1 Timer overview 7
4 Program logic 25
1 Timer overview
Operating water valve V 3 The bowl sludge space is partial emptied by actu-
T00 Partial ejection
opens ating the operating water valve V 3. (Option) X X X
Operating water valve V 3 The bowl sludge space is emptied by actuating the
T04 Total ejection
opens operating water valve V 3. X X X
Closing water impul- Operating water valve V 3 Timer for safety water to keep the bowl closed
T06
se opens during separation. X X X
After timer is expired, product After timer is expired, the standard alarms like
T07 Alarm delay
feed valve V 1 closes. PAL1/PAH1, TAL/TAH, PAH2 ect. will be initiated. X X X
T09 Waiting after filling Timer to stabilize the system after filling process. --- X X
T11 Alarm Bridging Alarms not activated. Timer to stabilize the process conditions! X X X
T14 Closing water interval Time interval between two closing water pulses. X X X
Circulation valve
T15
close
Circulation valve V 5 closes. Timer in which the circulation valve is closed! X --- ---
Circulation valve Circulation valve V 5 opens. Timer in which the circulation valve is opened!
T16
open WMS Sensor is activated. WMS Sensor Signal is checked. X --- ---
Active in
Timer Designation Action Description
-0136- -0196- -91-
program.
Water impulse by Operating water valve V 3 Timer for closing the bowl after separator is on
T19
start opens operating speed. X X X
T20 Separation Product feed valve V 1 opens Timer for adjusting the separating time. X X X
In case of pressure drop (SMS Timer in which a system pressure drop is eva-
Min separation time PT 2) during T21 , triggering of luated as an alarm.
T21
with SMS alarm "Minimum separating X --- ---
time during SMS" Timer starts together with timer 20.
Active in
Timer Designation Action Description
-0136- -0196- -91-
Bowl is filled in intervals controlled by T37 with
Filling water valve V 2 opens filling water to check whether the sludge space is
T36 SMS pressure check in intervals until SMS sensor filled with sludge. If the sludge space is not full, X --- ---
PT 2 is activated. the SMS sensor PT 2 must respond to pressure. If
pressure is not increasing, an ejection is triggered.
Timer to set the interval between two filling water
Filling water valve V 2 closes.
T37 SMS Waiting
SMS sensor PT 2 is activated.
pulses for sludge space monitoring! See also X --- ---
SMS pressure check, above.
WMS sensor not activated.
SMS sensor PT 2 not acti- Timer to flush the sensing line after the first pro-
WMS Sensor flush-
T38
ing
vated. gram start so that it is clean and excessive filling --- X ---
Water discharge valve V 6 water is discharged!
opens.
Separator off after After delay T 39, the separa- Timer delay for separator motor stop. Function
T39
idle run tor motor is switched off. must be preselected in the program. X X X
Timer to operate the sludge pump until the sludge
T40 CU-Sludge pump On Sludge pump activated.
tank is completely emptied. X X X
T41 CU-Sludge pump Off Sludge pump not activated. Time interval between two sludge pump starts. X X X
T42 Free
T43 Free
Circulation valve V 5 closes. Timer in which the function of the SMS sensor PT
Water discharge valve V 6 2 is tested. If T44 is elapsed without SMS Sensor
T44 SMS-Sensor-Check
closes. PT 2 Signal, Alarm "SMS sensor failure during X X ---
SMS sensor PT 2 is activated. WMS-SMS check" is triggered.
T45 Free
T46 Free
When SMS Sensor PT 2 is Capacity and machine type-dependent timer
activated while T 47 is run- which determines the increse of water in the lube
ning, the water discharge oil during WMS mode. The pressure increase is
T47 Min.SMS Time
valve V 6 is opened for 3 evaluated as a function of T 47 over several --- X ---
seconds and Counter 5 successive cycles which are defined via counter 5
counts the PT 2 signal. "SMS time interval water content"
Timer to fill filling water into the bowl. This timer
runs before timer T61 and T62. Timer is required
T60 Start Impulse Filling water valve V 2 opens.
for the automatic calculation of timers 01 and 02. X X ---
Timer is protected.
2.1
Separator-Type
Text Display Remarks OSE OSE OSE OSE OSE OSE
Full Text
(P = Setpoint; A = actual value) 5 10 20 40 80 120
Counter
C1 Flushing:
C01 Flushing Flushing counter 5 5 5 5 5 5
P: 5
A: 0
C2 Partial Ejection:
C02 Partial Ejection Partial ejection counter 5 5 5 5 5 5
(Option) P: 5
A: 0
C3 SMS Filling:
C03 SMS-Filling SMS fillng counter 5 5 5 5 5 5
P: 3
A: 0
C4 Sensor Check:
C04 Sensor-Check Sensor check counter 10 10 10 10 10 10
(Option) P: 10
A: 0
C5 Water content
Default settings Counter - Time records
Sludgep.-time
Time Record for Max. in 24 h 30 min
TR2 TR2 Sludgep. time sludgepump time operation 30 30 30 40 50 60
in last TR3 (24h) hours. Act. in 24 h 0 min (Act. in = actuel 24h)
Last. in 24 h 0 min (Last in = previous 24h)
Active in:
No. Designation: Status: Description:
-0136- -0196- -91-
2.3
Control Unit E40
Alarme Display Text Remarks Separator-Type
Full Text:
Control Unit:
Temperature- OSE
Monitoring DO MDO LO HFO
Separation Temperature 20 °C 40 °C 95 °C 98 °C
TAH OIL FEED
Temp. > max
TAH OIL FEED Alarm for an increase of the
Separation-Stop 30 °C 50 °C 105 °C 105 °C
Temp. > max oil temperature.
Alarm#06 press
HELP
TAL OIL FEED
Temp. < min
TAL OIL FEED Alarm for a decrease of the
Separation-Stop 10 °C 30 °C 85 °C 90 °C
Temp. < min oil temperature.
Alarm#05 press
HELP
Settings Temperature – Ejection monitoring
Ejection-
OSE 5 OSE 10 OSE 20 OSE 40 OSE 80 OSE 120
Monitoring
EJECTION
MONITORING:
Alarm for monitoring the
Eject. current < Value depending on the con-
Ejection monitoring ejection after separation or
Offset ditions of the power supply 0,5 A 0,5 A 0,5 A 3A 5A 8A
Eject. current < Offset after SMS ejection.
Separation-Stop system and the clutch shoes!
Current is monitored.
Alarm#07 press
HELP
EJECTION
MONITORING:
Alarm for monitoring the
Ejection monitoring Eject. speed < Off- Value depending on the con-
ejection after separation or
Eject. speed < Offset set ditions of the power supply 100 U/min 100 U/min 100 U/min 100 U/min 100 U/min 100 U/min
after SMS ejection.
(Option) Separation-Stop system and the clutch shoes!
Speed is monitored.
Alarm#33 press
HELP
8555-9201-140 / 1010
Maintenance-Interval:
Set: 4000 h 0m 0s
Actual: 22 h 12 m 46 s
The factory setting for "Set" is a maintenance interval of 4000 hours as specified
in the separator instruction manual. Under "Actual", the operating hours of the
separator are counted.
When the pre-set number of operating hours is reached, a common alarm is ac-
tivated and a corresponding warning appears in the display. A common alarm
does not interrupt the separating program and must be acknowledged using the
ACK key.
Note:
Please take the maintenance interval setting from the instruction manual of the
separator used.
Maintenance-Interval WMS
Set: 168 h 0m 0s
Actual: 22 h 12 m 46 s
The factory setting for "Set" is a maintenance interval of 168 hours (1 week).
Under "Actual", the operating hours of the WMS-Sensor water signal is counted.
In the case the “Actual” counter came up to the preset operating hours, a main-
tenance message will be activated with a corresponding hint that the WMS-
Sensor Check must be done! The message does not interrupt the separation
process and must be acknowledged with the „ACK“button after the WMS Sen-
sor Check. The acknowledgement resets the the “Actual” value.
Under “Last water signal WMS” the operating hours of the WMS Sensor since
the last water indication are counted. Only a water signal resets the operating
hours for “Last water signal WMS”.
In the case the message „Maintenance WMS-Sensor“ occurs in the display, a manual check of the WMS-
Sensor function must be done. Please follow up the described steps!
Step
1 • Stop separation sequence by pushing touch key “Prog. OFF” on the control unit.
Step
A:
Position 1: closed
Position 2: open
In the case that the signal did not change, • Take note to the chapter „Maintenance schedule“
• Remove waterdetector (WMS-Sensor), of the instruction manual of the used separator.
clean it and check function.
8 Start of the separation process is possible by pushing the touch key „Prig. ON“ at the control unit.
4 Program logic
A A
Power supply
ON
Selftest
Control Unit
Start of
Sensor Check Sequence
Precondition:
Oil temperature > TSL setpoint
Oil temperature < TSH setpoint
LSHH not activated
Vibro II not activated
B
B
B
Start of
Separation sequence
Process
monitoring
activated
E
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
C
C
Stop of separation sequence
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separator
Ready for operation
A
D
D
Process
options
activated
Alarm
Separator OFF activated
after (T39)
A
E
E
Process
monitoring
activated
CU = Compact Unit
Alarm
PAL / PAH
TAL / TAH
LAHH
A
A
A
Power supply
ON
Selftest
Control Unit
Process
optionens
activated
D
Start of
Sensor Check Sequence
Precondition:
Oil temperature > TSL setpoint
Oil temperature < TSH setpoint
LSHH not activated
Vibro II not activated
B
B
B
Start of
Separation sequence
Process
monitoring
activated
E
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separation program
Closing water impulse (T06)
Filling water (T02)
Waiting after filling (T09)
Separation (T20)
Sensor flushing (T38)
Bridging after ejection (T11)
C
C
Stop of separation sequence
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separator
Ready for operation
A
D
D
Process
options
activated
Alarm
Separator OFF activated
after (T39)
A
E
E
Process
monitoring
activated
CU = Compact Unit
Alarm
PAL / PAH
TAL / TAH
LAHH
A
A
A
Power supply
ON
Selftest
Control Unit
Process
optionens
activated
D
Start of
Separation Sequence
Precondition:
Oil temperature > TSL setpoint
Oil temperature < TSH setpoint
LSHH not activated
Vibro II not activated
B
B
B
Start of
Separation sequence
Process
monitoring
activated
E
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separation program
Closing water impulse (T06)
Filling water (T02)
Waiting after filling (T09)
Separation (T20)
Bridging after ejection (T11)
C
C
Stop of Separation sequence
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separator
Ready for operation
A
D
D
Process
options
activated
Alarm
Separator OFF activated
after (T39)
A
E
E
Process
monitoring
activated
Alarm
PAL / PAH CU = Compact Unit
TAL / TAH
LAHH
A
KNOW-HOW PROTECTION
No GEA-specific device
No warranty by operation!
Alarm#00 Please check:
Contact Westfalia
customer service !
MOTOR PROTECTION
Alarm#01 Please check:
Motor protection function / Brake
Thermistor relay / Operating water
Valve V2 / No. of clutch shoes
Drive blocked / Feed capacity
Press ESC then ACK
EJECTION MONITORING
Alarm#07 Please check:
Function of bowl / Hydraulics with V3
Connector valve V3 / Current offset setting/
Water quantity / TIMER 28
Current converter / Pre-strainer
Press ESC then ACK
VIBRATION STAGE 1
Alarm#11 Please check:
TIMER 25 / Solids holding space
Polyamide sealing ring / Sensor
Fixing / Limit value 1 / Correct
bowl parts / Foundation fixing
Press ESC then ACK
or
Step 2 Alarm acknowledgement
VIBRATION STAGE 2
Alarm #12 Please check:
Limit value 2 / Solids holding space
Polyamide sealing ring / Sensor
Fixing / Correct bowl parts
Foundation fixing
Press ESC then ACK
BOWL MONITORING
Alarm#18 Please check:
TIMER T06 / Current offset
Frequency power supply
Water pressure for hydraulic
Function V3
Press ESC then ACK
Note:
TR2 = Time record of sludge pump operation, TR2 will be deleted when
TR3 has expired.
TR3 = Time counter factory setting 24 h
Note:
TR1 = Time record of WMS water sensor during HFO operation, TR1 will be
deleted when TR3 has expired.
TR3 = Time counter factory setting 24 h
MAINTENANCE required
Alarm#27 Please check:
Operating hours have reached
4000; 8000; 12000; 16000 hours
or multiple / Carry out maintenance
according manual
Press ESC then ACK
EJECTION MONITORING
Alarm#33 Please check:
Function of bowl / Hydraulics with V3
Connector valve V3 / Speed offset eject.
Water quantity / TIMER 28 / Speed pick- up
defective / Pre-strainer
Press ESC then ACK
BOWL MONITORING
Alarm#34 Please check:
TIMER T06 / Water pressure
for hydraulic / Speed offset
bowl monitoring / Function V3
Speed pick- up defective
Press ESC then ACK
SEPARATOR- START
Alarm#35 Please check:
TIMER T10 / Brake unfastened / Clutch
shoes oily / Drive belt oily / Speed setting
of operation speed / Speed pick-up defective
Press ESC then ACK
BELT MONITORING
Alarm#36 Please check:
Drive belt / Motor defect electrically
Clutch shoes worn or oily
Speed pick- up defective
Press ESC then ACK
PT 1 MONITORING
Alarm#39 Please check:
Switching function PT 1
PT 1 dirty / Setpoint PAL 1
Bowl hydraulics / Ejection
monitoring / Discharge pressure
Press ESC then ACK
NO WATER SEAL
Alarm#40 Please check:
Clean oil discharge pressure
Function V2 / Filling water quantity
Valve V2 and filter / Water pressure
TIMER T06 / Setting TAL / Setting PT 2
Press ESC then ACK
EMERGENY STOP
Alarm#46 Please check:
Emergency Button
Press ESC then ACK
WATER DISCHARGE
Alarm#48 Please check:
Clean oil valve V7 / Water cont. in Oil
Filling water quantity / oil
Temperature / Regulating ring
Polyamide ring / Press. sensor PT2
Press ESC then ACK
Alarm#02
Free
Alarm#03
Free
Alarm#04
TAL PRODUCT FEED Separation Not possible Set setting higher than the • Separation
Temp. < min current temperature stop
Separation - Stop • V1 in circula-
Alarm#05 tion
• Common alarm
TAH PRODUCT FEED Separation Not possible Set setting lower than the • Separation
Temp. > max current temperature stop
Separation - Stop • V1 in circula-
Alarm#06 press ENTER tion
• Common alarm
EJECTION MONITORING Ejection Close manual ball valve Disconnect cable head of V3 • Separation
Current< Offset which is in front of V3 or increase offset Ejection stop
Separation – Stop shortly before and during current during discharge • V1 in circula-
ALARM#07 discharge cycle T04. cycle T04. tion
• Common alarm
LAHH SLUDGE TANK Control Immerse or dampen Disconnect cable head of • Separation
Sludge tank - full Active sensor LSHH. LSHH Sensor stop
Separation - Stop • V1 in circula-
Alarm#08 tion
• Common alarm
FEED PUMP FAULT Control Not possible Trigger motor protection • Separation
Motor protection Active switch stop
Separation - Stop • V1 in circula-
Alarm#09 press ENTER tion
• Common alarm
SLUDGE PUMP FAULT Control Not possible Trigger motor protection • Separation
Program - stop Active switch stop
• V1 in circula-
Alarm#10 tion
• Common alarm
Alarm#14
WMS SYSTEM FAULT Separation Open valve V2 to add Bridge WMS Sensor and set • Separation
Too much water water into bowl until pressure sensor PT2 switch- stop
Separation - Stop Timer 22 is elapsed. ing point to 0 or bridge. • V1 in circula-
Alarm#15 tion
• Common alarm
• Ejection
Free
Alarm#16
Free
Alarm#17
BOWL MONITORING Separation Not possible. Extend T06 during separa- • Common alarm
Current too high tion and shorten T14 to •
during TIMER 06 300sec.! Wait until T14 is
Alarm#18 elapsed and Alarm appears.
SEPARATOR MOTOR OFF Circulation Not possible. Set TIMER 39 to 10 seconds • Common alarm
Sep. in circulation and push program stop • Motor off
T 39 expired M. off button.
Alarm#19
Free
Alarm#20
Free
Alarm#21
EXCESSIVE RUNNING Control Set TR2 to 1 minute and Set TR2 to 1 minute • Common alarm
TIME OF SLUDGE PUMP Active immerse or dampen LSH Trigger testfunction with
In TR3 hours Sensor to start sludge magnet at testpoint of LSH
Alarm#22 pump until Alarm ap- sensor until Alarm appears.
pears.
WMS ACTIVATED Separation Set T22 to 300sec. and Set T22 to 300sec., TR1 to 1 • Common alarm
TOO OFTEN TR1 to 1 minute and minute and bridge WMS
open valve V2 to add sensor until Alarm appears.
Alarm#23 water into bowl until
Alarm appears.
Free •
Alarm#24
Free •
Alarm#25
Free •
Alarm#26
Maintenance Separation Not possible. Set value to actual value • Message in the
required see manual plus 1hour and wait 1hour. display
Alarm#27
WARNING Separation Set T17 to 1s and Set T17 to 1s and • Message in the
WATER CONTENT set counter 5 to 1 and set counter 5 to 1 and display
T47 to 60sec.than open bridge pressure sensor • V6 opens
Alarm#28 valve V2 for 10sec. to PSL2 or set optional PT2 to
add water into bowl until 0 and 1 in short intervals
warning appears. during T47 for minimum 2
times, so that warning ap-
pears.
Free
Alarm#29
Free
Alarm#30
Free
Alarm#31
Free
Alarm#32
EJECTION MONITORING Ejection Close manual ball valve Disconnect cable head of V3 • Separation
Eject. speed < Offset which is in front of V3 or increase offset Ejection stop
Separation – Stop shortly before and during speed during discharge • V1 in circula-
Alarm#33 discharge cycle T04. cycle T04. tion
• Common alarm
BOWL MONITORING Separation Not possible. Extend T06 during separa- • Common alarm
Speed drop too high tion and shorten T14 to •
during TIMER 06 300sec.! Wait until T14 is
Alarm#34 elapsed and Alarm appears.
SEPARATOR-START Separator Set Timer 10 to 10 sec. Set setting for min. speed • Motor off
monitoring Motor Start and press motor start higher than the normal • Message in the
during T10 button. operating speed. display
Alarm#35 • Common alarm
BELT MONITORING Separator Not possible. Disconnect speed pick-up • Motor off
Drive belt broken Motor Start sensor and press motor • Message in the
during start up start button. display
Alarm#36 • Common alarm
MAX.- SPEED Separator Not possible. Set setting for Max. Speed • Motor off
MONITORING Motor Start lower than normal operating • Message in the
during operation and Separa- speed, during start up or display
Alarm#37 tion during operation. • Common alarm
•
MIN.- SPEED Separator Not possible. Set setting for Min. Speed • Motor off
MONITORING Motor Start higher than normal operat- • Message in the
during operation and Separa- ing speed, display
Alarm#38 tion during start up or during • Common alarm
operation. •
PT 1 MONITORING Ejection Not possible. Set pressure sensor PT1 • Separation
clean oil discharge switching point to 0 while stop
Separation - Stop ejection sequence is run- • V1 in circula-
Alarm#39 ning. tion
• Common alarm
•
NO WATER SEAL Separation Reduce T34 and T35 to 5 Set pressure sensor PT2 to • Separation
during TIMER 35 sec. and close hand 0 and disconnect cable of stop
Separation - Stop valve before V2 during WMS sensor. • V1 in circula-
Alarm#40 T02. tion
• Common alarm
• Ejection
MIN. SEPARATING TIME Separation Not possible. Disconnect cable head on • Separation
< 10 Min pressure sensor PT2 during stop
Separation - Stop T21. • V1 in circula-
Alarm#41 tion
• Common alarm
• Ejection
SMS SENSOR FAULT Sensor Close hand valve at V2 Disconnect cable head on • Common alarm
during SMS Check Check while test is running. pressure sensor PT2 while • Ejection
during TIMER 44 test is running.
