slave control sequence is
Alarm’ key must be pressed to clear the used to sequence multiple chillers in one
alarm. installation according to the building load demand.
It also controls the dedicated chilled water pump
or motorized valve.
Vision2020i Controller offers this feature with
4.5 CALIBRATION OF minimized field wiring cost compare to
SCREW COMPRESSOR conventional method that involves lots of
CAPACITY AMPS AT hardware cost. It is carried out this control
FULL LOAD & MINIMUM function via the advanced DBLAN
LOAD PERCENTAGE communication bus to implement the network
management for multiple chillers lead/lag
1. Check calibration of all sensors (pressure communication, sequencing and monitoring.
sensors, current transducers, temp sensors and

- 54 -

También podría gustarte