INDICE
I. GENERALIDADES...........................................................................................................2
A.1 PORTICOS..........................................................................................................................4
D. CARGAS ACTUANTES....................................................................................................5
A. ESPECTRO DE PSEUDO-ACELERACIONES..............................................................9
A. COMBINACIONES DE CARGAS..............................................................................11
B. DISEÑO DE ARMADURAS.........................................................................................11
A. DISEÑO DE VIGAS......................................................................................................13
B. DISEÑO DE COLUMNAS...........................................................................................14
VIII............................................................................................DISEÑO DE CIMENTACION15
X. CONCLUSIONES:...........................................................................................................23
XI. RECOMENDACIONES:.................................................................................................23
I. GENERALIDADES
El presente documento (Memoria de cálculo) corresponde al análisis sísmico y cálculo
estructural de la cobertura metálica, del proyecto: “MEJORAMIENTO DEL SERVICIO DE
TRANSITABILIDAD VEHICULAR Y PEATONAL DE LA CIUDAD DE LLAMA,
DISTRITO DE LLAMA - CHOTA - CAJAMARCA”, con Código Unificado N° 2331331 -
META 01, Solicitado por MUNICIPALIDAD DISTRITAL DE LLAMA.
4. SOLDADURA:
- Electrodos: Fexx = 60 KSI (E70 XX - AWS, para acero liso) (en varillas)
- Fexx = 70 KSI (E70 XX - AWS, para acero corrug.)
5. COBERTURA:
- Peso Promedio = 4.30 kg/m2
- Material: (Aluminizinc; catalogo fabricante)
D. CARGAS ACTUANTES
Cargas por peso propio. - Son cargas provenientes del peso de los materiales, dispositivos
de servicio y otros elementos que forman parte de la estructura y/o se consideran
permanentes.
Cargas vivas. - Cargas que provienen de los pesos no permanentes en la estructura que
incluyen a los ocupantes, materiales, equipos, muebles y otros elementos móviles estimados
en la edificación. Teniendo en cuenta que la edificación es de tipo esencial se considera 5O
% de la carga viva para el análisis sísmico.
* Cargas muertas
- Peso propio de los elementos de armadura
* Cargas Vivas
Establecido por la norma sismo resistente:
Sobrecarga en coberturas livianas = 100 Kg/m2
* Cargas de sismo
Según norma E.030 de diseño sismo resistente Sa = (ZUCS/R) *g
* Cargas de viento
- Carga exterior del viento:
NTE E.020 - Art . 12 →: V h = V(H/ 10) 0.22 > V ("V" d e Ma p a Eo lic o - zo n a La mb a y e q ue )
Vie n t o e n Arc o s m e t a lic o s: 85.00 km/ h H= 11.37 m (a lt . p ro m . d e sd e t e rre n o )
V= 85.0 km / h θ = 9.000 ° (p e n d ie n t e p ro m e d io d e la su p e rfic ie - zo n a d e b a ja p e n d ie n te )
θ = 27.000 ° (p e n d ie n te p ro m e d io d e la su p e rfic ie - zo n a d e a lt a p e n d ie n te )
fa c t o r d e fo rm a
C=
+ 0.7 -0.7 a d im e n sio n a l (d e t a b la
Sup e rfic ie s inc lina d a s
izq u ie rd a )
e nt re 15° y 60°
-0.3 -0.6
ABERTURAS
Unifo rm e e n la d o s a
Prin c ip a le s e n
Princ ip a le s e n la d o la d o a
b a rlo v e nt o y
a b a rlo v e nt o so ta v e n to o e n
so t a v e nt o
lo s c o st a d o s
0.3 0.6
0.8
-0.3 -0.6
DIRECCION X:
- Carga externa
BARLOVENTO:
Considerando presion: C = +0.80 Ρh = +30.58 kg/m2
SOTAVENTO:
Se tiene succion: C = -0.50 Ρh = -19.11 kg/m2
- Carga interna
BARLOVENTO:
Considerando presion: C = -0.30 Ρh = -11.47 kg/m2
SOTAVENTO:
Se tiene succion: C = -0.30 Ρh = -11.47 kg/m2
DIRECCION Y:
- Carga externa
SOTAVENTO:
Se tiene succion: C = -0.70 Ρh = -26.76 kg/m2
- Carga interna
SOTAVENTO:
Se tiene succion: C = -0.30 Ρh = -11.47 kg/m2
NOMENCLATUR
FACTOR DESCRIPCION VALOR JUSTIFICACION
A
ZONA Z 3 0.40g Zona Sísmica 3: Racarrumi
USO U CATEGORIA “A” 1.50 Edificación Esencial
S3 1.1 Grava mal graduada con
SUELO S Tp (S) 1.0 limo y arena GP-GM
TL (S) 1.6
-PORTICOS DE - COLUMNAS Y VIGAS
CONCRETO (ELEMENTOS DE APOYO
Rx 8
-PORTICOS DE DE ARMADURAS)
SISTEM ACERO -ARMADURA METALICA
A -PORTICOS DE -COLUMNAS Y VIGAS
CONCRETO (ELEMENTOS DE APOYO
Ry 8
-PORTICOS DE DE ARMADURAS)
ACERO -ARMADURA METALICA
TABLA Nª 1: PARÁMETROS SÍSMICOS.
