Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Belmond Submittal#84 Rev 0 Hvac Unidad Condensador Enfriad 202307282042
Belmond Submittal#84 Rev 0 Hvac Unidad Condensador Enfriad 202307282042
Ciudad De Mexico, Carr. Cancún - Tulum Km 51, 77710 Riviera Maya, Q.R.
Teléfono: +52-55 55-530353 Rivera Maya, Quintana Roo 77710
Para Leonardo Díaz (ALPHA HARDIN), Felipe Velasquez (BCQS), Adriana López Urzúa (ALPHA HARDIN), Daniel Talero (BCQS),
Javier Soria (KVO), Jose Manuel Cruz Villareal (ALPHA HARDIN), Joel Flores Gregorio (KVO), Diego Pinilla (BCQS), Javier
Soria Pérez (KVO), Jorge Luis Caridad Lugo (KVO), Viviana Castellanos (ALPHA HARDIN)
Mensaje Ninguno
Adjuntos DX13SA060-CP.pdf
Ernesto Ávila (GRUPO-SACMAG) Approved as Noted Por favor revisar comentarios del diseñador
Gerardo Zenon (GRUPO-SACMAG) Approved Se aclara que el titulo del submital es referente a
la unidad condensadora, sin embargo la
descripción hace referencia a un tag de uma,
Persona
Responsable
Distribución Javier Soria Pérez (KVO), Joel Flores Gregorio (KVO), Jose Manuel Cruz Villareal (ALPHA HARDIN), Jorge Luis Caridad Lugo
(KVO), Felipe Velasquez (BCQS), Daniel Talero (BCQS), Diego Pinilla (BCQS), Adriana López Urzúa (ALPHA HARDIN),
Leonardo Díaz (ALPHA HARDIN)
Adjuntos de
DX13SA060-CP.pdf
información general
Comentarios Se aclara que el titulo del submital es referente a la unidad condensadora, sin embargo la descripción hace referencia a un
tag de uma,
Ernesto Ávila 7 jun, 2022 28 may, 2022 16 jun, 2022 Approved as Noted
STANDARD FEATURES
Energy-efficient compressor
Factory-installed filter drier
Copper tube/ enhanced aluminum fin coil
Service valves with sweat connections and easy-access gauge ports
Contactor with lug connection
Ground lug connection
Units meet the performance outlined in Table 6.8.1B of ASHRAE Standard
90.1-2010
AHRI Certified
ETL Listed
CABINET FEATURES
Innovative louvered sound control top design
Steel louver coil guard
Heavy-gauge galvanized-steel cabinet
Attractive Nickel Gray powder-paint finish
Top and side maintenance access
Single-panel access to controls with space provided for field-installed
accessories
When properly anchored, meets the 2010 Florida Building Code unit
integrity requirements for hurricane-type winds (Anchor bracket kits
available.)
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056
Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without
incurring any obligations)
PERFORMANCE * VALUES SHOWN ARE FOR AHRI RATED HIGH SALES VOLUME TESTED COMBINATION (HSVTC)
Min. Circuit Amps MCA (A): 14.1 Airflow Rate (High) (CFM):
Max Overcurrent Protection (MOP) (A): 20 Suction Valve Connection Size (inch): 3/4
Max Starting Current MSC(A): 10.40 Liquid Valve Connection Size (inch): 3/8
Additional Charge (lb/ft): 0.04 Max. Pipe Length (Vertical) (ft): 200
Pre-charge Piping (Length) (ft): 15 Min. Cooling Range w/Baffle (°F DB): 55
Max. Pipe Length (Total) (ft): 200 Min. Heating Range w/Baffle (°F DB):
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056
Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without
incurring any obligations)
DIMENSIONAL DRAWING
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056
Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without
incurring any obligations)