Está en la página 1de 6

Totally Integrated

Automation Portal

Main [OB1]
Main Propiedades
General
Nombre Main Número 1 Tipo OB
Idioma KOP Numeración Automático
Información
Título "Main Program Sweep Autor Comentario
(Cycle)"
Familia Versión 0.1 ID personali‐
zado

Nombre Tipo de datos Valor predet. Comentario


Input
Initial_Call Bool Initial call of this OB
Remanence Bool =True, if remanent data are available
Temp
Temp_1 Real
Temp_2 Bool
Constant

Segmento 1: ARRANQUE DEL SISTEMA

%I0.0 %I0.1 %I0.2 %M1.3 %M0.0


"START" "STOP" "P_EMERG" "FIN_MIX2" "MEM_ON"

%M0.0
"MEM_ON"

Segmento 2: MEDICION CAUDAL PRODUCTO B

%M0.0 NORM_X SCALE_X


"MEM_ON" Int to Real Real to Real
EN ENO EN ENO
0 MIN %MD2 0.0 MIN %MD6
%IW64 OUT "MEM_Q" %MD2 OUT "CAUDAL_B"
"S_PROD_B" VALUE "MEM_Q" VALUE
27648 MAX 9999.0 MAX

Segmento 3: MEDICION VOLUMEN AGUA


Totally Integrated
Automation Portal

%M0.0 NORM_X SCALE_X


"MEM_ON" Int to Real Real to Real
EN ENO EN ENO
0 MIN %MD18 0.0 MIN %MD22
%IW112 OUT "Norm_agua" %MD18 OUT "Niv_agua"
"S_Nivel_agua" VALUE "Norm_agua" VALUE
27648 MAX 1.6 MAX

Segmento 4: MEDICION TEMPERATURA

%M0.0 NORM_X SCALE_X


"MEM_ON" Int to Real Real to Real
EN ENO EN ENO
0 MIN %MD10 -70.0 MIN %MD14
%IW96 OUT "MEM_TEMP" %MD10 OUT "TEMP_MIX"
"S_TEMP" VALUE "MEM_TEMP" VALUE
27648 MAX 500.0 MAX

Segmento 5: MEDICION DE CAUDAL DE SALIDA

%M0.0 NORM_X SCALE_X


"MEM_ON" Int to Real Real to Real
EN ENO EN ENO
0 MIN %MD26 0.0 MIN %MD30
OUT "NORM_Q_OUT" %MD26 OUT "CAUDAL_SALIDA"
%IW114
"S_Caudal_ "NORM_Q_OUT" VALUE
salida" VALUE 100.0 MAX
27648 MAX

Segmento 6: DOSIFICACION AGUA

%MD22
%M0.0 %M0.1 %Q0.0
"MEM_ON" "Niv_agua" "AGUA_OK" "V3_AGUA"
<=
Real
0.12
%M0.1
"AGUA_OK"
S

Segmento 7: ARRANQUE MOTOR AGITADOR BAJA VELOCIDAD


Totally Integrated
Automation Portal

%M0.0 %M0.1 %M0.6 %M0.3 %Q0.6 %Q0.5


"MEM_ON" "AGUA_OK" "FIN_MIX1" "CICLO 1_H" "S_AH_MIX" "S_H_MIX"

%M0.3 %M0.4 %M0.5 %Q0.5 %Q0.6


"CICLO 1_H" "PARO 1" "CICLO 2_AH" "S_H_MIX" "S_AH_MIX"

%Q0.7
"VEL_BAJA_MIX"

%M0.2 %Q0.1
"PRODA_OK" "V1_A"

%Q0.4
"VARIAD_VALV_R"

Segmento 8: CONTEO PULSOS PRODUCTO A

%DB1
"IEC_Counter_
0_DB_PROD A"

%M0.0 %M0.1 %M0.2 %I0.3 CTU %M0.2


"MEM_ON" "AGUA_OK" "PRODA_OK" "S_REV_A" Int "PRODA_OK"
CU Q S
%M0.2 CV 0
"PRODA_OK" R
1366 PV

Segmento 9: 1er CICLO MEZCLA (CICLOS DE 4 min SH, para 1 MIN, 4 MIN S AH, PARA 1 MIN)

%DB2
"IEC_Timer_0_
DB_MIX_SH"

%M0.0 %M0.2 %M0.6 %M0.5 TON %M0.3


"MEM_ON" "PRODA_OK" "FIN_MIX1" "CICLO 2_AH" Time "CICLO 1_H"
IN Q
T#4M PT ET T#0ms

%DB3
"IEC_Timer_0_
DB_PARO 1"

