Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Título:
ESTUDIO DEFINITIVO
Revisión A
DOC-02 Memoria Descriptiva
Página 1 de 55
ESTUDIO DEFINITIVO
AMPLIACIÓN DE POTENCIA DE LA SUBESTACIÓN DE Página
TRANSMISIÓN DE MOYOBAMBA, DISTRITO Y PROVINCIA DE
2 de 59
MOYOBAMBA, REGIÓN DE SAN MARTÍN.
Memoria Descriptiva Rev. A
MEMORIA DESCRIPTIVA
ÍNDICE GENERAL
1. INTRODUCCIÓN............................................................................................................5
1.1 OBJETIVO.............................................................................................................5
1.2 ANTECEDENTES..................................................................................................5
1.3 ALCANCE.............................................................................................................. 6
2. ASPECTOS GENERALES.............................................................................................7
2.1 UBICACIÓN GEOGRAFICA..................................................................................7
2.2 DISPONIBILIDAD DE TERRENO..........................................................................8
2.3 VÍAS DE ACCESO.................................................................................................8
2.4 CONDICIONES CLIMATOLÓGICAS.....................................................................9
2.5 COMUNICACIÓN Y ALOJAMIENTO.....................................................................9
2.6 CARATERISTICAS DEL SISTEMA ELÉCTRICO..................................................9
2.6.1 NIVELES DE AISLAMIENTO.................................................................................10
2.6.2 DISTANCIAS MÍNIMAS DE SEGURIDAD.............................................................10
2.7 EVALUACIÓN DE LA OFERTA Y LA DEMANDA................................................11
2.7.1 Horizonte de Evaluación........................................................................................ 11
2.7.2 Metodología para el estudio de la demanda..........................................................11
2.7.3 Datos históricos...................................................................................................... 12
2.7.4 Proyección de la Demanda....................................................................................13
2.7.5 Determinación de la brecha oferta y demanda.......................................................16
2.7.6 Características del Transformador del Proyecto....................................................22
3. CARACTERISTICAS DE LAS INSTALACIONES EXISTENTES................................23
3.1 LINEAS DE TRANSMISION................................................................................23
3.2 SUBESTACION MOYOBAMBA...........................................................................23
4. INSTALACIONES PROYECTADAS............................................................................28
4.1 DESCRIPCIÓN DE LA SOLUCION.....................................................................28
4.2 EVALUACIÓN DE LAS FACILIDADES PARA LA AMPLIACIÓN DE LA
SUBESTACIÓN...................................................................................................29
4.3 AMPLIACIÓN EN 138 kV.....................................................................................29
4.4 AMPLIACIÓN EN 60 kV.......................................................................................31
4.5 AMPLIACIÓN EN 22.9 kV....................................................................................32
ENERZA– Ingeniería y Construcción.
AMPLIACIÓN DE POTENCIA DE LA SUBESTACIÓN DE Página
TRANSMISIÓN DE MOYOBAMBA, DISTRITO Y PROVINCIA DE
3 de 59
MOYOBAMBA, REGIÓN DE SAN MARTÍN.
Memoria Descriptiva Rev. A
MEMORIA DESCRIPTIVA
1. INTRODUCCIÓN
1.1 OBJETIVO
1.2 ANTECEDENTES
Esta problemática fue también evaluada por OSINERGMIN quienes, con fecha 19
de Julio del 2012, emite la Resolución de Consejo Directivo N° 151-2012-OS/CD
1.3 ALCANCE
Implementación de una barra flexible en 138 kV, una bahía de línea 138 kV y
dos bahías para conexión de los transformadores nuevo y existente en 138 kV.
aunque para el transformador existente se reutilizaran los mismos equipos.
2. ASPECTOS GENERALES
La Subestación Moyobamba existe espacio disponible para poder realizar los trabajos de
ampliación del proyecto, los cuales, se muestran en la siguiente figura:
3 2
4 1
Coordenadas UTM
Vértices (WGS 84)
Este Norte
1 281604.62 9331189.59
2 281613.14 9331232.16
3 281520.15 9331239.66
4 281520.42 9331195.90
Por vía terrestre tiene como acceso principal la Carretera Marginal de la Selva
Arquitecto Fernando Belaunde Terry, mediante el Sistema Norte: que une Lima –
Olmos – Chamaya - El Reposo - Puente Ingenio - Rioja con una longitud
aproximada de 1,488 Km; Sistema Centro: Lima- La Oroya- Cerro de Pasco –
Huánuco - Tingo María – Tocache - Juanjui - Tarapoto – Moyobamba.
