Está en la página 1de 6

TABLA No.

14
CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE DIRECTA
POTENCIA EN
HP

115 VOLTS

0.50
0.75
1.00
1.50
2.00
3.00

4.6
6.6
8.6
12.6
16.4
24.0

5.0
7.5
10.0
15.0
20.0

40.0
58.0
76.0
112.0
148.0

25.0
30.0
40.0
50.0
60.0

184.0
220.0
292.0
360.0
430.0

75.0
100.0
125.0
150.0
200.0

536.0
---------

CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE ALTERNA


MONOFASICOS
POTENCIA EN
HP
1/6

115 VOLTS
3.2
4.6
7.4

10.2

1.0

13.0

1.5
2.0
3.0
5.0
7.5
10.0

18.4
24.0
34.0
56.0
80.0
100.0

TABLA No. 16
CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE ALTERNA
TRIFASICOS
POTENCIA
HP

220 V

1/2
3/4
1.0
1.5
2.0

2.0
2.8
3.5
5.0
6.5

1.0
1.4
1.8
2.5
3.3

0.8
1.1
1.4
2.0
2.6

-----------

3.0
5.0
7.5
10.0
15.0

9.0
15.0
22.0
27.0
40.0

4.5
7.5
11.0
14.0
20.0

4.0
6.0
9.0
11.0
16.0

-----------

20.0
25.0
30.0
40.0
50.0

52.0
64.0
78.0
104.0
125.0

26.0
32.0
39.0
52.0
63.0

21.0
26.0
31.0
41.0
50.0

--7.0
8.5
10.5
13.0

60.0
75.0
100.0
125.0
150.0

150.0
185.0
246.0
310.0
360.0

75.0
93.0
123.0
155.0
180.0

60.0
74.0
98.0
124.0
144.0

16.9
19.0
25.0
31.0
37.0

200.0
250.0
300.0
350.0
400.0

480.0
---------

240.0
300.0
345.0
406.0
475.0

192.0

48.0

TABLA No. 6

MOTORES DE INDUCCIN
440 V
550 V

2400 V

CAPACIDAD DE CORRIENTE EN AMPERES PARA CONDUCTORES DE


COBRE, AISLADOS Y, PARA UNA TEMPERATURA AMBIENTE DE 30 C.
CALIBRE
AWG o MCM
14
12
10
8
6
4
2
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000

TIPOS T, TW, UF (60 C)


TUBO o DUCTO
EN AIRE
15
20
20
25
30
30
40
60
55
80
70
105
95
140
125
195
145
225
165
260
195
300
215
340
240
375
260
420
280
455
320
515
355
575
385
630
400
655
410
680
435
730
455
780
FACTORES DE CORRECCIN PARA TEMPE
MAYORES DE 30 C
0.91
0.91
0.82
0.82
0.71
0.71
0.58
0.58
0.41
0.41

31 A 35 C
36 A 40 C
41 A 45 C
46 A 50 C
51 A 55 C
56 A 60 C
61 A 79 C

NOTAS: Para 4 a 6 conductores en un tubo, la ampacidad se reduce al 80% de


las cifras dadas, de 7 a 9 conductores, la ampacidad se reduce al 70% ; al 50%
si hay de 10 a 20 conductores y, al 45% si hay de 21 a 30 conductores en un
tubo. En un sistema balanceado, el neutro no cuenta como conductor para los
efectos de esta nota.
HP

KW

I
115

FUS
115

PROT
115

I
220

FUS
220

PROT
220

I
440

FUS
440

PRO
440

1/6
1/4
1/3
1/2
3/4
1
1.5
2
3
5
7.5
10
15
20
25
30
40

0.12
0.19
0.25
0.37
0.56
0.75
1.12
1.49
2.24
3.73
5.60
7.46
11.2
14.9
18.7
22.4
29.8

