PROBLEMAS DE APLICACIÓN
PROBLEMA N° 1.- En el siguiente esquema se muestra:
PMI B
22.9 kV (INSTALACIÓN SUBTERRANEA) LONGITUD 1550 m.
S.E
A CELDA
LLEGADA
KWH
KVARH
PM710 TRAFOS DE
µZ = 5.5%
Scc = 455 MVA µR = 0.55% ……………….
tsv = 0.02 seg.
ITM1
CONDOMINIO
RRESIDENCIAL ITM3 ITM4 ITM5 ITM6
ITM2
420 KW
220 VOLTIOS ITM7
60 HZ FP=0.85
NYY
L= 156m TRIPLE
D 550 KW
M M FP=0.85
M M M
3 3
MOTOR ASINCRONO
3
157 KW FP=0.9
3
135 KW
3 FP=0.9
TRIFASICO 380 KW, 220 VOLT, 60HZ 380 VOLT, 60HZ
FP=0.79 EF=0.90 SERV. AUXIL. DATA CENTER
SOLUCION:
CUADRO DE CARGAS
Pinst. F.D MD
ITEM DESCRIPCION GENERAL
KW KW
1 CONDOMINIO 4200.8 336
2 MOTOR ASINC. 380 KW 4220.8 337.6
3 CCM 5500.8 440
4 SERV. AUXILIARES 1570.8 125.6
5 DATA CENTER 135 1 135
TOTAL KW 1684 1374
DEL TRAFO
CALCULO
Luego la POTENCIA CONTRATADA FINAL será de 950 KW, 22.9 KV, 60 Hz,
Tarifa MT4.
CARACTERÍSTICAS ELECTROMECÁNICAS
1 Tipo de transformador En baño de aceite
2 Tipo enfriamiento Natural
3 Altura máxima de trabajo 1 000 m.s.n.m.
4 Regulación 10 ± 2 x 2,5% Vn KV
5 Regulación 20 ± 2 x 2,5% Vn KV
6 Grupo de conexión Dyn5 Para 10 KV
7 Grupo de conexión YNyn6 Para 22.9 KV
8 Numero de bornes M.T. 04
9 Numero de bornes BT 03
10 Placa de características Normalizada
11 Conmutador de tomas En lado de MT
12 Conservador de aceite En la izquierda parte tracera
13 Indicador del nivel de aceite Con indicador visible
14 Tapón de llenado del aceite Sobre el tanque conservador
15 Grifo de vaciado y toma muestras de aceite En la parte baja inferiro del tanque
16 Pozo termométrico con contactos alarma Ubicados en el interior del tanque
17 Termómetro con contactos de alarma En la parte superior visible
18 Orejas de izamiento En la tapa superior del tanque
19 Pernos para puesta a tierra del tanque En el puente base de trafo
20 Ruedas bidireccionales 04 para desplazamiento
21 El nivel de PCB en el aceite Será menor a 2 p.p.m
22 Protección Buchold Por ser de potencia
455
ICCA = = 𝟏𝟏. 𝟒𝟕 KA
√3x22.9
CONDICION : Icc cable ≥ 1.5 x IccA Icc cable = 1.5 x 11.47 = 17.21 KA
𝑡
𝑆𝑐𝑢 𝑐𝑎𝑏𝑙𝑒 = √𝐼𝑐𝑐² 𝑥
𝑘²
0.02
𝑆𝑐𝑢 𝑐𝑎𝑏𝑙𝑒 = √17210² 𝑥 = 17.02 𝑚𝑚²
20446
PMI B
22.9 kV (INSTALACIÓN SUBTERRANEA) LONGITUD 1550 m.
S.E
A CELDA
LLEGADA
KWH
KVARH
PM710 TRAFOS DE
µZ = 5.5%
Scc = 455 MVA µR = 0.55% ……………….
tsv = 0.02 seg.
ITM1
SECCIÓN DIÁMETROS
T.G.PESO RESISTENCIA
0.44 KV,
REACTANCIA AMPACIDAD
C
NOMINAL CONDUCTOR EXTERIOR AC60
(A)HZ (A) ENTERRADO
2
mm
CONDOMINIO mm mm Kgr/Km OHM/Km OHM/Km AMPERIOS (Icat)
RRESIDENCIAL ITM40.2761
50KW
420 A)
8.7 31.9 1351
ITM2 0.494
ITM3 ITM5 250 ITM6
=
220 VOLTIOS ITM7
3 Cables Unipolares en
60 HZ FP=0.85
formación unipolar, tendidos paralelos con una separación
mayor ó igual a 7 cm.
