Documentos de Académico
Documentos de Profesional
Documentos de Cultura
SSALAZAR
1 07/07/2015 A.COTA DCHIGNE I. TURCO EMISIÓN ORIGINAL 0
LBARRERA
Elaborado Revisado Aprobado Validado
No FECHA por: por: por: por: Descripción Estado
Nombre/Firma Nombre/Firma Nombre/Firma Nombre/Firma
4 ANÁLISIS DE CORTOCIRCUITO................................................................................................. 28
10. ANEXO C - ANALISIS DE CORTOCIRCUITO PARA CADA ESCENARIO DE OPERACIÓN ................. 239
TABLA 24. AJUSTES COMUNES PARA LOS RELÉS REF 615. 67N ....................................................... 47
TABLA 25. AJUSTES COMUNES PARA LOS RELÉS REF 615. 67N (CONTINUACIÓN) ........................... 48
TABLA 26. AJUSTES COMUNES PARA LOS RELÉS REF 615. 67N (CONTINUACIÓN) ........................... 49
TABLA 27. AJUSTES COMUNES PARA LOS RELÉS REF 615. 67 ......................................................... 50
TABLA 28. AJUSTES COMUNES PARA LOS RELÉS REF 615. 67 (CONTINUACIÓN).............................. 51
TABLA 29. AJUSTES COMUNES PARA LOS RELÉS REG 650. 67N ...................................................... 51
TABLA 30. AJUSTES COMUNES PARA LOS RELÉS REG 650. 67N (CONTINUACIÓN) .......................... 52
TABLA 31. AJUSTES COMUNES PARA LOS RELÉS REG 650. 67N (CONTINUACIÓN) .......................... 53
TABLA 32. AJUSTES COMUNES PARA LOS RELÉS REG 650. 67N (CONTINUACIÒN) .......................... 54
TABLA 33. AJUSTES COMUNES PARA LOS RELÉS REG 650. 49 ........................................................ 54
TABLA 34. AJUSTES COMUNES PARA LOS RELÉS REG 650. 49 (CONTINUACIÓN) ............................. 55
TABLA 35. AJUSTES COMUNES PARA LOS RELÉS REG 650. 50BF ..................................................... 56
IPS510203121-1-0000-207-CAL-002 Revisión:0 Fecha: 01/10/2015
COORDINACION DE PROTECCIONES DE SOBRECORRIENTE
Página 4
TABLA 36. AJUSTES COMUNES PARA LOS RELÉS REG 650. 52PD .................................................... 57
TABLA 37. AJUSTES COMUNES PARA LOS RELÉS REF 620. 67N ....................................................... 58
TABLA 38. AJUSTES COMUNES PARA LOS RELÉS REF 620. 67N (CONTINUACIÓN) ........................... 59
TABLA 39. AJUSTES COMUNES PARA LOS RELÉS REF 620. 67N (CONTINUACIÓN) ........................... 60
TABLA 40. AJUSTES COMUNES PARA LOS RELÉS REF 620. 67 ......................................................... 61
TABLA 41. AJUSTES COMUNES PARA LOS RELÉS REF 620. 67 (CONTINUACIÓN).............................. 62
TABLA 42. AJUSTES COMUNES PARA LOS RELÉS REF 630. 67N ....................................................... 62
TABLA 43. AJUSTES COMUNES PARA LOS RELÉS REF 630. 67N (CONTINUACIÓN) ........................... 63
TABLA 44. AJUSTES COMUNES PARA LOS RELÉS REF 630. 67N (CONTINUACIÓN) ........................... 64
TABLA 45. AJUSTES COMUNES PARA LOS RELÉS REF 630. 67 ......................................................... 65
TABLA 49. AJUSTES COMUNES PARA LOS RELÉS F650. 51SG .......................................................... 67
TABLA 50. AJUSTES COMUNES PARA LOS RELÉS F650. 50SG .......................................................... 68
TABLA 51. AJUSTES COMUNES PARA LOS RELÉS F650. 67SG .......................................................... 68
TABLA 52. AJUSTES COMUNES PARA LOS RELÉS F650. 67P ............................................................ 69
TABLA 53. AJUSTES COMUNES PARA LOS RELÉS F650. 67N ........................................................... 69
TABLA 59. AJUSTES PARA EL RELÉ R_TABLERO DE SIST SER 2 (CONTINUACIÓN) ............................. 73
TABLA 60. AJUSTES PARA EL RELÉ R_TABLERO DE SIST SER 2 (CONTINUACIÓN) ............................. 74
TABLA 61. AJUSTES PARA EL RELÉ R_TABLERO DE SIST SER 2 (CONTINUACIÓN) ............................. 75
TABLA 91. AJUSTES PARA EL RELÉ R_TABLERO DE SIST SER 1 (CONTINUACIÓN) ............................. 94
TABLA 92. AJUSTES PARA EL RELÉ R_TABLERO DE SIST SER 1 (CONTINUACIÓN) ............................. 94
TABLA 93. AJUSTES PARA EL RELÉ R_TABLERO DE SIST SER 1 (CONTINUACIÓN) ............................. 95
TABLA 184. AJUSTES PARA EL RELÉ R A17 REF 630 (CB-9) ............................................................ 144
TABLA 185. AJUSTES PARA EL RELÉ R A17 REF 630 (CB-9) (CONTINUACIÓN) ................................ 145
TABLA 186. AJUSTES PARA EL RELÉ R A17 REF 630 (CB-9) (CONTINUACIÓN) ................................ 145
TABLA 187. AJUSTES PARA EL RELÉ R A17 REF 630 (CB-9) (CONTINUACIÓN) ................................ 145
TABLA 188. AJUSTES PARA EL RELÉ R A17 REF 630 (CB-9) (CONTINUACIÓN) ................................ 146
TABLA 207. AJUSTES PARA EL RELÉ R REF 630 A20 ...................................................................... 155
TABLA 209. AJUSTES PARA EL RELÉ R REF 630 A20 (CONTINUACIÓN)........................................... 156
TABLA 210. AJUSTES PARA EL RELÉ R REF 630 A20 (CONTINUACIÓN)........................................... 157
TABLA 211. AJUSTES PARA EL RELÉ R REF 630 A20 (CONTINUACIÓN)........................................... 157
TABLA 219. AJUSTES PARA EL RELÉ R 1300SG003_P4 F650 (CONTINUACIÓN) .............................. 161
TABLA 220. AJUSTES PARA EL RELÉ R 1300SG003_P4 F650 (CONTINUACIÓN) .............................. 161
TABLA 221. AJUSTES PARA EL RELÉ R 1300SG003_P4 F650 (CONTINUACIÓN) .............................. 162
TABLA 222. AJUSTES PARA EL RELÉ R 1300SG003_P4 F650 (CONTINUACIÓN) .............................. 162
TABLA 224. AJUSTES PARA EL RELÉ R 1300SG006-01-P01 F650 (CONTINUACIÓN) ........................ 163
TABLA 225. AJUSTES PARA EL RELÉ R 1300SG006-01-P01 F650 (CONTINUACIÓN) ........................ 164
TABLA 226. AJUSTES PARA EL RELÉ R 1300SG006-01-P01 F650 (CONTINUACIÓN) ........................ 164
TABLA 228. AJUSTES PARA EL RELÉ R 1300SG006-01-P01 F650 (CONTINUACIÓN) ........................ 165
TABLA 230. AJUSTES PARA EL RELÉ R 1300SG006-02-P01 F650 (CONTINUACIÓN) ........................ 167
TABLA 231. AJUSTES PARA EL RELÉ R 1300SG006-02-P01 F650 (CONTINUACIÓN) ........................ 167
TABLA 232. AJUSTES PARA EL RELÉ R 1300SG006-02-P01 F650 (CONTINUACIÓN) ........................ 168
TABLA 233. AJUSTES PARA EL RELÉ R 1300SG006-02-P01 F650 (CONTINUACIÓN) ........................ 168
TABLA 235. AJUSTES PARA EL RELÉ R 1300SG006-02-P02 F650 (CONTINUACIÓN) ........................ 169
TABLA 236. AJUSTES PARA EL RELÉ R 1300SG006-02-P02 F650 (CONTINUACIÓN) ........................ 170
TABLA 237. AJUSTES PARA EL RELÉ R 1300SG006-02-P02 F650 (CONTINUACIÓN) ........................ 170
TABLA 238. AJUSTES PARA EL RELÉ R 1300SG006-02-P02 F650 (CONTINUACIÓN) ........................ 171
TABLA 239. AJUSTES PARA EL RELÉ R 1300SG006-02-P02 F650 (CONTINUACIÓN) ........................ 171
TABLA 247. AJUSTES PARA EL RELÉ R 1300ER005A-P01_2 P34N (CONTINUACIÓN) ....................... 176
TABLA 257. AJUSTES PARA EL RELÉ R 1300SE001-03-P01 F650 (CONTINUACIÓN) ......................... 181
TABLA 258. AJUSTES PARA EL RELÉ R 1300SE001-03-P01 F650 (CONTINUACIÓN) ......................... 182
TABLA 259. AJUSTES PARA EL RELÉ R 1300SE001-03-P01 F650 (CONTINUACIÓN) ......................... 182
TABLA 260. AJUSTES PARA EL RELÉ R 1300SE001-03-P01 F650 (CONTINUACIÓN) ......................... 183
TABLA 261. AJUSTES PARA EL RELÉ R 1300SE001-03-P01 F650 (CONTINUACIÓN) ......................... 183
TABLA 263. AJUSTES PARA EL RELÉ R 1300SG007-01-P01 F650 (CONTINUACIÓN) ........................ 184
TABLA 264. AJUSTES PARA EL RELÉ R 1300SG007-01-P01 F650 (CONTINUACIÓN) ........................ 185
TABLA 265. AJUSTES PARA EL RELÉ R 1300SG007-01-P01 F650 (CONTINUACIÓN) ........................ 185
TABLA 266. AJUSTES PARA EL RELÉ R 1300SG007-01-P01 F650 (CONTINUACIÓN) ........................ 186
TABLA 267. AJUSTES PARA EL RELÉ R 1300SG007-01-P01 F650 (CONTINUACIÓN) ........................ 186
TABLA 269. AJUSTES PARA EL RELÉ R 1300SG007-03-P01 F650 (CONTINUACIÓN) ........................ 187
TABLA 270. AJUSTES PARA EL RELÉ R 1300SG007-03-P01 F650 (CONTINUACIÓN) ........................ 187
TABLA 271. AJUSTES PARA EL RELÉ R 1300SG007-03-P01 F650 (CONTINUACIÓN) ........................ 188
TABLA 273. AJUSTES PARA EL RELÉ R 1300SG007-03-P01 F650 (CONTINUACIÓN) ........................ 189
TABLA 274. AJUSTES PARA EL RELÉ R 1300SG007-03-P01 F650 (CONTINUACIÓN) ........................ 189
TABLA 281. AJUSTES PARA EL RELÉ R 1300ER006A-P01_2 P34N (CONTINUACIÓN) ....................... 193
TABLA 282. AJUSTES PARA EL RELÉ R 1300ER006A-P01_2 P34N (CONTINUACIÓN) ....................... 193
TABLA 283. AJUSTES PARA EL RELÉ R 1300ER006A-P01_2 P34N (CONTINUACIÓN) ....................... 194
TABLA 284. AJUSTES PARA EL RELÉ R 1300ER006A-P01_2 P34N (CONTINUACIÓN) ....................... 194
TABLA 285. AJUSTES PARA EL RELÉ R 1300ER006A-P01_2 P34N (CONTINUACIÓN) ....................... 194
TABLA 286. AJUSTES PARA EL RELÉ R 1300ER006A-P01_2 P34N (CONTINUACIÓN) ....................... 195
TABLA 288. AJUSTES PARA EL RELÉ R 1460-SG-001 F650 (CONTINUACIÓN) .................................. 196
TABLA 289. AJUSTES PARA EL RELÉ R 1460-SG-001 F650 (CONTINUACIÓN) .................................. 196
TABLA 290. AJUSTES PARA EL RELÉ R 1460-SG-001 F650 (CONTINUACIÓN) .................................. 196
TABLA 292. AJUSTES PARA EL RELÉ R 1460-SG-001 F650 (CONTINUACIÓN) .................................. 197
TABLA 294. AJUSTES PARA EL RELÉ R 1300SG007-01-P02 F650 (CONTINUACIÓN) ........................ 199
TABLA 295. AJUSTES PARA EL RELÉ R 1300SG007-01-P02 F650 (CONTINUACIÓN) ........................ 199
TABLA 296. AJUSTES PARA EL RELÉ R 1300SG007-01-P02 F650 (CONTINUACIÓN) ........................ 200
TABLA 297. AJUSTES PARA EL RELÉ R 1300SG007-01-P02 F650 (CONTINUACIÓN) ........................ 200
TABLA 300. AJUSTES PARA EL RELÉ R 1300SG007-03-P02 F650 (CONTINUACIÓN) ........................ 202
TABLA 309. AJUSTES PARA EL RELÉ R AGUA POTABLE_1 F650 ..................................................... 209
TABLA 310. AJUSTES PARA EL RELÉ R AGUA POTABLE_1 F650 (CONTINUACIÓN).......................... 210
TABLA 313. AJUSTES PARA EL RELÉ R 1300ER005B-P01_1 F650 (CONTINUACIÓN) ........................ 212
TABLA 314. AJUSTES PARA EL RELÉ R 1300ER005B-P01_1 F650 (CONTINUACIÓN) ........................ 213
TABLA 315. AJUSTES PARA EL RELÉ R 1300ER005B-P01_1 F650 (CONTINUACIÓN) ........................ 213
TABLA 317. AJUSTES PARA EL RELÉ R 1300ER005B-P01_2 P34N (CONTINUACIÓN) ....................... 215
TABLA 318. AJUSTES PARA EL RELÉ R 1300ER005B-P01_2 P34N (CONTINUACIÓN) ....................... 215
TABLA 319. AJUSTES PARA EL RELÉ R 1300ER005B-P01_2 P34N (CONTINUACIÓN) ....................... 216
TABLA 328. AJUSTES PARA EL RELÉ R REF 620 A21 ...................................................................... 221
TABLA 329. AJUSTES PARA EL RELÉ R REF 620 A21 (CONTINUACIÓN)........................................... 222
TABLA 330. AJUSTES PARA EL RELÉ R REF 620 A21 (CONTINUACIÓN)........................................... 223
TABLA 332. AJUSTES PARA EL RELÉ R REF 630 A22 (CONTINUACIÓN)........................................... 225
TABLA 333. AJUSTES PARA EL RELÉ R REF 630 A22 (CONTINUACIÓN)........................................... 225
TABLA 334. AJUSTES PARA EL RELÉ R REF 630 A22 (CONTINUACIÓN)........................................... 226
TABLA 342. AJUSTES PARA EL RELÉ R 1300SG006-01-P02 F650 (CONTINUACIÓN) ........................ 231
2 METODOLOGÍA Y SOFTWARE
Para el desarrollo del estudio se empleó el software ETAP versión 12.6, el cual es una
herramienta especializada para el modelamiento de sistemas eléctricos industriales,
simulación de fallas y coordinación de protecciones, entre otras funcionalidades.
Con base en la información, suministrada, se modelaron cada uno de los elementos bajo
estudio en ETAP, y se llevó a cabo el proceso de ajuste y coordinación de las protecciones
respectivas, con base en los criterios descritos más adelante (numeral 5).
La topología del sistema eléctrico bajo estudio se muestra en el anexo B. Dicha topología fue
construida en el programa de análisis de circuitos ETAP de acuerdo a la información
suministrada por el cliente.
De acuerdo a lo anterior, se plantearon tres escenarios de operación. Para cada uno de estos
escenarios se definen en los transformadores T1 y T2 de la subestación Quellopata,
aterrizamiento sólido, y aterrizamiento con impedancias de 6.3 y 15 ohm respectivamente.
Unidad de
ID Línea Longitud R X Y(m Mho)
Impeda
LINEA AEREA 8 260.00 m 0 0 0 Ohms por1.000 km
LINEA AEREA 9 106.00 m 0 0 0 Ohms por1.000 km
Tabla 2. Parámetros de Líneas (continuación)
4 ANÁLISIS DE CORTOCIRCUITO
Una vez modelado el sistema, se procedió a simular cortos trifásicos y monofásicos bajo los
siguientes tres escenarios de operación.
Los criterios de coordinación presentados en este documento se rigen bajo la guía de criterios
de ajuste y coordinación de los sistemas de protección del SEIN, establecida por el comité de
operación económica del sistema interconectado nacional (COES).
IPS510203121-1-0000-207-CAL-002 Revisión:0 Fecha: 01/10/2015
COORDINACION DE PROTECCIONES DE SOBRECORRIENTE
Página 37
5.1 CRITERIOS GENERALES PARA EL AJUSTE DE PROTECCIONES DE
SOBRECORRIENTE
Los criterios de coordinación usados se basan adicionalmente de la siguiente documentación:
IEEE/ANSI C57, NFPA 70 y los libros Buff, Red y Brown de IEEE. Éstos básicamente buscan
garantizar una operación rápida, selectiva y coordinada. Los criterios más relevantes son:
3. Para las corriente de falla en cada punto final de las distintas ramas del sistema, el
dispositivo de protección más cercano debe operar de manera instantánea y se
coordina su operación con los demás dispositivos aguas arriba.
5. El ajuste de tiempo debe hacerse para que las fallas en el extremo remoto sean
despejadas en un tiempo máximo de 500 ms. Este tiempo asegura que la operación
más allá de la zona de protección operará en un tiempo mayor de 500 ms, lo que permite
obtener el adecuado margen de tiempo para la operación coordinada de las
protecciones de la propia zona con la de la zona siguiente. Este ajuste corresponde al
IPS510203121-1-0000-207-CAL-002 Revisión:0 Fecha: 01/10/2015
COORDINACION DE PROTECCIONES DE SOBRECORRIENTE
Página 38
elemento (51). (Tomado de los criterios de ajuste y coordinación de los sistemas de
protección del SEIN)
2. El ajuste para la unidad de tiempo inverso de tierra (51N) es el menor valor entre el 10%
de la corriente nominal de la carga y el 30% de la corriente de falla a tierra.
3. Los valores de corriente de las unidades instantáneas de fase y tierra (50 y 50N), se
ajustan en el 50% de la corriente de falla trifásica y monofásica respectivamente.
1. Como criterio general, las curvas de operación de fase se ajustan para no causar
disparo ante las corrientes de energización estimadas y así operar por debajo del límite
térmico del equipo. Las unidades inversas de los relés de sobrecorriente de fase (51)
se ajustan al 115% de la corriente nominal del transformador.
2. Para las unidades inversas de los relés de sobrecorriente de tierra (51N) el criterio es
el 30% la corriente nominal del transformador.
Las unidades instantáneas de fase y tierra (50 y 50N) se ajustan al 50% de la corriente
de falla trifásica y monofásica respectivamente.
3. En alta tensión las unidades instantáneas de fase y tierra (50 y 50N) se ajustan de
acuerdo a los siguientes criterios:
La unidad instantánea de fase (50) se ajusta para el menor valor entre:
10 veces la corriente nominal del devanado (In).
1.25 veces el máximo aporte de corriente por el lado primario a la corriente de falla
trifásica en el secundario.
1.25 veces el máximo aporte de corriente por el lado primario a la corriente de falla
trifásica en el secundario.
2. Las unidades inversas de los relés de sobrecorriente de fase (51) se ajustan al 115%
de la corriente nominal del generador.
3. Para las unidades inversas de los relés de sobrecorriente de tierra (51N) el criterio es
el 30% la corriente nominal del generador.
4. Las unidades instantáneas de fase y tierra (50 y 50N) se ajustan al 50% de la corriente
de falla trifásica y monofásica respectivamente.
A continuación se muestran los elementos que son objeto de este estudio de coordinación de
protecciones.
SETTING DEFAULT
NAME STEP RANGE VALUE
DESCRIPTION VALUE
Directional earth Start Value Start value 0,01 00:05 0,010 - 5,00 0,01
fault protection, Multiplier for
low stage (67N-1), Start value
scaling the start 1 0,1 0,8 - 10,0 1
DEFLPDEF Mult
value
1=Non
Directional 2= directional 2=
Directional Mode -
Mode Forward 2=Forward Forward
3=Reverse
Time multiplier in
Time
IEC/ANSI IDMT 1.00 0,01 0,05 - 15,00 1.00
multiplier
curves
Tabla 24. Ajustes comunes para los relés REF 615. 67N
Tabla 26. Ajustes comunes para los relés REF 615. 67N (Continuación)
SETTING DEFAULT
NAME STEP RANGE VALUE
Sensitive DESCRIPTION VALUE
directional
residual Operation Off/On Operation Off - Off - On Off
overcurrent and
power protection Selection of 3I0Cosfi
(67N) SDEPSDE operation mode for OpMode 3I0Cosfi - 3I03U0Cosfi 3I0Cosfi
protection 3I0 and fi
Direction of
Forward -
operation forward DirMode Foward - Foward
Reverse
or reverse
Relay characteristic
RCADir -90 1 -179 - 180 -90
angle RCA
Relay charactricstic 0.0
angle RCAComp 0.0 0.1 -10 - 10
compensation
Tabla 29. Ajustes comunes para los relés REG 650. 67N
Tabla 30. Ajustes comunes para los relés REG 650. 67N (Continuación)
IEC inv.
IEC Ext. Inv
Programmable
RI type
RD type
Minimum operate
time for IEC IDMT tMin 0.040 0.001 0.00 - 60.00 0.040
curves
IDMT time multiplier
for non directional kIN 1.00 0.01 0.00 - 2.00 1.00
residual overcurrent
Operation of non
directional residual OpUN> Off - Off - On Off
overvoltage
Tabla 31. Ajustes comunes para los relés REG 650. 67N (Continuación)
Tabla 32. Ajustes comunes para los relés REG 650. 67N (continuaciòn)
1 out of 4
Operation mode of RetripMode Operation - Retrip Operation
re-trip logic mode of re- Off mode of
Breaker failure
trip logic CB Pos re-trip
protection, 3-
Check logic
phase activation
No
and output
CBPos
(50BF) CCRBRF
Check
IP> Operate 1 Operate
Operate phase phase current phase
current level in % level in % of current
of Ibase Ibase level in %
5 - 200 of Ibase
IN> Operate Operate
Operate residual residual residual
current level in % current level current
of in % of level in %
Ibase Ibase of
1 2 - 200 Ibase
Time delay of re- t1 Time delay of 0.001 0.000 - Time delay
trip re-trip 60.000 of re-trip
t2 Time delay of 0.001 Time delay
Time delay of
back-up trip 0.000 - of back-up
back-up trip
60.000 trip
Tabla 35. Ajustes comunes para los relés REG 650. 50BF
3=Reverse
Time multiplier in
Time
IEC/ANSI IDMT 1.00 0,01 0,05 - 15,00 1.00
multiplier
curves
1=ANSI
Ext. Inv
2=ANSI
Very inv.
