DISEO Y AJUSTES DE
PROTECCIONES EN UNA
SUBESTACIN DE ALTA TENSIN
AUTOR:
Fdo.:..
Fecha://
Fdo.:..
Fecha://
Resumen
Resumen
SUMMARY
This project consist of the design and adjust of a high voltaje substations
protection system.
This document is splitted into two sections. The first one has a more general
nature with special emphasis on knowing the various existing protections and
having an advice of which kind of protections should we use and how to combine
them according to which substation is going to include the protection system and
the kind of bay to protect: line, transformer, capacitors banks, bus bar bay and so
on. The second section consists of the implementation of the previously done
study in a true-life case. A protection system has been designed and adjusted for a
concrete substation according to clients specifications.
Electric protections constitute a fundamental system for every electric installation.
In this concrete case of a protection system for a substation we must understand
this as an integrant part of the transport and distribution system which works as a
connection or disconnection point of transport lines, distribution lines, generation
centrals and lifting or lowering transformers. Substation purposes are to get the
maximum security, flexibility and service realiability with the minimum costs of
investiment and operation which satisfice the Electric Systems requirements and
with this purpose substattions must have protection systems that help them to
perform their duties.
The need of this kind of systems is justified to maintain the quality of service on
electrical energy supply which is measured mainly in terms of the number and
length of supply interruptions, as well as keeping tension beetwen the previously
established or nominals limits.
Even in the cases in which electric systems are carefully designed, kept and
exploted there is always the possibility of faults and in that situation, these must
be solved so that the less part of the system get disconnected with the intention of
keep working as well as possible. This proposal is fulfilled by the implentation of
protection equipments.
Summary
On first section this project intends to be a usefull tool at the time of designing a
protection system for a substation. With this intention different protection systems
have beeen analysed according to their bay (tension line, transformer, bus bars)
and the kind of substation to protect (simple bus bar, double bus bar, switch and a
half, and so on).
Once the protections system has been designed, its operation must be properly
coordinated. The adjust and cordination of protections purpose is to ensure that
we have a primary protection system and also a secondary one so that primary
protection must protect all the electric system and solves any fault in the minor
time possible. Secondary protections must have a delay so that they allow
principal protections to act for on first instance. These protections are the
following:
A. Switch fault protection which detects failures in the switch which must
interrupt the faults current and so it opens the adjacent switches to
isolate the fault.
C. The secondary protection which detects the fault and takes effect on
second instante when primary protection has not worked. For a proper
backing this relay must have a different physical beahivour to the
principal one.
The second secton of the Project consists of the design and adjust of protections in
a real Project. In this case a high-voltage substation placed in Ethiopia called
Sebeta II 400/230/33 kV, which major characteristics are:
Summary
Summary
MEMORA
NDICE DE LA MEMORIA:
1. INTRODUCCIN..........................................................................................10
1.1 Motivacin del proyecto....................................................................10
1.2 Objetivos............................................................................................11
1.3 Sistema elctrico: definicin y elementos que lo constituyen........12
1.4 Desarrollo histrico: sistemas de proteccin directos e
indirectos............................................................................................13
1.5 Exigencias bsicas de los equipos de proteccin.............................16
1.6 Planificacin de las protecciones......................................................18
3. SUBESTACIONES..........................................................................................25
3.1 Configuracin elctrica de las subestaciones...................................25
3.2 Conexiones de las barras principales................................................27
3.3 Configuraciones elctricas en funcin de las tensiones de
servicio....................................................................................................32
Memoria
Memoria
Memoria
Memoria
10. ANEXOS.......................................................................................................172
10.1 Simbologas tpicas.........................................................................172
10.2 Funciones de los dispositivos / Cdigos ANSI..............................173
10.2.1 N Funcin y Descripcin................................................173
10.2.2 Letras y sufijos de las funciones descritas.....................183
10.3 Descripcin tcnica de los equipos................................................190
11. BIBLIOGRAFA..........................................................................................226
Memoria
NDICE DE FIGURAS
Memoria
Memoria
Memoria
10
1. INTRODUCCIN
1.1 Motivacin del proyecto
La calidad del servicio en el suministro de energa elctrica se mide, bsicamente,
en trminos del nmero y duracin de las interrupciones en el suministro, as
como por el mantenimiento de la tensin y la frecuencia dentro de unos lmites
prefijados y nominales.
Pero, aun en los casos en que los sistemas elctricos estn cuidadosamente
diseados, conservados y explotados, siempre existen posibilidades de que se
produzcan incidentes y, en tal caso, stos deben ser eliminados de forma que
quede desconectada del sistema la menor parte posible, a fin de que ste siga
funcionando. Esto se logra mediante la implantacin generalizada de equipos de
proteccin.
Memoria
11
1.2 Objetivos
El objetivo principal de este proyecto es el de ajustar y disear las protecciones
para una subestacin de alta tensin, es decir, para una subestacin que se
encuentra en el subsistema de transporte.
Para ello, previamente habr que estudiar los tipos de subestaciones, los tipos de
incidentes posibles en el sistema elctrico, en particular, en las diferentes
configuraciones de las subestaciones; adems de un amplio estudio de los
diferentes sistemas de proteccin.
Memoria
12
Dentro de las cuatro partes en que se divide el sistema elctrico, cabe citar sus
elementos ms destacados:
a)
b)
Memoria
c)
13
d)
e)
Son todos aquellos sistemas en los cuales el elemento de medida es, el mismo que
el de corte (o est incorporado en l) y la magnitud que hay que controlar,
normalmente la intensidad, se aplica a la proteccin sin ningn tipo de
transformacin.
a.1) Fusibles
Es el mtodo de proteccin ms antiguo de todos los utilizados. Se basa en
el incremento de temperatura que sufre un conductor al ser atravesado por
una intensidad. Se calibran de forma que el conductor se funde cuando es
atravesado por una intensidad prefijada, interrumpiendo el circuito.
Los fusibles son econmicos y son capaces de eliminar elevadas corrientes
de cortocircuito en tiempos inferiores a los 5 ms. No obstante, posee
desventajas como poca precisin, bajo poder de corte, envejecimiento, etc.,
Memoria
14
b)
Son aquellos en los que las magnitudes que hay que controlar (tensin, intensidad,
temperatura) se transforman en valores normalizados antes de inyectarse al rel de
proteccin.
En general estos sistemas son ms costosos que los directos, al requerir adems de
la proteccin propiamente dicha, de transductores y elementos de corte. Sin
embargo, con su aparicin el concepto de proteccin alcanza su plenitud.
Los principales tipos son:
b.1) Sistemas electromagnticos
La informacin suministrada a los rels en forma de intensidad o tensin
es transformada por stos en una fuerza capaz de cerrar unos contactos que
establecen la continuidad en el circuito de disparo. Segn su construccin,
los podemos clasificar en:
-
Disco de induccin
Memoria
15
Memoria
16
1.5
La proteccin ideal sera aquella que actuara solamente ante los incidentes para
los que ha sido instalada, que lo hiciera en el menor tiempo posible y que su
Memoria
17
2.
3.
4.
5.
6.
7.
8.
9.
10.
Memoria
11.
18
12.
Precio. Reducido.
1.6
b)
c)
d)
Memoria
19
Memoria
Otro punto importante que hay que tener en cuenta en la planificacin de las
protecciones es encontrar el ptimo entre las caractersticas, la fiabilidad y el
coste. Para ello, adems de lo dicho, es de gran utilidad conocer estadsticas
fiables tanto de la red y del equipo que hay que proteger como de los rels de
proteccin que deben usarse.
Memoria
20
21
2.1 Perturbaciones
Un ingeniero quiere que las cosas funcionen correctamente todo el tiempo. Sin
embargo, a veces esto no ocurre, y el sistema debe estar preparado para afrontarlo.
