Está en la página 1de 32

EFI100TE 3R S.A.C.

Sistemas Integrales

INFORME TECNICO

“AJUSTE DE RECLOSER ELPU”

Walter Cruz
Gerente Comercial
EFI100TE 3R S.A.C.

PUNO

AGOSTO - 2016

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

Contenido

....................................................................................................................................................... 2
1. MEMORIA DESCRIPTIVA ................................................................................................... 3
1.1 Objetivo: ........................................................................................................................... 3
1.2 Antecedentes:.................................................................................................................... 3
1.3 Alcances ........................................................................................................................... 4
2. Características del SEL – 351R ............................................................................................... 4
2.1 Funciones de Protección.................................................................................................... 5
2.2 Funciones de Medición ..................................................................................................... 6
2.3 Caracteristicas de comunicaciones. ................................................................................... 6
2.4 Características Adicionales ............................................................................................... 6
3. ACTIVIDADES REALIZADAS ............................................................................................. 7
3.1 Verificación de plantilla .................................................................................................... 7
3.2 Plantillas de Recloser ...................................................................................................... 15
3.3 Verificación de la Comunicación .................................................................................... 16
4 Reajuste de las curvas de protección: ..................................................................................... 18
4.1 SE Azangaro – salida 8001 ............................................................................................. 18
4.2 SE Azangaro – salida 8002 ............................................................................................. 18
4.3 SE Huancane – salida 4001 ............................................................................................. 19
4.4 SE Huancane – salida 4003 ............................................................................................. 20
4.5 SE Antauta – salida 9001 ................................................................................................ 20
4.6 SE Antauta – salida 9002 ................................................................................................ 21
4.7 SE Ilave – salida 1001 ..................................................................................................... 22
4.8 SE Ilave – salida 1002 ..................................................................................................... 22
4.9 SE Ilave – salida 1003 ..................................................................................................... 23
4.10 SE Pomata – salida 2001 ............................................................................................. 24
4.11 SE Pomata – salida 2002 ............................................................................................. 24
4.12 SE Pomata – salida 2003 ............................................................................................. 25
4.13 SE Pomata – salida 2004 ............................................................................................. 25
4.14 SE Puno– salida L0251................................................................................................ 26
4.15 SE Ayaviri – Salida 6001 ............................................................................................ 27
4.16 SE Ayaviri – Salida 6003 ............................................................................................ 27
4.17 SE San Gaban – Salida 9501 ....................................................................................... 28
4.18 SE Sandia – Salida 7501 .............................................................................................. 29
4.19 SE Juliaca – Salida 5010.............................................................................................. 29
5 CONCLUSIONES ................................................................................................................ 31
6 ANEXOS .............................................................................................................................. 32

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

1. MEMORIA DESCRIPTIVA

En conformidad al Contrato N° 153972 según la ADP-0025-2014-


ELECTROPERÚ, se entrega el presente informe técnico referente al “Servicio
de Integración de Equipamiento Al Sistema SCADA” ITEM 3 el cual consistio
en la puesta en servicio de un relé de máxima corriente para remplazar el relé
EPAC-3000 el cual es encontraba en la SE Mancora, ya que este no cuentan con
la tecnología para registrar información de los eventos que ocurren cuando
apertura la línea 6664, el cual es el informe final de la culminación del
proyecto, describiendo asi las actividades realizadas en el transcurso del
mismo.

1.1 Objetivo:
El presente servicio tiene por objetivo mejorar la coordinación de
protecciones como tambien validar la correcta configuración y
funcionamiento de los recloser SEL351R instalados en las redes de
distribución de ELECTROPUNO, es decir que sea mucho más selectivo.

1.2 Antecedentes:
ELECTROPUNO en el año 2015 realizo la instalación y puesta en servicio
de 65 RECLOSER a lo largo de todo su sistema de distribución, pero al
momento no actúan los Recloser se bloquean y a su ves tampoco operan
adecuadamente, revisando el expediente técnico podemos observar que
no se cuenta con una correcta coordinación ya que estos no tomaron en
cuenta los ajuste de los relés de las subestaciones es decir no están
coordinando.

A su vez también se observa que los reloser poseen una configuración


predefinida lo cual no se adecua a las redes de ELECTROPUNO, por lo que
los bloqueos son constantes y operaciones incorrectas ya que existen
funciones activas las cuales no deberían trabajar.

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

1.3 Alcances

Crear una plantilla adecuada para el funcionamiento de los Recloser en


las redes de ELECTROPUNO, el cual solo contenga funciones requeridas
por el estudio de coordinación.

Activar las funciones adecuadas y coordinar las curvas deacuerdo a las


curvas de los alimentadores de las Subestaciones que a la mayoría de
estos casos son propiedad de Electropuno.

Revisar y verificar los medios de comunicación que podrían utilizarse a


futuro en los puntos utilizados.

2. Características del SEL – 351R

EL SEL-351R cuenta con todos los elementos de protección y lógicas de


control necesarios para proteger alimentadores de Distribución. El relé mide
simultáneamente seis zonas de protección sobrecorriente de tiempo definido
y dos para tiempo inverso permitiendo nos asi ser mas selectivos, tanto para
fallas en fase, fallas a tierra y fallas en el neutro. Este dispositivo también
cuenta con LDP, lo que nos permite guardar un perfil de carga de tensiones,
corritentes, potencia, frecuencia, factor de potencia y asi tener una base de
datos de la carga que se consume.