3=ANSI
Norm. Inv
4=ANSI
Mod. Inv
5=ANSI
Def. Time
6=L.T.E inv
7=L.T.V.
inv 15=IEC
Selection of time Operating 15=IEC
- 8=L.T. inv Def.
delay curve type curve type Def. Time
Time
9=IEC
Norm. Inv
10=IEC
Very inv
11=IEC inv.
12=IEC
Ext. Inv
13=IEC
S.T. inv.
14=IEC L.T
inv
Tabla 37. Ajustes comunes para los relés REF 620. 67N
17=Program
mable
18=RI type
19=RD type
Directional earth
Characteristic Characteristic
fault protection, 60 1 -179 - 180 60
low stage (67N-1), angle angle
DEFLPDEF
Maximum
phase angle in Max. Forward
80 1 0 - 180 80
forward angle
direction
Maximum
phase angle in Max. Reverse
80 1 0 - 180 80
reverse angle
direction
Minimum phase
Min. Forward
angle in forward 80 1 0 - 180 80
angle
direction
Minimum phase
Min. Reverse
angle in reverse 80 1 0 - 180 80
angle
direction
Voltage start
Voltage start value Forward - 0.010 - 1.00 Forward
value
Tabla 38. Ajustes comunes para los relés REF 620. 67N (Continuación)
SETTING
DESCRIPTION NAME DEFAULT VALUE STEP RANGE VALUE
setpoint > protection elements > sensitive ground current > sensitive ground TOC
Fucntion [DISABLED-
N/A
permission Function DISABLED ENABLED] DISABLED
SENSITIVE Input Type Input PHASOR (DFT) N/A [PHASOR - RMS] PHASOR (DFT)
GROUND TIME Pickup 0,001
DELAYED Pickup Level Level 0,05 A [0.05:160.00] 0,05
OVERCURRENT N/A [See list of curves]
Curve Shape Curve IEEE Ext Inv IEEE Ext Inv
ELEMENT
TD 0,001
(51SG)
Time Dial Multiplier 1,00 s [0.00:900.00] 1
[INSTANTANEOUS
N/A
Reset Type Reset INSTANTANEOUS - LINEAR] INSTANTANEOUS
Snapshot [DISABLED-
Event Snapshot ENABLED N/A ENABLED]
Generation Events ENABLED
Tabla 49. Ajustes comunes para los relés F650. 51SG
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > sensitive ground current > sensitive ground directional
[DISABLED- DISABLE
N/A
SENSITIVE Fucntion permission Function DISABLED ENABLED] D
Maximum Torque 1
GROUND -45
DIRECTION Angle MTA Deg [-90:+90] -45
AL [FORWARD- FORWAR
FORWARD N/A
ELEMENT Operation Direction Direction REVERSE] D
(67SG) PERMISSIO [BLOCK - PERMISS
N/A
Block Logic Type Block Logic N PERMISSION] ION
Polarization Voltage Pol V
10 1V
Threshold Threshold [0:300] 10
Snapshot event Snapshot [DISABLED- ENABLE
ENABLED N/A
generation Events ENABLED] D
Tabla 51. Ajustes comunes para los relés F650. 67SG
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral directional
Function [DISABLED- DISABLE
DISABLED N/A
Permission Function ENABLED] D
Maximum Torque
-45 1 Deg
Angle MTA [-90:+90] -45
NEUTRAL Operation [FORWARD- FORWAR
DIRECTIONA FORWARD N/A
Direction Direction REVERSE] D
L ELEMENT [Vo - Ip - Vo+Ip
(67N) VO N/A
Polarization type Polarization - Vo *Ip] VO
PERMISSIO [BLOCK - PERMISS
Block Logic Type N/A
Block Logic N PERMISSION] ION
Polarization
Voltage Pol 10 1V
Threshold Threshold [0:300] 10
Snapshot Event Snapshot [DISABLED-
ENABLED N/A
Generation Events ENABLED] ENABLED
Tabla 53. Ajustes comunes para los relés F650. 67N
SETTING DEFAULT
NAME STEP RANGE VALUE
DESCRIPTION VALUE
Start Value Start Value 0,05 0,01 0,05 - 5,00 0.79
Multiplier for
Start Value
scaling the start 1,00 0,1 0,8 - 10,0 1.00
Mult
value
Time multiplier
Time
in IEC/ANSI 1,00 0,01 0,05 - 15,00 1.00
multiplier
curves
Three phase non Operate delay Operate
40 10 40 - 200000 90 ms
directional time delay time
overcurrent 1=ANSI Ext. Inv
protection, low 2=ANSI Very inv.
stage (51P-1) 3=ANSI Norm. Inv
PHLPTOC 4=ANSI Mod. Inv
Three phase non 5=ANSI Def. Time
directional
6=L.T.E inv
overcurrent
7=L.T.V. inv
protection, high
stage (51P-2) 8=L.T. inv
9=IEC
PHHPTOC Selection of time Operating 15=IEC 9=IEC Norm. Inv
- Norm.
delay curve type curve type Def. Time 10=IEC Very inv
Inv
11=IEC inv.
12=IEC Ext. Inv
13=IEC S.T. inv.
14=IEC L.T inv
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Tabla 54. Ajustes para el relé R_6220-TL-001A_LV1
SETTING DEFAULT
NAME STEP RANGE VALUE
DESCRIPTION VALUE
Start
Start Value 0,010 0,005 0,010 - 5,000 0.033
value
Multiplier for
Start
scaling the start 1,000 0,1 0,8 - 10,0 1
value Mult
value
Time multiplier
Time
in IEC/ANSI 1,000 0,01 0,05 - 15,00 1
multiplier
IDMT curves
Non directional Operate delay Operate
40 10 40 - 200000 90 ms
earth fault time delay time
protection, low 1=ANSI Ext. Inv
stage (51N-1) 2=ANSI Very inv.
EFLPTOC 3=ANSI Norm. Inv
Non directional 4=ANSI Mod. Inv
earth fault 5=ANSI Def. Time
protection, high 6=L.T.E inv
stage (51N-2)
7=L.T.V. inv
EFHPTOC
8=L.T. inv 9=IEC
Selection of time Operating 15= IEC
- 9=IEC Norm. Inv Norm.
delay curve type curve type Def. Time
10=IEC Very inv Inv
11=IEC inv.
12=IEC Ext. Inv
13=IEC S.T. inv.
14=IEC L.T inv
15=IEC Def. Time
17=Programmable
18=RI type
Tabla 56. Ajustes para el relé R_6220-TL-001A_LV1 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Operation Off/On Operatio Off - Off
n
On On
Directional mode of DirMode Non - Off Non
step 1 off / non- 1 directional directional
directional / forward / Non
reverse direction
al
Forward
Reverse
Reverse
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
0,010 -
Start Value Start value 0,010 0,005 5,000 0.44
Multiplier for
Start value
scaling the
Mult
start value 1,000 0,1 0,8 - 10,0 1.00
Time multiplier
in IEC/ANSI 0,05 -
IDMT curves Time multiplier 1,000 0,01 15,00 1.00
Operate delay Operate delay 40 -
Non directional 40
earth fault time time 10 200000 50 ms
protection, low Selection of Operating 15= IEC Def. - 1=ANSI 9=IEC
stage (51N-1) time delay curve type Time Ext. Inv Norm. Inv
EFLPTOC curve type 2=ANSI
Non directional Very inv.
earth fault 3=ANSI
protection, high Norm. Inv
stage (51N-2) 4=ANSI
EFHPTOC Mod. Inv
5=ANSI
Def. Time
6=L.T.E inv
7=L.T.V.
inv
8=L.T. inv
9=IEC
Norm. Inv
10=IEC
Very inv
Tabla 64. Ajustes para el relé R_BOLAS MOTOR 1 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start value 0,010 0,005 0,010 - 5,000 0.11
Multiplier for
Start value
scaling the
Mult
start value 1,000 0,1 0,8 - 10,0 1.00
Time multiplier
in IEC/ANSI Time
IDMT curves multiplier 1,000 0,01 0,05 - 15,00 1.00
Operate delay Operate
Non 40
time delay time 10 40 - 200000 50 ms
directional Selection of Operating 15= IEC - 9=IEC Norm.
earth fault 1=ANSI Ext. Inv
time delay curve type Def. Time Inv
protection, curve type 2=ANSI Very inv.
low stage 3=ANSI Norm. Inv
(51N-1)
EFLPTOC 4=ANSI Mod. Inv
Non 5=ANSI Def. Time
directional 6=L.T.E inv
earth fault
protection, 7=L.T.V. inv
high stage 8=L.T. inv
(51N-2) 9=IEC Norm. Inv
EFHPTOC
10=IEC Very inv
11=IEC inv.
12=IEC Ext. Inv
13=IEC S.T. inv.
14=IEC L.T inv
15=IEC Def. Time
17=Programmable
18=RI type
Tabla 69. Ajustes para el relé R_BOLAS MOTOR 2 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start Value 0,05 0,01 0,05 - 5,00 2.85
Multiplier for
scaling the start Start Value
value Mult 1,00 0,1 0,8 - 10,0 1.00
Time multiplier in 0,05 -
IEC/ANSI curves Time multiplier 1,00 0,01 15,00 1.00
Operate delay time Operate delay 40 40 -
time 10 200000 ms 50 ms
Three phase Selection of time Operating 15=IEC Def. - 1=ANSI 9=IEC
non delay curve type curve type Time Ext. Inv Norm. Inv
directional 2=ANSI
overcurrent Very inv.
protection, 3=ANSI
low stage Norm. Inv
(51P-1) 4=ANSI
PHLPTOC Mod. Inv
Three phase 5=ANSI
non Def. Time
directional
6=L.T.E inv
overcurrent
7=L.T.V.
protection,
inv
high stage
(51P-2) 8=L.T. inv
PHHPTOC 9=IEC
Norm. Inv
10=IEC
Very inv
11=IEC inv.
12=IEC
Ext. Inv
13=IEC
S.T. inv.
14=IEC L.T
inv
Tabla 71. Ajustes para el relé R_Molino SAG
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start value 0.010 0,005 0,010 - 5,000 0.035
Multiplier for
Start value
scaling the start
Mult
value 1.00 0,1 0,8 - 10,0 1
Time multiplier in
IEC/ANSI IDMT Time
curves multiplier 1.00 0,01 0,05 - 15,00 1
Selection of time Operating ANSI Def. - ANSI Ext. Inv IEC Norm. Inv
delay curve type curve type Time
Non ANSI Very inv.
directional
ANSI Norm.
earth fault
protection, Inv
low stage ANSI Mod. Inv
(51N-1) ANSI Def.
EFLPTOC Time
Non L.T.E inv
directional
earth fault L.T.V. inv
protection, L.T. inv
high stage IEC Norm. Inv
(51N-2)
EFHPTOC IEC Very inv
IEC inv.
IEC Ext. Inv
IEC S.T. inv.
IEC Def. Time
Programmable
RI type
RD type
Operate delay Operate
time delay time 0 0,01 0,04 - 200,00 90 ms
Tabla 78. Ajustes para el relé R_6220-TL-001A_HV 1 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start Value 0,05 0,01 0,05 - 5,00 0.83
Multiplier for
scaling the start Start Value
value Mult 1,00 0,1 0,8 - 10,0 1.00
Time multiplier in 0,05 -
IEC/ANSI curves Time multiplier 1,00 0,01 15,00 1.00
Operate delay time Operate delay 40 40 -
time 10 200000 ms 90 ms
Three phase Selection of time Operating 15=IEC Def. - 1=ANSI 9=IEC
non delay curve type curve type Time Ext. Inv Norm. Inv
directional 2=ANSI
overcurrent Very inv.
protection, 3=ANSI
low stage Norm. Inv
(51P-1) 4=ANSI
PHLPTOC Mod. Inv
Three phase 5=ANSI
non Def. Time
directional
6=L.T.E inv
overcurrent
protection, 7=L.T.V.
high stage inv
(51P-2) 8=L.T. inv
PHHPTOC 9=IEC
Norm. Inv
10=IEC
Very inv
11=IEC inv.
12=IEC
Ext. Inv
13=IEC
S.T. inv.
14=IEC L.T
inv
Tabla 80. Ajustes para el relé R_6220-TL-001A_HV 2
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start
Start Value value 0,010 0,005 0,010 - 5,000 0.173
Multiplier for Start
scaling the start value
value Mult 1,000 0,1 0,8 - 10,0 1.00
Time multiplier Time
in IEC/ANSI multiplie
IDMT curves r 1,000 0,01 0,05 - 15,00 1.00
Operate
Operate delay
delay 40
time
time 10 40 - 200000 50 ms
Selection of Operati 15= IEC - 1=ANSI Ext. 9=IEC
Non directional earth time delay ng Def. Time Inv Norm. Inv
fault protection, low curve type curve 2=ANSI Very
stage (51N-1) type inv.
EFLPTOC 3=ANSI
Non directional earth Norm. Inv
fault protection, high 4=ANSI Mod.
stage (51N-2) Inv
EFHPTOC 5=ANSI Def.
Time
6=L.T.E inv
7=L.T.V. inv
8=L.T. inv
9=IEC Norm.
Inv
10=IEC Very
inv
11=IEC inv.
12=IEC Ext.
Inv
13=IEC S.T.
inv.
Tabla 87. Ajustes para el relé R_6220-TL-001B_HV (Continuación)
Non DEFAULT
directional SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
earth fault 0.05 -
protection, Start Value Start Value 1.00 0.01 40.00 4.00
instantane Multiplier for scaling the Start value 0.8 -
ous stage start value Mult 1.0 0.1 10.0 1.00
(50N/51N) Operate delay 20 -
EFIPTOC Operate delay time time 20 20 200000 50 ms
Tabla 89. Ajustes para el relé R_6220-TL-001B_HV (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
0,010 -
Start Value Start value 0,010 0,005 5,000 0.832
Multiplier for
scaling the start Start value Mult
value 1,000 0,1 0,8 - 10,0 1
Time multiplier in
IEC/ANSI IDMT
curves Time multiplier 1,000 0,01 0,05 - 15,00 1
Operate delay Operate delay
40
Non time time 10 40 - 200000 50 ms
directional Selection of time Operating curve 15= IEC Def. - 1=ANSI Ext.
earth fault delay curve type type Time Inv
protection, low 2=ANSI
stage (51N-1) Very inv.
EFLPTOC 3=ANSI
Non Norm. Inv
directional 4=ANSI
earth fault Mod. Inv
protection, 5=ANSI Def.
high stage Time
(51N-2) 6=L.T.E inv
EFHPTOC
7=L.T.V. inv
8=L.T. inv
9=IEC
Norm. Inv
10=IEC Very
inv
11=IEC inv.
12=IEC Ext.
Inv
13=IEC S.T.
inv.
Tabla 92. Ajustes para el relé R_Tablero de Sist Ser 1 (Continuación)
Non DEFAULT
directional SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
earth fault 1.00 -
protection, Start Value Start Value 1.00 0.01 40.00 5
instantane Multiplier for scaling the Start value
ous stage start value Mult 1.0 0.1 0.8 - 10.0 1
(50N/51N) Operate 20 -
EFIPTOC Operate delay time delay time 20 20 200000 50ms
Tabla 94. Ajustes para el relé R_Tablero de Sist Ser 1 (Continuación)
SETTING
DESCRIPTIO DEFAULT STE
N NAME VALUE P RANGE VALUE
Start Value Start value 0,010 0,005 0,010 - 5,000 0.173
Multiplier for
Start value
scaling the
Mult
start value 1,000 0,1 0,8 - 10,0 1.00
Time
multiplier in
IEC/ANSI Time
IDMT curves multiplier 1,000 0,01 0,05 - 15,00 1.00
Operate delay Operate
40
time delay time 10 40 - 200000 50 ms
Non directional earth Selection of Operating 15= IEC - 1=ANSI Ext. 9=IEC
fault protection, low time delay curve type Def. Time Inv Norm. Inv
stage (51N-1) curve type 2=ANSI Very
EFLPTOC inv.
Non directional earth 3=ANSI
fault protection, high Norm. Inv
stage (51N-2) 4=ANSI Mod.
EFHPTOC Inv
5=ANSI Def.
Time
6=L.T.E inv
7=L.T.V. inv
8=L.T. inv
9=IEC Norm.
Inv
10=IEC Very
inv
11=IEC inv.
12=IEC Ext.
Inv
Tabla 97. Ajustes para el relé R_6220-TL-002_HV (Continuación)
Non DEFAULT
directional SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
earth fault 0.05 -
protection, Start Value Start Value 1.00 0.01 40.00 4.00
instantane Multiplier for scaling the
ous stage start value Start value Mult 1.0 0.1 0.8 - 10.0 1.00
(50N/51N) Operate delay 20 -
EFIPTOC Operate delay time time 20 20 200000 50 ms
Tabla 99. Ajustes para el relé R_6220-TL-002_HV (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
0,010 -
Start Value Start value 0,010 0,005 5,000 0.173
Multiplier for scaling Start value
the start value Mult 1,000 0,1 0,8 - 10,0 1.00
Time multiplier in
IEC/ANSI IDMT 0,05 -
curves Time multiplier 1,000 0,01 15,00 1.00
Non Operate delay 40 -
directional Operate delay time 40
time 10 200000 50 ms
earth fault Selection of time Operating 15= IEC Def. - 1=ANSI 9=IEC
protection delay curve type curve type Time Ext. Inv Norm. Inv
, low 2=ANSI
stage Very inv.
(51N-1) 3=ANSI
EFLPTOC
Norm. Inv
Non
4=ANSI
directional
Mod. Inv
earth fault
5=ANSI
protection
Def. Time
, high
stage 6=L.T.E inv
(51N-2) 7=L.T.V.
EFHPTOC inv
8=L.T. inv
9=IEC
Norm. Inv
10=IEC
Very inv
11=IEC
inv.
12=IEC
Ext. Inv
Tabla 107. Ajustes para el relé R_6220-TL-004_HV (Continuación)
Non DEFAULT
directional SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
earth fault 0.05 -
protection, Start Value Start Value 1.00 0.01 40.00 4.00
instantane Multiplier for scaling the Start value 0.8 -
ous stage start value Mult 1.0 0.1 10.0 1.00
(50N/51N) Operate delay 20 -
EFIPTOC Operate delay time time 20 20 200000 50 ms
Tabla 109. Ajustes para el relé R_6220-TL-004_HV (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start Value 0,05 0 0,05 - 5,00 0.73
Multiplier for scaling
the start value Start Value Mult 1,00 0,1 0,8 - 10,0 1
Time multiplier in 0,05 -
IEC/ANSI curves Time multiplier 1,00 0 15,00 1
Selection of time Operating curve IEC Def. - ANSI Ext. IEC Very
delay curve type type Time Inv inv
ANSI Very
inv.
ANSI
Three phase Norm. Inv
non directional ANSI Mod.
overcurrent Inv
protection, ANSI Def.
low stage Time
(51P-1) L.T.E inv
PHLPTOC
Three phase L.T.V. inv
non directional L.T. inv
overcurrent IEC Norm.
protection, Inv
high stage IEC Very
(51P-2) inv
PHHPTOC
IEC inv.
IEC Ext. Inv
IEC S.T.
inv.
IEC Def.
Time
Programma
ble
RI type
RD type
Operate delay 0,04 -
Operate delay time time 0,04 0 200,00 340 ms
Tabla 114. Ajustes para el relé R_6220-TL-005_HV 2
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
0,010 -
Start Value Start value 0,010 0 5,000 0.173
Multiplier for
scaling the start Start value Mult
value 1,000 0,1 0,8 - 10,0 1
Time multiplier in
IEC/ANSI IDMT
curves Time multiplier 1,000 0 0,05 - 15,00 1
Selection of time Operating curve ANSI Def. - ANSI Ext. IEC Norm.
Non delay curve type type Time Inv Inv
directional ANSI Very
earth fault inv.
protection, low ANSI Norm.
stage (51N-1) Inv
EFLPTOC
ANSI Mod.
Non
Inv
directional
ANSI Def.
earth fault
Time
protection,
high stage L.T.E inv
(51N-2) L.T.V. inv
EFHPTOC
L.T. inv
IEC Norm.
Inv
IEC Very
inv
IEC inv.
IEC Ext. Inv
IEC S.T.
inv.
IEC Def.
Time
Tabla 116. Ajustes para el relé R_6220-TL-005_HV 2 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start Value 0,05 0,01 0,05 - 5,00 0.71
Multiplier for
scaling the start Start Value
Three phase value Mult 1,00 0,1 0,8 - 10,0 1.00
non directional Time multiplier in
overcurrent IEC/ANSI curves Time multiplier 1,00 0,01 0,05 - 15,00 1.00
protection, Operate delay Operate delay 40 40 - 200000
low stage time time 10 ms 50 ms
(51P-1) Selection of time Operating 15=IEC - 1=ANSI Ext. 9=IEC
PHLPTOC delay curve type curve type Def. Time Inv Norm. Inv
Three phase 2=ANSI Very
non directional inv.
overcurrent 3=ANSI
protection, Norm. Inv
high stage 4=ANSI Mod.
(51P-2) Inv
PHHPTOC 5=ANSI Def.
Time
6=L.T.E inv
7=L.T.V. inv
8=L.T. inv
Tabla 119. Ajustes para el relé R_6220-TL-005_HV 1
Three DEFAULT
phase non SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
directional 1.0 -
overcurren Start Value Start Value 1.00 0,01 40.00 6
t Multiplier for scaling the Start Value 0,8 -
protection, start value Mult 1.00 0.1 10,0 1.00
instantane
ous stage
(50P/51P) Operate delay 20 -
PHIPTOC Operate delay time time 20 10 200000 40 ms
Tabla 121. Ajustes para el relé R_6220-TL-005_HV 1 (Continuación)
SETTING
Non
DESCRIPTION NAME DEFAULT VALUE STEP RANGE VALUE
directional
1.00 -
earth fault
Start Value Start Value 1.00 0.01 40.00 0.357
protection,
Multiplier for
instantaneous
scaling the Start value 0.8 -
stage
start value Mult 1.0 0.1 10.0 1.00
(50N/51N)
EFIPTOC Operate delay Operate 20 -
time delay time 20 20 200000 50 ms
Tabla 123. Ajustes para el relé R_6220-TL-005_HV 1 (Continuación)
IEC inv.
IEC Ext.
Inv
IEC S.T.
inv.
IEC Def.