Numerosas causas pueden provocar fallos en el sistema:
- Causas climticas: un rayo puede caer en una torre de alta tensin, una
subestacin de transformacin puede inundarse, el viento puede acercar dos
conductores produciendo descargas elctricas, etc.
- Envejecimiento de los equipos: el aislante de los conductores disminuye su
eficiencia con los aos, sucesivos ciclos de calentamientos y enfriamientos varan
las propiedades dielctricas de los materiales, partes metlicas se corroen, etc.
- Otras causas: mala operacin de los equipos, accin de animales, roturas por
obras de otras empresas, etc.
22
23
Memoria
24
Memoria
25
con
Memoria
26
SUBESTACIONES
Con el continuo aumento general en los costes de los equipos, mano de obra,
terreno y preparacin del emplazamiento, hay que esforzarse al mximo para
elegir criterios que representen la mejor composicin para satisfacer los requisitos
del Sistema con el coste mnimo. Como los costes mayores de la subestaciones
estn constituidos por los transformadores de potencia, los interruptores y los
seccionadores, la disposicin del embarrado y de las conexiones determina el
nmero de seccionadores e interruptores necesarios.
Memoria
27
Memoria
28
Simple barra
2.
Barra partida
Memoria
3.
4.
5.
Doble barra
Memoria
29
6.
7.
8.
Memoria
30
9.
Interruptor y medio
Memoria
31
12. Anillo
Memoria
32
3.3
33
10
12
(SB)
Distribucin 30-45 kV
Reparto
Transporte
50
15
30
66 kV
35
24
35
110 kV
28
12
44
132 kV
20
20
50
10
220 kV
13
18
35
13
33
33
17
17
400 kV
Memoria
34
A tiempo independiente
A tiempo dependiente
Memoria
35
Memoria
36
t=
Ip
1
Ia
Siendo:
Ip = intensidad de paso
Ia = intensidad de ajuste
, k = constantes de diseo
t = tiempo de operacin
37
Lo normal es que un rel ofrezca no slo una curva de actuacin, sino una
familia de ellas adecundose as la proteccin a las necesidades
particulares.
Memoria
38
Memoria
39
En la figura 4.1.3.2 puede verse que incluso con idnticos ajustes en los
tres rels A, B y C, la funcin de frenado por tensin establecera que
fuese el rel C el primero en actuar para el cortocircuito representado.
Memoria
40
(I2>I1)
Una vez ha disparado el interruptor del circuito (2), en el circuito (1) aumentar,
(en mayor o menor grado) la corriente y, si el cortocircuito no se elimina de una
manera natural, disparar el interruptor del circuito (1) al actuar su proteccin de
sobreintensidad.
Memoria
41
Por otro lado, no existira selectividad entre las protecciones 1b y 2b; en caso de
cortocircuito en uno de los circuitos alimentadores, por ejemplo el (2), la corriente
que circula a travs de las protecciones 1b y 2b sera prcticamente la misma y se
producira el disparo de ambos interruptores ya que, evidentemente, los ajustes de
sus protecciones seran idnticos.
Memoria
42
Memoria
43
Por esta razn se utilizan tensiones entre fases para polarizar rels
direccionales; los posibles tipos de conexin se definen por el ngulo en
que la tensin de polarizacin aplicada desfasa a la tensin de la fase a la
que est conectado el elemento de sobreintensidad.
Memoria
44
Memoria
45
Memoria
46
Memoria
47
En el caso de falta externa (Fig. 4.3.1), las corrientes de cortocircuito pueden ser
muy superiores a las normales. Por consiguiente, tambin los errores se
multiplican. Esto lleva a la conclusin de que el rel diferencial debe tener un
ajuste mnimo que garantice la estabilidad de la proteccin en ocasin de
cortocircuitos externos.
Memoria
48
Existe otro fenmeno que tambin puede influir sobre este tipo de protecciones: la
saturacin de los transformadores de intensidad. Esta saturacin puede producirse
bien por la propia magnitud de la corriente de cortocircuito o por la posible
componente asimtrica en la forma de onda. La desigual respuesta de los
transformadores produce falsas corrientes diferenciales. Para este problema
existen varias soluciones. La primera de ellas consiste en temporizar el disparo del
rel diferencial el tiempo suficiente (del orden de 0.5-0.8 s). Esta solucin es
inaceptable cuando la proteccin se aplica a equipos de gran responsabilidad y
costo (trafos y generadores), ya que el mantener 0.5 s un posible cortocircuito
interno puede dar lugar a grandes desperfectos.
Memoria
49
Para un reparto eficaz de cargas entre los secundarios de los T/I de ambos
extremos, lo ideal es que la longitud de los hilos pilotos entre los T/I y la
proteccin, a cada lado de sta, sean iguales.
Memoria
50
Memoria
51
de alta impedancia
de transductores lineales
con estabilizacin
Memoria
52
Memoria
53
La figura 4.4.2 ilustra las condiciones de falta interna. En este caso, la corriente
es saliente en ambos extremos. La combinacin de las seales local y remota da
como resultante una seal con huecos de 180, si se suponen en fase las f.e.m.
aplicadas en uno y otro extremo de la lnea.
Memoria
54
Memoria
55
Memoria
56
Los rels empleados para la deteccin de sobre y subtensin son, bsicamente los
mismos que los descritos para las protecciones de sobreintensidad, sustituyendo
las bobinas amperimtricas por voltimtricas. No obstante, debera matizarse que
en los rels de sobretensin es muy importante el factor de reposicin.
Memoria
57
Fig. 4.5.1 Falta monofsica RN en un sistema puesto a tierra. Las fases sanas
soportan una sobretensin, mientras que la fase afectada sufre una subtensin.
Las tensiones entre fases se mantienen estables.
Memoria
58
Memoria
59
Memoria
b)
60
Tipos de comunicacin:
1.- Sistemas de proteccin en subalcance
a)
con teledisparo
b)
permisivo
c)
con aceleracin
Memoria
a)
permisivo
b)
a bloqueo
c)
a desbloqueo
61
62
1.
2.
3.
Memoria
63
Memoria
64
Transformadores electromagnticos
Transformadores capacitivos
Memoria
65
5.2 Interruptores
Memoria
66
La fuente de energa que se utiliza para el mando de los interruptores es, casi
siempre, una tensin continua normalizada, utilizada tambin para alimentar los
rels estticos o los electromecnicos complejos (protecciones de distancia) por la
ventaja de poderse almacenar en bateras de acumuladores.
Memoria
67
acordes con las circunstancias. Para estos casos son tiles los registradores
cronolgicos y los equipos osciloperturbogrficos.
Son aquellos equipos que desempean una labor de automatizacin con influencia
sobre las protecciones, o en otros casos, condicionada a stas.
Memoria
68
El progresivo aumento de las cargas en las redes elctricas y los efectos de los
cortocircuitos sobre los grandes grupos de generacin van imponiendo unos
tiempos de eliminacin de las faltas imposibles de obtener sin la utilizacin de
protecciones de tipo cerrado, esto es, con intercambio de informacin entre los
estremos del elemento protegido.
Equipo de proteccin.
Equipo de teleproteccin.
Equipo de telecomunicacin.
Los sistemas analgicos son aquellos en los que se transmite una informacin
analgica entre los dos extremos para ser comparada con la informacin local
(comparacin de fases, diferencial, etc).
Memoria
69
Memoria
b)
70
Debido a los ruidos producidos en las lneas (descargas, efecto corona, etc.),
la relacin seal/ruido que se tiene en los equipos de transmisin es ms dbil a
medida que las longitudes de las lneas crecen, por ello, es recomendable no
utilizar este sistema para longitudes superiores a 200 km.
c)
d)
Enlace por fibra ptica. Una transmisin de este tipo est formada
bsicamente por un sistema transmisor ptico, una fibra ptica como medio de
transmisin y un receptor ptico que recibe y demodula la seal. Los emisores son
de diodos LED o semiconductores lser. Las principales ventajas de este tipo de
enlace son su total inmunidad a interferencias electromagnticas, total aislamiento
galvnico, gran ancho de banda y velocidad de transmisin, y su bajo nivel de
errores. En cuanto a sus desventajas, necesidad de repetidores para distancias
superiores a 30 km y su elevado coste.