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

2.1 Funciones de Protección

 50/51 - Sobrecorriente de fase instantanea y temporizada;


 50/51G – Sobrecorriente residual de fase instantanea y
temporizada;
 50/51N– Sobrecorriente neutro de fase instantanea y
temporizada, estas son utilizadas mas que todo para fallas de alta
impedancia;
 50/51Q (46) - Sobrecorriente de fase instantanea y temporizada
de secuencia negativa;
 67G - Sobrecorriente direccional de neutro (polarizado por
corrente y tension);
 67Q - direccional de secuencia negativa (polarizado por tension);
 79 – Recierre automático monopolar (2 opciones) o tripolar
(cuatro opciones) para hasta dos interruptores;
 25 - Verificacion de sincronismo para hasta dos interruptores;
 27/59 – Subtension y sobretenison fase-neutro y entre fases;
Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

 59G - Sobretension de neutro;


 59Q - Sobretension de secuencia negativa;
 50/62BF – Falla de interruptor para hasta dos interruptores;
 81 - Sub/Sobrefrecuencia, taza de variacion de frecuencia df/dt;

2.2 Funciones de Medición

 Corrientes de fase (Ia,Ib,Ic,Ig, IN) y corrientes de secuencia


(I1,I2,I0);
 Tensiones de fase (Va,Vb,Vc) para las 2 entradas de tensión , Vff,
tensiones de secuencia (V1, 3V2, 3V0);
 Potencia ativa e reativa por fase y trifásica (cuatro cuadrantes);
 Fator de potencia por fase e trifásico;
 Medicion RMS (que incluye harmónicas) para corriente, tensión,
potencia atiba, potencia aparente y factor de potencia;
 Demanda de corriente de fase, de neutro y de secuencia negativa;

2.3 Caracteristicas de comunicaciones.

 1 puerto serial EIA-232 delanteros, 3 puertos serie posterior EIA-


232.
 Sincronización de tiempo por la señal IRIG-B 1 kpps garantiza la
precisión tiempo de 5 microsegundos;
 DNP 3.0 Protocolos ASCII, ASCII comprimido, Medidor Rápido,
Rápido SER, Opere rápida y DNP3.

2.4 Características Adicionales

 Software de fácil uso para la parametrización (ACSELERATOR);


 Software de alarma de perturbación, con la posibilidad de abrir
oscilogramas múltiple, sincronizada en el tiempo, en la misma
pantalla;
 Contactos estándar: continua 3A capacidad de conducción, la
capacidad 30A propiedad conducción, rompiendo 0.3A capacidad
(125Vcc, L / R = 40 ms);
 Ampliación del número de E / S disponibles de, con la instalación
(en campo) de las nuevas tarjetas de E / S de, lo que permite la

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

expansión futura, ya que el relé ha sido adquirido con ranuras


adicionales para la instalación tarjetas adicionales;
 Temperatura de funcionamiento -40 ° a + 85 ° C;

3. ACTIVIDADES REALIZADAS

Lo primero que se hizo es verificar los ajustes de protección que fueron


programadas en el recloser, luego de esto corregir y crear una nueva plantilla
la cual este acorde a las necesidades de ELETROPUNO.

Luego verificar las curvas del ajuste de coordinación y corregirlas deacuerdo


a las curvas de protección deacuerdo a las salidas de los alimentadores.

Finalmente verificar el conexionado de cada recloser como los medios de


comunicación que pueden ser utilizados, en este caso verificamos que los
recloser solamente tienen puestos de salida de SERIAL, lo que ya no es
recomendable utilizar este tipo de puestos de comunicaciones.

3.1 Verificación de plantilla

A continuación podemos ver los ajustes una de las plantillas de los recloser
(SE Pomata - Pisacoma), todos los recloser tienen una plantilla similar, por eso
solo detallaremos los principales defectos que se encontró.

Summary Data:
FID = FID=SEL-351R-4-R503-V0-Z002001-D20140207
MONTH = 7
DAY = 1
YEAR = 2016
HOUR = 15
MIN = 34
SEC = 22
MSEC = 597
FREQ = 60.03
SAM/CYC_A = 16
SAM/CYC_D = 4
NUM_OF_CYC = 15
EVENT = CG
LOCATION = $$$$$$$
SHOT = 0
TARGETS = 11000000 10000000
Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

IA = 6
IB = 5
IC = 141
IN = 143
IG = 144
3I2 = 137
NFREQ = 60
PRE_FAULT_CYCLES = 4.000
START_TIME = 07/01/16,15:34:22.531375
TRIG_TIME = 07/01/16,15:34:22.597000

EZ Group 1
Control Identifier (30 chars) =RECLOSER CHUA CHUA R57
Circuit Identifier (30 chars) =LINEA PRIM CHUA CHUA PISACOMA
CT Ratio (1.0-6000) = 200.0
PT Ratio (1.0-10000) = 182.5
Min. trip - phase (OFF,10.00-639.99 A pri.) = 67.00
Min. trip - ground (OFF,1.00-639.99 A pri.) = 25.00
Min. trip - SEF (OFF,1.00-299.99 A pri.) = OFF
Fast curve - phase
(OFF,U1-U5,C1-C5,recloser or user curve) = C1
Time-dial - phase fast curve (0.05-1.00) = 0.09
EM reset - phase fast curve (Y/N) =N
Fast curve - ground
(OFF,U1-U5,C1-C5,recloser or user curve) = C1
Time-dial - ground fast curve (0.05-1.00) = 0.08
EM reset - ground fast curve (Y/N) =N
Delay curve - phase
(OFF,U1-U5,C1-C5,recloser or user curve) = C1
Time-dial - phase delay curve (0.05-1.00) = 0.09
EM reset - phase delay curve (Y/N) =N
Delay curve - ground
(OFF,U1-U5,C1-C5,recloser or user curve) = C1
Time-dial - ground delay curve (0.05-1.00) = 0.08
EM reset - ground delay curve (Y/N) =N
Operations - phase fast curve (OFF,1-5) =2
Operations - ground fast curve (OFF,1-5) =2
Operations to lockout - phase (2-5) =3
Operations to lockout - ground (2-5) =3
Reclose interval 1 (0.00-999999cyc) = 30.00
Reclose interval 2 (0.00-999999cyc) = 60.00
Reset time for auto-reclose (0.00-999999cyc) = 900.00
Reset time from lockout (0.00-999999cyc) = 600.00
Close power wait time (OFF,0.00-999999cyc) = 600.00
Complex fast curve - phase (Y/N) =N
Complex fast curve - ground (Y/N) =N
Complex delay curve - phase (Y/N) =N
Complex delay curve - ground (Y/N) =N
High current trip - phase (Y/N) =N
Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

