TESIS
PRESENTADO POR:
Flavio Cesar, GONZALES RONDON
HUANCAYO – PERÚ
2021
Asesor
ii
Dedicatoria
iii
Agradecimiento
iv
Índice
Asesor.............................................................................................................................ii
Agradecimiento ............................................................................................................. iv
Índice .............................................................................................................................. v
Resumen ........................................................................................................................ xi
Abstract ........................................................................................................................xii
Introducción ................................................................................................................. 13
1.4 Justificación...................................................................................................... 16
v
Capitulo II Marco Teórico .......................................................................................... 18
2.5 Variables......................................................................................................... 36
vi
3.3 Métodos de Investigación............................................................................... 38
Conclusiones ................................................................................................................ 69
Recomendaciones ......................................................................................................... 70
Bibliografía .................................................................................................................. 71
Anexos ......................................................................................................................... 73
vii
Índice de Figuras
viii
Índice de Tablas
ix
Tabla 25 Características de los Ensambles de las Cadenas de Aisladores.............................. 61
Tabla 28 Subestaciones Afectadas por Corte de Energía con la Línea Anillo Mina .............. 66
Tabla 29 Cortes Programados por Voladura con la Línea Anillo Mina ................................. 67
x
Resumen
eléctrica para las 3 subestaciones móviles de 7.5/8.4 MVA y 23/7.2 kV cada una de Minera
Chinalco Perú S.A. mediante el diseño de una línea eléctrica de distribución en 23kV, que hará
que el sistema eléctrico de mina pase de trabajar de sistema radial a sistema en anillo.
datos fue por entrevista y simulación digital, para el procesamiento de datos se usaron los
voladura, logrando con ello mejorar de la disponibilidad de suministro eléctrico hacia las 3
Para la presente tesis se menciona el nivel de tensión de 23kV para referirse al nivel
normalizado de 22.9kV, dado que Minera Chinalco Perú S.A considera el primero en informes,
xi
Abstract
The purpose of the present study is to improve the availability of electrical power supply for
the 3 mobile substations of 7.5 / 8.4 MVA and 23 / 7.2 kV each of Chinalco Peru mining
company S.A. through the design of a 23kV distribution power line, which will allow the mine's
The research was of the applied type, descriptive level and descriptive-analytical methodology.
The studies were carried out in the mine's electrical system at 23kV, the data collection was by
interview and digital simulation, for the data processing the DIGSILENT and DLTCAD
The design of the distribution line results in the reduction of scheduled outages per flying
machine, thereby improving the availability of electricity supply to the 3 mobile substations in
For this thesis, the voltage level of 23kV is mentioned to refer to the normalized level of
22.9kV, given that Minera Chinalco Peru S.A considers the first in reports, and tags of
xii
Introducción
Las empresas de gran minería constan de costos de producción muy elevados, por lo cual se
quiere que el suministro de energía eléctrica sea lo más continua posible para no tener paras de
producción, otro punto importante es que se requiere de redes eléctricas que adecuen su
anillo, ya que en él se obtiene más de una trayectoria para el paso de energía desde la fuente
hasta las cargas. Es por ello que la presente tesis titulada “DISEÑO DE LA LÍNEA DE
S.A.” describe el análisis de la línea aérea que hará que el sistema eléctrico de mina en 23 kV
de Minera Chinalco Perú S.A. tenga una estructura de distribución en anillo, con la cual se
quiere lograr.
En el capítulo 2, se expone el marco teórico integrado por los antecedes, bases teóricas que dan
discusión de resultados.
anexos.
13
Capítulo I
Minera Chinalco Perú S.A, es una empresa de gran minería creada por Aluminum
Minera Chinalco Perú S.A. instaló las líneas eléctricas en 23kV con el objetivo de
zona de la Mina Toromocho. Las cargas de mina están alimentadas por medio de 2
subestaciones móviles de 7.5/8.4 MVA y 23/7.2 kV cada una, que van reubicándose de
perforadora.
14
Se estima un aproximado de 120 cortes de energía al año por subestación móvil debido
distribución que alimenta a dicha subestación. Cada corte de energía programado por
motivos de voladura, implica que todas las subestaciones móviles conectadas a la línea
conecte estás 2 líneas de distribución existentes, dado que al conectarse las dos por
y conmutable.
15
1.3 Objetivo
1.4 Justificación
energético permanente.
16
mencionar que cada subestación móvil alimenta 01 pala y 01 perforador, los
1.5 Limitación
se pueden realizar trabajos y/o estudios a la intemperie durante estos eventos, retrasando
17
Capitulo II
Marco Teórico
2.1 Antecedentes
18
transmisión los cálculos manuales son completos e iterativos lo cual aumenta la
caso de falla y/o casos de corte de energía por mantenimiento en tramos la red,
19
de trasmisión se hace una medición de resistividad en todos los tipos de suelos
transmisión tiene que ser adaptable a los equipos instalados en las subestaciones
Figura 1
Sistema Eléctrico de Potencia
20
2.2.2 Sistemas de Distribución
tanto, es toda parte contenida entre el punto de alimentación y las cargas del
Figura 2
Diagrama Unifilar
Fuente: Osinergmin
cuenta que desde el punto de vista económico no todos los modelos de sistemas
21
tal caso, no aplica la misma configuración para un área rural que para un área
Figura 3
Sistema de Distribución Radial
cargas.
22
Figura 4
Sistema de Distribución en Anillo
para el flujo de carga, por lo que es más confiable y a la vez más costoso.
Figura 5
Sistema de Distribución Enmallado
Las subestaciones eléctricas son máquinas eléctricas que permiten modificar las
ubicación física fácilmente, es ideal para caso de las operaciones mineras donde
23
se requiere de suministro eléctrico en distintos lugares del proyecto según se
Figura 6
Subestación Móvil No 2 de Minera Chinalco Perú
- Recorridos alternos.
24
- Accesibilidad.
- Temperatura ambiente.
- Espesor de hielo.
- Altitud de la zona.
- Presión atmosférica.
- Precipitaciones.
se considera un ancho de 11m (5.5m a cada lado del eje) para el caso de líneas
de distribución de 23 kV.
25
Tabla 1
Anchos Mínimos de la Faja de Servidumbre
Es el análisis realizado para obtener los niveles de tensión en las barras o nodos
del circuito, corrientes que circulan a través de la red, flujos de potencia activa
26
2.2.6.3 Aislamiento.
aisladores de porcelana.
Son las distancias de prevención que debe mantener la línea de distribución con
los elementos físicos encontrados en área, para evitar los accidentes por contacto
27
Tabla 2
Distancias Mínimas de Seguridad
Descripción Línea de 23 kV
A áreas no transitado por vehículos 5,0 m
Al cruce de carreteras 8,0 m
Al cruce de vías de ferrocarril 10,0 m
Al cruce de caminos mineros 17,0 m
A lo largo de calles, carreteras y avenidas 8,0 m
Distancia mínima sobre conductores de líneas eléctricas
* Menor o igual a 23 kV 1,20 m
* Igual a 50 – 60 kV 2,50 m
* Igual a 138 kV 3,50 m
* Igual a 220 kV 4,50 m
Fuente: CNE Suministro
vano, esta distancia se determina de acuerdo a la norma alemana DIN VDE 210.