Memoria
71
Memoria
72
Memoria
73
Para ese caso, aparte de las oportunas alarmas que den cuenta de una
situacin anmala, deber disponerse de un automatismo que al cabo del
tiempo permitido desconecte el transformador. Similar resultado se puede
Memoria
74
Memoria
75
Memoria
76
Para poder aplicar esta proteccin es condicin esencial que la cuba del
transformador est debidamente aislada de tierra. Se considera adecuado
un aislamiento mnimo de 25 .
Memoria
77
Memoria
78
Para evitar faltas intempestivas por faltas en media tensin externas, este
elemento se ajusta por encima de la mxima corriente de cortocircuito (en
alta tensin) para una falta en media tensin, de forma que slo actuar
para faltas internas en el lado primario del transformador (fig. 6.1.9.2)
Memoria
79
291)
Fig. 6.1.10.1 Protecciones de distancia en transformadores de
interconexin
Memoria
80
E
f
En un sistema elctrico, las lneas y cables tienen la misin de enlazar los centros
de generacin-transformacin con el consumo, adaptndose a las condiciones del
entorno rural o urbano.
La proteccin de estos elementos precisa de la mayor atencin, dado que son los
ms castigados del sistema. Esto es debido a que las lneas y cables estn
sometidos en permanencia a las consecuencias de los fenmenos meteorolgicos y
Memoria
81
Memoria
82
El nmero y disposicin de los rels que hay que utilizar depender del
tratamiento que tenga el neutro de la red. En el caso de netro aislado de
tierra, se utilizarn al menos dos rels de fases. En el resto de situaciones
con el neutro a tierra, se utilizarn dos o tres rels en las fases y uno en el
neutro.
Memoria
83
Conviene que los circuitos que hay que proteger sean limpios entre una
y otra estacin; es decir, no deben incluir derivaciones intermedias.
Memoria
84
Memoria
85
Memoria
86
Con esta conexin de los T/T, cualquier contacto a tierra en las barras o
en los elementos conectados a ellas- produce una tensin en los bornes del
rel. Para obtener la necesaria selectividad en la localizacin de la avera,
se suele utilizar un automatismo buscador, que consiste en ir
desconectando y conectando, secuencialmente, los equipos conectados a
las barras, hasta que tras unas de estas desconexiones desaparezca la
tensin en el equipo detector, identificando el circuito en falta.
Memoria
87
Otro medio para la deteccin de las faltas a tierra en las redes aisladas
consiste en usar el hecho de que todas las corrientes capacitivas del
sistema van hacia el defecto.
La corriente capacitiva que aportan las fases sanas de la lnea con falta retorna por
l conductor donde se ha producido el cortocircuito a tierra, al que se aade la
corriente capacitiva de las fases sanas de las restantes lneas conectadas a las
mismas barras. (Fig. 6.2.7.1)
Memoria
88
En las lneas de M.T., para detectar lo que se llama faltas resistentes (de
magnitud inferior al ajuste usual de las protecciones) se utiliza un rel de
sobreintensidad de tiempo independiente instalado en el neutro fsico de la
red, con un valor de intensidad de ajuste inferior al rel de neutro de las
lneas y superior a los valores capacitivos de la red; la temporizacin esta
comprendida entre 10 y 60 s. (Fig. 6.2.8.1)
Memoria
89
90
Por otra parte, al ser una proteccin de tipo cerrado (al igual qu la
proteccin diferencial longitudinal), precisa de una proteccin de apoyo o
reserva.
Memoria
91
Memoria
92
Los sistemas utilizados (en M.T.) dan una indicacin luminosa o acstica
como el resultado del paso de corriente de defecto por el lugar donde estn
ubicados. Estos detectores van abrazados al conductor y funcionan por la
cada de tensin producida en la porcin abrazada del conductor o por la
intensidad del campo magntico.
Memoria
93
Por tanto, los interruptores, los seccionadores lado barras y los propios
transformadores de medida se consideran parte de las barras colectoras.
Las estadsticas de sistemas elctricos muestran que las faltas en barras son poco
frecuentes. No obstante, los efectos de estas faltas sobre el sistema son ms graves
que los debidos a faltas que ocurren en lneas, generadores, etc.
a) Proteccin de sobreintensidad
Esta proteccin se aplica a subestaciones M.T. y consiste en llevar a un
rel de sobreintensidad la corriente suma de todos los terminales de
entrada de barras. El rel de sobreintensidad suele suele ser un rel de
tiempo dependiente, con elementos de medida en fases y neutro. (Fig.
6.3.1.1)
Memoria
94
b)
Proteccin de cuba
Memoria
Memoria
95
c)
96
Proteccin diferencial
a)
Memoria
97
b)
Memoria
98
escaln de medida.
c)
Memoria
99
Criterio diferencial:
Vigila la corriente diferencial I87B.
Tiene una pendiente de frenado variable
..En condiciones normales: I87B = 0. Pulsos +/- No acta.
..En falta interna: I87B >> 0. Pulsos +. Acta.
..En falta externa: I87B > 0. Pulsos +/- por ser externa. No
Memoria
Memoria
100
101
Memoria
102
Memoria
103
Memoria
104
Memoria
105
Proteccin de sobreintensidad
Memoria
106
b)
Memoria
107
c)
Proteccin de desequilibrio
Memoria
108
Memoria
109
Para hacer frente a estas situaciones, es necesario mejorar las protecciones, de tal
forma que se obtengan las siguientes prestaciones:
-
Memoria
110
Memoria
111
Memoria
112
Memoria
113
Los ajustes obtenidos para las protecciones principales deben ser verificados para
coordinar su actuacin como protecciones de respaldo. Esto significa que las
protecciones unitarias no requieren ninguna coordinacin puesto que solamente
operan en una zona de proteccin, mientras que las protecciones graduadas deben
ser coordinadas para verificar su actuacin como protecciones de respaldo en las
zonas de proteccin vecinas.
El anlisis de la operacin del sistema elctrico tiene por objetivo determinar las
mximas y mnimas corrientes de falta que deben servir para ajustar los rels y
determinar sus tiempos de operacin que permitan asegurar la adecuada
coordinacin de la proteccin. Para ello se debe considerar todas las condiciones
operativas, incluso aquellas que son de carcter temporal como la conexin de los
circuitos.
Memoria
114
Para determinar las corrientes de falta se debe simular todos los tipos de
cortocircuitos, algunos de los cuales pueden tener contacto a tierra a travs
de una resistencia de falta. Esta simulacin debe efectuarse en las barras de
las centrales y subestaciones, as como a lo largo de las lneas.
Memoria
115
En las lneas de transmisin se debe simular faltas por lo menos 25%, 50%
y 75% de la lnea. Las simulaciones de faltas sern de los siguientes tipos:
Faltas monofsicas a tierra sin resistencia de falta
Faltas monofsicas a tierra con alta resistencia de falta
Faltas bifsicas (fase-fase) con resistencia de falta
Faltas trifsicas sin resistencia de falta
Memoria
116
3.
Memoria
117
4.
Memoria
118
Memoria
119
Memoria
120
Memoria
121
Vistas todas las protecciones elctricas, resulta evidente, por el nmero elevado de
estas, el uso de estndares que faciliten la integracin de los sistemas de
proteccin.
Cada compaa posee los suyos y, para el diseo y el ajuste de los sistemas de
proteccin, en el caso de subestaciones de muy alta tensin, el estndar utilizado
en Espaa es el de Red Elctrica, ya que esta compaa est adquiriendo la
totalidad de las subestaciones de 400 y 220 kV.