High current trip - ground (Y/N) =N


High current lockout - phase (Y/N) =N
High current lockout - ground (Y/N) =N
Cold load pickup scheme (Y/N) =N
Sequence coordination (Y/N) =N
Underfrequency loadshedding (Y/N) =N
Demand meter time constant =5
Group 1
Group Settings:
RID =RECLOSER CHUA CHUA R57 TID =LINEA PRIM CHUA CHUA
PISACOMA
CTR = 200.0 PTR = 182.5 PTRS = 182.5
Z1MAG = 32.10 Z1ANG = 68.86
Z0MAG = 95.70 Z0ANG = 72.47 LL = 4.84 1
E50P = 6 E50N = 6 E50G = 6 E50Q = N
E51P = 2 E51N = 2 E51G = 2 E51Q = N
E32 = N ELOAD = N ESOTF = N EVOLT = Y
E25 = N EFLOC = N ELOP = N ECOMM = N
E81 = 6 E79 = 4 ESV = 16 EDEM = THM
50P1P = OFF 50P2P = OFF 50P3P = OFF 50P4P = 0.34
50P5P = OFF 50P6P = 0.34
67P1D = 0.00 67P2D = 0.00 67P3D = 0.00 67P4D = 0.00
50PP1P= OFF 50PP2P= OFF 50PP3P= OFF 50PP4P= OFF
50N1P = OFF 50N2P = OFF 50N3P = OFF 50N4P = OFF
50N5P = OFF 50N6P = OFF
67N1D = 0.00 67N2D = 0.00 67N3D = 0.00 67N4D = 0.00
50G1P = OFF 50G2P = OFF 50G3P = OFF 50G4P = OFF
50G5P = OFF 50G6P = 0.12
67G1D = 0.00 67G2D = 0.00 67G3D = 0.00 67G4D = 0.00
51P1P = 0.34 51P1C = C1 51P1TD= 0.09 51P1RS= N
51P1CT= 0.00 51P1MR= 0.00
51P2P = 0.34 51P2C = C1 51P2TD= 0.09 51P2RS= N
51P2CT= 0.00 51P2MR= 0.00
51N1P = OFF 51N1C = C1 51N1TD= 0.08 51N1RS= N
51N1CT= 0.00 51N1MR= 0.00
51N2P = OFF 51N2C = C1 51N2TD= 0.08 51N2RS= N
51N2CT= 0.00 51N2MR= 0.00
51G1P = 0.12 51G1C = C1 51G1TD= 0.08 51G1RS= N
51G1CT= 0.00 51G1MR= 0.00
51G2P = 0.12 51G2C = C1 51G2TD= 0.08 51G2RS= N
51G2CT= 0.00 51G2MR= 0.00
27P1P = OFF 27P2P = OFF 59P1P = 104.0 59P2P = OFF
59N1P = OFF 59N2P = OFF 59QP = OFF 59V1P = OFF
27SP = OFF 59S1P = OFF 59S2P = OFF 27PP = OFF
59PP = OFF
27B81P= 80.0 81D1P = OFF 81D1D = 6.00
81D2P = OFF 81D2D = 2.00 81D3P = OFF 81D3D = 2.00
81D4P = OFF 81D4D = 2.00 81D5P = OFF 81D5D = 2.00
81D6P = OFF 81D6D = 2.00
Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

79OI1 = 30.00 79OI2 = 60.00 79OI3 = 0.00 79OI4 = 0.00


79RSD = 900.00 79RSLD= 600.00 79CLSD= 600.00
DMTC = 5
PDEMP = OFF NDEMP = OFF GDEMP = OFF QDEMP = OFF
TDURD = 12.00 CFD = 60.00 3POD = 1.50 50LP = 0.05
SV1PU = 0.00 SV1DO = 0.00 SV2PU = 0.00 SV2DO = 0.00
SV3PU = 0.00 SV3DO = 0.00 SV4PU = 0.00 SV4DO = 0.00
SV5PU = 0.00 SV5DO = 0.00 SV6PU = 0.00 SV6DO = 0.00
SV7PU = 900.00 SV7DO = 0.00 SV8PU = 0.00 SV8DO = 0.00
SV9PU = 900.00 SV9DO = 0.00 SV10PU= 0.00 SV10DO= 0.00
SV11PU= 900.00 SV11DO= 0.00 SV12PU= 0.00 SV12DO= 0.00
SV13PU= 0.00 SV13DO= 0.00 SV14PU= 0.00 SV14DO= 0.00
SV15PU= 0.00 SV15DO= 0.00 SV16PU= 0.00 SV16DO= 0.00
OPPH = 2 OPGR = 2 OPLKPH= 3 OPLKGR= 3
OPLKSF= OFF HITRPH= OFF HITRGR= OFF HILKPH= OFF
HILKGR= OFF ECOLDP= N ECOLDG= N RPPH = N
RPGR = N RPSEF = N ESEQ = N PRECED= N
SELogic group 1
2
SELogic Control Equations:
TR =51P1T + 51P2T + 51G1T + 51G2T + 51N1T + 51N2T + 67P2T + 67G2T
+ 67N2T + 67N3T + 81D1T + PB9 + OC
TRCOMM=0
TRSOTF=0
DTT =0
ULTR =!52A
PT1 =0
LOG1 =0
PT2 =0
LOG2 =0
BT =0
52A =SW1 * !CLOSE
CL =PB8 * LT4 * LT7 + CC * LT7
ULCL =TRIP + !PINF * SW1 + !(LT7 + CLOSE) + !(LT4 + CLOSE + CC + 79CY)
79RI =TRIP
79RIS =52A + 79CY
79DTL =67N3T * OLS + (67P1 + 67G1 + 67N1) * TRIP + (!LT2 + !LT7) * (TRIP
+ !52A) + 81D1T + SV16 + PB9 + OC
79DLS =79LO
79SKP =0
79STL =TRIP
3
79BRS =51P1 + 51P2 + 51G1 + 51G2 + 51N1 + 51N2 + 67N3 + TRIP
79SEQ =79RS * SEQC * (51P1 + 51G1 + 51N1)
79CLS =59L1 * !BADBAT * !DTFAIL
SET1 =(PB1 + RB1) * !LT1 * LT4
RST1 =(PB1 + RB1) * LT1 * LT4
SET2 =PB2 * !LT2 * LT4
4
RST2 =PB2 * LT2 * LT4 + !(79RS + 79CY + 79LO)
SET3 =PB3 * !LT3 * LT4
RST3 =PB3 * LT3 * LT4
Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

