CÁLCULOS JUSTIFICATIVOS
V = K x I x L x 10-3.
Donde:
Cuadro N° 01
RESISTENCIA RESISTENCIA
RESISTENCIA
DEL DEL REACTANCIA
DEL CAPACIDAD DE
CONDUCTOR DE CONDUCTOR INDUCTIVA
FORMACION CONDUCTOR DE FACTORES DE CAIDA DE TENSION CORRIENTE
ALUMBRADO NEUTRO (Ohm/km)
FASE A 40°C (Amp)
PUBLICO (Ohm/km)
(Ohm/km)
(Ohm/km)
Cond. Cond.
A 20°C A 40°C A 20°C A 40°C A 20°C A 40°C XL (3Ø) XL (1Ø) K(380-220) K(440-220) K(220AP)
Fase A.P.
2x25+16/25 1,200 1,285 1,910 2,045 1,380 1,478 0,093 0,109 3,538 1,610 3,272 83 64
2x16+16/25 1,910 2,045 1,910 2,045 1,380 1,478 0,096 0,096 3,538 2,480 3,272 64 64
POTENCIA INTENSID
VANO SECCION F.C.T. CAIDA DE TENSION
NODO LOTES CARGAS ESPECIALES TOTAL AD
LOTES Σ LOTES F.S. KW. C.E. Σ C.E. F.S. KW. ( KW. ) ( AMP. ) (M. ) ( MM2. ) (K) ΔV %ΔV ΣΔ %ΣΔ
S.E. 0 38 0.5 7.60 0 3 1.0 1.50 9.10 20.68 3.00 2x16+1x16/25P 2.480 0.15 0.03% 0.15 0.03%
1 0 15 0.5 3.00 0 0 1.0 0.00 3.00 6.82 30.21 2x16+1x16/25P 2.480 0.51 0.12% 0.66 0.15%
2 0 15 0.5 3.00 0 0 1.0 0.00 3.00 6.82 38.90 2x16+1x16/25P 2.480 0.66 0.15% 1.32 0.30%
3 0 15 0.5 3.00 0 0 1.0 0.00 3.00 6.82 34.00 2x16+1x16/25P 2.480 0.57 0.13% 1.90 0.43%
4 0 14 0.5 2.80 0 0 1.0 0.00 2.80 6.36 25.70 2x16+1x16/25P 2.480 0.41 0.09% 2.30 0.52%
5 2 14 0.5 2.80 0 0 1.0 0.00 2.80 6.36 64.76 2x16+1x16/25P 2.480 1.02 0.23% 3.32 0.76%
6 0 12 0.5 2.40 0 0 1.0 0.00 2.40 5.45 39.70 2x16+1x16/25P 2.480 0.54 0.12% 3.86 0.88%
7 0 12 0.5 2.40 0 0 1.0 0.00 2.40 5.45 39.70 2x16+1x16/25P 2.480 0.54 0.12% 4.40 1.00%
8 0 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 49.10 2x16+1x16/25P 2.480 0.39 0.09% 4.79 1.09%
9 0 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 100.93 2x16+1x16/25P 2.480 0.80 0.18% 5.58 1.27%
10 0 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 32.55 2x16+1x16/25P 2.480 0.11 0.03% 5.69 1.29%
11 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 57.50 2x16+1x16/25P 2.480 0.19 0.04% 5.89 1.34%
12 0 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 35.38 2x16+1x16/25P 2.480 0.08 0.02% 5.97 1.36%
13 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 41.23 2x16+1x16/25P 2.480 0.09 0.02% 6.06 1.38%
14 0 0 0.5 0.00 0 0 1.0 0.00 0.00 0.00 35.00 2x16+1x16/25P 2.480 0.00 0.00% 6.06 1.38%
15 0 0 0.5 0.00 0 0 1.0 0.00 0.00 0.00 40.00 2x16+1x16/25P 2.480 0.00 0.00% 6.06 1.38%
16 2 21 0.5 4.20 0 0 1.0 0.00 4.20 9.55 37.00 2x16+1x16/25P 2.480 0.88 0.20% 1.54 0.35%
17 0 19 0.5 3.80 0 0 1.0 0.00 3.80 8.64 27.40 2x16+1x16/25P 2.480 0.59 0.13% 2.13 0.48%
18 1 19 0.5 3.80 0 0 1.0 0.00 3.80 8.64 40.00 2x16+1x16/25P 2.480 0.86 0.19% 2.98 0.68%
19 1 15 0.5 3.00 0 0 1.0 0.00 3.00 6.82 41.05 2x16+1x16/25P 2.480 0.69 0.16% 3.68 0.84%
20 3 14 0.5 2.80 0 0 1.0 0.00 2.80 6.36 49.24 2x16+1x16/25P 2.480 0.78 0.18% 4.46 1.01%
21 1 11 0.5 2.20 0 0 1.0 0.00 2.20 5.00 42.20 2x16+1x16/25P 2.480 0.52 0.12% 4.98 1.13%
22 0 10 0.5 2.00 0 0 1.0 0.00 2.00 4.55 56.43 2x16+1x16/25P 2.480 0.64 0.14% 5.61 1.28%
23 0 10 0.5 2.00 0 0 1.0 0.00 2.00 4.55 32.25 2x16+1x16/25P 2.480 0.36 0.08% 5.98 1.36%
24 1 10 0.5 2.00 0 0 1.0 0.00 2.00 4.55 89.00 2x16+1x16/25P 2.480 1.00 0.23% 6.98 1.59%
25 1 9 0.5 1.80 0 0 1.0 0.00 1.80 4.09 50.00 2x16+1x16/25P 2.480 0.51 0.12% 7.49 1.70%
