Documentos de Académico
Documentos de Profesional
Documentos de Cultura
JA10084331
SERVICIO DE INGENIERÍA, COMPRAS,
CONSTRUCCIÓN, PRUEBAS Y PUESTA EN SERVICIO
PARA LA NUEVA SUBESTACIÓN RÍO, BAJO
MODALIDAD DE CONTRATACIÓN EPC
(ENGINEERING, PURCHASE AND CONSTRUCTION)
SUBESTACIÓN RÍO
LCL 6300191091
CIS 21-138
MÓDULO SUBESTACIÓN 115 kV
DISEÑO PLUVIAL
ERI-WE-CED-MEM-075-059-1
REVISIÓN 3
AJUSTES EMITIDOS
08/06/2022
2 POR J.E JAIME A. DÍAZ A. DÍAZ Y. CAMACHO
Tabla de Contenido
1. NOMENCLATURA ........................................................................................................................5
2. ESTIMACIÓN DE CURVAS IDF .......................................................................................................5
3. ÁREAS AFERENTES DE DRENAJE ...................................................................................................7
4. CÁLCULO DE CAUDALES Y DIMENSIONAMIENTO DE COLECTORES ............................................... 10
5. CÁLCULO HIDRÁULICO COLECTORES .......................................................................................... 11
6. CÁLCULO SUMIDEROS DE VENTANA LATERAL CON DEPRESIÓN................................................... 13
7. CÁLCULO CANALES EN CONCRETO ............................................................................................. 15
7.1 RESULTADOS CANAL CA1 ................................................................................................................. 15
7.2 RESULTADOS CA2 ........................................................................................................................ 16
7.3 RESULTADOS CA3 ........................................................................................................................ 17
7.2 RESULTADOS CANAL EXTERIOR 1 Y 2 PERIMETRALES A LOS MUROS DE CONTENCIÓN...................................... 18
8. DISEÑO DE CAJAS PLUVIALES, SUMIDEROS Y CANALES ............................................................... 18
8.1 VERIFICACIÓN CORTANTE. .............................................................................................................. 21
8.2 VERIFICACIÓN DE CAPACIDAD PORTANTE. .......................................................................................... 21
8.3 VERIFICACIÓN DE ASENTAMIENTO. ................................................................................................... 22
8.4 VERIFICACIÓN DE ACERO ................................................................................................................ 23
8.5 DISEÑO DE CANALES EXTERIORES 1 Y 2 .............................................................................................. 24
1.1 VERIFICACIÓN CORTANTE. .............................................................................................................. 27
1.2 VERIFICACIÓN DE CAPACIDAD PORTANTE. .......................................................................................... 27
1.3 VERIFICACIÓN DE ASENTAMIENTO. ................................................................................................... 28
1.4 VERIFICACIÓN DE ACERO ................................................................................................................ 30
Lista de Tablas
Tabla 1: Áreas aferentes de drenaje. ........................................................................................................................ 9
Tabla 2: Cálculo hidráulico de colectores (Parte 1). ......................................................................................... 11
Tabla 3: Cálculo hidráulico de colectores (Parte 2). ......................................................................................... 12
Tabla 4: Tabla Control................................................................................................................................................. 13
Tabla 5: Cálculo de sumideros.................................................................................................................................. 13
Tabla 6: Cálculo resumen canales en concreto. ................................................................................................. 15
Tabla 7: Resistencia al corte de la sección del concreto.................................................................................. 21
Tabla 8: Parámetros del suelo de Cimentación. ................................................................................................. 21
Tabla 9: Verificación de Asentamientos. .............................................................................................................. 23
Tabla 7: Resistencia al corte de la sección del concreto canal exterior 1 y 2. .......................................... 27
INFORME DE DISEÑO PLUVIAL ERI-WE-CED-MEM-075-059-2
Revisión 3
CONTRATO No. JA10084331
SERVICIO DE INGENIERÍA, COMPRAS,
CONSTRUCCIÓN, PRUEBAS Y PUESTA EN SERVICIO
PARA LA NUEVA SUBESTACIÓN RÍO, BAJO
MODALIDAD DE CONTRATACIÓN EPC
(ENGINEERING, PURCHASE AND CONSTRUCTION)
Lista de Ilustraciones
1. Nomenclatura
ALCANTARILLADO PLUVIAL
PARÁMETROS DE DISEÑO
ÁREAS TOTALES DE COEFICIENTE DE
ÁREAS PARCIALES DE APORTE
IDENTIFICACIÓN APORTE ESCORRENTÍA CALCULO DE COEFICIENTE
DE ESCORRENTÍA EQUIVALENTE
ID ÁREAS ID ÁREAS ÁREA ÁREA ÁREA ÁREA ÁREA ÁREA Ci*Ai ÁREA ÁREA COEF.