SET4 =PB5 * !LT4


RST4 =PB5 * LT4
SET5 =PB6 * !LT5 * LT4
RST5 =PB6 * LT5 * LT4
SET6 =PB7 * !LT6 * LT4
RST6 =PB7 * LT6 * LT4
SET7 =1
RST7 =0
SET8 =0
RST8 =0
SET9 =0
RST9 =0
SET10 =0
RST10 =0
SET11 =0
RST11 =0
SET12 =0
RST12 =0
SET13 =0
RST13 =0
SET14 =0
RST14 =0
SET15 =0
RST15 =0
SET16 =0
RST16 =0
67P1TC=HLP
67P2TC=HTP
67P3TC=1
67P4TC=1
67N1TC=HLG * LT1
67N2TC=HTG * LT1
67N3TC=LT1 * !(51P1 + 51P2 + 51G1 + 51G2 + 51N1 + 51N2) * (!SV12 + SV12
* 50G5 + SV12 * 50N5)
67N4TC=1
67G1TC=HLG * LT1
67G2TC=HTG * LT1
67G3TC=1
67G4TC=1
67Q1TC=1
67Q2TC=1
67Q3TC=1
67Q4TC=1
51P1TC=!SV8 * OCP
51N1TC=!SV10 * OCG * LT1
51G1TC=!SV10 * OCG * LT1
51P2TC=!SV8 + SV8 * 50P5
51N2TC=(!SV10 + SV10 * 50G5 + SV10 * 50N5) * LT1
51G2TC=(!SV10 + SV10 * 50G5) * LT1
Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

51QTC =1
SV1 =0
SV2 =0
SV3 =0
SV4 =0
SV5 =52A * (SV8 + SV10 + SV12) * (RPP + RPG + RPS)
SV6 =!52A * (79LO + !79RS * !79CY * !79LO) * (CLP + CLG)
SV7 =52A * !50P6 * SV8
SV8 =(SV8 + SV6T) * !(SV7T + SV5T * RPP + !CLP)
SV9 =52A * !50G6 * !50N6 * SV10
SV10 =(SV10 + SV6T) * !(SV9T + SV5T * RPG + !CLG)
SV11 =52A * !50N4 * SV12
SV12 =(SV12 + SV6T) * !(SV11T + SV5T * RPS + !CLG)
SV13 =51P1T + 51P2T + 51G1T + 51G2T + 51N1T + 51N2T + 67P2T + 67G2T
+ 67N2T
SV14 =50G6 + 50N6 + 51N1 + 51N2
SV15 =/SV13 * (OLG * GTP * SV14 + OLG * !GTP * SV14 * !50P6 + OLP * !GTP
* 50P6 + OLP * GTP * 50P6 * !SV14)
SV16 =SV15 + SV13 * OLP * OLG
SC1R =1
SC1I =0
SC1D =0
SC2R =1
SC2I =0
SC2D =0
SC3R =1
SC3I =0
SC3D =0
SC4R =1
SC4I =0
SC4D =0
SC5R =1
SC5I =0
SC5D =0
SC6R =1
SC6I =0
SC6D =0
SC7R =1
SC7I =0
SC7D =0
SC8R =1
SC8I =0
SC8D =0
RCTR =TRIP
RCCL =CLOSE
OUT101=0
OUT102=0
OUT103=0
OUT104=0
Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

OUT105=0
OUT106=0
OUT107=0
LED1 =LT1
LED2 =LT2
LED3 =LT3
LED4 =!SG1
LED5 =!LT4
LED6 =0
LED7 =0
LED8 =52A
LED9 =!52A * PINBD
LED11 =!DISCHG
LED12 =BADBAT + DTFAIL
LED13 =!LT7
LED14 =TRIP
LED15 =51P1T + 51G1T + 51N1T
LED16 =67P2T + 67G2T + 67N2T
LED17 =81D1T
LED18 =79RS
LED19 =79CY
LED20 =79LO
LED24 =50G6 + 50N6 + 51N1 + 51N2
LED25 =67N3T
LOCAL =0
DP1 =0
DP2 =0
DP3 =0
DP4 =0
DP5 =0
DP6 =0
DP7 =0
DP8 =0
DP9 =0
DP10 =0
DP11 =0
DP12 =0
DP13 =0
DP14 =0
DP15 =0
DP16 =0
SS1 =PB4 * LT4 * !SG1
SS2 =PB4 * LT4 * SG1
SS3 =0
SS4 =0
SS5 =0
SS6 =0
ER =/51P1 + /51P2 + /51G1 + /51G2 + /51N1 + /51N2 + /67N3
FAULT =51P1 + 51P2 + 51G1 + 51G2 + 51N1 + 51N2 + 67N3
Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