26 0 8 0.5 1.60 0 0 1.0 0.00 1.60 3.64 44.00 2x16+1x16/25P 2.480 0.40 0.09% 7.89 1.79%
27 1 8 0.5 1.60 0 0 1.0 0.00 1.60 3.64 34.00 2x16+1x16/25P 2.480 0.31 0.07% 8.19 1.86%
28 0 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 50.00 2x16+1x16/25P 2.480 0.39 0.09% 8.59 1.95%
29 1 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 42.00 2x16+1x16/25P 2.480 0.33 0.08% 8.92 2.03%
30 2 6 0.5 1.20 0 0 1.0 0.00 1.20 2.73 45.70 2x16+1x16/25P 2.480 0.31 0.07% 9.23 2.10%
31 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 71.00 1x16/25P 2.480 0.08 0.02% 9.31 2.12%
32 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 114.00 1x16/25P 2.480 0.13 0.03% 9.44 2.14%
3.1 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 25.00 1x16/25P 2.480 0.03 0.01% 1.93 0.44%
7.1 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 15.00 2x16/25P 2.480 0.05 0.01% 4.45 1.01%
7.2 0 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 49.37 2x16/25P 2.480 0.11 0.03% 4.56 1.04%
7.3 1 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 64.13 2x16/25P 2.480 0.14 0.03% 4.71 1.07%
7.4 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 41.76 2x16/25P 2.480 0.05 0.01% 4.75 1.08%
7.5 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 38.47 2x16/25P 2.480 0.04 0.01% 4.80 1.09%
POTENCIA INTENSID
VANO SECCION F.C.T. CAIDA DE TENSION
NODO LOTES CARGAS ESPECIALES TOTAL AD
LOTES Σ LOTES F.S. KW. C.E. Σ C.E. F.S. KW. ( KW. ) ( AMP. ) (M. ) ( MM2. ) (K) ΔV %ΔV ΣΔ %ΣΔ
7.6 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 54.60 2x16/25P 2.480 0.12 0.03% 4.57 1.04%
0.00
9.1 0 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 64.47 2x16/25P 2.480 0.22 0.05% 5.80 1.32%
9.2 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 86.28 2x16/25P 2.480 0.29 0.07% 6.09 1.38%
9.3 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 48.50 2x16/25P 2.480 0.11 0.02% 6.20 1.41%
9.4 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 72.50 2x16/25P 2.480 0.08 0.02% 10.86 2.47%
16.1 1 2 0.5 0.40 0 1 1.0 0.50 0.90 2.05 9.00 2x16+1x16/25P 2.480 0.05 0.01% 1.59 0.36%
16.2 1 1 0.5 0.20 1 1 1.0 0.50 0.70 1.59 29.85 2x16+1x16/25P 2.480 0.12 0.03% 1.70 0.39%
16.3 0 0 0.5 0.00 0 2 1.0 1.00 1.00 2.27 10.00 2x16+1x16/25P 2.480 0.06 0.01% 1.60 0.36%
16.4 0 0 0.5 0.00 2 2 1.0 1.00 1.00 2.27 21.50 2x16+1x16/25P 2.480 0.12 0.03% 1.72 0.39%
18.1 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 41.05 2x16+1x16/25P 2.480 0.09 0.02% 0.09 0.02%
18.2 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 22.00 2x16+1x16/25P 2.480 0.02 0.01% 0.02 0.01%
30.1 0 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 16.00 1x16/25P 2.480 0.05 0.01% 9.28 2.11%
30.2 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 45.00 1x16/25P 2.480 0.15 0.03% 9.43 2.14%
30.3 1 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 47.70 1x16/25P 2.480 0.11 0.02% 9.54 2.17%
30.4 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 36.20 1x16/25P 2.480 0.04 0.01% 9.58 2.18%
NOTA:
Calificación Eléctrica:
Vivienda Unifilar : 400 watts/lote
Carga Especial : 500 watts/lote
Sistema : 440/220 V.
