RESUMEN
ABSTRACT
The present work report of professional sufficiency has as its origin the supply of
electrical energy for the new industrial plant of "Envases y Envolturas", also with the
aim of providing a new medium voltage and low voltage network that meets the
technical characteristics of the facilities electrical project.
In the Present Project, the development of the Electrical Detail Engineering will be
carried out, as well as the selection of the electrical equipment to meet the Electrical
Demand in the medium term for the New Industrial Plant of Envases y Envolturas.
This document establishes the bases and design, plans that project of electrical
installations for the new plant must have to be elaborated within the current legal
framework, for which it is established, the project is elaborated in medium voltage and
low voltage with the sizing of a new Electrical Substation, Medium Voltage Cells,
Medium Voltage Transformers and Distribution Boards, to meet the projected demand
of the new plant.
The electrical design of this stage will be carried out in accordance with the Nacional
Electricity Code and the Planning Study developed based on the programmed growth
of the Electrical Demand.
TABLA DE CONTENIDO
RESUMEN i
ABSTRACT ii
TABLA DE CONTENIDO iii
LISTA DE TABLAS v
LISTA DE FIGURAS vi
CAPÍTULO I 1
INTRODUCCIÓN 1
1.1. Objetivo Del Informe 1
1.2. Estructura del informe 1
CAPÍTULO II 2
INFORMACIÓN DEL LUGAR DONDE SE DESARROLLÓ LA ACTIVIDAD 2
2.1. Institución donde se desarrolló la actividad 2
2.2. Periodo de duración de la actividad 2
2.3. Finalidad y objetivos de la entidad 3
2.4. Razón social 3
2.5. Dirección postal 3
2.6. Correo electrónico del profesional a cargo 3
CAPÍTULO III 4
DESCRIPCIÓN DE LA ACTIVIDAD 4
3.1. Organización de la actividad 4
Figura 1. Vista Panorámica de Nueva Planta. Fuente: Envases y Envolturas. 4
3.2. Finalidad y objetivos de la actividad 5
3.2.1. Finalidad. 5
3.2.2. Objetivos. 5
3.3. Problemática 5
3.3.1. Problema General. 5
3.3.2. Problema específico. 5
3.3.3. Justificación e importancia de la investigación 6
iv
3.4. Metodología 6
3.4.1. Bases teóricas 6
3.4.2. Marco Conceptual 9
3.5. Procedimiento 23
3.5.1. Punto de Diseño 23
3.5.2. Equipamiento de media tensión 23
3.5.3. Máxima Demanda 25
3.5.4. Cuadro de carga 26
3.5.5. Bases de Cálculo 29
3.5.6. Normas técnicas ambientales 30
3.5.7. Obras Civiles: 30
3.5.8. Celdas modulares compactas 30
3.5.9. Equipos de maniobra 31
3.5.10. Equipamiento del sistema de baja tensión 31
3.5.11. Sistema de 220 V. 32
3.5.12. Sistema de 380 V.- 33
3.6. Resultado de la Actividad 35
3.6.1. Conductor alimentador de ss.ee. planta de fuerza - 22.9 KV 35
3.6.2. Conductor alimentador de transformador seco 2500 KVA, 22.9/0.4 KV
40
3.6.3. Conductor alimentador de transformador seco 630 KVA, 22.9 /0.23 KV
43
3.6.4. Cálculo de ventilación SED 47
3.6.5. Cálculo de los cables de puesta a tierra 50
CAPÍTULO IV 52
CONCLUSIONES 52
4.1. Justificación 52
4.2. Metodología Aplicada 52
4.2.1. Evaluación Tecnica 52
4.2.2. Evaluación Económica 53
4.3. Descripción de la Implementación 57
4.4. Conclusiones 57
CAPÍTULO V 58
RECOMENDACIONES 58
CAPÍTULO VI 59
BIBLIOGRÁFIA 59
CAPÍTULO VII 61
ANEXOS 61
v
LISTA DE TABLAS
LISTA DE FIGURAS
CAPÍTULO I
INTRODUCCIÓN
La Estructura del informe, tendrá como inicio el diseño del proyecto,, de instalaciones
eléctricas de la nueva Planta de la Empresa Envases y Envolturas.
Dimensionamiento de la red de Media tensión que partirá de la subestación de luz del
Sur con destino a la subestación Principal de planta.
Diseño de la Subestación Principal de planta con sus respectivas Celdas de Media
Tensión, (Celda de Legada, Celda de Salida), Acometida de Media Tensión para los
Transformadores de Potencia.