Alarm#42
PT2 SENSOR ACTIVE Circulation Open valve V2 until pres- Set pressure sensor PT2 to • Message in the
in Idle run sure increase on pres- 0 during idle run. display
sure sensor PT2 during • Common alarm
Alarm#43 idle run. • Ejection
PAL1 CLEAN OIL DISCHARGE Separation Open clean oil discharge Disconnect cable head on • Separation
Pressure < setting valve V7 pressure sensor PT1 stop
Separation - Stop • V1 in circula-
Alarm#44 tion
• Common alarm
• Ejection
PAH 1 CLEAN OIL DISCHARGE Separation Close clean oil discharge Set pressure sensor PT1 • Separation
Pressure > setting valve V7 switching point to a lower stop
Separation - Stop value than the current value. • V1 in circula-
Alarm#45 tion
• Common alarm
• Ejection
EMERGENCY STOP Control Not possible. Push emergeny button. • All electric
Button pushed Active components
are shut down
ALARM#46 like Motors,
Control Units
ect!
FREE
ALARM#47
WATER DISCHARGE: Separation Close clean oil discharge Set pressure sensor PT1 • Separation
Overflow valve V7. Set optional PAH1 switching point to 0 while stop
Separation - Stop (PT1) in clean oil discharge separation sequence is
to 10 bar.
• V1 in circula-
Alarm#48 running. tion
• Common alarm
• Ejection
MAINTENANCE required Circulation Not possible. Set value to actual value • Message in the
WMS Sensor plus 1minute and wait display
1minute. Add extra water to
Alarm#49 get WMS Signal if neces-
sary.
Free
Alarm#50
For a simulation, the function must be activated and must be valid for the product.
ATTENTION:
After the simulation, all changes must be reset to the initial conditions!!!!
8.1 Bowl-Volumes
Separator type
3
Volumes in dm
Bowl volume 1,00 1,00 2,00 2,00 3,60 3,60 10,00 10,00 23,00 23,00 40,00 40,00
Sludgespace volume 0,50 0,50 0,90 0,90 1,60 1,60 4,00 4,00 10,00 10,00 14,60 14,60
Fillingwater volume 0,20 0,50 0,30 0,90 0,40 1,60 0,50 4,00 1,00 10,00 3,00 14,60
Displacementwater
volume
0,50 0,50 1,10 1,10 2,00 2,00 6,00 6,00 13,00 13,00 25,40 25,40
Separator type
OSE 5 / OSE 10 / OSE 20 OSE 40 OSE 80 OSE 120
Speed in U/min
Max. Speed 12 200 8 400 7 000 6 100
Min. Speed 11 500 7 800 6 300 5 400
Rated Speed 12 000 8 200 6 800 5 900
Speed -Offset
100 100 100 100
Ejection monitoring
Speed -Offset
100 100 100 100
Bowl monitoring
Type E 40
No. 8555-9201-140
Edition 1010
The authors are always grateful for comments and suggestions for improving
the documentation. They can be addressed to:
Note: • This symbol is not a safety precaution but rather a reference to infor-
mation which help to better understand the separator or plant compo-
nents and the processes.
1 Timer overview 7
4 Program logic 25
1 Timer overview
Operating water valve V 3 The bowl sludge space is partial emptied by actu-
T00 Partial ejection
opens ating the operating water valve V 3. (Option) X X X
Operating water valve V 3 The bowl sludge space is emptied by actuating the
T04 Total ejection
opens operating water valve V 3. X X X
Closing water impul- Operating water valve V 3 Timer for safety water to keep the bowl closed
T06
se opens during separation. X X X
After timer is expired, product After timer is expired, the standard alarms like
T07 Alarm delay
feed valve V 1 closes. PAL1/PAH1, TAL/TAH, PAH2 ect. will be initiated. X X X
T09 Waiting after filling Timer to stabilize the system after filling process. --- X X
T11 Alarm Bridging Alarms not activated. Timer to stabilize the process conditions! X X X
T14 Closing water interval Time interval between two closing water pulses. X X X
Circulation valve
T15
close
Circulation valve V 5 closes. Timer in which the circulation valve is closed! X --- ---
Circulation valve Circulation valve V 5 opens. Timer in which the circulation valve is opened!
T16
open WMS Sensor is activated. WMS Sensor Signal is checked. X --- ---
Active in
Timer Designation Action Description
-0136- -0196- -91-
program.
Water impulse by Operating water valve V 3 Timer for closing the bowl after separator is on
T19
start opens operating speed. X X X
T20 Separation Product feed valve V 1 opens Timer for adjusting the separating time. X X X
In case of pressure drop (SMS Timer in which a system pressure drop is eva-
Min separation time PT 2) during T21 , triggering of luated as an alarm.
T21
with SMS alarm "Minimum separating X --- ---
time during SMS" Timer starts together with timer 20.
Active in
Timer Designation Action Description
-0136- -0196- -91-
Bowl is filled in intervals controlled by T37 with
Filling water valve V 2 opens filling water to check whether the sludge space is
T36 SMS pressure check in intervals until SMS sensor filled with sludge. If the sludge space is not full, X --- ---
PT 2 is activated. the SMS sensor PT 2 must respond to pressure. If
pressure is not increasing, an ejection is triggered.
Timer to set the interval between two filling water
Filling water valve V 2 closes.
T37 SMS Waiting
SMS sensor PT 2 is activated.
pulses for sludge space monitoring! See also X --- ---
SMS pressure check, above.
WMS sensor not activated.
SMS sensor PT 2 not acti- Timer to flush the sensing line after the first pro-
WMS Sensor flush-
T38
ing
vated. gram start so that it is clean and excessive filling --- X ---
Water discharge valve V 6 water is discharged!
opens.
Separator off after After delay T 39, the separa- Timer delay for separator motor stop. Function
T39
idle run tor motor is switched off. must be preselected in the program. X X X
Timer to operate the sludge pump until the sludge
T40 CU-Sludge pump On Sludge pump activated.
tank is completely emptied. X X X
T41 CU-Sludge pump Off Sludge pump not activated. Time interval between two sludge pump starts. X X X
T42 Free
T43 Free
Circulation valve V 5 closes. Timer in which the function of the SMS sensor PT
Water discharge valve V 6 2 is tested. If T44 is elapsed without SMS Sensor
T44 SMS-Sensor-Check
closes. PT 2 Signal, Alarm "SMS sensor failure during X X ---
SMS sensor PT 2 is activated. WMS-SMS check" is triggered.
T45 Free
T46 Free
When SMS Sensor PT 2 is Capacity and machine type-dependent timer
activated while T 47 is run- which determines the increse of water in the lube
ning, the water discharge oil during WMS mode. The pressure increase is
T47 Min.SMS Time
valve V 6 is opened for 3 evaluated as a function of T 47 over several --- X ---
seconds and Counter 5 successive cycles which are defined via counter 5
counts the PT 2 signal. "SMS time interval water content"
Timer to fill filling water into the bowl. This timer
runs before timer T61 and T62. Timer is required
T60 Start Impulse Filling water valve V 2 opens.
for the automatic calculation of timers 01 and 02. X X ---
Timer is protected.
2.1
Separator-Type
Text Display Remarks OSE OSE OSE OSE OSE OSE
Full Text
(P = Setpoint; A = actual value) 5 10 20 40 80 120
Counter
C1 Flushing:
C01 Flushing Flushing counter 5 5 5 5 5 5
P: 5
A: 0
C2 Partial Ejection:
C02 Partial Ejection Partial ejection counter 5 5 5 5 5 5
(Option) P: 5
A: 0
C3 SMS Filling:
C03 SMS-Filling SMS fillng counter 5 5 5 5 5 5
P: 3
A: 0
C4 Sensor Check:
C04 Sensor-Check Sensor check counter 10 10 10 10 10 10
(Option) P: 10
A: 0
C5 Water content
Default settings Counter - Time records
Sludgep.-time
Time Record for Max. in 24 h 30 min
TR2 TR2 Sludgep. time sludgepump time operation 30 30 30 40 50 60
in last TR3 (24h) hours. Act. in 24 h 0 min (Act. in = actuel 24h)
Last. in 24 h 0 min (Last in = previous 24h)
Active in:
No. Designation: Status: Description:
-0136- -0196- -91-
2.3
Control Unit E40
Alarme Display Text Remarks Separator-Type
Full Text:
Control Unit:
Temperature- OSE
Monitoring DO MDO LO HFO
Separation Temperature 20 °C 40 °C 95 °C 98 °C
TAH OIL FEED
Temp. > max
TAH OIL FEED Alarm for an increase of the
Separation-Stop 30 °C 50 °C 105 °C 105 °C
Temp. > max oil temperature.
Alarm#06 press
HELP
TAL OIL FEED
Temp. < min
TAL OIL FEED Alarm for a decrease of the
Separation-Stop 10 °C 30 °C 85 °C 90 °C
Temp. < min oil temperature.
Alarm#05 press
HELP
Settings Temperature – Ejection monitoring
Ejection-
OSE 5 OSE 10 OSE 20 OSE 40 OSE 80 OSE 120
Monitoring
EJECTION
MONITORING:
Alarm for monitoring the
Eject. current < Value depending on the con-
Ejection monitoring ejection after separation or
Offset ditions of the power supply 0,5 A 0,5 A 0,5 A 3A 5A 8A
Eject. current < Offset after SMS ejection.
Separation-Stop system and the clutch shoes!
Current is monitored.
Alarm#07 press
HELP
EJECTION
MONITORING:
Alarm for monitoring the
Ejection monitoring Eject. speed < Off- Value depending on the con-
ejection after separation or
Eject. speed < Offset set ditions of the power supply 100 U/min 100 U/min 100 U/min 100 U/min 100 U/min 100 U/min
after SMS ejection.
(Option) Separation-Stop system and the clutch shoes!
Speed is monitored.
Alarm#33 press
HELP
8555-9201-140 / 1010
Maintenance-Interval:
Set: 4000 h 0m 0s
Actual: 22 h 12 m 46 s
The factory setting for "Set" is a maintenance interval of 4000 hours as specified
in the separator instruction manual. Under "Actual", the operating hours of the
separator are counted.
When the pre-set number of operating hours is reached, a common alarm is ac-
tivated and a corresponding warning appears in the display. A common alarm
does not interrupt the separating program and must be acknowledged using the
ACK key.
Note:
Please take the maintenance interval setting from the instruction manual of the
separator used.
Maintenance-Interval WMS
Set: 168 h 0m 0s
Actual: 22 h 12 m 46 s
The factory setting for "Set" is a maintenance interval of 168 hours (1 week).
Under "Actual", the operating hours of the WMS-Sensor water signal is counted.
In the case the “Actual” counter came up to the preset operating hours, a main-
tenance message will be activated with a corresponding hint that the WMS-
Sensor Check must be done! The message does not interrupt the separation
process and must be acknowledged with the „ACK“button after the WMS Sen-
sor Check. The acknowledgement resets the the “Actual” value.
Under “Last water signal WMS” the operating hours of the WMS Sensor since
the last water indication are counted. Only a water signal resets the operating
hours for “Last water signal WMS”.
In the case the message „Maintenance WMS-Sensor“ occurs in the display, a manual check of the WMS-
Sensor function must be done. Please follow up the described steps!
Step
1 • Stop separation sequence by pushing touch key “Prog. OFF” on the control unit.
Step
A:
Position 1: closed
Position 2: open
In the case that the signal did not change, • Take note to the chapter „Maintenance schedule“
• Remove waterdetector (WMS-Sensor), of the instruction manual of the used separator.
clean it and check function.
8 Start of the separation process is possible by pushing the touch key „Prig. ON“ at the control unit.
4 Program logic
A A
Power supply
ON
Selftest
Control Unit
Start of
Sensor Check Sequence
Precondition:
Oil temperature > TSL setpoint
Oil temperature < TSH setpoint
LSHH not activated
Vibro II not activated
B
B
B
Start of
Separation sequence
Process
monitoring
activated
E
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
C
C
Stop of separation sequence
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separator
Ready for operation
A
D
D
Process
options
activated
Alarm
Separator OFF activated
after (T39)
A
E
E
Process
monitoring
activated
CU = Compact Unit
Alarm
PAL / PAH
TAL / TAH
LAHH
A
A
A
Power supply
ON
Selftest
Control Unit
Process
optionens
activated
D
Start of
Sensor Check Sequence
Precondition:
Oil temperature > TSL setpoint
Oil temperature < TSH setpoint
LSHH not activated
Vibro II not activated
B
B
B
Start of
Separation sequence
Process
monitoring
activated
E
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separation program
Closing water impulse (T06)
Filling water (T02)
Waiting after filling (T09)
Separation (T20)
Sensor flushing (T38)
Bridging after ejection (T11)
C
C
Stop of separation sequence
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separator
Ready for operation
A
D
D
Process
options
activated
Alarm
Separator OFF activated
after (T39)
A
E
E
Process
monitoring
activated
CU = Compact Unit
Alarm
PAL / PAH
TAL / TAH
LAHH
A
A
A
Power supply
ON
Selftest
Control Unit
Process
optionens
activated
D
Start of
Separation Sequence
Precondition:
Oil temperature > TSL setpoint
Oil temperature < TSH setpoint
LSHH not activated
Vibro II not activated
B
B
B
Start of
Separation sequence
Process
monitoring
activated
E
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separation program
Closing water impulse (T06)
Filling water (T02)
Waiting after filling (T09)
Separation (T20)
Bridging after ejection (T11)
C
C
Stop of Separation sequence
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separator
Ready for operation
A
D
D
Process
options
activated
Alarm
Separator OFF activated
after (T39)
A
E
E
Process
monitoring
activated
Alarm
PAL / PAH CU = Compact Unit
TAL / TAH
LAHH
A
KNOW-HOW PROTECTION
No GEA-specific device
No warranty by operation!
Alarm#00 Please check:
Contact Westfalia
customer service !
MOTOR PROTECTION
Alarm#01 Please check:
Motor protection function / Brake
Thermistor relay / Operating water
Valve V2 / No. of clutch shoes
Drive blocked / Feed capacity
Press ESC then ACK
EJECTION MONITORING
Alarm#07 Please check:
Function of bowl / Hydraulics with V3
Connector valve V3 / Current offset setting/
Water quantity / TIMER 28
Current converter / Pre-strainer
Press ESC then ACK
VIBRATION STAGE 1
Alarm#11 Please check:
TIMER 25 / Solids holding space
Polyamide sealing ring / Sensor
Fixing / Limit value 1 / Correct
bowl parts / Foundation fixing
Press ESC then ACK
or
Step 2 Alarm acknowledgement
VIBRATION STAGE 2
Alarm #12 Please check:
Limit value 2 / Solids holding space
Polyamide sealing ring / Sensor
Fixing / Correct bowl parts
Foundation fixing
Press ESC then ACK
BOWL MONITORING
Alarm#18 Please check:
TIMER T06 / Current offset
Frequency power supply
Water pressure for hydraulic
Function V3
Press ESC then ACK
Note:
TR2 = Time record of sludge pump operation, TR2 will be deleted when
TR3 has expired.
TR3 = Time counter factory setting 24 h
Note:
TR1 = Time record of WMS water sensor during HFO operation, TR1 will be
deleted when TR3 has expired.
TR3 = Time counter factory setting 24 h
MAINTENANCE required
Alarm#27 Please check:
Operating hours have reached
4000; 8000; 12000; 16000 hours
or multiple / Carry out maintenance
according manual
Press ESC then ACK
EJECTION MONITORING
Alarm#33 Please check:
Function of bowl / Hydraulics with V3
Connector valve V3 / Speed offset eject.
Water quantity / TIMER 28 / Speed pick- up
defective / Pre-strainer
Press ESC then ACK
BOWL MONITORING
Alarm#34 Please check:
TIMER T06 / Water pressure
for hydraulic / Speed offset
bowl monitoring / Function V3
Speed pick- up defective
Press ESC then ACK
SEPARATOR- START
Alarm#35 Please check:
TIMER T10 / Brake unfastened / Clutch
shoes oily / Drive belt oily / Speed setting
of operation speed / Speed pick-up defective
Press ESC then ACK
BELT MONITORING
Alarm#36 Please check:
Drive belt / Motor defect electrically
Clutch shoes worn or oily
Speed pick- up defective
Press ESC then ACK
PT 1 MONITORING
Alarm#39 Please check:
Switching function PT 1
PT 1 dirty / Setpoint PAL 1
Bowl hydraulics / Ejection
monitoring / Discharge pressure
Press ESC then ACK
NO WATER SEAL
Alarm#40 Please check:
Clean oil discharge pressure
Function V2 / Filling water quantity
Valve V2 and filter / Water pressure
TIMER T06 / Setting TAL / Setting PT 2
Press ESC then ACK
EMERGENY STOP
Alarm#46 Please check:
Emergency Button
Press ESC then ACK
WATER DISCHARGE
Alarm#48 Please check:
Clean oil valve V7 / Water cont. in Oil
Filling water quantity / oil
Temperature / Regulating ring
Polyamide ring / Press. sensor PT2
Press ESC then ACK
Alarm#02
Free
Alarm#03
Free
Alarm#04
TAL PRODUCT FEED Separation Not possible Set setting higher than the • Separation
Temp. < min current temperature stop
Separation - Stop • V1 in circula-
Alarm#05 tion
• Common alarm
TAH PRODUCT FEED Separation Not possible Set setting lower than the • Separation
Temp. > max current temperature stop
Separation - Stop • V1 in circula-
Alarm#06 press ENTER tion
• Common alarm
EJECTION MONITORING Ejection Close manual ball valve Disconnect cable head of V3 • Separation
Current< Offset which is in front of V3 or increase offset Ejection stop
Separation – Stop shortly before and during current during discharge • V1 in circula-
ALARM#07 discharge cycle T04. cycle T04. tion
• Common alarm
LAHH SLUDGE TANK Control Immerse or dampen Disconnect cable head of • Separation
Sludge tank - full Active sensor LSHH. LSHH Sensor stop
Separation - Stop • V1 in circula-
Alarm#08 tion
• Common alarm
FEED PUMP FAULT Control Not possible Trigger motor protection • Separation
Motor protection Active switch stop
Separation - Stop • V1 in circula-
Alarm#09 press ENTER tion
• Common alarm
SLUDGE PUMP FAULT Control Not possible Trigger motor protection • Separation
Program - stop Active switch stop
• V1 in circula-
Alarm#10 tion
• Common alarm
Alarm#14
WMS SYSTEM FAULT Separation Open valve V2 to add Bridge WMS Sensor and set • Separation
Too much water water into bowl until pressure sensor PT2 switch- stop
Separation - Stop Timer 22 is elapsed. ing point to 0 or bridge. • V1 in circula-
Alarm#15 tion
• Common alarm
• Ejection
Free
Alarm#16
Free
Alarm#17
BOWL MONITORING Separation Not possible. Extend T06 during separa- • Common alarm
Current too high tion and shorten T14 to •
during TIMER 06 300sec.! Wait until T14 is
Alarm#18 elapsed and Alarm appears.