%M0.3 TON %M0.4


"CICLO 1_H" Time "PARO 1"
IN Q
T#1M PT ET T#0ms

%DB8
"IEC_Timer_0_
DB_MIX_SAH"

%M0.4 TON %M0.5


"PARO 1" Time "CICLO 2_AH"
IN Q
T#5M PT ET T#0ms
Totally Integrated
Automation Portal

Segmento 10: CONTADOR CICLOS MEZCLA BAJA VELOCIDAD

%DB16
"IEC_Counter_
0_DB_CICLO
MIX1_BV"

%M0.0 %M0.2 %M0.6 %M0.5 CTU %M0.6


"MEM_ON" "PRODA_OK" "FIN_MIX1" "CICLO 2_AH" Int "FIN_MIX1"
CU Q S
%M0.6 CV 0
"FIN_MIX1" R
6 PV

Segmento 11: DOSIFICACION PRODUCTO B

"IEC_Timer_0_
DB_1_t_
%M0.0 %M0.6 dosificacion_B". %M0.7 %Q0.2
"MEM_ON" "FIN_MIX1" Q "PROD_B_OK" "V2_B"

%M0.7
"PROD_B_OK"
S

%DB18
"IEC_Timer_0_
DB_1_t_
dosificacion_B"
%MD6 TON
"CAUDAL_B" Time
<=
Real IN Q
t#3M PT ET T#0ms
1.6

Segmento 12: ARRANQUE MOTOR AGITADOR ALTA VELOCIDAD


Totally Integrated
Automation Portal

Segmento 12: ARRANQUE MOTOR AGITADOR ALTA VELOCIDAD

%M0.0 %M0.6 %M0.7 %M1.3 %M1.0 %Q0.6


"MEM_ON" "FIN_MIX1" "PROD_B_OK" "FIN_MIX2" "MIX2_CICLO1_H" "S_AH_MIX"
1

%M0.3 %M1.1
"CICLO 1_H" "MIX2_PARO"
2

%Q1.0
"VEL_ALTA_MIX"

%Q0.5
"S_H_MIX"
1

%M1.2 %Q0.5 %Q0.6


"MIX2_CICLO_AH" "S_H_MIX" "S_AH_MIX"
2

Segmento 13: 2do CICLO DE MEZCLA

%DB9
"IEC_Timer_0_
DB_MIX2_SH_
A_VEL"

%M0.0 %M0.6 %M0.7 %M1.3 %M1.2 TON %M1.0


"MEM_ON" "FIN_MIX1" "PROD_B_OK" "FIN_MIX2" "MIX2_CICLO_AH" Time "MIX2_CICLO1_H"
IN Q
T#4M PT ET T#0ms

%DB11
"IEC_Timer_0_
DB_1_MIX2_
PARO"

%M1.0 TON %M1.1


"MIX2_CICLO1_H" Time "MIX2_PARO"
IN Q
T#1M PT ET T#0ms

%DB13
"IEC_Timer_0_
DB_1MIX2_
SAH_A_VEL"

%M1.1 TON %M1.2


"MIX2_PARO" Time "MIX2_CICLO_AH"
IN Q
T#5M PT ET T#0ms

Segmento 14: CONTADOR CICLOS ALTA VELOCIDAD


Totally Integrated
Automation Portal

%DB17
"IEC_Counter_
0_DB_CICLO_
MIX2_AV"

%M0.0 %M0.6 %M1.3 %M1.2 CTU %M1.3


"MEM_ON" "FIN_MIX1" "FIN_MIX2" "MIX2_CICLO_AH" Int "FIN_MIX2"
CU Q S
%M1.3 CV 0
"FIN_MIX2" R
6 PV

Segmento 15: TIEMPO DE VACIADO

%DB20
"IEC_Timer_
VACIADO"

%M0.0 %M1.3 TON


"MEM_ON" "FIN_MIX2" Time
IN Q
T#5M PT ET T#0ms

Segmento 16: FIN DE PROCESO

%M0.0 "IEC_Timer_ %M0.1


"MEM_ON" VACIADO".Q "AGUA_OK"
R

%M0.2
"PRODA_OK"
R

%M0.6
"FIN_MIX1"
R

%M0.7
"PROD_B_OK"
R

%M1.3
"FIN_MIX2"
R

También podría gustarte