1.DATOS GENERALES DE LA ESTRUCTURA

MODELO EXTRUIDO

LIBERACION DE MOMENTOS

.
Parte I- 2/25
1.1 ESPECIFICACIONES – MATERIALES EMPLEADOS:
ACERO : Tubos LAC ASTM A500 GB: Fy = 46 KSI λc = 7.85 Tn/m3, Ec = 2,038,000 Kg/cm2
Fu = 58 KSI u= 0.30
corrugado: Fy = 4200 Kg/cm2, λc = 7.85 Tn/m3, Ec = 2,100,000 Kg/cm2
ACERO : Tubos LAC ASTM A500 GA: Fy = 38 KSI λc = 7.85 Tn/m3, Ec = 2,038,000 Kg/cm2
Fu = 46 KSI u= 0.30
ACERO : Platinas A-36: Fy = 36 KSI λc = 7.85 Tn/m3, Ec = 2,038,000 Kg/cm2
Fu = 58 KSI u= 0.30

SOLDADURA: Electrodos: Fexx = 60 KSI (E70 XX - AWS, para acero liso) (en varillas)
Fexx = 70 KSI (E70 XX - AWS, para acero corrug.)
.
Parte I- 3/25
COBERTURA: Pu = 3.50 kg/m2 (Calaminon curvo CU ALUZINC AZ200 e=0.4mm; catalogo fabricante)

1.2. ESTRUCTURACION:
ARCOS METALICOS: El tipo de miembros estructurales empleados sonTubos LAC ASTM A500 GrB,Tubos LAC ASTM A500 GrA, varillas de acero liso , con las siguientes
caracteristicas:

.
Parte I- 4/25
ACERO ASTM A500 Gr A Y B

ACERO ASTM A500 Gr A

TENSORES: Los elementos complenetarios detio fierro lisos.

COLUMNAS METALICAS: Los miembros estructurales empleados son perfiles tipo cajon rectangular hueco. En el calculo se interactua probando diversas
secciones del grupo definido en el cuadro "Auto Selection Sections " mostrado abajo. En el cuadro "Box/Tube Section " se muestra las propiedades de una de
las secciones de dicho grupo

.
Parte I- 5/25
2. DISEÑO DE ARCO METALICO "AM - 01"

" V/14"
" V/14 "

VISTA GENERAL
ARCO METALICO
"AM-01"

ELEVACION TRIDIMENSIONAL DE LA ESTRUCTURA

2.1 PRE-DIMENCIONAMIENTO : Se asume en todos los elementos: A= 10.00 cm2

2.2 ESTADOS DE CARGAS: Identificando los tipos de cargas intervinientes en cada direccion de la Estructura:
CARGAS GRAVITACIONALES: CARGA MUERTA (D):
Cobertura (catalogo fabricante): D1 = 3.50 kg/m2 (Estimada por el SAP2000)
Estructura metalica (estimado a verificar): D2 = 30.00 kg/m2 (Estimada por el SAP2000)
Accesorios e iluminacion: D2 = 0.00 kg/m2
WD = 0.00 kg/m2
CARGA VIVA DE TECHO (Lr): NTE E.020 - TABLA 1: WLr = 30.00 kg/m2
CARGAS LATERALES (SENTIDO LONGITUDINAL): CARGAS DE VIENTO (W):
NTE E.020 - Art. 12 →: V h = V(H/10) 0.22 > V ("V" de Mapa Eolico Min 75km/h - Zona Cotabambas V=60km/h)
Viento en Arcos metalicos: V= 75.00 km/h H ≈ 13.100 m (alt. prom. desde terreno)
VH = 79.59 km/h θ= 18.000 ° (pendiente promedio de la superficie - zona de baja pendiente)
θ= 41.000 ° (pendiente promedio de la superficie - zona de alta pendiente)
Presiones: NTE E.020 - TABLA 4 → Ph = 0.005(C)(V h 2 )
CONSTRUCCION barlovento sotavento donde:
Arcos y cubiertas cilindricas con +0.8 Ph = Presión o succión del viento a una altura “h” perpendicular a
-0.5 .
Parte I- 6/25
-0.5
pendiente (θ) < 45º -0.8 la superficie, para "h"> 10m (kg/m2)
Superficies verticales de edificios +0.8 -0.6 C = factor de forma adimensional (de tabla izquierda)
Superficies verticales o inclinadas (planas
-0.7 -0.7
o curvas) paralelas al viento (El signo positivo indica presión y el negativo succión)
BARLOVENTO: Considerando presion: C= 0.8 ρh = 25.34 kg/m2 (en arcos)
Considerando succion: C= -0.8 ρh = -25.34 kg/m2 (en arcos)
SOTAVENTO Se tiene succion: C= -0.5 ρh = -15.84 kg/m2 (en arcos)
CARGAS LATERALES (SENTIDO TRANSVERSAL): CARGAS DE SISMO (E):
SISMO DINAMICO: Se aplica el "Espectro de Pseudo Aceleraciones" definido en la presente Memoria