SEPARATOR MOTOR OFF Circulation Not possible. Set TIMER 39 to 10 seconds • Common alarm
Sep. in circulation and push program stop • Motor off
T 39 expired M. off button.
Alarm#19
Free
Alarm#20
Free
Alarm#21
EXCESSIVE RUNNING Control Set TR2 to 1 minute and Set TR2 to 1 minute • Common alarm
TIME OF SLUDGE PUMP Active immerse or dampen LSH Trigger testfunction with
In TR3 hours Sensor to start sludge magnet at testpoint of LSH
Alarm#22 pump until Alarm ap- sensor until Alarm appears.
pears.
WMS ACTIVATED Separation Set T22 to 300sec. and Set T22 to 300sec., TR1 to 1 • Common alarm
TOO OFTEN TR1 to 1 minute and minute and bridge WMS
open valve V2 to add sensor until Alarm appears.
Alarm#23 water into bowl until
Alarm appears.
Free •
Alarm#24
Free •
Alarm#25
Free •
Alarm#26
Maintenance Separation Not possible. Set value to actual value • Message in the
required see manual plus 1hour and wait 1hour. display
Alarm#27
WARNING Separation Set T17 to 1s and Set T17 to 1s and • Message in the
WATER CONTENT set counter 5 to 1 and set counter 5 to 1 and display
T47 to 60sec.than open bridge pressure sensor • V6 opens
Alarm#28 valve V2 for 10sec. to PSL2 or set optional PT2 to
add water into bowl until 0 and 1 in short intervals
warning appears. during T47 for minimum 2
times, so that warning ap-
pears.
Free
Alarm#29
Free
Alarm#30
Free
Alarm#31
Free
Alarm#32
EJECTION MONITORING Ejection Close manual ball valve Disconnect cable head of V3 • Separation
Eject. speed < Offset which is in front of V3 or increase offset Ejection stop
Separation – Stop shortly before and during speed during discharge • V1 in circula-
Alarm#33 discharge cycle T04. cycle T04. tion
• Common alarm
BOWL MONITORING Separation Not possible. Extend T06 during separa- • Common alarm
Speed drop too high tion and shorten T14 to •
during TIMER 06 300sec.! Wait until T14 is
Alarm#34 elapsed and Alarm appears.
SEPARATOR-START Separator Set Timer 10 to 10 sec. Set setting for min. speed • Motor off
monitoring Motor Start and press motor start higher than the normal • Message in the
during T10 button. operating speed. display
Alarm#35 • Common alarm
BELT MONITORING Separator Not possible. Disconnect speed pick-up • Motor off
Drive belt broken Motor Start sensor and press motor • Message in the
during start up start button. display
Alarm#36 • Common alarm
MAX.- SPEED Separator Not possible. Set setting for Max. Speed • Motor off
MONITORING Motor Start lower than normal operating • Message in the
during operation and Separa- speed, during start up or display
Alarm#37 tion during operation. • Common alarm
•
MIN.- SPEED Separator Not possible. Set setting for Min. Speed • Motor off
MONITORING Motor Start higher than normal operat- • Message in the
during operation and Separa- ing speed, display
Alarm#38 tion during start up or during • Common alarm
operation. •
PT 1 MONITORING Ejection Not possible. Set pressure sensor PT1 • Separation
clean oil discharge switching point to 0 while stop
Separation - Stop ejection sequence is run- • V1 in circula-
Alarm#39 ning. tion
• Common alarm
•
NO WATER SEAL Separation Reduce T34 and T35 to 5 Set pressure sensor PT2 to • Separation
during TIMER 35 sec. and close hand 0 and disconnect cable of stop
Separation - Stop valve before V2 during WMS sensor. • V1 in circula-
Alarm#40 T02. tion
• Common alarm
• Ejection
MIN. SEPARATING TIME Separation Not possible. Disconnect cable head on • Separation
< 10 Min pressure sensor PT2 during stop
Separation - Stop T21. • V1 in circula-
Alarm#41 tion
• Common alarm
• Ejection
SMS SENSOR FAULT Sensor Close hand valve at V2 Disconnect cable head on • Common alarm
during SMS Check Check while test is running. pressure sensor PT2 while • Ejection
during TIMER 44 test is running.
Alarm#42
PT2 SENSOR ACTIVE Circulation Open valve V2 until pres- Set pressure sensor PT2 to • Message in the
in Idle run sure increase on pres- 0 during idle run. display
sure sensor PT2 during • Common alarm
Alarm#43 idle run. • Ejection
PAL1 CLEAN OIL DISCHARGE Separation Open clean oil discharge Disconnect cable head on • Separation
Pressure < setting valve V7 pressure sensor PT1 stop
Separation - Stop • V1 in circula-
Alarm#44 tion
• Common alarm
• Ejection
PAH 1 CLEAN OIL DISCHARGE Separation Close clean oil discharge Set pressure sensor PT1 • Separation
Pressure > setting valve V7 switching point to a lower stop
Separation - Stop value than the current value. • V1 in circula-
Alarm#45 tion
• Common alarm
• Ejection
EMERGENCY STOP Control Not possible. Push emergeny button. • All electric
Button pushed Active components
are shut down
ALARM#46 like Motors,
Control Units
ect!
FREE
ALARM#47
WATER DISCHARGE: Separation Close clean oil discharge Set pressure sensor PT1 • Separation
Overflow valve V7. Set optional PAH1 switching point to 0 while stop
Separation - Stop (PT1) in clean oil discharge separation sequence is
to 10 bar.
• V1 in circula-
Alarm#48 running. tion
• Common alarm
• Ejection
MAINTENANCE required Circulation Not possible. Set value to actual value • Message in the
WMS Sensor plus 1minute and wait display
1minute. Add extra water to
Alarm#49 get WMS Signal if neces-
sary.
Free
Alarm#50
For a simulation, the function must be activated and must be valid for the product.
ATTENTION:
After the simulation, all changes must be reset to the initial conditions!!!!
8.1 Bowl-Volumes
Separator type
3
Volumes in dm
Bowl volume 1,00 1,00 2,00 2,00 3,60 3,60 10,00 10,00 23,00 23,00 40,00 40,00
Sludgespace volume 0,50 0,50 0,90 0,90 1,60 1,60 4,00 4,00 10,00 10,00 14,60 14,60
Fillingwater volume 0,20 0,50 0,30 0,90 0,40 1,60 0,50 4,00 1,00 10,00 3,00 14,60
Displacementwater
volume
0,50 0,50 1,10 1,10 2,00 2,00 6,00 6,00 13,00 13,00 25,40 25,40
Separator type
OSE 5 / OSE 10 / OSE 20 OSE 40 OSE 80 OSE 120
Speed in U/min
Max. Speed 12 200 8 400 7 000 6 100
Min. Speed 11 500 7 800 6 300 5 400
Rated Speed 12 000 8 200 6 800 5 900
Speed -Offset
100 100 100 100
Ejection monitoring
Speed -Offset
100 100 100 100
Bowl monitoring
Language : en
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Title- / cover sheet
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 1
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EAA 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Table of contents
Document type Page Page description Plant Mounting place Date Editor
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Table of contents
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 2
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EAB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Table of contents
Document type Page Page description Plant Mounting place Date Editor
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Table of contents
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 3
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EAB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Table of contents
Document type Page Page description Plant Mounting place Date Editor
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Table of contents
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 4
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EAB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Table of contents
Document type Page Page description Plant Mounting place Date Editor
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Table of contents
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 5
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EAB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Revision overview
Revision name Revision comment Revision on the basis of change Page name Author Date
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Revision overview
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 6
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EBH 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Structure indicator
Complete name Labelling Structure descprition Complete name Labelling Structure descprition
=0 Plant Incoming
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Structure indicator
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 7
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EDB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Instruction / specification
Classification ...
Interface:
Incoming:
Mains frequency 60 Hz
Rotary field
Incoming redundant NO
Control voltages:
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Information-sheet
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 8
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EDB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Wiring
Electrical circuits Conductor Colour Cross-section Electrical circuits Conductor Colour Cross-section
Main circuits 480V AC L1 Black ≥ 1,5mm² Control voltage 220V AC L Red ≥ 0,75mm²
M Brown "
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Information-sheet
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 9
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EDB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
480V AC
L1 / 13.0
L2 / 13.0
L3 / 13.0
480V AC
L1.2 / 20.0
L2.2 / 11.0
L3.2 / 11.0
3
-F01
4
C6A
N/L2
L1
-T01
INPUT
120/230VAC GEA
24VDC/5A power
OFF
ON
A
B
OUTPUT
L+
L+'
PE
M'
12
14
1
-Q1
0M.R / 19.0
/26.1 11
56-80A -PE
In: 74A
I> I> I>
2
-024M
2
-PE
0M.T / 24.0
0M.X / 19.0
24V DC
0L+.A / 19.0
24V DC
0L+.X / 19.0
24V DC
0L+.T / 24.0
-X1_W1 -W001
Pre-fuse: Pre-fuse:
_-J _-J NH 80A 10 A
4x25 mm² 3x1,5 mm²
PE
PE
PE
PE
L1
L2
L3
N
L
=Customer
U: 480V AC U: 120V AC
+L-X
Earthing cabinet 1
120V AC 120V AC
Earthing door 1
f: 60 Hz f: 60 Hz
P: ~33 kW P: ~0,25 kW
Incoming 1 Incoming 2 Earthing screen Control voltage DC
480V AC 120V AC
Icn: 36 kA Icn: 36 kA
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 0
Editor GUE/PLE
Customer:
Separator Incoming
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 10
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
480V AC 480V AC
10.9 / L2.2 L2.2 / 20.0
10.9 / L3.2 L3.2 / 20.0
220V AC
L.A / 13.4
N.A / 12.0
220V AC
L.X / 12.0
1
5
-F1 N.X /
0,9...1,25A
EW:0,97A
I> I> I>
2
6
480V AC
480V AC
N/L2
L1
-T1 A F C K -T2
INPUT
400VA 120/230VAC GEA
24VDC/5A power
GND
OFF
ON
ua va PE ub vb
220V AC
220V AC
A
B
OUTPUT
-PE
L+
L+'
PE
M'
M.A / 13.2
-PE
M.K / 28.0
M.R / 14.0
2
-24M
1
-F2
2
C6A
-PE
M.T / 30.0
M.X / 18.0
24V DC
L+.A / 12.7
24V DC
L+.K / 31.0
24V DC
L+.X / 16.0
24V DC
L+.T / 30.0
3
-X1
-PE
-PE
N
L
-M1
M
45/39W 1~
Cabinet fan
PE
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 0
Editor GUE/PLE
Customer:
Separator Control voltage
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 11
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
220V AC 220V AC
11.9 / L.X L.X /
220V AC
1L.X / 13.4
220V AC
1L.A / 20.4
7
-X1
24V DC 24V DC
11.9 / L+.A L+.A / 13.2
11
-K1
12
14
/12.6
29
X11
E2.7
/32.5
=00-K1
Separator
emergency stop
A1
-K1
A2
11.9 / N.A N.A / 13.4
Remove link in case of
an external
8
emergency stop!
(optional) -X1
-X1_W17
.-O
2x1 mm²
21
14
11 /12.8
12
-S01
22
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 0
Editor GUE/PLE
Customer:
Separator Emergency stop
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 12
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
=00-K1
4-20mA = 0-50A
/32.4
PEW752I
X11
13
-F1
14
/13.4
11
1
-Q1 -K1
-T1
2
12
14
/13.8 /14.1
*0_9_011
7+
2
S1
Input
8
0-1A
-B1
3
Output
9-
S2
100/1A 0/4-20mA
A1
A1
T1
-F1 M -Q1
T2
A2
A2
12.9 / N.A N.A / 20.4
-PE
Link remove at
connection of an
sludge discharge flap!
1
5
(optional)
-X1 -X2 -X1
-X1_W2 -X1_W13
_-J .-O
4x16 mm² 2x1 mm²
Anti-clockwise rotation
W1
U1
V1
PE
13 14 /13.8 1 2 /13.1
M 21 22 /14.2 3 4 /13.1
10_1_001 3~ 5 6 /13.1
13 14
26,0kW/41,0-43,0A Θ
21 22
T2
T1
33 34 /14.1
43 44 /26.2
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 13
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
13.3 / L+.A L+.A / 15.0
33
21
-Q1 34 -F1
22
/13.8 /13.4
2
3
X12 X12
E0.0 E0.1
/33.4 /33.4
=00-K1 =00-K1
Separator Separator
operation failure
=00-K1
/33.5
A1.0
X12
32
A1
-K1
A2
14
11 /13.8
12
Separator
start/stop
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 14
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
14.9 / L+.A L+.A / 19.0
13.3 / M.A
=00-K1
0-6800 r.p.m.
/33.4
E0.3
X12
-T2 5
4+
6-
24VDC
5+
1+
2-
3
-X2
-X1_W9
.-J
7x1 mm²
/16.1
+JB
-1X10 1 2
+JB-WG101
.-O
2x0,34 mm²
+
10_9_018
SI
-
+ BN = brown
- BU = blue
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator speed measuring
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 15
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
=00-K1 =00-K1
4-20mA 4-20mA
/32.4 /32.4
PEW754I PEW756I
X11 X11
=00-K1 =00-K4
6
9
/33.4 /36.5
E0.5 E8.7
X12 X1
9
24V DC 24V DC
11.9 / L+.X L+.X / 23.0
-PE
10
11
12
5
-X2 9
-X1_W9 -WG001
.-J .-O
7x1 mm² 2x1 mm²
/15.1
+JB
L+_1X10 / 17.1
PE
4
-1X10 PE
+JB-WG121
.-J
5x1,5 mm²
+SB
PE_1X20 / 18.6
M_1X20 / 18.5
2
-1X20
13
+
1
13_7_020
11_9_002 I 10_9_014 I 10_9_013
14
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator signals
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 16
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
=00-K1
/33.4
E1.7
X12
19
13
-X2
-X1_W5
.-J
7x1 mm²
/18.3
+JB 16.3 / L+_1X10
M_1X10 / 18.3
-1X10 8 11 9 10
+JB-WG104
_CY-O
4x0,75 mm²
SC
1
10_9_020
PCH 1220
+24V DC
0V
-D1
Relay
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator vibro
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 17
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24
23
26
27
11.9 / M.X M.X / 22.0
-PE
14
15
16
17
18
19
20
21
-X2
-X1_W5
.-J
7x1 mm²
/17.4
+JB
17.1 / M_1X10
-PE -PE
12
13
15
14
16
18
17
PE
-1X10 PE PE -1X10 PE
+JB-WG122
.-J
4x1,5 mm²
+SB
16.3 / M_1X20
16.3
PE_1X20
11
10
PE
PE
8
9
-1X20 PE PE
PE
PE
PE
PE
+
+
10_7_006 19_7_003/B 19_7_003/A 10_7_010 10_7_011
-
-
-
Feed valve Operating water Displacem- and Circulation valve Water discharge valve
filling water
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator valves
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 18
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
10.9 / 0L+.X 0L+.X / 24.0
24V DC 24V DC
10.9 / 0L+.A 0L+.A / 24.0
24V DC 24V DC
15.9 / L+.A L+.A / 21.0
13
13
-K11 -K12
14
14
/19.3 /19.4
11
22
23
=00-K1
-K10
12
14
/33.5 /19.1 X11 X11
A1.7 E2.0 E2.1
/32.5 /32.5
X12
=00-K1 =00-K1
39
A1
A1
23
23
-K10 -K11 -K12 -K11 -K12
A2
A2
A2
24
24
/19.3 /19.4
10.9 / 0M.R 0M.R / 24.0
10.9 / 0M.X 0M.X / 24.0
14.9 / M.R M.R / 21.0
PE -PE
22
23
24
25
26
27
28
29
30
31
32
-X2 -X2 -X2
0,5A/MT
-X0_W3 -WG021
.-J .-J
7x1 mm² 7x1 mm²
1
3
2
5
4
8
10_7_014
Type RE
6+
3
2
5
4
PE
10_7_014/A 10_7_014/B 10_7_013
ZS ZS
1
7-
Open Closed +HFO2
PE
22
23
24
25
26
27
8106-2011-062
-X2
14 13 14 /19.8 13 14 /19.8
11 /19.5
12 23 24 /19.8 23 24 /19.8
33 34 33 34
43 44 43 44
Valve Valve clean-oil Valve clean-oil Valve Valve Valve clean-oil discharge
clean-oil discharge discharge limit switch open discharge limit switch closed clean-oil discharge clean-oil discharge limit switch open Valve clean-oil discharge
from HFO2 to HFO2 limit switch closed
to HFO2
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator clean-oil discharge
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 19
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
480V AC 220V AC
10.9 / L1.2 12.9 / 1L.A
11.9 / L2.2
11.9 / L3.2
5
-Q1
17
3-12A L1 L2 L3
13
21
A1
110-220V DC/AC -Q1
18
/20.2
14
22
A2
/20.7 /21.1
3-12A
110-220V DC/AC
Control module
LUCA12FU
EW:10,5A
11
-K2
14
12
/21.1
17
97
18
98
/20.7 /21.2
T1 T2 T3
2
A1
-Q1
A2
/20.2
13.9 / N.A
-PE
1
-X1
-X1_W3
_-J
4x2,5 mm²
V1
PE
21 22
Vor dem Einschalten der Zulaufpumpe 17 18 /20.7
10_3_001
M den Leistungsschalter auf Nennstrom 97 98 /21.2
6,33kW 3 des Motors einstellen (s. Typenschild des Motors)
10,5A
Attention!