D = U / 150 + k Lc + f
Donde:
D: Distancia en metros
U: Tensión de la línea en kV
28
determinarse de acuerdo a 0,80 + 0,01 por sobre 11kV. Para el caso de los 23kV
que tiene el mismo potencial a tierra. Para un nivel de tensión de 23kV las
para los equipos, su significado se traduce como la unión eléctrica entre una
29
2.2.7 Criterios de Diseño Mecánico
Son los diferentes escenarios a los cuales estarán expuestos los conductores de
- Viento máximo
- Temperatura máxima
- Viento y hielo
- Presencia de hielo
- Temperatura mínima
se adoptara el criterio que la flecha del cable de guarda sea menor o igual al
90% de la flecha del conductor. Bajo esta condición el esfuerzo óptimo del cable
rotura.
𝑃𝑣 = 𝐾 ∗ 𝑉 2 ∗ 𝑆𝑓 ∗ 𝐴
Donde:
Pv = Presión de viento en Pa
30
K = 0,455 para las elevaciones mayores de 3 000 m.s.n.m.
Sf = Factor de forma:
Luego:
Energía y Minas (MEM), donde se aprueba los valores de velocidad del viento
cable dentro de unas pocas horas de ser instalado en una línea se llama su
período de diez años, la condición del cable después de este período se llama
“inicial” y “final después de creep”. Por lo tanto, las hipótesis de cálculo son
flecha – tensión.
31
2.2.7.5 Tensado del Conductor
ferretería eléctrica. Para el proyecto Minera Chinalco Perú S.A. tiene dispuesto
propiedad.
- Vano peso: La carga vertical que ejercen los conductores sobre la estructura
en sus puntos de amarre dividida por la carga unitaria vertical del conductor.
de viento y temperatura.
32
La localización de estructuras considera la optimización en el diseño de las
AAAC
Aislante
También llamados dieléctricos, son los cuerpos que tienen la propiedad de ofrecer una
resistencia muy elevada al paso de la corriente eléctrica; entre ellas tenemos, madera
Aislador
Cuerpo del tipo aislante fabricado para separar eléctricamente y resistir físicamente a
Cable de Guarda
aéreos
Capacidad de Corriente
Conductor
Configuración Optima
de energía.
Corte
33
Perdida de energía eléctrica de todo o parte de un sistema de energía eléctrica.
Disponibilidad
Disponibilidad de Suministro:
Se considera como el tiempo por año en que la energía está presente en los terminales
En Servicio
o señales de comunicación.
Se refiere a los cuerpos en los cuales están soportados las líneas de distribución
Para el material empleado se toma en consideración tanto el factor económico como las
Fuera de Servicio
Fibra Óptica
Intensidad de Corriente
Cuantía de electrones que se movilizan por una sección de conductor eléctrico por
34
Línea
Pararrayos
Potencia
Habilidad producir trabajo mecánico o alguna acción, es expresado como la tensión por
Potencia Aparente
Potencia Efectiva
eléctrica.
Retenida
Ruta Alternativa
el enrutamiento normal.
Tensión
Magnitud de potencial eléctrico que permite que circule corriente, se mide en voltios.
2.4 Hipótesis
35
2.4.2 Hipótesis Específicas
2.5 Variables
Tabla 3
Operacionalización de Variables
36
Capitulo III
Metodología de Investigación
23kV, para lograr el uso de un sistema eléctrico en anillo con las líneas existentes en la
mina mejorado.
37
3.3 Métodos de Investigación
23kV.
Los datos se recopilaron por simulación digital y entrevista. Minera Chinalco Perú S.A.
El tratamiento de los datos del estudio se realizó con los softwares especializados
líneas).
38
Capitulo IV
Resultados de la Investigación
distribución existentes.
Tabla 4
Características de la Línea Troncal Mina (110-TN-001)
Características
Longitud de la línea 5,142 km
Tensión nominal 23 kV
Sistema Trifásico
Nro. de ternas Doble terna
Frecuencia nominal 60 Hz
Tipo de conductor AAAC 240 mm2
Tipo de cable de guarda OPGW 137 mm2
Estructuras de soporte Postes de madera
Configuración Vertical - Doble terna
Tipo de aisladores Porcelana
Fuente: Minera Chinalco Perú
39
Tabla 5
Características de la Línea Lazo Mina (110-TN-001 C2)
Características
Longitud de la línea 3,694 km
Tensión nominal 23 kV
Sistema Trifásico
Nro. de ternas Simple terna
Frecuencia nominal 60 Hz
Tipo de conductor AAAC 240 mm2
Tipo de cable de guarda OPGW 137 mm2
Estructuras de soporte Postes de madera y torrecillas
Configuración Triangular (simple terna)
Tipo de aisladores Porcelana
Fuente: Minera Chinalco Perú.
Tabla 6
Características de la Línea Norte (110-TN-001 C1)
Características
Longitud de la línea 3,070 km
Tensión nominal 23 kV
Sistema Trifásico
Nro. de ternas Simple terna
Frecuencia nominal 60 Hz
Tipo de conductor AAAC 240 mm2
Tipo de cable de guarda OPGW 137 mm2
Estructuras de soporte Postes de madera y torrecillas
Configuración Triangular (simple terna)
Tipo de aisladores Porcelana
Fuente: Minera Chinalco Perú
40
Tabla 7
Parámetros Eléctricos de las Líneas
Tabla 8
Características de las Subestaciones Móviles
Tabla 9
Carga de Equipos de Mina por Subestación Móvil
41
Figura 7
Líneas de Distribución en Mina
y la No 1 están conectadas la misma línea de distribución, si una de ellas tiene que salir
de servicio obliga a un corte de energía en toda la línea Lazo Mina lo que provoca que
Tabla 10
Subestaciones afectadas por Corte de Energía en Configuración Radial
42
Tabla 11
Cortes de Energía Programados por Voladura en Configuración Radial
- Tensión nominal : 23 kV
Aislamiento
En el proyecto se utilizarán aisladores de porcelana tipo estándar. De acuerdo al análisis
Trazo de Ruta
El diseño de ruta de la línea distribución en 23 kV, fue elaborado preliminarmente en
gabinete, posterior a ello se tomaron en campo los puntos topográficos para luego
una longitud de 1.9 km, iniciando en la estructura No 31 de la línea Lazo Mina (110-
43
A continuación, se muestra el cuadro de coordenadas del trazo de ruta en sistema de
Tabla 12
Vértices de la Línea Anillo Mina
Conductor
Minera Chinalco Perú S.A selecciono el conductor de aleación de aluminio (AAAC)
con sección de 240mm2 para todas las líneas de distribución en 23kV de su propiedad,
44
condiciones ambientales y la corriente circulante por el conductor, esta temperatura será
de 45 °C y nos permitirá transportar 15,28 MVA (384 A) por la línea de media tensión.