Cos Ø : 1.0
Tolerancia admitida en el punto de entrega al Consumidor es hasta 7% de la Tensión Nominal, para Zonas Rurales, según el Nuevo Código Nacional de
Electricidad (Norma Técnica de Calidad de Servicio Eléctrico)
POTENCIA INTENSID
VANO SECCION F.C.T. CAIDA DE TENSION
NODO LOTES CARGAS ESPECIALES TOTAL AD
LOTES Σ LOTES F.S. KW. C.E. Σ C.E. F.S. KW. ( KW. ) ( AMP. ) (M. ) ( MM2. ) (K) ΔV %ΔV ΣΔ %ΣΔ
S.E. 0 52 0.5 10.40 0 2 1.0 1.00 11.40 25.91 3.00 2x16+1x16/25P 2.480 0.19 0.04% 0.19 0.04%
1 0 52 0.5 10.40 0 2 1.0 1.00 11.40 25.91 30.21 2x16+1x16/25P 2.480 1.94 0.44% 2.13 0.48%
2 0 52 0.5 10.40 1 2 1.0 1.00 11.40 25.91 32.07 2x16+1x16/25P 2.480 2.06 0.47% 4.19 0.95%
3 1 52 0.5 10.40 1 1 1.0 0.50 10.90 24.77 37.90 2x16+1x16/25P 2.480 2.33 0.53% 6.52 1.48%
4 1 51 0.5 10.20 0 0 1.0 0.00 10.20 23.18 45.00 2x16+1x16/25P 2.480 2.59 0.59% 9.11 2.07%
5 0 31 0.5 6.20 0 0 1.0 0.00 6.20 14.09 50.00 2x16+1x16/25P 2.480 1.75 0.40% 10.86 2.47%
6 0 31 0.5 6.20 0 0 1.0 0.00 6.20 14.09 46.20 2x16+1x16/25P 2.480 1.61 0.37% 12.47 2.83%
7 1 28 0.5 5.60 0 0 1.0 0.00 5.60 12.73 41.50 2x16+1x16/25P 2.480 1.31 0.30% 13.78 3.13%
8 1 27 0.5 5.40 0 0 1.0 0.00 5.40 12.27 43.30 2x16+1x16/25P 2.480 1.32 0.30% 15.10 3.43%
9 1 26 0.5 5.20 0 0 1.0 0.00 5.20 11.82 46.90 2x16+1x16/25P 2.480 1.37 0.31% 16.47 3.74%
10 0 25 0.5 5.00 0 0 1.0 0.00 5.00 11.36 47.50 2x16+1x16/25P 2.480 1.34 0.30% 17.81 4.05%
11 1 25 0.5 5.00 0 0 1.0 0.00 5.00 11.36 57.40 2x16+1x16/25P 2.480 1.62 0.37% 19.43 4.42%
12 0 24 0.5 4.80 0 0 1.0 0.00 4.80 10.91 44.40 2x16+1x16/25P 2.480 1.20 0.27% 20.63 4.69%
13 0 24 0.5 4.80 0 0 1.0 0.00 4.80 10.91 42.70 2x16+1x16/25P 2.480 1.16 0.26% 21.79 4.95%
14 2 20 0.5 4.00 0 0 1.0 0.00 4.00 9.09 41.70 2x16+1x16/25P 2.480 0.94 0.21% 22.73 5.17%
15 1 18 0.5 3.60 0 0 1.0 0.00 3.60 8.18 31.50 2x16+1x16/25P 2.480 0.64 0.15% 23.37 5.31%
16 2 15 0.5 3.00 0 0 1.0 0.00 3.00 6.82 93.23 2x16+1x16/25P 2.480 1.58 0.36% 24.94 5.67%
17 0 9 0.5 1.80 0 0 1.0 0.00 1.80 4.09 55.40 2x16+1x16/25P 2.480 0.56 0.13% 25.50 5.80%
18 0 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 80.80 2x16+1x16/25P 2.480 0.64 0.14% 26.14 5.94%
19 1 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 31.70 2x16+1x16/25P 2.480 0.25 0.06% 26.39 6.00%
20 0 6 0.5 1.20 0 0 1.0 0.00 1.20 2.73 30.30 2x16+1x16/25P 2.480 0.20 0.05% 26.60 6.04%
21 1 5 0.5 1.00 0 0 1.0 0.00 1.00 2.27 56.20 2x16/25P 2.480 0.32 0.07% 26.91 6.12%
22 0 4 0.5 0.80 0 0 1.0 0.00 0.80 1.82 50.00 2x16/25P 2.480 0.23 0.05% 27.14 6.17%
23 1 4 0.5 0.80 0 0 1.0 0.00 0.80 1.82 52.60 2x16/25P 2.480 0.24 0.05% 27.38 6.22%
24 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 47.10 2x16/25P 2.480 0.16 0.04% 27.54 6.26%
25 1 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 36.30 2x16/25P 2.480 0.08 0.02% 27.62 6.28%
26 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 71.95 2x16/25P 2.480 0.08 0.02% 27.70 6.30%
4.1 1 19 0.5 3.80 0 0 1.0 0.00 3.80 8.64 100.99 2x16+1x16/25P 2.480 2.16 0.49% 29.87 6.79%
4.2 2 18 0.5 3.60 0 0 1.0 0.00 3.60 8.18 54.26 2x16+1x16/25P 2.480 1.10 0.25% 1.29 0.29%
4.3 0 16 0.5 3.20 0 0 1.0 0.00 3.20 7.27 56.20 2x16+1x16/25P 2.480 1.01 0.23% 2.31 0.52%
4.4 1 16 0.5 3.20 0 0 1.0 0.00 3.20 7.27 34.00 2x16+1x16/25P 2.480 0.61 0.14% 2.92 0.66%
4.5 3 15 0.5 3.00 0 0 1.0 0.00 3.00 6.82 58.00 2x16+1x16/25P 2.480 0.98 0.22% 3.90 0.89%
4.6 0 12 0.5 2.40 0 0 1.0 0.00 2.40 5.45 27.40 2x16+1x16/25P 2.480 0.37 0.08% 3.29 0.75%
4.7 1 12 0.5 2.40 0 0 1.0 0.00 2.40 5.45 41.40 2x16+1x16/25P 2.480 0.56 0.13% 3.85 0.88%
4.8 2 11 0.5 2.20 0 0 1.0 0.00 2.20 5.00 39.10 2x16+1x16/25P 2.480 0.48 0.11% 14.27 3.24%
4.9 0 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 49.90 2x16+1x16/25P 2.480 0.39 0.09% 22.18 5.04%
4.10 1 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 50.10 2x16+1x16/25P 2.480 0.40 0.09% 22.58 5.13%
4.11 0 6 0.5 1.20 0 0 1.0 0.00 1.20 2.73 53.00 2x16+1x16/25P 2.480 0.36 0.08% 22.93 5.21%
4.12 0 5 0.5 1.00 0 0 1.0 0.00 1.00 2.27 31.00 2x16+1x16/25P 2.480 0.17 0.04% 23.11 5.25%
