Capitulo 2 - Conductores
Capitulo 2 - Conductores
NEGOCIO DE ENERGA
Revisin: 00
DIRECCIN DISTRIBUCIN Fecha: diciembre de 2006
NORMAS TECNICAS DE ENERGA
Aprob: Resolucin 0407
NORMAS DE DISEO
CAPITULO 2
CONDUCTORES
Pgina 1 de 30
INDICE DE CONTENIDO
2
CONDUCTORES ................................................................................................. 3
2.1. Conductores para redes areas ....................................................................... 3
2.1.1 Generalidades ........................................................................................... 3
2.1.1.1 Redes abiertas............................................................................... 3
2.1.1.2 Redes preensambladas ..........................................................
4
2.1.2 Seleccin ................................................................................................... 7
2.1.3 Pases subterrneos................................................................................. 15
2.2. Conductores para redes subterrneas Nivel de tensin 1 ........................... 17
2.2.1 Generalidades ......................................................................................... 17
2.2.2 Seleccin. ................................................................................................ 18
2.3. Conductores para redes areas Nivel de tensin 2 y 3. .............................. 19
2.3.1 Generalidades ......................................................................................... 19
2.3.2 Seleccin. ................................................................................................ 20
2.3.3 Acometidas. ............................................................................................. 20
2.4. Conductores para redes subterrneas Nivel de tensin 2 y 3 ..................... 24
2.4.1 Generalidades ......................................................................................... 24
2.4.2 Seleccin. ................................................................................................ 26
2.4.3 Seleccin de conductos........................................................................... 27
2.4.4 Acometidas. ............................................................................................. 27
INDICE DE TABLAS
.
Tabla 2.1. Factores de ajuste para ms de tres conductores portadores de corriente
en una canalizacin o cable con diversidad de carga. ......................................... 5
Tabla 2.2. Caractersticas fsicas y mecnicas de los conductores. ........................... 6
Tabla 2.3. Factor de diversidad................................................................................. 10
Tabla 2.4. Seleccin del conductor. Redes de distribucin areas Nivel 1 .............. 12
Tabla 2.5. Seleccin del conductor. Redes de distribucin subterrneas nivel de
tensin 1 (conductores de cobre aislado)........................................................... 13
Tabla 2.6. Valores de la constante K para el clculo de regulacin. Distribucin B.T.
Area. Conductores de Aluminio. % Reg = (kVA x m) x K ................................. 14
Tabla 2.7. Valores de la constante K para el clculo de regulacin. Distribucin B.T.
Subterrnea. Conductores de Cobre % Reg = (kVA x m) x K ............................ 15
Tabla 2.8. Seleccin del dimetro del conducto para pases subterrneos en baja
tensin................................................................................................................ 16
Tabla 2.9. Seleccin conductores para los pases subterrneos en baja tensin. ..... 16
1
INDICE DE FIGURAS
Figura 2.1. Modelo de crecimiento de carga tipo rampa............................................. 7
Figura 2.2. Transposicin de cables para circuitos subterrneos en media tensin
con longitud igual o mayor a 500 metros............................................................ 26
2 CONDUCTORES
2.1. Conductores para redes areas
2.1.1 Generalidades
2.1.1.1 Redes abiertas (solo para reposicin o mantenimiento de redes
existentes)
Para las redes del tipo abiertas (no preensambladas) los conductores sern de
aluminio, tipo AAC (All Aluminium Conductors), cableados concntricos clase B, con
7 hilos de aluminio duro (estirado en fro), aislado en polietileno para 75 grados
centgrados y desnudos, con conductividad mnima del 61% a 20 grados centgrados.
Las redes elctricas areas a construir en el rea de influencia de EMCALI, y donde
lo permita el POT, sern en calibre 21.14 mm2 (4 AWG), 53.5 mm2 (1/0 AWG), y
107.21 mm2 (4/0 AWG).