T CREEP = 15°C.
Parámetros de la Línea
Los parámetros eléctricos para la nueva línea de distribución son los correspondientes
a los calculados para las 2 líneas que se conectaran (Lazo Mina y Norte) debido a la
similitud entre estas, estos datos fueron calculados en el software PARALINE y fueron
Tabla 13
Parámetros Eléctricos de la Línea Anillo Mina
45
Tabla 14
Cargas de Máxima Demanda
Figura 8
Flujo de Potencia en DIGSILENT
Estructuras:
A: Distancia Horizontal entre Conductores:
46
Vano 200 m, D = 1,64 m.
De acuerdo a la sección 235, regla 235.C, Tabla 235-5 del Código Nacional de
las cuales fueron definidas por Minera Chinalco Perú S.A. tomando en cuenta el CNE
Tabla 15
Hipótesis de Cálculo Mecánico del Conductor
I II III V VI
IV
Hipótesis Cond. Viento Temp. Solo Temp.
Viento/Hielo
Inicial Máximo Máxima Hielo Mínima
Temperatura °C 6 0 60 -2 -4 -4
Viento (km/h) 0 113 0 56 0 0
Espesor de Hielo (mm) 0 0 0 12 25 0
% Tiro de Seguridad 7 60 60 60 60 33
Fuente: Minera Chinalco Perú
Tabla 16
Hipótesis de Cálculo Mecánico del Cable de Guarda
I II III V VI
IV
Hipótesis Cond. Viento Temp. Solo Temp.
Viento/Hielo
Inicial Máximo Máxima Hielo Mínima
Temperatura °C 6 0 60 -2 -4 -4
Viento (km/h) 0 113 0 56 0 0
Espesor de Hielo (mm) 0 0 0 12 25 0
% Tiro de Seguridad 7 60 60 60 60 33
Fuente: Minera Chinalco Perú
47
Distribución de Estructuras:
el Software DLTCAD, el cual configuro con los datos del proyecto antes mencionados:
de salida de resultado.
- Datos del Proyecto, se cargan las bases de datos de conductores, armados y soportes
Figura 9
Distribución de Estructuras en DLTCAD
48
Tabla 17
Ubicación de Estructuras
Tipo de Estructuras:
Las estructuras fueron seleccionadas de acuerdo a los ángulos de trazo y de los vanos
encontrados.
49
Tabla 18
Tipos de Estructura
50
Tabla 19
Cálculos Mecánicos del Conductor
20 0.2 1202.84 1202.99 0.03 1372.37 1372.62 0.05 145.9 146.12 0.22 1441.27 1441.64 0.06 1579.98 1580.93 0.12 1466.37 1466.53 0.02
30 0.3 1202.84 1203.04 0.06 1384.62 1385 0.1 202.6 202.94 0.36 1471.07 1471.68 0.14 1687.19 1688.88 0.26 1464.1 1464.31 0.05
40 0.4 1202.84 1203.11 0.11 1400.72 1401.27 0.18 253.42 253.9 0.51 1508.58 1509.48 0.25 1805.38 1807.94 0.43 1460.98 1461.24 0.09
50 0.5 1202.84 1203.18 0.17 1419.91 1420.63 0.27 299.79 300.41 0.68 1551.31 1552.54 0.37 1926.57 1930.12 0.63 1457.03 1457.36 0.14
60 0.6 1202.84 1203.26 0.24 1441.4 1442.33 0.39 342.54 343.31 0.85 1597.24 1598.84 0.52 2047.08 2051.7 0.86 1452.34 1452.74 0.2
70 0.7 1202.84 1203.35 0.33 1464.51 1465.67 0.52 382.25 383.17 1.04 1644.91 1646.92 0.69 2165.2 2170.99 1.1 1446.96 1447.44 0.28
80 0.8 1202.84 1203.45 0.43 1488.67 1490.08 0.67 419.33 420.41 1.24 1693.29 1695.74 0.88 2280.22 2287.25 1.37 1440.97 1441.54 0.36
90 0.9 1202.84 1203.55 0.55 1513.42 1515.1 0.84 454.08 455.34 1.45 1741.67 1744.58 1.08 2391.86 2400.19 1.65 1434.46 1435.12 0.46
100 1 1202.84 1203.67 0.68 1538.38 1540.35 1.01 486.76 488.19 1.67 1789.56 1792.97 1.29 2500.08 2509.78 1.95 1427.51 1428.27 0.57
110 1.1 1202.84 1203.79 0.82 1563.3 1565.57 1.21 517.55 519.17 1.9 1836.65 1840.59 1.53 2604.91 2616.04 2.27 1420.2 1421.08 0.69
120 1.2 1202.84 1203.93 0.97 1587.94 1590.54 1.42 546.62 548.43 2.14 1882.74 1887.23 1.77 2706.48 2719.1 2.6 1412.64 1413.64 0.83
130 1.3 1202.84 1204.07 1.14 1612.17 1615.11 1.64 574.1 576.11 2.39 1927.69 1932.75 2.03 2804.91 2819.07 2.94 1404.89 1406.02 0.98
140 1.4 1202.84 1204.22 1.32 1635.87 1639.16 1.87 600.12 602.33 2.66 1971.43 1977.08 2.3 2900.34 2916.1 3.3 1397.05 1398.31 1.14
150 1.5 1202.84 1204.38 1.52 1658.96 1662.62 2.12 624.78 627.2 2.93 2013.9 2020.18 2.59 2992.9 3010.31 3.67 1389.18 1390.59 1.32
160 1.6 1202.84 1204.55 1.73 1681.39 1685.44 2.38 648.16 650.8 3.21 2055.09 2062.02 2.89 3082.72 3101.83 4.06 1381.35 1382.92 1.51
170 1.7 1202.84 1204.73 1.95 1703.12 1707.58 2.65 670.36 673.23 3.5 2095.01 2102.6 3.19 3169.92 3190.79 4.45 1373.63 1375.36 1.71
180 1.8 1202.84 1204.91 2.19 1724.14 1729.01 2.93 691.45 694.55 3.81 2133.65 2141.94 3.52 3254.63 3277.29 4.86 1366.05 1367.96 1.93
51
Vano Desnivel Hip. 1 Hip. 2 Hip. 3 Hip. 4 Hip. 5 Hip. 6
TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha
(m) (m)
(Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m)
190 1.9 1202.84 1205.11 2.44 1744.43 1749.74 3.23 711.49 714.83 4.13 2171.05 2180.05 3.85 3336.95 3361.46 5.28 1358.67 1360.76 2.16