Time
Programma
ble
RI type
RD type
Operate delay 0,04 -
Operate delay time time 0,04 0,01 200,00 50 ms
Tabla 130. Ajustes para el relé R_6320-TD-003_HV 2 (Continuación)
Non DEFAULT
directional SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
earth fault 0.10 -
protection, Start Value Start Value 0.10 0.01 40.00 0.357
instantane Multiplier for scaling the Start value 0.8 -
ous stage start value Mult 1.0 0.1 10.0 1
(50N/51N) Operate delay 0.02 -
EFIPTOC Operate delay time time 0.02 0.02 200.00 50 ms
Tabla 134. Ajustes para el relé R_6320-TD-003_HV 2 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start value 0,010 0,01 0,010 - 5,000 0.185
Multiplier for
Start value
scaling the
Mult
start value 1,000 0,1 0,8 - 10,0 1.00
Time multiplier
in IEC/ANSI Time
IDMT curves multiplier 1,000 0,01 0,05 - 15,00 1.00
Operate delay Operate
40
Non time delay time 10 40 - 200000 50 ms
directional Selection of Operating 15= IEC - 1=ANSI Ext. Inv 9=IEC
earth fault time delay curve type Def. Time Norm. Inv
curve type 2=ANSI Very inv.
protection, low
stage (51N-1) 3=ANSI Norm. Inv
EFLPTOC 4=ANSI Mod. Inv
Non
5=ANSI Def. Time
directional
earth fault 6=L.T.E inv
protection, 7=L.T.V. inv
high stage
(51N-2) 8=L.T. inv
EFHPTOC 9=IEC Norm. Inv
10=IEC Very inv
11=IEC inv.
12=IEC Ext. Inv
13=IEC S.T. inv.
14=IEC L.T inv
15=IEC Def. Time
17=Programmable
18=RI type
Tabla 137. Ajustes para el relé R_6320-TD-003_HV 1 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start value 0,010 0,005 0,010 - 5,000 0.185
Multiplier for
Start value
scaling the start
Mult
value 1,000 0,1 0,8 - 10,0 1.00
Time multiplier in
IEC/ANSI IDMT Time
curves multiplier 1,000 0,01 0,05 - 15,00 1.00
Operate
Non Operate delay time 40
delay time 10 40 - 200000 50 ms
directional Selection of time Operating 15= IEC - 9=IEC
earth fault 1=ANSI Ext. Inv
delay curve type curve type Def. Time Norm. Inv
protection, 2=ANSI Very inv.
low stage 3=ANSI Norm. Inv
(51N-1)
EFLPTOC 4=ANSI Mod. Inv
Non 5=ANSI Def. Time
directional 6=L.T.E inv
earth fault
protection, 7=L.T.V. inv
high stage 8=L.T. inv
(51N-2) 9=IEC Norm. Inv
EFHPTOC
10=IEC Very inv
11=IEC inv.
12=IEC Ext. Inv
13=IEC S.T. inv.
14=IEC L.T inv
15=IEC Def. Time
17=Programmable
18=RI type
Tabla 147. Ajustes para el relé R_6320-TD-004_HV 1 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start Value 0,05 0,01 0,05 - 5,00 0.71
Multiplier for scaling the Start Value
start value Mult 1,00 0,1 0,8 - 10,0 1
Time multiplier in
IEC/ANSI curves Time multiplier 1,00 0,01 0,05 - 15,00 1
Selection of time delay Operating IEC Def. - ANSI Ext. Inv IEC
curve type curve type Time Norm.
Three ANSI Very inv.
phase non Inv
ANSI Norm.
directional Inv
overcurrent
protection, ANSI Mod. Inv
low stage ANSI Def.
(51P-1) Time
PHLPTOC L.T.E inv
Three L.T.V. inv
phase non
directional L.T. inv
overcurrent IEC Norm. Inv
protection, IEC Very inv
high stage
(51P-2) IEC inv.
PHHPTOC IEC Ext. Inv
IEC S.T. inv.
IEC Def. Time
Programmable
RI type
RD type
Operate delay
Operate delay time time 0,04 0,01 0,04 - 200,00 50 ms
Tabla 149. Ajustes para el relé R_6320-TD-005_HV 2
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start
Start Value Value 0,05 0,01 0,05 - 5,00 0.71
Multiplier for Start
scaling the Value
start value Mult 1,00 0,1 0,8 - 10,0 1.00
Time multiplier
Three in IEC/ANSI Time
phase non curves multiplier 1,00 0,01 0,05 - 15,00 1.00
directional Operate delay Operate 40
overcurrent time delay
protection, time 10 40 - 200000 ms 50 ms
low stage Selection of Operating 15=IEC Def. - 9=IEC
(51P-1) 1=ANSI Ext. Inv
time delay curve Time Norm. Inv
PHLPTOC curve type type 2=ANSI Very inv.
Three 3=ANSI Norm. Inv
phase non
directional 4=ANSI Mod. Inv
overcurrent 5=ANSI Def. Time
protection, 6=L.T.E inv
high stage
(51P-2) 7=L.T.V. inv
PHHPTOC 8=L.T. inv
9=IEC Norm. Inv
10=IEC Very inv
11=IEC inv.
12=IEC Ext. Inv
13=IEC S.T. inv.
14=IEC L.T inv
Tabla 153. Ajustes para el relé R_6320-TD-005_HV 1
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start value 0,010 0,005 0,010 - 5,000 0.185
Non Multiplier for
Start value
directional scaling the start
Mult
earth fault value 1,000 0,1 0,8 - 10,0 1.00
protection, Time multiplier in
low stage IEC/ANSI IDMT Time
(51N-1) curves multiplier 1,000 0,01 0,05 - 15,00 1.00
EFLPTOC Operate delay Operate
40
Non time delay time 10 40 - 200000 50 ms
directional Selection of time Operating 15= IEC - 1=ANSI Ext. Inv 9=IEC
earth fault delay curve type curve type Def. Time Norm. Inv
protection, 2=ANSI Very inv.
high stage 3=ANSI Norm. Inv
(51N-2) 4=ANSI Mod. Inv
EFHPTOC
5=ANSI Def. Time
6=L.T.E inv
7=L.T.V. inv
Tabla 156. Ajustes para el relé R_6320-TD-005_HV 1 (Continuación)
SETTING DEFAULT
Non DESCRIPTION NAME VALUE STEP RANGE VALUE
directional
1.00 -
earth fault
Start Value Start Value 1.00 0.01 40.00 0.357
protection,
Multiplier for
instantaneous
scaling the start 0.8 -
stage
value Start value Mult 1.0 0.1 10.0 1.00
(50N/51N)
EFIPTOC Operate delay Operate delay 20 -
time time 20 20 200000 50 ms
Tabla 158. Ajustes para el relé R_6320-TD-005_HV 1 (Continuación)
SETTING DEFAULT
Three phase DESCRIPTION NAME VALUE STEP RANGE VALUE
non
directional Start Value Start Value 0,05 0,01 0,05 - 5,00 OFF
overcurrent Multiplier for
protection, scaling the start Start Value
low stage value Mult 1,00 0,1 0,8 - 10,0 OFF
(51P-1) Time multiplier in Time
PHLPTOC IEC/ANSI curves multiplier 1,00 0,01 0,05 - 15,00 OFF
Three phase Operate delay Operate 40
non time delay time 10 40 - 200000 ms OFF
directional Selection of time Operating 15=IEC Def. - 1=ANSI Ext. Inv OFF
overcurrent delay curve type curve type Time
2=ANSI Very inv.
protection,
high stage 3=ANSI Norm. Inv
(51P-2) 4=ANSI Mod. Inv
PHHPTOC
5=ANSI Def. Time
Tabla 159. Ajustes para el relé R_6320-TD-001_NEUTRO
6=L.T.E inv
7=L.T.V. inv
8=L.T. inv
9=IEC Norm.
Inv
10=IEC Very
inv
11=IEC inv.
12=IEC Ext.
Inv
13=IEC S.T.
inv.
14=IEC L.T
inv
15=IEC Def.
Time
17=Program
mable
18=RI type
Tabla 168. Ajustes para el relé R_6320-TD-002_NEUTRO (Continuación)
6=L.T.E inv
7=L.T.V. inv
8=L.T. inv
9=IEC Norm.
Inv
10=IEC Very
inv
11=IEC inv.
Tabla 171. Ajustes para el relé R_6320-TD-003_NEUTRO (Continuación)
13=IEC S.T.
inv.
14=IEC L.T
inv
15=IEC Def.
Time
17=Program
mable
18=RI type
Tabla 172. Ajustes para el relé R_6320-TD-003_NEUTRO (Continuación)
Non DEFAULT
directional SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
earth fault 1.00 -
protection, Start Value Start Value 1.00 0.01 40.00 0.471
instantaneous Multiplier for scaling the Start value 0.8 -
stage start value Mult 1.0 0.1 10.0 1.00
(50N/51N) Operate delay 20 -
EFIPTOC Operate delay time time 20 20 200000 50 ms
Tabla 173. Ajustes para el relé R_6320-TD-003_NEUTRO (Continuación)
SETTING
DESCRIPTI DEFAULT
ON NAME VALUE STEP RANGE VALUE
Start Value Start value 0,010 0,005 0,010 - 5,000 0.069
Multiplier for
Start value
scaling the
Mult
start value 1,000 0,1 0,8 - 10,0 1.00
Time
multiplier in
IEC/ANSI
IDMT
curves Time multiplier 1,000 0,01 0,05 - 15,00 1.00
Non directional Operate Operate delay
earth fault 40
delay time time 10 40 - 200000 50 ms
protection, low
Selection of Operating 15= IEC - 1=ANSI Ext. 9=IEC
stage (51N-1)
time delay curve type Def. Time Inv Norm. Inv
EFLPTOC
curve type 2=ANSI Very
Non directional
inv.
earth fault
3=ANSI
protection, high
Norm. Inv
stage (51N-2)
EFHPTOC 4=ANSI Mod.
Inv
5=ANSI Def.
Time
6=L.T.E inv
7=L.T.V. inv
8=L.T. inv
9=IEC Norm.
Inv
10=IEC Very
inv
11=IEC inv.
Tabla 176. Ajustes para el relé R_6320-TD-004_NEUTRO (Continuación)
Non DEFAULT
directional SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
earth fault 1.00 -
protection, Start Value Start Value 1.00 0.01 40.00 0.471
instantaneous Multiplier for scaling the start Start value 0.8 -
stage value Mult 1.0 0.1 10.0 1.00
(50N/51N) Operate delay 20 -
EFIPTOC Operate delay time time 20 20 200000 50 ms
Tabla 178. Ajustes para el relé R_6320-TD-004_NEUTRO (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start
Start Value Value 0,05 0,01 0,05 - 5,00 OFF
Three phase Start
non directional Multiplier for scaling Value
overcurrent the start value Mult 1,00 0,1 0,8 - 10,0 OFF
protection,
Time multiplier in Time
low stage
IEC/ANSI curves multiplier 1,00 0,01 0,05 - 15,00 OFF
(51P-1)
Operate delay time Operate 40
PHLPTOC
delay
Three phase
time 10 40 - 200000 ms OFF
non directional
Selection of time Operating 15=IEC Def. - OFF
overcurrent 1=ANSI Ext. Inv
delay curve type curve Time
protection,
type
high stage 2=ANSI Very inv.
(51P-2)
PHHPTOC 3=ANSI Norm. Inv
7=L.T.V. inv
8=L.T. inv
11=IEC inv.
17=Programmable
18=RI type
19=RD type
Selection of reset Type of 1=immediate - OFF
curve type reset 1=immediate
curve
2=Def time reset
3=Inverse reset
Tabla 180. Ajustes para el relé R_6320-TD-005_NEUTRO (Continuación)
Three DEFAULT
phase non SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
directional 1.0 -
overcurrent Start Value Start Value 1.00 0,01 40.00 OFF
protection, Multiplier for scaling the Start Value 0,8 -
instantane start value Mult 1.00 0.1 10,0 OFF
ous stage
(50P/51P) Operate delay 20 -
PHIPTOC Operate delay time time 20 10 200000 OFF
Tabla 181. Ajustes para el relé R_6320-TD-005_NEUTRO (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
IEC inv.
RD type
Operate delay 0,04 -
Operate delay time time 0,04 0,01 200,00 690 ms
Tabla 185. Ajustes para el relé R A17 REF 630 (CB-9) (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
L.T. inv
Programmable
RI type
RD type
Operate delay
Operate delay time time 0,04 0,01 0,04 - 200,00
Tabla 188. Ajustes para el relé R A17 REF 630 (CB-9) (Continuación)
Non DEFAULT
directional SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
earth fault 0.10 -
protection, Start Value Start Value 0.10 0.01 40.00 2.58
instantaneous Multiplier for scaling the Start value
stage start value Mult 1.0 0.1 0.8 - 10.0 1
(50N/51N) Operate delay 0.02 -
EFIPTOC Operate delay time time 0.02 0.02 200.00 300 ms
Tabla 189. Ajustes para el relé R A17 REF 630 (CB-9) (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Phase CT Phase CT
GENERAL Ratio Ratio 1,0 0,1 [1,0:6000,0] 100
SETTING
Ground CT Ground CT
Ratio Ratio 1,0 0,1 [1,0:6000,0] 1
Sensitive
Ground CT Stv Ground
Ratio CT Ratio 1,0 0,1 [1,0:6000,0] 1
Phase VT Phase VT
Ratio Ratio 1,0 0,1 [1,0:6000,0] 1
Tabla 190. Ajustes para el relé R_6220-TL-006B_HV
Nominal
Rated Voltage Voltage 100 0,1 [1,0:250,0] 10
Rated Nominal
Frequency Frequency 50 Hz N/A [50-60] 60
Phase Pahse
Rotation Rotation ABC N/A [ABC-ACB] ABC
Frequency Frequency
Reference Reference VI N/A [VI-VII-VIII] VI
Auxiliary Auxiliary
Voltage Voltage VX N/A [VX-VN] VX
Snapshot
Event Snapshot [DISABLED-
Generation Event DISABLED N/A ENABLED] DISABLED
Device
Device Name Name N/A
Tabla 191. Ajustes para el relé R_6220-TL-006B_HV (Continuación)
SETTING
DESCRIPTIO DEFAULT
N NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase TOC high > phase TOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] ENABLED
PHASOR PHASOR
Input Type Input (DFT) N/A [PHASOR-RMS] (DFT)
PHASE TOC Pickup
HIGH (51PH) Pickup Level Level 1.00 0.01A [0.05:160.00] 0.53
PHASE TOC IEEE Ext
LOW (51PL) Curve Shape Curve Inv N/A [See list of curves] IEC - Curve A
TD
Time Dial Multiplier 1.00 0.01 s [0.00:900.00] 1
INSTANTA [INSTANTANEOUS- INSTANTAN
Reset Type Reset NEOUS N/A LINEAR] EOUS
Voltage Voltage [DISABLED-
Restraint Restraint DISABLED N/A ENABLED] DISABLED
Snapshot
Event Snapshot [DISABLED-
Generation Events ENABLED N/A ENABLED] ENABLED
Tabla 192. Ajustes para el relé R_6220-TL-006B_HV (Continuación)
SETTING
DESCRIPTION NAME DEFAULT VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral TOC
Fucntion [DISABLED-
N/A
permission Function DISABLED ENABLED] ENABLED
Pickup 0,01
NEUTRAL TIME
Pickup Level Level 1.00 A [0.05:160.00] 0.13
DELAYED
OVERCURRENT Curve Shape Curve IEEE Ext Inv N/A [See list of curves] IEC - Curve A
ELEMENT (51N) TD 0,01
Time Dial Multiplier 1.00 s [0.00:900.00] 0.05s
[INSTANTANEOUS
N/A
Reset Type Reset INSTANTANEOUS - LINEAR] INSTANTANEOUS
Snapshot [DISABLED-
Event Snapshot N/A ENABLED]
Generation Events ENABLED ENABLED
Tabla 194. Ajustes para el relé R_6220-TL-006B_HV (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start value 0,010 0,005 0,010 - 5,000 0.126
Non Multiplier for
Start value
directional scaling the start
Mult
earth fault value 1,000 0,1 0,8 - 10,0 1.00
protection, Time multiplier in
low stage IEC/ANSI IDMT Time
(51N-1) curves multiplier 1,000 0,01 0,05 - 15,00 1.00
EFLPTOC Operate delay Operate
40
Non time delay time 10 40 - 200000 50 ms
directional Selection of time Operating 15= IEC - 1=ANSI Ext. Inv 9=IEC
earth fault delay curve type curve type Def. Time Norm. Inv
protection, 2=ANSI Very inv.
high stage 3=ANSI Norm. Inv
(51N-2) 4=ANSI Mod. Inv
EFHPTOC
5=ANSI Def. Time
6=L.T.E inv
7=L.T.V. inv
Tabla 199. Ajustes para el relé R_A18 (Continuación)
Non DEFAULT
directional SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
earth fault 1.00 -
protection, Start Value Start Value 1.00 0.01 40.00 2.56
instantaneous Multiplier for scaling the start Start value 0.8 -
stage value Mult 1.0 0.1 10.0 1.00
(50N/51N) Operate delay 20 -
EFIPTOC Operate delay time time 20 20 200000 100ms
Tabla 201. Ajustes para el relé R_A18 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start Value 0,05 0,01 0,05 - 5,00 0.75
Three phase non
Multiplier for
directional
overcurrent scaling the start
protection, low value Start Value Mult 1,00 0,1 0,8 - 10,0 1
stage (51P-1) Time multiplier
PHLPTOC in IEC/ANSI 0,05 -
Three phase non curves Time multiplier 1,00 0,01 15,00 1
directional Selection of time Operating curve IEC Def. - ANSI Ext. IEC Very
overcurrent delay curve type type Time Inv inv
protection, high ANSI Very
stage (51P-2) inv.
PHHPTOC ANSI Norm.
Inv
ANSI Mod.
Inv
Tabla 202. Ajustes para el relé R A19
Three DEFAULT
phase non SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
directional 0,10 -
overcurren Start Value Start Value 0,1 0,01 40,00 10.42
t Multiplier for scaling the Start Value 0,8 -
protection, start value Mult 1 1 10,0 1
instantane
ous stage
(50P/51P) Operate delay 0,02 -
PHIPTOC Operate delay time time 0,02 0,02 200,00 120 ms
Tabla 204. Ajustes para el relé R A19 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start
Start Value Value 0,05 0,01 0,05 - 5,00 1.8
Start
Multiplier for scaling Value
the start value Mult 1,00 0,1 0,8 - 10,0 1
Time multiplier in Time
IEC/ANSI curves multiplier 1,00 0,01 0,05 - 15,00 1
Selection of time Operating IEC Def. - ANSI Ext. Inv IEC
delay curve type curve type Time Norm.
ANSI Very inv. Inv
Three phase non ANSI Norm.
directional Inv
overcurrent
ANSI Mod. Inv
protection, low
ANSI Def.
stage (51P-1)
Time
PHLPTOC
Three phase non L.T.E inv
directional L.T.V. inv
overcurrent
protection, high L.T. inv
stage (51P-2) IEC Norm. Inv
PHHPTOC IEC Very inv
IEC inv.
IEC Ext. Inv
IEC S.T. inv.