BSYNCH=52A
CLMON =0
BKMON =TRIP
E32IV =1
TMB1A =0
TMB2A =0
TMB3A =0
TMB4A =0
TMB5A =0
TMB6A =0
TMB7A =0
TMB8A =0
TMB1B =0
TMB2B =0
TMB3B =0
TMB4B =0
TMB5B =0
TMB6B =0
TMB7B =0
TMB8B =0
Global EZ Settings:
System Frequency (50,60 Hz) = 60
Phase Rotation (ABC,ACB) = ABC
Recloser Wear Monitor (AUTO,Y,N) = AUTO
Recloser type (OIL,VAC1,VAC2) = VAC1
Interrupt rating (500-20000) = 6000
Reset trip-latched LEDs on close (Y,Y1,N,N1) =Y
True three-phase voltage connected (Y,N) =N
Phantom voltages from (VA,VB,VC,VAB,VBC,VCA,OFF) = OFF
V123 Terminal Conn. (A,B,C,AB,BC,CA,OFF) =A
I123 Terminal Conn. (ABC,ACB,BAC,BCA,CAB,CBA) = ABC
CT Polarity (POS,NEG) = POS
Battery Amp-hours (6.5-20) = 16.0
Power-off Delay After AC Loss (OFF,1-1440min) = 180
Power-off Delay After Wake Up (OFF,1-1440min) = 20
Power-off Voltage Level 1 (19.2-24Vdc) = 19.2
Global Settings:
TGR = 0.00 NFREQ = 60 PHROT = ABC
DATE_F= MDY FP_TO = 15
LER = 15 PRE = 4
IN101D= 0.50 IN102D= 0.50 IN103D= 0.50 IN104D= 0.50
IN105D= 0.50 IN106D= 0.50
EBMON = Y COSP1 = 10000 COSP2 = 40 COSP3 = 40
KASP1 = 0.15 KASP2 = 6.00 KASP3 = 6.00
LED11L= N LED12L= N LED13L= N LED14L= Y
LED15L= Y LED16L= Y LED17L= Y LED18L= N
LED19L= N LED20L= N LED24L= Y LED25L= Y
RSTLED= Y PB8D = 0.00 PB9D = 0.00
3PVOLT= N PHANTV= OFF VPCONN= A
Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

IPCONN= ABC CTPOL = POS


EZGRPS= 2 AMPHR = 16.0
PWR_AC= 180 PWR_WU= 20 V_LOW1= 19.2 5
UTCOFF= 0.00

Como podemos observar los principales errores que encontramos, son que el
personal que configuro estos recloser solamente hizo unos cambios a la
plantilla por defecto.

Este recloser tiene dos tipos de configuración, primero la configuracion EZ


esta es una configuración fácil, trabajando por la plantilla por defecto y otra es
la configuración personalizada la cual es mucho mejor y recomendada ya que
trabajamos una plantilla específica para el tipo de problema con los que
contamos.

 En el Punto 5, EZGRPS =2 , nos indica que se esta usando los ajustes


fáciles, por lo que no se tiene plemanente control de las plantillas del
recloser.
 En el punto 1, podemos observas que hay habilitadas 6 etapas de
sobrecorriente de tiempo definico E50P=6, E50N=6, E50G=6, E51P=2,
E51N=2 y E51G=2, podemos ver que nisiquiera en el estudio de
coordinación hay ajustes de tiempo definido por que podemos ver que
existe una mala configuracion.
 En el punto 2, Podemos observar las lógicas de disparo, en lo cual
podemos ver que hay disparos con funciones que no fueron
configuradas por ejemplo la función 81 viendo la disminución de
frecuencia el cual no es necesario para el sistema de ELECTROPUNO.
 En el punto 3, Es la configuración del bloqueo de recierre una lógica que
viene por defecto, lo cual no es adecuada ya que los niveles de corriente
con los que contamos en los alimentadores son de corrientes muy bajas.
 En el punto 4, Lógica de verificación de recierre la cual observamos que
no es la adecuada, por los niveles de tensión con los que trabajamos y es
por eso que no realizan los recierres.

3.2 Plantillas de Recloser

Se crearon nuevas plantillas en las se corrigieron todos esos detalles, las


cuales se adjuntaran en un disco y las curvas utilizadas se adjuntaran en los
Anexos.

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

3.3 Verificación de la Comunicación

A continuación verificamos la comunicación en los distintos puntos donde


están instalados en los recloser, la señal de movistar podemos observar que
existe mas de 90% de los puntos.

SEÑAL CELULAR
UBICACIÓN NRO DERIVACION MOVISTAR CLARO
R41 Santa Maria E/- 3G
R42 Checa E -
ILAVE-S03 R43 Lopez G E/-
TOTORANI Conduriri G -
R44 Conduriri G -
Mazocruz - -
R37 Yanaque H
ILAVE-S01 R38 Charcas E
PILCUYO R39 Pilcuyo H
R40 Juli H
POMATA-
S01 R51 Juli H+
POMATA- R58 Huanacaya H+
S04 R64 Pueblo Libre 4G
POMATA- R54 Unicachi 4G
S03 R55 Copani H+
YUNGUYO R56 Anapia -
R57 Chua Chua H+
R60 Yaurichambi -
POMATA- R61 Yaurichambi -
S02 R62 Tanca Tanca E
KELLUYO R63 Pisacoma G
R52 Huacullani 4G
R53 Huacasuma -
R46 Paratia H
R47 Vila Vila H
JULIACA
Drv Lampa H+
Drv Cabanillas H
Totorani H+
PUNO
R72 Vilque H
ZONA
NORTE R71 Illpa H
R70 Paucarcolla H+
Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