4.13 1 5 0.5 1.00 0 0 1.0 0.00 1.00 2.27 62.65 2x16+1x16/25P 2.480 0.35 0.08% 23.46 5.33%
4.14 0 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 44.20 2x16+1x16/25P 2.480 0.15 0.03% 22.73 5.16%
4.15 0 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 44.20 2x16+1x16/25P 2.480 0.15 0.03% 22.87 5.20%
4.16 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 45.00 2x16+1x16/25P 2.480 0.15 0.03% 23.03 5.23%
4.17 0 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 44.60 2x16+1x16/25P 2.480 0.10 0.02% 23.13 5.26%
4.18 0 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 38.10 2x16+1x16/25P 2.480 0.09 0.02% 23.21 5.28%
4.19 1 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 35.60 2x16+1x16/25P 2.480 0.08 0.02% 27.22 6.19%
4.20 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 34.60 1x16/25P 2.480 0.04 0.01% 27.26 6.20%
4.21 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 47.00 1x16/25P 2.480 0.05 0.01% 27.31 6.21%
POTENCIA INTENSID
VANO SECCION F.C.T. CAIDA DE TENSION
NODO LOTES CARGAS ESPECIALES TOTAL AD
LOTES Σ LOTES F.S. KW. C.E. Σ C.E. F.S. KW. ( KW. ) ( AMP. ) (M. ) ( MM2. ) (K) ΔV %ΔV ΣΔ %ΣΔ
4.8.1 1 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 18.00 1x16/25P 2.480 0.04 0.01% 14.31 3.25%
4.8.2 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 47.00 1x16/25P 2.480 0.05 0.01% 14.36 3.26%
4.11.1 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 37.00 1x16/25P 2.480 0.04 0.01% 22.98 5.22%
4.13.1 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 33.30 1x16/25P 2.480 0.04 0.01% 23.50 5.34%
6.1 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 34.30 2x16+1x16/25P 2.480 0.12 0.03% 12.59 2.86%
6.2 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 36.70 2x16+1x16/25P 2.480 0.08 0.02% 12.67 2.88%
13.1 1 4 0.5 0.80 0 0 1.0 0.00 0.80 1.82 13.32 2x16/25P 2.480 0.06 0.01% 21.85 4.97%
13.2 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 34.00 2x16/25P 2.480 0.11 0.03% 21.96 4.99%
13.3 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 33.23 2x16/25P 2.480 0.07 0.02% 22.04 5.01%
15.1 0 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 21.80 1x16/25P 2.480 0.05 0.01% 23.42 5.32%
15.2 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 124.90 1x16/25P 2.480 0.28 0.06% 23.70 5.39%
16.1 1 4 0.5 0.80 0 0 1.0 0.00 0.80 1.82 65.00 1x16/25P 2.480 0.29 0.07% 25.24 5.74%
16.2 0 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 47.10 1x16/25P 2.480 0.16 0.04% 25.40 5.77%
16.3 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 48.00 1x16/25P 2.480 0.16 0.04% 25.56 5.81%
16.4 1 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 104.79 1x16/25P 2.480 0.24 0.05% 25.79 5.86%
16.5 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 26.17 1x16/25P 2.480 0.03 0.01% 27.29 6.20%
16.6 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 50.00 1x16/25P 2.480 0.06 0.01% 27.34 6.21%
16.7 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 30.00 1x16/25P 2.480 0.03 0.01% 27.38 6.22%
17.1 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 28.00 1x16/25P 2.480 0.06 0.01% 25.57 5.81%
20.1 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 28.00 1x16/25P 2.480 0.03 0.01% 26.63 6.05%
NOTA:
Calificación Eléctrica:
Vivienda Unifilar : 400 watts/lote
Carga Especial : 500 watts/lote
Sistema : 440/220 V.
Cos Ø : 1.0
Tolerancia admitida en el punto de entrega al Consumidor es hasta 7% de la Tensión Nominal, para Zonas Rurales, según el Nuevo Código Nacional de
Electricidad (Norma Técnica de Calidad de Servicio Eléctrico)
POTENCIA INTENSID
VANO SECCION F.C.T. CAIDA DE TENSION
NODO LOTES CARGAS ESPECIALES TOTAL AD
LOTES Σ LOTES F.S. KW. C.E. Σ C.E. F.S. KW. ( KW. ) ( AMP. ) (M. ) ( MM2. ) (K) ΔV %ΔV ΣΔ %ΣΔ
S.E. 0 18 0.5 3.60 0 3 1.0 1.50 5.10 11.59 3.00 2x16+1x16/25P 2.480 0.09 0.02% 0.09 0.02%
1 0 18 0.5 3.60 0 3 1.0 1.50 5.10 11.59 42.00 2x16+1x16/25P 2.480 1.21 0.27% 1.29 0.29%