IEC Def. Time
Programmable
RI type
RD type
Operate
Operate delay time delay time 0,04 0,01 0,04 - 200,00 280 ms
Tabla 207. Ajustes para el relé R REF 630 A20
Non DEFAULT
directional SETTING DESCRIPTION NAME VALUE STEP RANGE VALUE
earth fault 0.10 -
protection, Start Value Start Value 0.10 0.01 40.00 OFF
instantaneous Multiplier for scaling the Start value
stage start value Mult 1.0 0.1 0.8 - 10.0 OFF
(50N/51N) Operate delay 0.02 -
EFIPTOC Operate delay time time 0.02 0.02 200.00 OFF
Tabla 211. Ajustes para el relé R REF 630 A20 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > system setup > geenral settings
Phase CT Phase CT
Ratio Ratio 1,0 0,1 [1,0:6000,0] 60
Ground CT Ground CT
Ratio Ratio 1,0 0,1 [1,0:6000,0] 10
Sensitive
Ground CT Stv Ground
Ratio CT Ratio 1,0 0,1 [1,0:6000,0] 1
GENERAL Phase VT Phase VT
SETTING Ratio Ratio 1,0 0,1 [1,0:6000,0] 0.0833
Phase VT Phase VT
Connection Connection WYE N/A [WYE-DELTA] WYE
Nominal
Rated Voltage Voltage 100,0 0,1 [1,0:250,0] 1O kV
Rated Nominal
Frequency Frequency 50 Hz N/A [50-60] 60
Phase Pahse
Rotation Rotation ABC N/A [ABC-ACB] ABC
Frequency Frequency
Reference Reference VI N/A [VI-VII-VIII] VI
Tabla 212. Ajustes para el relé R 1300SG002_P01 F650
SETTING
DESCRIP DEFAULT STE
TION NAME VALUE P RANGE VALUE
setpoint > protection elements > phase current > phase TOC high > phase TOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] ENABLED
PHASOR PHASOR
Input Type Input (DFT) N/A [PHASOR-RMS] (DFT)
PHASE TOC Pickup Pickup 0.01
HIGH (51PH) Level Level 1.00 A [0.05:160.00] 6.04
PHASE TOC Curve
LOW (51PL) Shape Curve IEEE Ext Inv N/A [See list of curves] IEC-Curve A
0.01
Time Dial TD Multiplier 1.00 s [0.00:900.00] 250 ms
Reset INSTANTA [INSTANTANEOUS- INSTANTAN
Type Reset NEOUS N/A LINEAR] EOUS
Voltage Voltage [DISABLED-
Restraint Restraint DISABLED N/A ENABLED] DISABLED
Snapshot
Event Snapshot [DISABLED-
Generation Events ENABLED N/A ENABLED] ENABLED
Tabla 214. Ajustes para el relé R 1300SG002_P01 F650 (Continuación)
SETTING
DESCRIPTION NAME DEFAULT VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral TOC
Fucntion [DISABLED-
N/A
permission Function DISABLED ENABLED] ENABLED
Pickup
NEUTRAL TIME 0,01 A
Pickup Level Level 1.00 [0.05:160.00] 3.15
DELAYED
OVERCURRENT Curve Shape Curve IEEE Ext Inv N/A [See list of curves] IEC-Curve A
ELEMENT (51N) TD
0,01 s
Time Dial Multiplier 1.00 [0.00:900.00] 390 ms
[INSTANTANEOUS
N/A
Reset Type Reset INSTANTANEOUS - LINEAR] INSTANTANEOUS
Snapshot [DISABLED-
Event Snapshot N/A ENABLED]
Generation Events ENABLED ENABLED
Tabla 216. Ajustes para el relé R 1300SG002_P01 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral IOC
[DISABLED- DISABL
NEUTRAL N/A
INSTANTANE Fucntion permission Function DISABLED ENABLED] ED
OUS DISABL
0,0,1A
OVERCURRE Pickup Level Pickup Level 30,00 [0.05:160.00] ED
NT ELEMENT DISABL
0,01 s
(50N) Trip Time Trip Delay 0,00 [0.00:900.00] ED
DISABL
0,01 s
Reset Time Reset Delay 0,00 [0.00:900.00] ED
Snapshot Event Snapshot [DISABLED- DISABL
N/A
Generation Events ENABLED ENABLED] ED
Tabla 222. Ajustes para el relé R 1300SG003_P4 F650 (Continuación)
SETTING
DESCRIP DEFAULT
TION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase TOC high > phase TOC low
PHASE Function Functio [DISABLED-
TOC HIGH Permission n DISABLED N/A ENABLED] ENABLED
(51PH) PHASOR PHASOR
PHASE Input Type Input (DFT) N/A [PHASOR-RMS] (DFT)
TOC LOW Pickup Pickup
(51PL) Level Level 1.00 0.01A [0.05:160.00] 4.94
Curve
Shape Curve IEEE Ext Inv N/A [See list of curves] IEC-Curve A
TD
Multiplie
Time Dial r 1.00 0.01 s [0.00:900.00] 250 ms
Tabla 224. Ajustes para el relé R 1300SG006-01-P01 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
PHASE IOC Permission Function DISABLED N/A ENABLED] DISABLED
HIGH PHASOR
(50PH) Input Type Input (DFT) N/A [PHASOR-RMS] DISABLED
PHASE IOC
LOW Pickup Level Pickup Level 30.0 0.01 A [0.05:160.00] DISABLED
(50PL)
Trip Time Trip Delay 0.00 0.01 s [0.00:900.00] DISABLED
setpoint > protection elements > neutral current > neutral TOC
Fucntion Functio [DISABLED-
N/A
permission n DISABLED ENABLED] ENABLED
NEUTRAL
Pickup
TIME 0,01 A
Pickup Level Level 1.00 [0.05:160.00] 2.57
DELAYED
OVERCURR Curve Shape Curve IEEE Ext Inv N/A [See list of curves] IEC-Curve A
ENT TD
ELEMENT Multipli 0,01 s
(51N) Time Dial er 1.00 [0.00:900.00] 380 ms
INSTANTAN [INSTANTANEOU INSTANTAN
N/A
Reset Type Reset EOUS S - LINEAR] EOUS
Snapsh [DISABLED-
Snapshot Event ot N/A ENABLED]
Generation Events ENABLED ENABLED
Tabla 227. Ajustes para el relé R 1300SG006-01-P01 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral IOC
[DISABLED- DISABL
NEUTRAL N/A
INSTANTAN Fucntion permission Function DISABLED ENABLED] ED
EOUS Pickup DISABL
0,0,1A
OVERCURRE Pickup Level Level 30,00 [0.05:160.00] ED
NT ELEMENT DISABL
0,01 s
(50N) Trip Time Trip Delay 0,00 [0.00:900.00] ED
DISABL
0,01 s
Reset Time Reset Delay 0,00 [0.00:900.00] ED
Snapshot Event Snapshot [DISABLED- DISABL
N/A
Generation Events ENABLED ENABLED] ED
Tabla 228. Ajustes para el relé R 1300SG006-01-P01 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] DISABLED
PHASOR
PHASE IOC Input Type Input (DFT) N/A [PHASOR-RMS] DISABLED
HIGH (50PH)
0.01
PHASE IOC Pickup Level Pickup Level 30.0 A [0.05:160.00] DISABLED
LOW (50PL)
0.01
Trip Time Trip Delay 0.00 s [0.00:900.00] DISABLED
0.01
Reset Time Reset Delay 0.00 s [0.00:900.00] DISABLED
Snapshot Snapshot ENABLED N/A
Event Events [DISABLED-
Generation ENABLED] DISABLED
Tabla 231. Ajustes para el relé R 1300SG006-02-P01 F650 (Continuación)
setpoint > protection elements > neutral current > neutral TOC
Fucntion [DISABLED-
NEUTRAL N/A
permission Function DISABLED ENABLED] ENABLED
TIME
Pickup 0,01
DELAYED
Pickup Level Level 1.00 A [0.05:160.00] 2.57
OVERCUR
RENT Curve Shape Curve IEEE Ext Inv N/A [See list of curves] IEC-Curve A
ELEMENT TD
(51N) 0,01 s
Time Dial Multiplier 1.00 [0.00:900.00] 320 ms
INSTANTAN [INSTANTANEOU INSTANTAN
N/A
Reset Type Reset EOUS S - LINEAR] EOUS
Snapshot Event Snapshot [DISABLED-
N/A
Generation Events ENABLED ENABLED] ENABLED
Tabla 232. Ajustes para el relé R 1300SG006-02-P01 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral IOC
[DISABLED-
N/A
NEUTRAL Fucntion permission Function DISABLED ENABLED] DISABLED
INSTANTANEOUS Pickup
0,0,1A
OVERCURRENT Pickup Level Level 30,00 [0.05:160.00] DISABLED
ELEMENT (50N) Trip Time Trip Delay 0,00 0,01 s [0.00:900.00] DISABLED
Reset
0,01 s
Reset Time Delay 0,00 [0.00:900.00] DISABLED
Snapshot Event Snapshot [DISABLED-
N/A
Generation Events ENABLED ENABLED] DISABLED
Tabla 233. Ajustes para el relé R 1300SG006-02-P01 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral IOC
[DISABLED- DISABL
NEUTRAL N/A
INSTANTAN Fucntion permission Function DISABLED ENABLED] ED
Pickup DISABL
EOUS 0,0,1A
OVERCURRE Pickup Level Level 30,00 [0.05:160.00] ED
NT ELEMENT DISABL
0,01 s
(50N) Trip Time Trip Delay 0,00 [0.00:900.00] ED
DISABL
0,01 s
Reset Time Reset Delay 0,00 [0.00:900.00] ED
Snapshot Event Snapshot [DISABLED- DISABL
N/A
Generation Events ENABLED ENABLED] ED
Tabla 239. Ajustes para el relé R 1300SG006-02-P02 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
PHASE Permission Function DISABLED N/A ENABLED] ENABLED
IOC HIGH PHASOR [PHASOR-
(50PH) Input Type Input (DFT) N/A [PHASOR-RMS] RMS]
PHASE Pickup
IOC LOW Pickup Level Level 30.0 0.01 A [0.05:160.00] 18
(50PL)
Trip Time Trip Delay 0.00 0.01 s [0.00:900.00] 40 ms
Reset Time Reset Delay 0.00 0.01 s [0.00:900.00] DISABLED
Snapshot Event Snapshot ENABLED N/A [DISABLED-
Generation Events ENABLED] DISABLED
Tabla 242. Ajustes para el relé R 1300ER005A-P01_1 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral IOC
NEUTRAL Fucntion [DISABLED- ENABL
N/A
INSTANTANEO permission Function DISABLED ENABLED] ED
US 0,0,1A [0.05:160.00]
Pickup Level Pickup Level 30,00 160
OVERCURRENT
ELEMENT (50N) Trip Time Trip Delay 0,00 0,01 s [0.00:900.00] 50 ms
Reset Time Reset Delay 0,00 0,01 s [0.00:900.00] 0
Snapshot Event Snapshot [DISABLED- ENABL
N/A
Generation Events ENABLED ENABLED] ED
Tabla 244. Ajustes para el relé R 1300ER005A-P01_1 F650 (Continuación)
SETTING
DESCRIPTIO DEFAULT
N NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
PHASE IOC Permission Function DISABLED N/A ENABLED] ENABLED
HIGH PHASOR [PHASOR-
(50PH) Input Type Input (DFT) N/A [PHASOR-RMS] RMS]
PHASE IOC Pickup Level Pickup Level 30.0 0.01 A [0.05:160.00] 12
LOW (50PL)
Trip Time Trip Delay 0.00 0.01 s [0.00:900.00] 40 ms
Reset Time Reset Delay 0.00 0.01 s [0.00:900.00] DISABLED
Snapshot Snapshot ENABLED N/A
Event Events [DISABLED-
Generation ENABLED] DISABLED
Tabla 248. Ajustes para el relé R 1300ER005A-P01_2 P34N (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral IOC
Fucntion [DISABLED-
N/A
NEUTRAL permission Function DISABLED ENABLED] ENABLED
INSTANTANEOUS Pickup
0,0,1A
OVERCURRENT Pickup Level Level 30,00 [0.05:160.00] 30.5
ELEMENT (50N) Trip Time Trip Delay 0,00 0,01 s [0.00:900.00] 50 ms
Reset
0,01 s
Reset Time Delay 0,00 [0.00:900.00] 0
Snapshot Event Snapshot [DISABLED-
N/A
Generation Events ENABLED ENABLED] ENABLED
Tabla 250. Ajustes para el relé R 1300ER005A-P01_2 P34N (Continuación)
SETTING
DESCRIPTIO DEFAULT
N NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
PHASE IOC Permission Function DISABLED N/A ENABLED] ENABLED
HIGH PHASOR [PHASOR- [PHASOR-
(50PH) Input Type Input (DFT) N/A RMS] RMS]
PHASE IOC Pickup Level Pickup Level 30.0 0.01 A [0.05:160.00] 57.15
LOW (50PL)
Trip Time Trip Delay 0.00 0.01 s [0.00:900.00] 100 ms
Reset Time Reset Delay 0.00 0.01 s [0.00:900.00] DISABLED
Snapshot Snapshot ENABLED N/A
Event Events [DISABLED-
Generation ENABLED] DISABLED
Tabla 253. Ajustes para el relé R 1300SE001-01-P01 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral IOC
Fucntion [DISABLED-
N/A
permission Function DISABLED ENABLED] ENABLED
NEUTRAL
Pickup
INSTANTANEOUS 0,0,1A
Pickup Level Level 30,00 [0.05:160.00] 50.5
OVERCURRENT
ELEMENT (50N) Trip Time Trip Delay 0,00 0,01 s [0.00:900.00] 110 ms
Reset
0,01 s
Reset Time Delay 0,00 [0.00:900.00] 0
Snapshot [DISABLED-
Event Snapshot N/A ENABLED]
Generation Events ENABLED ENABLED
Tabla 255. Ajustes para el relé R 1300SE001-01-P01 F650 (Continuación)
SETTING
DESCRIPTI DEFAULT
ON NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase TOC high > phase TOC low
PHASE
Function [DISABLED-
TOC HIGH
Permission Function DISABLED N/A ENABLED] ENABLED
(51PH)
PHASOR PHASOR
PHASE
Input Type Input (DFT) N/A [PHASOR-RMS] (DFT)
TOC LOW
Pickup
(51PL)
Pickup Level Level 1.00 0.01A [0.05:160.00] 2.31
Curve [See list of
Shape Curve IEEE Ext Inv N/A curves] IEC-Curve A
Time Dial TD Multiplier 1.00 0.01 s [0.00:900.00] 160 ms
Tabla 257. Ajustes para el relé R 1300SE001-03-P01 F650 (Continuación)
SETTING
DESCRIPTIO NAM DEFAULT
N E VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function Functi ENABLE
Permission on DISABLED N/A [DISABLED-ENABLED] D
PHASOR [PHASO
PHASE IOC Input Type Input (DFT) N/A [PHASOR-RMS] R-RMS]
HIGH (50PH) Picku
PHASE IOC p
LOW (50PL) Pickup Level Level 30.0 0.01 A [0.05:160.00] 38.1
Trip
Trip Time Delay 0.00 0.01 s [0.00:900.00] 100 ms
Reset DISABL
Reset Time Delay 0.00 0.01 s [0.00:900.00] ED
Snapshot Snaps ENABLED N/A
Event hot
Generation Event DISABL
s [DISABLED-ENABLED] ED
SETTING NAM DEFAULT STEP
DESCRIPTIO E VALUE
N RANGE VALUE
setpoint > protection elements > neutral current > neutral TOC
NEUTRAL Fucntion Functi [DISABLED-ENABLED] ENABLE
N/A
TIME permission on DISABLED D
DELAYED Picku
OVERCURRE p 0,01 A
NT ELEMENT Pickup Level Level 1.00 [0.05:160.00] 1.21
(51N) IEC-
N/A
Curve Shape Curve IEEE Ext Inv [See list of curves] Curve A
TD
Multip 0,01 s
Time Dial lier 1.00 [0.00:900.00] 150 ms
Tabla 259. Ajustes para el relé R 1300SE001-03-P01 F650 (Continuación)
Frequency Frequency
Reference Reference VI N/A [VI-VII-VIII] VI
Auxiliary
Auxiliary Voltage Voltage VX N/A [VX-VN] VX
Snapshot Event Snapshot [DISABLED-
Generation Event DISABLED N/A ENABLED] DISABLED
Primary Meter Primary Meter
Units Units KA_KV N/A [KA_KV;A_V] KA_KV
Device Name Device Name N/A
Tabla 263. Ajustes para el relé R 1300SG007-01-P01 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
PHASE Permission Function DISABLED N/A ENABLED] DISABLED
IOC HIGH PHASOR
(50PH) Input Type Input (DFT) N/A [PHASOR-RMS] DISABLED
PHASE Pickup
IOC LOW Pickup Level Level 30.0 0.01 A [0.05:160.00] DISABLED
(50PL) Trip Time Trip Delay 0.00 0.01 s [0.00:900.00] DISABLED
Reset Time Reset Delay 0.00 0.01 s [0.00:900.00] DISABLED
Snapshot Snapshot ENABLED N/A
Event Events [DISABLED-
Generation ENABLED] DISABLED
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral IOC
Fucntion [DISABLED-
N/A
NEUTRAL permission Function DISABLED ENABLED] DISABLED
Pickup
INSTANTANEOUS 0,0,1A
OVERCURRENT Pickup Level Level 30,00 [0.05:160.00] DISABLED
ELEMENT (50N) Trip
0,01 s
Trip Time Delay 0,00 [0.00:900.00] DISABLED
Reset
0,01 s
Reset Time Delay 0,00 [0.00:900.00] DISABLED
Snapshot Event Snapshot [DISABLED-
N/A
Generation Events ENABLED ENABLED] DISABLED
Tabla 267. Ajustes para el relé R 1300SG007-01-P01 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > system setup > geenral settings
Phase CT Phase CT
GENERAL Ratio Ratio 1,0 0,1 [1,0:6000,0] 40
SETTING Ground CT Ground CT
Ratio Ratio 1,0 0,1 [1,0:6000,0] 10
Sensitive
Ground CT Stv Ground
Ratio CT Ratio 1,0 0,1 [1,0:6000,0] 1
Tabla 268. Ajustes para el relé R 1300SG007-03-P01 F650
SETTING
DESCRIPTIO DEFAULT
N NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase TOC high > phase TOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] ENABLED
PHASOR PHASOR
PHASE Input Type Input (DFT) N/A [PHASOR-RMS] (DFT)
TOC HIGH Pickup
(51PH) Pickup Level Level 1.00 0.01A [0.05:160.00] 2.28
PHASE
TOC LOW Curve Shape Curve IEEE Ext Inv N/A [See list of curves] IEC-Curve A
(51PL) Time Dial TD Multiplier 1.00 0.01 s [0.00:900.00] 230 ms
INSTANTAN [INSTANTANEOU INSTANTAN
Reset Type Reset EOUS N/A S-LINEAR] EOUS
Voltage Voltage [DISABLED-
Restraint Restraint DISABLED N/A ENABLED] DISABLED
Snapshot
Event Snapshot [DISABLED-
Generation Events ENABLED N/A ENABLED] ENABLED
Tabla 270. Ajustes para el relé R 1300SG007-03-P01 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] ENABLED
PHASOR [PHASOR- PHASOR
PHASE IOC Input Type Input (DFT) N/A RMS] (DFT)
HIGH (50PH) Pickup 0.01
PHASE IOC Pickup Level Level 30.0 A [0.05:160.00] 18
LOW (50PL) Trip 0.01
Trip Time Delay 0.00 s [0.00:900.00] 40 ms
Reset 0.01
Reset Time Delay 0.00 s [0.00:900.00] 0.00
Snapshot Snapshot ENABLED N/A
Event Events [DISABLED-
Generation ENABLED] ENABLED
SETTING DEFAULT
NEUTRAL TIME DESCRIPTION NAME VALUE STEP RANGE VALUE
DELAYED
OVERCURRENT setpoint > protection elements > neutral current > neutral TOC
ELEMENT (51N) Fucntion [DISABLED-
N/A
permission Function DISABLED ENABLED] ENABLED
Tabla 277. Ajustes para el relé R 1300ER006A-P01_1 F650 (Continuación)
Pickup 0,01
Pickup Level Level 1.00 A [0.05:160.00] 0.57
Curve Shape Curve IEEE Ext Inv N/A [See list of curves] IEC-Curve A
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral IOC
Fucntion [DISABLED-
N/A
NEUTRAL permission Function DISABLED ENABLED] ENABLED
INSTANTANEOUS Pickup
0,0,1A
OVERCURRENT Pickup Level Level 30,00 [0.05:160.00] 24.95
ELEMENT (50N) Trip Time Trip Delay 0,00 0,01 s [0.00:900.00] 50 ms
Reset
0,01 s
Reset Time Delay 0,00 [0.00:900.00] 0
Snapshot Event Snapshot [DISABLED-
N/A
Generation Events ENABLED ENABLED] ENABLED
Tabla 279. Ajustes para el relé R 1300ER006A-P01_1 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > system setup > geenral settings
Phase CT Ratio Phase CT Ratio 1,0 0,1 [1,0:6000,0] 60
Ground CT
Ground CT Ratio Ratio 1,0 0,1 [1,0:6000,0] 50
GENERAL Sensitive Ground CT Stv Ground CT
SETTING Ratio Ratio 1,0 0,1 [1,0:6000,0] 1
Phase VT Ratio Phase VT Ratio 1,0 0,1 [1,0:6000,0] 0.0833
Phase VT Phase VT
Connection Connection WYE N/A [WYE-DELTA] WYE
Nominal
Rated Voltage Voltage 100,0 0,1 [1,0:250,0] 1O kV
Nominal
Rated Frequency Frequency 50 Hz N/A [50-60] 60
Tabla 280. Ajustes para el relé R 1300ER006A-P01_2 P34N
SETTING
DESCRIPTION NAME DEFAULT VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase TOC high > phase TOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] ENABLED
PHASE Input Type Input PHASOR (DFT) N/A [PHASOR-RMS] PHASOR (DFT)
TOC Pickup
HIGH Pickup Level Level 1.00 0.01A [0.05:160.00] 0.22
(51PH) IEC-Normal
PHASE Curve Shape Curve IEEE Ext Inv N/A [See list of curves] Inverse
TOC TD 0.01
LOW Time Dial Multiplier 1.00 s [0.00:900.00] 50 ms
(51PL) [INSTANTANEOUS-
Reset Type Reset INSTANTANEOUS N/A LINEAR] INSTANTANEOUS
Voltage Voltage [DISABLED-
Restraint Restraint DISABLED N/A ENABLED] DISABLED
Snapshot
Event Snapshot [DISABLED-
Generation Events ENABLED N/A ENABLED] ENABLED
Tabla 282. Ajustes para el relé R 1300ER006A-P01_2 P34N (Continuación)
SETTING
DESCRIPTION NAME DEFAULT VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral TOC
Fucntion [DISABLED-
N/A
permission Function DISABLED ENABLED] ENABLED
Pickup 0,01
NEUTRAL TIME Pickup Level Level 1.00 A [0.05:160.00] 0.114
DELAYED IEC-Normal
OVERCURRENT N/A
Curve Shape Curve IEEE Ext Inv [See list of curves] Inverse
ELEMENT (51N) TD 0,01
Time Dial Multiplier 1.00 s [0.00:900.00] 50 ms
[INSTANTANEOUS
N/A
Reset Type Reset INSTANTANEOUS - LINEAR] INSTANTANEOUS
Snapshot [DISABLED-
Event Snapshot N/A ENABLED]
Generation Events ENABLED ENABLED
Tabla 285. Ajustes para el relé R 1300ER006A-P01_2 P34N (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > system setup > geenral settings
Phase CT
Phase CT Ratio Ratio 1,0 0,1 [1,0:6000,0] 60
Ground CT
Ground CT Ratio Ratio 1,0 0,1 [1,0:6000,0] 10
Sensitive Ground Stv Ground
CT Ratio CT Ratio 1,0 0,1 [1,0:6000,0] 1
Phase VT
Phase VT Ratio Ratio 1,0 0,1 [1,0:6000,0] 0.0833
Phase VT Phase VT
Connection Connection WYE N/A [WYE-DELTA] WYE
GENERAL Nominal
SETTING Rated Voltage Voltage 100,0 0,1 [1,0:250,0] 1O kV
Nominal
Rated Frequency Frequency 50 Hz N/A [50-60] 60
Pahse
Phase Rotation Rotation ABC N/A [ABC-ACB] ABC
Frequency Frequency
Reference Reference VI N/A [VI-VII-VIII] VI
Auxiliary
Auxiliary Voltage Voltage VX N/A [VX-VN] VX
Snapshot Event Snapshot [DISABLED-
Generation Event DISABLED N/A ENABLED] DISABLED
Primary Meter Primary Meter
Units Units KA_KV N/A [KA_KV;A_V] KA_KV
Device Name Device Name N/A
Tabla 287. Ajustes para el relé R 1460-SG-001 F650
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
PHASE Permission Function DISABLED N/A ENABLED] DISABLED
IOC HIGH
Input Type Input PHASOR (DFT) N/A [PHASOR-RMS] DISABLED
(50PH)
Pickup 0.01
PHASE
Pickup Level Level 30.0 A [0.05:160.00] DISABLED
IOC LOW
(50PL) Trip Time Trip Delay 0.00 0.01 s [0.00:900.00] DISABLED
Reset
Reset Time Delay 0.00 0.01 s [0.00:900.00] DISABLED
Snapshot Event Snapshot ENABLED N/A [DISABLED-
Generation Events ENABLED] DISABLED
Tabla 295. Ajustes para el relé R 1300SG007-01-P02 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] DISABLED
PHASOR [PHASOR-
PHASE IOC Input Type Input (DFT) N/A RMS] DISABLED
HIGH (50PH) Pickup 0.01
PHASE IOC Pickup Level Level 30.0 A [0.05:160.00] DISABLED
LOW (50PL) Trip 0.01
Trip Time Delay 0.00 s [0.00:900.00] DISABLED
Reset 0.01
Reset Time Delay 0.00 s [0.00:900.00] DISABLED
Snapshot Snapshot ENABLED N/A
Event Events [DISABLED-
Generation ENABLED] DISABLED
Tabla 300. Ajustes para el relé R 1300SG007-03-P02 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > system setup > geenral settings
Phase CT Phase CT
Ratio Ratio 1,0 0,1 [1,0:6000,0] 60
Ground CT Ground CT
Ratio Ratio 1,0 0,1 [1,0:6000,0] 50
Sensitive
Ground CT Stv Ground
Ratio CT Ratio 1,0 0,1 [1,0:6000,0] 1
GENERAL Phase VT Phase VT
SETTING Ratio Ratio 1,0 0,1 [1,0:6000,0] 0.0833
Phase VT Phase VT
ConnectionConnection WYE N/A [WYE-DELTA] WYE
Nominal
Rated Voltage Voltage 100,0 0,1 [1,0:250,0] 1O kV
Rated Nominal
Frequency Frequency 50 Hz N/A [50-60] 60
Phase Pahse
Rotation Rotation ABC N/A [ABC-ACB] ABC
Frequency Frequency
Reference Reference VI N/A [VI-VII-VIII] VI
Tabla 306. Ajustes para el relé R 1300ER006B-P02 P34N (Continuación)
SETTING
DESCRIPTION NAME DEFAULT VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase TOC high > phase TOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] ENABLED
PHASE Input Type Input PHASOR (DFT) N/A [PHASOR-RMS] PHASOR (DFT)
TOC Pickup
HIGH Pickup Level Level 1.00 0.01A [0.05:160.00] 0.81
(51PH)
Curve Shape Curve IEEE Ext Inv N/A [See list of curves] IEC-Curve A
PHASE
TD 0.01
TOC
Time Dial Multiplier 1.00 s [0.00:900.00] 150ms
LOW
(51PL) [INSTANTANEOUS-
Reset Type Reset INSTANTANEOUS N/A LINEAR] INSTANTANEOUS
Voltage Voltage [DISABLED-
Restraint Restraint DISABLED N/A ENABLED] DISABLED
Snapshot
Event Snapshot [DISABLED-
Generation Events ENABLED N/A ENABLED] ENABLED
Tabla 308. Ajustes para el relé R 1300ER006B-P02 P34N (Continuación)
PHASE SETTING
TOC DESCRIPTION NAME DEFAULT VALUE STEP RANGE VALUE
HIGH setpoint > protection elements > phase current > phase TOC high > phase TOC low
IPS510203121-1-0000-207-CAL-002 Revisión:0 Fecha: 01/10/2015
COORDINACION DE PROTECCIONES DE SOBRECORRIENTE
Página 211
(51PH) Function [DISABLED-
PHASE Permission Function DISABLED N/A ENABLED] ENABLED
TOC Input Type Input PHASOR (DFT) N/A [PHASOR-RMS] PHASOR (DFT)
LOW Pickup
(51PL) Pickup Level Level 1.00 0.01A [0.05:160.00] 1.65
Curve Shape Curve IEEE Ext Inv N/A [See list of curves] IEC-Curve A
TD 0.01
Time Dial Multiplier 1.00 s [0.00:900.00] 50ms
[INSTANTANEOUS-
Reset Type Reset INSTANTANEOUS N/A LINEAR] INSTANTANEOUS
Voltage Voltage [DISABLED-
Restraint Restraint DISABLED N/A ENABLED] DISABLED
Snapshot
Event Snapshot [DISABLED-
Generation Events ENABLED N/A ENABLED] ENABLED
Tabla 312. Ajustes para el relé R 1300ER005B-P01_1 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] ENABLED
PHASE IOC PHASOR [PHASOR- PHASOR
HIGH (50PH) Input Type Input (DFT) N/A RMS] (DFT)
PHASE IOC Pickup
LOW (50PL) Pickup Level Level 30.0 0.01 A [0.05:160.00] 18
Trip
Trip Time Delay 0.00 0.01 s [0.00:900.00] 40 ms
Reset
Reset Time Delay 0.00 0.01 s [0.00:900.00] 0.00
Snapshot Event Snapshot ENABLED N/A [DISABLED-
Generation Events ENABLED] ENABLED
Tabla 313. Ajustes para el relé R 1300ER005B-P01_1 F650 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral IOC
Fucntion [DISABLED-
N/A
NEUTRAL permission Function DISABLED ENABLED] ENABLED
INSTANTANEOUS Pickup
0,0,1A
OVERCURRENT Pickup Level Level 30,00 [0.05:160.00] 20
ELEMENT (50N) Trip Time Trip Delay 0,00 0,01 s [0.00:900.00] 50 ms
Reset
0,01 s
Reset Time Delay 0,00 [0.00:900.00] 0
Snapshot Event Snapshot [DISABLED-
N/A
Generation Events ENABLED ENABLED] ENABLED
Tabla 315. Ajustes para el relé R 1300ER005B-P01_1 F650 (Continuación)
SETTING
DESCRIPTION NAME DEFAULT VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] ENABLED
PHASE IOC Input Type Input PHASOR (DFT) N/A [PHASOR-RMS] PHASOR (DFT)
HIGH (50PH) Pickup 0.01
PHASE IOC Pickup Level Level 30.0 A [0.05:160.00] 2.4
LOW (50PL) Trip 0.01
Trip Time Delay 0.00 s [0.00:900.00] 40 ms
Reset 0.01
Reset Time Delay 0.00 s [0.00:900.00] 0.00
Snapshot Snapshot ENABLED N/A
Event Events [DISABLED-
Generation ENABLED] ENABLED
SETTING
DESCRIPTION NAME DEFAULT VALUE STEP RANGE VALUE
setpoint > protection elements > neutral current > neutral TOC
Fucntion [DISABLED-
N/A
permission Function DISABLED ENABLED] ENABLED
Pickup 0,01
NEUTRAL TIME Pickup Level Level 1.00 A [0.05:160.00] 11.48
DELAYED IEC-Normal
OVERCURRENT N/A
Curve Shape Curve IEEE Ext Inv [See list of curves] Inverse
ELEMENT (51N) TD 0,01
Time Dial Multiplier 1.00 s [0.00:900.00] 50 ms
[INSTANTANEOUS
N/A
Reset Type Reset INSTANTANEOUS - LINEAR] INSTANTANEOUS
Snapshot [DISABLED-
Event Snapshot N/A ENABLED]
Generation Events ENABLED ENABLED
Tabla 318. Ajustes para el relé R 1300ER005B-P01_2 P34N (Continuación)
SETTING
DESCRIPTI DEFAULT STE
ON NAME VALUE P RANGE VALUE
Start Value Start Value 0,05 0,01 0,05 - 5,00 0.71
Multiplier for
scaling the Start Value
start value Mult 1,00 0,1 0,8 - 10,0 1
Time
Three phase non multiplier in
directional IEC/ANSI 0,05 -
overcurrent curves Time multiplier 1,00 0,01 15,00 1
protection, low Operate Operate delay 40 40 -
stage (51P-1) delay time time 10 200000 ms 50 ms
PHLPTOC Selection of Operating 15=IEC Def. - 1=ANSI 9=IEC
Three phase non time delay curve type Time Ext. Inv Norm. Inv
directional curve type 2=ANSI
overcurrent Very inv.
