Está en la página 1de 9

UNIVERSIDAD MAYOR DE SAN ANDRÉS

FACULTAD DE INGENIERÍA
INGENIERÍA MECÁNICA Y
ELECTROMECÁNICA
REFRIGERACION Y AIRE
ACONDICIONADO MEC 450

SOLUCIONARÍO DEL PRIMER PARCIAL PARCIAL

INTEGRANTE:

UNIV, FLORES MACHICADO LIMBER


RAMIRO

DOCENTE:
ING. MARCELO VASQUEZ
VILLAMOR
INTENSIVO INVIERNO 2022

LA PAZ – BOLIVIA
Q1 CARGA DEBIDA AL PRODUCTO

Primero asumiremos que el sistema trabaja a 24 hrs

5 toneladas =5000kg=11023 lb
11023 lb BTU
Qα =m∗Cp1 ( tbs−tpc )= ∗0.68 ∗( 64.4−32 )=10119.11 BTU /hrs
24 hrs lb° k

11023 lb BTU
Q β=m∗Cl= ∗86.5 =39728.72 BTU /hrs
24 hrs lb
11023 lb BTU
Qγ =m∗Cp2 ( tpc−T )= ∗0.38 ∗( 32−10.4 ) =3769.86 BTU /hrs
24 hrs lb ° k

Q1=( 10119.11+39728.72+3769.86 ) BTU /hrs=53617.69 BTU /hrs

Q1=53617.69 BTU /hrs

Q2 CARGA DEBIDA A LA TRASMISIÓN DE CALOR

Q2=15000 BTU /hrs

Q3 DEBIDA A PERSONAS E ILUMINACIÓN ES EL 10% DE LAS ANTERIORES


Q3=0.1 ( 53617.69+15000 ) BTU /hrs

Q3=6861.769 BTU /hrs

Q4 CARGA LATENTE VT= 44 M3/hrs caudal total en volumen de aire por infiltración

Kcal
Q4 =ρ AIRE∗VT∗∆ W∗590
kg

TBS = 64.4°F= 18°C

TBH = 59°F = 15°C

DE LA CARTA PSICOMETRICA TENEMOS W=9.1/1000

PARA LA CAMARA

T BS = T = 10.4°F= -12°C

HR% = 85%
W=1.1/1000
3
KG m /hr∗9.5−1.1 Kcal
Q4 =1.2 ∗44 ∗590
m3
1000 kg

kcal 12000 BTU



hr hrs
Q4 =261.7 =1838.41 BTU /hrs
kcal
3024
hrs

Q4 =1838.41 BTU /hrs

Q5 CARGA POR INFILTRACIÓN (APERTURA DE PUERTAS )

Vcamara = 140 m3
Q AP= ρ AIRE∗Vinfil∗Cp AIRE∗(T ambiente −T almacenamiento )
fap
Vinfil=¿ Vcamara *
24 hrs

3
m ∗7.2 3
Vinfil=140 =42 m
24 hrs
KG kcal
∗(18−(−12))= 370.44 kcal
3
Q5=1.2 ∗42m ∗0.245
m
3
hr ° c hrs

12000 BTU
kcal hrs
Q5=370.44
hrs * kcal
3024
hrs

Q 5=1470 BTU /hrs

Q6 CARGA POR INFILTRACIÓN (grietas y ranuras )

Q AP= ρ AIRE∗Vinfil∗Cp AIRE∗(T ambiente −T almacenamiento )


Vt =Vinfil 1+Vinfil 2
Vinfil 2=Vt−Vinfil 1

3
Vinfil 2=(44−42) m /hr

3
Vinfil 2=2 m /hr
KG 3 kcal
Q6=1.2 ∗2 m ∗0.245 ∗(18−(−12))=
m 3
hr ° c

kcal 12000 BTU



hrs hrs
Q6=17.6
kcal
3024
hrs
Q 6=70 BTU /hrs

QT =1.1(53617.69+15000+6861.769+1838.41+1470+70)BTU / hrs

1 TON
QT =85863.679 BTU /hrs
12000 BTU /hrs
Q T =7.155 TON

TON∗3024 kcal /hr


QT =7.155
1 TON

Estado 1 (vapor saturado)

P=1.3299 bar
T=-20°c
h=211.05 kj/kg
s=0.9332 kj/kgK
vg=0.1464
m3/kg
ESTADO 2 VAPOR SOBRECALENTADO PARA

P=12 BAR

s=0.9332 kj/kgK

12 bar S T h
0,9164 50 275
0,9332 54,62 281,03
0,9527 60 287,44
Tenemos

S=0,9332 KJ/KG k
P=12 bar
T= 54,62 °C
h=281,03 kj/kg

Estado 3 (liquid saturado )

P=12 bar
T= 46,32 °C
h=112,76 kj/kg

Estado 4 (mescla vapor –liquido)

P=1,3299 bar
T=-20 °C
h=115,76 kj/kg

Table resumen

punto p (bar) T( °C) h(kj/kg)


1 1,3299 -20 211,05
2 12 54,32 281,03
3 12 46,32 115,76
4 1,3299 -20 115,76
Capacidad del Sistema

CAP=m∗( h 1−h 4 )
v adm 3 m3 /hr
m= =
v 1 0.1464 m3 /hr

m3
m=20.5 =0.00569m 3/s
hr
CAP=0.00569 m3 /s∗( 211.03−115.76 ) kj/ kg
CAP=0.5423 kwatt
Potencia del compressor

Wc=m ( h 2−h 1 )
Wc=0.00569m 3/s ( 281.03−211.05 ) kj/kg
Wc=0.398 kwatt
COP

CAP 0.5423 kwatt


COP= =
Wc 0.398 kwatt

COP=1.36