Los criterios de coordinacin de ajustes son las directrices que permiten ajustar
los equipos de proteccin de manera que puedan detectar y eliminar cualquier
perturbacin con la mxima selectividad y rapidez, sin arrastrar a otros elementos
del sistema.
Los criterios de ajuste de las protecciones especifican la respuesta que debe dar un
equipo de proteccin ante variaciones de los parmetros fsicos del sistema
elctrico.
Tanto el diseo como los ajustes sern establecidos por los propietarios de las
instalaciones respectivas. En el caso de que no sean establecidos por el
propietario, la compaa encargada de la realizacin del proyecto decidir ese
diseo y esos ajustes atendiendo a sus estndares y pudiendo incluso mejorarlos
con recomendaciones vistas en el apartado 6 de la memoria.
Memoria
122
Memoria
123
El plan de expansin del sistema elctrico etope en abril de 2004 previ un pico
de demanda para el 2013 de 2.547 MW con una demanda de energa estimada de
10.690 GWH/ao frente a los actuales 676 MW y 3.250 GWh/ao.
Memoria
124
De Gilgel Gibe II saldrn dos lneas de 400 kV, una conectar con la subestacin
Gilgel Gibe 400/230/132/33 kV mientras que la segunda conectar con la
subestacin Sebeta II 400/230/33 kV.
Memoria
125
Memoria
126
Memoria
127
Todas las posiciones enumeradas anteriormente son las que hay que proteger
mediante un sistema de protecciones adecuado, teniendo en cuenta primeramente
espicificaciones del cliente y diseando el sistema utilizando los estndares de
Red Elctrica.
Memoria
128
Descripcin
Referencia
Uds
Proteccin de distancia
7SA5221-4DB90-4HR4-L0S
7SA5221-4DB90-4HR4-L0S
7PA3030-1
Descripcin
Referencia
Proteccin de distancia
7SA5221-4CB90-0EE0
Memoria
Uds
1
129
7SA5221-4CB90-0EE0
7UT6121-4EB92-1BA0-L0S
7PA3030-1
Regulador de tensin
TAPCON 230
Descripcin
Referencia
Uds
Proteccin de sobreintensidad
7SJ6222-4EB90-1FD0
7PA3030-1
Referencia
Uds
Descripcin
central)
Funciones incluidas: 87A, 87B
Proteccin de diferencial de barras (unidad 7SS5251-5FA01-1AA1
de campo)
Funciones incluidas: 87A, 87B, 50BF
Proteccin de sobreintensidad
7SJ6401-4EB91-1FA4-L0S
7PA3030-1
Memoria
Descripcin
Proteccin de distancia
Referencia
130
Uds
7SA5221-4DB90-4HR4-L0S
7SA5221-4DB90-4HR4-L0S
7PA3030-1
Descripcin
Referencia
7SJ6221-4EB90-1FC0-L0S
Uds
1
7UT6131-5EB91-1BA0-L0S
7PA3030-1
Regulador de tensin
TAPCON 230
33KV (1 posicin)
Descripcin
Referencia
Proteccin de sobreintensidad
7SJ6021-4EB30-1FA0
Uds
4
Descripcin
Referencia
Proteccin de sobreintensidad
7SJ6222-4EB90-1FD0
Memoria
Uds
1
131
7PA3030-1
Referencia
Uds
Descripcin
central)
Funciones incluidas: 87A, 87B
Proteccin de diferencial de barras (bay
7SS5251-5FA01-1AA1
7SJ6401-4EB91-1FA4-L0S
7PA3030-1
Referencia
Uds.
unitl)
Funciones incluidas: 87A, 87B, 50BF
Proteccin de sobreintensidad
Funciones incluidas: 50/51, 25
Rel de supervisin de circuito de disparo
SOFTWARE DE CONFIGURACIN
Descripcin
Memoria
132
1.
2.
3.
Memoria
133
4.
de la placa de caracteristicas):
Memoria
134
Potencia nominal
Relacin de transformacin en todas las tomas
Tensin de cortocircuito
Grupo de conexin
Indice horario
5.
7.
Subestacin
Potencia de
X/R monofsica
c/cto trifsica
mxima
mxima (MVA)
Memoria
2847
-108,63
2531
15,88
2531
18,5
Sebeta II 400 kV
1992
-564,82
Sebeta II 230 kV
2138
10,39
Sebeta I 230 kV
2281
10,62
Ghedo 230 kV
1869
8,65
Wolkite 230 kV
1574
8,75
135
Memoria
Xl
Bl
Gl
1,19591 0,83618332
5,98036
0,299636 3,33738269
48,38866
0,299636 3,33738269
48,38866
0,167214
0,020666
0,020666
16
Rc
Xc
Bc
0
-477370
-2,10E-06
0
-261251,3
-3,83E-06
0
-261251,3
-3,83E-06
Gc
infinita
infinita
infinita
Memoria
136
Xl
0,167214
1,19591
0,020666
0,299636
0,020666
0,299636
16
Rc
Xc
0
-477370
0
-261251,3
0
-261251,3
Bl
Gl
0,83618332
5,98036
3,33738269
48,38866
3,33738269
48,38866
Xl
0,180904
1,174594
0,034746
0,277341
0,034746
0,277341
2,5
Rc
Xc
0
-492169,3
0
-262187,4
0
-262187,4
Bl
Gl
0,90643322
0,022931
3,92821122 50,023007
3,92821122 50,023007
Bl
Gl
0,90643322
0,022931
3,92821122 50,023007
3,92821122 50,023007
Xl
0,180904
1,174594
0,034746
0,277341
0,034746
0,277341
2,5
Rc
Xc
0
-492169,3
0
-262187,4
0
-262187,4
Xl
Bc
-2,10E-06
-3,83E-06
-3,83E-06
Bc
-2,03E-06
-3,81E-06
-3,81E-06
Bc
-2,03E-06
-3,81E-06
-3,81E-06
Gc
infinita
infinita
infinita
Gc
infinita
infinita
infinita
Bl
Gl
1,215463 0,86431445
0,032971
0,307351 3,22821348 46,123606
0,307351 3,22821348 46,123606
0,201756
0,031598
0,031598
73,22
Rc
Xc
Bc
0
-412796,5
-2,18E-06
0
-242659,1
-3,96E-06
0
-242659,1
-3,96E-06
Gc
infinita
infinita
infinita
Xl
0,201756
1,215463
0,031598
0,307351
0,031598
0,307351
73,22
Rc
Xc
0
-412796,5
Gc
infinita
infinita
infinita
Bl
Gl
0,86431445
0,032971
3,22821348 46,123606
3,22821348 46,123606
Bc
Gc
-2,18E-06 infinita
Sebeta-Kaliti 230 kV
Secuencia
Homopolar
Directa
Inversa
Longitud de la lnea (km)
Secuencia
Homopolar
Directa
Inversa
Memoria
0
0
-242659,1
-242659,1
137
-3,96E-06 infinita
-3,96E-06 infinita
Xl
0,198647
1,239745
0,030568
0,298712
0,030568
0,298712
131,2
Rc
Xc
0
-403546,3
0
-222654,8
0
-222654,8
Bl
Gl
0,93254785
0,041857
3,12569874 44,235874
3,12569874 44,235874
Bl
Gl
0,93254785
0,041857
3,12569874 44,235874
3,12569874 44,235874
Xl
0,198647
1,239745
0,030568
0,298712
0,030568
0,298712
131,2
Rc
Xc
0
-403546,3
0
-222654,8
0
-222654,8
Xl
Bc
-2,23E-06
-3,47E-06
-3,47E-06
Bc
-2,23E-06
-3,47E-06
-3,47E-06
Gc
infinita
infinita
infinita
Gc
infinita
infinita
infinita
Bl
Gl
1,289849 0,97865432
0,041857
0,278946 3,08765032 40,089547
0,278946 3,08765032 40,089547
0,216781
0,026098
0,026098
81
Rc
Xc
e
Gc
0
-436790,3
-2,55E-06 infinita
0
-265478,8
-3,86E-06 infinita
0
-265478,8
-3,86E-06 infinita
Xl
Bl
Gl
1,457896 0,89569876
0.03876
0,274512 3,98765874 42,725634
0,274512 3,98765874 42,725634
0,187601
0,028968
0,028968
98
Rc
Xc
Bc
0
-415646,2
-2,45E-06
0
-245690,8
-3,35E-06
0
-245690,8
-3,35E-06
Gc
infinita
infinita
infinita
Xl
Bl
Gl
1,237731 0,80793021
0,069421
0,356134 2,85412397 48,758964
0,356134 2,85412397 48,758964
0,238596
0,035692
0,035692
35
Rc
Xc
Bc
0
-480797,5
-2,04E-06
0
-378940,3
-2,64E-06
0
-378940,3
-2,64E-06
Memoria
138
Gc
infinita
infinita
infinita
- Autotransformador 400/230/38 kV
Memoria
139
- Barras de 400 kV
Memoria
140
- Barras de 230 kV
Potencia nominal: 45.11 Mvar
Tensin nominal: 230 kV
Numero de condensadores: 14//14 por fase->un total de 86
Tensin nominal, potencia y capacidad por unidad de condensador:
9485 V
536 kVar
19.0 uF
Memoria
141
142
Este es un documento que tiene por objeto hacer el clculo de los valores de ajuste
de las protecciones elctricas de la subestacin Sebeta II del presente proyecto.