protection, high 3=ANSI
stage (51P-2) Norm. Inv
PHHPTOC 4=ANSI
Mod. Inv
5=ANSI
Def. Time
6=L.T.E inv
7=L.T.V.
inv
8=L.T. inv
Tabla 320. Ajustes para el relé R_6320-TD-001_HV 2
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
Start Value Start value 0,010 0,005 0,010 - 5,000 0.185
Multiplier for
Start value
scaling the start
Mult
value 1,000 0,1 0,8 - 10,0 1.00
Time multiplier in
IEC/ANSI IDMT
curves Time multiplier 1,000 0,01 0,05 - 15,00 1.00
Operate delay Operate delay
Non 40
time time 10 40 - 200000 50 ms
directional Selection of time Operating 15= IEC - 9=IEC
earth fault delay curve type 1=ANSI Ext. Inv
curve type Def. Time Norm. Inv
protection, 2=ANSI Very inv.
low stage 3=ANSI Norm. Inv
(51N-1)
EFLPTOC 4=ANSI Mod. Inv
Non 5=ANSI Def. Time
directional 6=L.T.E inv
earth fault
protection, 7=L.T.V. inv
high stage 8=L.T. inv
(51N-2) 9=IEC Norm. Inv
EFHPTOC
10=IEC Very inv
11=IEC inv.
12=IEC Ext. Inv
13=IEC S.T. inv.
14=IEC L.T inv
15=IEC Def. Time
17=Programmable
18=RI type
Tabla 326. Ajustes para el relé R_6320-TD-001_HV 1 (Continuación)
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
0,05 -
Start Value Start Value 0,05 0,01 5,00 0.79
Multiplier for
scaling the start Start Value
value Mult 1,00 0,1 0,8 - 10,0 1
Time multiplier in 0,05 -
IEC/ANSI curves Time multiplier 1,00 0,01 15,00 1
Operate delay time Operate delay 40 40 -
time 200000
Three phase 10 ms 50 ms
non directional Selection of time Operating 15=IEC Def. - 1=ANSI 9=IEC
overcurrent delay curve type curve type Time Ext. Inv Norm. Inv
protection, 2=ANSI
low stage Very inv.
(51P-1) 3=ANSI
PHLPTOC Norm. Inv
Three phase 4=ANSI
non directional Mod. Inv
overcurrent 5=ANSI
protection, Def. Time
high stage
6=L.T.E
(51P-2)
inv
PHHPTOC
7=L.T.V.
inv
8=L.T. inv
9=IEC
Norm. Inv
10=IEC
Very inv
11=IEC
inv.
12=IEC
Ext. Inv
Tabla 328. Ajustes para el relé R REF 620 A21
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > system setup > geenral settings
Phase CT Phase CT
Ratio Ratio 1,0 0,1 [1,0:6000,0] 60
Ground CT Ground CT
Ratio Ratio 1,0 0,1 [1,0:6000,0] 50
Sensitive
Ground CT
Stv Ground
Ratio CT Ratio 1,0 0,1 [1,0:6000,0] 1
Phase VT Phase VT
Ratio Ratio 1,0 0,1 [1,0:6000,0] 0.0833
GENERAL Phase VT Phase VT
SETTING Connection
Connection WYE N/A [WYE-DELTA] WYE
Nominal
Rated Voltage Voltage 100,0 0,1 [1,0:250,0] 1O kV
Rated Nominal
Frequency Frequency 50 Hz N/A [50-60] 60
Phase Pahse
Rotation Rotation ABC N/A [ABC-ACB] ABC
Frequency Frequency
Reference Reference VI N/A [VI-VII-VIII] VI
Auxiliary Auxiliary
Voltage Voltage VX N/A [VX-VN] VX
Snapshot
Event Snapshot [DISABLED-
Generation Event DISABLED N/A ENABLED] DISABLED
Tabla 335. Ajustes para el relé R 1300SG003_P01 F650
SETTING DEFAULT
DESCRIPTION NAME VALUE STEP RANGE VALUE
setpoint > protection elements > phase current > phase IOC high > phase IOC low
Function [DISABLED-
Permission Function DISABLED N/A ENABLED] DISABLED
PHASE PHASOR
IOC HIGH Input Type Input (DFT) N/A [PHASOR-RMS] DISABLED
(50PH) 0.01
PHASE Pickup Level Pickup Level 30.0 A [0.05:160.00] DISABLED
IOC LOW 0.01
(50PL) Trip Time Trip Delay 0.00 s [0.00:900.00] DISABLED
0.01
Reset Time Reset Delay 0.00 s [0.00:900.00] DISABLED
Snapshot Snapshot ENABLED N/A
Event Events [DISABLED-
Generation ENABLED] DISABLED
Tabla 337. Ajustes para el relé R 1300SG003_P01 F650 (Continuación)
Con base en los ajustes propuesto en el numeral 6, se hace necesario la revisión de los ajustes
de los transformadores T1 y T2 de la subestación Quellopata cada uno con niveles de tensión
de 66/10 kV. Esto se debe a que para poder garantizar la operación coodinada de todos los
elementos de protección del circuito se hace necesario un reajuste de los tiempos de operación
de las protecciones de dichos transformadores.
Por lo tanto se presentan a continuación los ajustes en valores primarios, con el fin de que se
puedan implementar para cualquier tipo de relé y relación de CT’s y PT’s en dichas
subestaciones.
PARÁMETRO AJUSTE
51 - Arranque (Aprim) 210
51 - Dial de tiempo [s] 0.32
51 - Curva IEC IEC Normal Inverse
Tabla 343. Transformador T1 Quellopata 66kV (ajustes en valores primarios)
PARÁMETRO AJUSTE
51 - Arranque (Aprim) 210
51 - Dial de tiempo [s] 0.32
51 - Curva IEC IEC Normal Inverse
Tabla 345. Transformador T2 Quellopata 66kV (ajustes en valores primarios)
PARÁMETRO AJUSTE
51 - Arranque (Aprim) 1360
51 - Dial de tiempo [s] 0.32
Curva IEC IEC Normal Inverse
51N - Arranque (Aprim) 240
51N - Dial de tiempo [s] 0.5
51N - Curva IEC IEC Normal Inverse
Se pretende estableces para cada una de las celdas del sistema el valor máximo de impedancia de falla
para el cual el ajuste de protecciones eléctricas lograra operar y despejar de manera coordinada la falla
hasta las protecciones ubicadas en los transformadores T1 y T2 de Quellopata.
Se realizaron fallas en diferentes puntos del circuito y con diferentes valores de impedancia de falla. De
dicho análisis se encontraron dos valores máximos para las celdas en exterior e interior mina
respectivamente. Adicionalmente se presentan los casos en los cuales no fue posible obtener la
coordinación en todos los elementos de protección.
Los ajustes recomendados con base en los criterios establecidos, funcionan de manera
correcta para cada uno de los escenarios de operación, en cuanto a coordinación,
selectividad, rapidez y estabilidad.
Las fallas a tierra con impedancia dentro del sistemas son detectables hasta valores
de 1.25 [Ohm] para las celdas en el exterior de la mina y de 1 [Ohm] para el inerior de
la mina. Hasta dichos valores se logra que todos los elementos de protección
implicados hasta los transformadores T1 y T2 de la subestación Quellopata operen de
forma coordinada. Debe tenerse en cuenta la presencia de una impedancia de puesta
en dichos transformadores la cual ya limita las corrientes de falla, por lo que una falla
con impedacia en diferentes puntos del sistema no son perceptibles por todas las
protecciones para magnitudes superiores a las mencionadas.
100 100
50 50
30 30
R_6220-TL-001A_LV - P - 51
OC1
R_6220-TL-001A_HV 1 - P - 51
10 OC1 10
R_6220-TL-001A_HV 2 - P - 51
5 OC1 5
Seconds
Seconds
3 3
1 6220-TL-001A. 1
.5 .5
.3 R_6220-TL-001A_HV 1 .3
R
R_6220-TL-001A_HV 2
R_6220-TL-001A_HV 2 - P - 50
.1 6220-TL-001A. OC1 .1
6220-TL-001A.
Inrush R_6220-TL-001A_HV 1 - P - 50
10 MVA
.05 OC1 .05
±
R_6220-TL-001A_LV - P - 50
.03 .03
OC1
500 500
300 300
R_6220-TL-001A_HV 2 - P - 51
100 100
OC1
R_6220-TL-001A_HV 1 - P - 51
50 50
OC1
30 R_6220-TL-001A_LV - P - 51 30
OC1
10 R T1 QUELLOPATA 10KV LV - P - 51 10
OC1
5 R T2 QUELLOPATA 10KV - P - 51 5
Seconds
Seconds
OC1
3 3
1 1
.5 .5
.3 .3
.1 R_6220-TL-001A_HV 1 - P - 50 .1
OC1
.05 R
R T2 QUELLOPATA 10KV
R T1R QUELLOPATA 10KV LV R_6220-TL-001A_LV - P - 50 .05
R_6220-TL-001A_HV 1
R
OC1
.03 R
.03
R_6220-TL-001A_HV 2
R_6220-TL-001A_HV 2 - P - 50
OC1
.01 R
R_6220-TL-001A_LV .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-2. Coordinación de curvas de sobrecorriente de Fase (50 - 51) celda A-01.
Amps X 100 Bus32-1 (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
100 100
50 50
30 30
10 10
5 5
Seconds
Seconds
R_6220-TL-001B_HV - P - 51
3
OC1 3
1 6220-TL-001B 1
.5 .5
.3 .3
R_6220-TL-001B_HV
.1 .1
6220-TL-001B
Inrush
.05 .05
.03 .03
6220-TL-001B R_6220-TL-001B_HV - P - 50
2.5 MVA
OC1
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
100 100
50 50
30 30
10 10
R_6220-TL-003_HV - P - 51
5 5
Seconds
Seconds
OC1
3 3
1 6220-TL-003 1
.5 .5
.3 .3
R_6220-TL-003_HV
.1 .1
6220-TL-003
Inrush
.05 .05
.03 .03
R_6220-TL-003_HV - P - 50
6220-TL-003
2 MVA OC1
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-4. Curvas curvas de sobrecorriente de Fase (50 - 51) Transformador 6220-TL-003
Amps X 100 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
R T1 QUELLOPATA 10KV LV - P - 51
OC1
10 10
R T2 QUELLOPATA 10KV - P - 51
5 OC1 5
Seconds
Seconds
3 3
1 1
R_6220-TL-001B_HV - P - 51
.5 OC1 .5
.3 .3
.1 .1
.05 .05
.03 .03
R_6220-TL-001B_HV - P - 50
R
R
R T2 QUELLOPATA 10KV
R T1 QUELLOPATA 10KV LV OC1
.01 R
R_6220-TL-001B_HV .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-5. Coordinación de curvas de sobrecorriente de Fase (50 - 51) celdas A03, A-04, A-06.
Amps X 100 (Plot Ref. kV=4.16)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 R_Molino SAG - P - 51 30
OC1
R_Bolas Motor 1 - P - 51
OC1
10 10
R_Bolas Motor 2 - P - 51
OC1
5 5
Seconds
Seconds
3 R_6220-TL-001A_LV - P - 51 3
OC1
1 1
.5 .5
.3 .3
R_6220-TL-001A_LV - P - 50
.1 .1
OC1
.05 .05
Figura A-6. Coordinación de curvas de sobrecorriente de Fase (50 - 51) Bolas Motor 1,
Bolas Motor 2, Molino SAG.
Amps X 100 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
R T1 QUELLOPATA 10KV LV - P - 51
OC1
R T2 QUELLOPATA 10KV - P - 51
10 10
OC1
5 5
Seconds
Seconds
3 3
1 1
R_6220-TL-003_HV - P - 51
.5 OC1 .5
.3 .3
.1 .1
.05 .05
.03 .03
R_6220-TL-003_HV - P - 50
OC1
R R T1R QUELLOPATA
R T2 QUELLOPATA
10KV LV 10KV
.01 R
R_6220-TL-003_HV .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-7. Coordinación de curvas de sobrecorriente de Fase (50 - 51) celda A-05.
Amps X 10 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
6212-SW-007
100 100
50 50
30 R T1 QUELLOPATA 10KV LV - P - 51 30
OC1
R T2 QUELLOPATA 10KV - P - 51
10 OC1 10
5 5
Seconds
Seconds
3 3
1 1
R A07 - P - 51
.5 .5
OC1
.3 .3
.1 .1
R R A07
.03 .03
.01 6212-SW-007
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-8. Coordinación de curvas de sobrecorriente de Fase (50 - 51) celda A-07.
Amps X 10 Bus125 (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
100 100
50 50
30 30
R_6220-TL-005_HV - P - 51
OC1
10 10
5 5
Seconds
Seconds
3 3
1 6220-TL-005 1
.5 .5
.3 .3
R
R_6220-TL-005_HV
.1 6220-TL-005 .1
Inrush
.05 .05
R_6220-TL-005_HV - P - 50
.03 OC1 .03
6220-TL-005
1000 kVA
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
100 100
R_6220-TL-005_HV - P - 51
50 OC1 50
30 R T1 QUELLOPATA 10KV LV - P - 51 30
OC1
R T2 QUELLOPATA 10KV - P - 51
10 10
OC1
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
.1 .1
R
R T2 QUELLOPATA 10KV
R R T1 QUELLOPATA 10KV LV
.01 R
R_6220-TL-005_HV
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-10. Coordinación de curvas de sobrecorriente de Fase (50 - 51) celda A-08.
Amps X 10 Bus131 (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
100 100
50 50
30 30
10 10
5 R_6320-TD-001_HV 1 - P - 51 5
Seconds
Seconds
OC1
3 3
R_6320-TD-001_HV 2 - P - 51
OC1
1 6320-TD-001 1
.5 .5
.3 .3
R
R_6320-TD-001_HV 1
R
R_6320-TD-001_HV 2
.1 .1
6320-TD-001
Inrush
.05 .05
.03
6320-TD-001
R_6320-TD-001_HV 1 - P - 50 .03
1600 kVA OC1
±
R_6320-TD-001_NEUTRO
R_6320-TD-001_HV 2 - P - 50
OC1
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
100 100
50 6320-TD-001 50
30 30
R T1 QUELLOPATA 10KV LV - P - 51
OC1
R T2 QUELLOPATA 10KV - P - 51
10 10
OC1
5 5
Seconds
Seconds
3 3
1 R_6320-TD-001_HV 2 - P - 51 1
OC1
.5 R_6320-TD-001_HV 1 - P - 51 .5
OC1
.3 .3
.1 .1
.05 .05
OC1
R R T1 QUELLOPATA 10KV LV R
R T2 QUELLOPATA 10KV
R_6320-TD-001_HV 1 - P - 50
R
R_6320-TD-001_HV 1 OC1
.01 R
R_6320-TD-001_HV 2
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
100 100
100E
R T2 QUELLOPATA 10KV - P - 51
OC1
10 R T1 QUELLOPATA 10KV LV - P - 51 10
OC1
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
.05 .05
.03 .03
R R T1 QUELLOPATA
R
R T210KV
QUELLOPATA
LV 10KV
Figura A-13. Coordinación de curvas de sobrecorriente de Fase (50 - 51) celda A-17.
Amps X 100 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
R_6220-TL-006B_HV - P - 51
100 100
OC1
R A17 REF 630 (CB-9) - P - 51
50 OC1 50
30 30
R T2 QUELLOPATA 10KV - P - 51
OC1
10
R T1 QUELLOPATA 10KV LV - P - 51 10
OC1
5 5
3 3
Seconds
Seconds
1 1
.5 .5
.3 .3
.05 .05
R_6220-TL-006B_HV - P - 50
.03 .03
OC1
.01 .01
R T2
R T1 QUELLOPATA QUELLOPATA
10KV LV 10KV
R R
.005 .005
R R A17 REF 630 (CB-9)
.003 .003
R_6220-TL-006B_HV
R
.001 .001
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-14. Coordinación de curvas de sobrecorriente de Fase (50 - 51) celda A-17.
Amps X 100 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
R T2 QUELLOPATA 10KV - P - 51
OC1
10 R T1 QUELLOPATA 10KV LV - P - 51 10
OC1
5 R A18 - P - 51 5
Seconds
Seconds
OC1
3 3
1 1
.5 .5
.3 .3
.1 .1
R A18 - P - 50
OC1
.05 .05
.03 .03
R T2 QUELLOPATA 10KV
R T1 QUELLOPATA 10KV LV R
R
.01 R R A18
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-15. Coordinación de curvas de sobrecorriente de Fase (50 - 51) celda A-18.
Amps X 100 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
40A..
50 50
30 30
R T1 QUELLOPATA 10KV LV - P - 51
R A19 - P - 51 OC1
10 OC1 R T2 QUELLOPATA 10KV - P - 51 10
OC1
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
.1 .1
R A19 - P - 50
R T2 QUELLOPATA 10KV
OC1
R
R T1 QUELLOPATA 10KV LV
.05 .05
R
.03 .03
R R A19
.01 40A..