ZUSC m
Sa= g ; g=9.81 y C=2.5(Tp/T )≤ 2.5
R s2
T < Tp … …C=2.5
Cla sific a c ió n
Fa c to r No me c la tura Va lo r Justific a c ió n
Ca te g ó ric a Tip o
Zo na Z 4 0.45 zo na sism ic a 4
Uso U A 1.5 Ed ific a c io ne s e se nc ia le s
S3 1.1
sue lo fle xib le a rc illa lim o sa
Sue lo S Tp 1
(SM)
TL 1.6
Co e fie nte d e Rx Po rt ic o d e c o n c re t o 8 C o lu m n a s y v ig a s
Re d uc c io n Ry Po rt ic o d e c o n c re t o 8 C o lu m n a s y v ig a s
X Po rt ic o d e c o n c re t o 35 C o lu m n a s y v ig a s
CT
Y Po rt ic o d e c o n c re t o 35 C o lu m n a s y v ig a s
T Cx ZUCS/ Rx
0.0000 2.5000 0.2320
0.0200 2.5000 0.2320
0.0400 2.5000 0.2320
0.0600 2.5000 0.2320
0.0800 2.5000 0.2320
0.1000 2.5000 0.2320
0.2000 2.5000 0.2320
0.3000 2.5000 0.2320
0.4000 2.5000 0.2320
0.5000 2.5000 0.2320
0.6000 2.5000 0.2320
0.7000 2.5000 0.2320
0.8000 2.5000 0.2320
0.9000 2.5000 0.2320
1.0000 2.5000 0.2320
1.1000 2.2727 0.2109
1.2000 2.0833 0.1934
1.3000 1.9231 0.1785
1.4000 1.7857 0.1657
1.5000 1.6667 0.1547
1.6000 1.5625 0.1450
1.7000 1.3841 0.1285
1.8000 1.2346 0.1146
1.9000 1.1080 0.1028
2.0000 1.0000 0.0928
3.0000 0.4444 0.0413
4.0000 0.2500 0.0232
5.0000 0.1600 0.0149
6.0000 0.1111 0.0103
7.0000 0.0816 0.0076
8.0000 0.0625 0.0058
9.0000 0.0494 0.0046
10.0000 0.0400 0.0037
COMB 1: 1.4 CM
COMB 2: 1.2CM + 1.6L
COMB 3: 1.2CM +0.8W
COMB 4: 1.2CM+1.3W+0.5CV
COMB 5: 1.2CM+1SISMO+0.5CV
COMB 6: 0.9+1.3W
ENVOL: ENVOLVENTE DE (COMB1, COMB2,….COMB8, COMB6)
- Para las combinaciones 4 y 5 se considera 0.5CV para cargas vivas menores a 4800Pa
según la norma E090 Estructuras metálicas.