2 2 8 0.5 1.60 0 0 1.0 0.00 1.60 3.64 64.10 2x16+1x16/25P 2.480 0.58 0.13% 1.87 0.43%
3 1 6 0.5 1.20 0 0 1.0 0.00 1.20 2.73 37.90 2x16+1x16/25P 2.480 0.26 0.06% 2.13 0.48%
4 0 4 0.5 0.80 0 0 1.0 0.00 0.80 1.82 40.00 2x16+1x16/25P 2.480 0.18 0.04% 2.31 0.52%
5 0 4 0.5 0.80 0 0 1.0 0.00 0.80 1.82 35.00 2x16+1x16/25P 2.480 0.16 0.04% 2.47 0.56%
6 0 4 0.5 0.80 0 0 1.0 0.00 0.80 1.82 64.60 2x16+1x16/25P 2.480 0.29 0.07% 2.76 0.63%
7 1 4 0.5 0.80 0 0 1.0 0.00 0.80 1.82 22.70 2x16/25P 2.480 0.10 0.02% 2.86 0.65%
8 2 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 51.00 2x16/25P 2.480 0.17 0.04% 3.03 0.69%
9 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 28.00 2x16/25P 2.480 0.03 0.01% 3.06 0.70%
10 0 10 0.5 2.00 0 3 1.0 1.50 3.50 7.95 8.00 2x16+1x16/25P 2.480 0.16 0.04% 3.32 0.76%
11 0 10 0.5 2.00 1 1 1.0 0.50 2.50 5.68 49.80 2x16+1x16/25P 2.480 0.70 0.16% 4.02 0.91%
12 1 10 0.5 2.00 0 0 1.0 0.00 2.00 4.55 36.00 2x16+1x16/25P 2.480 0.41 0.09% 4.43 1.01%
13 1 9 0.5 1.80 0 0 1.0 0.00 1.80 4.09 38.34 2x16+1x16/25P 2.480 0.39 0.09% 4.82 1.10%
14 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 58.00 2x16+1x16/25P 2.480 0.07 0.01% 4.88 1.11%
15 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 42.00 2x16+1x16/25P 2.480 0.05 0.01% 4.93 1.12%
16 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 33.98 2x16+1x16/25P 2.480 0.04 0.01% 1.33 0.30%
17 1 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 19.17 2x16+1x16/25P 2.480 0.15 0.03% 4.97 1.13%
18 1 4 0.5 0.80 0 0 1.0 0.00 0.80 1.82 44.83 2x16+1x16/25P 2.480 0.20 0.05% 5.17 1.18%
19 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 53.60 2x16+1x16/25P 2.480 0.18 0.04% 5.35 1.22%
20 0 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 35.00 1x16/25P 2.480 0.08 0.02% 5.43 1.23%
21 1 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 80.00 1x16/25P 2.480 0.18 0.04% 5.61 1.28%
22 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 33.33 1x16/25P 2.480 0.04 0.01% 5.65 1.28%
23 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 33.33 1x16/25P 2.480 0.04 0.01% 5.69 1.29%
24 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 33.33 1x16/25P 2.480 0.04 0.01% 5.73 1.30%
1.1 0 0 0.5 0.00 0 0 1.0 0.00 0.00 0.00 32.00 2x16+1x16/25P 2.480 0.00 0.00% 1.29 0.29%
3.1 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 16.64 1x16/25P 2.480 0.02 0.00% 2.15 0.49%
3.2 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 38.00 1x16/25P 2.480 0.04 0.01% 2.19 0.50%
10.1 0 0 0.5 0.00 2 2 1.0 1.00 1.00 2.27 24.50 2x16+1x16/25P 2.480 0.14 0.03% 3.46 0.79%
14.1 0 0 0.5 0.00 0 0 1.0 0.00 0.00 0.00 36.50 2x16+1x16/25P 2.480 0.00 0.00% 4.88 1.11%
17.1 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 43.00 2x16+1x16/25P 2.480 0.10 0.02% 7.93 1.80%
NOTA:
Calificación Eléctrica:
Vivienda Unifilar : 400 watts/lote
Carga Especial : 500 watts/lote
Sistema : 440/220 V.
Cos Ø : 1.0
Tolerancia admitida en el punto de entrega al Consumidor es hasta 7% de la Tensión Nominal, para Zonas Rurales, según el Nuevo Código Nacional de
Electricidad (Norma Técnica de Calidad de Servicio Eléctrico)
POTENCIA INTENSID
VANO SECCION F.C.T. CAIDA DE TENSION
NODO LOTES CARGAS ESPECIALES TOTAL AD
LOTES Σ LOTES F.S. KW. C.E. Σ C.E. F.S. KW. ( KW. ) ( AMP. ) (M. ) ( MM2. ) (K) ΔV %ΔV ΣΔ %ΣΔ
S.E. 0 22 0.5 4.40 1 1 1.0 0.50 4.90 11.14 3.00 2x16+1x16/25P 2.480 0.08 0.02% 0.08 0.02%
1 1 22 0.5 4.40 0 0 1.0 0.00 4.40 10.00 13.10 2x16+1x16/25P 2.480 0.32 0.07% 0.41 0.09%
2 2 19 0.5 3.80 0 0 1.0 0.00 3.80 8.64 22.90 2x16+1x16/25P 2.480 0.49 0.11% 0.90 0.20%
3 0 14 0.5 2.80 0 0 1.0 0.00 2.80 6.36 13.40 2x16+1x16/25P 2.480 0.21 0.05% 1.11 0.25%
4 2 14 0.5 2.80 0 0 1.0 0.00 2.80 6.36 39.70 2x16+1x16/25P 2.480 0.63 0.14% 1.74 0.39%
5 1 12 0.5 2.40 0 0 1.0 0.00 2.40 5.45 46.20 2x16+1x16/25P 2.480 0.62 0.14% 2.36 0.54%
6 1 9 0.5 1.80 0 0 1.0 0.00 1.80 4.09 50.00 2x16+1x16/25P 2.480 0.51 0.12% 2.87 0.65%
7 0 8 0.5 1.60 0 0 1.0 0.00 1.60 3.64 49.00 2x16+1x16/25P 2.480 0.44 0.10% 3.31 0.75%