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-16. Coordinación de curvas de sobrecorriente de Fase (50 - 51) celda A-19.
Amps X 100 B 1460-SG-001 (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
50 50
30 30
R 1300SE001-03-P01 F650 - P - 51
OC1
10 10
R 1300SE001-01-P01 F650 - P - 51
OC1
5 5
Seconds
Seconds
3 3
1 1
.5 .5
R R 1300SE001-01-P01 F650
.3 .3
.1 .1
R 1300SE001-03-P01 F650 - P - 50
.05 OC1 .05
R 1300SE001-01-P01 F650 - P - 50
.03 OC1 .03
R R 1300SE001-03-P01 F650
.01 F 1460-XFD-001P
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-17. Curvas de sobrecorriente de Fase (50 - 51) Interior Mina: Transformadores T
1460-TL-001, T 1460-TL-002.
Amps X 10 B 1460-SG-001 (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100
R AGUA POTABLE_1 F650 - P - 51 100
OC1
50 50
30 30
10 10
R 1300SE001-01-P01 F650 - P - 51
5 OC1 5
Seconds
Seconds
3 3
R 1300SE001-03-P01 F650 - P - 51
OC1
1 1
.5 .5
.3 R R 1300SE001-01-P01 F650 .3
R 1460-SG-001 F650 - P - 51
OC1
.1 .1
R AGUA POTABLE_1 F650 - P - 50
OC1
.05 .05
R 1300SE001-01-P01 F650 - P - 50
.03 OC1 .03
R
R AGUA POTABLE_1 F650
R 1300SE001-03-P01 F650 - P - 50
R R 1300SE001-03-P01 F650
OC1
.01 R R 1460-SG-001 F650
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-18. Coordinación de curvas de sobrecorriente de Fase (50 - 51) Interior Mina:
Celdas 1460-SG-001(Sist. de Bombeo), 1300-US-001 (Agua Potable).
Amps X 10 B 1300-ER-006A (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
100 100
50 50
30 R 1300ER006A-P01_1 F650 - P - 51 30
OC1
10 10
5 R 1300ER006A-P01_2 P34N - P - 51 5
Seconds
Seconds
OC1
3 3
1 T 1300-ER-006A 1
.5 .5
.3 .3
.1 .1
T 1300-ER-006A
R 1300ER006A-P01_1 F650
Inrush
.05 .05
R
R 1300ER006A-P01_2 P34N
OC1
R 1300ER006A-P01_2 P34N - P - 50
T 1300-ER-006A
1 MVA OC1
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
100 100
50 50
R 1300ER006B-P01 F650 - P - 51
30 OC1 30
R 1300ER006B-P02 P34N - P - 51
OC1
10 10
5 5
3 3
Seconds
Seconds
1 T 1300-ER-006B 1
.5 .5
.3 .3
.1 .1
T 1300-ER-006B
Inrush
.05 .05
.005 .005
R 1300ER006B-P01
R F650
T 1300-ER-006B
1 MVA
.001 .001
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
R 1300SG007-01-P02 F650 - P - 51
OC1
R 1300SG007-03-P02 F650 - P - 51
100 OC1 100
50 50
R 1300SG006-02-P01 F650 - P - 51
30 OC1 30
R 1300SG006-01-P01 F650 - P - 51
10
OC1 10
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
R R 1300SG006-01-P01 F650
.1 .1
R R 1300SG006-02-P01 F650
.05 .05
R R 1300SG007-01-P02 F650
.03 .03
R R 1300SG007-03-P02 F650
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
R 1300SG007-03-P02 F650 - P - 51
OC1
R 1300SG007-01-P02 F650 - P - 51
100 100
OC1
50 50
R 1300SG006-01-P02 F650 - P - 51
30 OC1 30
R 1300SG006-02-P02 F650 - P - 51
OC1
10 10
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
R R 1300SG006-01-P02 F650
.1 .1
R R 1300SG006-02-P02 F650
.03 .03
100 100
50 50
R 1300ER005A-P01_1 F650 - P - 51
30 OC1 30
R 1300ER005A-P01_2 P34N - P - 51
OC1
10 10
5 5
3 3
Seconds
Seconds
1 T 1300-ER-005A 1
.5 .5
.3 .3
.1 .1
T 1300-ER-005A
Inrush
.05 .05
OC1
R 1300ER005A-P01_2 P34N - P - 50
.01 OC1 .01
.005 .005
R R 1300ER005A-P01_2 P34N
.003 .003
T 1300-ER-005A
1 MVA
.001 .001
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
100 100
50 50
30 30
R 1300ER005B-P01_1 F650 - P - 51
10 OC1 10
5 5
Seconds
Seconds
R 1300ER005B-P01_2 P34N - P - 51
3 3
OC1
1 T 1300-ER-005B 1
.5 .5
.3 R R 1300ER005B-P01_1 F650
.3
.1 .1
T 1300-ER-005B
Inrush
.05 R R 1300ER005B-P01_2 P34N
.05
500 500
300 300
R 1300SG006-02-P02 F650 - P - 51
OC1
R 1300SG006-01-P02 F650 - P - 51
100 100
OC1
50 R 1300SG003_P01 F650 - P - 51 50
OC1
30 30
10 10
Seconds
OC1
3 3
1 1
.5 .5
.3 .3
.1 .1
.05 .05
R R 1300SG003_P01 F650
.03 .03
R R 1300SG006-01-P02 F650
500 500
300 300
R 1300SG006-02-P02 F650 - P - 51
100 100
OC1
R 1300SG006-01-P02 F650 - P - 51
50 50
OC1
30 30
R 1300SG003_P02 F650 - P - 51
10 OC1 10
Seconds
3 3
1 1
.5 .5
.3 .3
.1 .1
.05 .05
R R REF 630 A22
.03 .03
R R 1300SG003_P02 F650
R R 1300SG006-01-P02 F650
500 500
300 300
100
R 1300SG002_P01 F650 - P - 51 100
OC1
50 50
30 30
10 10
Seconds
3 3
1 1
.5
R REF 630 A20 R
.5
R 1300SG006-01-P01 F650 - P - 51
.3 .3
OC1
R 1300SG006-02-P01 F650 - P - 51
OC1
.1 .1
R R 1300SG002_P01 F650
.05 .05
R R 1300SG006-01-P01 F650
.03 .03
500 500
R 1300SG006-02-P01 F650 - P - 51
300 OC1 300
R 1300SG006-01-P01 F650 - P - 51
OC1
100 100
R 1300SG003_P4 F650 - P - 51
OC1
50 50
30 30
10 10
5 5
Seconds
Seconds
3 3
R REF 630 A22 - P - 51
OC1
1 1
.3 .3
.1 .1
R R 1300SG003_P4 F650
.05 .05
R R 1300SG006-01-P01 F650
.03 .03
500 500
300 300
100 100
OC1
30 30
R T1 QUELLOPATA 10KV LV - P - 51
OC1
10 10
R T2 QUELLOPATA 10KV - P - 51
OC1
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
.1 .1
.05 .05
.03 .03
R
R T2 QUELLOPATA 10KV
R R T1 QUELLOPATA 10KV LV
500 500
300 300
100 100
30 R T2 QUELLOPATA 10KV - P - 51 30
OC1
R T1 QUELLOPATA 10KV LV - P - 51
10 10
OC1
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
.1 .1
.05 .05
.03 .03
R
R T2 QUELLOPATA 10KV
R R T1 QUELLOPATA 10KV LV
500 500
300 300
100 100
50 50
30 30
R_6220-TL-001A_HV 2 - G - 50
10 OC1 10
R_6220-TL-001A_HV 1 - G - 50
5 OC1 5
Seconds
Seconds
3 3
R_6220-TL-001A_LV - G - 50
OC1
1 1
.5 .5
.3 R_6220-TL-001A_HV 1 .3
R
R_6220-TL-001A_HV 2
R_6220-TL-001A_HV 1 - G - 51
.1 .1
OC1
6220-TL-001A.
.05
10 MVA
R_6220-TL-001A_LV - G - 51 .05
±
OC1
.03 .03
R_6220-TL-001A_HV 2 - G - 51
OC1
R
500 500
300 300
100 100
50 50
30
R T1 QUELLOPATA 10KV LV - G - 51 30
OC1
R_6220-TL-001A_LV - G - 50
OC1 R T2 QUELLOPATA 10KV - G - 51
10 OC1 10
R_6220-TL-001A_HV 1 - G - 50
OC1
5 5
Seconds
Seconds
R_6220-TL-001A_HV 2 - G - 50
3 3
OC1
1 1
.5 .5
.3 .3
R_6220-TL-001A_HV 2 - G - 51
.1 .1
OC1
R_6220-TL-001A_HV 1 - G - 51
.05 .05
R T2 QUELLOPATA 10KV
R R T1R QUELLOPATA 10KV LV
R_6220-TL-001A_HV 1
OC1
R
.03 R
R_6220-TL-001A_HV 2
R_6220-TL-001A_LV - G - 51 .03
OC1
.01 R
R_6220-TL-001A_LV .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-32. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) celda A-01.
Amps X 10 (Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
10 10
5 5
Seconds
Seconds
3 3
R_6220-TL-001B_HV - G - 51
OC1
1 1
.5 .5
.3 .3
R_6220-TL-001B_HV
.1 .1
.05 .05
.03
R_6220-TL-001B_HV - G - 50 .03
6220-TL-001B
OC1
2.5 MVA
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
100 100
50 50
30 30
10 10
5 5
Seconds
Seconds
3 3
R_6220-TL-003_HV - G - 51
OC1
1 1
.5 .5
.3 .3
R_6220-TL-003_HV
.1 .1
.05 .05
R_6220-TL-003_HV - G - 50
.03 .03
OC1
6220-TL-003
2 MVA
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-34. Curvas curvas de sobrecorriente de Tierra (50N - 51N) Transformador 6220-TL-003
Amps X 10 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
R T1 QUELLOPATA 10KV LV - G - 51
10 10
OC1
R T2 QUELLOPATA 10KV - G - 51
5 5
Seconds
Seconds
OC1
3 3
1 R_6220-TL-001B_HV - G - 51 1
OC1
.5 .5
.3 .3
.1 .1
.05 .05
R_6220-TL-001B_HV - G - 50
.03 .03
OC1
R T2 QUELLOPATA 10KV
R
R T1 QUELLOPATA 10KV LV
R
.01 R
R_6220-TL-001B_HV .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-35. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) celdas A03, A-04, A-06.
Amps X 10 (Plot Ref. kV=4.16)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
10 10
5 5
Seconds
Seconds
3 R_6220-TL-001A_LV - G - 51 3
OC1
1 1
.5 .5
R_Bolas Motor 1 - G - 51
.3
OC1 .3
R_Molino SAG - G - 51
OC1
R_Bolas Motor 2 - G - 51 R_6220-TL-001A_LV - G - 50
.1 .1
OC1 OC1
.05 .05
Figura A-36. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) Bolas Motor 1,
Bolas Motor 2, Molino SAG.
Amps X 10 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
R T2 QUELLOPATA 10KV - G - 51
OC1
R T1 QUELLOPATA 10KV LV - G - 51
10 OC1 10
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
R_6220-TL-003_HV - G - 51
.1 OC1 .1
.05 .05
R_6220-TL-003_HV - G - 50
.03 .03
OC1
R R T1R QUELLOPATA
R T2 QUELLOPATA
10KV LV 10KV
.01 R
R_6220-TL-003_HV .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-37. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) celda A-05.
Amps X 10 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 R T2 QUELLOPATA 10KV - G - 51 30
OC1
R T1 QUELLOPATA 10KV LV - G - 51
OC1
10 10
5 5
Seconds
Seconds
3 3
R A07 - G - 51
1 1
OC1
.5 .5
.3 .3
.1 .1
R R A07
.03 .03
.01 6212-SW-007
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-38. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) celda A-07.
Amps X 10 (Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
10 10
5 5
Seconds
Seconds
3 3
1 1
R_6220-TL-005_HV - G - 51
OC1
.5 .5
.3 .3
R
R_6220-TL-005_HV
.1 .1
.05 .05
6220-TL-005
OC1
1000 kVA
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
100 100
50 50
30 R T2 QUELLOPATA 10KV - G - 51 30
OC1
R T1 QUELLOPATA 10KV LV - G - 51
10 OC1 10
5 5
Seconds
Seconds
3 3
R_6220-TL-005_HV - G - 51
1 1
OC1
.5 .5
.3 .3
.1 .1
.05 .05
R_6220-TL-005_HV - G - 50
.03 .03
OC1
R
R T2 QUELLOPATA 10KV
R R T1 QUELLOPATA 10KV LV
.01 R
R_6220-TL-005_HV
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-40. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) celda A-08.
Amps X 10 (Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
10 10
5
R_6320-TD-001_HV 2 - G - 51 5
Seconds
Seconds
OC1
3 3
R_6320-TD-001_HV 1 - G - 51
OC1
1 1
.5 .5
.3 .3
R
R_6320-TD-001_NEUTRO - G - 51
R_6320-TD-001_HV 1 OC1
R
R_6320-TD-001_HV 2
.1 .1
.05 .05
R_6320-TD-001_HV 2 - G - 50 R_6320-TD-001_NEUTRO - G - 50
.03 .03
6320-TD-001 OC1 OC1
1600 kVA
±
R
R_6320-TD-001_HV 1 - G - 50
R_6320-TD-001_NEUTRO OC1
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
100 100
50 50
30 30
R T1 QUELLOPATA 10KV LV - G - 51
OC1
R T2 QUELLOPATA 10KV - G - 51
10 10
OC1
5 5
Seconds
Seconds
3 3
R_6320-TD-001_HV 2 - G - 51
OC1
1 R_6320-TD-001_HV 1 - G - 51 1
OC1
.5 .5
.3 .3
.1 .1
.05 .05
.03
R_6320-TD-001_HV 1 - G - 50 .03
OC1
R R T1 QUELLOPATA 10KV LV R
R T2 QUELLOPATA 10KV R_6320-TD-001_HV 2 - G - 50
R
R_6320-TD-001_HV 1
OC1
.01 R
R_6320-TD-001_HV 2
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
100 100
50 50
30 30
R T1 QUELLOPATA 10KV LV - G - 51
OC1
10 R T2 QUELLOPATA 10KV - G - 51 10
OC1
5 5
Seconds
Seconds
3 3
1 1
R A17 REF 630 (CB-9) - G - 51
.5
OC1 .5
.3 .3
.05 .05
.03 .03
R R T1 QUELLOPATA
R
R T210KV
QUELLOPATA
LV 10KV
Figura A-43. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) celda A-17.
Amps X 10 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
R_6220-TL-006B_HV - G - 51
30
OC1 30
R T2 QUELLOPATA 10KV - G - 51
OC1
10
R T1 QUELLOPATA 10KV LV - G - 51 10
OC1
5 5
3 3
Seconds
Seconds
1 1
R A17 REF 630 (CB-9) - G - 51
OC1
.5 .5
.3 .3
.05 .05
.03 .03
.01 .01
R T2 QUELLOPATA 10KV
R R T1 QUELLOPATA
R 10KV LV
R_6220-TL-006B_HV - G - 50
.005 OC1 .005
R R A17 REF 630 (CB-9)
.003 .003
R_6220-TL-006B_HV
R
.001 .001
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-44. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) celda A-17.
Amps X 10 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
R T1 QUELLOPATA 10KV LV - G - 51
OC1
R T2 QUELLOPATA 10KV - G - 51
10 10
OC1
5 5
Seconds
Seconds
3 3
R A18 - G - 51
1 OC1 1
.5 .5
.3 .3
.1 .1
R A18 - G - 50
.05 OC1 .05
.03 .03
R T2 QUELLOPATA 10KV
R T1 QUELLOPATA 10KV LV R
R
.01 R R A18
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-45. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) celda A-18.
Amps X 100 QUELLOPATA 10KV (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 R T2 QUELLOPATA 10KV - G - 51 30
OC1
R T1 QUELLOPATA 10KV LV - G - 51
10 OC1 10
5 5
Seconds
Seconds
3 3
1
R A19 - G - 51 1
OC1
.5 .5
.3 .3
.1 R A19 - G - 50 .1
OC1
R T2 QUELLOPATA 10KV
R
R T1 QUELLOPATA 10KV LV
.05 .05
R
.03 .03
R R A19
.01 40A..
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-46. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) celda A-19.
Amps X 10 (Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30 30
R 1300SE001-01-P01 F650 - G - 51
OC1
R 1300SE001-03-P01 F650 - G - 51
10 10
OC1
5 5
Seconds
Seconds
3 3
1 1
.5 .5
R R 1300SE001-01-P01 F650
.3 .3
.1 .1
R 1300SE001-03-P01 F650 - G - 50
OC1
.05 .05
R 1300SE001-01-P01 F650 - G - 50
.03 OC1 .03
R R 1300SE001-03-P01 F650
.01 F 1460-XFD-001P
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Figura A-47. Curvas de sobrecorriente de Tierra (50N - 51N) Interior Mina: Transformadores
T 1460-TL-001, T 1460-TL-002.
Amps X 10 B 1460-SG-001 (Nom. kV=10, Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
R 1300SE001-01-P01 F650 - G - 51
OC1
100 100
R 1300SE001-03-P01 F650 - G - 51
OC1
50 50
30 30
10 10
5 5
Seconds
Seconds
R AGUA POTABLE_1 F650 - G - 51
3 OC1 3
R 1460-SG-001 F650 - G - 51
OC1
1 1
.5 .5
.3 R R 1300SE001-01-P01 F650 .3
.1 .1
R 1300SE001-03-P01 F650 - G - 50
.05 OC1 .05
OC1
R
R AGUA POTABLE_1 F650
R R 1300SE001-03-P01 F650
Figura A-48. Coordinación de curvas de sobrecorriente de Tierra (50N - 51N) Interior Mina:
Celdas 1460-SG-001(Sist. de Bombeo), 1300-US-001 (Agua Potable).
