CALCULO DE LA CAIDA DE TENSION TD - 1

SISTEMA TRIFASICO RESULTADOS


∆v= √3 x Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 22,558 w.
In = MD / √3 x V x Cos Φ 65.78 A.
Id = In x 1,25 82.22 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 19.20 m.
S = SECCION DEL CONDUCTOR (p/fase) 25 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 1.73 v.
∆ = % DE 220 v. 0.78 % < 2.50%

INTERRUPTOR GENERAL 3 x 100 A.

CALCULO DE LA CAIDA DE TENSION TD - 2


SISTEMA TRIFASICO RESULTADOS
∆v= √3 x Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 26,627 w.
In = MD / √3 x V x Cos Φ 77.64 A.
Id = In x 1,25 97.05 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 26.50 m.
S = SECCION DEL CONDUCTOR (p/fase) 25 mm.2 LSOH
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 LSOH
∆v. = CAIDA DE TENSION EN VOLTIOS 2.81 v.
∆ = % DE 220 v. 1.28 % < 2.50%

INTERRUPTOR GENERAL 3 x 100 A.

CALCULO DE LA CAIDA DE TENSION TD - 301


SISTEMA TRIFASICO RESULTADOS
∆v= √3 x Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 11,875 w.
In = MD / √3 x V x Cos Φ 34.63 A.
Id = In x 1,25 43.28 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 24.65 m.
S = SECCION DEL CONDUCTOR (p/fase) 16 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 1.82 v.
∆ = % DE 220 v. 0.83 % < 2.50%

INTERRUPTOR GENERAL 3 x 50 A.

CALCULO DE LA CAIDA DE TENSION TD - 401


SISTEMA TRIFASICO RESULTADOS
∆v= √3 x Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 11,875 w.
In = MD / √3 x V x Cos Φ 34.63 A.
Id = In x 1,25 43.28 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 27.35 m.
S = SECCION DEL CONDUCTOR (p/fase) 16 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 2.02 v.
∆ = % DE 220 v. 0.92 % < 2.50%

INTERRUPTOR GENERAL 3 x 50 A.

CALCULO DE LA CAIDA DE TENSION TD - 501


SISTEMA TRIFASICO RESULTADOS
∆v= √3 x Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 12,875 w.
In = MD / √3 x V x Cos Φ 37.54 A.
Id = In x 1,25 46.93 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 30.55 m.
S = SECCION DEL CONDUCTOR (p/fase) 16 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 2.45 v.
∆ = % DE 220 v. 1.11 % < 2.50%

INTERRUPTOR GENERAL 3 x 50 A.
CALCULO DE LA CAIDA DE TENSION TSG
SISTEMA TRIFASICO RESULTADOS
∆v= √3 x Id x ρ x Cos Φ x L / S
In = MD / √3 x V x Cos Φ 104.00 A.
Id = In x 1,25 130.00 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535
*mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.80
L = LONGITUD (DESDE EL MEDIDOR) 12.10 m.
S = SECCION DEL CONDUCTOR (p/fase) 50 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 16 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 0.76 v.
∆ = % DE 220 v. 0.35 % < 2.50%

INTERRUPTOR GENERAL 3 x 150 A.

CALCULO DE LA CAIDA DE TENSION ASCENSOR


SISTEMA TRIFASICO RESULTADOS
∆v= √3 x Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 8,250 w.
In = MD / √3 x V x Cos Φ 27.06 A.
Id = In x 1,25 33.83 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.80
L = LONGITUD (DESDE EL MEDIDOR) 19.20 m.
S = SECCION DEL CONDUCTOR (p/fase) 16 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 0.99 v.
∆ = % DE 220 v. 0.45 % < 1.50%

INTERRUPTOR GENERAL 3 x 60 A.
CALCULO DEL ALIMENTADOR DEL TABLERO DE SERVICIOS GENERALES

PARA EL CALCULO DEL ALIMENTADOR SE ESTA CONSIDERANDO EL 300% DE LA CORRIENTE NOMINAL DEL
MOTOR DEL ASCENSOR , PARA QUE EL ARRANQUE Y PARADA NO ALTERE CON UNA CAIDA DE TENSION
EXCESIVA EN EL NORMAL FUNCIONAMIENTO DE LAS DEMAS CARGAS DE SERVICIOS GENERALES.

MAXIMA DEMANDA DEL TSG ( MD tsg ) = 18,363 w.


MAXIMA DEMANDA DEL ASCENSOR ( MD asc ) = 6,600 w.
Cos Φ = 0.80

In = ( 3 x MD asc. )+ ( MD tsg - MD asc. ) / ( √3 x V. X Cos Φ )

REEMPLAZAMDO VALORES TENEMOS QUE :


In = 104 A.
Id = In x 1,25
Id = 129 A.

EL CONDUCTOR SELECCIONADO SERA : ### mm.2 THW CON UNA CAPACIDAD DE CORRIENTE DE 150 A.