1P-15 AMP. 600V. 2P-15 AMP. 600V. 1P-15 AMP. 600V. 1P-15 AMP. 600V.
BOMBA SUMERGIBLE C.I. 10 KA C.I. 10 KA C.I. 10 KA C.I. 10 KA
93.75 KW
2 COND. CAL. 12 THW-LS 2 COND. CAL. 12 THW-LS 2 COND. CAL. 12 THW-LS 2 COND. CAL. 12 THW-LS
(3.31 mm²) FASE Y NEUTRO (3.31 mm²) FASES (3.31 mm²) FASE Y NEUTRO (3.31 mm²) FASE Y NEUTRO
1 COND. CAL. 12 AWG Cu 1 COND. CAL. 12 AWG Cu 1 COND. CAL. 12 AWG Cu 1 COND. CAL. 12 AWG Cu
(3.31 mm²) TIERRA FISICA (3.31 mm²) TIERRA FISICA (3.31 mm²) TIERRA FISICA (3.31 mm²) TIERRA FISICA PROYECTO
TUBERIA DE 21 mm Ø TUBERIA DE 21 mm Ø TUBERIA DE 21 mm Ø TUBERIA DE 21 mm Ø
In= 4.78 AMP In= 3.03 AMP In= 6.56 AMP In= 6.56 AMP
e% = 0.364 e% = 0.749 e% = 0.312 e% = 0.312
L = 8 mts. L = 45 mts. L = 5 mts. L = 5 mts.
4
3 3 REF 1HP 1HP
C:\Users\Usuario\Downloads\cancha_de_usos-Presentaci-000.jpg
In Ic COND. CAIDA DE TUB.
CTO. VOLT. ITM m mm
93.75 KW WATTS AMP. AMP. A B C F/N mm2 T. F. TENSION
BOMBA
1 93,750 136.68 170.85 440 31,250 31,250 31,250 3X175 3F-3/0 AWG 85.01 4 116 1.468 CABLE
SUMERGIBLE SUBTERRANEO
INT. 1 136.68 170.85 440 2 2 53 mm (2)
PRINCIPAL 93,750 31,250 31,250 31,250 3X200 3F-3/0 AWG 85.01 0.025
DIRECCIÓN DE OBRA PÚBLICA
TABLERO DE DISTRIBUCION, 220/127V CARGA INSTALADA = 2,646W H.XLII AYUNTAMIENTO CONSTITUCIONAL DE
ALUMBRADO
REFLECTORES 4 600 3.03 3.79 220 300 300 2X15 2F-12 AWG 3.31 12 45 0.749 21 mm (3/4) PRESIDENTE MUNICIPAL:
FILTRO
1 750 6.56 8.20 127 750 1F-12 AWG 3.31 5 0.312 21 mm (3/4)
CLORADOR 1X15 1N-12 AWG 12
DE
FILTRO
1 1F-12 AWG TA LIC. MANUEL RAMÓN SALCEDO OSUNA
CLORADOR 750 6.56 8.20 127 750 1X15 1N-12 AWG 3.31 12 5 0.312 21 mm (3/4) LLE
DE CONTENIDO:
INT TRO 3 4 3 2 750 3F-10 AWG 12 10 27 mm (1) SU
2,646 7.72 9.64 220 846 1050 3X20 5.26 0.231 BE
SECO 1N-12 AWG ST FECHA: No. PLANO Acotaciones:
AC METROS
ION