200 2 1202.84 1205.31 2.7 1764 1769.76 3.54 730.55 734.13 4.45 2207.22 2216.96 4.2 3416.98 3443.38 5.72 1351.51 1353.79 2.41
210 2.1 1202.84 1205.52 2.98 1782.85 1789.07 3.86 748.69 752.52 4.79 2242.2 2252.7 4.56 3494.82 3523.16 6.16 1344.6 1347.08 2.67
220 2.2 1202.84 1205.75 3.27 1800.99 1807.7 4.2 765.95 770.05 5.14 2276.02 2287.29 4.93 3570.55 3600.88 6.62 1337.96 1340.65 2.94
230 2.3 1202.84 1205.98 3.57 1818.45 1825.65 4.54 782.39 786.75 5.5 2308.71 2320.79 5.31 3644.26 3676.62 7.09 1331.6 1334.51 3.23
240 2.4 1202.84 1206.21 3.89 1835.23 1842.94 4.9 798.06 802.69 5.87 2340.31 2353.21 5.7 3716.02 3750.46 7.57 1325.52 1328.66 3.53
250 2.5 1202.84 1206.46 4.22 1851.35 1859.59 5.27 812.99 817.9 6.25 2370.85 2384.59 6.11 3785.91 3822.47 8.07 1319.74 1323.12 3.85
260 2.6 1202.84 1206.72 4.57 1866.84 1875.62 5.66 827.22 832.42 6.65 2400.36 2414.97 6.53 3853.99 3892.72 8.57 1314.23 1317.86 4.18
270 2.7 1202.84 1206.98 4.93 1881.72 1891.05 6.05 840.79 846.3 7.05 2428.89 2444.39 6.95 3920.33 3961.27 9.09 1309.01 1312.9 4.53
280 2.8 1202.84 1207.26 5.3 1896 1905.91 6.46 853.75 859.55 7.47 2456.46 2472.87 7.4 3984.99 4028.19 9.62 1304.07 1308.22 4.89
290 2.9 1202.84 1207.54 5.68 1909.72 1920.22 6.88 866.11 872.23 7.9 2483.1 2500.44 7.85 4048.03 4093.53 10.15 1299.39 1303.81 5.26
300 3 1202.84 1207.83 6.08 1922.89 1933.99 7.31 877.91 884.35 8.34 2508.86 2527.15 8.31 4109.49 4157.34 10.71 1294.96 1299.67 5.65
310 3.1 1202.84 1208.13 6.5 1935.53 1947.25 7.76 889.19 895.95 8.79 2533.75 2553.02 8.79 4169.44 4219.68 11.27 1290.78 1295.78 6.05
320 3.2 1202.84 1208.44 6.92 1947.67 1960.02 8.21 899.96 907.06 9.26 2557.82 2578.09 9.28 4227.92 4280.6 11.84 1286.82 1292.13 6.47
330 3.3 1202.84 1208.76 7.36 1959.32 1972.32 8.68 910.25 917.7 9.73 2581.08 2602.38 9.78 4284.97 4340.13 12.43 1283.09 1288.71 6.9
340 3.4 1202.84 1209.09 7.81 1970.5 1984.17 9.17 920.1 927.89 10.22 2603.58 2625.91 10.29 4340.64 4398.33 13.02 1279.57 1285.51 7.35
350 3.5 1202.84 1209.43 8.28 1981.24 1995.59 9.66 929.51 937.66 10.72 2625.33 2648.73 10.82 4394.98 4455.23 13.63 1276.24 1282.52 7.8
360 3.6 1202.84 1209.77 8.76 1991.56 2006.6 10.17 938.52 947.04 11.23 2646.36 2670.85 11.35 4448.01 4510.88 14.25 1273.1 1279.71 8.28
370 3.7 1202.84 1210.12 9.26 2001.46 2017.22 10.69 947.14 956.03 11.76 2666.71 2692.31 11.9 4499.79 4565.32 14.88 1270.13 1277.1 8.76
380 3.8 1202.84 1210.49 9.76 2010.98 2027.46 11.22 955.39 964.66 12.3 2686.39 2713.12 12.46 4550.35 4618.58 15.52 1267.33 1274.65 9.27
52
Vano Desnivel Hip. 1 Hip. 2 Hip. 3 Hip. 4 Hip. 5 Hip. 6
TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha
(m) (m)
(Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m)
390 3.9 1202.84 1210.86 10.28 2020.12 2037.35 11.77 963.29 972.96 12.85 2705.43 2733.31 13.03 4599.72 4670.7 16.17 1264.68 1272.37 9.78
400 4 1202.84 1211.24 10.82 2028.9 2046.89 12.33 970.86 980.92 13.41 2723.84 2752.91 13.62 4647.94 4721.71 16.84 1262.18 1270.25 10.31
410 4.1 1202.84 1211.63 11.37 2037.34 2056.11 12.9 978.11 988.58 13.99 2741.67 2771.93 14.22 4695.03 4771.64 17.51 1259.81 1268.26 10.85
420 4.2 1202.84 1212.02 11.93 2045.46 2065.01 13.48 985.07 995.95 14.57 2758.92 2790.4 14.83 4741.04 4820.53 18.2 1257.57 1266.42 11.41
430 4.3 1202.84 1212.43 12.5 2053.26 2073.62 14.08 991.73 1003.04 15.17 2775.61 2808.34 15.45 4785.99 4868.41 18.9 1255.45 1264.7 11.98
440 4.4 1202.84 1212.85 13.09 2060.76 2081.95 14.69 998.13 1009.87 15.79 2791.77 2825.77 16.08 4829.91 4915.3 19.61 1253.45 1263.1 12.56
450 4.5 1202.84 1213.27 13.7 2067.97 2090 15.31 1004.27 1016.45 16.41 2807.42 2842.71 16.73 4872.83 4961.23 20.33 1251.54 1261.62 13.16
460 4.6 1202.84 1213.7 14.31 2074.92 2097.8 15.94 1010.16 1022.79 17.05 2822.57 2859.17 17.39 4914.77 5006.24 21.07 1249.74 1260.25 13.77
470 4.7 1202.84 1214.14 14.94 2081.59 2105.35 16.59 1015.82 1028.9 17.7 2837.24 2875.18 18.06 4955.77 5050.34 21.81 1248.02 1258.97 14.4
480 4.8 1202.84 1214.6 15.59 2088.02 2112.67 17.25 1021.25 1034.8 18.37 2851.46 2890.75 18.74 4995.84 5093.57 22.57 1246.4 1257.8 15.04
490 4.9 1202.84 1215.06 16.24 2094.21 2119.76 17.93 1026.47 1040.5 19.04 2865.23 2905.91 19.44 5035.01 5135.94 23.34 1244.85 1256.71 15.69
500 5 1202.84 1215.52 16.91 2100.17 2126.65 18.62 1031.49 1046 19.73 2878.57 2920.65 20.15 5073.31 5177.49 24.12 1243.39 1255.71 16.36