FUENTE Q NYY
L= 156m TRIPLE
22.9
𝐼𝐶𝐶𝐵 = = 6.92 𝐾𝐴 Según VDE 0102 – Parte 1 – Metodología UTILIZADA
√3𝑥1.9105
PMI B
22.9 kV (INSTALACIÓN SUBTERRANEA) LONGITUD 1550 m.
S.E
A CELDA
LLEGADA
KWH
KVARH
PM710 TRAFOS DE
µZ = 5.5%
Scc = 455 MVA µR = 0.55% ……………….
tsv = 0.02 seg.
ITM1
CONDOMINIO
RRESIDENCIAL
PROBLEMAS DE
420APLICACION
KW MSC. ING. ITM3
ITM2 HUBER ITM4
MURILLO ITM5
MANRIQUE ITM6
Página 4
220 VOLTIOS ITM7
60 HZ FP=0.85
NYY
L= 156m
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
𝑍𝑇 = 0.0055 + 𝑗 0.054724 𝑝. 𝑢
22.92
𝑍𝑇 = (0.0055 + 𝑗 0.054724) ( ) = 1.4421 + 𝑗 14.3489 Ω
2.0
0.442
𝑍𝑡𝑜𝑡𝑎𝑙 𝐶 = 16.2073 ( ) = 0.0059834 Ω 𝑒𝑛 440 𝑣𝑜𝑙𝑡𝑖𝑜𝑠
22.9²
440
𝐼𝑐𝑐 𝐶 = ( ) = 42.46 𝐾𝐴 𝑒𝑛 440 𝑣𝑜𝑙𝑡𝑖𝑜𝑠
1.7321 𝑥 0.0059834
PMI B
22.9 kV (INSTALACIÓN SUBTERRANEA) LONGITUD 1550 m.
S.E
A CELDA
LLEGADA
KWH
KVARH
POR CAPACIDAD
PM710 TRAFOS DE
µZ = 5.5%
Scc = 455 MVA µR = 0.55% ……………….
Corriente nominal : lN = S / 3. V
tsv = 0.02 seg.
Donde: S Potencia aparente nominal. ITM1
V Tensión nominal (22.9 KV)
V = 3 In L (R cos + x sen)
Donde:
In Corriente nominal.
L Longitud máxima de la última cola a la SE.
Cos Factor de potencia promedio industrial.
V Caída de tensión
L = 1550 m. FP = 0.85 Ø = 31.8
Con Icat. aplicamos los factores de corrección considerados por el CNE y finalmente
evaluamos la Iconductor.
20446
𝐼𝐶𝐶 𝐶𝐴𝐵𝐿𝐸 = √502 = 50.55 𝐾𝐴
0.02
𝐼𝐶𝐶 𝐶𝐴𝐵𝐿𝐸 = 50.55 𝐾𝐴, 𝐼𝑐𝑐 𝐵 = 6.92 𝐾𝐴 𝐼𝑐𝑐 𝑐𝑎𝑏𝑙𝑒 > 𝐼𝑐𝑐 𝐵 LUEGO SI CUMPLE
R X Z(Ω) θ
ZC (MT) 2.1773 + 16.84 = 16.9850 82.63
D RD XD Z(Ω) θ
720 mm² 0.0052 + 0.0050 = 0.0072 44.07
ENTERRADO
ZD (B.T) 0.0060 0.0115330 = 0.0130 62.38
ΔV (%) = (0.309 x 156 x 6 x Idiseño x F.P)/ (Scu x 44) Caída de tensión a Iarranque
Cap Scu (A) = 3 x 426 x 0.7 = 895 A (0.7 tabla 12B del CNE)
N°
FACTOR
CONDUCTORES
3 1
4-6 0.8
7 - 24 0.7
25 - 42 0.6
> 43 0.5
60 10
100 10
200 16
400 25
600 50
800 50
sobre 800 70
9.- Hacer la compensación localizada del Motor asíncrono trifásico (carga 3).
NOTA IMPORTANTE
Cap Scu (A) = = 2 x 525 x 0.8 = 840 A (tabla del cable N2XH)
El regulador automático de potencia reactiva a utilizarse debe ser de 12 pasos, de los cuales solo vamos
a utilizar 11 pasos, el otro queda como reserva.
TAREA 1.- Hacer la compensación reactiva de un motor asíncrono trifásico de 500 KW, 460 Hz, 02
polos, Arranque estrella – triángulo.
TAREA 2.- Hacer la compensación reactiva grupal de los siguientes motores asíncronos trifásicos.
PASOS P POLOS Vn F
KW VOL Hz
1 10 2 460 60
2 7.5 2 460 60
3 15 4 460 60
4 30 6 460 60
5 45 8 460 60
6 50 4 460 60
7 4.5 4 460 60
TOTAL
Sn = 100 MVA
t = 0.02 seg.