R65 Carucaya E
R66 Cutimbo E
PUNO
R67 Huacochullo G
ZONA SUR
R68 Ichuna -
R69 Cachipascana -
R20 Arapa H+
R21 San Jose H+
R23 Chupa E
AZANGARO R18 Asillo 4G
R16 San Anton -
R19 Choquehuanca 4G
R17 Pupuja E
R15 Pacobamba 4G
R8 Sta.Rosa-Llalli 4G
R14 Orurillo H+
R10 Santa Rosa E
AYAVIRI
R11 Macari E
R9 Llalli E
R12 Nuñoa H
R13 La Raya H
R73 Ollachea H
SAN GABAN R74 Casahuiri H
R75 Oroya G
R76 Puncu H
R78 Masiapo H
SANDIA
R77 Quiquira E
R79 Yanamayo E
R27 Huatasani H+
R26 Taraco H+
R29 Rosapata H
HUANCANE
R28 Jipata -
R31 Huayrapata -
R32 Tilali -

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4 Reajuste de las curvas de protección:


4.1 SE Azangaro – salida 8001
Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
10 12 DT 10 12 DT
7SJ61 SE AZANGARO - 8001 50/1 1.6 0.1 C1 0.8 0.1 C1
20 3 DT 20 3 DT
SEL - 351R R21 SAN JOSE 200/1 0.13 0.2 C2 2 0 DT 0.1 0.13 C2 2 0 DT
SEL - 351R R18 ASILLO 200/1 0.15 0.19 C2 1.5 0 DT 0.1 0.12 C2 1.5 0 DT
SEL - 351R R16 SAN ANTON 200/1 0.1 0.1 C2 0.75 0 DT 0.05 0.1 C2 0.75 0 DT

4.2 SE Azangaro – salida 8002


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
2.5 12 DT 2.5 12 DT
7SJ61 SE AZANGARO - 8002 200/1 0.4 0.1 C1 0.2 0.1 C1
5 3 DT 5 3 DT
2.25 10 DT
SEL - 351R R24 PUTINA 200/1 0.4 0.09 C1 0.17 0.09 C1 2.25 0 DT
4 0 DT
1 12 DT
SEL - 351R R19 CHOQUEHUANCA 200/1 0.13 0.21 C2 0.1 12 C2 2 0 DT
2 0 DT
SEL - 351R R17 PUPUJA 200/1 0.1 0.14 C2 0.75 0 DT 0.07 0.1 C2 0.75 0 DT
SEL - 351R R20 ARAPA 200/1 0.15 0.15 C2 2 0 DT 0.1 0.12 C2 2 0 DT
SEL - 351R R23 CHUPA 200/1 0.1 0.15 C2 0.5 0 DT 0.1 0.06 C2 0.5 0 DT

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4.3 SE Huancane – salida 4001


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
GE F650 SE HUANCANE - 4001 75/5 6.5 0.07 IEC - A 40 0 DT 1.5 0.12 IEC - A 40 0 DT
SEL - 351R R26 TARACO 200/1 0.15 0.09 C1 1 0 DT 0.08 0.06 C1 1 0 DT
SEL - 351R R27 HUATASANI 200/1 0.09 0.05 C1 0.4 0 DT 0.06 0.06 C1 0.4 0 DT

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4.4 SE Huancane – salida 4003


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
GE F650 SE HUANCANE - 4003 75/5 6.5 0.07 IEC - A 40 0 DT 1 0.12 IEC - A 40 0 DT
SEL - 351R R28 JIPATA 200/1 0.15 0.06 C1 1.6 0 DT 0.07 0.07 C1 1.5 0 DT
SEL - 351R R31 HUAYRAPATA 200/1 0.08 0.05 C2 0.4 0 DT 0.05 0.05 C2 0.4 0 DT
SEL - 351R R32 TILALI 200/1 0.08 0.05 C2 0.4 0 DT 0.05 0.05 C2 0.4 0 DT
SEL - 351R R29 ROSASPATA 200/1 0.08 0.05 C2 0.4 0 DT 0.05 0.05 C2 0.4 0 DT

4.5 SE Antauta – salida 9001


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
1.5 9 DT
SEL 751A SE ANTAUTA - 9001 100/1 0.8 0.1 C1 - - - 0.8 0.1 C1
4.5 0 DT
SEL - 351R R1 MACUSANI 200/1 0.2 0.08 C2 - - - 0.08 0.05 C2 0.3 0 DT
SEL - 351R R2 USICAYOS 200/1 0.1 0.1 C2 - - - 0.04 1 C2 0.2 0 DT
SEL - 351R R3 COASA 200/1 0.1 0.1 C2 - - - 0.05 0.05 C2 0.2 0 DT

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4.6 SE Antauta – salida 9002


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
1 6 DT
RECLOSER SE ANTAUTA - 9002 200/1 0.15 0.24 C1 - - - 0.08 0.15 C2
1.5 0 DT
0.05 30 DT
RECLOSER R4 SAN ANTON 1000/1 0.1 0.05 C3 0.01 0.05 C1 0.05 0.1 DT
0.1 5 DT
SEL - 351R R3 COASA 200/1 0.1 0.08 C2 - - - 0.05 0.05 C2 0.25 0 DT

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4.7 SE Ilave – salida 1001


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
SEL - 351A SE ILAVE - 1001 100/5 3 0.1 C2 - - - 0.75 0.1 C1 30 0 DT
SEL - 351R R37 YANQUE 200/1 0.1 0.1 C2 - - - 0.07 0.05 C2 0.75 0 DT
SEL - 351R R38 CHARCAS 200/1 0.1 0.1 C2 - - - 0.07 0.05 C2 0.75 0 DT
SEL - 351R R39 PILCUYO 200/1 0.1 0.1 C2 - - - 0.07 0.05 C2 0.75 0 DT
SEL - 351R R40 JULI 200/1 0.1 0.1 C2 - - - 0.07 0.05 C2 0.75 0 DT