PELIGRO SISMICO CARACTERIZACION DEL EDIFICIO

FACTOR ZONA PERFIL DEL SUELO PARAMETROS DE SITIO CATEG. DE LA EDIFIC. SISTEMA ESTRUCTURAL FACT. DE IRREGULARIDAD RESTRIC. IRRE.

Zona: 2 Z=0.25 Perfil Tipo S3:Suelos Blandos


FACT S:= 1.40 B:Edif. Importantes As°:SMF(Pórticos Especiales Regular Ia=1.00
Resistentes a Momentos) No se permiten
COEF. PARA ESTIMAR "T" T (s):= 1.00 FACT"U":= 1.3 Regular Ip=1.00
Su:0.25 kg/cm2 a 0.5kg/cm2 P irregularidades extremas
Edif. cuyos elementosCt=
resistentes
35 TL(s):=
en la dirección considerada sean únicamente:a)1.60
Pórticos de
Sinconcreto
Aislamiento
armado
Sísmico
sin muros COEF.
de corte.
BASICO
b) Pórticos
REDUC.dúctiles
F. SISMICAS:
de acero con uniones resistentes
Ro=8.00a momentos, sin arriostramiento.
R=Ro.Ia.Ip= 8.00
Categ. Edif.:(Cines,teatros,estadios, coliseos, centros comerciales, terminales de pasajeros, establecimientos penitenciarios, o que guardan patrimonios valiosos como
museos y bibliotecas.)(depósitos de granos y otros almacenes importantes para el abastecimiento)