B. DISEÑO DE ARMADURAS
DISEÑO DE Barra mas Pu = 2605.72 Kg = 5.74 Kips requiere:
2
BRIDA INFERIOR: critica: L= 0.490 m = 19.29 pulg Ag = 0.267 pulg
5710 de (5): r> 0.322 pulg
2
Se elige perfil: L 1 1/2" x 1 1/2" x 3/16" Ag = 3.400 pulg > Ag …...… OK
rx= 1.160 pulg > r …...… OK
ry= 1.160 pulg > r …...… OK
VERIFICACION POR ESBELTES:
de (7): λc = 0.187 < 1.5 … OK Puadm = Ø(Fcr)(Ag) = 102.54 Kips > Pu OK
de (6): Fcr = 35.480 Ksi
2
Se elige perfil: L 1 1/2" x 1 1/2" x 3/16" Ag = 3.400 pulg > Ag …...… OK
rx= 1.160 pulg > r …...… OK
ry= 1.160 pulg > r …...… OK
VERIFICACION POR ESBELTES:
de (7): λc = 0.187 < 1.5 … OK Puadm = Ø(Fcr)(Ag) = 102.54 Kips > Pu OK
de (6): Fcr = 35.480 Ksi
2
Se elige varilla: Ø 5/8" (corrugado) Ag = 0.307 pulg > Ag …...… OK
rx= 0.156 pulg > r …...… MAL (se obvia)
ry= 0.156 pulg > r …...… MAL (se obvia)
VERIFICACION POR ESBELTES:
de (7): λc = 1.874 < 1.5 … MAL Puadm = Ø(Fcr)(Ag) = 3.66 Kips > Pu OK
de (6): Fcr = 14.038 Ksi
Ø 5/8" (corrugado)
2
Se elige varilla: Ø 1/2" (corrugado) Ag = 0.196 pulg > Ag …...… OK
rx= 0.125 pulg > r …...… MAL (se obvia)
ry= 0.125 pulg > r …...… MAL (se obvia)
VERIFICACION POR ESBELTES:
de (7): λc = 1.590 < 1.5 … MAL Puadm = Ø(Fcr)(Ag) = 2.34 Kips > Pu OK
de (6): Fcr = 14.038 Ksi
Ø 1/2" (corrugado)
A. DISEÑO DE VIGAS
Para el diseño de vigas se tomarán los resultados de diseño proporcionados por el programa
SAP V 20.2.0 y su comprobación se hará usando hojas de cálculo en Excel.
Se han creado las combinaciones de carga de acuerdo a lo estipulado por la NTE E.060 Art.
9.2 del Reglamento Nacional de Edificaciones, donde se evalúan los efectos máximos en la
viga, con una combinación de envolvente.
DISEÑO DE VIGA
DISEÑO POR FLEXION
MOMENTO POSITIVO MOMENTO NEGATIVO
f`c : 210.00 kg/cm2 f`c : 210.00 kg/cm2
fy : 4200.00 kg/cm3 fy : 4200.00 kg/cm3
b: 25.00 cm b: 25.00 cm
h: 30.00 cm h: 30.00 cm
r: 4.00 cm r: 4.00 cm
Ø b: 1/2 " Ø b: 1/2 "
d ef: 24.42 cm (una sola capa) d ef: 24.42 cm (una sola capa)
AS min b d
B. DISEÑO DE COLUMNAS
PLANTA
ELEVACION
ESTADO DE CARGAS
CARGA MUERTA (DEAD)
CARGA VIVA
VERIFICACION DE ASENTAMIENTOS
De donde se observa que las deformaciones máximas del suelo son de 0.29 cm y este valor no
supera el asentamiento máximo permisible (EMS), por lo tanto, la cimentación tiene las
dimensiones adecuadas en planta.
VERIFICACION DE PRESIONES
Diagrama de Presiones en el Terreno, bajo estado de Cargas “en Servicio ”(en kg/cm2) →
σMAX= 0.59kg/cm2 la cual no supera a 0.83kg/cm2 que indica el EMS, por lo tanto el diseño
propuesto es correcto.
DISEÑO DE REFUERZO
B = 120 cm
H = 50 cm
rec = 7 cm
Ø = 1.27 cm
d = 42.37 cm
Asmin = 0.0018*B*h
Asmin = 10.80 cm2
#Aceros = 9
s = 14.00 cm
1Ø1/2"@0.14m
X. CONCLUSIONES:
La presente estructura cumple con todos los requisitos de rigidez, ductilidad y resistencia,
establecidos en el Reglamento Nacional de Edificaciones del Perú, así como la Norma ACI
318-14.
XI. RECOMENDACIONES:
No debe cimentarse sobre turba, suelo orgánico, tierra vegetal, relleno de desmonte o
rellenos sanitario o industrial, ni rellenos no controlados. Estos materiales inadecuados
deberán ser removidos en su totalidad, antes de construir la edificación y ser reemplazados
con materiales que cumplan con las indicaciones de la norma de Suelos y Cimentaciones
NTE E.050