Dimensionamiento de Máxima Demanda de la Planta de Envases y Envolturas.
Dimensionamiento de los Tableros de Distribución, Instalaciones Eléctricas de baja
tensión
Dimensionamiento del sistema de Puesta a Tierra de la Planta.
2
CAPÍTULO, II
INFORMACIÓN DEL LUGAR, DONDE SE DESARROLLÓ LA
ACTIVIDAD
Juancarlos.lugon@grupojlb.com
4
CAPÍTULO, III
DESCRIPCIÓN DE LA ACTIVIDAD,
3.2.1. Finalidad.
3.2.2. Objetivos.
3.3. Problemática
3.4. Metodología
3.4.1.1. Internacional
3.4.1.2. Nacional
La Subestación proyectada es del tipo compacta metal - enclosed y está compuesta por
celdas equipadas con estructura metálica envolvente y aparatos de corte y
seccionamiento.
Nivel de Aislamiento : 50 KV
Corriente nominal : 630 A
Máxima capacidad de ruptura : 16 KA
Resistencia mecánica : 1000 operaciones
Resistencia eléctrica : 100 aperturas
3.4.2.4. Normativas
Se cumple con las normativas del ministerio de Energía y minas RD. N.º 018-2002-
EM/DGE, Reglamento Nacional de Edificaciones y el Código Nacional de
Electricidad Utilización. Así como las normas IEEE, NEMA y además las que se
indican en cada equipo o sistema. En base en el Código Nacional de Electricidad.
Las celdas deberán cumplir con las últimas ediciones de las siguientes
recomendaciones IEC:
IEC 298 Equipos de maniobra y protección AC metal-enclosed para voltajes
superiores a 1 KV y superiores incluyendo 54 KV Facilidad de instalación.
IEC 265 Seccionadores de alta-tensión
IEC 129 Desconectores AC y seccionadores de puesta a tierra
IEC 694 Cláusulas comunes para equipos de maniobra y protección en alta tensión.
IEC 56 Interruptores AC en alta tensión
IEC 185 Transformadores de corriente
11
Nivel de Aislamiento
Aislamiento 50
50 Hz/1 min
Aislamiento 125
1.2/50 ms
El equipo deberá satisfacer los criterios establecidos para celdas de tipo “metal-
enclosed” compartimentadas, para instalación interior según lo establecido en las
recomendaciones de la IEC 298.
Las celdas deberán ser diseñadas con cinco compartimientos dentro de una misma
envolvente:
Compartimiento de barras,
Compartimiento de conexión,
Seccionadores
Interruptores
Barras
Auxiliares de BT
Características Eléctricas
Tensión nominal : 24 KV
13
Nivel de Aislamiento : 50 KV
Esta celda modular tiene la función de acometida y protección general para alimentar
el equipamiento del usuario.
01 interruptor de potencia con cámara de extinción de arco en vacío 630Amp.,
24kV.; con mando motorizado a 24 Vcc.
01 seccionador tripolar 24 kV, 630 A, Línea–Tierra de acción rápida para maniobra
sin carga.
03 transformador de corriente monofásico encapsulado en resina epóxica 15 VA en
clase 0.2S/5P20
14
Placa de características.
Conmutador manual en vacío.
Ruedas bidireccionales.
Abrazaderas de tierra.
Ganchos de elevación.
01 Centralina de control de visualización.
03 Sensores de temperatura PT100
01 Disyuntor bipolar, 2A, 440Vac, 10kA@230Vac.
Soporte para terminales de cable seco de 24 KV.
Equipamiento:
01 transformador de distribución seco encapsulado en resina, de 2500 KVA,
arrollamiento de aluminio, núcleo fabricado con láminas magnéticas con cristales
orientados, laminada en frío y aislada sobre los dos lados por medio de una capa fina
de barniz aislante.
Placa de características.
Conmutador manual en vacío.
Ruedas bidireccionales.
Abrazaderas de tierra.
Ganchos de elevación.
01 Centralina de control de visualización.
17
Equipamiento:
3.4.2.10. Conductores
Estas especificaciones técnicas del cable de cobre tipo, N2XSY, - 18/30 kV, 1x70mm2
que proveerá de energía a las Subestacion de Distribución.
Normas aplicables
El cable de cobre, materia de la presente especificación, cumple con:
Ntp 370.042: Conductores, De Cobre Recocido, Para El Uso, Eléctrico.