8 1 8 0.5 1.60 0 0 1.0 0.00 1.60 3.64 62.50 2x16/25P 2.480 0.56 0.13% 3.87 0.88%
9 0 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 62.50 2x16/25P 2.480 0.49 0.11% 4.37 0.99%
10 1 7 0.5 1.40 0 0 1.0 0.00 1.40 3.18 53.60 2x16/25P 2.480 0.42 0.10% 4.79 1.09%
11 1 6 0.5 1.20 0 0 1.0 0.00 1.20 2.73 54.50 2x16/25P 2.480 0.37 0.08% 5.16 1.17%
12 0 5 0.5 1.00 0 0 1.0 0.00 1.00 2.27 42.00 2x16/25P 2.480 0.24 0.05% 5.40 1.23%
13 0 5 0.5 1.00 0 0 1.0 0.00 1.00 2.27 45.19 2x16/25P 2.480 0.25 0.06% 5.65 1.28%
14 0 5 0.5 1.00 0 0 1.0 0.00 1.00 2.27 52.00 2x16/25P 2.480 0.29 0.07% 5.94 1.35%
15 0 5 0.5 1.00 0 0 1.0 0.00 1.00 2.27 52.30 2x16/25P 2.480 0.29 0.07% 6.24 1.42%
16 1 5 0.5 1.00 0 0 1.0 0.00 1.00 2.27 67.30 2x16/25P 2.480 0.38 0.09% 6.62 1.50%
17 1 4 0.5 0.80 0 0 1.0 0.00 0.80 1.82 48.70 2x16/25P 2.480 0.22 0.05% 6.84 1.55%
18 0 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 45.60 2x16/25P 2.480 0.15 0.04% 6.99 1.59%
19 0 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 55.00 2x16/25P 2.480 0.19 0.04% 7.18 1.63%
20 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 31.24 2x16/25P 2.480 0.11 0.02% 7.28 1.66%
21 0 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 40.85 1x16/25P 2.480 0.09 0.02% 7.37 1.68%
22 1 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 44.70 1x16/25P 2.480 0.10 0.02% 7.48 1.70%
23 0 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 30.00 1x16/25P 2.480 0.03 0.01% 7.51 1.71%
24 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 30.00 1x16/25P 2.480 0.03 0.01% 7.54 1.71%
1.1 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 42.20 2x16+1x16/25P 2.480 0.10 0.02% 0.50 0.11%
2.1 0 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 50.60 2x16/25P 2.480 0.17 0.04% 1.57 0.36%
2.2 0 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 59.20 2x16/25P 2.480 0.20 0.05% 0.28 0.06%
2.3 1 3 0.5 0.60 0 0 1.0 0.00 0.60 1.36 44.85 2x16/25P 2.480 0.15 0.03% 0.43 0.10%
2.4 1 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 38.00 1x16/25P 2.480 0.09 0.02% 0.52 0.12%
2.5 1 1 0.5 0.20 0 0 1.0 0.00 0.20 0.45 92.00 1x16/25P 2.480 0.10 0.02% 0.62 0.14%
10.1 2 2 0.5 0.40 0 0 1.0 0.00 0.40 0.91 35.00 1x16/25P 2.480 0.08 0.02% 4.87 1.11%
NOTA:
Calificación Eléctrica:
Vivienda Unifilar : 400 watts/lote
Carga Especial : 500 watts/lote
Sistema : 440/220 V.
Cos Ø : 1.0
Tolerancia admitida en el punto de entrega al Consumidor es hasta 7% de la Tensión Nominal, para Zonas Rurales, según el Nuevo Código Nacional de
Electricidad (Norma Técnica de Calidad de Servicio Eléctrico)
SERVICIO PARTICULAR
N° de Usuarios : 90
Factor de Simultaneidad (f.s.) : 0,5
Calificación Eléctrica (C.E.) : 0,4 kW/lote
N° de Cargas Especiales : 05
Factor de Simultaneidad (f.s.) : 1,0
Calificación Eléctrica (C.E.) : 0,5 kW/lote
N° de Usuarios : 38
Factor de Simultaneidad (f.s.) : 0,5
Calificación Eléctrica (C.E.) : 0,4 kW/lote
N° de Cargas Especiales : 06
Factor de Simultaneidad (f.s.) : 1,0
Calificación Eléctrica (C.E.) : 0,5 kW/lote
ALUMBRADO PUBLICO
De la fórmula:
Donde:
Donde:
PI : Punto de iluminación
CMAP : Consumo mensual de alumbrado público en kWh.
NHMAP : Número de horas mensuales del servicio de A.P. (horas/mes)
PPL : Potencia nominal promedio de la lámpara de A.P. en Watt.
Considerando que las horas de funcionamiento de las luminarias será con una
célula fotoeléctrica de operación mensual de NHMAP = 360 horas/mes
(proyectada para operar con un nuevo sistema)
En fórmula (1)
PI = 598,5x1000/(360x60) = 27,71
PI = 277,2x1000/(360x60) = 12,83
Presentamos Cálculos:
A NORMATIVIDAD
RD Nº 17-EM7DGE "ALUMBRADO DE VIA PUBLICAS EN AREAS RURALES"
RM Nº 074-2009-MEM/DM "FACTORES KALP PARA ALUMBRADO PUBLICO"
B CALCULOS
CMAP = KALP x UN
C ALCANCES
1.- PI debe ser redondeado al entero inferior en caso de ser decimal.
2.- PPL comprende las potencias nominles de la lámpara y de accesorios de encendido.
3.- El número de horas/dìa de AP deberá estar comprendido entre 8 y 12 horas.
