VOLTAJE 220.

00V
K 1
FACTOR DE POTENCIA
=COSø 0.9
CUADRO DE CARGAS MEDIDOR 1 (AMBIENTE 1)
CALCULANDO DEMANDA DE CARGAS PARA TIENDA Y NIVELES CONSECUTIVOS
NIVEL USO AREA CU PI FD DM DM TOTAL I ID CONDUCTOR Ø COMERCIAL TUBERIA PVC TABLERO MEDIDOR
a b c d e f g h i j
axb d/(kx v x cos) ex 1,25 f/8
DEPARTAMENTO 112.29m2 25.00W/m2 2807.25W 1 2807.25W 4937.90W 24.94 31.17 4mm2 4mm2 20mm TD-1 M-1
LAVADORA 500.00W 0 0.00W
1° PISO CARGA MOVIL 650.00W 0.8 520.00W
CIRCUITO COSINA 1500.00W 1 1500.00W
AREA LIBRE 22.13m2 5.00W/m2 110.65W 1 110.65W
DEPARTAMENTO 120.81m2 25.00W/m2 3020.25W 1 3020.25W 6620.25W 33.44 41.79 5mm2 6mm2 20mm TD-2 M-2
LAVADORA 500.00W 1 500.00W
AREA LIBRE 0.00m2 5.00W/m2 0.00W 1 0.00W
2° PISO
THERMA 1200.00W 1 1200.00W
CIRCUITO COSINA 1500.00W 1 1500.00W
CARGA MOVIL 500.00W 0.8 400.00W
DEPARTAMENTO 120.81m2 25.00W/m2 3020.25W 1 3020.25W 6620.25W 33.44 41.79 5mm2 6mm2 20mm TD-3 M-3
LAVADORA 500.00W 1 500.00W
AREA LIBRE 0.00m2 5.00W/m2 0.00W 1 0.00W
3°PISO
THERMA 1200.00W 1 1200.00W
CIRCUITO COSINA 1500.00W 1 1500.00W
CARGA MOVIL 500.00W 0.8 400.00W
DEPARTAMENTO 120.81m2 25.00W/m2 3020.25W 1 3020.25W 6620.25W 33.44 41.79 5mm2 6.0mm2 20mm TD-4 M-4
THERMA 500.00W 1 500.00W
AREA LIBRE 0.00m2 5.00W/m2 0.00W 1 0.00W
4° PISO
CIRCUITO COSINA 1500.00W 1 1500.00W
THERMA 1200.00W 1 1200.00W
CARGA MOVIL 500.00W 0.8 400.00W
DEPARTAMENTO 120.81m2 25.00W/m2 3020.25W 1 3020.25W 6620.25W 33.44 41.79 5mm2 6.0mm2 20mm TD-5 M-5
LAVADORA 500.00W 1 500.00W
AREA LIBRE 0.00m2 5.00W/m2 0.00W 1 0.00W
5° PISO
THERMA 1200.00W 1 1200.00W
CIRCUITO COSINA 1500.00W 1 1500.00W
CARGA MOVIL 500.00W 0.8 400.00W
DEPARTAMENTO 12.16m2 25.00W/m2 304.00W 1 304.00W 804.00W 4.06 5.08 1mm2 4.0mm2 20mm TD-6 M-1
ASOTEA
ASOTEA THERMA 0.00W 1 0.00W
CARGA MOVIL 500.00W 1 500.00W
33,252.90 POTENCIA INSTALADA

PRIMER PISO: 2 - 1x 4mm2 THW ------ ø PVC 20mm 2000.00W 1 2000.00W


SEGUNDO PISO: 2 - 1x 6mm2 THW ------ ø PVC 20mm 7500.00W 1 7500.00W
TERCER PISO: 2 - 1x 6mm2 THW ------ ø PVC 20mm 4800.00W 1 4800.00W
CUARTO PISO: 2 - 1x 6mm2 THW ------ ø PVC 20mm 18952.90W 0.35 6633.52W
QUINTO PISO: 2 - 1x 6mm2 THW ------ ø PVC 20mm
ASOTEA 2 - 1x 4mm2 THW ------ ø PVC 20mm 20933.52W MAXIMA DEMANDA TOTAL 20.93 KW

PARA TODO EL AMBIENTE 1 105.72 INTENSIDAD DE CORRIENTE


DM TOTAL I ID CONDUCTOR Ø COMERCIAL TUB.PVC TABLERO MEDIDOR
32,222.9 162.74 203.43 25mm2 25mm2 25mm TRG-1 M-1 132.16 INTENSIDAD DE CORRIENTE MAXIMA

VOLTAJE 220.00V 61.04


K 1 76.30

FACTOR DE POTENCIA
=COSø 0.9 CUADRO DE CARGAS MEDIDOR 2 ( AMBIENTE 2 )
CALCULANDO DEMANDA DE CARGAS PÁRA DEPARTAMENTOS CONSECUTIVOS

NIVEL USO AREA CU PI FD DM DM TOTAL I ID CONDUCTOR Ø COMERCIAL TUBERIA PVC TABLERO MEDIDOR
DEPARTAMENTO 63.00m2 25.00W/m2 1575.00W 1 1575.00W 2880.00W 14.55 18.18 2mm2 4mm2 20mm TD-1 M-2
THERMA 0.00W 1 0.00W
1° DEPARTAMENTO CARGA MOVIL 1200.00W 0.5 600.00W
ELECTROBOMBA 750.00W 0.8 600.00W
AREA LIBRE 21.00m2 5.00W/m2 105.00W 1 105.00W
DEPARTAMENTO 76.00m2 20.00W/m2 1520.00W 1 1520.00W 3390.00W 17.12 21.40 3mm2 4mm2 20mm TD-2 M-2
THERMA 1200.00W 1 1200.00W
2° DEPARTAMENTO
AREA LIBRE 14.00m2 5.00W/m2 70.00W 1 70.00W
CARGA MOVIL 1200.00W 0.5 600.00W
DEPARTAMENTO 76.00m2 20.00W/m2 1520.00W 1 1520.00W 3390.00W 17.12 21.40 3mm2 4mm2 20mm TD-3 M-2
THERMA 1200.00W 1 1200.00W
3° DEPARTAMENTO
AREA LIBRE 14.00m2 5.00W/m2 70.00W 1 70.00W
CARGA MOVIL 1200.00W 0.5 600.00W
DEPARTAMENTO 13.00m2 20.00W/m2 260.00W 1 260.00W 260.00W 1.31 1.64 0mm2 4mm2 20mm TD-4 M-2
4° AZOTEA THERMA 0.00W 1 0.00W
CARGA MOVIL 0.00W 1 0.00W
PRIMER PISO: 2 - 1x 4mm2 THW ------ ø PVC 20mm
SEGUNDO PISO: 2 - 1x 4mm2 THW ------ ø PVC 20mm
TERCER PISO: 2 - 1x 4mm2 THW ------ ø PVC 20mm

PARA TODO EL AMBIENTE 2


DM TOTAL I ID CONDUCTOR Ø COMERCIAL TUBERIA PVC TABLERO MEDIDOR
9,920.00 45.09 56.36 7mm2 8mm2 25mm TRG-2 M-2