Ct:Edif. cuyos elementos resistentes en la dirección considerada sean únicamente:a) Pórticos de concreto armado sin muros de corte. b) Pórticos dúctiles de acero con
uniones resistentes a momentos, sin arriostramiento.
Ia:Regular
Ip:Regular
hn= 14.1 m Altura total de la edificacion.(*No se incluye sótanos)
T= 0.40 Periodo fundamental de la estructura
RESPUESTA SISMICA Max= 0.1422 0.2220 0.0565
T(seg.) C Sa (m/s2) Sa-i Sv (m/s) Sd (m)
0.10 2.50 1.3949 0.1422 0.0000 0.0000
0.20 2.50 1.3949 0.1422 0.0444 0.0014
0.30 2.50 1.3949 0.1422 0.0666 0.0032
0.40 2.50 1.3949 0.1422 0.0888 0.0057
0.50 2.50 1.3949 0.1422 0.1110 0.0088
0.60 2.50 1.3949 0.1422 0.1332 0.0127
0.70 2.50 1.3949 0.1422 0.1554 0.0173
0.80 2.50 1.3949 0.1422 0.1776 0.0226
0.90 2.50 1.3949 0.1422 0.1998 0.0286 Z .U .C .S  Z .U .S 
V = P =  C .P
1.00 2.50 1.3949 0.1422 0.2220 0.0353 R  R 
1.10 2.27 1.2681 0.1293 0.2220 0.0389 T < TP → C = 2.5
T
1.20 2.08 1.1624 0.1185 0.2220 0.0424 TP < T < TL → C = 2.5( P )
T
1.30 1.92 1.0730 0.1094 0.2220 0.0459 T ⋅T
T > TL → C = 2.5( P 2 L )
1.40 1.79 0.9963 0.1016 0.2220 0.0495 FACTORES DE TZONA "Z"
1.50 1.67 0.9299 0.0948 0.2220 0.0530 T = nZONA
h Z
1.60 1.56 0.8718 0.0889 0.2220 0.0565 CZona:
T 4 0.45
Z .U .C .S
1.70 1.38 0.7722 0.0787 0.2089 0.0565 S a −i = Zona: 3 0.35
R
1.80 1.23 0.6888 0.0702 0.1973 0.0565 Zona: 2 m 0.25
F .E2 = g = 9.81 2
1.90 1.11 0.6182 0.0630 0.1869 0.0565 Zona: 1 s 0.10
2.00 1.00 0.5579 0.0569 0.1776 0.0565
2.10 0.91 0.5061 0.0516 0.1691 0.0565
2.20 0.83 0.4611 0.0470 0.1615 0.0565
2.30 0.76 0.4219 0.0430 0.1544 0.0565
2.40 0.69 0.3875 0.0395 0.1480 0.0565
2.50 0.64 0.3571 0.0364 0.1421 0.0565
3.00 0.44 0.2480 0.0253 0.1184 0.0565
3.50 0.33 0.1822 0.0186 0.1015 0.0565
4.00 0.25 0.1395 0.0142 0.0888 0.0565
4.50 0.20 0.1102 0.0112 0.0789 0.0565
5.00 0.16 0.0893 0.0091 0.0710 0.0565
5.50 0.13 0.0738 0.0075 0.0646 0.0565
6.00 0.11 0.0620 0.0063 0.0592 0.0565
6.50 0.09 0.0528 0.0054 0.0546 0.0565
7.00 0.08 0.0455 0.0046 0.0507 0.0565
7.50 0.07 0.0397 0.0040 0.0474 0.0565
8.00 0.06 0.0349 0.0036 0.0444 0.0565
8.50 0.06 0.0309 0.0031 0.0418 0.0565
9.00 0.05 0.0276 0.0028 0.0395 0.0565
9.50 0.04 0.0247 0.0025 0.0374 0.0565
10.00 0.04 0.0223 0.0023 0.0355 0.0565

.
Parte I- 7/25
ESPECTRO DE ACELERACION SISMICA
(Sin Acel. de la Gravedad - FACTOR ESCALA=g=9.81m/s2)

ACELERACION (Sa-i)
ESPECTRO DE
ACELERACION, FE=9.81m/s2
0.20

0.10

0.00
0 2 4 6 8 10

SISMO ESTATICO: Periodo T(seg.)

Peso de la estructura: La estructura clasifico como categoría B, por lo tanto el peso que se ha considerado para el análisis sísmico es el debido a la carga permanente
más el 50% de la carga viva (100%CM + 50%CV). En azoteas y techo en general se considera el 25% de la carga viva (100%CM + 25%CV).