Ntp-Iec 60502-2: Cable De Energía Con Aislamiento Extruido y Sus Accesorios Para
Tensiones Nominales Desde 1kv Hasta 30kv
Condiciones ambientales
El cable de cobre tiene las siguientes condiciones, ambientales:
Altitud (msnm) : hasta 1 000 m.
Temperatura mínima : 12 °C
Temperatura media anual : 20 °C
Temperatura máxima : 32 °C
Humedad relativa : 50 a 95%
Cable de energía, con conductor de cobre, del tipo aislado con polietileno reticulado,
y cubierta externa de, cloruro de polivinilo (PVC) y aislamiento de polietileno
reticulado (XLPE).
18
Condiciones de servicio
Los terminales se instalarán en los sistemas, cuyas características ambientales son las
siguientes:
Después de instaladas las Celdas, se tendrá que realizar las conexiones de puesta a
tierra, según planos y láminas de detalle correspondientes.
Se deberá realizar todas las conexiones a las mallas de tierra de seguridad existentes
que se indiquen en la documentación. Éstas tienen por objeto proveer la tierra de
servicio a la que se conectaran los neutros primarios de los transformadores. También
se deberá conectar la tierra de MT la totalidad de tuberías metálicas, los soportes,
gabinetes, tableros y demás componentes metálicos que normalmente no estén bajo
tensión.
En las celdas de media tensión se deberá conectar la tierra de cada uno de sus
elementos inclusive la puerta.
19
La construcción, de las mallas de tierra queda fuera del alcance del presente diseño,
pero será responsabilidad del contratista de Mallas de Tierra su construcción.
Deberán ser las siguientes: tres (04) mallas de tierra: Una (01) para la MT con un valor
máximo de 15 Ohm, Una (01) segunda para el aterramiento de los neutros primarios
de los transformadores y las dos (02) últimas para la BT y comunicaciones de 10 Ohm
como máximo.
a) Tablero de distribución
Del tipo para empotrar, adosar o auto soportar, ubicados según los planos, para cubrir
las necesidades de energía normal, de energía estabilizada de UPS donde sea
requerido. Con interruptores secundarios termo magnéticos diferenciales y barra de
tierra de protección. Los de energía estabilizada de UPS llevan adicionalmente barra
de tierra aislada. Incluye los demás accesorios de acuerdo con normas y
especificaciones técnicas.
d) Pruebas
Todas las pruebas (parciales y finales) y puesta en servicio serán responsabilidad del
contratista, incluyendo la elaboración, de los protocolos, de prueba, tal como se define
en las especificaciones técnicas.
Durante las pruebas, se tendrá que poner fuera de servicio las instalaciones
desenergizando las fases.
Las pruebas se tendrán que realizar, Para tensiones nominales, menores de 500 V (300
V fase, neutro), la tensión, de pruebas será mayor a 500 V.
e) Símbolos Eléctricos
La Norma para utilizar es la DGE – SÍMBOLOS GRÁFICOS EN ELECTRICIDAD.
a) Normas y Estándares.
b) Condiciones de Operación
Los equipos y materiales suministrados deberán ser apropiados para trabajar en las
siguientes condiciones:
Temperatura, Ambiente, Máxima : 31°C
Temperatura, Ambiente, Mínima : 10°C
Altitud Promedio : 65 m.s.n.m
Humedad Relativa Máxima Mensual : 97%
Humedad Relativa Mínima Mensual : 71%
Zona Sísmica :2
Nivel Polución : No severo
23
3.5. Procedimiento
En la figura 5, figura 6 se puede visualizar los ítems del equipamiento de media tensión
del proyecto respectivamente de la marca Schneider Electric.
24
Potencia de cortocircuito (en 22,9 kV) 350 MVA (Según punto, de, diseño)
Las celdas son del tipo compacta integrada compuesta por 01 de celda modular de
Llegada y Protección, 02 celdas modulares de salida y 02 celda de Transformación.
Estas celdas son para montaje interior IP2X (hasta 1000 m.s.n.m), para una tensión de
servicio proyectada 22,9 kV. Las celdas compactas integradas están compuestas por
unidades, modulares, bajo envolventes, metálicas, del tipo compartimentadas
Las condiciones necesarias que deberán tener en consideración serán las siguientes:
Condiciones de servicio
Códigos y normas específicas
Estructura
Compartimentación
Enclavamientos
Puesta a tierra
31
El detalle de las consideraciones para las Celdas compactas será denotado en el anexo
2
Los equipos de maniobra que deberán estar en la subestación serán los siguientes:
Revelador de tensión
Pértiga
Banco de Maniobras.
Zapatos
Lentes de seguridad
Casco
Guantes
Placa de señalización
La conexión trifásica (3 fases + tierra) a 60 Hz, que corresponde a los tableros de las
máquinas descritas en la tabla 7.
34
PCC
I CC ( KA)
3xV
En el punto de Alimentación:
Potencia de cortocircuito del sistema : Pcc= 350 MVA
Tensión nominal de servicio : V= 22.9 KV
Duración del cortocircuito : t = 0.2 seg.
Sección del conductor : s = 70 mm2
Corriente de cortocircuito permanente : Icc
Luego:
Icc = 8.82 KA
En condiciones, de, cortocircuito, se incrementa la temperatura, de los cables de
energía.
Para el cálculo en condiciones, de cortocircuito, con parámetros, perfectamente
definidos, la fórmula de la sección mínima del cable que pueda soportar la corriente
de cortocircuito en un tiempo determinado es:
36
I CC x t
S min x 1000 (mm2)
143
Donde:
Icc : Corriente de cortocircuito que soportará el cable en KA.
Smín : Sección, transversal, mínima del cable en mm2
t : tiempo, de apertura, del sistema, de protección (0.2 seg.)
8.82 ∗ √0.2
𝑆= 𝑥1000
143
0.143 x 70 m2
Icc , cable 22.38KA
0.2seg
Según este resultado el cable puede soportar hasta 22.38 kA y como la corriente de
cortocircuito es de 8.82 KA; En conclusión, el, cable de 3-1 x 70 mm2 N2XSY
(18/30) KV, es el indicado y soportará la corriente de cortocircuito.
3130𝐾𝑉𝐴
𝐼𝑛 = = 78.913 A
√3 x 22.9KV
Según tablas del fabricante la capacidad máxima del cable N2XSY (18/30)
KV,1x70 mm2 es de 305 Amperios.
Esta capacidad del cable es afectada por el factor, de, corrección Fc.:
De donde se tiene:
El cable instalado es del tipo N2XSY (18/30) KV y de sección 70 mm2, para trabajo
a tensión nominal de Operación de 22.9 KV.
La longitud del cable entre la Subestación Principal y la subestación Planta de
Fuerza es de aproximadamente 75 metros.
Según el fabricante, los parámetros eléctricos del cable son los siguientes:
Resistencia 0.342 Ω/Km.
Reactancia 0.2638 Ω/Km.
De acuerdo con la fórmula de caída de tensión en condición de plena carga:
Donde:
38
1.73205𝑥225𝑥78.913(0.342𝑥0.85 + 0.2638𝑥0.5267)
𝛥𝑉 = 𝑉𝑜𝑙𝑡𝑖𝑜𝑠
1000
En Conclusión:
El cable seleccionado: 3-1x70 mm2 N2XSY (18/30) KV, podrá atender la Carga
Solicitada por cumplir las condiciones de:
Cortocircuito : Icc, cable = 22.38 KA > Icc, red = 8.82 KA.
Luego:
Z = j 1.560
PCC
I CC ( KA)
3xV
Donde:
Icc = 8.47 KA
I CC x t
S min x 1000 (mm2)
143
Donde:
8.71 ∗ √0.2
𝑆= 𝑥1000
143
0.143 x 70 m2
𝐼𝑐𝑐 , 𝑐𝑎𝑏𝑙𝑒 = = 22.38 𝐾𝐴
√0.2𝑠𝑒𝑔
Según este resultado el cable puede soportar hasta 22.38 kA y como la corriente de
cortocircuito es de 8.47 KA; se concluye que, el cable, de 3-1 x 70 mm2 N2XSY
(18/30) KV, es el indicado y soportará la corriente de cortocircuito.
2500𝐾𝑉𝐴
𝐼𝑛 = = 63.03 A
√3 x 22.9KV
Según tablas del fabricante la capacidad máxima del cable N2XSY (18/30)
KV,1x50 mm2 es de 250 Amperios.
De donde se tiene:
Nótese que se está asumiendo como carga máxima el 100 % de Potencia Nominal
del Transformador de 2500 KVA, que sería el caso más desfavorable. (Máxima
Carga).
El cable instalado es del tipo N2XSY (18/30) KV y de sección 70 mm2, para trabajo
a tensión nominal de Operación de 22.9 KV.
Según el fabricante, los parámetros eléctricos del cable son los siguientes:
Resistencia 0.342 Ω/Km.
Reactancia 0.264 Ω/Km.
El cálculo, de caída, de tensión, se efectuará para, la condición de plena carga:
43
Donde:
1.73205𝑥8𝑥63.03(0.342𝑥0.85 + 0.2638𝑥0.5267)
𝛥𝑉 = 𝑉𝑜𝑙𝑡𝑖𝑜𝑠
1000
Caída de tensión = 0.62 Voltios que equivale a: ∆V cable= 0.002% < 3.5% de
22.9 KV.
En este caso, verificando por caída de tensión; el cable seleccionado también
cumple con las exigencias de las Normas.
En Conclusión:
El cable seleccionado: 3-1x70 mm2 N2XSY (18/30) KV, podrá atender la Carga
Solicitada por cumplir las condiciones de:
Cortocircuito : Icc, cable = 22.38 KA > Icc, red = 8.478 KA.
Capacidad de corriente : Icable corregido = 196.4Amp > In = 63.03 A.
Caída de tensión : ∆V cable = 0.002 % < 3.5 % de 22.9 KV
𝑷𝑪𝑪
𝑰𝑪𝑪 = (𝑲𝑨)
√𝟑 x V
Donde:
Icc = 8.478 KA
𝐼𝐶𝐶 x √𝑡
𝑆 𝑚𝑖𝑛 = 𝑥 1000 (mm2)
143
Donde:
45
8.71 ∗ √0.2
𝑆= 𝑥1000
143
𝑆 𝑚𝑖𝑛 = 27.24 mm
0.143 x 50 m2
𝐼𝑐𝑐, 𝑐𝑎𝑏𝑙𝑒 = = 15.99𝐾𝐴
√0.2𝑠𝑒𝑔
Según este resultado el cable puede soportar hasta 15.99 kA y como la corriente de
cortocircuito es de 8.47 KA; se concluye que el cable de 3-1 x 50 mm2 N2XSY
(18/30) KV, podrá soportar, la corriente, de cortocircuito.
Según tablas del fabricante la capacidad máxima del cable N2XSY (18/30)
KV,1x50 mm2 es de 250 Amperios.
De donde se tiene:
Nótese que, si se asume como carga máxima el 100 % de Potencia Nominal del
Transformador de 630 KVA, que sería el caso más desfavorable. (Máxima Carga).
En este caso, verificando por capacidad de corriente, el cable seleccionado también
puede transportar toda la carga nominal del Transformador.
El cable instalado es del tipo N2XSY (18/30) KV y de sección 50 mm2, para trabajo
a tensión nominal de Operación de 22.9 KV.
La longitud del cable entre la Subestación Principal y la subestación Planta de
Fuerza es de aproximadamente 10 metros.
Según el fabricante, los parámetros eléctricos del cable son los siguientes:
Resistencia 0.494 Ω/Km.
Reactancia 0.2761 Ω/Km.
El cálculo, de caída, de tensión se efectuará para, la condición de plena carga:
Donde:
1.73205𝑥10𝑥15.88(0.494𝑥0.85 + 0.2761𝑥0.5267)
𝛥𝑉 = 𝑉𝑜𝑙𝑡𝑖𝑜𝑠
1000
47
Caída de tensión = 0.16 Voltios que equivale a: ∆V cable= 0.001% < 3.5% de
22.9 KV
En Conclusión:
El cable seleccionado: 3-1x50, mm2 N2XSY, (18/30) KV, podrá atender la Carga
Solicitada por cumplir las condiciones de:
Los datos del Cálculo de ventilación se denotan en la tabla 14, las dimensiones en
la Figura 8
H = 1.55 m
Vs = 0.48 m/s
Sección mínima de la rejilla de salida (Sr)
Media Tensión
0 .10525 S MT
It Icc
t
Icc 1 t
S tMT
0 . 10525
Donde:
It : Corriente de corta duración soportada por el cable (kA)
SMT : Sección del cable de tierra en media tensión (mm2)
T : Tiempo, de apertura, del dispositivo de protección (seg)
Icc1 : Corriente de cortocircuito en media tensión (kA)
Datos:
StMT : mm2
T : 0.2 seg
Icc1 : 8.63 KA
SMT ≥ 36.66 mm2
BAJA TENSION
Donde:
Pcc2 : Potencia de cortocircuito en baja tensión (MVA)
Pcc1 : Potencia de cortocircuito en media tensión (MVA)
51
Icc 2 t
S BT
0 . 11671
Donde:
It : Corriente de corta duración soportada por el cable (kA)
SBT : Sección del cable de tierra en baja tensión (mm2)
T : tiempo, de apertura, del dispositivo de protección, (seg)
Icc2 : Corriente, de cortocircuito en baja tensión (kA)
Datos:
Pcc1 = 342.23 MVA; Z = 0.060 Ω; PT = 0.63 MVA; T = 0.20 seg;
SBT ≥ 56.34 mm2
Por lo que se selecciona la sección de 70 mm
52
CAPÍTULO, IV
CONCLUSIONES,
4.1. Justificación
Los resultados del diseño de las instalaciones eléctricas de la nueva planta de envases
y envolturas se denotarán en los anexos de los planos respectivamente.
La propuesta técnica, económica se brindó a Gerencia para la respectiva evaluación,
se respecto el alcance, y presupuestos requeridos para que Gerencia tome la decisión
en un corto plazo en la Implementación de este.
4.4. Conclusiones
CAPÍTULO V
RECOMENDACIONES
El contenido del TSP abarca todos los parámetros del proyecto de sistema eléctrico
de Envases y Envolturas.
En los enlaces se ha revisado el tipo de cable, longitud, y cálculos justificativos
para los enlaces del sistema eléctrico del proyecto.
La capacidad máxima de carga en cada uno de los enlaces en media tensión y en
baja tensión es la indicada y cumple con el proyecto del sistema eléctrico de
Envases y envolturas.
El proyecto involucra el dimensionamiento del equipamiento de una nueva
subestación que incluye Nuevas Celdas de Media Tensión, Conductores y Obras
Civiles para la red de ductos, bandejas portacables, buzones para el transporte de
los alimentadores.
En los anexos se brinda toda la información necesaria de planos de detalle,
unifilares de los tableros de distribución y servicios generales para su respectiva
implementación.
.
59
CAPÍTULO VI
BIBLIOGRÁFIA
https://www.se.com/pe/es/search/celdas+sm6
Ulrich (2006), “Guía para el diseño de la instalación eléctrica de una fábrica de envases
de plástico”. (Trabajo de graduación). Guatemala. Obtenido de
http://biblioteca.usac.edu.gt/tesis/08/08_0602_EA.pdf
CAPÍTULO VII
ANEXOS
Las barras de puesta a tierra de cada una de las celdas que conforman el tablero deberán
estar interconectadas por un juego de barras que deberá ser conectable por la parte
externa del tablero y se deberá extender a todo lo largo del mismo.
La sección transversal tendrá que soportar la capacidad de cortocircuito de las celdas
según lo establecido en la recomendación IEC 298.
La barra de puesta a tierra deberá estar diseñada para conexión de la barra principal de
puesta a tierra de la subestación sin desmantelar ninguna de las barras.
La puesta, a tierra de los cables deberá ser realizada por un seccionador, de puesta, a
tierra con capacidad de, cierre contra cortocircuito, según lo establecido en la
recomendación IEC 129. Deberá ser posible operar el seccionador, de puesta, a tierra
cuando el, seccionador de potencia, este abierto
c) Seccionadores
Los seccionadores deberán emplear gas SF6 a baja presión, para la interrupción, de
corriente, y no deberán requerir ningún mantenimiento. Con respecto al seccionador
instalado, dentro de la celda, sus contactos principales y de puesta a tierra tendrán que
ser visibles. La envolvente deberá estar fabricada con resina epóxica encapsulada.
62
d) Interruptores
Contactos, auxiliares.
Deberá ser posible añadir en sitio un motor con sus accesorios para carga
e) Características Técnicas
f) Barras
g) Conexiones
El compartimiento de baja tensión deberá estar incluido dentro del volumen total de la
celda (ser parte integral de la misma). Deberá diseñarse para alojar los diferentes
elementos de BT requeridos para la operación del mecanismo de mando motorizado y
equipos auxiliares.
Para necesidades específicas, deberá ser posible agrandar o extender el
compartimiento de baja tensión añadiendo una envolvente con una puerta en la parte
superior de la celda. La altura total de la celda no deberá exceder 2225 mm.
En todos los casos, estos compartimientos deberán ser accesibles.
j) Auxiliares de BT
64
k) Control y monitoreo
l.1 El Relé:
Deberá ser del tipo digital a base de microprocesador con pantalla en LCD, lectura de
parámetros básicos, armónicos y capacidad de almacenar información.