Before switch-on feed pump, adjust the circuit breaker
to nominal current of the motor (look at motor label)
Feed pump Feed pump
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 11
Editor GUE/PLE
Customer:
Separator Feed pump
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 20
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
19.9 / L+.A L+.A / 22.0
13
97
-Q1 -Q1
14
98
/20.2 /20.3
12
13
X12 X12
E1.0 E1.1
/33.4 /33.4
=00-K1 =00-K1
Feed pump Feed pump
operation failure
=00-K1
/33.5
A1.1
X12
33
A1
-K2
A2
14
11 /20.7
12
Feed pump
start / stop
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 11
Editor GUE/PLE
Customer:
Separator Feed pump
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 21
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
21.9 / L+.A L+.A / 25.0
18.9 / M.X M.X / 27.0
12
14
15
19
-SC -SC
1
-T1
Output
0/4-20mA
PT100
-SC
4
-SC
SC
SC
7
4
-X2 -X2
-X1_W14 -X1_W12
.CY-O .CY-O
2x1 mm² 4x1 mm²
/22.3
10_9_008
1
3
Θ Θ
+
PT100 PT100
10_7_012
2
4
SIPART PS2
4-20mA
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 11
Editor GUE/PLE
Customer:
Separator Product temperature control
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 22
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
=00-K2
/34.3
PEW256I
X1
2
24V DC 24V DC
16.9 / L+.X L+.X / 27.0
5
-X2
-WG004
.-O
2x1 mm²
1
10_9_009 I
FI P
4-20mA
FI flow measuring
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 11
Editor GUE/PLE
Customer:
Separator FI flow measuring
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 23
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC
19.9 / 0L+.X
19.9 / 0L+.A
10.9 / 0L+.T
23
13
13
23
M 0 A
-S1 -S2 -K1
14
24
/24.1
24
14
11
13
33
-K3 -K1 -K1
12
14
14
34
/24.5 /24.1 /24.1
11
-K2
12
14
/24.3
A1
A1
A1
A1
x1
x2
A2
A2
A2
RD
19.6 / 0M.R
19.6 / 0M.X
10.9 / 0M.T
11
10
1
9
-X2 -X2
0,5A/MT
+
4
2
90_9_003 90_9_002 90_9_001 98_7_002
3
1
LSL LSH LSHH
-
13 14 /24.2 14 14 13 14 /25.1
11 /24.1 11 /24.1
23 24 /24.3 12 12 23 24 /25.1
33 34 /24.9 24 33 34
21 /26.8
43 44 22 43 44
Valve pneumatic sludge Sludge pump LSL sludge tank LSH sludge tank LSHH sludge tank Valve pneumatic sludge
pump operation level min. level max. level max. / max. pump
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 16
Editor GUE/PLE
Customer:
Separator Sludge pump
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 24
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
22.9 / L+.A L+.A / 28.0
-K4 13
14
/24.6
9
X12
E0.7
/33.4
=00-K1
LSHH sludge tank
23
-K4
24
/24.6
-PE
12
13
-X2
-WG010
.-J
3x1 mm²
+HFO2
PE
1
8106-2011-062
-X2
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 16
Editor GUE/PLE
Customer:
Separator Sludge pump
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 25
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
35
36
37
12
13
A1
A1
A1
A1
A1
A1
-K1 -K2 -K3 -K4 -K5 -K6
A2
A2
A2
A2
A2
A2
21.9 / M.R
14 14 14 14 14 14
11 11 /26.2 11 /26.4 11 /26.5 11 /26.6 11 /26.7
12 12 12 12 12 12
24
21 /26.0
22
43
12
14
12
14
12
14
12
14
12
14
22
24
22
24
12
14
11
11
11
11
11
21
/13.8 /26.3 /26.4 /26.5 /26.6 /26.7 /24.3
21
11
/26.1 /10.1
PE
10
11
12
13
14
15
16
17
1
3
4
9
-X2
-X1_W19
.-J
18x1,5 mm²
=+DCS
PE
-X -X -X -X -X -X -X -X
Common failure Separator Sludge tank TAH TAL Local / remote PAL clean-oil Sludge tank
operation Level high / high Alarm HFO temperature HFO temperature status discharge pressure Low alarm
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 100
Editor GUE/PLE
Customer:
Separator Signal exchange
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 26
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
7
-SC -SC
=0-SC =0-SC
24V DC 24V DC
23.9 / L+.X L+.X /
22.9 / M.X M.X /
-SC
PE
SC
18
19
20
21
22
23
24
25
26
27
-X2
-X1_W20 -X1_W18
.-J .CY-O
7x1,5 mm² 4x1,5 mm²
/27.8
=+DCS
PE
-X -X -X -X -X
-K -K -K
HFO daily tank level HFO daily tank level Remote start / stop Clean-oil HFO temperature
Low control High control NO for stop, NC for start discharge pressure
Change to daily tank Change to settling tank
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 100
Editor GUE/PLE
Customer:
Separator Signal exchange
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 27
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
10
13
24V DC
25.9 / L+.A
11.9 / M.K M.K / 29.0
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 28
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Mana
6
Mana
10
5
10
15
20
25
30
35
40
28.9 / M.K M.K / 31.0
Earth analog Earth analog Earth analog Earth analog Earth analog Earth analog Earth analog Earth analog Earth analog Earth analog
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 29
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-P1
Button Designation Symbol
Westfalia Separator
OP 177B
ACK
SC
A
A
B
B
24V
0V
PE
24V DC
11.9 / L+.T MPI_A / 31.0
11.9 / M.T MPI_B / 31.0
-PE
Process display
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator Process display OP 177B
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 30
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
PEW270M-
PAW754U
PEW758V
MRES
PAW274
7 7 7 7 7
A1.7
A8.7
E2.7
E1.7
IN IN OUT IN IN
-
-
-
-
-
-
E2.0
E0.0
A0.0
PEW752V
PAW752U
PAW272
E8.0
PEW256I
L+ 0 0 0 0
1 1 1 1
M
2 2 2 2
3 3 3 3
4 4 4 4
5 5 5 5
6 6 6 6
7 7 7 7
X1 MPI
A
30.9 / MPI_A
B
30.9 / MPI_B
SC
A
Mana /32.4
B
1L+ /33.4
2L+ /33.5
3L+ /33.5
1L+ /35.5
2L+ /36.5
4M /32.5
1M /33.4
2M /33.5
3M /33.5
1M /35.5
1M /36.5
2M /36.5
SC
DC 24V
L+
X11:20
X11:30
X12:1
X12:20
X12:21
X12:30
X12:31
X12:40
X1:1
X1:20
X1:10
X1:11
X1:20
24V DC
11.9 / L+.K
29.9 / M.K
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC power supply
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 31
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-K1
X11:1 X11:21
X11:2 X11:22
PEW752V E2.0 /19.8 =01-K11:14 Valve clean-oil discharge limit switch open
X11:3 X11:23
Current measuring separator =01-T1:8 /13.3 PEW752I E2.1 /19.8 =01-K12:14 Valve clean-oil discharge limit switch closed
X11:4 X11:24
Earth analog /28.2 - E2.2
X11:5 X11:25
PEW754V E2.3
X11:6 X11:26
Clean-oil discharge pressure =01-X2:6 /16.1 PEW754I E2.4
X11:7 X11:27
Earth analog /28.3 E2.5
X11:8 X11:28
PEW756V E2.6
X11:9 X11:29
Sludge room monitoring =01-X2:8 /16.2 PEW756I E2.7 /12.8 =0-K1:14 Separator emergency stop
X11:10
Earth analog /28.4 - X11:30
4M /31.3 0V
X11:11
PEW758V V X11:31
X11:12
Product temperature control =11-T1:1 /22.5 PEW758I A
X11:32
X11:13
Earth analog /28.4
X11:33
X11:14
Min / max temperature monitoring =11-X2:3 /22.6 PEW760+
X11:34
PT100
X11:15
Min / max temperature monitoring /22.6 PEW760-
X11:35
X11:16 X11:36
PAW752U
X11:17 X11:37
PAW752I
X11:18 X11:38
PAW754U
X11:19 X11:39
Control valve heating medium positioner =11-X2:7 /22.3 PAW754I
X11:20 X11:40
Mana /31.3 Mana
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 32
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-K1
X12:1 X12:21
24V /31.3 1L+ 2L+ /31.3 24V
X12:2 X12:22
Separator operation =01-Q1:34 /14.1 E0.0 A0.0 /18.1 =01-X2:14 Feed valve
X12:3 X12:23
Separator failure =01-F1:22 /14.2 E0.1 A0.1 /18.4 =01-X2:17 Displacem- and filling water
X12:4 X12:24
E0.2 A0.2 /18.3 =01-X2:16 Operating water
X12:5 X12:25
Speed monitoring device =01-T2:4+ /15.2 E0.3 A0.3
X12:6 X12:26
E0.4 A0.4 /18.5 =01-X2:19 Circulation valve
X12:7 X12:27
Water discharge =01-X2:10 /16.3 E0.5 A0.5 /18.6 =01-X2:20 Water discharge valve
X12:8 X12:28
E0.6 A0.6
X12:9 X12:29
LSHH sludge tank =16-K4:14 /25.1 E0.7 A0.7 /26.1 =100-K1:A1 Common failure
X12:10 X12:30
2M /31.3 0V
X12:11 X12:31
3L+ /31.4 24V
X12:12 X12:32
Feed pump operation =11-Q1:14 /21.1 E1.0 A1.0 /14.1 =01-K1:A1 Separator start/stop
X12:13 X12:33
Feed pump failure =11-Q1:98 /21.2 E1.1 A1.1 /21.1 =11-K2:A1 Feed pump start / stop
X12:14 X12:34
E1.2 A1.2
X12:15 X12:35
E1.3 A1.3 /26.3 =100-K2:A1 Sludge tank Level high / high Alarm
X12:16 X12:36
E1.4 A1.4 /26.4 =100-K3:A1 TAH HFO temperature
X12:17 X12:37
E1.5 A1.5 /26.5 =100-K4:A1 TAL HFO temperature
X12:18 X12:38
Spare =16-K4:13 /28.1 E1.6 A1.6
X12:19 X12:39
NAHH separator vibration monitoring =01-X2:13 /17.4 E1.7 A1.7 /19.1 =01-K10:A1 Valve clean-oil discharge
X12:20 X12:40
0V /31.3 1M 3M /31.4 0V
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 33
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-K2
X1:1 X1:21
PEW256V PEW264V
X1:2 X1:22
FI flow measuring =11-10_9_009:2 /23.1 PEW256I V V PEW264I
X1:3 X1:23
PEW256S- A A PEW264S-
X1:4 X1:24
PEW256M+ PEW264M+
X1:5 X1:25
Earth analog /29.1 PEW256M- PEW264M- /29.4 Earth analog
X1:6 X1:26
PEW258V PEW266V
X1:7 X1:27
PEW258I V V PEW266I
X1:8 X1:28
PEW258S- A A PEW266S-
X1:9 X1:29
PEW258M+ PEW266M+
X1:10 X1:30
Earth analog /29.2 PEW258M- PEW266M- /29.5 Earth analog
X1:11 X1:31
PEW260V PEW268V
X1:12 X1:32
PEW260I V V PEW268I
X1:13 X1:33
PEW260S- A A PEW268S-
X1:14 X1:34
PEW260M+ PEW268M+
X1:15 X1:35
Earth analog /29.2 PEW260M- PEW268M- /29.6 Earth analog
X1:16 X1:36
PEW262V PEW270V
X1:17 X1:37
PEW262I V V PEW270I
X1:18 X1:38
PEW262S- A A PEW270S-
X1:19 X1:39
PEW262M+ PEW270M+
X1:20 X1:40
Earth analog /29.3 PEW262M- PEW270M- /29.7 Earth analog
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 34
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-K3
2AO
X1:1
1L+ /31.5 24V
X1:2
X1:3
PAW272 /27.6 =100-X2:24 Clean-oil discharge pressure
X1:4
S+
X1:5
S-
X1:6
Mana /29.8 Earth analog
X1:7
PAW274 /27.8 =100-X2:26 HFO temperature
X1:8
S+
X1:9
S-
X1:10
Mana /29.8 Earth analog
X1:11
X1:12
X1:13
X1:14
X1:15
X1:16
X1:17
X1:18
X1:19
X1:20
1M /31.6 0V
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 35
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-K4
X1:1
1L+
X1:2
E8.0 /27.1 =100-X2:19 HFO daily tank level Low control Change to daily tank
X1:3
E8.1 /27.2 =100-X2:21 HFO daily tank level High control Change to settling tank
X1:4
E8.2 /27.4 =100-X2:23 Remote start / stop NO for stop, NC for start
X1:5
E8.3
X1:6
E8.4
X1:7
E8.5
X1:8
E8.6
X1:9
E8.7 /16.6 =01-13_7_020:14 Sludge discharge flap
X1:10
1M /31.6 0V
X1:11
2L+ /31.7 +24V
X1:12
A8.0 /26.6 =100-K5:A1 Local / remote status
X1:13
A8.1 /26.7 =100-K6:A1 PAL clean-oil discharge pressure
X1:14
A8.2
X1:15
A8.3
X1:16
A8.4
X1:17
A8.5
X1:18
A8.6
X1:19
A8.7
X1:20
2M /31.7 0V
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 36
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EFS 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
600 mm
560 mm 300 mm
0-T01
0-T2
Filter
=00-P1
100-K1
16-K2
01-K11
01-K12
16K1
16K4
01-K10
100-K2
100-K3
100-K4
100-K5
100-K6
16-K3
01-K1
11-K2
0-K1
=16-S1
=16-P1 =16-S2
0-F01
0-F1
01-F1
01-T1
0-F2
01-T2
0-T1
11-T2
1200 mm
1160 mm
0-024M
01-B1
0-24M
0-Q1
11-Q1
100-X2
01-Q1
=0-Q1
I
O
=0-M1
01-X1
11-X1
01-X2
11-X2
16-X2
0-X1
=00-P1 Process display
=0-M1 Filter / fan
=0-Q1 Isolator Cable glands Size
=16-P1 Sludge pump operation
14x M20 incl. 3x spare 8 - 13mm
=16-S1 Sludge pump manual-0-automatic
11x M25 incl. 3x spare 11 - 17mm
=16-S2 Lamp test
3x M32 incl. 1x spare 15 - 21mm
3x M40 incl. 1x spare 19 - 28mm
Bestell-nr.
0005-4050-700
Westfalia Separator AG
order no.
Programm-Nr.
8106-1E40-768
program-no.
Tiefe: __mm
215
depth:
Ausschnittmass: 228x195mm
cutout dimension:
Gewicht: _,__kg
weight:
ACK
245
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator E40
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 38
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & ELU 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
&EFS/11.6
&EFS/11.6
&EFS/11.6
Cross reference
0V
PE
=00-P1
Target internal
-PE
-T2
Bridges
=0+-24M
Terminal number
1
2
Control voltage DC
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =0+-24M
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 39
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMA 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
&EFS/10.6
&EFS/10.6
&EFS/10.6
Cross reference
x2
PE
=16-P1
Target internal -T01
-PE
Bridges
=0+-024M
Terminal number
1
2
Control voltage DC before isolator
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =0+-024M
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 40
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMA 62 Bl./Sh.
=0+-PE
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
=Customer+L-X
Editor
&EFS/10.1
Tested
Incoming 1 480V AC PE
PE
-X1_W1
PE
_-J 4x25 mm²
PE
Incoming 2 120V AC PE &EFS/10.2
PE
1
-W001
PE
_-J 3x1,5 mm²
GUE/PLE
19.07.2012
07.09.2012/KA
-SC
Earthing screen PE &EFS/10.3
SC
SC
-1M
Kunde:
&EFS/10.4
Project:
Projekt:
Earthing mounting plate 1 PE PE
PE
Customer:
-PE
GN/YE
2
-1T
Earthing door 1 PE PE &EFS/10.4
PE
-PE
GN/YE
Esmeraldas II
-1G
Earthing cabinet 1 PE PE &EFS/10.5
PE
-PE
GN/YE
-M1
= PE &EFS/11.2
PE
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
GN/YE
4
Separator
L
M
1~
GEA Westfalia
PE N
N
-PE
Control voltage DC PE &EFS/11.6
= PE &EFS/11.6
-24M 2
Benennung/Description:
5
=01-10_7_014
Valve clean-oil discharge PE &EFS/19.5
8
=01-X0_W3
PE
-PE
.-J 7x1 mm²
=01-X1_W2
PE
T2 U1
V1
V1
Θ
M
6
3~
T1 W1
W1
PE
T2
T1
=01+HFO2-X2
Valve clean-oil discharge limit switch closed to HFO2 PE &EFS/19.9
PE
Sprache:
PE
=01-WG021
PE
Language:
-PE
.-J 7x1 mm²
7
=16+HFO2-X2
LSHH sludge tank to HFO2 PE &EFS/25.1
PE
PE
=16-WG010
PE
-PE
.-J 3x1 mm²
en
=01+JB-1X10
Water discharge PE &EFS/16.3
PE =01-X1_W9
PE
=01-X1_W5
Zeichnungs Nr.:
PE
-PE
.-J 7x1 mm²
8
=11-10_3_001
Feed pump PE &EFS/20.1
PE
U1 =11-X1_W3
PE
-PE
_-J 4x2,5 mm²
U1
V1
M
W1
V1
8106-2011-061
PE
As built +
Rev.05 =
W1
DCC
& EMA
9
Bl./Sh.
62 Bl./Sh.
41
0 1 2 3 4 5 6 7 8 9
&EFS/26.9
&EFS/27.4
Cross reference
Target internal
Bridges
=0+-PE
Terminal number
PE
PE
=100-X1_W20
=100-X1_W19
.-J 18x1,5 mm²
.-J 7x1,5 mm²
PE PE
PE PE
PE
+DCS-X
Remote start / stop NO for stop, NC for start
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =0+-PE
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 42
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMA 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
&EFS/10.3
&EFS/22.6
&EFS/22.3
&EFS/22.4
&EFS/22.7
&EFS/27.8
&EFS/27.8
&EFS/27.7
Cross reference
-SC
-SC
-SC
-SC
-SC
Bridges
=0+-SC
SC
SC
SC
SC
SC
SC
SC
SC
Terminal number
PE SC SC SC
PE SC SC SC
-PE
=11-X2
=100-X2
=11-X2
-SC
Control valve heating medium positioner
HFO temperature
Earthing screen
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =0+-SC
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 43
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMA 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
&EFS/10.2
&EFS/10.2
&EFS/11.1
&EFS/11.1
&EFS/11.1
&EFS/11.2
&EFS/12.1
&EFS/12.1
&EFS/12.1
Cross reference
vb
4
=01-X1
Target internal -F01
-F01
-F2
-T1
Bridges
=0+-X1
Terminal number
1
9
_-J 3x1,5 mm²
21
M
1~
PE
PE
L
22
=Customer+L-X
-M1
-PE
-S01
Emergency stop external
Control voltage AC
Control voltage AC
Spare
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =0+-X1
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 44
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMA 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
&EFS/10.1
&EFS/10.1
&EFS/10.1
Cross reference
6
Target internal -Q1
-Q1
-Q1
Bridges
=0+-XQ1
Terminal number
2
6
_-J 4x25 mm²
-X1_W1
1 2 3
L1 L2 L3
L1
=Customer+L-X
Incoming 1 480V AC
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =0+-XQ1
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 45
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMA 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
&EFS/13.1
&EFS/13.1
&EFS/13.1
&EFS/13.8
&EFS/13.7
Cross reference
13
Target internal
=0-X1
-Q1
-Q1
-Q1
-F1
Bridges
=01+-X1
Terminal number
1
5
_-J 4x16 mm²
-X1_W2
1 2 3
U1 V1 W1 T2 T1 PE
W1
U1
V1
PE
M
3~
Θ
T2
T1
-10_1_001
Separator
Spare
=
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =01+-X1
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 46
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMA 62 Bl./Sh.
=01+-X2
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
-10_1_001
Editor
&EFS/13.3
Tested
PTC-feeler separator 1
T1
1
-F1 T1
-X1_W13 &EFS/13.3
= .-O 2x1 mm² 2
T2
1
2
T2 U1
-F1 T2
GUE/PLE
19.07.2012
U1
V1
Θ
M
3~
07.09.2012/KA
T1 W1
V1
PE
W1
Kunde:
Project:
Projekt:
PE
Customer:
2
+JB-1X10
Speed monitoring device 3 &EFS/15.2
1
1
-T2 1+
= 4 &EFS/15.2
Esmeraldas II
2
-T2 2-
Clean-oil discharge pressure 5 &EFS/16.1
4
3
=0-T2 L+
&EFS/16.1
3
4
=00-K1 X11:6
1
-X1_W9 &EFS/16.2
Sludge room monitoring .-J 7x1 mm² 7
3
= 8 &EFS/16.2
6
5
=00-K1 X11:9
Spare 9 &EFS/16.3
=00-K1 X12:7
-13_7_020
Sludge discharge flap 11 &EFS/16.5
13
1
-13_7_020 13
14 13
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
-WG001 &EFS/16.6
4
Separator
= .-O 2x1 mm² 12
14
2
GEA Westfalia
-13_7_020 14
+JB-1X10
NAHH separator vibration monitoring 13 &EFS/17.4
10
1
10
-10_7_006 - +
Feed valve 14 &EFS/18.1
+
1
=00-K1 X12:22
-X1_W4 &EFS/18.1
Benennung/Description:
-
=0-24M 1
+JB-1X10
Operating water 16 &EFS/18.3
12
2
=00-K1 X12:24
=00-K1 X12:23
= 18 &EFS/18.4
12
-X1_W5 &EFS/18.5
Circulation valve .-J 7x1 mm² 19
16
4
=00-K1 X12:26
6
=00-K1 X12:27
= 21 &EFS/18.7
17
6
=11-X2 8
-10_7_014
Valve clean-oil discharge 22 &EFS/19.2
1
1
=0-T01 L+
Valve clean-oil discharge limit switch open 23 &EFS/19.2
2
Sprache:
2
Language:
-K11 A1
7
-X0_W3 -K12 A1
.-J 7x1 mm²
Valve clean-oil discharge 25 &EFS/19.5
6
4
-K10 14
en
= 26 &EFS/19.5
7
5
=0-024M 1
+HFO2-X2
Valve clean-oil discharge from HFO2 27 &EFS/19.7
Drawing No.:
22
1
Zeichnungs Nr.:
-K10 14
&EFS/19.7
8
= 28
23
2
=16-X2 2
Valve clean-oil discharge limit switch open 29 &EFS/19.8
24
-K11 24
22
-WG021 &EFS/19.8
Valve clean-oil discharge limit switch closed .-J 7x1 mm² 30
25
4
-K12 24
Valve clean-oil discharge limit switch closed to HFO2 31 &EFS/19.9
26
5
8106-2011-061
-K12 23
As built +
Rev.05 =
= 32 &EFS/19.9
27
DCC
6
& EMA
9
Bl./Sh.
