PLANTA – EL AGUSTINO
CPPQ2-QRM03-6-DC-001
Rev. A
APROBADO POR:
COMENTARIOS:
ÍNDICE
1. INTRODUCCIÓN......................................................................................................................................3
2. NIVELES DE TENSIÓN............................................................................................................................3
2.1. TENSIONES.....................................................................................................................................3
2.2. COMPATIBILIDAD DE TENSIONES...............................................................................................3
3. IDENTIFICACIÓN DE ÁREAS..................................................................................................................3
4. IDENTIFICADOR DE EQUIPOS..........................................................................................................4
5. DESIGNACIONES....................................................................................................................................5
5.1. IDENTIFICACIÓN DE TABLERO ELÉCTRICOS............................................................................5
5.2. IDENTIFICACIÓN DE CAJAS DE PASO Y CONEXIONES............................................................5
5.3. IDENTIFICACIÓN DE MOTORES Y BOMBAS...............................................................................6
5.4. IDENTIFICACIÓN DE CIRCUITOS..................................................................................................6
5.4.1. Cables de Fuerza:........................................................................................................................6
5.4.2. Cables de Control:........................................................................................................................6
5.4.3. Cables de Iluminación:.................................................................................................................7
5.5. IDENTIFICACIÓN DE BANDEJAS...................................................................................................7
5.6. IDENTIFICACIÓN DE POZOS A TIERRA:......................................................................................7
1. INTRODUCCIÓN
El presente documento establece los criterios para la designación de códigos para los equipos eléctricos,
cables, canalización, etc, a usar en el Proyecto “Servicio de Ingeniería de control de inventarios de tanques
IGBF – Planta El Agustino”.
2. NORMAS Y ESTÁNDARES
El sistema eléctrico deberá cumplir con las normativas nacionales y locales, además cumplirá estándares
internacionales que a continuación indicamos:
RNE – 2006 Reglamento Nacional de Edificaciones
DGE / MEM - 2006 Código Nacional de Electricidad – Utilización (CNE).
DGE / MEM - 2011 Código Nacional de Electricidad – Suministro (CNE).
SLUMP Sistema Legal de Unidades de Medida del Perú.
NTP Norma Técnica Peruana.
NEC National Electric Code.
IES Illuminating Engineering Society.
National Fire Protection Agency (NFPA)
NFPA 70, “National Electrical Code (NEC)”
National Electrical Manufacturer Association (NEMA)
NEMA 250, “Enclosures for Electrical Equipment”
NEMA ICS 18, “Motor Control Centers”
Underwriters Laboratories, Inc. (UL)
NEMA ICS 1-2000 Industrial Control and Systems General Requirements.
NEMA ICS 2-2000 Industrial Control and Systems. Controllers, Contactors, and Overload Relays Rated
600 Volts.
NEMA ICS 4-2005 Terminal Blocks
NEMA ICS 6- 1993 Industrial Control and Systems. Enclosures R (2001)
NEMA ICS 18-2001 Motor Control Center
NEMA ICS 2 Part 8-1998 Industrial Control and Systems: Controllers, Contactors, and Overload
Relays, Rated Not More Than 2000 Volts AC or 750 Volts DC Part 8: Disconnect Devices for Use in
Industrial Control Equipment.
NEMA ICS 2 Part 9-2002 Industrial Automation Control Products and Systems: Starters, Contactors,
and Overload Relays Rated Not More Than 2000 Volts AC or 750 Volts DC Part 9: AC Vacumm-Break
Magnetic Controllers Rated 1500 Volts AC.
NEMA-250-2003 Enclosures for Electrical Equipment (100 Volts maximum)
NEMA-PB-2-1995 Deadfront Distribution Switchboards.
ANSI C 57-13-1993 Standard Requirements for Instrument Transformers.
NEMA SG3-1995 Power Switching Equipment
ANSI C37.20.1-2002 Standard for Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear.
NFPA-70E-2004 Standard for electrical safety requirements for employee workplace.
El Código Nacional de Electricidad (CNE) – Suministro 2011 será complementado por el National
Electric Safety Code (NESC) en todo aquello que no se le oponga. De igual manera, el Código
Nacional de Electricidad – Utilización 2006 será complementado por el National Electric Code (NEC).
3. NIVELES DE TENSIÓN
3.1. TENSIONES
Los niveles de tensión a usar en el presente proyecto, así como su designación a fin de que sean instalados
adecuadamente.
4. IDENTIFICACIÓN DE ÁREAS
La estructura de la planta ha definido las siguientes áreas:
5. IDENTIFICADOR DE EQUIPOS
A continuación, se muestran los códigos para equipos eléctricos:
6. DESIGNACIONES
Ejemplos:
PP-QUI-P-101 - Tablero de fuerza, Planta químicos, Baja Tensión, 440 – 480 VAC.
CP-RES-B-102 - Tablero de control, Planta resinas, Baja Tensión, 110 - 220 VAC
Ejemplos:
Nivel de tensión
XXX-N-YYY-101
Número correlativo
Ejemplos:
Si el equipo tiene más de un motor, en la parte final se agregará una letra (A, B, C, etc.)
Ejemplo:
Ejemplo:
Cable de Fuerza desde el Tablero de fuerza PP-QUI-P-101 hasta el motor QUI-P-MO-101.
Tag de cable: PP101-QUI/MO101-QUI-P-001.
Ejemplo:
Cable de Control desde el Centro de Control de Motores MCC-QUI-F-101 hasta el Tablero de Control CP-
QUI-F-101.
Tag de cable: MCC101-QUI-CP101-C001.
Ejemplo:
Cable de Tablero de Iluminación LB-QUI-L-101 hasta las luminarias del circuito N° 1.
Tag de cable: LB101-QUI-L-001.
Nivel de tensión
XXX-YY-N-001
Número correlativo
Ejemplos:
Documento elaborado por GYS Control Industrial S. A. C. Código: GYS-PRO-CP
La información contenida en este documento es confidencial. Toda reproducción o copia sin autorización está prohibida. Revisión: 2.0
CRITERIO DE DISEÑO
Rev.: A
Proyecto: CRITERIO DE DISEÑO PARA CODIFICACIÓN ELÉCTRICO
Fecha: 29-03-2021
Documento: GYS-QRM03-DC-002 Pág.: 9 de 9
Los pozos a tierra, dependiendo si son de Control o Fuerza, serán identificados de la siguiente manera:
XXX-YY-N-001
Número correlativo
Código de área PE
en
Ejemplos: