JOSE ANTONIO DE LA CRUZ QUISPE Y ESPOSA NANCY CAMAYO PIÑAS
Proyecto: VIVIENDA BIFAMILIAR Asunto: LICENCIA DE EDIFICACION Ubicación: CALLE ROSITA Y PASAJE LAS FUCSIAS Mz "A" Lt "4" Profes. Responsable.: ARQ. TEODORO SANTOS POMAYAY INGA
CALCULO DE CARGAS ELECTRICAS : VIVIENDA BIFAMILIAR
PISO AMBIENTE AREA C. UNIT. PI FD M.D. (Watts) M.D. + FACTOR DE INTENSIDAD DISEÑO CONDUCTOR TABLERO MEDIDOR (m2) W/m2 (Watts) SUBTOTAL TOTAL + 20% SIMULT. 0.60 AMPERIOS CORRIENTE TUBERIA DE DIST. 18.84 25.0 471.00 100% 471.00 CARGA ESPECIAL: M-1 CUARTO AZOTE LAVADO Y 1 LAVADORA 700.00 25% 175.00 I= MD 1545.12 2-1x4mm2THW fi ∅ 46mm PVC-SAP TG-02 A PLANCHADO 1 THERMA ELECTRICA 0.00 100% 0.00 K V cos F 220*0.82 2-1x4mm2THW fi 46mm ∅ PVC-SAP CARGA MOVIL 1500.00 100% 1500.00 2575.20 Watts 1545.12 Watts 8.56 Amp 10.71 73.62 25.0 1840.50 100% 1840.50 CARGA ESPECIAL: M-1 3er. 1 COCINA ELECTRICA 3000.00 80% 2400.00 I= MD 5069.16 2-1x4mm2THW fi DEP N° 201 TG-02 PISO 1 LAVADORA 700.00 25% 175.00 ∅ 80mm PVC-SAP 2-1x4mm2THW fi 80mm 1 CALENTADOR DE AGUA 4500.00 25% 1125.00 K V cos F 220*0.82 PVC-SAP ∅ CARGA MOVIL 1500.00 100% 1500.00 8448.60 Watts 5069.16 Watts 28.10 Amp 35.12 73.62 25.0 1840.50 100% 1840.50 CARGA ESPECIAL: M-1 2do. 1 LAVADORA 700.00 25% 175.00 I= MD 3341.16 2-1x4mm2THW fi TD-01 PISO ∅ 80mm PVC-SAP 2-1x4mm2THW fi 80mm 1 CALENTADOR DE AGUA 4500.00 25% 1125.00 K V cos F 220*0.82 ∅ PVC-SAP VIVIENDA CARGA MOVIL 1500.00 100% 1500.00 5568.60 Watts 3341.16 Watts 18.52 Amp 23.15 FAMILIAR 46.98 25.0 1174.50 100% 1174.50 CARGA ESPECIAL: M-1 1 COCINA ELECTRICA 3000.00 80% 2400.00 I= MD 4463.64 2-1x4mm2THW fi TG-02 ∅ 80mm PVC-SAP 2-1x4mm2THW fi 80mm 1 CALENTADOR DE AGUA 4500.00 25% 1125.00 K V cos F 220*0.82 ∅ PVC-SAP CARGA MOVIL 1500.00 100% 1500.00 7439.40 Watts 4463.64 Watts 24.74 Amp 30.93 20.77 5.0 103.85 100% 103.85 M-1 CARGA ESPECIAL: 2-1x7.5mm2THW fi COCHERA 1 COCINA ELECTRICA 0.00 80% 0.00 I= MD 1154.77 TG-02 ∅ 34mm PVC-SAP 2-1x7.5mm2THW fi 34mm 1er. 1 THERMA ELECTRICA 0.00 100% 0.00 K V cos F 220*0.82 ∅ PVC-SAP PISO CARGA MOVIL 1500.00 100% 1500.00 1924.62 Watts 1154.77 Watts 6.40 Amp 8.00 71.48 5.0 357.40 100% 357.40 CARGA ESPECIAL: 0.00 0.00 TERMA ELECTRICA.: M-1 AREAS COMUNES Capacidad LTS): 0 0.00 100% 0.00 I= MD 525.89 2-1x6mm2THW fi (Desde el 1er. 2 ELECTROBOMBA: ∅ 26mm PVC-SAP TGS-01 K V cos F 220*0.82 Piso a la Azotea) Capacidad (HP): 0.5 373.00 100% 373.00 2-1x6mm2THW fi 26mm CARGA MOVIL: 0.00 100% 0.00 ∅ PVC-SAP 876.48 Watts 525.89 Watts 2.92 Amp 3.64 CALCULO TOTAL 26832.90 Watts 16099.74 Watts TOTAL 89.24 Amp 133.87 3-1x25mm2THW ACOMETIDA ∅ 185mm PVC-SAP ELECTROC.
POTENCIA A CONTRATAR 16.09974 KW
Propietario: SRA. HERLINDA QUISPE PORTA Proyecto: HOSPEDAJE Asunto: MEDIDOR TRIFASICO Ubicación: JIRON TAYLOR N° S/N Mz "A" LOTE "3" Profes. Responsable.: ARQ. SEMINARIO DAVID PORTA MACHA
CALCULO DE CARGAS ELECTRICAS : HOSPEDAJE
PISO AMBIENTE AREA C. UNIT. PI FD M.D. (Watts) M.D. + FACTOR DE INTENSIDAD DISEÑO CONDUCTOR TABLERO MEDIDOR (m2) W/m2 (Watts) SUBTOTAL TOTAL + 20% SIMULT. 0.60 AMPERIOS CORRIENTE TUBERIA DE DIST. 179.16 13.0 2329.08 100% 2329.08 CARGA ESPECIAL: M-1 5to. 1 COCINA ELECTRICA 0.00 80% 0.00 I= MD 1676.94 2-1x4mm2THW fi HOSPEDAJE TG-05 PISO ∅ 19.5mm PVC-SAP 2-1x4mm2THW fi 19.5mm 1 THERMA ELECTRICA 0.00 100% 0.00 K V cos F 220*0.82 ∅ PVC-SAP CARGA MOVIL 0.00 100% 0.00 2794.90 1676.94 9.30 11.62 179.16 13.0 2329.08 100% 2329.08 CARGA ESPECIAL: M-1 4to. 1 COCINA ELECTRICA 0.00 80% 0.00 I= MD 1676.94 2-1x4mm2THW fi HOSPEDAJE TG-03 PISO ∅ 19.5mm PVC-SAP 2-1x4mm2THW fi 19.5mm 1 THERMA ELECTRICA 0.00 100% 0.00 K V cos F 220*0.82 ∅ PVC-SAP CARGA MOVIL 0.00 100% 0.00 2794.90 1676.94 9.30 11.62 179.16 13.0 2329.08 100% 2329.08 CARGA ESPECIAL: M-1 3er. 1 COCINA ELECTRICA 0.00 80% 0.00 I= MD 1676.94 2-1x4mm2THW fi HOSPEDAJE TD-01 PISO ∅ 19.5mm PVC-SAP 2-1x4mm2THW fi 19.5mm 1 THERMA ELECTRICA 0.00 100% 0.00 K V cos F 220*0.82 ∅ PVC-SAP CARGA MOVIL 0.00 100% 0.00 2794.90 1676.94 9.30 11.62 178.26 13.0 2317.38 100% 2317.38 CARGA ESPECIAL: M-1 2do. 1 COCINA ELECTRICA 0.00 80% 0.00 I= MD 1668.51 2-1x4mm2THW fi HOSPEDAJE TG-02 PISO ∅ 19.5mm PVC-SAP 2-1x4mm2THW fi 19.5mm 1 THERMA ELECTRICA 0.00 100% 0.00 K V cos F 220*0.82 ∅ PVC-SAP CARGA MOVIL 0.00 100% 0.00 2780.86 1668.51 9.25 11.56 184.97 5.0 924.85 100% 924.85 M-1 LOCAL DE CARGA ESPECIAL: I= MD 665.89 2-1x4mm2THW fi REUNIONES TOMACORRIENTES 0.00 100% 0.00 K V cos F 220*0.82 ∅ 19.5mm PVC-SAP TG-01 2-1x4mm2THW fi 19.5mm CARGA MOVIL 0.00 100% 0.00 1109.82 665.89 3.69 4.61 ∅ PVC-SAP 51.71 5.0 258.55 100% 258.55 1er. CARGA ESPECIAL: 0.00 0.00 AREAS M-1 PISO TERMA ELECTRICA.: COMUNES Capacidad LTS): 303 3200.00 100% 3200.00 I= MD 2438.28 2-1x6mm2THW fi (Desde el 1er. ∅ 34mm PVC-SAP TGS-01 Piso al 3er. 2 ELECTROBOMBA: K V cos F 220*0.82 Piso) Capacidad (HP): 0.25 186.50 100% 186.50 2-1x6mm2THW fi 34mm CARGA MOVIL: 0.00 100% 0.00 ∅ PVC-SAP 4063.80 2438.28 13.52 16.89 CALCULO TOTAL 16339.16 9803.50 TOTAL 54.34 81.51 3-1x25mm2THW 50mm ACOMETIDA ∅ PVC-SAP ELECTROC.