Para los clculos, se han utilizado los datos proporcionados en el apartado 9.3 de
la memoria.
Memoria
143
Arranque de 1 o 2 zona
Mnima tensin
Memoria
144
Ramas de rbol
Nidos
Cada de rayos
Funcin 21:
-Datos de TT:
400000/100V
-Datos de TI:
Memoria
145
1600/1 A
- Datos lneas:
Longitud (Km) R (Omh/Km) X (Omh/Km)
L1: SII-GGII
Z1
185
Z0
L2: GG-GGII
Z1
28
Z0
L3: GG-Ghedo
Z1
131,2
Z0
0,02950089
0,289654
0,178072
1,12358
0,04465
0,265088
0,153078
1,071135
0,030568
0,298712
0,198647
1,239745
L1: SII-GGII
L2: GG-GGII
L3: GG-Ghedo
SECUNDARIO
R (Ohm)
X (Ohm)
R (Ohm)
X (Ohm)
PHI ()
Z1L
5,4577
53,586
2,1831
21,4344
84,18
Z0L
32,9433
207,8623
13,1773
83,1449
80,99
Z1L
1,2502
7,4225
0,5001
2,969
80,44
Z0L
4,2862
29,9918
1,7145
11,9967
81,87
Z1L
4,0105
39,191
1,6042
15,6764
84,16
Z0L
26,0625
162,6545
10,425
65,0618
80,9
-Alcances:
PRIMARIO
Zona 1
Zona 2
Memoria
0,85 *L1
0,5 *L2 + L1
SECUNDARIO
R (Ohm)
X (Ohm)
R (Ohm)
X (Ohm)
PHI ()
4,639
45,5481
1,8556
18,2192
84,18
6,0828
57,2973
2,4331
22,9189
83,94
8,7132
73,1815
3,4853
-Caractersticas de disparo:
Alcance (Ohm. BT)
Zona 1
18,31
Zona 2
23,05
300
Zona 3
29,48
600
Funcin 79 (reenganchador):
- Reenganche monofsico
Nmero de ciclos de reenganche: 3
Tiempo de 1 ciclo: 3s
Tiempo de 2 ciclo: 30s
Tiempo de 3 ciclo: 60s
Tiempo de reinicio: 120s
Memoria
Temporiz. (ms.)
146
29,2726
83,21
147
podra haber colocado una proteccin con las mismas funciones que la principal,
pero distinta marca, para que en caso de un fallo particular de la proteccin
principal, la secundaria est lista para actuar, en cambio, si son iguales, se podra
producir el mismo fallo y no actuar ninguna de las dos.
Memoria
En esta posicin, consideramos las dos posiciones de lnea de 230 kV con los
mismos ajustes, debido a que los datos proporcionados por el cliente de las
caractersticas de las lneas son iguales.
Funcin 21:
-Tensin nominal: 230kV
-Datos de TT:
230000/100V
-Datos de TI:
800/1 A
Memoria
148
149
-Datos lneas:
Longitud (Km) R (Omh/Km) X (Omh/Km)
L1: SII-S
Z1
16
Z0
L2: S-Gafarsa
Z1
81
Z0
L3: G-Hossiana
Z1
35
Z0
0,020666
0,299636
0,167214
1,19591
0,026098
0,278946
0,216781
1,289849
0,035692
0,356134
0,238596
1,237731
L1: SII-S
L2: S-Gafarsa
L3: G-Hossiana
-Alcances:
Memoria
SECUNDARIO
R (Ohm)
X (Ohm)
R (Ohm)
X (Ohm)
PHI ()
Z1L
0,3307
4,7942
0,115
1,6675
86,05
Z0L
2,6754
19,1346
0,9306
6,6555
82,04
Z1L
2,1139
22,5946
0,7353
7,859
84,66
Z0L
17,5593
104,4778
6,1076
36,3401
80,46
Z1L
1,2492
12,4647
0,4345
4,3355
84,28
Z0L
8,3509
43,3206
2,9047
15,068
79,09
150
SECUNDARIO
R (Ohm)
X (Ohm)
R (Ohm)
X (Ohm)
PHI ()
0,2811
4,0751
0,0978
1,4174
86,05
Zona 2
0,5 *L2 + L1
1,3877
16,0915
0,4827
5,597
85,07
Zona 3
3,0692
33,6212
1,0675
11,6943
84,78
-Caractersticas de disparo:
Alcance (Ohm. BT)
Temporiz. (ms.)
Zona 1
1,42
Zona 2
5,62
300
Zona 3
11,74
600
Funcin 79 (reenganchador):
- Reenganche monofsico y trifsico.
Nmero de ciclos de reenganche: 3
Tiempo de 1 ciclo: 3s
Tiempo de 2 ciclo: 30s
Tiempo de 3 ciclo: 60s
Tiempo de reinicio: 120s
Memoria
151
podra haber colocado una proteccin con las mismas funciones que la principal,
pero distinta marca, para que en caso de un fallo particular de la proteccin
principal, la secundaria est lista para actuar, en cambio, si son iguales, se podra
producir el mismo fallo y no actuar ninguna de las dos.
Memoria
152
Proteccin de sobreintensidad
Funciones: 51, 51N
Referencia: 7SJ6021-4EB30-1FA0
Memoria
153
En esta posicin, pueden existir defectos externos e internos. Los internos son los
propios del transformador: deterioro del ncleo magntico, faltas entre espiras de
una fase, corte de arrollamientos, faltas de aislamiento, defectos en el circuito de
aceite. Estos defectos se eliminan con protecciones equipadas en el propio
transformador como son en el caso de nuestro transformador, las siguientes:
-
Memoria
154
Las protecciones elctricas utilizadas en esta posicin para detener dichos efectos:
-
devanados por:
-
Memoria
Memoria
155
156
Memoria
Datos Trafo:
Fabricante:
AREVA
N Serie:
N de tomas (+/-):
Potencia:
250 MVA
Tensin AT:
400 kV
Tensin BT:
230 kV
Conexin:
Regulacin:
AT
11
Tensin toma:
1,35 %
Lado BT:
800 A
YNd11
Datos T.I.:
Lado AT:
400 A
1A
Ajustes de Configuracin:
Grupo de conexin:
Lado AT:
Lado BT:
D11
Memoria
1A
157
158
Filtro Homopolar:
Lado AT:
SI
Lado BT:
SI
Ajustes de Proteccin:
Datos nominales:
Potencia (MVA) Tensin (kV)
250
459,4
314,1871295
0,785467824
250
400
360,8439182
0,902109796
250
340,6
423,7744195
1,059436049
250
230
627,5546404
0,453435434
Unidad
Diferencial:
Lado AT:
0,902109796 In
(0,1-2,5)
Lado BT:
0,453435434 In
(0,1-2,5)
Memoria
Lado 400kV
Int. AT (A)
Int. BT (A)
Int. Diferenial
159
Error (%)
(A)
Toma mxima: 0,785467824
0,906870868
0,121403044
0,785467824 15,45614476
Toma media:
0,902109796
0,906870868
0,004761072
0,902109796 0,527770797
0,906870868
0,152565181
0,906870868 16,82325308
Ajuste de la pendiente:
16,82325308 %
5%
2%
Error total:
23,82325308 %
Toma mxima:
0,121403044
0,785467824
ZONA II
0,353866956
NO
Toma media:
0,004761072
0,902109796
ZONA II
0,383027449
NO
Toma mnima:
0,152565181
0,906870868
ZONA II
0,384217717
NO
Unidad Diferencial:
Habilitacin de Unidad:
SI
0,9
0,45
0,27
(0,5 - 5)
25
(15 - 50)
Pendiente (%):
Memoria
25
25
Temporizacin (seg.):
Id> (p.u.):
0,2
Id>> (p.u.):
Funcin 21:
- Tensin nominal: lado de 400kV
-Datos de TT:
400000/100V
-Datos de TI:
Memoria
160
161
400/1 A
- Datos lneas:
Longitud (Km)
(Omh/Km)
(Omh/Km)
0,02950089
0,289654
0,178072
1,12358
0,04465
0,265088
0,153078
1,071135
0,026098
0,278946
0,216781
1,289849
Z1
Z0
L2: SII-S
Z1
28
Z0
L3: S-Gafarsa
Z1
81
Z0
L2: SII-S
L3: S-Gafarsa
Memoria
SECUNDARIO
R (Ohm)
X (Ohm)
R (Ohm)
X (Ohm)
PHI ()
Z1L
0,0295
0,2897
0,003
0,029
84,19
Z0L
0,1781
1,1236
0,0178
0,1124
80,99
Z1L
1,2502
7,4225
0,125
0,7423
80,44
Z0L
4,2862
29,9918
0,4286
2,9992
81,87
Z1L
2,1139
22,5946
0,2114
2,2595
84,66
17,5593
104,4778
1,7559
162
10,4478
80,46
-Alcances:
PRIMARIO
Zona 1
0,85 *L1
SECUNDARIO
R (Ohm)
X (Ohm)
R (Ohm)
X (Ohm)
PHI ()
0,0251
0,2462
0,0025
0,0246
84,18
Zona 2
0,5 *L2 + L1
0,6546
4,001
0,0655
0,4001
80,71
Zona 3
2,3367
11,587
0,2337
1,1587
78,6
-Caractersticas de disparo:
Temporiz.
Alcance (Ohm. BT)
(ms.)
Zona 1
0,02
Zona 2
0,41
300
Zona 3
1,18
600
Funcin 21:
- Tensin nominal: lado de 230kV
-Datos de TT:
230000/100V
-Datos de TI:
800/1 A
- Datos lneas:
Longitud (Km) R (Omh/Km) X (Omh/Km)
L1: Trafo SII
Z1
Z0
L2: SII-GGII
Z1
185
Z0
L3: GG-Ghedo
Z1
Z0
Memoria
28
0,025
7,3
0,178072
1,12358
0,02950089
0,289654
0,178072
1,12358
0,04465
0,265088
0,153078
1,071135
163
164
L2: SII-GGII
L3: GG-Ghedo
SECUNDARIO
R (Ohm)
X (Ohm)
R (Ohm)
X (Ohm)
PHI ()
Z1L
0,025
7,3
0,0087
2,5391
89,8
Z0L
0,1781
1,1236
0,0619
0,3908
80,99
Z1L
5,4577
53,586
1,8983
18,6386
84,18
Z0L
32,9433
207,8623
11,4585
72,2999
80,99
Z1L
1,2502
7,4225
0,4349
2,5817
80,44
Z0L
4,2862
29,9918
1,4909
10,4319
81,87
-Alcances:
PRIMARIO
SECUNDARIO
R (Ohm)
X (Ohm)
R (Ohm)
X (Ohm)
PHI ()
Zona 1 0,85*L1
0,0213
6,205
0,0074
2,1583
89,8
Zona 2
0,5*L2 + L1
2,7539
34,093
0,9579
11,8584
85,38
Zona 3
0,5*L3 + L1+ L2
6,1078
64,5973
2,1245
22,4686
84,6
-Caractersticas de disparo:
Memoria
Temporiz. (ms.)
Zona 1
2,16
Zona 2
11,9
300
Zona 3
22,57
600
Datos Trafo:
Memoria
165
Fabricante:
ZTR
N Serie:
Potencia:
25 MVA
Tensin AT:
230 kV
Tensin BT:
33 kV
Conexin:
166
Regulacin:
AT
N de tomas (+/-):
11
Tensin toma:
1,5 %
Lado BT:
600 A
YNd11
Datos T.I.:
Lado AT:
100 A
1A
1A
Ajustes de Configuracin:
Grupo de conexin:
Lado AT:
Lado BT:
D11
Filtro Homopolar:
Lado AT:
SI
Lado BT:
SI
Memoria
167
Ajustes de Proteccin:
Datos nominales:
Potencia (MVA) Tensin (kV)
25
267,95
53,86735111
0,538673511
25
230
62,75546404
0,62755464
25
192,05
75,15624436
0,751562444
25
33
437,3865676
0,421374343
Unidad Diferencial:
Lado AT:
0,62755464 In
(0,1 - 2,5)
Lado BT:
0,421374343 In
(0,1 - 2,5)
Int. AT (A)
Int. BT (A)
Int. Diferenial
Error (%)
(A)
Toma mxima:
0,538673511
0,632061514
0,093388003
0,538673511
17,33666141
Toma media:
0,62755464
0,632061514
0,004506873
0,62755464
0,718164302
Toma mnima:
0,751562444
0,632061514
0,11950093
0,632061514
18,90653476
Ajuste de la pendiente:
Memoria
18,90653476 %
5%
2%
Error total:
168
25,90653476 %
Operac. Unidad
Toma mxima:
0,093388003
0,538673511
ZONA II
0,257102053
NO
Toma media:
0,004506873
0,62755464
ZONA II
0,283766392
NO
Toma mnima:
0,11950093
0,632061514
ZONA II
0,285118454
NO
Unidad Diferencial:
Habilitacin de Unidad:
SI
0,63
0,42
0,19
Pendiente (%):
30
30
30
Temporizacin (seg.):
Unidad Instantnea:
Habilitacin de Unidad:
Unidad Instantnea:
Temporizacin (seg.):
Memoria
SI
8 * ITOMA
0
Id> (p.u.):
0,2
Id>> (p.u.):
Proteccin de sobreintensidad
Memoria
169
170
-Temporizacin: 0ms
Memoria
171
Proteccin de sobreintensidad
Memoria
172
-Arranque: 0.3 A
-Temporizacin: cuva inversa ndice k = 0.1
173
Las barras de las subestaciones son crticas en la red, por ello el sistema de
protecciones debe ser fiable:
-
Memoria
174
Memoria
Memoria
175
10. ANEXOS
10.1 Simbologas tpicas.
I>
Memoria
176
177
control, rel de tensin, interruptor de flotador, etc., que sirve para poner el
aparato en operacin o fuera de servicio, bien directamente o a travs de
dispositivos, tales como rels de proteccin retardados
2 Rel de cierre o arranque con demora de tiempo es el que da la demora de
Memoria
178
circuito en shunt entre los extremos de cualquier pieza o aparato (excepto una
resistencia) tal como el campo de una mquina, un condensador o una reactancia.