F1
IP1 52
10 KV, 60 HZ
Sn = 160 KVA
Uz = 4.37%
F2
Ur = 0.2%
Dny5
ITM1 ITM
REG.
F3
0.44 KV, 60 HZ
40 KW 35 KW MATJA WEG DE 18 KW
60 HP, 4 PLOOS
1.1
𝑋𝑄II = = 1.0945Ω
1.005
𝑅𝑄
= 0.1
𝑋𝑄II
0.46 2
𝑍𝑄II = 1.0999( ) = 0.2317 + 𝑗 2.3159 = 2.3274𝑥10−3 Ω 0.46 kV
10
0.462
𝑅𝑇 = 0.002 ( ) = 2.645𝑥10−3 Ω
0.16
15
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
𝑍𝑇𝑂𝑇𝐴𝐿 = 𝑍𝑄II + 𝑍𝑇
𝑅𝑇𝑂𝑇
= 0.048 𝑍𝑇𝑂𝑇𝐴𝐿 = 0.0601Ω
𝑋𝑇𝑂𝑇
II 10𝐾𝑉
𝐼𝑚𝑎𝑥3 = 1.1𝑥 𝑥1.0999 = 5.77 𝐾𝑉𝐴 𝐼𝑠II𝑚𝑎𝑥3 = 𝑋√2𝐼𝑚𝑎𝑥3
II
= 13.9 𝐾𝑉𝐴
√3
𝑅
= 0.1 𝑋 = 1.7𝐴
𝑋
𝐼𝑎II𝑚𝑎𝑥3 = µ𝐼 II𝑚𝑎𝑥3
10 2
𝑍𝑇 = 0.0578 ( ) = 27.31 Ω (10𝐾𝑉)
0.46
Análisis de potencias
𝑆𝑆 = 246 𝑀𝑉𝐴
𝑆𝑎 = 100 𝑀𝑉𝐴
𝐼𝐼 𝑉𝑁 460
𝐼𝑚𝑎𝑥3 = = = 4.42 𝐾𝐴
√3𝑍𝑇𝑂𝑇 √3𝑥0.0601
II
𝐼𝑆 = 𝑋√2𝐼𝑚𝑎𝑥3 = 1.86𝑥√2𝑥4.42 = 11.63 𝐾𝐴
16
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
Análisis de potencias
𝑆 𝐼𝐼 = √3𝑥460𝑥4420 = 3.5𝑀𝑉𝐴
𝑆𝑎 = 3.5𝑀𝑉𝐴
𝑆𝑆 = 9.3𝑀𝑉𝐴
160
𝐼𝑁 𝑇𝑅𝐴𝐹𝑂 = = 200.8 𝐴 𝐼𝐷𝐼𝑆𝐸Ñ𝑂 = 1.2𝑥200.8 = 240.96 𝑒𝑙𝑖𝑗𝑜 250 𝐴
√3 𝑥460
200.8
𝑅𝐸𝐺𝑈𝐿. 𝑇𝐸𝑅𝑀𝐼𝐶𝐴 = = 0.81(0.5 − 1)𝐼𝑁
250
200.8 𝑥 6
𝑅𝐸𝐺𝑈𝐿. 𝑇𝐸𝑅𝑀𝐼𝐶𝐴 = = 4.81 (1 − 10)𝐼𝑁
250
𝑃𝑂𝐷𝐸𝑅 𝐶𝑂𝑅𝑇𝐸 ≥ 15 𝐾𝐴
𝑃𝑂𝑇. 𝐼𝑁𝐼𝐶𝐼𝐴𝐿 𝐷𝐸 𝐶. 𝐶 ≥ 5 𝑀𝑉𝐴
𝐶𝐴𝑃. 𝐼𝑀𝑃𝑈𝐿𝑆𝑂 ≥ 10 𝑀𝑉𝐴
𝐶𝐴𝑃. 𝑅𝑈𝑃𝑇𝑈𝑅𝐴 ≥ 5 𝑀𝑉𝐴
TAREA DOMICILIARIA:
17
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
PROBLEMA N° 3.- En el siguiente esquema se muestra un sistema de MEDIA TENSION, con sus respectivas
cargas en baja tensión, en estas condiciones se le solicita:
ITM1
0.46 KV, 60 HZ
C
1. Haga el cuadro de cargas y calcule la MD, tome para todas las cargas el FD = 0.9 según el CNE.
2. Con un F. Ampliación de 25%, dimensione y seleccione el M
transformador y Mpresente sus características
M
de
M
funcionamiento. 3 3 3 3
SOLUCION
1.- Haga el cuadro de cargas y calcule la MD, tome para todas las cargas el FD = 0.8 según el CNE.