CM= 14584.24 kg (Automatico de SAP2000)


CV= 29685.60 kg (Automatico de SAP2000)
P= 22005.64 kg

Fuerza sismica asociada al peso: Sa_i= 0.14


V= 3128.93 kg P= 22005.64 kg (peso propio + 25%carga viva, automatico de SAP2000)

223.49 1571.83

2.3 ALTERNANCIA DE CARGAS:

CARGA MUERTA (PD): Se indican valores de la carga muerta en kg/m2 en la cobertura. 3.50 kg/m2 (Estimada por el SAP2000
CARGA VIVA DE TECHO (PLr): Se indican valores de la 1º y 2º alternancia de la carga viva en kg/m2

.
Parte I- 8/25
CARGA DE VIENTO (W) - ARCOS: Se indican valores del 1º y 2º caso de la carga de viento, en kg/m2:
BARLOVENTO: Considerando presion en el Barlovento:
Considerando succion en el Barlovento:

.
Parte I- 9/25
SOTAVENTO: Se tiene succion en el Sotavento:

.
Parte I- 10/25
CARGA DE SISMO (E) - COLUMNAS:
SISMO: Repartiendo las carga en ambas columnas: → "V/14" = 223.49 kg (ver VISTA GENERAL ARCO METALICO)

.
Parte I- 11/25
2.4 COMBINACIONES DE CARGAS:
Especificacion A-4.1 LRFD - 99: (se entiende que "V" y "E" corresponden a
los casos mas criticos de Viento y Sismo
respectivamente)

2.5 ANALISIS ESTRUCTURAL:

ESPECIFICACIONES AISC LRFD 93

RESULTADOS DE DISEÑO:

Verificación de Ratios en el Diseño de estructuras de Acero (Tubos LAC)

.
Parte I- 12/25
.
Parte I- 13/25
.
Parte I- 14/25
DIAGONAL
SUPERIOR
BRIDA

TENSOR
INFERIOR
BRIDA

COLUMNA

DIAGRAMAS - ENVOLVENTES DE FUERZA AXIAL (+): traccion (-): compresion

.
Parte I- 15/25
Se observa que el punto con deflexion maxima esta en la
brida inferior, cuyo valor (en cm) se considera aceptable
dmax=L/300= 83.667 mm

Se observa que el punto con desplazamiento lateral maximo


esta en la columna, cuyo valor (en cm) se considera aceptable
DIAGRAMA-ENVOLVENTE DE DEFORMACIONES

DESPLAZAMIENTO DE ENTREPISOS: CONTROL DE DERIVAS

El control por carga lateral es el control por deriva de entrepiso, y que según la norma E.030, el máximo desplazamiento relativo de entrepiso,
dividido entre la altura de entrepiso no deberá exceder de 0.001 para estructuras de Acero.

.
Parte I- 16/25
A NA LISIS D E RESULTA DO S

SISMO EN X-X
MAX. PER M. : A c ero 0.010 ∆H ≤ 0.01 Tipo de Estructura: Regular
R X= 8.0 DE LA TABLA DE DES PLAZAMIE NTOS EN EL SAP2000
Dreal=0.75RDelast. MAX.
PISO (i) H(cm) ∆(cm)=D(i+1)-Di Δ/H VERIFICACION
(cm) PERMISIBLE
1 900 2.52 2.52 0.0028 0.010 OK
1 410 1.28 1.28 0.0031 0.010 OK

SISMO EN Y-Y
MAX. PERM.: Acero 0.010 ∆H ≤0.01 Tipo de Estructura: Regular
RX= 8.0 DE LA TABLA DE DESPLAZAMIENTOS EN EL SAP2000
Dreal=0.75RDelast. MAX.
PISO (i) H(cm) ∆(cm)=D(i+1)-Di Δ/H VERIFICACION
(cm) PERMISIBLE
1 900 2.00 2.00 0.0022 0.010 OK
1 410 0.58 0.58 0.0014 0.010 OK

.
Parte I- 17/25
REACCIONES EN LA BASE

Para el estado de cargas de servicio.

Para el estado de envolvente de cargas.

.
Parte I- 18/25
RESULTADPOS DE LA MODELACION ESTRUCTURAL DE LOS SSHH

MODELO EXTRUIDO
DISEÑO DE ACERO VERTICAL PRINCIPAL

AREAS DE ACERO DE LOS ELEMENTOS ESTRUCTURALES

.
Parte I- 19/25