Amps (Plot Ref. kV=10)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
100 100
50 50
30
R 1300ER006A-P01_1 F650 - G - 51 30
OC1
10 10
5 5
Seconds
Seconds
3 3
1 1
R 1300ER006A-P01_2 P34N - G - 51
OC1
.5 .5
.3 .3
.1 .1
R 1300ER006A-P01_1 F650
.05 .05
R
R 1300ER006A-P01_2 P34N
OC1
R 1300ER006A-P01_2 P34N - G - 50
T 1300-ER-006A
1 MVA OC1
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
100 100
50 50
30 30
R 1300ER006B-P02 P34N - G - 51
10 OC1 10
R 1300ER006B-P01 F650 - G - 51
5 OC1 5
3 3
Seconds
Seconds
1 1
.5 .5
.3 .3
.1 .1
.05 .05
R 1300ER006B-P01 F650 - G - 50
.03 .03
OC1
R 1300ER006B-P02 P34N - G - 50
OC1
.01 .01
.005 .005
R 1300ER006B-P01
R F650
T 1300-ER-006B
1 MVA
.001 .001
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
R 1300SG007-01-P02 F650 - G - 51
300 300
OC1
R 1300SG007-03-P02 F650 - G - 51
OC1
100 100
R 1300SG006-02-P01 F650 - G - 51
OC1
50 50
R 1300SG006-01-P01 F650 - G - 51
30 OC1 30
10 10
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
R R 1300SG006-01-P01 F650
.1 .1
R R 1300SG006-02-P01 F650
.05 .05
R R 1300SG007-01-P02 F650
.03 .03
R R 1300SG007-03-P02 F650
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
R 1300SG006-02-P02 F650 - G - 51
50 OC1 50
30 R 1300SG006-01-P02 F650 - G - 51 30
OC1
10 10
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
R R 1300SG006-01-P02 F650
.1 .1
R R 1300SG006-02-P02 F650
.03 .03
500 500
300 300
100 100
50 50
30 30
R 1300ER005A-P01_1 F650 - G - 51
OC1
R 1300ER005A-P01_2 P34N - G - 51
10 OC1 10
5 5
3 3
Seconds
Seconds
1 1
.5 .5
.3 .3
.1 .1
.05 .05
R 1300ER005A-P01_1 F650
.03 R
.03
R 1300ER005A-P01_2 P34N - G - 50
OC1
R 1300ER005A-P01_1 F650 - G - 50
.01 .01
OC1
.005 .005
R R 1300ER005A-P01_2 P34N
.003 .003
T 1300-ER-005A
1 MVA
.001 .001
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
500 500
300 300
100 100
50 50
30 30
R 1300ER005B-P01_1 F650 - G - 51
10 10
OC1
5 5
Seconds
Seconds
3 3
1 1
R 1300ER005B-P01_2 P34N - G - 51
OC1
.5 .5
.3 R R 1300ER005B-P01_1 F650
.3
.1 .1
500 500
R 1300SG006-02-P02 F650 - G - 51
300 OC1 300
R 1300SG006-01-P02 F650 - G - 51
OC1
100 100
R 1300SG003_P01 F650 - G - 51
OC1
50 50
30 30
10 10
R REF 630 A20 - G - 51
OC1
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
.1 .1
.05 .05
R R 1300SG003_P01 F650
.03 .03
R R 1300SG006-01-P02 F650
500 500
300 300
R 1300SG006-02-P02 F650 - G - 51
100 OC1 100
R 1300SG006-01-P02 F650 - G - 51
50 OC1 50
30 30
R 1300SG003_P02 F650 - G - 51
OC1
10 10
Seconds
3 3
1 1
.5 .5
.3 .3
.1 .1
.05 .05
R R REF 630 A22
.03 .03
R R 1300SG003_P02 F650
R R 1300SG006-01-P02 F650
500 500
R 1300SG006-02-P01 F650 - G - 51
300 OC1 300
R 1300SG006-01-P01 F650 - G - 51
OC1
100 100
R 1300SG002_P01 F650 - G - 51
OC1
50 50
30 30
Seconds
3 3
1 1
.5
R REF 630 A20 R
.5
.3 .3
.1 .1
R R 1300SG002_P01 F650
.05 .05
R R 1300SG006-01-P01 F650
.03 .03
500 500
R 1300SG006-02-P01 F650 - G - 51
300 OC1 300
R 1300SG006-01-P01 F650 - G - 51
OC1
100 100
R 1300SG003_P4 F650 - G - 51
50 OC1 50
30 30
OC1
5 5
Seconds
Seconds
3 3
1 1
.3 .3
.1 .1
R R 1300SG003_P4 F650
.05 .05
R R 1300SG006-01-P01 F650
.03 .03
500 500
300 300
100 100
50
R REF 630 A20 - G - 51 50
OC1
30 30
R T1 QUELLOPATA 10KV LV - G - 51
OC1
10 R T2 QUELLOPATA 10KV - G - 51 10
OC1
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
.1 .1
.05 .05
.03 .03
R
R T2 QUELLOPATA 10KV
R R T1 QUELLOPATA 10KV LV
500 500
300 300
100 100
50 50
R REF 630 A22 - G - 51
30 OC1 30
R T1 QUELLOPATA 10KV LV - G - 51
OC1
10 10
R T2 QUELLOPATA 10KV - G - 51
OC1
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
.1 .1
.05 .05
.03 .03
R
R T2 QUELLOPATA 10KV
R R T1 QUELLOPATA 10KV LV
QUELLOPATA 66KV
66 kV 1.01 kA
kV
45.118kA
1.0
± ±
R R
T1 T2
20 MVA 20 MVA
621OSG001-P1 621OSG001-P2
±
±
R
R
kV
±
±
7.8 2
QUELLOPATA 10KV
10 kV 0.879 kA 0.878 kA
0.378 kA 0.378 kA 0.378 kA 0.378 kA 0.378 kA 3.65
kA
Open ±
±
±
±
±
R R
± ± ± ± ± R R
R
±
±
R
R R
R R 10 kV C 6310TL001-P
R
±
±
±
R ±
B 6310TL001-P 3.61 kA
R R ± ± ±
± R ±
R R ±
kV
±
± ±
R ± R
R R 3.6
7.81 kA
R R
R
± ± T10 T12
R
R
3.65 kA 0.5 MVA 0.13 MVA
6320TD001-P
kV
7.82
6220TL001A-P1/P2 6220TL003-P 6220TL004-P
6220TL002-P 10 kV 3.23 kA 7.8 kV 3.65 kA
6220TL001B-P Bus131 6320TD004-P 6320TD005-P
0.377 kA 6320TD003-P 10 kV 3.65 kA
6220TL005-P 3.6
6320TD002-P Bus158
RESERVA 1 3.65 kA kA 3.65 B 6210-DP-001A B 6210-DP-001B
0 MVA kA 0.48 kV 0.23 kV
6220-TL-001A. 6220-TL-004
10 MVA 6220-TL-002 6220-TL-003 6320-TD-005
6220-TL-001B 2 MVA 2500 kVA 6320-TD-003 6320-TD-004 10 kV 2.06 kA
2.5 MVA 6320-TD-001 6320-TD-002 1600 kVA 1600 kVA Bus161 6220TLO12B-P 6220TL012AC-P Load2 Load1
2.5 MVA 6220-TL-005 1600 kVA ±
kV 2.06 kA 3.65 kA
±
±
1000 kVA 1600 kVA 1600 kVA ±
±
R 7.068 kA
2.0 C 1300LP001-P C 6210XC001-P C 1300LP002-P 0.5 MVA 0.13 MVA
R
±
±
R
3.65 kA
R
R
±
Load1-1 7.039 kA
1.9 7.29
R kA
1300-TF-008 6220DP012A-P
630 kVA 6220-TL-015 6220DP012C-P
2130MC006-P 500 kVA
±
6220DP012B-P C 1300SG002_P01
±
± 500 kVA Bus21 C 1300SG003_P4 ± ±
R
R ± Load2-1 10 kV 3.52 kA ±
±
R R
R
R 800 kVA 3.5 9 kV R
± ±
7.62 kA
R
±
6220-DP-012A 6220-DP-012B 6220-DP-012C
1.06 kA 1.06 kA CHANCADORA Y AGUA FRESCA 400 kVA 400 kVA 400 kVA
1000 kVA CAMPAMENTO ZICSA BOCAMINA 4300
500 kVA 500 kVA
± ±
±
± ±
1.22 kA ±
R
±
C 1300TF003_P02
R
6212-SE-004 1.22 kA 6212-SE-006 C 1300TF002_P01
6212-SE-003 45 kVA 0.993 kA ± ±
250 kVA
MOLINO DE BOLAS MOTOR 2 MOLINO SAG TABLERO DEL SISTEMA SER 250 kVA
MOLINO DE BOLAS MOTOR 1 2250 kW T 1300_TF_003
2250 kW 2250 kW 10000 kVA 6212-SE-005 1.02 kA 6212-SE-002 ± ±
T 1300_TF_002 ± 1 MVA
45 kVA 250 kVA 1 MVA ±
3.52 kA 3.52 kA
6212-SE-001
Cable1-1 250 kVA
3950DP002-P01 6220-TL-008 6220-TL-008A
6212-SE-007 6212-SE-008 C 1300SG006-01-P02 C 1300DP003_P02
3950DP005-P01 3950DP004-P01 2500 kVA 1500 kVA C 1300DP002-P01 C 1300SG006-01-P01
3950DP003-P01 250 kVA 45 kVA
3950DP001-P01
± R
3950-DP-007 PTAR
250 kVA 45 kVA Load4
Load3 1 MVA
1 MVA
R
B 1300-SG-006_2
10 kV
2.31 kA 0.814 kA
B 1300-SG-006 kVkA kV
10 kV 2.31
0.814
3.1
7.31
8 kA 7.318 kA
3.1
kA
±
R R
± ±
R
R R
± ±
Bus2
10 kV 3.11 kA
kV
7.318 kA
3.1
T 1300-TF-010 T-01
0.125 MVA T 1300-TF-010 T-02 ±
± ±
0.125 MVA
± ±
C 1300SE001-01-P01 C 1300SG007-01-P01
C 1300ER005A-P01 C 1300SG007-01-P02 C 1300ER005B-P01
Cable42 Cable43
C 1300SG007-02-P01 C 1300SG007-02-P02 ±
Bus26 Bus27
C 1300SG007-03-P01 0.48 kV 0.23 kV
±
C 1300SG007-03-P02
R
R
Load7 Load8 ±
B 1300-ER-005B
B 1300-ER-005A 10 kV 3.07 kA
10 kV 3.07 kA kV
3.0 kV R 7.377 kA
3.0
7.377 kA ±
±
R
1300-SG-007_1 1300-SG-007_2
10 kV 1.1 kA 10 kV 1.1 kA
1.1 kA kV
1.96
7.3 7
3.0 kA 7.357 kA
0.859 kA 3.0
kV
T 1300-ER-005A 5 kA
R R T 1300-ER-005B
± ±
1 MVA R
Bus4 1 MVA
±
10 kV 3.05 kA
kV
7.357 kA
3.0
T8 T6
0.125 MVA 0.125 MVA
B 1300-ER-005A LV C 1300SE001-02-P01 B 1300-ER-005B LV
± ±
0.48 kV 0.48 kV
±
C 1300ER006B-P01
Load5 C 1300ER006A-P01 Load6
1 MVA C 1300-DP-012 C 1300-DP-012A 1 MVA
Load10 Load9
± 0.125 MVA 0.125 MVA
C 1460-SG-001 C 1300ER006B-P02
T AGUA POTABLE
0.5 MVA
±
B 1300-ER-006A R R
±
T 1460-TL-001 T 1460-TL-002
0.8 MVA 0.8 MVA
B T 1300-ER-006A
0.48 kV T 1300-ER-006B
1 MVA
Load13
1 MVA
B T 1300-ER-006B
0.48 kV
B 1460-TL-001 ± B 1460-TL-002 ±
0.48 kV 0.48 kV
Load12
1 MVA
Load11
0.8 MVA
QUELLOPATA 66KV
66 kV 1.01 kA
kV
45.118kA
1.0
± ±
R R
T1 T2
20 MVA 20 MVA
621OSG001-P1 621OSG001-P2
±
±
R
R
kV
±
±
8.4 2
QUELLOPATA 10KV
10 kV 0.386 kA 0.386 kA
0.394 kA 0.394 kA 0.394 kA 0.394 kA 0.394 kA 2.74
kA
Open ±
±
±
±
±
R R
± ± ± ± ± R R
R
±
±
R
R R
R R 10 kV C 6310TL001-P
R
±
±
±
R ±
B 6310TL001-P 2.72 kA
R R ± ± ±
± R ±
R R ±
2.7 kV
8.329 kA
± ± R R
± R ± R
R R
R
± ± T10 T12
R
R
2.74 kA 0.5 MVA 0.13 MVA
6320TD001-P
kV
8.42
6220TL001A-P1/P2 6220TL003-P 6220TL004-P
10 kV 2.33 kA kV 2.74 kA
6220TL001B-P 6220TL002-P Bus131 8.39 6320TD005-P
6320TD003-P 6320TD004-P 10 kV 2.74 kA
6220TL005-P 0.393 kA 6320TD002-P
RESERVA 1 2.7 2 Bus158 2.74 B 6210-DP-001A B 6210-DP-001B
0 MVA 2.74 kA kA kA
6220-TL-001A. 0.48 kV 0.23 kV
6220-TL-003 6220-TL-004
10 MVA 6220-TL-002 2500 kVA 6320-TD-004 6320-TD-005
6220-TL-001B 2.5 MVA 2 MVA 6320-TD-003 1600 kVA 10 kV 1.78 kA
Bus161
2.5 MVA 6220-TL-005 6320-TD-001 6320-TD-002 1600 kVA 1600 kVA ±
kV
6220TLO12B-P 6220TL012AC-P Load2 Load1
1600 kVA 1600 kVA ±
R 7.484 kA
1.7 1.78 kA 2.74 kA C 1300LP001-P C 6210XC001-P C 1300LP002-P 0.5 MVA 0.13 MVA
±
±
1000 kVA ±
R
±
±
R
2.74 kA
R
R
±
Load1-1 1.6 kV 7.38
R 7.48 kA kA
1300-TF-008 6220DP012A-P
630 kVA 6220-TL-015 6220DP012C-P
2130MC006-P 500 kVA
±
6220DP012B-P C 1300SG002_P01
±
± 500 kVA Bus21 C 1300SG003_P4 ± ±
R
R ± Load2-1 10 kV 2.68 kA ±
±
R R
R
R 800 kVA 2.6 kV R
± ±
8.38 kA
R
±
6220-DP-012A 6220-DP-012B 6220-DP-012C
0.966 kA 0.966 kA CHANCADORA Y AGUA FRESCA 400 kVA 400 kVA 400 kVA
1000 kVA CAMPAMENTO ZICSA BOCAMINA 4300
500 kVA 500 kVA
± ±
±
± ±
1.1 kA ±
R
±
C 1300TF003_P02
R
6212-SE-004 1.1 kA 6212-SE-006 C 1300TF002_P01
6212-SE-003 45 kVA 0.914 kA ± ±
250 kVA
MOLINO DE BOLAS MOTOR 2 MOLINO SAG TABLERO DEL SISTEMA SER 250 kVA
MOLINO DE BOLAS MOTOR 1 2250 kW T 1300_TF_003
2250 kW 2250 kW 10000 kVA 6212-SE-005 0.94 kA 6212-SE-002 ± ±
T 1300_TF_002 ± 1 MVA
45 kVA 250 kVA 1 MVA ±
2.68 kA 2.68 kA
6212-SE-001
Cable1-1 250 kVA
3950DP002-P01 6220-TL-008 6220-TL-008A
6212-SE-007 6212-SE-008 C 1300SG006-01-P02 C 1300DP003_P02
3950DP005-P01 3950DP004-P01 2500 kVA 1500 kVA C 1300DP002-P01 C 1300SG006-01-P01
3950DP003-P01 250 kVA 45 kVA
3950DP001-P01
± R
3950-DP-007 PTAR
250 kVA 45 kVA Load4
Load3 1 MVA
1 MVA
R
B 1300-SG-006_2
10 kV
1.82 kA 0.64 kA
B 1300-SG-006 kV kV
10 kV 1.82
0.64
2.4
7.95
9 kAkA 7.959 kA
2.4
kA
±
R R
± ±
R
R R
± ±
Bus2
10 kV 2.45 kA
kV
7.959 kA
2.4
T 1300-TF-010 T-01
0.125 MVA T 1300-TF-010 T-02 ±
± ±
0.125 MVA
± ±
C 1300SE001-01-P01 C 1300SG007-01-P01
C 1300ER005A-P01 C 1300SG007-01-P02 C 1300ER005B-P01
Cable42 Cable43
C 1300SG007-02-P01 C 1300SG007-02-P02 ±
Bus26 Bus27
C 1300SG007-03-P01 0.48 kV 0.23 kV
±
C 1300SG007-03-P02
R
R
Load7 Load8 ±
B 1300-ER-005B
B 1300-ER-005A 10 kV 2.42 kA
10 kV 2.42 kA kV
2.4 kV R 7.928 kA
2.4
7.928 kA ±
±
R
1300-SG-007_1 1300-SG-007_2
10 kV 0.866 kA 10 kV 0.866 kA
0.866 kA kV
1.54
7.9 7
2.4 kA 7.917 kA
0.677 kA 2.4
kV
T 1300-ER-005A 1 kA
R R T 1300-ER-005B
± ±
1 MVA R
Bus4 1 MVA
±
10 kV 2.41 kA
kV
7.917 kA
2.4
T8 T6
0.125 MVA 0.125 MVA
B 1300-ER-005A LV C 1300SE001-02-P01 B 1300-ER-005B LV
± ±
0.48 kV 0.48 kV
±
C 1300ER006B-P01
Load5 C 1300ER006A-P01 Load6
1 MVA C 1300-DP-012 C 1300-DP-012A 1 MVA
Load10 Load9
± 0.125 MVA 0.125 MVA
C 1460-SG-001 C 1300ER006B-P02
T AGUA POTABLE
0.5 MVA
±
B 1300-ER-006A R R
±
T 1460-TL-001 T 1460-TL-002
0.8 MVA 0.8 MVA
B T 1300-ER-006A
0.48 kV T 1300-ER-006B
1 MVA
Load13
1 MVA
B T 1300-ER-006B
0.48 kV
B 1460-TL-001 ± B 1460-TL-002 ±
0.48 kV 0.48 kV
Load12
1 MVA
Load11
0.8 MVA
QUELLOPATA 66KV
66 kV 1.17 kA -69.7 deg
0 deg
0.17 kA -84 deg 0.17 kA -81.1 deg 1.5
0 kVkA
-72 .6
± ± deg
R R
T1 T2
20 MVA 20 MVA
621OSG001-P1 621OSG001-P2
±
±
R
R
0 deg
±
±
0 kV
QUELLOPATA 10KV
10 kV 2.94 kA -74.8 deg 2.94 kA -72 deg
2.48 kA -82.3 deg 8.34
kA -76
.1 deg
Open ±
±
±
±
±
R R
± ± ± ± ± R R
R
±
±
R
R R
R R 10 kV C 6310TL001-P
R
±
±
±
R ±
B 6310TL001-P 8.24 kA -75.4 deg
R R ± ± ±
R
R
±
R ±
±
R R 8.2 0 deg
±
±
R
±
R ±
R
R 0 kV
4 kA
R -75 .4 deg
± ± T10 T12
R
R
8.34 kA -76.1 deg 0.5 MVA 0.13 MVA
6320TD001-P
0 deg
0 kV
6220TL001A-P1/P2 6220TL003-P 6220TL004-P deg
10 kV 8.24 kA -75.2 0deg 8.34 kA -76.1 deg
6220TL001B-P 6220TL002-P Bus131 0 kV 6320TD005-P
6320TD003-P 6320TD004-P 10 kV 8.34 kA -76.1 deg
6220TL005-P 8.2 4
6320TD002-P Bus158
RESERVA 1 8.34 kA -76.1 deg kA -75 8.34 B 6210-DP-001A B 6210-DP-001B
0 MVA kA -76 0.48 kV 0.23 kV
6220-TL-001A. .2 deg .1
6220-TL-003 6220-TL-004 deg
10 MVA 6220-TL-002 2500 kVA 6320-TD-004 6320-TD-005
6220-TL-001B 2.5 MVA 2 MVA 6320-TD-003 1600 kVA 10 kV 4 kA -63.1 deg
Bus161
2.5 MVA 6220-TL-005 6320-TD-001 6320-TD-002 1600 kVA 1600 kVA ±
0 deg
6220TLO12B-P 6220TL012AC-P Load2 Load1
1600 kVA 1600 kVA ±
R 40 kA
kV 4 kA -63.1 deg 8.34 kA -76.1 deg C 1300LP001-P C 6210XC001-P C 1300LP002-P 0.5 MVA 0.13 MVA
±
±
1000 kVA ±
R
-63 .1
±
±
Load1-1 0 kV
±
deg 3.6
0 kV9 kA 3 kA -44
R
630 kVA -59.5
1300-TF-008 6220DP012A-P 6220DP012C-P
6220-TL-015 .4 deg
2130MC006-P deg 500 kVA
±
6220DP012B-P C 1300SG002_P01
±
± 500 kVA Bus21 C 1300SG003_P4 ± ±
R
R ± Load2-1 10 kV 7.85 kA -75.1 deg ±
±
R R
deg R
R 0 kA -133.5 deg 800 kVA 7.8 0 R
± ±
0 kV
5 kA
R -75.1
deg
±
6220-DP-012A 6220-DP-012B 6220-DP-012C
1.5 kA -23.3 deg 1.5 kA -23.3 deg CHANCADORA Y AGUA FRESCA 400 kVA 400 kVA 400 kVA
1000 kVA CAMPAMENTO ZICSA BOCAMINA 4300
500 kVA 500 kVA
± ±
±
± ±
250 kVA
MOLINO DE BOLAS MOTOR 2 MOLINO SAG TABLERO DEL SISTEMA SER 250 kVA
MOLINO DE BOLAS MOTOR 1 2250 kW T 1300_TF_003
2250 kW 2250 kW 10000 kVA 6212-SE-005 1.45 kA -23.4 deg 6212-SE-002 ± ±
T 1300_TF_002 ± 1 MVA
45 kVA 250 kVA 1 MVA ±
± R
3950-DP-007 PTAR
250 kVA 45 kVA Load4
Load3 1 MVA
1 MVA
R
B 1300-SG-006_2
10 kV
4.51 kA -66.5 deg 2.12 kA -75.4 deg
B 1300-SG-006 deg
0kA 0 deg
10 kV 4.51 kA -66.5
02.12
6.6 kV
2
deg -75.4 deg 0 kA -143.5 deg 6.6
0 kV
2 kA
kA -69 -69 .3
R R .3 deg
±
deg
± ±
R
R R
± ±
Bus2
10 kV 6.62 kA -69.3 deg
6.6 0 deg
0 kV2 kA
T 1300-TF-010 T-01 -69.3
0.125 MVA T 1300-TF-010
deg T-02 ±
± ±
0.125 MVA
± ±
C 1300SE001-01-P01 C 1300SG007-01-P01
C 1300ER005A-P01 C 1300SG007-01-P02 C 1300ER005B-P01
Cable42 Cable43
C 1300SG007-02-P01 C 1300SG007-02-P02 ±
Bus26 Bus27
C 1300SG007-03-P01 0.48 kV 0.23 kV
±
C 1300SG007-03-P02
R
R
Load7 Load8 ±
B 1300-ER-005B
B 1300-ER-005A 10 kV 6.52 kA -68.6 deg
10 kV 6.52 kA -68.6 deg 0 deg
0 deg R 6.5
0 kV
2 kA
6.5
0 kV
2 kA ±
±
-68
-68.6 R .6 deg
deg 1300-SG-007_1 1300-SG-007_2
10 kV 2.33 kA -68.4 deg 10 kV 2.33 kA -68.4 deg
deg 0kAdeg
2.33 kA -68.46.5
4.16
0 kV
-68.4 deg 6.5 0 deg
0 kVkA deg
1.83 kA -68.4
T 1300-ER-005A kA -68 R R -68 .4 T 1300-ER-005B
.4 deg ± ±
deg
1 MVA R
Bus4 1 MVA
±
C 1300ER006B-P01
Load5 C 1300ER006A-P01 Load6
1 MVA C 1300-DP-012 C 1300-DP-012A 1 MVA
Load10 Load9
± 0.125 MVA 0.125 MVA
C 1460-SG-001 C 1300ER006B-P02
T AGUA POTABLE
0.5 MVA
±
B 1300-ER-006A R R