Fuente: Elaboración propia
Tabla 20
Cálculos Mecánicos del Cables de Guarda
20 0.2 1267.98 1268.12 0.02 1404.3 1404.52 0.04 563.19 563.32 0.06 1464.94 1465.27 0.06 1597.01 1597.85 0.11 1480.61 1480.76 0.02
30 0.3 1267.98 1268.17 0.06 1413.68 1414 0.08 587.17 587.36 0.12 1494.23 1494.77 0.13 1706.8 1708.28 0.24 1478.72 1478.92 0.05
53
Vano Desnivel Hip. 1 Hip. 2 Hip. 3 Hip. 4 Hip. 5 Hip. 6
TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha
(m) (m)
(Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m)
40 0.4 1267.98 1268.23 0.1 1426.12 1426.56 0.15 614.63 614.91 0.2 1531.19 1531.97 0.22 1827.57 1829.79 0.39 1476.12 1476.37 0.08
50 0.5 1267.98 1268.29 0.15 1441.1 1441.68 0.23 643.37 643.74 0.3 1573.38 1574.44 0.33 1951.23 1954.3 0.58 1472.85 1473.16 0.13
60 0.6 1267.98 1268.37 0.22 1458.05 1458.78 0.33 672.12 672.6 0.42 1618.82 1620.19 0.47 2074.06 2078.05 0.78 1468.97 1469.35 0.19
70 0.7 1267.98 1268.45 0.3 1476.46 1477.37 0.44 700.2 700.79 0.55 1666.05 1667.76 0.62 2194.38 2199.36 1 1464.53 1464.98 0.26
80 0.8 1267.98 1268.54 0.39 1495.88 1496.98 0.57 727.28 727.99 0.69 1714.03 1716.11 0.79 2311.49 2317.52 1.24 1459.6 1460.13 0.34
90 0.9 1267.98 1268.63 0.5 1515.92 1517.22 0.71 753.17 754.01 0.84 1762.06 1764.53 0.97 2425.1 2432.24 1.5 1454.26 1454.88 0.43
100 1 1267.98 1268.74 0.61 1536.27 1537.8 0.86 777.83 778.8 1 1809.64 1812.53 1.16 2535.19 2543.5 1.77 1448.57 1449.29 0.54
110 1.1 1267.98 1268.85 0.74 1556.69 1558.45 1.03 801.23 802.34 1.18 1856.45 1859.77 1.37 2641.82 2651.34 2.06 1442.62 1443.45 0.65
120 1.2 1267.98 1268.97 0.88 1576.98 1578.98 1.21 823.4 824.66 1.36 1902.27 1906.05 1.59 2745.11 2755.88 2.36 1436.48 1437.41 0.78
130 1.3 1267.98 1269.1 1.04 1597 1599.26 1.4 844.38 845.8 1.56 1946.96 1951.23 1.83 2845.18 2857.26 2.67 1430.21 1431.26 0.92
140 1.4 1267.98 1269.23 1.2 1616.63 1619.16 1.61 864.23 865.81 1.77 1990.45 1995.22 2.07 2942.18 2955.61 3 1423.89 1425.06 1.07
150 1.5 1267.98 1269.37 1.38 1635.79 1638.6 1.82 882.99 884.74 1.98 2032.69 2037.97 2.33 3036.25 3051.08 3.33 1417.56 1418.87 1.24
160 1.6 1267.98 1269.52 1.57 1654.42 1657.53 2.05 900.72 902.64 2.21 2073.65 2079.47 2.6 3127.53 3143.8 3.68 1411.29 1412.74 1.41
170 1.7 1267.98 1269.68 1.78 1672.5 1675.91 2.29 917.47 919.58 2.45 2113.34 2119.71 2.88 3216.14 3233.89 4.04 1405.11 1406.7 1.6
180 1.8 1267.98 1269.84 1.99 1689.98 1693.71 2.54 933.31 935.6 2.7 2151.76 2158.71 3.17 3302.2 3321.47 4.41 1399.06 1400.81 1.8
190 1.9 1267.98 1270.02 2.22 1706.85 1710.92 2.8 948.27 950.76 2.97 2188.93 2196.47 3.47 3385.82 3406.65 4.8 1393.18 1395.09 2.02
200 2 1267.98 1270.2 2.46 1723.12 1727.53 3.08 962.42 965.11 3.24 2224.87 2233.03 3.78 3467.11 3489.54 5.19 1387.48 1389.57 2.25
210 2.1 1267.98 1270.39 2.71 1738.78 1743.55 3.36 975.8 978.7 3.52 2259.62 2268.41 4.11 3546.16 3570.23 5.59 1381.99 1384.26 2.49
220 2.2 1267.98 1270.58 2.97 1753.85 1758.98 3.66 988.45 991.56 3.81 2293.21 2302.64 4.44 3623.06 3648.81 6.01 1376.72 1379.18 2.74
230 2.3 1267.98 1270.78 3.25 1768.32 1773.83 3.97 1000.42 1003.76 4.12 2325.67 2335.77 4.79 3697.91 3725.37 6.44 1371.67 1374.32 3
54
Vano Desnivel Hip. 1 Hip. 2 Hip. 3 Hip. 4 Hip. 5 Hip. 6
TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha
(m) (m)
(Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m)
240 2.4 1267.98 1271 3.54 1782.21 1788.12 4.29 1011.75 1015.31 4.44 2357.03 2367.81 5.14 3770.76 3799.98 6.87 1366.85 1369.71 3.28
250 2.5 1267.98 1271.21 3.84 1795.55 1801.86 4.62 1022.48 1026.27 4.76 2387.33 2398.82 5.51 3841.71 3872.72 7.32 1362.25 1365.33 3.57
260 2.6 1267.98 1271.44 4.15 1808.34 1815.07 4.96 1032.63 1036.67 5.1 2416.6 2428.81 5.89 3910.82 3943.66 7.78 1357.89 1361.18 3.88
270 2.7 1267.98 1271.67 4.48 1820.6 1827.76 5.31 1042.26 1046.55 5.45 2444.89 2457.83 6.27 3978.16 4012.86 8.25 1353.74 1357.27 4.2
280 2.8 1267.98 1271.92 4.82 1832.36 1839.96 5.67 1051.38 1055.92 5.81 2472.21 2485.92 6.67 4043.78 4080.39 8.73 1349.82 1353.57 4.52
290 2.9 1267.98 1272.17 5.17 1843.63 1851.68 6.05 1060.02 1064.83 6.18 2498.62 2513.09 7.08 4107.75 4146.3 9.21 1346.1 1350.1 4.87
300 3 1267.98 1272.42 5.53 1854.43 1862.94 6.44 1068.23 1073.3 6.57 2524.13 2539.4 7.5 4170.12 4210.65 9.71 1342.57 1346.83 5.22
310 3.1 1267.98 1272.69 5.91 1864.78 1873.76 6.84 1076.01 1081.36 6.96 2548.78 2564.86 7.93 4230.95 4273.49 10.22 1339.25 1343.76 5.59
320 3.2 1267.98 1272.96 6.29 1874.69 1884.17 7.25 1083.4 1089.04 7.37 2572.6 2589.5 8.38 4290.27 4334.87 10.74 1336.1 1340.88 5.97
330 3.3 1267.98 1273.24 6.69 1884.19 1894.17 7.67 1090.41 1096.35 7.78 2595.61 2613.37 8.83 4348.15 4394.84 11.27 1333.12 1338.18 6.36
340 3.4 1267.98 1273.53 7.1 1893.3 1903.78 8.1 1097.08 1103.31 8.21 2617.86 2636.49 9.29 4404.62 4453.44 11.82 1330.31 1335.65 6.77
350 3.5 1267.98 1273.82 7.53 1902.02 1913.03 8.54 1103.42 1109.96 8.65 2639.37 2658.88 9.77 4459.73 4510.71 12.37 1327.65 1333.29 7.19
360 3.6 1267.98 1274.13 7.97 1910.39 1921.93 9 1109.45 1116.3 9.11 2660.16 2680.57 10.25 4513.52 4566.7 12.93 1325.14 1331.08 7.62
370 3.7 1267.98 1274.44 8.41 1918.4 1930.5 9.47 1115.18 1122.35 9.57 2680.26 2701.59 10.75 4566.03 4621.45 13.5 1322.77 1329.01 8.07
380 3.8 1267.98 1274.76 8.88 1926.09 1938.75 9.95 1120.64 1128.14 10.04 2699.69 2721.96 11.26 4617.3 4674.99 14.08 1320.52 1327.08 8.52
390 3.9 1267.98 1275.08 9.35 1933.46 1946.69 10.44 1125.84 1133.67 10.53 2718.49 2741.72 11.78 4667.36 4727.36 14.67 1318.4 1325.28 8.99
400 4 1267.98 1275.42 9.84 1940.53 1954.34 10.94 1130.8 1138.97 11.03 2736.67 2760.87 12.31 4716.24 4778.6 15.28 1316.39 1323.6 9.47
410 4.1 1267.98 1275.76 10.33 1947.31 1961.72 11.45 1135.52 1144.04 11.54 2754.25 2779.45 12.85 4763.98 4828.73 15.89 1314.48 1322.04 9.97
420 4.2 1267.98 1276.11 10.84 1953.81 1968.84 11.98 1140.02 1148.9 12.06 2771.26 2797.47 13.4 4810.62 4877.79 16.52 1312.68 1320.58 10.47
430 4.3 1267.98 1276.46 11.37 1960.06 1975.71 12.52 1144.32 1153.56 12.6 2787.72 2814.96 13.97 4856.18 4925.81 17.15 1310.98 1319.23 10.99
55
Vano Desnivel Hip. 1 Hip. 2 Hip. 3 Hip. 4 Hip. 5 Hip. 6
TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha TiroH TMax Flecha
(m) (m)
(Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m) (Kg) (Kg) (m)
440 4.4 1267.98 1276.83 11.9 1966.05 1982.34 13.07 1148.42 1158.04 13.14 2803.64 2831.94 14.54 4900.69 4972.83 17.79 1309.36 1317.97 11.53
450 4.5 1267.98 1277.2 12.45 1971.8 1988.74 13.63 1152.34 1162.33 13.7 2819.06 2848.43 15.13 4944.19 5018.86 18.45 1307.82 1316.81 12.07
460 4.6 1267.98 1277.58 13.01 1977.33 1994.93 14.2 1156.08 1166.46 14.27 2833.98 2864.44 15.72 4986.69 5063.94 19.12 1306.36 1315.73 12.63
470 4.7 1267.98 1277.97 13.58 1982.64 2000.91 14.79 1159.65 1170.43 14.85 2848.42 2879.99 16.33 5028.23 5108.09 19.79 1304.98 1314.73 13.2
480 4.8 1267.98 1278.36 14.17 1987.74 2006.7 15.39 1163.08 1174.25 15.45 2862.41 2895.1 16.95 5068.83 5151.34 20.48 1303.67 1313.81 13.78
490 4.9 1267.98 1278.77 14.76 1992.65 2012.3 15.99 1166.35 1177.93 16.05 2875.95 2909.8 17.58 5108.52 5193.72 21.18 1302.42 1312.96 14.37
500 5 1267.98 1279.18 15.37 1997.36 2017.73 16.62 1169.48 1181.48 16.67 2889.07 2924.08 18.23 5147.32 5235.25 21.89 1301.23 1312.18 14.98
Fuente: Elaboración propia
56
Pararrayos de Línea
Son del tipo TLA (Transmission Line Surge Arrester) para instalación a la intemperie e
Pararrayos de Seccionamiento
Son de tipo oxido metálico para instalación a la intemperie en las estructuras de fin de
Fundación de Postes
Para el poste de madera con longitud de 18,29 m (60 pies) empleado en el estudio, la
Retenidas
Las retenidas fueron instaladas en las estructuras de ángulo, anclaje y anclaje angular
con el objetivo amortiguar los esfuerzos mecánicos que no puedan soportar las
estructuras. El ángulo formado por el eje del poste y el cable de la retenida inclina es
de 37°.
Puesta a Tierra
Gran parte de la ruta de la línea de distribución está conformada por terreno semi
rocoso, es por ello que se ha diseñado un sistema de puesta a tierra para cada estructura,
variable y una varilla de cobre recubierta con acero tipo Copperweld hasta alcanzar el
57
4.1.2.2 Descripción Técnica de la Línea de Distribución Anillo Mina
Tabla 21
Características Principales de la Línea Anillo Mina
Características
Longitud de la línea 1,926 km
Tensión nominal 23 kV
Sistema Trifásico
Nro. de ternas Simple terna
Frecuencia nominal 60 Hz
Tipo de conductor AAAC 240 mm2
Tipo de cable de guarda OPGW 137 mm2
Estructuras de soporte Postes de madera y torrecillas
Configuración Triangular (simple terna)
Aislamiento Cadena de aisladores de porcelana, tipo Estándar 254
x146, 120 kN de carga de rotura
Puesta a tierra Conductor de acero recubierto con cobre de 35 mm2 y
conductor de cobre de 35 mm2.