CUADRO DE CARGAS
PINST. F.D MD
18
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
Luego la potencia contratada será de 1400 KW, 22.9 KV, 60 Hz, Tarifa MT4.
2.- Con un F. Ampliación de 25%, dimensione y seleccione el transformador y presente sus características de
funcionamiento.
19
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
R X Z(Ω) θ
ZC (M.T) 1.95472448 + 13.14 = 13.2856 81.54
TAREAS DOMICIALIARIAS.-
6.- Si la carga del ITM3 arranca en directo y se halla a 135 metros de la barra C. Hallar estos cables
alimentadores tipo NYY triple. Utilice únicamente cables de 240 mm² NYY. Ducto PVC SAP.
7.- Hacer la compensación localizada de la carga conectada al ITM3 con bancos electronicom.
8.- Hacer la compensación automatizada del sistema eléctrico utilizando bancos electronicom.
20
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
PROBLEMA N° 4.- En el siguiente esquema se muestra un sistema de MEDIA TENSION, con sus respectivas
cargas en baja tensión, en estas condiciones se le solicita:
PMI
22.9 kV LONGITUD 1200 m B
A CUT
OUT
Scc = 395 MVA
tsv = 0.550 seg. TCC = 5.75% …… MVA
UR = 0.55%
ITM1
REGULABLE
0.45 KV, 60 HZ
C
ITM5
ITMBC1 ITM2 ITM3 ITM4
REG
REG REG REG REG
D
ITM7 ITMBC2
ITM6
REG REG
REG.
L= 175 m
75 HP BANCO
FP= 0.91 LOCAL
E EF= 91%
1. Haga el cuadro de cargas y calcule: La MD, POTENCIA CONTRATADA E ITMs del sistema de BAJA
TENSION.
2. Dimensione y seleccione el transformador y presente sus características electromecánicas más importantes
de funcionamiento.
3. Hallar los cables de los circuitos CD y DE tipo N2XH triple instalados en ducto.
4. Hacer el cálculo de la corriente de corto circuito en los puntos A, B y C.
5. Hacer el cálculo de la corriente de corto circuito en el punto D y E.
6. Dimensione y seleccione el cable óptimo de M.T.
7. Hallar el banco localizado en el punto D.
8. Hallar el banco auto(compensación centralizada en el punto C).+ Montaje electromecánico de los bancos.
21
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
SOLUCIONARIO
RT XT z (Ω) θ
ZT (MT) Ω
3.3932 + 35.4748 = 35.6367 84.54
R X Z(Ω) θ
ZC (MT) 4.1321 + 37.26 = 37.4877 83.67
RD XD Z(Ω) θ
CABLE 240 mm² 0.0014 + 0.0135 = 0.0136 84.10
RE XE Z(Ω) θ
CABLE 185 mm² 0.0228 + 0.0173 = 0.0286 37.29
22
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
CARGAS EN EL PUNTO D
CABLES EN EL CIRCUITO CD Y DE
23
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
24
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
MODELOS DE SEPS.-
25
CORTO CIRCUITO SEGUN VDE 102 – 1 – 2
PROBLEMA N° 5.- En el siguiente esquema se muestra un sistema de MEDIA TENSION, con sus
respectivas cargas en baja tensión, en estas condiciones se le solicita:
LA DISTANCIA ENTRE
LAS BARRAS DE 440 V Y
ITMB ITM1 ITM2 ITM3 ITM4 EL TRANSFORMADOR ES
DE 12.4 m.
315 KVA 86 m.
Banco de TD3
OTRAS 102 m. 440/380 V
capacitores CARGAS
175 KW. FP TD2 Banco
= 0.95 C
TD1 Motor
100 KVAR TRIFASICO
450 HP
OTRAS CARGAS SERVICIOS AUXILAR
395 KW. FP = 0.8 I 250 KW 380 V EF = 93%
FP = 0.72 I FP = 0.86 I
1. Haga el cuadro de cargas y calcule la MD, tome para todas las cargas el FD = 0.85 según el CNE.
2. Con un F. Ampliación de 15%, dimensione y seleccione el transformador y presente sus
características eléctricas de funcionamiento.
3. Hacer el cálculo de la corriente de corto circuito en los puntos A, B y C.
4. Hacer el cálculo de la corriente de corto circuito en el punto D y E.
5. Dimensione y seleccione el cable óptimo de M.T.
6. Si la carga del ITM8 se halla a 65 metros de la barra D. Hallar estos cables alimentadores tipo
N2XH triple.