Q1 CARGA DEBIDA AL PRODUCTO
5 toneladas =5000kg=11023 lb
11023 lb BTU
Qα =m∗Cp1 ( tbs−tpc )= ∗0.68 ∗( 64.4−32 )=10119.11 BTU /hrs
24 hrs lb° k
11023 lb BTU
Q β=m∗Cl= ∗86.5 =39728.72 BTU /hrs
24 hrs lb
11023 lb BTU
Qγ =m∗Cp2 ( tpc−T )= ∗0.38 ∗( 32−10.4 ) =3769.86 BTU /hrs
24 hrs lb ° k
Q4 CARGA LATENTE VT= 44 M3/hrs caudal total en volumen de aire por infiltración
Kcal
Q4 =ρ AIRE∗VT∗∆ W∗590
kg
PARA LA CAMARA
T BS = T = 10.4°F= -12°C
HR% = 85%
W=1.1/1000
3
KG m /hr∗9.5−1.1 Kcal
Q4 =1.2 ∗44 ∗590
m3
1000 kg
Vcamara = 140 m3
Q AP= ρ AIRE∗Vinfil∗Cp AIRE∗(T ambiente −T almacenamiento )
fap
Vinfil=¿ Vcamara *
24 hrs
3
m ∗7.2 3
Vinfil=140 =42 m
24 hrs
KG kcal
∗(18−(−12))= 370.44 kcal
3
Q5=1.2 ∗42m ∗0.245
m
3
hr ° c hrs
12000 BTU
kcal hrs
Q5=370.44
hrs * kcal
3024
hrs
3
Vinfil 2=(44−42) m /hr
3
Vinfil 2=2 m /hr
KG 3 kcal
Q6=1.2 ∗2 m ∗0.245 ∗(18−(−12))=
m 3
hr ° c
QT =1.1(53617.69+15000+6861.769+1838.41+1470+70)BTU / hrs
1 TON
QT =85863.679 BTU /hrs
12000 BTU /hrs
Q T =7.155 TON
P=1.3299 bar
T=-20°c
h=211.05 kj/kg
s=0.9332 kj/kgK
vg=0.1464
m3/kg
ESTADO 2 VAPOR SOBRECALENTADO PARA
P=12 BAR
s=0.9332 kj/kgK
12 bar S T h
0,9164 50 275
0,9332 54,62 281,03
0,9527 60 287,44
Tenemos
S=0,9332 KJ/KG k
P=12 bar
T= 54,62 °C
h=281,03 kj/kg
P=12 bar
T= 46,32 °C
h=112,76 kj/kg
P=1,3299 bar
T=-20 °C
h=115,76 kj/kg
Table resumen
CAP=m∗( h 1−h 4 )
v adm 3 m3 /hr
m= =
v 1 0.1464 m3 /hr
m3
m=20.5 =0.00569m 3/s
hr
CAP=0.00569 m3 /s∗( 211.03−115.76 ) kj/ kg
CAP=0.5423 kwatt
Potencia del compressor
Wc=m ( h 2−h 1 )
Wc=0.00569m 3/s ( 281.03−211.05 ) kj/kg
Wc=0.398 kwatt
COP
COP=1.36