4.8 SE Ilave – salida 1002


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
4 15 DT
SEL - 351A SE ILAVE - 1002 100/5 4 0.07 C1 - - - 0.8 0.09 C1
25 0 DT
0.35 6 DT
SEL - 351R R36 PEAJE 200/1 0.22 0.08 C2 - - - 0.065 0.06 C1
1.5 0 DT
SEL - 351R R33 PLATERIA 200/1 0.06 0.05 C2 - - - 0.05 0.05 C2 0.3 0 DT
SEL - 351R R34 PENINSULA 200/1 0.06 0.05 C2 - - - 0.05 0.05 C2 0.3 0 DT
SEL - 351R R35 USICAYOS 200/1 0.06 0.05 C2 - - - 0.05 0.05 C2 0.3 0 DT

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4.9 SE Ilave – salida 1003


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
SEL - 351A SE ILAVE - 1003 100/5 2.8 0.07 C1 - - - 1 0.15 C1 25 0 DT
0.75 10 DT
SEL - 351R R42 CHECA 200/1 0.15 0.09 C2 - - - 0.09 0.12 C1
1.4 0 DT
0.5 5 DT
SEL - 351R R43 LOPEZ 200/1 0.15 0.06 C2 - - - 0.08 0.08 C2
1 0 DT
SEL - 351R R44 CONDURIRI 200/1 0.1 0.05 C3 - - - 0.06 0.05 C2 0.4 0 DT
0.5 9 DT
SEL - 351R R41 SANTA MARIA 200/1 0.1 0.07 C2 - - - 0.08 0.08 C1
1.3 0 DT
SEL - 351S R80 200/1 0.1 0.05 C1 0.3 0 DT - - - - - -
SEL - 351S R81 200/1 0.08 0.05 C1 0.3 0 DT - - - - - -

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4.10 SE Pomata – salida 2001


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
10 8 DT
SEL - 351A SE POMATA- 2001 100/5 3 0.15 C2 - - - 0.75 0.2 C2
25 0 DT
SEL - 351R R51 JULI 200/1 0.13 0.21 C2 - - - 0.07 0.13 C2 0.5 0 DT

4.11 SE Pomata – salida 2002


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
SEL - 351A SE POMATA - 2002 100/5 3.2 0.15 C2 - - - 0.75 0.1 C1 30 0 DT
SEL - 351R R57 CHUA CHUA 200/1 0.15 0.18 C2 - - - 0.07 0.05 C2 1.25 0 DT
SEL - 351S R60 YAURICHAMBI 200/1 0.1 0.15 C2 0.4 0 DT - - - - - -
SEL - 351S R61 YAURICHAMBI 200/1 0.1 0.05 C2 0.25 0 DT - - - - - -
SEL - 351R R62 TANCA TANCA 200/1 0.1 0.15 C2 - - - 0.06 0.08 C2 0.8 0 DT
SEL - 351R R63 PISACOMA 200/1 0.1 0.05 C2 - - - 0.05 0.05 C2 0.5 0 DT
SEL - 351R R52 200/1 0.15 0.17 C2 - - - 0.08 0.12 C2 1.25 0 DT
SEL - 351S R53 200/1 0.1 0.15 C2 0.4 0 DT - - - - - -

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4.12 SE Pomata – salida 2003


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
12.5 6 DT
SEL - 351A SE POMATA - 2003 100/5 4 0.07 C1 - - - 0.75 0.2 C2
25 0 DT
SEL - 351R R55 COPANI 200/1 0.1 0.2 C2 - - - 0.06 0.14 C2 0.5 0 DT
SEL - 351S R56 ANAPIA 200/1 0.1 0.05 C1 0.4 0 DT - - - - - -
SEL - 351R R54 UNICACHI 200/1 0.13 0.18 C2 - - - 0.07 0.12 C2 0.75 0 DT

4.13 SE Pomata – salida 2004


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
SEL - 351A SE POMATA - 2004 100/5 5 0.1 C2 - - - 1 0.15 C2 25 0 DT
SEL - 351R R64 PUEBLO LIBRE 200/1 0.4 0.06 C2 - - - 0.08 0.11 C2 1.5 0 DT
SEL - 351R R58 HUANACAYA 200/1 0.25 0.05 C2 - - - 0.08 0.05 C2 0.75 0 DT

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4.14 SE Puno– salida L0251


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
NULEC SE PUNO - L 0251 200/1 0.5 0.12 C1 - - - 0.12 0.15 C1 - - -
SEL - 351R R TOTORANI 1000/1 0.1 0.07 C1 - - - 0.02 0.1 C1 0.25 0 DT
SEL - 351R R71 VILQUE 200/1 0.15 0.15 C2 - - - 0.08 0.07 C2 0.5 0 DT
SEL - 351R R EXISTENTE 1000/1 0.1 0.07 C1 - - - 0.02 0.08 C1 0.6 0 DT
SEL - 351R R65 CARUCAYA 200/1 0.1 0.2 C2 - - - 0.05 0.08 C2 0.8 0 DT
SEL - 351R R66 CUTIMBO 200/1 0.15 0.15 C2 - - - 0.08 0.06 C2 1 0 DT
SEL - 351S R69 ICHUA 200/1 0.08 0.1 C2 0.4 0 DT - - - - - -
SEL - 351R R70 PAUCARCOLLA 200/1 0.2 0.2 C2 - - - 0.1 0.1 C1 1.5 0 DT
SEL - 351R R71 ILLPA 200/1 0.15 0.13 C2 - - - 0.08 0.07 C1 0.5 0 DT
SEL - 351S R68 CACHIPASCANA 200/1 0.06 0.1 C2 0.4 0 DT - - - - - -
SEL - 351R R67 HUACHOCHULLO 200/1 0.1 0.16 C2 - - - 0.07 0.05 C2 0.75 0 DT

R R72

R67

R66
R - L0251

R68
R

RELE L0251
REP R69

R70 R71

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4.15 SE Ayaviri – Salida 6001


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
7SJ61 SE AYAVIRI - 6001 50/1 1.32 0.12 C1 - - - 0.6 0.1 C1 - - -
SEL - 351R R14 ORURILLO 200/1 0.09 0.2 C2 - - - 0.07 0.12 C2 1.25 0 DT

