Main
Nombre Tipo de datos Valor predet. Comentario
Input
Initial_Call Bool Initial call of this OB
Remanence Bool =True, if remanent data are available
Temp
Constant
Segmento 1:
%M0.0
"MODO_AUTO_
ON"
Segmento 2:
%M0.0
"MODO_AUTO_ NORM_X SCALE_X
ON" Int to Real Real to Real
EN ENO EN ENO
0 MIN %MD4 0.0 MIN %MD8
%IW64 OUT "TEMP_REAL" %MD4 OUT "TEMP_MON"
"TEMPERATURA" VALUE "TEMP_REAL" VALUE
27648 MAX 100.0 MAX
Segmento 3:
Totally Integrated
Automation Portal
%M0.0
"MODO_AUTO_ %MD8
%M0.1
ON" "TEMP_MON" "ALARMA_65"
>
Real
65.0
Segmento 4:
SI T>65 SE ACTIVA EL VENTILADOR
%M0.0
"MODO_AUTO_ %M0.1
ON" "ALARMA_65" MOVE
EN ENO
18432 IN %QW96
OUT1 "VENTILADOR"
Segmento 5:
SI T<65 SE REALIZA UN ESCALAMIENTO
Totally Integrated
Automation Portal
Segmento 5:
%M0.0
"MODO_AUTO_ %M0.1 NORM_X
ON" "ALARMA_65" Real to Real
EN ENO 1
0.0 MIN %MD12
%MD8 "SENSOR_
"TEMP_MON" VALUE OUT VENTILADOR"
100.0 MAX
%M0.0
"MODO_AUTO_ NORM_X
ON" Int to Real
EN ENO 2
0 MIN
%MD18
%QW96 "Ventilador_
"VENTILADOR" VALUE OUT Norm"
27648 MAX
SCALE_X
Real to Int
1 EN ENO 3
0 MIN %MW16
%MD12 "RPM_
"SENSOR_ OUT VENTILADOR"
VENTILADOR" VALUE
27648 MAX
SCALE_X
Real to Real
2 EN ENO
0.0 MIN
%MD22
%MD18 "RPM_
"Ventilador_ OUT Ventilador_Mon"
Norm" VALUE
1800.0 MAX
MOVE
3 EN ENO
%MW16 %QW96
"RPM_ OUT1 "VENTILADOR"
VENTILADOR" IN
Segmento 6:
%M0.2
"MODO_PRED_
ON"
Totally Integrated
Automation Portal
Segmento 7:
%M0.2
"MODO_PRED_ %M0.5
ON" "MP.PRED1_HMI" MOVE
EN ENO
15360 IN %QW96
OUT1 "VENTILADOR"
Segmento 8:
%M0.2
"MODO_PRED_ %I0.3
ON" "MP.PRED2" MOVE
EN ENO
18432 IN %QW96
%M0.6 OUT1 "VENTILADOR"
"MP.PRED2_HMI"
Segmento 9:
%M0.2
"MODO_PRED_ %I0.4
ON" "MP.PRED3" MOVE
EN ENO
10752 IN %QW96
%M0.7 OUT1 "VENTILADOR"
"MP.PRED3_HMI"
Segmento 10:
%M0.0
"MODO_AUTO_ %M0.1 %Q0.5
ON" "ALARMA_65" "REFIGERACION"
%M0.2
"MODO_PRED_ %M0.6
ON" "MP.PRED2_HMI"