Fuente: Elaboración propia
58
Tabla 22
Características del Conductor AAAC 240
Características
Tipo AAAC
Material Aluminio
Sección 240 mm²
Sección real 235.88 mm²
Diámetro exterior 19.88 mm²
No hilos 19
Diámetro de cada hilo 3.975 mm
Pesó unitario 0.650 kg/m
Carga de rotura 69.39 kN
Resistencia eléctrica a 20°C en DC 0.142 ohm/km
Fuente: Elaboración propia
de fibra óptica, con la finalidad de obtener mayores ventajas al transportar las señales
Tabla 23
Características del Cable de Guarda
Características
Tipo OPGW
Material Aluminio
Sección 137.45 mm²
Diámetro 16 mm
Peso unitario 0.623 kg/m
Carga de rotura mínimo 9057 kg
Coeficiente térmico de dilatación 15 x 10-6 1/°C
Módulo de elasticidad final 12000 kg/mm²
Número máximo de fibras ópticas 24
Fuente: Elaboración propia
59
Aislamiento
Sobre las estructuras se utilizaron cadenas de aisladores de porcelana tipo estándar, con
ensamble bola y casquillo (Ball & socket). Las cadenas de aisladores de porcelana, para
de porcelana, para estructuras de suspensión angular y las estructuras tipo anclaje estará
Tabla 24
Características del Aislador Estándar de Porcelana
Características
Clase ANSI 52-5
Tipo Ball & Socket
Diámetro 245 mm
Altura 146 mm
Línea de fuga 292 mm
Fuente: Elaboración propia
60
Tabla 25
Características de los Ensambles de las Cadenas de Aisladores
Ensamble Elementos
Grillete recto
Adaptador Anillo - Bola
Cadena de Suspensión Angular
Adaptador Casquillo - Ojo (largo)
Grapa de Angulo, conductor AAAC 240 mm²
Grillete recto
Adaptador Anillo - Bola
Cadena de Anclaje Normal
Adaptador Casquillo - Ojo (largo)
Grapa de Anclaje tipo pistola, conductor AAAC
240 mm²
Grillete recto
Aislador Tipo Line Post
Grapa de Suspensión, conductor AAAC 240 mm²
Fuente: Elaboración propia
uso de ensambles de contrapesos para los casos donde el ángulo de línea es mayor a
utilizarán contrapesos.
Postes y Crucetas:
La cruceta es de madera importada Douglas Fir que cumple con lo establecido por la
Accesorios metálicos para postes y crucetas que se utilizaron son: pernos maquinados,
perno-ojo, tuerca-ojo, perno tipo doble armado, riostra de A°G°, gancho tipo cuello,
arandelas y otros.
61
Tipos de Armados:
De acuerdo a los ángulos del trazo de ruta, se ha previsto los tipos de armado
Puesta a Tierra
El tipo de puesta a tierra fue asignado en función de la apreciación del tipo de terreno
igual a 25 ohm, para este fin se utilizará, el tipo de puesta a tierra a emplearse es:
PAT 0: Sistema de PT con una varilla vertical para cada estructura monoposte
Anti Vibradores
La vibración de los conductores en líneas aéreas, bajo la acción del viento conocida
como “vibración eólica” puede causar fallas por fatiga de los conductores en los puntos
de soporte.
vibración resonante ocurre en los cables de las líneas aéreas sin cambio apreciable de
su longitud de modo que los puntos de apoyo permanecen casi estacionarios. Estas
vibraciones son ondas estacionarias de baja amplitud y alta frecuencia. Las vibraciones
producidas por el viento generan frecuencias de peligro según estudios dentro del rango
vibraciones resonantes y los mayores de 24 km/h tienden a producir ráfagas. Los vientos
62
turbulentos producen diferentes frecuencias en los conductores y las vibraciones no se
Para evitar fatiga en los conductores, es necesario reducir las vibraciones resonantes,
Pararrayos de Línea:
Los pararrayos serán del tipo Transmission Line Surge Arrester “TLA” para uso en
ambiente severamente contaminado, con una línea de fuga mínima entre fase-tierra de
largos años de uso; las partes selladas estarán diseñadas de tal modo de prevenir la
penetración de agua.
El pararrayos cuenta con un elemento para liberar los gases creados por el arco que se
originen en el interior, cuando la presión de los mismos llegue a valores que podrían
63
Las partes metálicas de hierro o acero deben estar protegidas contra la corrosión
Tabla 26
Características del TLA
Características
Especificación IEC 60099-4
Corriente de descarga nominal 10 kA
Clase de descarga de la línea 3
Capacidad de disipación de energía 8 kJ/kV
Tensión Nominal de Red 23 kV
Tensión Máxima de servicio 25.5 kV
Tensión Nominal del Pararrayos 27 kV
Tensión de operación continua 22 kV
Tensión residual Máxima Corriente Nominal
65 kV
de Descarga (10 KA - 8/20)
Frecuencia Nominal 60 Hz
Línea de fuga mínima 1400 mm
Tipo de Instalación Vertical en fase inferior
Número de pararrayos por estructura 1o2
Fuente: Elaboración propia
Pararrayos de Seccionamiento
Se utilizaron pararrayos en las estructuras de seccionamiento, las cuales son las ultimas
estructuras de las líneas existentes Lazo Mina y Línea Norte (estructuras que se
Los pararrayos son del tipo oxido metálico para instalación a la intemperie en postes de
ambiente severamente contaminado, con una línea de fuga mínima entre fase-tierra de
64
largos años de uso; las partes selladas estarán diseñadas de tal modo de prevenir la
penetración de agua.
El pararrayos cuenta con un elemento para liberar los gases creados por el arco que se
originen en el interior, cuando la presión de los mismos llegue a valores que podrían
Las partes metálicas de hierro o acero deben estar protegidas contra la corrosión
Tabla 27
Características del Pararrayos de Seccionamiento
Características
Especificación IEC 60099-4
Corriente de descarga Nominal 10 kA
Clase de descarga de la línea 2
Capacidad de disipación de energía 4.5 kJ/kV
Tensión Nominal de Red 23 kV
Tensión Máxima de servicio 25.5 kV
Tensión Nominal del Pararrayos 21 kV
Tensión de operación continua 17 kV
Tensión residual Máxima Corriente Nominal
62.5 kV
de Descarga (10 KA - 8/20)
Frecuencia Nominal 60 Hz
Línea de fuga mínima 784.3 mm
Tipo de Instalación Horizontal en poste
Número de pararrayos por estructura 3
Fuente: Elaboración propia
subestación móvil 2.
65
Figura 10
Instalación de la Línea Anillo Mina
alimentación de energía eléctrica hacia las subestaciones móviles sea de lado a lado,
funcionamiento de otra.
Tabla 28
Subestaciones Afectadas por Corte de Energía con la Línea Anillo Mina
Como se puede observar en la tabla 29, con la instalación de la Línea Anillo Mina se
logra reducir a una cantidad de 360 cortes de energía programados por voladura al año.
66
Tabla 29
Cortes Programados por Voladura con la Línea Anillo Mina
eléctrico de las subestaciones móviles de Minera Chinalco Perú S.A, cuando el número
Ho > = 600
Hi < 600
Tabla 30
Cuadro Estadístico de Cortes Programados por Voladura
hipótesis de investigación.
67
4.3 Discusión de Resultados
Estos resultados guardan relación con lo que sostiene Mendez (2009), quien señala que
la configuración de una red eléctrica esta correctamente diseñada si esta ofrece caminos
alternativos hacia la fuente de alimentación eléctrica en caso de falla y/o casos de corte
de energía programados en ciertos tramos de la red. Este autor manifiesta que debe
resuelto.
también se observa que al ser estos cálculos tediosos e iterativos es conveniente uso se
softwares especializados como DLTCAD para no caer en errores, que concuerda con lo
No obstante, Santos (2013) y Rivadeneira (2013) solo se refieren al diseño de una línea
demanda eléctrica sino también buscar que nuestro sistema final sea el más confiable
posible.
