CAPACIDAD DE DISTRIBUCIN (kVA-m) PARA CIRCUITOS TRIFSICOS CON CABLES

MONOPOLARES DE COBRE (AMERICANOS) EN DUCTOS PARA INSTALACIONES INTERIORES.


kVA-m (1%)
CALIBRE
AWG

14
12
10
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500

60C Y 75C
Cosq=0,9

90C
Cosq=0,8

Cosq=0,9

Cosq=0,8

208Y120V

480Y277V

208Y120V

480Y277V

208Y120V

480Y277V

208Y120V

480Y277V

47
72
119
181
281
430
639
785
1,007
1,152
1,404
1,644
1,832
2,069
2,317
2,564
2,708

249
384
633
962
1,496
2,292
3,404
4,183
5,365
6,136
7,478
8,757
9,759
11,019
12,338
13,654
14,423

52
80
132
199
306
462
674
816
1,030
1,163
1,396
1,602
1,759
1,949
2,163
2,351
2,458

278
428
703
1,060
1,629
2,462
3,589
4,347
5,486
6,194
7,432
8,533
9,366
10,378
11,520
12,522
13,091

45
69
114
173
269
412
613
754
969
1,110
1,354
1,589
1,733
2,006
2,249
2,493
2,636

237
367
605
919
1,430
2,195
3,265
4,017
5,161
5,910
7,213
8,463
9,445
10,684
11,974
13,277
14,040

50
77
126
190
293
443
648
786
994
1,124
1,352
1,555
1,710
1,899
2,110
2,298
2,405

266
409
672
1,014
1,561
2,362
3,451
4,188
5,295
5,988
7,198
8,284
9,108
10,114
11,237
12,238
12,809

NOTAS:
1.- Valores de capacidad de distribucin calculados en base a la frmula: kVA= 104 x (V%) x (kV)2 / (Rcos x Xsen), con los
valores de R y X tomados de la tabla 9, del Captulo 9 del C.E.N 1999 y ajustados para la temperatura y factor de potencia de
operacin.
2.- Se tomaron las condiciones de instalacin ms desfavorables para la Capacidad de Distribucin que corresponden a cables
en tuberia metlica.