Las redes sern trifsicas, 4 hilos, 120/208 voltios, en trminos generales, a menos
que EMCALI, en los datos bsicos, indique que sean monofsicas, 3 hilos, 120/240
voltios, lo cual ocurre en aquellos sitios donde las redes trifsicas en media tensin a
13.2 kV., quedan muy retiradas del sitio del proyecto.
La disposicin fsica de los conductores en las redes ser as, siguiendo el orden, de
arriba hacia abajo:
Descripcin
Conductor
Redes
Trifsicas
Neutro
Fase 1
Fase 2
Fase 3
Desnudo
Aislada
Desnuda
Aislada
Redes
Monofsicas
Desnudo
Aislada
Desnuda
Los conductores neutro para redes trifsicas se especificarn de acuerdo con los
calibres de la fase, as:
Calibre fase mm2 (AWG)
21.14 (4)
33.62 (2)
53.5 (1/0)
67.44 (2/0)
85.02 (3/0)
107.21 (4/0)
Lnea AP aislada
Lnea AP desnuda (de igual calibre).
De 4 a 6
De 7 a 9
De 10 a 20
De 21 a 30
De 31 a 40
De 41 en adelante
Ver excepciones NTC 2050 artculo 310-15
Debe aplicar la tabla 2-1 para conductores que van por bandeja y no estn separados segn normas.
ACSR
Cobre
Aluminio
Material
Calib.
Cond.
AWG
Nombre
Peso
(Kg/Km)
Dimetro (mm)
Carga de
rotura
(Kg)
Desnudo
Aislado
Desnudo
Aislado
58
72
147
184
234
295
79
131
208
253
313
386
21.14
33.62
53.50
67.44
85.02
107.21
4
2
1/0
2/0
3/0
4/0
5.89
7.42
9.35
10.52
11.79
13.26
7.48
9.82
12.56
13.70
14.99
16.46
374
574
846
1066
1291
1628
8.36
13.29
21.14
33.62
53.50
107.21
33.62
8
6
4
2
1/0
4/0
2
6.90
7.86
9.08
10.62
13.46
17.40
Sparrrow
3.70
4.66
5.88
7.42
9.46
13.40
8.01
135.6
1265
53.50
1/0
Raven
10.11
215.9
1940
Mdulo de
Elastic.
Final
(Kg/mm2)
Coef. de
Dilatac.
lineal
(1/ C)
6200
23 x 10 -6
8000
8000
8000
8000
8000
8000
8000
7000
19.1 x 10-6
19.1 x 10-6
117
169
252
382
609
1150
67.44
2/0
Quail
11.34
272.1
2425
107.21
4/0
Penguin
14.31
432.5
3820
135.20
266.8
Waxwing
15.47
429.8
3210
201.40
397.5
Chickadee
20.44
923.3
9060
201.40
397.5
Ibis
19.88
811.7
7340
241.70
477
Pelican
20.68
770.9
5579
19.1 x 10-6
19.1 x 10-6
19.1 x 10-6
17.8 x10-6
18.9 x 10-6
21.2 x 10-6
Carga inicial
0
KVAn = kVA0 * (1 + r) 2n
Donde:
KVAn: Carga al final del perodo (ver tabla 2.3 A)
kVA0 : Carga inicial (ver tabla 2.3 A)
r: Tasa de crecimiento anual de la demanda = 1%
n: Perodo = 10 aos
Calcule la demanda mxima por tramo o transformador as (ver ejemplo en el anexo 2.1):
DMAX = (kVAn* #Usuarios)/Factor diversidad + KVAL * #LOCALES + CE + CAP
Donde:
DMAX:
Demanda mxima.
KVAn
Carga instalada por usuario (VER TABLA 2.3 A). Cuando se trata
de viviendas con ms de 300 m2 la carga se debe calcular como se indica en
el captulo 2 de la NTC 2050 y en ningn caso podr ser inferior a 18.3 kVA.