TRAMO PARCIAL ACUM. PATIO PAVIMENTO PATIO PAVIMENTO PATIO PAVIMENTO PARCIAL TOTAL ESCORR
DE A Ha Ha Ha Ha Ha C
CÁRCAMO
C.I.P.#1 A1 A1 0.000 0.033 0.033 0.00 0.83 0.03 0.03 0.03 0.83
#1
C.I.P.#1 C.I.P.#2 A6 A1+A6 0.000 0.018 0.051 0.00 0.83 0.04 0.02 0.05 0.83
C.I.P.#2 C.I.P.#3 A2+A19 A1+A6+A2+A19 0.048 0.033 0.048 0.084 0.70 0.83 0.10 0.08 0.13 0.78
C.I.P.#3 C.I.P.#4 A3+A20 A1+A6+A2+A19+A3+A20 0.048 0.019 0.096 0.103 0.70 0.83 0.15 0.07 0.20 0.77
C.I.P.#4 C.I.P.#5 A4.+A21 A1+A6+A2+A19+A3+A20+A4+A21 0.055 0.023 0.151 0.126 0.70 0.83 0.21 0.08 0.28 0.76
A1+A6+A2+A19+A3+A20+A4+A21+
C.I.P.#5 C.I.P.#6 A23 0.021 0.000 0.173 0.126 0.70 0.83 0.23 0.02 0.30 0.75
A23
A5+A22+A12 A1+A6+A2+A19+A3+A20+A4+A21+
C.I.P.#6 C.I.P.#8 0.101 0.039 0.274 0.166 0.70 0.83 0.33 0.14 0.44 0.75
+A13+A14 A23+A5+A22+A12+A13+A14
A1+A6+A2+A19+A3+A20+A4+A21+
C.I.P.#8 C.I.P.#14 - 0.000 0.000 0.274 0.166 0.70 0.83 0.33 0.00 0.44 0.75
A23+A5+A22+A12+A13+A14
A1+A6+A2+A19+A3+A20+A4+A21+
C.I.P.#14 C.I.P.# 26 - A23+A5+A22+A15+A11+A16+A7+A 0.000 0.000 0.397 0.344 0.70 0.83 0.56 0.00 0.74 0.76
8+A9+A10+A17+A18
A1+A6+A2+A19+A3+A20+A4+A21+
A23+A5+A22+A15+A11+A16+A7+A
C.I.P.# 26 M1 A28+A29 0.074 0.000 0.565 0.344 0.70 0.83 0.68 0.07 0.91 0.75
8+A9+A10+A17+A18+A28+A29+A2
5+A26+A27+A24
A1+A6+A2+A19+A3+A20+A4+A21+
A23+A5+A22+A12+A13+A14+A15+
ÁREA
M1 CABEZOTE A11+A16+A7+A8+A9+A10+A17+A1 0.410 0.540 0.975 0.884 0.60 0.83 1.32 0.95 1.86 0.71
EXTERNA
8+A28+A29+A25+A26+A27+A24+A
REA EXTERNA
CÁRCAMO
C.I.P# 9 A15 A15 0.017 0.000 0.017 0.70 0.01 0.02 0.02 0.70
#2
CÁRCAMO
C.I.P# 10 A11+A16 A15+A11+A16 0.000 0.015 0.017 0.015 0.70 0.83 0.02 0.01 0.03 0.76
#2
C.I.P# 10 C.I.P# 11 A7 A15+A11+A16+A7 0.000 0.000 0.017 0.015 0.70 0.83 0.02 0.00 0.03 0.76
C.I.P# 11 C.I.P# 12 A8 A15+A11+A16+A7+A8 0.029 0.038 0.046 0.053 0.70 0.83 0.08 0.07 0.10 0.77
C.I.P# 12 C.I.P# 13 A9 A15+A11+A16+A7+A8+A9 0.000 0.025 0.046 0.078 0.70 0.83 0.10 0.03 0.12 0.78
A10+A17+A1 A15+A11+A16+A7+A8+A9+A10+A1
C.I.P# 13 C.I.P# 14 0.077 0.100 0.123 0.179 0.70 0.83 0.23 0.18 0.30 0.78
8 7+A18
C.I.P# 22 C.I.P# 23 A25+A26 A25+A26 0.010 0.000 0.010 0.000 0.70 0.01 0.01 0.01 0.70
C.I.P# 23 C.I.P# 25 A27 A25+A26+A27 0.017 0.000 0.027 0.000 0.70 0.02 0.02 0.03 0.70
C.I.P# 25 C.I.P# 26 A25+A26+A27+A24 0.024 0.000 0.094 0.000 0.70 0.07 0.02 0.09 0.70