Esto excluye los dispositivos que realizan las funciones de shunt necesarias para
arrancar una mquina por los dispositivos 6 42, o su equivalente, y tambin
Memoria
179
cerrar los circuitos que sirven para aumentar o disminuir la velocidad de una
mquina.
19 Contactos de transicin de arranque a marcha normal. Su funcin es hacer
o motor, que se utiliza en circuitos de vaco, aire, gas, aceite, agua o similares.
21 Rels de distancia es el que funciona cuando la admitancia, impedancia o
dos circuitos de alterna estn dentro de los lmites deseados de tensin, frecuencia
o ngulo de fase, lo cul permite o causa la puesta en paralelo de estos circuitos.
26 Dispositivo trmico es el que funciona cuando la temperatura del campo en
Memoria
180
valor prerreglado.
28 Detector de llama. Su funcin es detectar la existencia de llama en el piloto o
Memoria
181
elevar, bajar o desviar las escobillas de una mquina, o para cortocircuitar los
anillos rozantes.
36 Dispositivo de polaridad es el que acciona o permite accionar a otros
mecnicas anormales (excepto las que suceden a los cojinetes de una mquina,
funcin 38), tales como vibracin excesiva, excentricidad, expansin choque, etc.
40 Rel de campo/prdida de excitacin es el que funciona a un valor
Memoria
182
Memoria
183
Memoria
184
Memoria
185
bajo el dispositivo 30 que se utiliza para accionar u operar en unin de una alarma
visible o audible.
75 Mecanismo de cambio de posicin se utiliza para cambiar un interruptor
un interruptor de ca.
80 Rel de flujo lquido o gaseoso acta para valores dados de la magnitud del
Memoria
186
frenado por una seal y se usa en combinacin con una proteccin direccional que
funciona con equipos de transmisin de onda portadora o hilos piloto de cc.
86 Rel de enclavamiento es un rel accionado elctricamente con reposicin a
mano o elctrica, que funciona para parar y mantener un equipo un equipo fuera
de servicio cuando concurren condiciones anormales.
87 Rel de proteccin diferencial es el que funciona sobre un porcentaje o
Memoria
187
excitacin de la mquina.
94 Rel de disparo o disparo libre es el que funciona para disparar o permitir
CL
posicin de
CS
Memoria
cierre)
Conmutador de control
188
Rel de descenso
OP
posicin abierta)
PB
Pulsador
Rel de subida
Rel auxiliar
Nota: El control de un interruptor con el llamado esquema de control del rel XY, el rel de X es el dispositivo cuyos contactos principales son usados para
energizar la bobina de cierre o el dispositivo que, de alguna manera, como la
liberacin de la energa acumulada, causa el cierre del interruptor. Los contactos
del rel Y proporcionan una funcin antibombeo al interruptor.
Aire y Amperios
Corriente
Electrolito
Nivel o lquido
Potencia o presin
Memoria
PF
Factor de potencia
Aceite
Velocidad
Temperatura
VAR
Potencia reactiva
VB
Vibracin
Agua o Vatios
189
AC
Corriente alterna
AN
nodo
BK
Freno
BP
Bypass
CA
Ctodo
Descarga
DC
Corriente continua
Excitatriz
Memoria
Calentador o albergue
lnea o lgica
Motor o contador
Reactancia o rectificador
Sincronizacin o secundario
Transformador o tiratrn
TH
TI
TM
Telemetro
Unidad
190
- Letras que denotan las partes de los dispositivos principales, divididas en dos
categoras:
Memoria
191
- Todas las partes, tales como las que se indican, excepto los contactos auxiliares,
conmutadores de posicin, fines de carrera y conmutadores de posicin, los
cules se tratarn por separado.
BK
Freno
Bobina o condensador
CC
Bobina de cierre
HC
Bobina de retencin
Motor de operacin
ML
MS
Solenoide
SI
Sellado
TC
Bobina de disparo
Vlvula
Memoria
192
mecanismo, el cual est cerrado cuando los puentes del mecanismo estn
bloqueados despus de la operacin de apertura del interruptor.
LS
Memoria
tqc
193
cierre de la vlvula.
tqo
Aceleracin o automtica
Bloque o apoyo
Cerrado o fro
Emergencia o conectado
Cada o adelante
Caliente o alta
HR
Reposicin manual
HS
Alta velocidad
Manual
Abierto
OFF
Desconectado o parado
ON
Conectado o en marcha
Polarizante
Memoria
Transmisin o balanceo
Prueba o disparo
TDC
Cierre retardado
TDO
Apertura retardada
Arriba
194
- Nmero de sufijos:
Si dos o ms dispositivos con el mismo numero de funcin y sufijo estn
presentes, estos pueden distinguirse por sufijos numerados, como por ejemplo,
4X-1, 4X-2 y 4X-3, cuando sea necesario.
- Dispositivos realizando ms de una funcin
Si un dispositivo realiza dos funciones relativamente importantes en un equipo en
el que se desean identificar ambas funciones, puede usarse una funcin de doble
numero y nombre, tal como rel instantneo de sobreintensidad y temporizado
50/51.
Caractersticas generales:
Memoria
195
Funciones de proteccin:
Funcin eco.
Memoria
196
sobretensin. (27W)
curvas de disparo I(t) de tiempo definido o curvas inversas. (50, 50N, 51, 51N).
Curvas ANSI/IEEE
Medidas en servicio:
Potencia activa, P
Potencia reactiva Q
Potencia aparente S
Factor de potencia
Frecuencia
Autosupervisin.
previamente definidos.
Memoria
197
seleccionables.
homopolar.
Funciones opcionales
Verificacin de sincronismo ( 25 )
Memoria
198
Funciones de control
Referencias:
7SA522*-*****-****
Memoria
199
Memoria
200
Caractersticas generales:
Memoria
201
7SJ641/2/5
Memoria
202
Funciones incluidas:
Medidas de servicio, I1, I2, I3, IN, f, cos phi; Usinc, U1, U2, U3, UN, U12, U13,
Autosupervisin.
Paquetes multifuncin
Opciones
Memoria
203
Funciones de control
Comunicaciones
Memoria
204
Memoria
205
Caractersticas generales:
Memoria
206
Funciones incluidas:
Memoria
207
Medidas de servicio, I1,I2,I3,IN,f, cos phi; U1, U2, U3,UN, U12, U13, U23, P, Q, S
Autosupervisin.
Paquetes multifuncin.
Opciones
Funciones de control
Memoria
208
Memoria
209
Medida/oscilografa (*******-*****-1***-***):
Oscilofrafa
Multifuncin con sincronizacin (*******-*****-*FC4-***):
Multifuncin FC
-Proteccin de sobreintensidad trifsica de fase (50/51).
-Proteccin de sobreintensidad de neutro (50N/51N).
-Proteccin de sobrecarga por imagen trmica.(49)
-Proteccin de fallo de interruptor (50 BF)
-Proteccin contra desequilibrios de cargas.(46)
-Supervisin del circuito de disparo (74TC)
-Funcin de bloqueo y rearme (86)
-Determinacin direccional de sobreintensidad fases y tierra
(67/67N)
-Sentido de giro (47)
Con funcin 25 (4)
Memoria
210
Memoria
211
direccional
faltas
tierra
en
redes
aisladas/compensadas (67Ns)
-Tensin de desplazamiento (64)
Con funcin 25 (4)
Caractersticas generales:
Memoria
212
Funciones incluidas:
la sobrecarga.(49)
excesivamente largos.
Autosupervisin.
interruptor.
Memoria
Referencia:
213
7SJ602*-**B**-**A*
Memoria
214
Caractersticas generales:
Memoria
215
Funciones incluidas:
Autosupervisin.