62 Bl./Sh.
47
=01+JB-1X10
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
-19_7_003/B
Editor
&EFS/18.3
Tested
Operating water PE PE
PE
-WG105
PE
-PE
.-J 3x1,5 mm²
1
+SB-1X20
GUE/PLE
PE &EFS/16.3
Water discharge PE
19.07.2012
PE:PE
-WG121
PE
=0-PE PE
PE
.-J 5x1,5 mm²
07.09.2012/KA
-10_9_018
Speed monitoring device - + 1 &EFS/15.2
+
-X2 3
BN
Kunde:
-WG101 &EFS/15.2
Project:
Projekt:
-
= .-O 2x0,34 mm² 2
Customer:
-X2 4
BU
2
+SB-1X20
Clean-oil discharge pressure 3 &EFS/16.1
1
1
-X2 6
= 4 &EFS/16.1
Esmeraldas II
2
-X2 5
= 5 &EFS/16.1
1
-WG121
.-J 5x1,5 mm²
&EFS/16.2
4
3
-X2 8
Water discharge 7 &EFS/16.3
5
4
-X2 10
3
-10_9_020
NAHH separator vibration monitoring 8 &EFS/17.1
1
BN
= 9 &EFS/17.3
3
BK
-WG104 &EFS/17.4
= 10
4
= 11 &EFS/17.1
2
BU
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
4
Separator
GEA Westfalia
-19_7_003/B
Operating water - + 12 &EFS/18.3
+
-X2 16
BN
-WG105 &EFS/18.3
-
-19_7_003/A
- + &EFS/18.4
-
-WG106 &EFS/18.4
Benennung/Description:
= 15
+
-X2 17
BN
+SB-1X20
Circulation valve 16 &EFS/18.5
8
1
-X2 19
Water discharge valve 17 &EFS/18.7
10
2
-X2 21
-WG122 &EFS/18.6
= .-J 4x1,5 mm² 18
11
3
-X2 20
= PE &EFS/18.7
PE:PE
PE
=0-PE PE
6
-19_7_003/A
Displacem- and filling water PE PE &EFS/18.4
PE
-WG106
PE
-PE
.-J 3x1,5 mm²
Sprache:
Language:
7
en Drawing No.:
Zeichnungs Nr.:
8
8106-2011-061
As built +
Rev.05 =
DCC
& EMA
9
Bl./Sh.
62 Bl./Sh.
48
=01+SB-1X20
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
-11_9_002
I
1
Editor
&EFS/16.1
Tested
Clean-oil discharge pressure 1
2
+JB-1X10 3
WH
2
-WG201 &EFS/16.1
= 2
1
.-O 2x0,34 mm²
1
+JB-1X10 4
BK
GUE/PLE
19.07.2012
07.09.2012/KA
-10_9_014
I
1 &EFS/16.2
Sludge room monitoring 3
1
BK
2
-WG202 &EFS/16.2
= 4
2
.-O 2x0,34 mm²
+JB-1X10 6
P
WH
Kunde:
Project:
Projekt:
Customer:
-10_9_013
Water discharge 5 &EFS/16.3
+
A/Q
+JB-1X10 7
2
BK
= A/Q 6 &EFS/16.3
+
-WG203
BN
.-O 3x0,75 mm²
- &EFS/16.3
-
= 7
Esmeraldas II
GY
-10_7_010
- + &EFS/18.5
+
+JB-1X10 16
BN
-WG204 &EFS/18.5
-
= .-J 3x0,75 mm² 9
BU
3
-10_7_011
- + &EFS/18.7
-
-WG205 &EFS/18.6
= 11
+
-10_7_010
Circulation valve PE PE &EFS/18.6
PE
-WG204
PE
+JB-1X10 PE
.-J 3x0,75 mm²
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
4
Separator
GEA Westfalia
-10_7_011
Water discharge valve PE PE &EFS/18.7
PE
-WG205
PE
+JB-1X10 PE
.-J 3x0,75 mm²
Benennung/Description:
5
Sprache:
Language:
7
en Drawing No.:
Zeichnungs Nr.:
8
8106-2011-061
As built +
Rev.05 =
DCC
& EMA
9
Bl./Sh.
62 Bl./Sh.
49
0 1 2 3 4 5 6 7 8 9
&EFS/20.1
&EFS/20.1
&EFS/20.1
Cross reference
6
Target internal -Q1
-Q1
-Q1
Bridges
=11+-X1
Terminal number
1
3
_-J 4x2,5 mm²
-X1_W3
1 2 3
U1 V1 W1 PE
W1
U1
V1
PE
M
3
-10_3_001
Feed pump
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =11+-X1
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 50
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMA 62 Bl./Sh.
=11+-X2
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
-10_9_008
Editor
&EFS/22.5
Tested
Product temperature control 1
1
1
-T1 3
= 2 &EFS/22.5
Θ
1
2
2 1 -T1 4
GUE/PLE
-X1_W12 &EFS/22.6
Min / max temperature monitoring 3
3
.CY-O 4x1 mm²
19.07.2012
3
=00-K1 X11:14
07.09.2012/KA
= 4 &EFS/22.6
4
4
=00-K1 X11:15
-X1_W14
Kunde:
&EFS/22.4
Project:
Projekt:
Control valve heating medium positioner SC
SC
Customer:
-X1_W14 =0-SC SC
SC
.CY-O 2x1 mm²
2
-X1_W12
Min / max temperature monitoring SC &EFS/22.7
SC
-X1_W12 =0-SC SC
SC
.CY-O 4x1 mm²
Esmeraldas II
-10_9_009
I
1 &EFS/23.1
FI flow measuring 5
1
1
=01-X2 11
-WG004 &EFS/23.1
2
.-O 2x1 mm²
2
=00-K2 X1:2
P
3
-10_7_012 +
Control valve heating medium positioner 7 &EFS/22.3
+
1
=00-K1 X11:19
-
-X1_W14 &EFS/22.3
-
=01-X2 21
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
4
Separator
GEA Westfalia Benennung/Description:
5
Sprache:
Language:
7
en Drawing No.:
Zeichnungs Nr.:
8
8106-2011-061
As built +
Rev.05 =
DCC
& EMA
9
Bl./Sh.
62 Bl./Sh.
51
=16+-X2
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
-90_9_003
Editor
&EFS/24.4
Tested
LSL sludge tank level min. 1
4
1
-K2 A1
3 4 -X0_W7 &EFS/24.4
= 2
3
.-O 2x1 mm²
1
2
=01-X2 28
GUE/PLE
= 3 &EFS/24.4
19.07.2012
=01-X2 26
07.09.2012/KA
LSH sludge tank level max. 4 &EFS/24.6
-90_9_002
= 5 &EFS/24.5
4
1
-K3 A1
Kunde:
3 4 -X0_W6 &EFS/24.6
Project:
Projekt:
= 6
3
.-O 2x1 mm²
Customer:
2
-90_9_001
LSHH sludge tank level max. / max. 7 &EFS/24.7
1
1
1 2 -X0_W5 &EFS/24.7
= 8
Esmeraldas II
.-O 2x1 mm²
2
-K4 A1
= 9 &EFS/24.8
-98_7_002 - + &EFS/24.9
1
-X0_W4
.-O 2x1 mm²
+
3
+HFO2-X2
LSHH sludge tank 12 &EFS/25.1
1
1
1
-WG010 -K4 24
.-J 3x1 mm²
-98_7_002 - +
Valve pneumatic sludge pump 11 &EFS/24.9
+
2
-X0_W4 -K1 34
.-O 2x1 mm²
-
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
4
Separator
GEA Westfalia
+HFO2-X2
LSHH sludge tank to HFO2 13 &EFS/25.1
2
2
2
-WG010 -K4 23
.-J 3x1 mm²
Benennung/Description:
5
Sprache:
Language:
7
en Drawing No.:
Zeichnungs Nr.:
8
8106-2011-061
As built +
Rev.05 =
DCC
& EMA
9
Bl./Sh.
62 Bl./Sh.
52
=100+-X2
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
+DCS-X
Editor
&EFS/26.1
Tested
Common failure 1
1
-K1 21
= 2 &EFS/26.1
1
2
-K1 24
GUE/PLE
Separator operation 3 &EFS/26.2
19.07.2012
3
=01-Q1 44
07.09.2012/KA
= 4 &EFS/26.2
4
=01-Q1 43
Sludge tank Level high / high Alarm 5 &EFS/26.3
5
-K2 11
Kunde:
&EFS/26.3
Project:
Projekt:
= 6
Customer:
-K2 14
TAH HFO temperature 7 &EFS/26.4
7
-K3 11
2
= 8 &EFS/26.4
8
-K3 14
TAL HFO temperature 9 &EFS/26.5
Esmeraldas II
9
-X1_W19 -K4 11
.-J 18x1,5 mm²
= 10 &EFS/26.5
10
-K4 14
&EFS/26.6
11
-K5 11
= 12 &EFS/26.6
12
-K5 14
3
-K6 14
Sludge tank Low alarm 15 &EFS/26.9
15
=16-K2 21
= 16 &EFS/26.9
16
=16-K2 24
= 17 &EFS/26.9
17
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
&EFS/27.1
4
Separator
HFO daily tank level Low control Change to daily tank 18
1
GEA Westfalia
=11-X2 5
= 19 &EFS/27.1
2
=00-K4 X1:2
HFO daily tank level High control Change to settling tank 20 &EFS/27.2
3
-X1_W20 &EFS/27.2
= .-J 7x1,5 mm² 21
4
=00-K4 X1:3
Remote start / stop NO for stop, NC for start 22 &EFS/27.4
5
&EFS/27.4
Benennung/Description:
= 23
5
=00-K4 X1:4
Clean-oil discharge pressure 24 &EFS/27.6
1
=00-K3 X1:3
= 25 &EFS/27.6
2
=11-X2 8
-X1_W18
=00-K3 X1:7
= 27 &EFS/27.8
4
= SC &EFS/27.8
=0-SC SC
6
Sprache:
Language:
7
en Drawing No.:
Zeichnungs Nr.:
8
8106-2011-061
As built +
Rev.05 =
DCC
& EMA
9
Bl./Sh.
62 Bl./Sh.
53
0 1 2 3 4 5 6 7 8 9
Cable layout
Cable name /page.path Source (from) Target (to) Cable type Wires total Wires used Cross-section Length Cable gland / clamping range Remark
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Cable layout
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 54
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Cable layout
Cable name /page.path Source (from) Target (to) Cable type Wires total Wires used Cross-section Length Cable gland / clamping range Remark
=100-X1_W19 &EFS/26.1 +DCS-X =100-X2;=0-PE .-J 18x 18 1,5 mm² M40x1,5 / 19-28mm
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Cable layout
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 55
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Instructions for installation
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 56
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
FU
FC
=..-U.
Generelle Information zum Potentialausgleich.
Die Informationen auf diesem Blatt sind nicht
kundenspezifisch angepasst.
IP54
PE-Schiene
protective earth - rail
IDM
≥25 mm²
GN YE
≥10 mm²
GN YE
PA
PA7
PA6
PA5
PA4
PA3
PA2
PA1
≥10 mm²
GN YE
equipotential bonding building
Potentialausgleich Gebäude
≥25 mm²
GN YE
Fundamenterder
foundation earth
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Potential equalization Separator
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 57
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EMB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Parts list
=0-F01 &EFS/10.6 0005-4560-160 23750 Sicherungsautomat C 6A, 2 pol, C60N Groupe Schneider
Circuit breaker
=0-024M &EFS/10.6 0005-4708-890 1031400000 Durchgangs-Reihenklemme, 1,5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 1,5 mm², screw connection, Wemid, dark-beige, TS 35
=0-Q1 &EFS/10.1 0005-1837-060 LV429631 Compact Leistungsschalter, NSX100F+TM80D 3P3D 56-80A, 36KA/415VAC Groupe Schneider
Compact circuit breaker
=0-Q1 &EFS/10.1 Konsole 90X160X100 Konsole 90X160X100 Konsole verzinkt Zimmermeyer
Bracket zinced
=0-Q1 &EFS/10.1 0005-1438-200 29450 Hilfsschalter OF/SD/SDE/SDV für NS/NSX100..630 Groupe Schneider
auxiliary contact
=0-Q1 &EFS/10.1 0005-1837-160 LV429515 Klemmenabdeckung kurz, 3-polig für NSX100/160/250 Groupe Schneider
Cover of terminals, short
=0-Q1 &EFS/10.1 0005-1837-180 LV429338 Drehantrieb mit Türkupplung für NSX 100...250, Standard, schwarzer Griff Groupe Schneider
Front-rotating drive, black
=0-T01 &EFS/10.5 0005-1407-020 6EP1333-2AA01-0AA0 Einphasennetzgeraet Prim.: 120/230V, 50/60Hz, Sec.: 24VDC, 5A Siemens
Single phase power supply
=0-X1 &EFS/10.2; 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
=0-F1 &EFS/11.1 0005-1872-670 3RV2411-0KA10 Leistungsschalter, 0,9...1,25A, BGR S00, für den Transformatorschutz Siemens
Circuit-breaker, 0.9...1.25A, size S00, transformer protection
=0-F2 &EFS/11.1 0005-1428-000 23732 Sicherungsautomat C 6A, 1 pol, C60N Groupe Schneider
Circuit breaker
=0-M1 &EFS/11.1 0005-1409-390 116 43 10 1 055 Filterlüfter, 207-253V, 50/60Hz, 45/39W, 231/265m³/h Pfannenberg
Filter fan
=0-M1 &EFS/11.1 0005-1409-240 117 40 00 1 055 Austrittsfilter Pfannenberg
Discharge filter
=0-24M &EFS/11.6 0005-4708-890 1031400000 Durchgangs-Reihenklemme, 1,5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 1,5 mm², screw connection, Wemid, dark-beige, TS 35
=0-T1 &EFS/11.1 0005-0551-490 700199 Steuerspannungstransformator, Prim.: 200-560VAC, Sek.: 115/230V, 400VA Ismet
Control voltage transformer, prim.: 200-560 VAC, sec.: 115/230 V, 400 VA
=0-T2 &EFS/11.5 0005-1407-020 6EP1333-2AA01-0AA0 Einphasennetzgeraet Prim.: 120/230V, 50/60Hz, Sec.: 24VDC, 5A Siemens
Single phase power supply
=0-K1 &EFS/12.6 0005-4033-110 2966207 Relais Einzelkontakt,PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Phoenix Contakt
Relay for single contact, PLC interface, miniature relay with power contact, 1 change-over
=0-S01 &EFS/12.1 0005-0081-030 3SB3801-0DF3 Pilzdrucktaster Gehäuse, verrastend, mit Schutzkragen, 1NC, 2x M20 Siemens
Mushroom push button box
=0-S01 &EFS/12.1 0005-4487-930 70-20-060-000-13-041 Verschraubung Polyamid, M20x1,5, RAL 7032, halogenfrei, d=8-13mm Jacob
Screw connection polyamide, M20x1,5, RAL 7032, halogen free, 8-13mm
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Parts list
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 58
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EPB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Parts list
=0-S01 &EFS/12.1 0013-0132-900 50225 PA7035 Gegenmutter Polyamid, M25x1,5, RAL 7035 Jacob
Counter nut polyamide, M25x1,5, RAL 7035
=01-B1 &EFS/13.1 0005-0924-090 TAID10C100 Stromwandler, 100/1A IME
Current transformer
=01-F1 &EFS/13.4 0005-1100-070 3RN1010-1CM00 THERMISTOR-MOTORSCHUTZ, STANDARD-AUSWERTEGERÄT, AUTO, 1S+1OE, AC 230V Siemens
THERMISTOR MOTOR PROTECTION EVALUATION UNIT AUTO, 1NO+1NC, AC 230V
=01-Q1 &EFS/13.8 0005-4382-270 3RT1044-1AL20 Leistungsschütz, 30KW/400V, 230VAC 50/60HZ, 3POLIG, BGR. S3, SCHRAUBANSCHLUSS Siemens
CONTACTOR, AC-3 30 KW/400 V, AC 230V 50/60HZ 3-POLE, SIZE S3, SCREW
=01-Q1 &EFS/13.8 0005-4399-050 3RH1921-1HA31 HILFSSCHALTERBLOCK, 31, 3S+1OE, DIN EN 50012, 4POLIG, FÜR MOTORSCHÜTZE, BGR. Siemens
AUXILIARY SWITCH BLOCK, 31, 3NO+1NC
=01-Q1 &EFS/13.8 0005-0915-170 3RT1936-1CD00 RC-GLIED, AC 127...240V, UEBERSPANNUNGSBEGRENZER, ZUM AUFSETZEN, BGR. S2, S3 Siemens
RC-ELEMENT, AC 127...240 V, SURGE SUPPRESSOR
=01-T1 &EFS/13.2 0005-3482-070 1073490000 Stromüberwachung, 0...1 A AC/ 0...5 A AC/ 0...10 A AC , 1 , 0(4)...20 mA , 0...10 V , 1 Weidmueller
Current monitoring, 0 - 1 A AC/0 - 5 A AC/0 - 10 A AC, 1, 0(4) - 20 mA , 0 - 10 V , 1 screw
=01-X1 &EFS/13.1 1028800000 1028800000 Durchgangs-Reihenklemme, 35 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal
=01-X1 &EFS/13.7; 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
=01-X2 &EFS/13.3; 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
=01-K1 &EFS/14.1 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=01-T2 &EFS/15.1 0005-4509-000 KCD2-E2 Sensor-Endstufenklemme, Eingang für NAMUR-Sensoren, 24V DC Speisespannung Pepperl & Fuchs
Converters- Amplifier to convert NAMUR sensor
=01-K10 &EFS/19.1 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=01-K11 &EFS/19.3 0005-1870-200 3RH2140-1JB40 Koppelhilfsschütz, 4S DC 24V, mit Diode Siemens
Coupling contactor relay, 4NO DC 24V, integrated diode
=01-K12 &EFS/19.4 0005-1870-200 3RH2140-1JB40 Koppelhilfsschütz, 4S DC 24V, mit Diode Siemens
Coupling contactor relay, 4NO DC 24V, integrated diode
=01-X2 &EFS/19.5 0005-1442-890 1011300000 Sicherungs-Reihenklemme, 6 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Fused terminal block, 6 mm², screw connection, Wemid, dark-beige, TS 35
=01-X2 &EFS/19.5 0005-0541-020 5X20MM 0,5A MT Feinsicherung 5x20, 0,5A/MT, 250V Plenge
Miniature fuse
=11-Q1 &EFS/20.0 0005-1730-000 LUB12 Motorabgang Grundgerät - 12A AC-43, 440V Groupe Schneider
Motor outlet of basic unit - 12 A AC-43, 440 V
=11-Q1 &EFS/20.0 0005-1730-130 LUCA12FU Steuereinheit Standard LUCA - class 10, 3-12A 110-220V DC/AC Groupe Schneider
Standard control unit LUCA - class 10, 3-12A 110-220V DC/AC
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Parts list
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 59
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EPB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Parts list
Parts list
=100-K4 &EFS/26.5 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=100-K5 &EFS/26.6 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=100-K6 &EFS/26.7 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=100-X2 &EFS/26.1.. 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
=0-SC &EFS/27.7; 1600480000 1600480000 Klemmbügel für Schirmanschluss, zur Montage auf Sammelschiene 10x3mm Weidmueller
Retaining clip for shield connection
=00-P1 &EFS/30.1 0005-4050-710 6AV6642-5DA10-1AC0 Prozessanzeige OP177B, Farb-Display, 24VDC Siemens
Process display OP177B
=00-P1 &EFS/30.1 6AV6671-1CB00-0AX2 6AV6671-1CB00-0AX2 Speicherkarte, 128 MByte, MMC Siemens
Memory card
=00-K1 &EFS/31.1 0005-4050-720 6ES7313-5BF03-0AB0 Zentralbaugruppe, CPU 313C Siemens
CPU modul
=00-K1 &EFS/31.1 0005-4050-760 6ES7390-1AE80-0AA0 Profilschiene, 480mm Siemens
Profile bar, 480mm
=00-K1 &EFS/31.1 0005-4050-722 6ES7392-1AM00-0AA0 Frontstecker, 40POLIG Siemens
Front connector, 40 PIN
=00-K1 &EFS/31.1 6ES7953-8LG20-0AA0 6ES7953-8LG20-0AA0 Speicherkarte, 128 kByte, MMC Siemens
Memory card, 128 kByte, MMC
=00-K1 &EFS/31.1 6ES7901-0BF00-0AA0 6ES7901-0BF00-0AA0 MPI-Kabel zur Verbindung von SIMATIC S7 und PG über MPI, 5M Siemens
MPI cable
=00-K2 &EFS/31.4 6ES7331-1KF02-0AB0 6ES7331-1KF02-0AB0 Analogbaugruppe Eingang, SM 331, 8AE, 13BIT Siemens
Analog module input, SM 331, 8AI, 13BIT
=00-K2 &EFS/31.4 0005-4050-722 6ES7392-1AM00-0AA0 Frontstecker, 40POLIG Siemens
Front connector, 40 PIN
=00-K3 &EFS/31.5 0005-4281-010 6ES7332-5HB01-0AB0 Analogbaugruppe Ausgang, SM 332, 2AA, U/I, 11/12BIT Siemens
Analog Module Output, SM 332, 2AO, U/I, 11/12BIT
=00-K3 &EFS/31.5 0005-4050-731 6ES7392-1AJ00-0AA0 Frontstecker, 20POLIG Siemens
Front connector, 20 PIN
=00-K4 &EFS/31.6 0005-4050-730 6ES7323-1BH01-0AA0 Digitalbaugruppe Ein-/Ausgang, SM 323, 8DE/DA, DC 24V, 0.5A Siemens
Digital Module Input/Output, SM 323, 8DI/DO, DC 24V, 0.5A
=00-K4 &EFS/31.6 0005-4050-731 6ES7392-1AJ00-0AA0 Frontstecker, 20POLIG Siemens
Front connector, 20 PIN
-Cabinet &ELU/37.1 1260500 1260500 Kompakt-Schaltschrank AE, lackiert RAL 7035, eintürig mit Montageplatte Rittal
Compact enclosure AE, painted RAL 7035, single door with mounting plate
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Parts list
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 61
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EPB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Parts list
Date 19.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Parts list
HFO Separator Double Unit (HFO 1) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 62
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-061 & EPB 62 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Language : en
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Title- / cover sheet
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 1
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EAA 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Table of contents
Document type Page Page description Plant Mounting place Date Editor
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Table of contents
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 2
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EAB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Table of contents
Document type Page Page description Plant Mounting place Date Editor
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Table of contents
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 3
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EAB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Table of contents
Document type Page Page description Plant Mounting place Date Editor
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Table of contents
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 4
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EAB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Revision overview
Revision name Revision comment Revision on the basis of change Page name Author Date
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Revision overview
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 6
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EBH 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Structure indicator
Complete name Labelling Structure descprition Complete name Labelling Structure descprition
=0 Plant Incoming
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Structure indicator
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 7
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EDB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Instruction / specification
Classification ...