C.I.P# 24 C.I.P# 25 A24 A24 0.043 0.000 0.043 0.70 0.03 0.04 0.04 0.70
C.I.P# 9 CÁRCAMO #2 5.10 313.4 0.70 0.02 3.81 0.01 0.145 6 0.50 1.00
CÁRCAMO #2 C.I.P# 10 5.11 313.4 0.76 0.03 7.69 0.01 0.145 6 0.50 1.00
C.I.P# 10 C.I.P# 11 5.12 313.4 0.76 0.03 7.69 0.01 0.145 6 25.55 1.00
C.I.P# 11 C.I.P# 12 5.60 313.4 0.77 0.10 24.00 0.01 0.182 8 24.60 1.00
C.I.P# 12 C.I.P# 13 5.93 313.4 0.78 0.12 30.57 0.01 0.227 8 33.37 1.00
C.I.P# 13 C.I.P# 14 6.37 313.4 0.78 0.30 73.50 0.01 0.284 12 66.18 1.50
C.I.P# 22 C.I.P# 23 5.10 313.4 0.70 0.01 2.13 0.01 0.145 6 12.51 1.00
C.I.P# 23 C.I.P# 25 5.44 313.4 0.70 0.03 5.89 0.01 0.145 6 16.44 1.00
C.I.P# 25 C.I.P# 26 5.77 313.4 0.70 0.09 20.52 0.01 0.182 8 12.22 1.00
C.I.P# 24 C.I.P# 25 5.10 313.4 0.70 0.04 9.46 0.01 0.145 6 8.46 1.00
C.I.P.#1 C.I.P.#2 18.97 0.70 0.10 1.15 1.09 1.15 1.09 0.47 0.24 0.18
C.I.P.#2 C.I.P.#3 59.77 0.59 0.13 1.48 1.30 1.48 1.30 0.63 0.21 0.16
C.I.P.#3 C.I.P.#4 59.77 0.76 0.17 1.48 1.46 1.48 1.46 0.69 0.21 0.19
C.I.P.#4 C.I.P.#5 108.62 0.64 0.18 1.71 1.56 1.71 1.56 0.81 0.11 0.10
C.I.P.#5 C.I.P.#6 113.92 0.64 0.18 1.80 1.65 1.80 1.65 0.90 0.17 0.18
C.I.P.#6 C.I.P.#8 158.19 0.66 0.22 1.88 1.75 1.88 1.75 0.95 0.28 0.29
C.I.P.#8 C.I.P.#14 158.19 0.66 0.22 1.88 1.75 1.88 1.75 0.95 0.12 0.13
C.I.P.#14 C.I.P.# 26 254.09 0.69 0.25 2.47 2.34 2.47 2.34 1.60 0.03 0.05
C.I.P.# 26 M1 254.09 0.79 0.28 2.47 2.47 2.47 2.47 1.65 0.09 0.20
M1 CABEZOTE 484.72 0.79 0.32 3.76 3.77 3.76 3.77 3.69 0.01 0.06
C.I.P# 9 CÁRCAMO #2 18.09 0.35 0.05 1.10 0.73 1.10 0.73 0.00 0.01 0.01
CÁRCAMO #2 C.I.P# 10 18.09 0.52 0.07 1.10 0.89 1.10 0.89 0.37 0.01 0.01
C.I.P# 10 C.I.P# 11 18.09 0.52 0.07 1.10 0.89 1.10 0.89 0.37 0.48 0.26
C.I.P# 11 C.I.P# 12 33.16 0.71 0.13 1.27 1.22 1.27 1.22 0.54 0.33 0.25
C.I.P# 12 C.I.P# 13 59.77 0.57 0.13 1.48 1.27 1.48 1.27 0.61 0.44 0.33
C.I.P# 13 C.I.P# 14 133.03 0.60 0.17 2.10 1.86 2.10 1.86 1.18 0.59 0.99
C.I.P# 22 C.I.P# 23 18.09 0.26 0.04 1.10 0.61 1.10 0.61 0.22 0.34 0.13
C.I.P# 23 C.I.P# 25 18.09 0.45 0.06 1.10 0.83 1.10 0.83 0.34 0.33 0.16
C.I.P# 25 C.I.P# 26 33.16 0.64 0.12 1.27 1.17 1.27 1.17 0.52 0.17 0.12
C.I.P# 24 C.I.P# 25 18.09 0.58 0.08 1.10 0.95 1.10 0.95 0.40 0.15 0.08
Tabla 2: Cálculo hidráulico de colectores (Parte 1).