R - L0240

R14 Orurillo

RELE 6001
REP

4.16 SE Ayaviri – Salida 6003


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
7SJ61 SE AYAVIRI - 6003 200/1 0.33 0.12 C1 - - - 0.15 0.1 C1 - - -
SEL - 351R R8 TRONCAL 200/1 0.22 0.11 C2 - - - 0.12 0.07 C1 3.5 0 DT
SEL - 351R R10 SANTA ROSA 200/1 0.1 0.12 C2 - - - 0.08 0.05 C2 1.25 0 DT
0.06 15 DT
SEL - 351R R13 LA RAYA 200/1 0.07 0.05 C2 - - - - - - 0.15 6 DT
0.35 0 DT
0.06 15 DT
SEL - 351R R12 MUÑOA 200/1 0.07 0.05 C2 - - - - - - 0.15 6 DT
0.35 0 DT
SEL - 351R R09 LLALLI 200/1 0.1 0.11 C2 - - - 0.07 0.05 C3 - - -
SEL - 351R R11 MACARI 200/1 0.1 0.11 C2 - - - 0.07 0.05 C3 - - -
SEL - 351R R15 PACOBAMBA 200/1 0.1 0.11 C2 - - - 0.07 0.05 C3 - - -

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

Pacobamba
R09 Llalli

R15
R11 Macari

R - L0241
R08

RELE 6003
REP
R10 R12 Muñoa

R13

La Raya

4.17 SE San Gaban – Salida 9501


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
SEL - 351R R74 CASAHURI 200/1 0.15 0.12 C1 0.5 0 DT 0.08 0.09 C1 0.4 0 DT
SEL - 351S R75 OROYA 200/1 0.08 0.05 C1 0.3 0 DT - - - - - -
SEL - 351R R73 OYACHEA 200/1 0.13 0.2 C2 2 0 DT 0.1 0.13 C2 2 0 DT

R73 Ollachea
PCD

R74 R75 Oroya

RELE ELPU

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

4.18 SE Sandia – Salida 7501


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
2 21 DT
SEL - 351R R76 SANDIA 200/1 0.15 0.15 C1 - - - 0.15 0.16 C1
10.5 0 DT
1.75 10 DT
SEL - 351R R77 QUIQUIRA 200/1 0.12 0.1 C1 - - - 0.12 0.1 C1
10 0 DT
0.5 6 DT
SEL - 351R R79 YANAMAYO 200/1 0.1 0.06 C1 - - - 0.1 0.05 C1
1.5 0 DT
SEL - 351S R78 MASIAPO 200/1 0.1 0.07 C1 0.4 0 DT - - - - - -

R78 Misiapo

R76

R77 R79 Yanamayo

4.19 SE Juliaca – Salida 5010


Aquí observamos el alimentador y mas abajo los ajustes de coordinación
correspondientes:

RELE UBICACIÓN TC I> T> CURVA I>> T>> CURVA I0> T0>(cyc) CURVA I0>> T0>> CURVA
MICOM P139 SE JULIACA 5010 250/1 1.3 0.1 IEC - A - - - 0.25 0.15 IEC - A - - -
SEL - 351R R TAPARACHI 500/1 0.6 0.07 C1 - - - 0.09 0.1 C1 - - -
SEL - 351R R CABANILLAS 1000/1 0.1 0.05 C1 0.3 0 DT 0.02 0.05 C1 0.3 0 DT
SEL - 351R R LAMPA 1000/1 0.23 0.05 C1 1 0 DT 0.04 0.06 C1 0.2 0 DT
SEL - 351R R46 PARATIA 200/1 0.23 0.05 C1 1 0 DT 0.05 0.05 C1 0.3 0 DT
SEL - 351R R47 VILA VILA 200/1 0.08 0.05 C1 0.4 0 DT 0.04 0.05 C2 0.2 0 DT

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

Cabanillas

Taparachi
R - 5010
R
R46 Paratia

RELE REP
R

Lampa
R47 Vila Vila

Teléfono: 5377528 / Jr. Hermilio Valdizan N° 427, Urbanización Santa Luzmila, Comas – Lima /
ventas@efi100te3r.com
EFI100TE 3R S.A.C.
Sistemas Integrales

5 CONCLUSIONES

 Para ELECTROPUNO, es necesario realizar un estudio de coordinación


Anual, ya que es necesario coordinar los fusibles, lo cual no se esta
haciendo actualmente.

 El personal de ELECTROPUNO, pone fusibles de bajo amperaje a la


salida de los recloser por lo cual en algunos de estos casos los fusibles
actuaran no coordinando con los recloser.

 En cuanto a la comunicación, en los puntos donde existe claro


confirmamos que existe la señal de Claro, por lo que se debería tomar
acciones con la contratista que instalo los modens GPRS, para que
pongan en funcionamiento nuevamente el sistema.

 Es necesario capacitar al personal de ELECTROPUNO, en el


funcionamiento de los recloser, ya que el personal posee un gran
desconocimiento del uso de los recloser, y en algunos casos del
desconocimiento del sistema los cuales manejan un claro ejemplo es el
sistema de Azangaro.

 Es necesario actualizar el GIS, para poder realizar el estudio de


coordinación de todo el sistema de distribución, para que la información
sea real.

 Se observo en muchos casos que los recloser tiene una relación de PT de


182.5, lo cual en algunos casos acierta a dar a los 22,9KV y en otros casos
a esta misma relación 53KV, lo cual es bastante inusual que ocurra, ya
que según lo que se menciono al personal de ELECTROPUNO, estor ese
PT es único para todos y ya estaba probado en fabrica, por lo cual seria
bueno consultar al proveedor sobre este detalle.

 En muchos casos se puedo observar que los CT se encuentran invertidos


dándonos una potencia negativa por lo que si a futuro se utilizara
protecciones direccionales será necesario instalar correctamente los
recloser mirando hacia la carga.