Interface:
Incoming:
Mains frequency 60 Hz
Rotary field
Incoming redundant NO
Control voltages:
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Information-sheet
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 8
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EDB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Wiring
Electrical circuits Conductor Colour Cross-section Electrical circuits Conductor Colour Cross-section
Main circuits 480V AC L1 Black ≥ 1,5mm² Control voltage 220V AC L Red ≥ 0,75mm²
M Brown "
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Information-sheet
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 9
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EDB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
480V AC
L1 / 13.0
L2 / 13.0
L3 / 13.0
480V AC
L1.2 / 20.0
L2.2 / 11.0
L3.2 / 11.0
12
14
1
-Q1
/25.1 11
56-80A
In: 74A
I> I> I>
2
Data incoming:
-PE -PE -SC -PE -PE -PE
Min. Cross-section:
25 mm²
-X2_W1
Pre-fuse:
_-J NH 80A
4x25 mm²
PE
PE
PE
Ambient temperature:
~45 °C
-1M -1T -1G
PE
L1
L2
L3
=Customer
U: 480V AC
+L-X
Earthing cabinet 1
-
Earthing door 1
f: 60 Hz
P: ~33 kW
Incoming Earthing screen
Icn: 36 kA
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 0
Editor GUE/PLE
Customer:
Separator Incoming
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 10
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
480V AC 480V AC
10.9 / L2.2 L2.2 / 20.0
10.9 / L3.2 L3.2 / 20.0
220V AC
L.A / 13.4
N.A / 12.0
220V AC
L.X / 12.0
1
5
-F1 N.X /
0,9...1,25A
EW:0,97A
I> I> I>
2
6
480V AC
480V AC
N/L2
L1
-T1 A F C K -T2
INPUT
400VA 120/230VAC GEA
24VDC/5A power
GND
OFF
ON
ua va PE ub vb
220V AC
220V AC
A
B
OUTPUT
-PE
L+
L+'
PE
M'
M.A / 13.2
-PE
M.K / 27.0
M.R / 14.0
2
-24M
1
-F2
2
C6A
-PE
M.T / 29.0
M.X / 18.0
24V DC
L+.A / 12.7
24V DC
L+.K / 30.0
24V DC
L+.X / 16.0
24V DC
L+.T / 29.0
1
-X1
-PE
-PE
N
L
-M1
M
45/39W 1~
Cabinet fan
PE
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 0
Editor GUE/PLE
Customer:
Separator Control voltage
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 11
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
220V AC 220V AC
11.9 / L.X L.X /
220V AC
1L.X / 13.4
220V AC
1L.A / 20.4
7
-X1
24V DC 24V DC
11.9 / L+.A L+.A / 13.2
11
-K1
12
14
/12.6
29
X11
E2.7
/31.5
=00-K1
Separator
emergency stop
A1
-K1
A2
11.9 / N.A N.A / 13.4
Remove link in case of
an external
8
emergency stop!
(optional) -X1
-X2_W17
.-O
2x1 mm²
21
14
11 /12.8
12
-S01
22
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 0
Editor GUE/PLE
Customer:
Separator Emergency stop
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 12
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
=00-K1
4-20mA = 0-50A
/31.4
PEW752I
X11
13
-F1
14
/13.4
11
1
-Q1 -K1
-T1
2
12
14
/13.8 /14.1
*0_9_011
7+
2
S1
Input
8
0-1A
-B1
3
Output
9-
S2
100/1A 0/4-20mA
A1
A1
T1
-F1 M -Q1
T2
A2
A2
12.9 / N.A N.A / 20.4
-PE
Link remove at
connection of an
sludge discharge flap!
1
5
(optional)
-X1 -X2 -X1
-X2_W2 -X2_W13
_-J .-O
4x16 mm² 2x1 mm²
Anti-clockwise rotation
W1
U1
V1
PE
13 14 /13.8 1 2 /13.1
M 21 22 /14.2 3 4 /13.1
20_1_001 3~ 5 6 /13.1
13 14
26,0kW/41,0-43,0A Θ
21 22
T2
T1
33 34 /14.1
43 44 /25.2
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 13
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
13.3 / L+.A L+.A / 15.0
33
21
-Q1 34 -F1
22
/13.8 /13.4
2
3
X12 X12
E0.0 E0.1
/32.4 /32.4
=00-K1 =00-K1
Separator Separator
operation failure
=00-K1
/32.5
A1.0
X12
32
A1
-K1
A2
14
11 /13.8
12
Separator
start/stop
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 14
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
14.9 / L+.A L+.A / 21.0
13.3 / M.A
=00-K1
0-6800 r.p.m.
/32.4
E0.3
X12
-T2 5
4+
6-
24VDC
5+
1+
2-
3
-X2
-X2_W9
.-J
7x1 mm²
/16.1
+JB
-1X10 1 2
+JB-WG101
.-O
2x0,34 mm²
+
20_9_018
SI
-
+ BN = brown
- BU = blue
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator speed measuring
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 15
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
=00-K1 =00-K1
4-20mA 4-20mA
/31.4 /31.4
PEW754I PEW756I
X11 X11
=00-K1 =00-K4
6
9
/32.4 /35.5
E0.5 E8.7
X12 X1
9
24V DC 24V DC
11.9 / L+.X L+.X / 19.0
-PE
10
11
12
5
-X2 9
-X2_W9 -WG001
.-J .-O
7x1 mm² 2x1 mm²
/15.1
+JB
L+_1X10 / 17.1
PE
4
-1X10 PE
+JB-WG121
.-J
5x1,5 mm²
+SB
PE_1X20 / 18.6
M_1X20 / 18.5
2
-1X20
13
+
1
23_7_020
21_9_002 I 20_9_014 I 20_9_013
14
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator signals
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 16
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
=00-K1
/32.4
E1.7
X12
19
13
-X2
-X2_W5
.-J
7x1 mm²
/18.3
+JB 16.3 / L+_1X10
M_1X10 / 18.3
-1X10 8 11 9 10
+JB-WG104
_CY-O
4x0,75 mm²
SC
1
20_9_020
PCH 1220
+24V DC
0V
-D1
Relay
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator vibro
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 17
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24
23
26
27
11.9 / M.X M.X / 22.0
-PE
14
15
16
17
18
19
20
21
-X2
-X2_W5
.-J
7x1 mm²
/17.4
+JB
17.1 / M_1X10
-PE -PE
12
13
15
14
16
18
17
PE
-1X10 PE PE -1X10 PE
+JB-WG122
.-J
4x1,5 mm²
+SB
16.3 / M_1X20
16.3
PE_1X20
11
10
PE
PE
8
9
-1X20 PE PE
PE
PE
PE
PE
+
+
20_7_006 29_7_003/B 29_7_003/A 20_7_010 20_7_011
-
-
-
Feed valve Operating water Displacem- and Circulation valve Water discharge valve
filling water
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator valves
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 18
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
16.9 / L+.X L+.X / 23.0
22
23
11
-K10
12
14
/19.1
A1
-K10
A2
-PE
22
23
24
25
26
27
-X2
-WG021
.-J
7x1 mm²
+HFO1
PE
27
28
29
30
31
32
8106-2011-061
-X2
24
24
14
11 /19.6 -K11 -K12
12
23
23
Valve Valve Valve clean-oil Spare
clean-oil discharge clean-oil discharge limit switch Valve clean-oil
discharge to HFO1 open from HFO1 discharge limit
switch closed from HFO1
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 01
Editor GUE/PLE
Customer:
Separator Separator clean-oil discharge
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 19
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
480V AC 220V AC
10.9 / L1.2 12.9 / 1L.A
11.9 / L2.2
11.9 / L3.2
5
-Q1
17
3-12A L1 L2 L3
13
21
A1
110-220V DC/AC -Q1
18
/20.2
14
22
A2
/20.7 /21.1
3-12A
110-220V DC/AC
Control module
LUCA12FU
EW:10,5A
11
-K2
14
12
/21.1
17
97
18
98
/20.7 /21.2
T1 T2 T3
2
A1
-Q1
A2
/20.2
13.9 / N.A
-PE
1
-X1
-X2_W3
_-J
4x2,5 mm²
V1
PE
21 22
Vor dem Einschalten der Zulaufpumpe 17 18 /20.7
20_3_001
M den Leistungsschalter auf Nennstrom 97 98 /21.2
6,33kW 3 des Motors einstellen (s. Typenschild des Motors)
10,5A
Attention!
Before switch-on feed pump, adjust the circuit breaker
to nominal current of the motor (look at motor label)
Feed pump Feed pump
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 11
Editor GUE/PLE
Customer:
Separator Feed pump
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 20
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
15.9 / L+.A L+.A / 22.0
13
97
-Q1 -Q1
14
98
/20.2 /20.3
12
13
X12 X12
E1.0 E1.1
/32.4 /32.4
=00-K1 =00-K1
Feed pump Feed pump
operation failure
=00-K1
/32.5
A1.1
X12
33
A1
-K2
A2
14
11 /20.7
12
Feed pump
start / stop
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 11
Editor GUE/PLE
Customer:
Separator Feed pump
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 21
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
21.9 / L+.A L+.A / 24.0
18.9 / M.X M.X / 26.0
12
14
15
19
-SC -SC
1
-T1
Output
0/4-20mA
PT100
-SC
4
-SC
SC
SC
7
4
-X2 -X2
-X2_W14 -X2_W12
.CY-O .CY-O
2x1 mm² 4x1 mm²
/22.3
20_9_008
1
3
Θ Θ
+
PT100 PT100
20_7_012
2
4
SIPART PS2
4-20mA
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 11
Editor GUE/PLE
Customer:
Separator Product temperature control
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 22
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
=00-K2
/33.3
PEW256I
X1
2
24V DC 24V DC
19.9 / L+.X L+.X / 26.0
5
-X2
-WG004
.-O
2x1 mm²
1
20_9_009 I
FI P
4-20mA
FI flow measuring
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 11
Editor GUE/PLE
Customer:
Separator FI flow measuring
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 23
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
24V DC 24V DC
22.9 / L+.A L+.A / 27.0
=00-K1
/32.4
E0.7
X12
9
-PE
1
-X2
-WG010
.-J
3x1 mm²
+HFO1
PE
12
13
8106-2011-061
-X2
24
-K4
23
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 16
Editor GUE/PLE
Customer:
Separator Sludge pump
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 24
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
35
36
37
12
13
A1
A1
A1
A1
A1
A1
-K1 -K2 -K3 -K4 -K5 -K6
A2
A2
A2
A2
A2
A2
21.9 / M.R
14 14 14 14 14 14
11 11 /25.3 11 /25.4 11 /25.5 11 /25.7 11 /25.8
12 12 12 12 12 12
24
21 /25.0
22
43
12
14
12
14
12
14
12
14
12
14
22
24
12
14
11
11
11
11
11
/13.8 /25.3 /25.4 /25.6 /25.7 /25.8
21
11
/25.1 /10.1
PE
10
11
12
13
14
15
16
17
1
3
4
9
-X2
-X2_W19
.-J
18x1,5 mm²
=+DCS
PE
-X -X -X -X -X -X -X -X
Common failure Separator Sludge tank TAH TAL Local / remote PAL clean-oil
operation Level high / high alarm HFO temperature HFO temperature status discharge pressure
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 100
Editor GUE/PLE
Customer:
Separator Signal exchange
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 25
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
7
-SC -SC
=0-SC =0-SC
24V DC 24V DC
23.9 / L+.X L+.X /
22.9 / M.X M.X /
-SC
PE
SC
18
19
20
21
22
23
24
25
26
27
-X2
-X2_W20 -X2_W18
.-J .CY-O
7x1,5 mm² 4x1,5 mm²
/26.8
=+DCS
PE
-X -X -X -X -X
-K -K -K
HFO daily tank level HFO daily tank level Remote start / stop Clean-oil HFO temperature
Low control High control NO for stop, NC for start discharge pressure
Change to daily tank Change to settling tank
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 100
Editor GUE/PLE
Customer:
Separator Signal exchange
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 26
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
10
13
24V DC
24.9 / L+.A
11.9 / M.K M.K / 28.0
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 27
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Mana
6
Mana
10
5
10
15
20
25
30
35
40
27.9 / M.K M.K / 30.0
Earth analog Earth analog Earth analog Earth analog Earth analog Earth analog Earth analog Earth analog Earth analog Earth analog
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 28
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-P1
Button Designation Symbol
Westfalia Separator
OP 177B
ACK
SC
A
A
B
B
24V
0V
PE
24V DC
11.9 / L+.T MPI_A / 30.0
11.9 / M.T MPI_B / 30.0
-PE
Process display
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator Process display OP 177B
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 29
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
PEW270M-
PAW754U
PEW758V
MRES
PAW274
7 7 7 7 7
A1.7
A8.7
E2.7
E1.7
IN IN OUT IN IN
-
-
-
-
-
-
E2.0
E0.0
A0.0
PEW752V
PAW752U
PAW272
E8.0
PEW256I
L+ 0 0 0 0
1 1 1 1
M
2 2 2 2
3 3 3 3
4 4 4 4
5 5 5 5
6 6 6 6
7 7 7 7
X1 MPI
A
29.9 / MPI_A
B
29.9 / MPI_B
SC
A
Mana /31.4
B
1L+ /32.4
2L+ /32.5
3L+ /32.5
2L+ /35.5
1L+ /34.5
4M /31.5
1M /32.4
2M /32.5
3M /32.5
1M /35.5
2M /35.5
1M /34.5
SC
DC 24V
L+
X11:20
X11:30
X12:1
X12:20
X12:21
X12:30
X12:31
X12:40
X1:1
X1:20
X1:10
X1:11
X1:20
24V DC
11.9 / L+.K
28.9 / M.K
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC power supply
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 30
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-K1
X11:1 X11:21
X11:2 X11:22
PEW752V E2.0 /19.7 =01+HFO1-K11:24 Valve clean-oil discharge limit switch open from HFO1
X11:3 X11:23
Current measuring separator =01-T1:8 /13.3 PEW752I E2.1 /19.8 =01+HFO1-K12:24 Valve clean-oil discharge limit switch closed from HFO1
X11:4 X11:24
Earth analog /27.2 - E2.2
X11:5 X11:25
PEW754V E2.3
X11:6 X11:26
Clean-oil discharge pressure =01-X2:6 /16.1 PEW754I E2.4
X11:7 X11:27
Earth analog /27.3 E2.5
X11:8 X11:28
PEW756V E2.6
X11:9 X11:29
Sludge room monitoring =01-X2:8 /16.2 PEW756I E2.7 /12.8 =0-K1:14 Separator emergency stop
X11:10
Earth analog /27.4 - X11:30
4M /30.3 0V
X11:11
PEW758V V X11:31
X11:12
Product temperature control =11-T1:1 /22.5 PEW758I A
X11:32
X11:13
Earth analog /27.4
X11:33
X11:14
Min / max temperature monitoring =11-X2:3 /22.6 PEW760+
X11:34
PT100
X11:15
Min / max temperature monitoring /22.6 PEW760-
X11:35
X11:16 X11:36
PAW752U
X11:17 X11:37
PAW752I
X11:18 X11:38
PAW754U
X11:19 X11:39
Control valve heating medium positioner =11-X2:7 /22.3 PAW754I
X11:20 X11:40
Mana /30.3 Mana
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 31
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-K1
X12:1 X12:21
24V /30.3 1L+ 2L+ /30.3 24V
X12:2 X12:22
Separator operation =01-Q1:34 /14.1 E0.0 A0.0 /18.1 =01-X2:14 Feed valve
X12:3 X12:23
Separator failure =01-F1:22 /14.2 E0.1 A0.1 /18.4 =01-X2:17 Displacem- and filling water
X12:4 X12:24
E0.2 A0.2 /18.3 =01-X2:16 Operating water
X12:5 X12:25
Speed monitoring device =01-T2:4+ /15.2 E0.3 A0.3