C.I.P# 22 C.I.P# 23 0.15 0.00 0.09 -2.71 -2.75 -2.88 -2.84 -0.86
C.I.P# 23 C.I.P# 25 0.15 0.00 0.15 -2.81 -2.88 -3.04 -2.97 -0.86
C.I.P# 25 C.I.P# 26 0.18 0.00 0.30 -2.92 -3.04 -3.16 -3.04 -0.86
C.I.P# 24 C.I.P# 25 0.15 0.00 0.20 -1.23 -1.31 -1.39 -1.31 -0.76
Tabla 3: Cálculo hidráulico de colectores (Parte 2).
control
Tmax 3.0m
Ymax 0.1m
Tabla 4: Tabla Control
T L
Sumidero C I A Qt n Sx Sy cal. W a S´w Sw Eo Ts Qs Qcaptado Qw Se Y Cal. LT Proyectado
l/s/Ha Ha l/s piso m/m m/m m m m m/m m/m m m l/s l/s l/s m/m m m m
1 0.83 313.4 0.018 4.60 0.016 0.003 0.01 0.70 0.6 0.050 0.083 0.087 1.0000 0.10 0.0 10.41 10.41 0.087 0.039 1.11 2.00
2 0.83 313.4 0.033 8.68 0.016 0.01 0.01 0.70 0.6 0.050 0.083 0.093 0.9998 0.10 0.0 12.06 12.06 0.093 0.050 1.39 2.00
3 0.83 313.4 0.019 4.82 0.016 0.01 0.01 0.70 0.6 0.050 0.083 0.093 0.9998 0.10 0.0 12.06 12.06 0.093 0.040 1.08 2.00
4 0.83 313.4 0.042 11.02 0.016 0.01 0.01 1.00 0.6 0.050 0.083 0.093 0.9934 0.40 0.1 13.88 13.79 0.093 0.055 1.54 2.00
5 0.83 313.4 0.039 10.21 0.016 0.01 0.01 0.70 0.6 0.050 0.083 0.093 0.9998 0.10 0.0 12.06 12.06 0.093 0.053 1.49 2.00
6 0.83 313.4 0.038 9.93 0.016 0.01 0.01 0.70 0.6 0.050 0.083 0.093 0.9998 0.10 0.0 12.06 12.06 0.093 0.053 1.47 2.00
7 0.83 313.4 0.025 6.57 0.016 0.01 0.01 0.70 0.6 0.050 0.083 0.093 0.9998 0.10 0.0 12.06 12.06 0.093 0.045 1.24 2.00
8 0.83 313.4 0.030 7.77 0.016 0.01 0.01 0.70 0.6 0.050 0.083 0.093 0.9998 0.10 0.0 12.06 12.06 0.093 0.048 1.33 2.00
Tabla 5: Cálculo de sumideros.
Para el diseño de las cajas pluviales se toma la altura más critica la cual se evalúa en su diseño a
flexión y cortante determinando el acero que le corresponde a la geometría debido a las cargas
generadas por los esfuerzos del terreno y sobrecargas.
Ilustración 9: Modelo 3D
Se cumple la verificación de cortante dado que lo que resiste es de 51.01 kn Y el cortante ultimo por
diseño es de 20 Kn.
La verificación de capacidad portante cumple ya que la estructura soporta 136.4 kN/m², y el modelo
genera una de 39.2 kN/m²
El acero dado por las caras del elemento estructural determina que supera la cuantía mínima de
diseño de 0.0030 por lo cual se requiere una barras verticales y horizontales de Ø 3/8” cada 15 cm,
como se especifica en los planos estructurales (Ver ERI-WE-CED-RG-075-059-1).
Para el diseño de los sumideros y canales se hicieron las mimas verificaciones dando como resultado
lo plasmado en los planos estructurales (Ver ERI-WE-CED-RG-075-059-1).
ϰs 1750 Kgf/m3.
sobrecar. 200Kgf/m2
h eq. 0.11m
ka 0.28
Ilustración 19: Parámetros de terreno canal exterior 1 y 2.
SOBRECARGA
56 kgf/m2 56 kgf/m2
=
0.5
Ilustración 22: Presión de suelo en las caras del elemento canal exterior 1 y 2.
Ilustración 25: Momentos generados por las cargas en el modelo canal exterior 1 y 2.
Se cumple la verificación de cortante dado que lo que resiste es de 58.90 kn Y el cortante ultimo por
diseño es de 1.40 Kn.
La verificación de capacidad portante cumple ya que la estructura soporta 136.4 kN/m², y el modelo
genera una de 12.6 kN/m²
El acero dado por las caras del elemento estructural determina no supera la cuantía mínima de
diseño de 0.0030 por lo cual se requiere una barras verticales y horizontales de Ø 3/8” cada 15 cm,
como se especifica en los planos estructurales (Ver ERI-WE-CED-RG-075-059-1).