KVAL:
CE:
CAP:
- 107.21 mm2 (4/0 AWG) a calibre menor o igual a 53.50 mm2 (1/0 AWG)
2
2
3
%Reg =
(i=1,n)
DMAX * Li * Ki
Donde:
%Reg : Porcentaje de regulacin
DMAX : Demanda mxima
Ki
: Constante que depende del tipo de sistema, del factor de potencia de
la carga, y del conductor, en 1/kVAxm).
Li
I
: Nmero indicativo de la secuencia de tramos hasta un terminal
secundario.
n
Una vez calculada la regulacin debe verificarse que cumpla con los siguientes
criterios:
%Reg 3.0% Para urbanizaciones con posibilidad de expansin (2do o 3er piso)
Factor diversidad
# usuarios
Factor diversidad
1,00
38
4,40
1,19
39
4,44
1,37
40
4,48
1,54
41
4,52
1,71
42
4,56
1,86
43
4,59
2,00
44
4,63
2,14
45
4,66
2,27
46
4,70
10
2,39
47
4,73
11
2,51
48
4,77
12
2,62
49
4,80
13
2,73
50
4,83
14
2,83
51
4,86
15
2,93
52
4,89
16
3,02
53
4,92
17
3,11
54
4,93
18
3,20
55
4,94
19
3,28
56
4,99
20
3,36
57
5,03
21
3,44
58
5,06
22
3,51
59
5,08
23
3,58
60
5,11
24
3,65
61
5,13
25
3,72
62
5,15
26
3,78
63
5,17
27
3,84
64
5,20
28
3,90
65
5,22
29
3,96
66
5,24
30
4,02
67
5,26
31
4,07
68
5,28
32
4,12
69
5,30
33
4,17
70
5,32
34
4,22
71
5,34
35
4,26
72
5,36
36
4,31
73
5,38
37
4,35
74
5.40
10
Factor diversidad
# usuarios
Factor diversidad
75
5,42
113
5,92
76
5,44
114
5,93
77
5,45
115
5,94
78
5,47
116
5,95
79
5,48
117
5,95
80
5,50
118
5,96
81
5,52
119
5,97
82
5,54
120
5,98
83
5,55
121
5,99
84
5,57
122
6,00
85
5,58
123
6,01
86
5,60
124
6,02
87
5,61
125
6,02
88
5,63
126
6,03
89
5,64
127
6,04
90
5,65
128
6,05
91
5,66
129
6,06
92
5,68
130
6,07
93
5,69
131
6,07
94
5,71
132
6,08
95
5,72
133
6,09
96
5,73
134
6,10
97
5,74
135
6,10
98
5,76
136
6,11
99
5,77
137
6,12
100
5,78
138
6,13
101
5,79
139
6,13
102
5,80
140
6,14
103
5,81
141
6,14
104
5,82
142
6,15
105
5,83
143
6,16
106
5,85
144
6,17
107
5,86
145
6,17
108
5,87
146
6,18
109
5,88
147
6,18
110
5,89
148
6,19
111
5.90
149
6,20
112
5.90
150
6,2
11
AREAS (M )
KVA
Mnima
Mxima
Inicial (kVAo)
Final (kVAn)
65
6.1
65.1
85
5.5
6.7
85.1
105
8.5
10.4
105.1
125
10
12.2
125.1
200
12
14.6
200.1
300
15
18.3
Tabla 2.4. Seleccin del conductor. Redes de distribucin areas del Nivel de tensin 1
Transf.