50

37.3

4.4
5.8
7.2
9.8
13.8
16
20
24
34
56
80
100
131

8
10
16
20
25
32
40
50
63
100
160
200
250

16
16
20
25
40
40
50
63
82
150
200
250
350

2.2
3.2
4.2
6
6.8
9.6
15.2
22
28
42
54
68
80
104

4
6
8
10
16
20
32
40
50
80
100
125
160
200

6
10
10
16
20
25
40
63
80
125
150
175
200
300

1.1
1.6
2.1
3
3.4
4.8
7.6
11
14
21
27
34
40
52

2
4
4
6
6
8
16
20
25
40
50
63
80
100

130

250

300

65

125

LA TABLA ANTERIOR NOS PROPORCIONA LA CORRIENTE QUE CONSUME UN MOTOR EN LAS


TENSIONES DE 115, 220 Y 440 VOLTS AS COMO LA PROTECION QUE DEBE UTILIZAR YA SEA
UTILIZANDO UN FUSIBLE O UN INTERRUPTOT TERMOMAGNETICO, LOS CUALES SE PUEDEN
CALCULAR DE LA SIGUIENTE FORMA:
CORRIENTE PARA UN MOTOR MONOFASICO O 115 V:
IP= P/ E COS 0 N
DONDE EL SIGNIFICADO DE CADA UNA DE LAS LITERALES ES:
IP= CORRIENTE NOMINAL O A PLENA CARGA QUE CONSUME UN MOTOR (AMPERS)
P= POTENCIA QUE DESARROLLA UN MOTOR (WATTS O KILOWATTS)
E= TENSION A LA QUE SE CONECTA EL MOTOR (VOLTS)
COS 0= FACTOR DE POTENCIA
N= RENDIMIENTO DEL MOTOR
LA CORRIENTE PARA UN MOTOR TRIFASICO CONECTADO A 220 O 440 vOLTS
SE AFECTA EN EL DENOMINADOR POR LA RAIZ CUADRADA DE 3, LA CUAL
REPRESENTAREMOS EN LA ECUACION POR /3
IP = P / /3 E COS 0 N
NOTA: EL VALOR DE LAS LITERALES EL EL MISMO
EJEMPLO 1:
DETERMINAR LA CORRIENTE QUE CONSUME UN MOTOR MONOFASICO EL CUAL ESTA
CONECTADO A UNA FUENTE DE ALIMENTACION DE 115 VOLTS Y TIENE UNA POTENCIA DE 1/2
H.P. EL CUAL TIENE UN FACTOR DE POTENCIA DE 0.6 EN ATRASO Y UN RENDIMIENTO DE 55%.
DATOS
MOTOR MONOFASICO
CALCULO DE LA CORRIENTE
IP= ?
E= 115 VOLTS
IP = P / E COS 0 N
P= 1/2 H.P. = 370 WATTS
COS 0 = 0.6
IP = 370 / 115*0.6*0.55
N= 0.55
IP = 9.74 AMPERS

4
4
6
10
10
16
20
32
40
63
82
100
100
150
175

COMO PODEMOS OBSERVAR EL RESULTADO ES MUY SEMEJANTE AL DE LA TABLA ANTERIOR


PARA UN MOTOR DE 1/2 H.P Y TENSION DE 115 VOLTS.
EJEMPLO 2.
CALCULAR LA CORRIENTE QUE CONSUME UN MOTOR TRIFASICO QUE SE CONECATA A UNA
TENSION DE 220 VOLTS , EL CUAL TIENE LOS SIGUIENTES DATOS DE PLACA: POTENCIA 5
H.P. ; FACTOR DE POTENCIA 0.65 EN ATRASO Y RENDIMIENTO DE 50%
DATOS
MOTOR TRIFASICO
CALCULO DE LA CORRIENTE
IP =?
E= 220
IP = P / /3 E COS 0 N
F.P.= 0.80
N= 0.80
IP = 3730 / 1.732*220*0.8*0.85
P= 3.73 KW = 5 H.P.
IP = 15.29 AMPERS
DEBEMOS COMPARAR EL RESULTADO CON EL DE LA TABLA Y PODEMOS OBSERVAR QUE ES
MUY SEMEJANTE AL DE UN MOTOR TRIFASICO DE 5H.P. Y TENSION DE 220 VOLTS