4.- Para la distribución de los PI considerar:
i.- Plazas Principales o centro comunal de la localidad.
ii.- Vías públicas en el perimetro de las plazas principales.
iii.- Vías públicas importantes.
iv .- Areas restantes de la localidad.
D CONCLUSION:
El número de puntos de iluminación es de 27 unidades con lámparas de 50watts de Sodio
A NORMATIVIDAD
RD Nº 17-EM7DGE "ALUMBRADO DE VIA PUBLICAS EN AREAS RURALES"
RM Nº 074-2009-MEM/DM "FACTORES KALP PARA ALUMBRADO PUBLICO"
B CALCULOS
CMAP = KALP x UN
C ALCANCES
1.- PI debe ser redondeado al entero inferior en caso de ser decimal.
2.- PPL comprende las potencias nominles de la lámpara y de accesorios de encendido.
3.- El número de horas/dìa de AP deberá estar comprendido entre 8 y 12 horas.
4.- Para la distribución de los PI considerar:
i.- Plazas Principales o centro comunal de la localidad.
ii.- Vías públicas en el perimetro de las plazas principales.
iii.- Vías públicas importantes.
iv .- Areas restantes de la localidad.
D CONCLUSION:
El número de puntos de iluminación es de 12 unidades con lámparas de 50watts de Sodio
4.2.1. OBJETIVO
DIAM.
SECCIÓN DEL MASA MODULO DE
EXTERIOR COEFICIC.
FORMACIÓN CONDUCTOR TOTAL ELAST. DEL
TOTAL DE DILAT.
PORTANTE (N/m) PORTANTE
(mm)
Las hipótesis de estado para los cálculos mecánicos del conductor se definen
sobre la base de los factores meteorológicos.
Sobre la base de la Zonificación del territorio del Perú, definir las Hipótesis del
estado según el Código Nacional de Electricidad y SENAMHI; a continuación las
hipótesis base ha considerar para el cálculo:
Donde:
2 2 2 2
wr 1 d E wr 2 d E
2 2 2
22 { 2 + E (t2-t1) + 24 S δ 1 - 1} = 24 S
d : Vano en (m)
2
d E
2
M = 24 S ………………………..(1)
MxW
r 12
δ
N= 01 2 ……………………..(2)
P = MxWr2 ……………………….(3)
2
871,67.
o1 = 25 = 34,87 N/mm2
La fuerza del viento sobre el conductor está dada por la fórmula
SEGÚN LA HIPÓTESIS 2
Pv = kx V2 Sfx A
W r d2
f=
8 T 01
Donde:
Wr : Carga Unitaria N/m
d : Vano
To1 : Tiro Unitario (N)
Reemplazando datos:
2
(5 ,5581 N /m) xd
f= 8 x 871 ,67
SEGÙN LA HIPÒTESIS 1
Pv = 0
t2 = 20° C
Wr1 = Wr3 – Wc = 3,02 N/m
TEMPLADO HIPOTESIS I
MAXIMO ESFUERZO
ANALISIS DE LOS ESFUERZOS SEGÚN LA HIPOTESIS II
MAXIMA FLECHA
ANALISIS DE LOS ESFUERZOS SEGÚN LA HIPOTESIS III
TABLA DE FLECHA
I II III
VANO
FLECHA (m) FLECHA (m) FLECHA (m)
20 0,094 0,119 0,157
30 0,210 0,262 0,317
40 0,374 0,452 0,519
50 0,585 0,689 0,762
60 0,842 0,970 1,048
4.3.1. OBJETIVO
Estos cálculos tienen por objeto determinar las cargas mecánicas en los postes,
cables de retenidas y sus accesorios, de tal manera que en las condiciones, es
decir a temperatura mínima y máxima a velocidad de viento no se superen los
esfuerzos máximos previstos en el Código Nacional de Electricidad Suministro.
En su punto de aplicación Z.
Pv = k x V2Sf x A
( De+2 xDp )
Z = h/3 x ( De+Dp)
( Db−Dp)
De = Db – h x H
Fvp = Fv x Z/6,3
Municipalidad Distrital de San Juan de Lopecancha – Provincia Luya – Región Amazonas
Proyectista: Ing. Amner Ramón Santa Cruz Benavides – CIP 74710
Proyecto: “Ampliación y Remodelación de las Redes Secundarias 440/220V. y Acometidas Domiciliarias, de los
Anexos San Martín del Mango y San Antonio”
Cálculos Justificativos
Fv = Pv x Apv
Donde:
Fvp : Fuerza de viento sobre el poste a 10 cm. de la punta
Apv : Área del poste expuesta al viento
Pv : Presión del viento
h : Altura del poste expuesta al viento
Dp : Diámetro en la punta del poste
De : Diámetro del poste en el empotramiento
Db : Diámetro de la base del poste
Z : Punto de aplicación de Fvp
h : Altura de empotramiento del poste
H : Altura total del poste
K : 0,613 para elevaciones hasta 3,000 m.s.n.m
Sf : 0,102 dato obtenido de ELECTRONORTE
A : Área proyectada según C.N.E.S es 1
En nuestro caso dada las condiciones del terreno, los potes se cimentarán con
macizo de concreto e irán enterrados a H/10, 10 cm. de solado de concreto.