(Kva)
No.
ramales
KVA/ramal
Mn
Mx
No. vanos
Longitud de cada
vano (m)
*
*
4
*
*
34
*15
*25
37.5
*
*
2
50
75
45
75
5.96
8.66
14.62
8.66
14.62
22.2
21.14 (4)
21.14 (4)
53.50 (1/0)
21.14 (4)
53.50 (1/0)
53.50 (1/0)
22.2
29.78
53.50 (1/0)
107.21 (4/0)
34
29.78
35.73
107.21 (4/0) 107.21 (4/0)
Sistema trifsico urbano
34
17.87
26.53
21.14 (4)
53.50 (1/0)
36
26.53
44.94
53.50 (1/0)
107.21 (4/0)
36
107.21 (4/0)
112.5
44.94
67.14
107.21 (4/0)
36
150
44.76
35
25
37.5
3
3
5.78
9.75
59.92
107.21 (4/0) 107.21 (4/0)
Sistema bifsico rural
9.75
21.14 (4)
21.14 (4)
14.8
21.14 (4)
53.50 (1/0)
4
4
67
33
50
14.8
19.85
53.50 (1/0)
33
75
19.85
33
45
75
2
2
17.87
26.53
29.96
53.50 (1/0) 107.21 (4/0)
Sistema trifsico rural
26.53
21.14 (4)
53.50 (1/0)
44.94
53.50 (1/0) 107.21 (4/0)
7
7
37
37
112.5
44.94
67.14
35
53.50 (1/0)
107.21 (4/0)
107.21 (4/0)
12
KVA/ramal
Transf.
(Kva)
No.
ramales
Mn
*15
*25
37.5
50
75
*
*
2
2
2
5.96
7.20
12.24
18.36
24.20
45
75
112.5
150
2
2
2
3
17.87
22.14
36.52
44.76
25
37.5
50
75
3
3
3
3
5.78
8.20
12.24
15.48
17.87
22.14
21.14 (4)
53.50 (1/0)
30
75
22.14
36.52
53.50 (1/0)
107.21 (4/0)
30
107.21 (4/0)
112.5
2
36.52
54.78
* Solo para circuitos de alumbrado pblico, ver topologa
107.21 (4/0)
30
13
21.14 (4)
33.62 (2)
53.50 (1/0)
67.44 (2/0)
85.02 (3/0)
107.21 (4/0)
Cos
0.85
0.90
0.95
0.85
0.90
0.95
0.85
0.90
0.95
0.85
0.90
0.95
0.85
0.90
0.95
0.85
0.90
0.95
3F -4h120/208V
3 F -3h-208V
3.6904
3.8118
3.9071
2.4536
2.5070
2.5359
1.6678
1.6799
1.6688
1.3895
1.3876
1.3632
1.1661
1.1536
1.1191
0.9865
0.9660
0.9245
14
Calibre
Mm2
(AWG
o KCM)
8.36
(8)
13.29
(6)
21.14
(4)
33.62
(2)
53.50
(1/0)
107.21
(4/0)
cos
0.85
0.90
0.95
0.85
0.90
0.95
0.85
0.90
0.95
0.85
0.90
0.95
0.85
0.90
0.95
0.85
0.90
0.95
3F 4h120/208V
3F- 3h
208V
5.1475
5.4231
5.6912
3.2824
3.4483
3.6066
2.1073
2.2045
2.2932
1.3816
1.4357
1.4823
0.9206
0.9475
0.9670
0.5299
0.5338
0.5303
10.2949
10.8461
11.3823
6.5649
6.8965
7.2123
4.2145
4.4081
4.5865
2.7632
2.8713
2.9645
1.8412
1.8949
1.9341
1.0598
1.0676
1.0607
11.5818
12.2019
12.8051
7.3855
7.7586
8.1149
4.7413
4.9591
5.1598
3.1086
3.2302
3.3351
2.0713
2.1318
2.1758
1.1923
1.2010
1.1933
1F- 2h
120V
3F- 2h
23V
30.8847
32.5383
34.1470
19.6946
20.6896
21.6398
12.6435
13.2243
13.7594
8.2895
8.6140
8.8936
5.5235
5.6648
5.8022
3.1794
3.2027
3.1820
Dimetro
conducto (*)
Monofsica
Trifsica
Alumbrado Pblico mm (pulgadas)
21.14 (4) 33.62 (2)
25.4 ( 1 )
21.14 (4) 33.62 (2)
21.14 (4)
53.50 (1/0)
31.8 ( 1 1/4 )
33.62 (2)
38.1 ( 1 1/2 )
53.50 (1/0) - 85.02 (3/0)
53.50 (1/0)
50.8 ( 2 )
107.21 (4/0)
67.44 (2/0)107.21 (4/0)
63.5 ( 2 1/2 )
(*) El conducto correspondiente al bajante (a la vista) debe ser conduit metlico galvanizado y el
correspondiente al tramo subterrneo (entre cmaras) debe ser conduit P.V.C.