Funciones especficas
sensibilidad de ajuste.(87H)
Memoria
216
Funciones opcionales
Funciones de control
Memoria
Referencia:
217
7UT613*-*****-**A0
Memoria
218
Memoria
219
Medida selectiva por fase por cada una de las secciones de barras.
Memoria
220
Tiempo de disparo: 15 ms
durante 3 ms.
Chekzone).
DIGSI4.
Central.
12 Secciones de Barras.
Memoria
16 Acoplamientos Transversales.
24 Seccionadores Longitudinales.
221
ptica.
Osciloperturbografa
valores de medida.
Memoria
222
interruptor.
campo.
1,2 Mbaud
Memoria
223
Frecuencia (*****2*-*****-****-***):
50/60 Hz
Memoria
224
Frecuencia (*****2*-*****-****-***):
50/60 Hz
Tensin auxiliar (*******-4****-****-***):
110/125Vcc
Armazn (*******-*A***-****-***):
ES902C
Idioma (*******-**B**-****-***):
Ingls britnico
Tipo de puerto de comunicacin posterior para comunicacin con el sistema de
control y protocolo de comunicacin deseado (*******-***92-****-L0R):
IEC 618506), 100 Mbit Ethernet,
Tipo de puerto de comunicacin posterior para DIGSI: RS485
Equipado con (*******-*****-*B**-***):
16 posiciones
Memoria
225
Armazn (*******-*F***-****):
7XP2040-2
Funciones adicionales (*******-*****-1***):
Con proteccin de sobrecorriente
Caractersticas:
Construccin mecnica
Frecuencia nominal : 50 Hz
Memoria
Referencia:
7PA30*0-*
Referencia: 7XS5402-0AA0
Soporte: CD-Rom
Idioma: Espaol, Ingls, Alemn, Francs,
Software DIGSI v3.32 incluido en la licencia
Requerimientos
Software
Sistemas operativos:
Windows 95,
Windows 98 o
Windows NT
Hardware
32 Mbyte de RAM
Mdulos incluidos :
Memoria
226
227
de subestacin
1- Estructura
Memoria
228
Memoria
229
2- Cableado
Memoria
230
11. BIBLIOGRAFA
Memoria
PLANOS
LISTA DE PLANOS
PLANO N1 Esquema unifilar subestacin Sebeta II 400/230/33 kV
PLANO N2 Esquema layout Sebeta II 400/230/33 kV
PLANO N3 Esquema de medida y proteccin. Posicin banco de condensadores
230 kV
PLANO N4 Esquema de medida y proteccin. Posicin acoplamiento de barras
230 kV
PLANO N5 Esquema de medida y proteccin. Posicin autotransformador AT-2
230 kV
PLANO N6 Esquema de medida y proteccin. Posicin autotransformador AT-3
230 kV
PLANO N7 Esquema de medida y proteccin. Posicin de lnea de 230 kV
PLANO N8 Esquema de medida y proteccin. Posicin de lnea de 230 kV
PLANO N9 Esquema de medida y proteccin. Posicin de barras de 230 kV
PLANO N10 Esquema de medida y proteccin. Posicin de banco de
condensadores de 400 kV
PLANO N11 Esquema de medida y proteccin. Posicin de lnea de 400 kV
PLANO N12 Esquema de medida y proteccin. Posicin de autotransformador
AT-2 400 kV
PLANO N13 Esquema de medida y proteccin. Posicin de autotransformador
AT-3 400 kV
PLANO N14 Esquema de medida y proteccin. Posicin acoplamiento de barras
400 kV
PLANO N15 Esquema de medida y proteccin. Posicin de barras de 400 kV
PLIEGO DE CONDICIONES
GENERALES
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
PLIEGO DE CONDICIONES
TCNICAS
10
11
12
13
14
15
16
17
18
19
20
PRESUPUESTO
Lnea 400 kV
Uds.
2
1
Descripcin
Referencia
Proteccin de distancia
7SA5221-4DB90-4HR4
Rel de supervisin de circuito 7PA3030-1
de disparo
SUBTOTAL
Precio
Unitario
()
8.914,50
148,90
Importe
Total
()
17.829,0
148.90
17.977,90
Autotransformador 400/230 kV
Uds.
Descripcin
4
2
4
Proteccin de distancia
Proteccin diferencial de trafo
Rel de supervisin de circuito
de disparo
Regulador de tensin
Referencia
7SA5221-4CB90-0EE0
7UT6131-4EB92-1BA0
7PA3030-1
TAPCON 230
SUBTOTAL
Precio
Importe
Unitario
Total
()
()
8.046,20 32.184,70
4.091,40 8.182,80
148,90
595,60
3.973,50
7.947,00
48.909,90
Precio
Unitario
()
2.696,00
148,90
Importe
Total
()
2.696,00
148,90
1
1
Descripcin
Referencia
2.844,90
Barras 400 kV
Uds.
Descripcin
Proteccin de diferencial de
barras (unidad central)
Proteccin de diferencial de
barras (unidad de baha)
Proteccin de sobreintensidad
Rel de supervisin de circuito
de disparo
5
1
1
7SS5220-4AB92-1AA0
Precio
Importe
Unitario
Total
()
()
42.969,60 42.969,60
7SS5251-5FA01-1AA1
7.090,70 35.453,60
7SJ6401-4EB91-1FA4
7PA3030-1
3.596,50
148,90
Referencia
SUBTOTAL
Mediciones y presupuestos
3.596,50
148,90
82.168,60
Lnea 230 kV
Uds.
4
2
Descripcin
Referencia
Proteccin de distancia
7SA5221-4DB90-4HR4
Rel de supervisin de circuito 7PA3030-1
de disparo
SUBTOTAL
Precio
Importe
Unitario
Total
()
()
8.914,50 35.658,00
148,90
297,80
35.955,80
Autotransformador 230/33 kV
Uds.
Descripcin
Proteccin de sobreintensidad
de respaldo (lado de 230 kV)
Proteccin diferencial de trafo
Rel de supervisin de circuito
de disparo
Regulador de tensin
1
2
1
7SJ6221-4EB90-1FC0
Precio
Unitario
()
2.697,00
Importe
Total
()
2.697,00
7UT6131-5EB91-1BA0
7PA3030-1
4.091,40
148,90
4091,40
297,80
TAPCON 230
SUBTOTAL
3.973,50
3.973,50
11.059,60
Precio
Unitario
()
1.544,70
Importe
Total
()
6.178,80
6.178,80
Precio
Unitario
()
2.697,00
148,90
Importe
Total
()
2.697,00
148,90
Referencia
33 kV
Uds.
Descripcin
Referencia
1
1
Descripcin
Referencia
Mediciones y presupuestos
2.845,90
Barras 230 kV
Uds.
Descripcin
Proteccin de diferencial de
barras (unidad central)
Proteccin de diferencial de
barras (unidad de baha)
Proteccin de sobreintensidad
Rel de supervisin de circuito
de disparo
7
1
1
7SS5220-4AB92-1BA0
Precio
Importe
Unitario
Total
()
()
42.969,60 42.969,60
7SS5251-5FA01-1AA1
7.090,70 49.635,00
7SJ6401-4EB91-1FA4
7PA3030-1
3.596,50
148,90
Referencia
SUBTOTAL
3.596,50
148,90
96.350,00
Software de configuracin
Uds.
Descripcin
Referencia
Software de configuracin
DIGSI
7XS5402-0AA00
Precio
Unitario
()
4.405,90
TOTAL PROTECCIONES
COSTE ()
Suministros
308.698,10
Ingeniera
103.896,20
Supervisin
51.577,00
Montaje
72.231,60
Puesta en servicio
68.954,30
Transporte
12.590,00
TOTAL
Mediciones y presupuestos
617.947,20
Importe
Total
()
4.405,90
308.698,10