Usando protocolos estándar, vía puerto de comunicación RS485
Adaptándose a un amplio rango de voltajes de alimentación,
65
a) Condiciones de servicio
Clima : Templado.
b.1 En general
controlgear.
IEC 62271-200: A.C. Metal-enclosed Switchgear for rated voltage above 1kV
and up to 52kV.
IEC 298 (1990): A.C. Metal-enclosed Switchgear and Controlgear for Rated
c) Estructura
Cabinas del tipo modular, contra la corrosión, pintada con pintura epoxi y secado
al horno.
d) Compartimentación
La celda o cabina del seccionador fusible, caso más complejo, se dispone de los
siguientes compartimientos:
1: Compartimiento, de juego, de barras.
2: Compartimiento, de baja, tensión.
3: Compartimiento, del tablero: seccionador bajo carga y seccionador, de puesta, a
tierra,
4: Compartimiento, del mecanismo de operación,
5: Compartimiento, conexionado de cables y de fusibles,
e) Enclavamientos
f) Puesta, a tierra,
Barra de tierra de 60 mm2 mínimo de, sección, que recorre todas las cabinas y vaya
conectando a tierra a todas las partes que no estén bajo tensión.
67
Equipamiento:
Equipamiento
Tipo modular, Está constituida por un gabinete fabricado con lámina de fierro
galvanizado o equivalente, de 2mm, doblada, que le otorga gran resistencia
mecánica durante el transporte, montaje o frente a fallas internas.
71
Equipamiento
Equipamiento:
Barras de Cobre
El tablero deberá cumplir, con lo, especificado en el Tomo V del Código, Nacional
de, Electricidad. El tablero deberá tener salidas de reserva equipadas en un orden
del 25% .de la cantidad de interruptores equipados más un 15% de espacio de
reserva por cada tablero.
El tablero placa de identificación con letras y números en alto relieve de color
negro.
b) Gabinete
Los tableros generales autosoportados y de distribución tendrán que ser del tipo
para adosar, en gabinete metálico, con marco y puerta, directorio de circuitos y porta
directorio y cumplir con lo siguiente:
Fabricados con planchas de acero inoxidable de 1.9mm de espesor mínimo, el
acabado pintado al horno según norma ,con las dimensiones necesarias para
alojar los equipos que se detallan en los planos del proyecto.
En su interior cubiertos con una contratapa fabricada en plancha, de, acero de
1.5mm de, espesor mínimo, abisagrado, con, llave, que solo deja al descubierto
los elementos de operación de los interruptores. Sobre esta contratapa estarán
indicados los nombres en placas de acero inoxidables con letras y números en
color negro de bajo relieve.
Los interruptores generales tendrán su descripción en bloques de letras de 18mm
de alto en placa de 27x75mm y los alimentadores y circuitos pueden usar block
de letras de 3mm en placa de 10x35mm.
El tablero dispondrá un sistema de cierre para lock out mediante llave, para
impedir el acceso a este, de personal no autorizado. Deberá tener mecanismo
montado a la derecha del tablero para desconectar el Breaker principal.
El tablero poseerá luces piloto que indiquen tablero energizado. Dichas luces
estarán montadas sobre la puerta de este, siendo estas del tipo neón color verde
con nema 4x.
Todas las partes metálicas tendrán que estar limpiadas y protegidas contra el
óxido aplicándoseles luego doble capa de pintura anticorrosiva, tanto interior
86
c) Barras de cobre
Las barras tendrán que ser de cobre , su capacidad nominal de las barras son las
que se indica en los planos; esta capacidad se calcula con una temperatura
ambiente de 300 C.
87
Para, la puesta a tierra, de los equipos y del, propio tablero se tiene una barra de
cobre instalada a todo lo largo del tablero. A esta barra se conectará el cable de
puesta a tierra.
Los tableros deberán incluir aisladores porta barras, platinas de cobre
electrolítico para el amperaje adecuado, conectores de bronce de derivación,
bornera de conexión a tierra y materiales de conexión, Se deja el 15% de la
extensión de cada barra libre, sin conexiones, todas disponibles. La protección
de zonas bajo potencial eléctrico (por ejemplo, barras, bulones, puentes
derivadores, etc.) se cubre mediante una placa acrílica y la protección de barras
con placa transparente con señalización autoadhesiva "Tensión Peligrosa".
d) Equipamiento
e) Luminarias
Artefacto para adosar en muro, con cuerpo de metal esmaltado. Cuenta con
lámpara fluorescente compacta con balasto electrónico incorporado menor a 60
W, 220 V, 60 Hz.