X12:6 X12:26
E0.4 A0.4 /18.5 =01-X2:19 Circulation valve
X12:7 X12:27
Water discharge =01-X2:10 /16.3 E0.5 A0.5 /18.6 =01-X2:20 Water discharge valve
X12:8 X12:28
E0.6 A0.6
X12:9 X12:29
LSHH sludge tank from HFO1 =16+HFO1-K4:24 /24.1 E0.7 A0.7 /25.1 =100-K1:A1 Common failure
X12:10 X12:30
2M /30.3 0V
X12:11 X12:31
3L+ /30.4 24V
X12:12 X12:32
Feed pump operation =11-Q1:14 /21.1 E1.0 A1.0 /14.1 =01-K1:A1 Separator start/stop
X12:13 X12:33
Feed pump failure =11-Q1:98 /21.2 E1.1 A1.1 /21.1 =11-K2:A1 Feed pump start / stop
X12:14 X12:34
E1.2 A1.2
X12:15 X12:35
E1.3 A1.3 /25.3 =100-K2:A1 Sludge tank Level high / high alarm
X12:16 X12:36
E1.4 A1.4 /25.4 =100-K3:A1 TAH HFO temperature
X12:17 X12:37
E1.5 A1.5 /25.6 =100-K4:A1 TAL HFO temperature
X12:18 X12:38
Spare =16+HFO1-K4:23 /27.1 E1.6 A1.6
X12:19 X12:39
NAHH separator vibration monitoring =01-X2:13 /17.4 E1.7 A1.7 /19.1 =01-K10:A1 Valve clean-oil discharge
X12:20 X12:40
0V /30.3 1M 3M /30.4 0V
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 32
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-K2
X1:1 X1:21
PEW256V PEW264V
X1:2 X1:22
FI flow measuring =11-20_9_009:2 /23.1 PEW256I V V PEW264I
X1:3 X1:23
PEW256S- A A PEW264S-
X1:4 X1:24
PEW256M+ PEW264M+
X1:5 X1:25
Earth analog /28.1 PEW256M- PEW264M- /28.4 Earth analog
X1:6 X1:26
PEW258V PEW266V
X1:7 X1:27
PEW258I V V PEW266I
X1:8 X1:28
PEW258S- A A PEW266S-
X1:9 X1:29
PEW258M+ PEW266M+
X1:10 X1:30
Earth analog /28.2 PEW258M- PEW266M- /28.5 Earth analog
X1:11 X1:31
PEW260V PEW268V
X1:12 X1:32
PEW260I V V PEW268I
X1:13 X1:33
PEW260S- A A PEW268S-
X1:14 X1:34
PEW260M+ PEW268M+
X1:15 X1:35
Earth analog /28.2 PEW260M- PEW268M- /28.6 Earth analog
X1:16 X1:36
PEW262V PEW270V
X1:17 X1:37
PEW262I V V PEW270I
X1:18 X1:38
PEW262S- A A PEW270S-
X1:19 X1:39
PEW262M+ PEW270M+
X1:20 X1:40
Earth analog /28.3 PEW262M- PEW270M- /28.7 Earth analog
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 33
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-K3
2AO
X1:1
1L+ /30.5 24V
X1:2
X1:3
PAW272 /26.6 =100-X2:24 Clean-oil discharge pressure
X1:4
S+
X1:5
S-
X1:6
Mana /28.8 Earth analog
X1:7
PAW274 /26.8 =100-X2:26 HFO temperature
X1:8
S+
X1:9
S-
X1:10
Mana /28.8 Earth analog
X1:11
X1:12
X1:13
X1:14
X1:15
X1:16
X1:17
X1:18
X1:19
X1:20
1M /30.6 0V
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 34
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
-K4
X1:1
1L+
X1:2
E8.0 /26.1 =100-X2:19 HFO daily tank level Low control Change to daily tank
X1:3
E8.1 /26.2 =100-X2:21 HFO daily tank level High control Change to settling tank
X1:4
E8.2 /26.4 =100-X2:23 Remote start / stop NO for stop, NC for start
X1:5
E8.3
X1:6
E8.4
X1:7
E8.5
X1:8
E8.6
X1:9
E8.7 /16.6 =01-23_7_020:14 Sludge discharge flap
X1:10
1M /30.6 0V
X1:11
2L+ /30.7 +24V
X1:12
A8.0 /25.7 =100-K5:A1 Local / remote status
X1:13
A8.1 /25.8 =100-K6:A1 PAL clean-oil discharge pressure
X1:14
A8.2
X1:15
A8.3
X1:16
A8.4
X1:17
A8.5
X1:18
A8.6
X1:19
A8.7
X1:20
2M /30.7 0V
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 = 00
Editor GUE/PLE
Customer:
Separator PLC overview
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 35
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EFS 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
600 mm
560 mm 300 mm
0-T2
Filter
=00-P1
100-K1
01-K10
100-K2
100-K3
100-K4
100-K5
100-K6
01-K1
11-K2
0-K1
0-F1
01-F1
01-T1
0-F2
01-T2
0-T1
11-T2
1200 mm
1160 mm
01-B1
0-24M
0-Q1
11-Q1
100-X2
01-Q1
=0-Q1
I
O
=0-M1
01-X1
11-X1
01-X2
11-X2
16-X2
0-X1
=00-P1 Process display
=0-M1 Filter / fan
=0-Q1 Isolator Cable glands Size
9x M20 incl. 3x spare 8 - 13mm
10x M25 incl. 3x spare 11 - 17mm
3x M32 incl. 1x spare 15 - 21mm
3x M40 incl. 1x spare 19 - 28mm
Bestell-nr.
0005-4050-700
Westfalia Separator AG
order no.
Programm-Nr.
8106-1E40-768
program-no.
Tiefe: __mm
215
depth:
Ausschnittmass: 228x195mm
cutout dimension:
Gewicht: _,__kg
weight:
ACK
245
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator E40
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 37
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & ELU 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
&EFS/11.6
&EFS/11.6
&EFS/11.6
Cross reference
0V
PE
=00-P1
Target internal
-PE
-T2
Bridges
=0+-24M
Terminal number
1
2
Control voltage DC
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =0+-24M
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 38
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMA 57 Bl./Sh.
=0+-PE
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
=Customer+L-X
Editor
&EFS/10.1
Tested
Incoming PE
PE
PE
-X2_W1
PE
_-J 4x25 mm²
1
-SC
GUE/PLE
Earthing screen PE &EFS/10.3
20.07.2012
SC
SC
07.09.2012/KA
-1M
Earthing mounting plate 1 PE PE &EFS/10.4
PE
-PE
Kunde:
GN/YE
Project:
Projekt:
Customer:
-1T
Earthing door 1 PE PE &EFS/10.4
PE
-PE
2
GN/YE
-1G
Earthing cabinet 1 PE PE &EFS/10.5
Esmeraldas II
PE
-PE
GN/YE
-PE
&EFS/11.1
= PE &EFS/11.2
-X1 6
3
-M1
= PE &EFS/11.2
PE
L
GN/YE
L
M
1~
PE N
N
-PE
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
&EFS/11.6
4
Separator
Control voltage DC PE
GEA Westfalia
= PE &EFS/11.6
-24M 2
=01-20_1_001
Separator PE &EFS/13.2
PE
=01-X2_W2
PE
T2 U1
Benennung/Description:
V1
5
V1
Θ
M
3~
T1 W1
W1
PE
T2
=01+HFO1-X2
Spare PE &EFS/19.8
PE
PE
=01-WG021
PE
-PE
6
=16+HFO1-X2
LSHH sludge tank from HFO1 PE &EFS/24.1
PE
PE
=16-WG010
PE
-PE
.-J 3x1 mm²
=01+JB-1X10
Water discharge PE &EFS/16.3
PE =01-X2_W9
PE
=01-X2_W5
PE
Language:
-PE
.-J 7x1 mm²
7
=11-20_3_001
Feed pump PE &EFS/20.1
PE
U1 =11-X2_W3
PE
-PE
_-J 4x2,5 mm²
en
U1
V1
M
W1
V1
PE
Drawing No.:
W1
Zeichnungs Nr.:
8
+DCS-X
Remote start / stop NO for stop, NC for start PE &EFS/26.4
PE
=100-X2_W20
PE
=100-X2_W19
PE
DCC
& EMA
9
Bl./Sh.
57 Bl./Sh.
39
0 1 2 3 4 5 6 7 8 9
&EFS/10.3
&EFS/22.6
&EFS/22.3
&EFS/22.4
&EFS/26.8
&EFS/26.8
&EFS/22.7
&EFS/26.7
Cross reference
-SC
-SC
-SC
-SC
-SC
Bridges
=0+-SC
SC
SC
SC
SC
SC
SC
SC
SC
Terminal number
PE SC SC SC
PE SC SC SC
-PE
=11-X2
=100-X2
=11-X2
-SC
Control valve heating medium positioner
HFO temperature
Earthing screen
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =0+-SC
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 40
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMA 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
&EFS/11.0
&EFS/11.1
&EFS/11.1
&EFS/11.1
&EFS/11.1
&EFS/11.2
&EFS/12.1
&EFS/12.1
&EFS/12.1
Cross reference
vb
4
=01-X1
Target internal
-F2
-T1
Bridges
=0+-X1
Terminal number
1
21
M
1~
PE
PE
22
-M1
-PE
-S01
Emergency stop external
Control voltage AC
Control voltage AC
Spare
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =0+-X1
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 41
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMA 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
&EFS/10.1
&EFS/10.1
&EFS/10.1
Cross reference
6
Target internal -Q1
-Q1
-Q1
Bridges
=0+-XQ1
Terminal number
2
6
_-J 4x25 mm²
-X2_W1
1 2 3
L1 L2 L3
L1
=Customer+L-X
Incoming
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =0+-XQ1
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 42
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMA 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
&EFS/13.1
&EFS/13.1
&EFS/13.1
&EFS/13.8
&EFS/13.7
Cross reference
13
Target internal
=0-X1
-Q1
-Q1
-Q1
-F1
Bridges
=01+-X1
Terminal number
1
5
_-J 4x16 mm²
-X2_W2
1 2 3
U1 V1 W1 T2 T1 PE
W1
U1
V1
PE
M
3~
Θ
T2
T1
-20_1_001
Separator
Spare
=
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =01+-X1
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 43
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMA 57 Bl./Sh.
=01+-X2
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
-20_1_001
Editor
&EFS/13.3
Tested
PTC-feeler separator 1
T1
1
-F1 T1
-X2_W13 &EFS/13.3
= .-O 2x1 mm² 2
T2
1
2
T2 U1
-F1 T2
GUE/PLE
20.07.2012
U1
V1
Θ
M
3~
07.09.2012/KA
T1 W1
V1
PE
W1
Kunde:
Project:
Projekt:
PE
Customer:
2
+JB-1X10
Speed monitoring device 3 &EFS/15.2
1
1
-T2 1+
= 4 &EFS/15.2
Esmeraldas II
2
-T2 2-
Clean-oil discharge pressure 5 &EFS/16.1
4
3
=0-T2 L+
&EFS/16.1
3
4
=00-K1 X11:6
1
-X2_W9 &EFS/16.2
Sludge room monitoring .-J 7x1 mm² 7
3
= 8 &EFS/16.2
6
5
=00-K1 X11:9
Spare 9 &EFS/16.3
=00-K1 X12:7
-23_7_020
Sludge discharge flap 11 &EFS/16.5
13
1
-23_7_020 13
14 13
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
-WG001 &EFS/16.6
4
Separator
= .-O 2x1 mm² 12
14
2
GEA Westfalia
-23_7_020 14
+JB-1X10
NAHH separator vibration monitoring 13 &EFS/17.4
10
1
10
-20_7_006 - +
Feed valve 14 &EFS/18.1
+
1
=00-K1 X12:22
-X2_W4 &EFS/18.1
Benennung/Description:
-
=0-24M 1
+JB-1X10
Operating water 16 &EFS/18.3
12
2
=00-K1 X12:24
=00-K1 X12:23
= 18 &EFS/18.4
12
-X2_W5 &EFS/18.5
Circulation valve .-J 7x1 mm² 19
16
4
=00-K1 X12:26
6
=00-K1 X12:27
= 21 &EFS/18.7
17
6
=11-X2 8
+HFO1-X2
Valve clean-oil discharge to HFO1 22 &EFS/19.6
27
1
-K10 14
= 23 &EFS/19.6
28
Sprache:
2
Language:
-K10 11
7
=00-K1 X11:22
27
-WG021 &EFS/19.8
Valve clean-oil discharge limit switch closed from HFO1 .-J 7x1 mm² 25
30
4
=00-K1 X11:23
en
+24VDC 26 &EFS/19.8
31
5
=11-X2 5
Spare 27 &EFS/19.8
32
6
Drawing No.:
Zeichnungs Nr.:
8
8106-2011-062
As built +
Rev.05 =
DCC
& EMA
9
Bl./Sh.
57 Bl./Sh.
44
=01+JB-1X10
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
-29_7_003/B
Editor
&EFS/18.3
Tested
Operating water PE PE
PE
-WG105
PE
-PE
.-J 3x1,5 mm²
1
+SB-1X20
GUE/PLE
PE &EFS/16.3
Water discharge PE
20.07.2012
PE:PE
-WG121
PE
=0-PE PE
PE
.-J 5x1,5 mm²
07.09.2012/KA
-20_9_018
Speed monitoring device - + 1 &EFS/15.2
+
-X2 3
BN
Kunde:
-WG101 &EFS/15.2
Project:
Projekt:
-
= .-O 2x0,34 mm² 2
Customer:
-X2 4
BU
2
+SB-1X20
Clean-oil discharge pressure 3 &EFS/16.1
1
1
-X2 6
= 4 &EFS/16.1
Esmeraldas II
2
-X2 5
= 5 &EFS/16.1
1
-WG121
.-J 5x1,5 mm²
&EFS/16.2
4
3
-X2 8
Water discharge 7 &EFS/16.3
5
4
-X2 10
3
-20_9_020
NAHH separator vibration monitoring 8 &EFS/17.1
1
BN
= 9 &EFS/17.3
3
BK
-WG104 &EFS/17.4
= 10
4
= 11 &EFS/17.1
2
BU
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
4
Separator
GEA Westfalia
-29_7_003/B
Operating water - + 12 &EFS/18.3
+
-X2 16
BN
-WG105 &EFS/18.3
-
-29_7_003/A
- + &EFS/18.4
-
-WG106 &EFS/18.4
Benennung/Description:
= 15
+
-X2 17
BN
+SB-1X20
Circulation valve 16 &EFS/18.5
8
1
-X2 19
Water discharge valve 17 &EFS/18.7
10
2
-X2 21
-WG122 &EFS/18.6
= .-J 4x1,5 mm² 18
11
3
-X2 20
= PE &EFS/18.7
PE:PE
PE
=0-PE PE
6
-29_7_003/A
Displacem- and filling water PE PE &EFS/18.4
PE
-WG106
PE
-PE
.-J 3x1,5 mm²
Sprache:
Language:
7
en Drawing No.:
Zeichnungs Nr.:
8
8106-2011-062
As built +
Rev.05 =
DCC
& EMA
9
Bl./Sh.
57 Bl./Sh.
45
=01+SB-1X20
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
-21_9_002
I
1
Editor
&EFS/16.1
Tested
Clean-oil discharge pressure 1
2
+JB-1X10 3
WH
2
-WG201 &EFS/16.1
= 2
1
.-O 2x0,34 mm²
1
+JB-1X10 4
BK
GUE/PLE
20.07.2012
07.09.2012/KA
-20_9_014
I
1 &EFS/16.2
Sludge room monitoring 3
1
BK
2
-WG202 &EFS/16.2
= 4
2
.-O 2x0,34 mm²
+JB-1X10 6
P
WH
Kunde:
Project:
Projekt:
Customer:
-20_9_013
Water discharge 5 &EFS/16.3
+
A/Q
+JB-1X10 7
2
BK
= A/Q 6 &EFS/16.3
+
-WG203
BN
.-O 3x0,75 mm²
- &EFS/16.3
-
= 7
Esmeraldas II
GY
-20_7_010
- + &EFS/18.5
+
+JB-1X10 16
BN
-WG204 &EFS/18.5
-
= .-J 3x0,75 mm² 9
BU
3
-20_7_011
- + &EFS/18.7
-
-WG205 &EFS/18.6
= 11
+
-20_7_010
Circulation valve PE PE &EFS/18.6
PE
-WG204
PE
+JB-1X10 PE
.-J 3x0,75 mm²
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
4
Separator
GEA Westfalia
-20_7_011
Water discharge valve PE PE &EFS/18.7
PE
-WG205
PE
+JB-1X10 PE
.-J 3x0,75 mm²
Benennung/Description:
5
Sprache:
Language:
7
en Drawing No.:
Zeichnungs Nr.:
8
8106-2011-062
As built +
Rev.05 =
DCC
& EMA
9
Bl./Sh.
57 Bl./Sh.
46
0 1 2 3 4 5 6 7 8 9
&EFS/20.1
&EFS/20.1
&EFS/20.1
Cross reference
6
Target internal -Q1
-Q1
-Q1
Bridges
=11+-X1
Terminal number
1
3
_-J 4x2,5 mm²
-X2_W3
1 2 3
U1 V1 W1 PE
W1
U1
V1
PE
M
3
-20_3_001
Feed pump
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =11+-X1
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 47
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMA 57 Bl./Sh.
=11+-X2
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
-20_9_008
Editor
&EFS/22.5
Tested
Product temperature control 1
1
1
-T1 3
= 2 &EFS/22.5
Θ
1
2
2 1 -T1 4
GUE/PLE
-X2_W12 &EFS/22.6
Min / max temperature monitoring 3
3
.CY-O 4x1 mm²
20.07.2012
3
=00-K1 X11:14
07.09.2012/KA
= 4 &EFS/22.6
4
4
=00-K1 X11:15
-X2_W14
Kunde:
&EFS/22.4
Project:
Projekt:
Control valve heating medium positioner SC
SC
Customer:
-X2_W14 =0-SC SC
SC
.CY-O 2x1 mm²
2
-X2_W12
Min / max temperature monitoring SC &EFS/22.7
SC
-X2_W12 =0-SC SC
SC
.CY-O 4x1 mm²
Esmeraldas II
-20_9_009
I
1 &EFS/23.1
FI flow measuring 5
1
1
=01-X2 26
-WG004 &EFS/23.1
2
.-O 2x1 mm²
2
=00-K2 X1:2
P
3
-20_7_012 +
Control valve heating medium positioner 7 &EFS/22.3
+
1
=00-K1 X11:19
-
-X2_W14 &EFS/22.3
-
=01-X2 21
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
4
Separator
GEA Westfalia Benennung/Description:
5
Sprache:
Language:
7
en Drawing No.:
Zeichnungs Nr.:
8
8106-2011-062
As built +
Rev.05 =
DCC
& EMA
9
Bl./Sh.