68
Conclusiones
subestaciones móviles puedan tener cortes de energía sin afectar al funcionamiento de la otra.
Además, ahora tienen una línea de distribución de respaldo que las alimentara en caso de
Para el diseño del proyecto se cumplió con la normativa vigente y se emplearon armados que
móviles se ubican por debajo del 5 % el cuál es el límite permitido por la norma.
El circuito final está en capacidad de incluir una subestación móvil futura en el tramo de la
Línea Norte.
69
Recomendaciones
del conductor, esto es, para la máxima temperatura del conductor y en condición final (después
de creep).
(recloser) en los puntos de conexión con la nueva línea de distribución Anillo Mina, para
70
Bibliografía
Dammert, A., Garcia, R., & Molinelli, F. (2013). Regulación y Supervición del Sector
Darmmert, A., Monilelly, F., & Carbajal, M. (2011). Fundamentos Tecnicos y Económincos
Institute of Electrical and Electronics Engineers. (1992). Guide to the installation of Overhead
Azcapotzalco.
Juárez, J. (1995). Sistemas de Distribución de Energía Eléctrica. México: Snas Serif Editores.
Laplante, P. (2000). Electrical Engieering Dictionary. Boca Raton: CRC Press LLC.
Mendez, C. (2009). Confiabilidad de una Red de Energía Eléctrica para un Usuario Industrial.
Tesis de grado para optar el Título de Ingeniero Eléctrico Electrónico, Universidad San
71
Santos, W. (2013). Línea en 22.9kV SE Huamachuco-Minaspampa. Tesis para optar título
https://www.electrical-
installation.org/enwiki/Availability_and_quality_of_electrical_power
72
Anexos
73
Anexo 1: Cálculo de Aislamiento
Cadenas de suspensión
CR fs Cvt 2 + Ctt 2
Donde:
El cálculo se realiza para el conductor seleccionado AAAC 240 mm², y los valores de carga
Considerando la carga de rotura del aislador estándar 52-3, CR = 120kN, el factor de seguridad
El análisis se realizó para la condición más crítica (Hipótesis N°5 – Presencia de Hielo)
Cadenas de anclaje
CR fs Cl
Donde:
74
Cl = Carga longitudinal máxima
Donde:
El análisis se realizó para la condición más crítica (Hipótesis N°5 – Presencia de Hielo). De
Las estructuras con aisladores Line Post se utilizará para superficies planas.
El tratamiento del cálculo de la tensión crítica disruptiva es similar al utilizado para evaluar las
con las curvas dadas por los fabricantes de aisladores de acuerdo a la Norma IEC. A
75
a) Por sobretensión de impulso
Por sobretensiones de impulso, el número de aisladores de porcelana requeridos son tres (03),
• Para el caso de utilizar aisladores Line Post, se utilizaría el Horizontal Line Post Stud Base
• Para el caso de utilizar aisladores Line Post, se utilizaría el Horizontal Line Post Stud Base
las lluvias son periódicas entre los meses de enero a marzo y limpian los aisladores. Por tanto,
se puede establecer una línea de fuga específica de 31 mm/kV de acuerdo a Norma IEC-60815-
Tabla II.
Df = lf x Vmax x kd
Donde:
Df = 31x23x1.1x1 = 784.3mm
Considerando el aislador estándar de 255 x 146 mm con una línea de fuga de 292 mm, el
76
D) Conclusión
Los aisladores de porcelana tipo estándar de 254 x 146 mm que conformaran la cadena de
suspensión son tres (03) unidades y la cadena de anclaje estará conformada también por (04)
unidades.
Considerando el aislador Horizontal Line Post Stud Base Mounting (Catálogo de referencia
NGK. No L1-SN131-27), para tensiones del orden de los 46/69 kV con una línea de fuga de
• En utilizar este aislador ya que cumple con tener una Tensión Crítica Disruptiva mayor a las
• Tensión de aislamiento del Horizontal Line Post Stud Base Mounting L1-SN131-27:
77
Anexo 2: Puesta a Tierra
en 23kV
78
2.- Procesamiento de Datos
79
80
81
82
83
3.- Resumen de la Estratificación del Terreno con Valores Asumidos para Suelos
Similares al Proyecto
84
Anexo 3: Cálculos Eléctrico del Pararrayos
Usamos un factor de 1.35 por ser alta la resistencia de puesta a tierra según cuadro
85
Ver tabla siguiente.
Tabla de factores de cálculo
Tipo de conexionado a malla de tierra Factor a utilizar
Por tanto, el voltaje nominal del pararrayo debería ser como mínimo de 27kV.
86
81.25KV. Si tomamos un impulso de 10KAMP; El voltaje residual del pararrayo de Ur =
27KV es de 72.8KV
(𝐵𝐼𝐿 − 𝑉𝑟𝑒𝑠𝑖𝑑𝑢𝑎𝑙) × 100%
𝑀. 𝑃 =
𝑉𝑟𝑒𝑠𝑖𝑑𝑢𝑎𝑙
Entonces:
(91.25 − 72.8) × 100%
𝑀. 𝑃 = = 25%
72.8
Para la protección el valor está en el rango de protección
Cálculo del contenedor polimérico de pararrayo
BIL del transformador o equipo a nivel del mar : 150 KV
Factor de derrateo a 5000 msnm : 0,73 SEGUN ANSI C57
BIL requerido en el contenedor : 150/0,73= 205 KV
Para el pararrayo : Ur = 27kV
El BIL estándar del contenedor es de 253kv, por lo que es suficiente.
Cálculo de la distancia de fuga (según IEC-71-2)
Nivel de contaminación Distancia de fuga / voltaje fase a tierra
(mm/k.v.)
Cont. no significativa 20 a 25
Cont. suave 30 a 35
Contaminación pesada 40 a 50
Contaminación muy pesada mayor a 60
87
Conclusión:
Especificación IEC 60099-4
Corriente de descarga Nominal 10 kA
Clase de descarga de la línea 2
Capacidad de disipación energía 4,5 kJ/kV
Tensión Nominal de la Red 23 kV
Tensión Máxima de servicio 25,5 kV
Tensión Nominal del Pararrayos 21 kV
Tensión de operación continúa 21,6 kV
Tensión Residual Máxima a Corriente
Nominal de Descarga (10 kA - 8/20) 72,8 kV
Frecuencia Nominal 60 Hz
Línea de fuga mínima 784,3 mm
Tipo de Instalación vertical en fase inferior
Numero de pararrayos por estructura 1o2
Figura 1
88
Anexo 4: Flujo de Potencia
89
Anexo 5: Planilla de Estructuras
AMORTIGUADOR
AMORTIGUADOR
VANO VANO VANO
TIPO ACUMULADA COTA ANGULO TIPO N°
FASE
CG
N° FUNCIÓN ADELANTE PESO VIENTO PAT
ESTRUCTURA (m) (m) (°) POSTE RETENIDA
(m) (m) (m)
90
Anexo 5: Fotografías
91
Foto 3: Construcción de la Línea Anillo Mina
92