Tabla 2.9. Seleccin conductores para los pases subterrneos en baja tensin.
Calibre conductor fase de la red
area (AAC)
2
mm (AWG)
21.14 (4) - 53.50 (1/0)
107.21 (4/0)
Conductor de cobre de
2
Puesta a tierra mm (AWG - Cu)
8.36 (8)
13.29 (6)
21.14 (4)
336.2 (2)
53.50 (1/0)
67.44 (2/0)
Nota:
Para conductores en paralelo por fase se debe encontrarse el conductor por fase equivalente en rea
y utilizar la tabla anterior.
16
18
Dimetro
mm (pulgadas)
25.4 (1)
31.8 (1)
38.1 (1 )
50.8 (2)
63.5 (2 )
2.3.2 Seleccin.
Antes de seleccionar el calibre de los conductores en las redes de distribucin en
media tensin se debern considerar los criterios sobre ubicacin de postera de la
presente norma, teniendo en cuenta que las nter distancias mximas debern ser el
doble de los valores estipulados para baja tensin.
En la Tabla 2.12 se muestran los criterios que se deben tener en cuenta para la
seleccin de los conductores en las redes areas de distribucin en media tensin.
En ellos se ha considerado el criterio de planeamiento que recomienda disear un
circuito para atender carga elctrica en suplencia de otro circuito, adems de las
consideraciones econmicas y de prdidas tcnicas de energa.
Tabla 2.12. Seleccin de conductores en redes areas de media tensin
Carga inicial de
Carga mxima
Calibre ACSR
2
diseo
normal
mm
AWG/KCM)
(A)
(MVA)
(A)
(MVA)
33.62 (2)*
40
0.92
67
1.53
13.2 kV
53.50 (1/0)*
67
1.53
92
2.10
135.2 (266.8)**
92
2.10
339
7.75
33.62 (2)*
37
2.21
61
3.65
34.5 kV
53.50 (1/0)*
61
3.65
84
5.02
135.2 (266.8)**
93
5.02
339
20.23
(*) Siempre y cuando la corriente de cortocircuito sea igual o inferior a 6 kA.
(**) Siempre y cuando la corriente de cortocircuito sea igual o inferior a 12 kA.
Tensin
de la red
Carga mxima en
suplencia
(A)
(MVA)
185
4.23
248
5.67
440
10.06
185
11.06
248
14.82
440
26.29
2.3.3 Acometidas.
2.3.3.1 Generalidades.
Las acometidas, desde redes areas en media tensin, podrn ser areas, en
conductor de aluminio cableado concntrico reforzado con ncleo de acero
recubierto ACSR (Aluminium Cable Steel Reinforced) o subterrneas, en conductor
monopolar de cobre aislado 100% en polietileno reticulado (90C) para 15 kV, en el
caso de acometidas a 13.2 kV, y para 35 kV, en el caso de acometidas a 34.5 kV.
Todo predio que posea ms de un transformador particular deber instalar todos los
transformadores dentro del predio y alimentarlos desde una acometida (o ms a
criterio de EMCALI) en media tensin.