57 Bl./Sh.
48
0 1 2 3 4 5 6 7 8 9
&EFS/24.1
&EFS/24.1
Cross reference
X12:9
2
=00-K1
=11-T1
Target internal
Bridges
=16+-X2
Terminal number
1
1 2
12 13
12
+HFO1-X2
LSHH sludge tank from HFO1
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Terminal connecting plan =16+-X2
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 49
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMA 57 Bl./Sh.
=100+-X2
Changes
Date
0
Bridges
Target internal
Name
Cross reference
Terminal number
Date
+DCS-X
Editor
&EFS/25.1
Tested
Common failure 1
1
-K1 21
= 2 &EFS/25.1
1
2
-K1 24
GUE/PLE
Separator operation 3 &EFS/25.2
20.07.2012
3
=01-Q1 44
07.09.2012/KA
= 4 &EFS/25.2
4
=01-Q1 43
Sludge tank Level high / high alarm 5 &EFS/25.3
5
-K2 11
Kunde:
&EFS/25.3
Project:
Projekt:
= 6
Customer:
-K2 14
TAH HFO temperature 7 &EFS/25.4
7
-K3 11
2
= 8 &EFS/25.4
8
-K3 14
TAL HFO temperature 9 &EFS/25.6
Esmeraldas II
9
-X2_W19 -K4 11
.-J 18x1,5 mm²
= 10 &EFS/25.6
10
-K4 14
&EFS/25.7
11
-K5 11
= 12 &EFS/25.7
12
-K5 14
3
-K6 14
= 15 &EFS/25.9
15
= 16 &EFS/25.9
16
= 17 &EFS/25.9
17
© This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved.
&EFS/26.1
4
Separator
HFO daily tank level Low control Change to daily tank 18
1
GEA Westfalia
=11-X2 5
= 19 &EFS/26.1
2
=00-K4 X1:2
HFO daily tank level High control Change to settling tank 20 &EFS/26.2
3
-X2_W20 &EFS/26.2
= .-J 7x1,5 mm² 21
4
=00-K4 X1:3
Remote start / stop NO for stop, NC for start 22 &EFS/26.4
5
&EFS/26.4
Benennung/Description:
= 23
5
=00-K4 X1:4
Clean-oil discharge pressure 24 &EFS/26.6
1
=00-K3 X1:3
= 25 &EFS/26.6
2
=11-X2 8
-X2_W18
=00-K3 X1:7
= 27 &EFS/26.8
4
= SC &EFS/26.8
=0-SC SC
6
Sprache:
Language:
7
en Drawing No.:
Zeichnungs Nr.:
8
8106-2011-062
As built +
Rev.05 =
DCC
& EMA
9
Bl./Sh.
57 Bl./Sh.
50
0 1 2 3 4 5 6 7 8 9
Cable layout
Cable name /page.path Source (from) Target (to) Cable type Wires total Wires used Cross-section Length Cable gland / clamping range Remark
=100-X2_W19 &EFS/25.1 +DCS-X =100-X2;=0-PE .-J 18x 18 1,5 mm² M40x1,5 / 19-28mm
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Cable layout
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 51
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Cable layout
Cable name /page.path Source (from) Target (to) Cable type Wires total Wires used Cross-section Length Cable gland / clamping range Remark
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Cable layout
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 52
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Instructions for installation
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 53
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
FU
FC
=..-U.
Generelle Information zum Potentialausgleich.
Die Informationen auf diesem Blatt sind nicht
kundenspezifisch angepasst.
IP54
PE-Schiene
protective earth - rail
IDM
≥25 mm²
GN YE
≥10 mm²
GN YE
PA
PA7
PA6
PA5
PA4
PA3
PA2
PA1
≥10 mm²
GN YE
equipotential bonding building
Potentialausgleich Gebäude
≥25 mm²
GN YE
Fundamenterder
foundation earth
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Potential equalization Separator
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 54
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EMB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Parts list
=0-Q1 &EFS/10.1 0005-1837-060 LV429631 Compact Leistungsschalter, NSX100F+TM80D 3P3D 56-80A, 36KA/415VAC Groupe Schneider
Compact circuit breaker
=0-Q1 &EFS/10.1 Konsole 90X160X100 Konsole 90X160X100 Konsole verzinkt Zimmermeyer
Bracket zinced
=0-Q1 &EFS/10.1 0005-1438-200 29450 Hilfsschalter OF/SD/SDE/SDV für NS/NSX100..630 Groupe Schneider
auxiliary contact
=0-Q1 &EFS/10.1 0005-1837-160 LV429515 Klemmenabdeckung kurz, 3-polig für NSX100/160/250 Groupe Schneider
Cover of terminals, short
=0-Q1 &EFS/10.1 0005-1837-180 LV429338 Drehantrieb mit Türkupplung für NSX 100...250, Standard, schwarzer Griff Groupe Schneider
Front-rotating drive, black
=0-F1 &EFS/11.1 0005-1872-670 3RV2411-0KA10 Leistungsschalter, 0,9...1,25A, BGR S00, für den Transformatorschutz Siemens
Circuot-breaker, 0.9...1.25A, size S00, transformer protection
=0-F2 &EFS/11.1 0005-1428-000 23732 Sicherungsautomat C 6A, 1 pol, C60N Groupe Schneider
Circuit breaker
=0-M1 &EFS/11.1 0005-1409-390 116 43 10 1 055 Filterlüfter, 207-253V, 50/60Hz, 45/39W, 231/265m³/h Pfannenberg
Filter fan
=0-M1 &EFS/11.1 0005-1409-240 117 40 00 1 055 Austrittsfilter Pfannenberg
Discharge filter
=0-24M &EFS/11.6 0005-4708-890 1031400000 Durchgangs-Reihenklemme, 1,5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 1,5 mm², screw connection, Wemid, dark-beige, TS 35
=0-T1 &EFS/11.1 0005-0551-490 700199 Steuerspannungstransformator, Prim.: 200-560VAC, Sek.: 115/230V, 400VA Ismet
Control voltage transformer, prim.: 200-560 VAC, sec.: 115/230 V, 400 VA
=0-T2 &EFS/11.5 0005-1407-020 6EP1333-2AA01-0AA0 Einphasennetzgeraet Prim.: 120/230V, 50/60Hz, Sec.: 24VDC, 5A Siemens
Single phase power supply
=0-X1 &EFS/11.0.. 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
=0-K1 &EFS/12.6 0005-4033-110 2966207 Relais Einzelkontakt,PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Phoenix Contakt
Relay for single contact, PLC interface, miniature relay with power contact, 1 change-over
=0-S01 &EFS/12.1 0005-0081-030 3SB3801-0DF3 Pilzdrucktaster Gehäuse, verrastend, mit Schutzkragen, 1NC, 2x M20 Siemens
Mushroom push button box
=0-S01 &EFS/12.1 0005-4487-930 70-20-060-000-13-041 Verschraubung Polyamid, M20x1,5, RAL 7032, halogenfrei, d=8-13mm Jacob
Screw connection polyamide, M20x1,5, RAL 7032, halogen free, 8-13mm
=0-S01 &EFS/12.1 0013-0132-900 50225 PA7035 Gegenmutter Polyamid, M25x1,5, RAL 7035 Jacob
Counter nut polyamide, M25x1,5, RAL 7035
=01-B1 &EFS/13.1 0005-0924-090 TAID10C100 Stromwandler, 100/1A IME
Current transformer
=01-F1 &EFS/13.4 0005-1100-070 3RN1010-1CM00 THERMISTOR-MOTORSCHUTZ, STANDARD-AUSWERTEGERÄT, AUTO, 1S+1OE, AC 230V Siemens
THERMISTOR MOTOR PROTECTION EVALUATION UNIT AUTO, 1NO+1NC, AC 230V
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Parts list
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 55
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EPB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Parts list
=01-Q1 &EFS/13.8 0005-4382-270 3RT1044-1AL20 Leistungsschütz, 30KW/400V, 230VAC 50/60HZ, 3POLIG, BGR. S3, SCHRAUBANSCHLUSS Siemens
CONTACTOR, AC-3 30 KW/400 V, AC 230V 50/60HZ 3-POLE, SIZE S3, SCREW
=01-Q1 &EFS/13.8 0005-4399-050 3RH1921-1HA31 HILFSSCHALTERBLOCK, 31, 3S+1OE, DIN EN 50012, 4POLIG, FÜR MOTORSCHÜTZE, BGR. Siemens
AUXILIARY SWITCH BLOCK, 31, 3NO+1NC
=01-Q1 &EFS/13.8 0005-0915-170 3RT1936-1CD00 RC-GLIED, AC 127...240V, UEBERSPANNUNGSBEGRENZER, ZUM AUFSETZEN, BGR. S2, S3 Siemens
RC-ELEMENT, AC 127...240 V, SURGE SUPPRESSOR
=01-T1 &EFS/13.2 0005-3482-070 1073490000 Stromüberwachung, 0...1 A AC/ 0...5 A AC/ 0...10 A AC , 1 , 0(4)...20 mA , 0...10 V , 1 Weidmueller
Current monitoring, 0 - 1 A AC/0 - 5 A AC/0 - 10 A AC, 1, 0(4) - 20 mA , 0 - 10 V , 1 screw
=01-X1 &EFS/13.1 1028800000 1028800000 Durchgangs-Reihenklemme, 35 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal
=01-X1 &EFS/13.7; 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
=01-X2 &EFS/13.3; 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
=01-K1 &EFS/14.1 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=01-T2 &EFS/15.1 0005-4509-000 KCD2-E2 Sensor-Endstufenklemme, Eingang für NAMUR-Sensoren, 24V DC Speisespannung Pepperl & Fuchs
Converters- Amplifier to convert NAMUR sensor
=01-K10 &EFS/19.1 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=11-Q1 &EFS/20.0 0005-1730-000 LUB12 Motorabgang Grundgerät - 12A AC-43, 440V Groupe Schneider
Motor outlet of basic unit - 12 A AC-43, 440 V
=11-Q1 &EFS/20.0 0005-1730-130 LUCA12FU Steuereinheit Standard LUCA - class 10, 3-12A 110-220V DC/AC Groupe Schneider
Standard control unit LUCA - class 10, 3-12A 110-220V DC/AC
=11-Q1 &EFS/20.0 0005-1730-310 LUA1C20 Hilfsschaltermodul MSS LUA, 2S Groupe Schneider
Aux. switch module, MSS LUA, 2 NO.
=11-X1 &EFS/20.1 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
=11-K2 &EFS/21.1 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=11-T1 &EFS/22.5 0005-3482-060 8483680000 Signalwandler/-trenner, 4...20 mA (Stromschleife), Zugfederanschluss Weidmueller
Signal converter/disconnector, 4...20 mA (current loop), Tension clamp connection
=11-X2 &EFS/22.4.. 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
=11-X2 &EFS/22.3 0005-3499-890 1020080000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, blau, TS 35 Weidmueller
Feed-through terminal
=16-X2 &EFS/24.1 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Parts list
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 56
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EPB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Parts list
=100-K1 &EFS/25.1 0005-4033-080 2967060 Relais Mehrfachkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 2 Wechsler, Phoenix Contakt
Relay, PLC interface, relay with power contact, 2 change-over contacts, Un=24 VDC
=100-K2 &EFS/25.3 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=100-K3 &EFS/25.4 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=100-K4 &EFS/25.6 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=100-K5 &EFS/25.7 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=100-K6 &EFS/25.8 0005-4033-040 2966171 Relais Einzelkontakt, PLC-Interface, Miniaturrelais mit Leistungskontakt, 1 Wechsler, Un=24 Phoenix Contakt
Relay , PLC interface, relay with power contact, 1 change-over contact, Un=24 VDC
=100-X2 &EFS/25.1.. 0005-3503-890 1020000000 Durchgangs-Reihenklemme, 2.5 mm², Schraubanschluss, Wemid, dunkelbeige, TS 35 Weidmueller
Feed-through terminal block, 2,5 mm², screw connection, Wemid, dark-beige, TS 35
=0-SC &EFS/26.7; 1600480000 1600480000 Klemmbügel für Schirmanschluss, zur Montage auf Sammelschiene 10x3mm Weidmueller
Retaining clip for shield connection
=00-P1 &EFS/29.1 0005-4050-710 6AV6642-5DA10-1AC0 Prozessanzeige OP177B, Farb-Display, 24VDC Siemens
Process display OP177B
=00-P1 &EFS/29.1 6AV6671-1CB00-0AX2 6AV6671-1CB00-0AX2 Speicherkarte, 128 MByte, MMC Siemens
Memory card
=00-K1 &EFS/30.1 0005-4050-720 6ES7313-5BF03-0AB0 Zentralbaugruppe, CPU 313C Siemens
CPU modul
=00-K1 &EFS/30.1 0005-4050-760 6ES7390-1AE80-0AA0 Profilschiene, 480mm Siemens
Profile bar, 480mm
=00-K1 &EFS/30.1 0005-4050-722 6ES7392-1AM00-0AA0 Frontstecker, 40POLIG Siemens
Front connector, 40 PIN
=00-K1 &EFS/30.1 6ES7953-8LG20-0AA0 6ES7953-8LG20-0AA0 Speicherkarte, 128 kByte, MMC Siemens
Memory card, 128 kByte, MMC
=00-K1 &EFS/30.1 6ES7901-0BF00-0AA0 6ES7901-0BF00-0AA0 MPI-Kabel zur Verbindung von SIMATIC S7 und PG über MPI, 5M Siemens
MPI cable
=00-K2 &EFS/30.4 6ES7331-1KF02-0AB0 6ES7331-1KF02-0AB0 Analogbaugruppe Eingang, SM 331, 8AE, 13BIT Siemens
Analog module input, SM 331, 8AI, 13BIT
=00-K2 &EFS/30.4 0005-4050-722 6ES7392-1AM00-0AA0 Frontstecker, 40POLIG Siemens
Front connector, 40 PIN
=00-K3 &EFS/30.5 0005-4281-010 6ES7332-5HB01-0AB0 Analogbaugruppe Ausgang, SM 332, 2AA, U/I, 11/12BIT Siemens
Analog Module Output, SM 332, 2AO, U/I, 11/12BIT
=00-K3 &EFS/30.5 0005-4050-731 6ES7392-1AJ00-0AA0 Frontstecker, 20POLIG Siemens
Front connector, 20 PIN
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Parts list
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 57
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EPB 57 Bl./Sh.
0 1 2 3 4 5 6 7 8 9
Parts list
=00-K4 &EFS/30.6 0005-4050-730 6ES7323-1BH01-0AA0 Digitalbaugruppe Ein-/Ausgang, SM 323, 8DE/DA, DC 24V, 0.5A Siemens
Digital Module Input/Output, SM 323, 8DI/DO, DC 24V, 0.5A
=00-K4 &EFS/30.6 0005-4050-731 6ES7392-1AJ00-0AA0 Frontstecker, 20POLIG Siemens
Front connector, 20 PIN
-Cabinet &ELU/36.1 1260500 1260500 Kompakt-Schaltschrank AE, lackiert RAL 7035, eintürig mit Montageplatte Rittal
Compact enclosure AE, painted RAL 7035, single door with mounting plate
-Cabinet &ELU/36.1 0005-1412-000 2519000 Türarretierung für das AE Programm Rittal
Door stay for the AE range
-Cabinet &ELU/36.1 RESOPALSCHILD100/13 RESOPALSCHILD100/13 Resopalschild Kaiser
0 0 Resopal plate
-Cabinet &ELU/36.1 8556-9999-000 KLEINMATERIAL Kleinmaterial Schaltschrank Plenge
Incidentals control cabinet
-Cabinet &ELU/36.1 ADERKENNZEICHNUNG ADERKENNZEICHNUNG Aderkennzeichnung Plenge
Wire marking
-Cable_Glands &ELU/36.9 0013-0131-900 50220 PA7035 Gegenmutter Polyamid, M20x1,5, RAL 7035 Jacob
Counter nut polyamide, M20x1,5, RAL 7035
-Cable_Glands &ELU/36.9 0005-4487-930 70-20-060-000-13-041 Verschraubung Polyamid, M20x1,5, RAL 7032, halogenfrei, d=8-13mm Jacob
Screw connection polyamide, M20x1,5, RAL 7032, halogen free, 8-13mm
-Cable_Glands &ELU/36.9 0013-0132-900 50225 PA7035 Gegenmutter Polyamid, M25x1,5, RAL 7035 Jacob
Counter nut polyamide, M25x1,5, RAL 7035
-Cable_Glands &ELU/36.9 0005-4488-930 70-25-060-000-17-041 Verschraubung Polyamid, M25x1,5, RAL 7032, halogenfrei, d=11-17mm Jacob
Screw connection polyamide, M25x1,5, RAL 7032, halogen free, 11-17mm
-Cable_Glands &ELU/36.9 50232-PA7035 50232 PA7035 Gegenmutter Polyamid, M32x1,5, RAL 7035 Jacob
Counter nut polyamide, M32x1,5, RAL 7035
-Cable_Glands &ELU/36.9 0005-4489-930 70-32-060-000-21-041 Verschraubung Polyamid, M32x1,5, RAL 7032, halogenfrei, d=15-21mm Jacob
Screw connection polyamide, M32x1,5, RAL 7032, halogen free, 15-21mm
-Cable_Glands &ELU/36.9 50240-PA7035 50240 PA7035 Gegenmutter Polyamid, M40x1,5, RAL 7035 Jacob
Counter nut polyamide, M40x1,5, RAL 7035
-Cable_Glands &ELU/36.9 0005-4490-930 70-40-060-000-28-041 Verschraubung Polyamid, M40x1,5, RAL 7032, halogenfrei, d=19-28mm Jacob
Screw connection polyamide, M40x1,5, RAL 7032, halogen free, 19-28mm
-Cable_Glands &ELU/36.9 0005-4443-900 81-20-866-0000-04 Blindstopfen Polyamid, M20x1,5, RAL 7035 Jacob
Blanking plug polyamide, M20x1,5, RAL 7035
-Cable_Glands &ELU/36.9 0005-4444-900 81-25-866-0000-04 Blindstopfen Polyamid, M25x1,5, RAL 7035 Jacob
Blanking plug polyamide, M25x1,5, RAL 7035
=Additions &ELU/36.9 0005-1554-000 1646461044 Kabelbezeichnung, polyamid Weidmueller
Cable designation
=Additions &ELU/36.9 8555-9001-200 8555-9001-200 Betriebsanleitung E40, englisch WS Mineraloil Systems
Instruction manual
Date 20.07.2012 Kunde: PDV Power Technology GEA Westfalia Benennung/Description: Rev.05 =
Editor GUE/PLE
Customer:
Separator Parts list
HFO Separator Double Unit (HFO 2) As built +
Projekt:
Tested 07.09.2012/KA Project:
Esmeraldas II Sprache: Zeichnungs Nr.: DCC Bl./Sh. 58
Changes Date Name © This document is COPYRIGHTED by GEA Westfalia Separator Group GmbH. All rights being reserved. Language: en Drawing No.: 8106-2011-062 & EPB 57 Bl./Sh.