Documentos de Académico
Documentos de Profesional
Documentos de Cultura
DISEÑO de Manatial
DISEÑO de Manatial
L.C1
L.C.2
L.A
PARAMETROS:
Variacin de consumo
K 1=1.3 K 2=2.0
DISEO:
Agua contra incendio : 30l/s
Calculamos ahora
Qm
l
hab . dia
=39.931 l /seg
86400 seg
23000 hab150
Q m=
79.862VS 81.9103
INGENIERIA CIVIL
Pgina 1
Q mh VS (Q md +30)
OBRAS DE SANEAMIENTO
81.9103 l/seg
S=50 m/ Km
Reemplazando:
S=
200190
=50 m/ Km
0.2
Reemplazando:
2.63
0.54
51.9103=0.0004264( 140 ) D (50 )
S=
190170
=40 m/ Km
0.5
Reemplazando:
INGENIERIA CIVIL
25 volumen diario=0.253450=862.5 m3
Pgina 2
OBRAS DE SANEAMIENTO
L=1 Km
C=140
T =25 C
=8.94107 m2 /seg
=0.0015 mm
50
1
0.54
( )
Entonces:
Q= AV
V =Q / A
V =3 .01 m/seg
R=VD /
INGENIERIA CIVIL
Pgina 3
OBRAS DE SANEAMIENTO
R=513114
2.51
=2 log
+
3.71 D R f
f
f =0. 013
h f =f
L V2
D 2g
h f =39.4 m
h L25 0=K e
V2
2g
K e =0.5
h L25 0=0. 23 m
V2
h L200 =K s
2g
K s =1
h L200 =0. 46 m
2) TRAMO PT R
D=6 plg=0.1524 m
L=0.20 Km
C=140
Q=0.0004264 C D
2.63
=0.0015 mm
0.54
Q=0.0004264 (140)(6)2.63
10
0.20
0.54
( )
INGENIERIA CIVIL
Pgina 4
OBRAS DE SANEAMIENTO
Entonces:
Q= AV
V =Q / A
V =3.01 m/seg
R=VD /
R=513114
2.51
=2 log
+
3.71 D R f
f
f =0.013
h f =f
L V2
D 2g
h f =39.4 m
2
h L20 0=K e
V
2g
K e =0.5
h L20 0=0.23 m
h L19 0=K s
V2
2g
K s =1
h L19 0=0.46 m
3) TRAMO RESERVORIO-URBANIZACIN:
INGENIERIA CIVIL
Pgina 5
OBRAS DE SANEAMIENTO
D=8 plg=0.2032 m
L=0.5 Km
C=140
T =25 C
7
=0.0015 mm
=8.9410 m /seg
Q=0.0004264 C D
2.63
0.54
Q=0.0004264 (140)(8)2.63
20
0.50
0.54
( )
Q=103.8< seg
Entonces:
Q= AV
V =Q / A
V =3.2 m/seg
R=VD /
R=727337.8
2.51
=2 log
+
3.71
D
R f
f
f =0.012
2
h f =f
L V
D 2g
h f =15.41 m
2
h L190 =K e
V
2g
K e =0.5
h L190 =0.26 m
INGENIERIA CIVIL
Pgina 6
OBRAS DE SANEAMIENTO
2
h L170 =K s
V
2g
K s =1
h L170 =0.52 m
INGENIERIA CIVIL
Pgina 7