Si un predio requiere ms de una acometida en media tensin cada una de ellas
debe llegar a un mismo sitio del edificio y por medio de un equipo de maniobra
seleccionar la alimentacin alterna o normal, sin permitir que accidentalmente se
20
Bajantes Cu-DD
2
Mm (AWG)
21.14 (4)
33.62 (2)
107.21 (4/0)
Bajantes Cu-DD
2
mm (AWG)
21.14 (4)
33.62 (2)
53.50 (1/0)
pulg
4
4
4
4
22
Conductor subterrneo
2
Cobre (Monopolar 15kV / 35 kV ) mm (AWG/KCM)
Tensin 13.2 kV
Tensin 34.5 kV
33.62 (2)
53.50 (1/0)
53.50 (1/0)
53.50 (1/0)
67.44 (2/0)
67.44 (2/0)
107.21 (4/0)
107.21 (4/0)
253.40 (500)
253.40 (500)
23
13.2 kV
34.5 kV
Mm
Pulg.
mm
Pulg.
33.62 (2)
76.2
3
53.50 (1/0)
101.6
4
67.44 (2/0)
101.6
4
107.21 (4/0)
101.6
4
101.6
4
253.4 (500) (*) (1)
76.2
3
76.2
3
(2)
101.6
4
152.4
6
(*)
Todos los dimetros sirven tanto para la seleccin del conducto metlico bajante, como del
conducto subterrneo en P.V.C, excepto los dimetros de los conductos para el conductor 500 kCMCu, donde el (1) corresponde al conducto subterrneo y el (2) corresponde al conducto metlico
bajante.
Todos los conductores irn por el mismo conducto, con excepcin del conductor subterrneo
500 kCM-Cu, sealado con el (1), donde cada conductor ir por un conducto.
Las uniones entre los conductores subterrneos en cobre y los conductores areos
en ACSR se realizarn mediante terminales premoldeados tipo exterior para cada
uno de los niveles de tensioness correspondientes.
En cada poste adyacente a la transicin se instalar un juego de descargadores de
sobretensiones y cuchillas trifsicas de accionamiento tripolar.
Los terminales premoldeados de los pases subterrneos se conectan a la red area
mediante entice y cable ACSR luego ste se empalmar con cable de cobre duro
desnudo con conectores bimetlicos de compresin. Las conexiones entre estos
conductores de cobre y los de ACSR se realizarn mediante conectores bimetlicos
tipo tornillo (2 por conductor).
Xc
I
(ohm/km)
(Amperios)
Cable 15 kV Cable 35 kV Cable 15 kV Cable 35 kV
15000
13000
12000
11500
9800
8150
7200
-20000
18500
17600
16500
13800
12500
172
225
256
297
343
471
488
168
218
248
282
237
428
470
SECCION CONDUCTOR
(mm2)
PESO
(Kg/km)
Cable 15 kV
Cable 35 kV
Cable 15 kV
Cable 35 kV
33.63
53.46
67.44
85.02
107.22
177.31
253.35
-53.46
67.44
85.02
107.22
177.31
253.35
820.5
1059
1224
1439.9
1682.5
2451
3234
1468
1643
1860
2112
2903
3874
26
CARGA MAXIMA
TOTAL
CARGA MAXIMA
EN SUPLENCIA
(A)
(MVA)
(A)
(MVA)
121
233
330
153
217
330
2.7
5.3
7.5
9.1
12.9
19.7
121
343
440
153
327
440
2.7
7.8
10
9.1
19.5
26.2
Tabla 2.20. Seleccin del dimetro de los conductos en redes de distribucin subterrnea en
media tensin
Calibre conductor de
2
cobre mm (AWG-KCM)
Media tensin
2.4.4 Acometidas.
2.4.4.1 Generalidades
Las acometidas, desde las redes subterrneas en media tensin, deben ser
subterrneas en conductor monopolar de cobre aislado 100%, polietileno reticulado
(90) para 15 kV., en el caso de acometidas a 13.2 kV. y para 35 kV., en el caso de
acometidas a 34.5 kV.
Las pantallas del cable monopolar de la acometida deben estar conectadas en uno
solo de los extremos al sistema puesto a tierra, en el lado de llegada de la acometida
al sistema principal depuesta a tierra.