Tc = 2T Sen Ø/2
Donde:
Fc = Tc + Fvc
Fp = M/he (kg)
Donde:
MVP = 11,247
- Momento total en condiciones normales:
α α
MRN = 25,789 Cos 2 + 11 680,38 Sen 2 + 11, 247
Concluimos:
0° - 30° ………….. sin retenida
LEYENDA
SIMBOLOG DESCRIPCIÓN
Apv Area del poste expuesta al viento (m2)
Fc Fuerza total sobre el conductor (kgf)
Fp Fuerza en la punta del poste (kgf)
Fvc Fuerza del viento sobre el conductor (kgf)
Fvp Fuerza viento sobre el poste (Kg)
Hc Alturade aplicación de Fc (mts)
Hpv Altura del poste expuesta al viento (mts)
M Momento total (kg-m)
Mc Momento debido al viento sobre el conductor (kg-m)
Mvp Momento causado por Fvp (kg-m)
T Tiro máximo de trabajo del conductor (kgf)
Tc Tracción de los conductores sobre el poste (Kgf)
Z Alturade aplicación de Fvp (mts)
Pv Presión del viento (kgf/m2)
a Tc Fvc Fc Mc M Fp
grados sex(°) Kg Kg Kg Kg-m Kg-m Kg
0 0.000 27.347 27.347 188.694 294.538 43.961
5 57.032 27.321 84.353 582.038 687.882 102.669
10 113.956 27.243 141.199 974.274 1080.117 161.212
15 170.663 27.113 197.776 1364.655 1470.498 219.477
20 227.045 26.932 253.977 1752.438 1858.282 277.355
25 282.995 26.699 309.694 2136.886 2242.729 334.736
30 338.406 26.415 364.821 2517.265 2623.109 391.509
35 393.173 26.081 419.254 2892.853 2998.697 447.567
40 447.191 25.698 472.889 3262.935 3368.778 502.803
45 500.359 25.265 525.624 3626.805 3732.649 557.112
50 552.573 24.785 577.358 3983.771 4089.615 610.390
55 603.736 24.257 627.993 4333.154 4438.998 662.537
60 653.750 23.683 677.433 4674.289 4780.133 713.453
65 702.519 23.064 725.583 5006.526 5112.369 763.040
70 749.951 22.401 772.353 5329.233 5435.076 811.205
75 795.956 21.696 817.651 5641.795 5747.638 857.856
80 840.445 20.949 861.394 5943.617 6049.461 902.905
85 883.334 20.162 903.497 6234.126 6339.970 946.264
90 924.542 19.337 943.879 6512.768 6618.611 987.852
180 1307.500 0.000 1307.500 9021.750 9127.594 1362.327
Ma=Fp(h+t )
Mr=
P
2 [
a−
4P
3 bσ 10 4 ]
+Cbt 3
c) consideraciones
P= Pp + Pe +Pm
Pm = (Vm –Vtc)x γc
Vm = axb x t1
t
Vtc= ×( Ab+ Ae+ ( Ab+ Ae )¿ ¿ 1 ¿ ¿ )
2¿
3
3 ,1416
Ab= ×Db 2
4
3 ,1416
Ae= ×De 2
4
Donde:
Los datos del poste y de los valores calculados se ven en el cuadro de características del
poste.
Ma = Fp (h + t)
Donde:
Postes de 200
Fp= 200 Kg
Pp= 470 Peso del poste
Pesos
Pe= 120 varios
Pm = (Vm-Vtc) x γc
Vm= axbxt base cuadrada
Vtc= t1/3 x (Ab+Ae + (Ab+Ae)0,5)
t1= 1 empotramiento
F= 200 fuerza en la punta
h= 7 altura libre
t= 1,1 profundidad del macizo
a= 0,8 m
b= 0,8 m
γc = 2200 Kg/m2
σ: 2,0 Kg/cm2
C= 2000 Kg/m3
Ma = 1600 Kg
Ab= 0,0452 m2
Ae= 0,0398 m2
Ab+Ae= 0,0850 m2
Vtc= 0,04247 m3
Vm= 0,704 m3
Pm= 1455,366 Kg
P= 2042,665 Kg
Ma < Mr
Postes de 300
Fp= 300 Kg
Pp= 550 Peso del poste
Pesos
Pe= 200 varios
Pm = (Vm-Vtc) x γc
Vm= axbxt base cuadrada
Vtc= t1/3 x (Ab+Ae + (Ab+Ae)0,5)
t1= 1 empotramiento
F= 300 fuerza en la punta
h= 7 altura libre
t= 1,1 profundidad del macizo
a= 0,8
b= 0,8
γc = 2200 Kg/m2
σ: 2,0 Kg/cm2
C= 2000 Kg/m3
Ma = 2400 Kg
Ab= 0,0452 m2
Ae= 0,0398 m2
Ab+Ae= 0,0850 m2
Vtc= 0,04247 m2
Vm= 0,704 m3
Pm= 1455,37 Kg
P= 2205 Kg
Ma < Mr
Por lo tanto según los análisis para postes de C.A.C. de 8/200/150/270 y 8/300/150/270
se usaran los valores de:
a) Cable de Retenida.
Diámetro : 10 mmϕ
b) Varilla de anclaje
Fp = 589,53 kg.
c) Cálculo de Anclaje
D≥ TR/1,5 x L
Donde:
Haciendo L = 40 cm
1579,4
D ≥ 1,5 x 40
D ≥ 26,32
( )
1/2
T R Sen θ
P≥ 8 , 65 xL
P ≥ 1,51 m
L ≥ = P / Cos Ø L ≥ 1,74 m
4.6.1. Objeto
Establecer los criterios para el dimensionamiento de las puestas a tierra en Redes
Secundarias, considerando los criterios de los proyectos que ejecuta la
DEP/MEN.
4.6.2. Antecedentes