±
Load13
1 MVA
B T 1300-ER-006B
0.48 kV
B 1460-TL-001 ± B 1460-TL-002 ±
0.48 kV 0.48 kV
Load12
1 MVA
Load11
0.8 MVA
QUELLOPATA 66KV
66 kV 1.01 kA
kV
45.118kA
1.0
± ±
R R
T1 T2
20 MVA 20 MVA
621OSG001-P1 621OSG001-P2
±
±
R
R
kV
±
±
7.8 2
QUELLOPATA 10KV
10 kV 0.879 kA 0.878 kA
0.378 kA 0.378 kA 0.378 kA 0.378 kA 0.378 kA 3.65
kA
Open ±
±
±
±
±
R R
± ± ± ± ± R R
R
±
±
R
R R
R R 10 kV C 6310TL001-P
R
±
±
±
R ±
B 6310TL001-P 3.61 kA
R R ± ± ±
± R ±
R R ±
kV
±
± ±
R ± R
R R 3.6
7.81 kA
R R
R
± ± T10 T12
R
R
3.65 kA 0.5 MVA 0.13 MVA
6320TD001-P
kV
7.82
6220TL001A-P1/P2 6220TL003-P 6220TL004-P
6220TL002-P 10 kV 3.23 kA 7.8 kV 3.65 kA
6220TL001B-P Bus131 6320TD004-P 6320TD005-P
0.377 kA 6320TD003-P 10 kV 3.65 kA
6220TL005-P 3.6
6320TD002-P Bus158
RESERVA 1 3.65 kA kA 3.65 B 6210-DP-001A B 6210-DP-001B
0 MVA kA 0.48 kV 0.23 kV
6220-TL-001A. 6220-TL-004
10 MVA 6220-TL-002 6220-TL-003 6320-TD-005
6220-TL-001B 2 MVA 2500 kVA 6320-TD-003 6320-TD-004 10 kV 2.06 kA
2.5 MVA 6320-TD-001 6320-TD-002 1600 kVA 1600 kVA Bus161 6220TLO12B-P 6220TL012AC-P Load2 Load1
2.5 MVA 6220-TL-005 1600 kVA ±
kV 2.06 kA 3.65 kA
±
±
1000 kVA 1600 kVA 1600 kVA ±
±
R 7.068 kA
2.0 C 1300LP001-P C 6210XC001-P C 1300LP002-P 0.5 MVA 0.13 MVA
R
±
±
R
3.65 kA
R
R
±
Load1-1 7.039 kA
1.9 7.29
R kA
1300-TF-008 6220DP012A-P
630 kVA 6220-TL-015 6220DP012C-P
2130MC006-P 500 kVA
±
6220DP012B-P C 1300SG002_P01
±
± 500 kVA Bus21 C 1300SG003_P4 ± ±
R
R ± Load2-1 10 kV 3.52 kA ±
±
R R
R
R 800 kVA 3.5 9 kV R
± ±
7.62 kA
R
±
6220-DP-012A 6220-DP-012B 6220-DP-012C
1.06 kA 1.06 kA CHANCADORA Y AGUA FRESCA 400 kVA 400 kVA 400 kVA
1000 kVA CAMPAMENTO ZICSA BOCAMINA 4300
500 kVA 500 kVA
± ±
±
± ±
1.22 kA ±
R
±
C 1300TF003_P02
R
6212-SE-004 1.22 kA 6212-SE-006 C 1300TF002_P01
6212-SE-003 45 kVA 0.993 kA ± ±
250 kVA
MOLINO DE BOLAS MOTOR 2 MOLINO SAG TABLERO DEL SISTEMA SER 250 kVA
MOLINO DE BOLAS MOTOR 1 2250 kW T 1300_TF_003
2250 kW 2250 kW 10000 kVA 6212-SE-005 1.02 kA 6212-SE-002 ± ±
T 1300_TF_002 ± 1 MVA
45 kVA 250 kVA 1 MVA ±
3.52 kA 3.52 kA
6212-SE-001
Cable1-1 250 kVA
3950DP002-P01 6220-TL-008 6220-TL-008A
6212-SE-007 6212-SE-008 C 1300SG006-01-P02 C 1300DP003_P02
3950DP005-P01 3950DP004-P01 2500 kVA 1500 kVA C 1300DP002-P01 C 1300SG006-01-P01
3950DP003-P01 250 kVA 45 kVA
3950DP001-P01
± R
3950-DP-007 PTAR
250 kVA 45 kVA Load4
Load3 1 MVA
1 MVA
R
B 1300-SG-006_2
10 kV
2.31 kA 0.814 kA
B 1300-SG-006 kVkA kV
10 kV 2.31
0.814
3.1
7.31
8 kA 7.318 kA
3.1
kA
±
R R
± ±
R
R R
± ±
Bus2
10 kV 3.11 kA
kV
7.318 kA
3.1
T 1300-TF-010 T-01
0.125 MVA T 1300-TF-010 T-02 ±
± ±
0.125 MVA
± ±
C 1300SE001-01-P01 C 1300SG007-01-P01
C 1300ER005A-P01 C 1300SG007-01-P02 C 1300ER005B-P01
Cable42 Cable43
C 1300SG007-02-P01 C 1300SG007-02-P02 ±
Bus26 Bus27
C 1300SG007-03-P01 0.48 kV 0.23 kV
±
C 1300SG007-03-P02
R
R
Load7 Load8 ±
B 1300-ER-005B
B 1300-ER-005A 10 kV 3.07 kA
10 kV 3.07 kA kV
3.0 kV R 7.377 kA
3.0
7.377 kA ±
±
R
1300-SG-007_1 1300-SG-007_2
10 kV 1.1 kA 10 kV 1.1 kA
1.1 kA kV
1.96
7.3 7
3.0 kA 7.357 kA
0.859 kA 3.0
kV
T 1300-ER-005A 5 kA
R R T 1300-ER-005B
± ±
1 MVA R
Bus4 1 MVA
±
10 kV 3.05 kA
kV
7.357 kA
3.0
T8 T6
0.125 MVA 0.125 MVA
B 1300-ER-005A LV C 1300SE001-02-P01 B 1300-ER-005B LV
± ±
0.48 kV 0.48 kV
±
C 1300ER006B-P01
Load5 C 1300ER006A-P01 Load6
1 MVA C 1300-DP-012 C 1300-DP-012A 1 MVA
Load10 Load9
± 0.125 MVA 0.125 MVA
C 1460-SG-001 C 1300ER006B-P02
T AGUA POTABLE
0.5 MVA
±
B 1300-ER-006A R R
±
T 1460-TL-001 T 1460-TL-002
0.8 MVA 0.8 MVA
B T 1300-ER-006A
0.48 kV T 1300-ER-006B
1 MVA
Load13
1 MVA
B T 1300-ER-006B
0.48 kV
B 1460-TL-001 ± B 1460-TL-002 ±
0.48 kV 0.48 kV
Load12
1 MVA
Load11
0.8 MVA
QUELLOPATA 66KV
66 kV 1.17 kA -69.7 deg
0 deg
0.17 kA -84 deg 0.17 kA -81.1 deg 1.5
0 kVkA
-72 .6
± ± deg
R R
T1 T2
20 MVA 20 MVA
621OSG001-P1 621OSG001-P2
±
±
R
R
0 deg
±
±
0 kV
QUELLOPATA 10KV
10 kV 2.94 kA -74.8 deg 2.94 kA -72 deg
2.48 kA -82.3 deg 8.34
kA -76
.1 deg
Open ±
±
±
±
±
R R
± ± ± ± ± R R
R
±
±
R
R R
R R 10 kV C 6310TL001-P
R
±
±
±
R ±
B 6310TL001-P 8.24 kA -75.4 deg
R R ± ± ±
R
R
±
R ±
±
R R 8.2 0 deg
±
±
R
±
R ±
R
R 0 kV
4 kA
R -75 .4 deg
± ± T10 T12
R
R
8.34 kA -76.1 deg 0.5 MVA 0.13 MVA
6320TD001-P
0 deg
0 kV
6220TL001A-P1/P2 6220TL003-P 6220TL004-P deg
10 kV 8.24 kA -75.2 0deg 8.34 kA -76.1 deg
6220TL001B-P 6220TL002-P Bus131 0 kV 6320TD005-P
6320TD003-P 6320TD004-P 10 kV 8.34 kA -76.1 deg
6220TL005-P 8.2 4
6320TD002-P Bus158
RESERVA 1 8.34 kA -76.1 deg kA -75 8.34 B 6210-DP-001A B 6210-DP-001B
0 MVA kA -76 0.48 kV 0.23 kV
6220-TL-001A. .2 deg .1
6220-TL-003 6220-TL-004 deg
10 MVA 6220-TL-002 2500 kVA 6320-TD-004 6320-TD-005
6220-TL-001B 2.5 MVA 2 MVA 6320-TD-003 1600 kVA 10 kV 4 kA -63.1 deg
Bus161
2.5 MVA 6220-TL-005 6320-TD-001 6320-TD-002 1600 kVA 1600 kVA ±
0 deg
6220TLO12B-P 6220TL012AC-P Load2 Load1
1600 kVA 1600 kVA ±
R 40 kA
kV 4 kA -63.1 deg 8.34 kA -76.1 deg C 1300LP001-P C 6210XC001-P C 1300LP002-P 0.5 MVA 0.13 MVA
±
±
1000 kVA ±
R
-63 .1
±
±
Load1-1 0 kV
±
deg 3.6
0 kV9 kA 3 kA -44
R
630 kVA -59.5
1300-TF-008 6220DP012A-P 6220DP012C-P
6220-TL-015 .4 deg
2130MC006-P deg 500 kVA
±
6220DP012B-P C 1300SG002_P01
±
± 500 kVA Bus21 C 1300SG003_P4 ± ±
R
R ± Load2-1 10 kV 7.85 kA -75.1 deg ±
±
R R
deg R
R 0 kA -133.5 deg 800 kVA 7.8 0 R
± ±
0 kV
5 kA
R -75.1
deg
±
6220-DP-012A 6220-DP-012B 6220-DP-012C
1.5 kA -23.3 deg 1.5 kA -23.3 deg CHANCADORA Y AGUA FRESCA 400 kVA 400 kVA 400 kVA
1000 kVA CAMPAMENTO ZICSA BOCAMINA 4300
500 kVA 500 kVA
± ±
±
± ±
250 kVA
MOLINO DE BOLAS MOTOR 2 MOLINO SAG TABLERO DEL SISTEMA SER 250 kVA
MOLINO DE BOLAS MOTOR 1 2250 kW T 1300_TF_003
2250 kW 2250 kW 10000 kVA 6212-SE-005 1.45 kA -23.4 deg 6212-SE-002 ± ±
T 1300_TF_002 ± 1 MVA
45 kVA 250 kVA 1 MVA ±
± R
3950-DP-007 PTAR
250 kVA 45 kVA Load4
Load3 1 MVA
1 MVA
R
B 1300-SG-006_2
10 kV
4.51 kA -66.5 deg 2.12 kA -75.4 deg
B 1300-SG-006 deg
0kA 0 deg
10 kV 4.51 kA -66.5
02.12
6.6 kV
2
deg -75.4 deg 0 kA -143.5 deg 6.6
0 kV
2 kA
kA -69 -69 .3
R R .3 deg
±
deg
± ±
R
R R
± ±
Bus2
10 kV 6.62 kA -69.3 deg
6.6 0 deg
0 kV2 kA
T 1300-TF-010 T-01 -69.3
0.125 MVA T 1300-TF-010
deg T-02 ±
± ±
0.125 MVA
± ±
C 1300SE001-01-P01 C 1300SG007-01-P01
C 1300ER005A-P01 C 1300SG007-01-P02 C 1300ER005B-P01
Cable42 Cable43
C 1300SG007-02-P01 C 1300SG007-02-P02 ±
Bus26 Bus27
C 1300SG007-03-P01 0.48 kV 0.23 kV
±
C 1300SG007-03-P02
R
R
Load7 Load8 ±
B 1300-ER-005B
B 1300-ER-005A 10 kV 6.52 kA -68.6 deg
10 kV 6.52 kA -68.6 deg 0 deg
0 deg R 6.5
0 kV
2 kA
6.5
0 kV
2 kA ±
±
-68
-68.6 R .6 deg
deg 1300-SG-007_1 1300-SG-007_2
10 kV 2.33 kA -68.4 deg 10 kV 2.33 kA -68.4 deg
deg 0kAdeg
2.33 kA -68.46.5
4.16
0 kV
-68.4 deg 6.5 0 deg
0 kVkA deg
1.83 kA -68.4
T 1300-ER-005A kA -68 R R -68 .4 T 1300-ER-005B
.4 deg ± ±
deg
1 MVA R
Bus4 1 MVA
±
C 1300ER006B-P01
Load5 C 1300ER006A-P01 Load6
1 MVA C 1300-DP-012 C 1300-DP-012A 1 MVA
Load10 Load9
± 0.125 MVA 0.125 MVA
C 1460-SG-001 C 1300ER006B-P02
T AGUA POTABLE
0.5 MVA
±
B 1300-ER-006A R R
±
Load13
1 MVA
B T 1300-ER-006B
0.48 kV
B 1460-TL-001 ± B 1460-TL-002 ±
0.48 kV 0.48 kV
Load12
1 MVA
Load11
0.8 MVA
QUELLOPATA 66KV
66 kV 1.01 kA
kV
45.118kA
1.0
± ±
R R
T1 T2
20 MVA 20 MVA
621OSG001-P1 621OSG001-P2
±
±
R
R
± kV
± 5.3
QUELLOPATA 10KV
10 kV 5.29 kA 5.29 kA
0.065 kA 0.065 kA 0.065 kA 0.065 kA 0.065 kA 10.64
kA
Open ±
±
±
±
±
R R
± ± ± ± ± R R
R
±
±
R
R R
R R 10 kV C 6310TL001-P
R
±
±
±
R ±
B 6310TL001-P 10.42 kA
R R ± ± ±
± R ±
R
±
± ±
R
R
±
±
R
R R 10. 7 kV
5.242
R R kA
R
± ± T10 T12
R
R
10.64 kA 0.5 MVA 0.13 MVA
6320TD001-P
kV
5.3
6220TL001A-P1/P2 6220TL003-P 6220TL004-P
6220TL002-P 10 kV 10.38 kA 5.19 kV 10.64 kA
6220TL001B-P Bus131 6320TD004-P 6320TD005-P
0.068 kA 6320TD003-P 10 kV 10.64 kA
6220TL005-P 10. 4
6320TD002-P Bus158
RESERVA 1 10.64 kA kA 10.64 B 6210-DP-001A B 6210-DP-001B
0 MVA kA 0.48 kV 0.23 kV
6220-TL-001A. 6220-TL-004
10 MVA 6220-TL-002 6220-TL-003 6320-TD-005
6220-TL-001B 2 MVA 2500 kVA 6320-TD-003 6320-TD-004 10 kV 2.86 kA
2.5 MVA 6320-TD-001 6320-TD-002 1600 kVA 1600 kVA Bus161 6220TLO12B-P 6220TL012AC-P Load2 Load1
2.5 MVA 6220-TL-005 1600 kVA ±
kV 2.86 kA 10.64 kA
±
±
1000 kVA 1600 kVA 1600 kVA ±
±
R 7.164 kA
2.8 C 1300LP001-P C 6210XC001-P C 1300LP002-P 0.5 MVA 0.13 MVA
R
±
±
R
10.64 kA
R
R
±
Load1-1 7.231 kA
2.6 7.41 kA
R
630 kVA 1300-TF-008 6220DP012A-P 6220DP012C-P
2130MC006-P 6220-TL-015 ±
C 1300SG002_P01
500 kVA 500 kVA 6220DP012B-P
±
±
Bus21 C 1300SG003_P4 ± ±
R
R ± Load2-1 10 kV 9.11 kA ±
±
R R
R
R 800 kVA 9.1 2 kV R
± ±
5.51 kA
R
±
6220-DP-012A 6220-DP-012B 6220-DP-012C
1.35 kA 1.35 kA CHANCADORA Y AGUA FRESCA 400 kVA 400 kVA 400 kVA
1000 kVA CAMPAMENTO ZICSA BOCAMINA 4300
500 kVA 500 kVA
± ±
±
± ±
1.62 kA ±
R
±
C 1300TF003_P02
R
6212-SE-004 1.62 kA 6212-SE-006 C 1300TF002_P01
6212-SE-003 45 kVA 1.25 kA ± ±
250 kVA
MOLINO DE BOLAS MOTOR 2 MOLINO SAG TABLERO DEL SISTEMA SER 250 kVA
MOLINO DE BOLAS MOTOR 1 2250 kW T 1300_TF_003
2250 kW 2250 kW 10000 kVA 6212-SE-005 1.3 kA 6212-SE-002 ± ±
T 1300_TF_002 ± 1 MVA
45 kVA 250 kVA 1 MVA ±
9.11 kA 9.11 kA
6212-SE-001
Cable1-1 250 kVA
3950DP002-P01 6220-TL-008 6220-TL-008A
6212-SE-007 6212-SE-008 C 1300SG006-01-P02 C 1300DP003_P02
3950DP005-P01 3950DP004-P01 2500 kVA 1500 kVA C 1300DP002-P01 C 1300SG006-01-P01
3950DP003-P01 250 kVA 45 kVA
3950DP001-P01
± R
3950-DP-007 PTAR
250 kVA 45 kVA Load4
Load3 1 MVA
1 MVA
R
B 1300-SG-006_2
10 kV
4.9 kA 1.73 kA
B 1300-SG-006
10 kV 4.9 kV
1.73
6.6
5.9 kAkA 6.6 kV
5.9 kA
kA
±
R R
± ±
R
R R
± ±
Bus2
10 kV 6.6 kA
6.6 kV
5.9 kA
T 1300-TF-010 T-01
0.125 MVA T 1300-TF-010 T-02 ±
± ±
0.125 MVA
± ±
C 1300SE001-01-P01 C 1300SG007-01-P01
C 1300ER005A-P01 C 1300SG007-01-P02 C 1300ER005B-P01
Cable42 Cable43
C 1300SG007-02-P01 C 1300SG007-02-P02 ±
Bus26 Bus27
C 1300SG007-03-P01 0.48 kV 0.23 kV
±
C 1300SG007-03-P02
R
R
Load7 Load8 ±
B 1300-ER-005B
B 1300-ER-005A 10 kV 6.45 kA
10 kV 6.45 kA kV
6.4 kV R 5.857 kA
6.4
5.857 kA ±
±
R
1300-SG-007_1 1300-SG-007_2
10 kV 2.3 kA 10 kV 2.3 kA
2.3 kA kV
4.11
5.8 7
6.4 kA 1.8 kA
kV
5.817 kA
6.4
T 1300-ER-005A 1 kA
R R T 1300-ER-005B
± ±
1 MVA R
Bus4 1 MVA
±
10 kV 6.41 kA
kV
5.817 kA
6.4
T8 T6
0.125 MVA 0.125 MVA
B 1300-ER-005A LV C 1300SE001-02-P01 B 1300-ER-005B LV
± ±
0.48 kV 0.48 kV
±
C 1300ER006B-P01
Load5 C 1300ER006A-P01 Load6
1 MVA C 1300-DP-012 C 1300-DP-012A 1 MVA
Load10 Load9
± 0.125 MVA 0.125 MVA
C 1460-SG-001 C 1300ER006B-P02
T AGUA POTABLE
0.5 MVA
±
B 1300-ER-006A R R
±
T 1460-TL-001 T 1460-TL-002
0.8 MVA 0.8 MVA
B T 1300-ER-006A
0.48 kV T 1300-ER-006B
1 MVA
Load13
1 MVA
B T 1300-ER-006B
0.48 kV
B 1460-TL-001 ± B 1460-TL-002 ±
0.48 kV 0.48 kV
Load12
1 MVA
Load11
0.8 MVA
QUELLOPATA 66KV
66 kV 1.17 kA -69.7 deg
0 deg
0.17 kA -84 deg 0.17 kA -81.1 deg 1.5
0 kVkA
-72 .6
± ± deg
R R
T1 T2
20 MVA 20 MVA
621OSG001-P1 621OSG001-P2
±
±
R
R
0 deg
±
±
0 kV
QUELLOPATA 10KV
10 kV 2.94 kA -74.8 deg 2.94 kA -72 deg
2.48 kA -82.3 deg 8.34
kA -76
.1 deg
Open ±
±
±
±
±
R R
± ± ± ± ± R R
R
±
±
R
R R
R R 10 kV C 6310TL001-P
R
±
±
±
R ±
B 6310TL001-P 8.24 kA -75.4 deg
R R ± ± ±
R
R
±
R ±
±
R R 8.2 0 deg
±
±
R
±
R ±
R
R 0 kV
4 kA
R -75 .4 deg
± ± T10 T12
R
R
8.34 kA -76.1 deg 0.5 MVA 0.13 MVA
6320TD001-P
0 deg
0 kV
6220TL001A-P1/P2 6220TL003-P 6220TL004-P deg
10 kV 8.24 kA -75.2 0deg 8.34 kA -76.1 deg
6220TL001B-P 6220TL002-P Bus131 0 kV 6320TD005-P
6320TD003-P 6320TD004-P 10 kV 8.34 kA -76.1 deg
6220TL005-P 8.2 4
6320TD002-P Bus158
RESERVA 1 8.34 kA -76.1 deg kA -75 8.34 B 6210-DP-001A B 6210-DP-001B
0 MVA kA -76 0.48 kV 0.23 kV
6220-TL-001A. .2 deg .1
6220-TL-003 6220-TL-004 deg
10 MVA 6220-TL-002 2500 kVA 6320-TD-004 6320-TD-005
6220-TL-001B 2.5 MVA 2 MVA 6320-TD-003 1600 kVA 10 kV 4 kA -63.1 deg
Bus161
2.5 MVA 6220-TL-005 6320-TD-001 6320-TD-002 1600 kVA 1600 kVA ±
0 deg
6220TLO12B-P 6220TL012AC-P Load2 Load1
1600 kVA 1600 kVA ±
R 40 kA
kV 4 kA -63.1 deg 8.34 kA -76.1 deg C 1300LP001-P C 6210XC001-P C 1300LP002-P 0.5 MVA 0.13 MVA
±
±
1000 kVA ±
R
-63 .1
±
±
Load1-1 0 kV
±
deg 3.6
0 kV9 kA 3 kA -44
R
630 kVA -59.5
1300-TF-008 6220DP012A-P 6220DP012C-P
6220-TL-015 .4 deg
2130MC006-P deg 500 kVA
±
6220DP012B-P C 1300SG002_P01
±
± 500 kVA Bus21 C 1300SG003_P4 ± ±
R
R ± Load2-1 10 kV 7.85 kA -75.1 deg ±
±
R R
deg R
R 0 kA -133.5 deg 800 kVA 7.8 0 R
± ±
0 kV
5 kA
R -75.1
deg
±
6220-DP-012A 6220-DP-012B 6220-DP-012C
1.5 kA -23.3 deg 1.5 kA -23.3 deg CHANCADORA Y AGUA FRESCA 400 kVA 400 kVA 400 kVA
1000 kVA CAMPAMENTO ZICSA BOCAMINA 4300
500 kVA 500 kVA
± ±
±
± ±
250 kVA
MOLINO DE BOLAS MOTOR 2 MOLINO SAG TABLERO DEL SISTEMA SER 250 kVA
MOLINO DE BOLAS MOTOR 1 2250 kW T 1300_TF_003
2250 kW 2250 kW 10000 kVA 6212-SE-005 1.45 kA -23.4 deg 6212-SE-002 ± ±
T 1300_TF_002 ± 1 MVA
45 kVA 250 kVA 1 MVA ±
± R
3950-DP-007 PTAR
250 kVA 45 kVA Load4
Load3 1 MVA
1 MVA
R
B 1300-SG-006_2
10 kV
4.51 kA -66.5 deg 2.12 kA -75.4 deg
B 1300-SG-006 deg
0kA 0 deg
10 kV 4.51 kA -66.5
02.12
6.6 kV
2
deg -75.4 deg 0 kA -143.5 deg 6.6
0 kV
2 kA
kA -69 -69 .3
R R .3 deg
±
deg
± ±
R
R R
± ±
Bus2
10 kV 6.62 kA -69.3 deg
6.6 0 deg
0 kV2 kA
T 1300-TF-010 T-01 -69.3
0.125 MVA T 1300-TF-010
deg T-02 ±
± ±
0.125 MVA
± ±
C 1300SE001-01-P01 C 1300SG007-01-P01
C 1300ER005A-P01 C 1300SG007-01-P02 C 1300ER005B-P01
Cable42 Cable43
C 1300SG007-02-P01 C 1300SG007-02-P02 ±
Bus26 Bus27
C 1300SG007-03-P01 0.48 kV 0.23 kV
±
C 1300SG007-03-P02
R
R
Load7 Load8 ±
B 1300-ER-005B
B 1300-ER-005A 10 kV 6.52 kA -68.6 deg
10 kV 6.52 kA -68.6 deg 0 deg
0 deg R 6.5
0 kV
2 kA
6.5
0 kV
2 kA ±
±
-68
-68.6 R .6 deg
deg 1300-SG-007_1 1300-SG-007_2
10 kV 2.33 kA -68.4 deg 10 kV 2.33 kA -68.4 deg
deg 0kAdeg
2.33 kA -68.46.5
4.16
0 kV
-68.4 deg 6.5 0 deg
0 kVkA deg
1.83 kA -68.4
T 1300-ER-005A kA -68 R R -68 .4 T 1300-ER-005B
.4 deg ± ±
deg
1 MVA R
Bus4 1 MVA
±
C 1300ER006B-P01
Load5 C 1300ER006A-P01 Load6
1 MVA C 1300-DP-012 C 1300-DP-012A 1 MVA
Load10 Load9
± 0.125 MVA 0.125 MVA
C 1460-SG-001 C 1300ER006B-P02
T AGUA POTABLE
0.5 MVA
±
B 1300-ER-006A R R
±
Load13
1 MVA
B T 1300-ER-006B
0.48 kV
B 1460-TL-001 ± B 1460-TL-002 ±
0.48 kV 0.48 kV
Load12
1 MVA
Load11
0.8 MVA