Todo predio que posea ms de un transformador particular deber instalar todos los
transformadores dentro del predio y alimentados desde acometida(s) en media
tensin.
27
kV.
Pulgadas.
4
4
4
4
Tabla 2.22. Porcentaje de la seccin transversal en tubos conduit y tuberas para el llenado
de conductores.
Nmero de conductores
Todos los tipos de conductores
1
53%.
2
31%
Ms de 2
40%
28
TW
THW
Seccin
transversal del
conductor
2.08
3.30
5.25
8.36
13.29
21.14
33.62
53.50
67.44
85.02
107.21
126.67
152.01
177.34
253.35
380.02
405.36
456.03
506.70
633..38
14
12
10
8
6
4
2
1/0
2/0
3/0
4/0
250
300
350
500
750
800
900
1000
1250
4
3
3
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
8
7
5
3
2
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
1
15
12
9
5
4
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
1
27
21
17
10
7
5
4
2
1
1
1
1
1
1
1
0
0
0
0
0
1
37
29
23
14
10
8
6
3
3
2
1
1
1
1
1
1
1
0
0
0
2
61
49
38
23
17
13
9
5
5
4
3
2
2
1
1
1
1
1
1
1
2
93
76
61
32
23
17
13
8
7
6
5
4
3
3
1
1
3
143
117
95
49
36
27
20
12
10
9
7
6
5
4
3
2
3
192
157
127
66
48
36
27
16
14
12
10
8
7
6
4
3
163
85
62
47
34
21
18
15
13
10
9
8
6
4
Factores de ajuste para ms de tres conductores portadores de corriente en una canalizacin o cable con diversidad de carga.
Nmero de conductores portadores de corriente
De 4 a 6
De 7 a 9
De 10 a 20
De 21 a 30
De 31 a 40
De 41 en adelante
Ver excepciones NTC 2050 artculo 310-15
Debe aplicar la tabla 2-1 para conductores que van por bandeja y no estn separados segn normas.
29
REDES M.T.
REDES B.T.
3F
3F-4H
13200
120/208V
Sistema
Tensin (voltios)
Nivel de cortocirc.
PARMETROS DE DISEO
SUBTERRANEO
1,3
>2/0
AEREO
1/0
m2
5,5
Kva.
= kVA
4/0
aos
DEMANDA INDIVIDUAL =
6,7
KVA
250
r = 1%
10
Perodo:
4/0
)2 n
+ r
n =
4 a 1/0
4/0
(1
SUBTERRANEO
4 a 1/0 2,1
75
kVA
8,0 KA
AEREO
2F
3F
Usuarios
Cantidad
70
W
250
W
400
W
Kva.
No.
Kva.
TRANSFORMADOR
Carga
total Kva.
Urbanizacin
Cerrada
Urbanizacin
Abierta
Kva.
Kva.
Regulacin
ramal crtico
Bajante
Cu THW
AWG o
KCM
Cortacircuito
Pararrayo
(kv.)
Fusibles
AMP
TIPO
13
1.17
35
57,85
59,02
75
21
75
21
4/0
12
16
1.44
48
67,25
68,69
75
112,5
38
4/0
12
17
1.53
54
71,41
72,94
75
112,5
35
4/0
12
12
1.08
37
59,40
60,48
75
19
75
19
4/0
12
19
1.71
51
69,42
71,13
75
112,5
36
4/0
12
10
0.90
49
67,94
68,84
75
112,5
38
4/0
12
20
1.80
46
65,89
67,69
75
10
112,5
39
4/0
12
17
1.53
44
64,47
66,00
75
12
112,5
41
4/0
12
27
2.43
42
63,06
65,49
75
13
112,5
41
4/0
12
10
10
0.90
41
62,39
63,29
75
16
112,5
43
4/0
12
649
624
750
Total
161
14.49 447
30