Artefacto para adosar, de 0.230 m de diámetro exterior máximo. Sistema óptico con
reflector, con 2 lámparas ahorradoras fluorescentes compactas de 18 W TC-D y
balasto electrónico para 220V, 60Hz.
Artefacto para empotrar en FCR, de 0.218 m de diámetro exterior máximo. Unidad
de reflector y cerco en una sola pieza de policarbonato, resistente a UV. Con 2
lámparas fluorescentes compactas de 18 W TC-D en posición horizontal y balasto
electrónico para 220V, 60Hz.
Luminaria para alumbrado 218w 20001m Philips BY461P lx LED 2003740 HRO
GC, para 220V, 60Hz.
Luminaria para alumbrado 108W 10001m Philips BY460P lx LED 2003740 HRO
CC, para 220V, 60Hz.
89
f) Conductores eléctricos
g.1 Conductores:
g.2 Conectores
g.4 Conexiones
h) Canalizaciones
Son de acero galvanizado en caliente con cubierta de PVC; dicho baño incluye las
roscas. La superficie interior pulida. Tubos de 3 m de longitud con una unión en el
extremo. Se emplearán en todos los circuitos de baja tensión, luces de emergencia,
aterramiento y CCTV de instalación visible. Los diámetros de las tuberías deberán
cumplir con los estipulado en la siguiente tabla:
Diámetros de Tuberías
Las cajas deberán ser del tipo pesado de fierro galvanizado, fabricado por
estampados en planchas de 1.5mm de espesor mínimo. Las cajas mayores de
0.30x0.30m fueron fabricados con planchas galvanizadas de 2.0mm de espesor. Las
tapas son del mismo material empernadas.
Las cajas metálicas deberán cumplir con lo siguiente:
Cajas metálicas pesadas con tapa, de fierro galvanizado
fabricadas con planchas de acero laminado en frío, el acabado es zincado
electrolíticamente u otro medio que brinde protección contra la corrosión.
Las cajas serán las siguientes:
Octogonal de 100x55mm y Rectangular de 100x50x55mm
Cuadrada de 150x150x75mm : Para salida de tomacorrientes dobles
Cuadrada de 200x200x100mm : Para salida de tomacorrientes dobles
Cuadrada de 250x250x100mm : Para salida de tomacorrientes dobles
No se permite, la instalación, de mayor cantidad, de cables por tubería, de lo que
estipula el CNE, así como, el número de curvas, de 90 entre cajas, o puntos de
derivación, de la tubería de pvc.
Las cajas tipo Condulet será con aleación de aluminio inyectado con cubierta de
PVC, lo cual les confiere una elevada, resistencia mecánica y a la corrosión, así
como una excelente presentación. Poseen rosca Standard, NPT. Son
suministradas con tapa, junta, dé sellado de tapa, tomillos y protector, de cables.
Terminación superficial en pintura de aluminio acrílico. Certificado de Calidad
bajo Norma UL. Se emplearon en el punto de derivación del tubo Conduit hacia
las luminarias.
h.5 Tomacorrientes
Fabricación bajo norma: NTP 370.054 0 IEC 608841-1. Las placas y soporte han
sido fabricadas en material aislante y de óptima resistencia mecánica. Cuentan
con terminal de tierra que ofrezca flexibilidad al cableado. Tomacorriente
monofásico doble con línea a tierra tipo tres en línea, 250V, 3 hilos (IF+N+T),
95
16A. Sus cajas están preparadas para la influencia de los agentes exteriores ya
sea polvo, humedad y lluvia su grado de protección NEMA 4X o equivalente.
Los tomacorrientes industriales son capases de soportar el ambiente de trabajo
donde se instalaron (alta polución, ambiente salino).
96
a) Revelador de tensión
b) Pértiga
c) Banco de Maniobras.
Tensión, Nominal : 45 kV
Capacidad, de aislamiento, (BIL) : 150 KVp
d) Zapatos,
Un par, de la, talla del operador, no menor de 30 kV, los que están clavados con
clavijas de madera o cocidos.
e) Lentes de seguridad
f) Casco
El casco está fabricado, de un material, aislante para uso eléctrico, de una tensión,
nominal, no menor de 30 kV.
97
g) Guantes
Guantes de jebe u otro material, aislante para uso, eléctrico a una tensión nominal,
de 30 kV.
h) Placa de señalización
Diagramas Unifilares
Recorrido de Cables