Aunque todo el año hay lluvias, son los meses de noviembre hasta abril en los que
se presenta con mayor incidencia (en promedio 137mm) y los meses de julio y
agosto en los que disminuye el nivel (61mm).
El sistema eléctrico de la región San Martin está a cargo de Electro Oriente. Las
características se muestran en la tabla N° 2.1.
Cuadro N° 2.1 Característica del Sistema Eléctrico.
Descripción 138 kV 60 kV 22.9 kV 10 kV
Tensión nominal del sistema, kV 138 60 22.9 10
Frecuencia nominal, Hz 60 60 60 60
Nivel básico de aislamiento al impulso tipo
650 325 125 95
rayo (BIL), kV pico
Distancia de fuga mínima, mm/kV 31 31 31 31
Estrella, N a Estrella, N a Estrella , N a Estrella, N
Conexión
tierra tierra tierra a tierra
Identificación de fases R, S, T R, S, T R, S, T R, S, T
Las distancias mínimas de seguridad son las distancias mínimas que deben ser
mantenidas en el aire entre partes energizadas de equipos y tierra, o entre equipos
sobre los cuales es necesario llevar a cabo un trabajo.
Moyobamba
Distancias Mínimas de Seguridad
138 kV 60 kV 22,9 kV
Distancia de los Vehículos a las partes con tensión mm 2000 1330 920
Distancia mínima entre fases (De Tabla A.1 IEC 60071-1) mm 1300 630 220
Distancia mínima entre fase y tierra (De Tabla A.1 IEC 60071-1) mm 1300 630 220
Distancia mínima entre fases (para diseño de SE) mm 2500 1500 500
Distancia mínima entre fase y tierra (para diseño de SE) mm 1800 1200 500
Zona de seguridad del personal mm 2250 2250 2250
Distancia a la parte bajo tensión a las cercana mm 3680 2943 2510
Distancia de trabajo vertical mm 2800 2130 1720
Distancia de trabajo horizontal mm 3300 2630 2220
ENERGÍA POTENCIA
AÑO
GWH % MW %
2003 12.34 2.35
2004 12.96 5.0% 2.47 5.0% Crecimiento de la Demanda y Energia de Moyobamba
2005 13.59 4.9% 2.59 4.9%
2006 15.55 14.4% 2.96 14.4% 30.00 6.00
2007 19.81 27.4% 3.77 27.4%
2008 16.35 -17.5% 3.11 -17.5% 25.00 5.00
2009 17.53 7.2% 3.33 7.2%
2010 18.88 7.8% 3.59 7.8% 20.00 4.00
2011 21.64 14.6% 4.12 14.6%
GWh
MW
2012 12.25 -43.4% 2.33 -43.4% 15.00 3.00
2013 16.97 38.5% 3.23 38.5%
2014 25.31 49.1% 4.81 49.1% 10.00 2.00
2015 26.53 4.8% 5.05 4.8%
2016 25.67 -3.2% 4.88 -3.2% 5.00 1.00
ENERGÍA POTENCIA
AÑO Crecimiento de la Demanda y Energia de Rioja
GWH % MW %
2003 20.14 3.83 45.00 9.00
2004 22.24 10.4% 4.23 10.4%
40.00 8.00
2005 23.53 5.8% 4.48 5.8%
2006 27.43 16.6% 5.22 16.6% 35.00 7.00
2007 30.79 12.2% 5.86 12.2% 30.00 6.00
2008 33.62 9.2% 6.40 9.2%
25.00 5.00
GWh
MW
2009 27.23 -19.0% 5.18 -19.0%
2010 27.22 0.0% 5.18 0.0% 20.00 4.00
2011 29.06 6.8% 5.53 6.8% 15.00 3.00
2012 40.97 41.0% 7.79 41.0%
10.00 2.00
2013 39.68 -3.1% 7.55 -3.1%
2014 39.79 0.3% 7.57 0.3% 5.00 1.00
2015 39.35 -1.1% 7.49 -1.1% 0.00 0.00
2016 37.75 -4.1% 7.18 -4.1% 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016
MW
15.00 2.50
2012 18.83 44.9% 3.58 44.9%
2013 18.71 -0.6% 3.56 -0.6% 2.00
10.00
2014 20.33 8.6% 3.87 8.6% 1.50
2015 22.52 10.8% 4.28 10.8% 1.00
5.00
2016 23.36 3.7% 4.44 3.7% 0.50
0.00 0.00
PROMEDIO (2009-2016) 15.9% 15.9%
2003 2004 2005 2006 2007 2008 2009 2010
TC Considerada 4.7% 4.7%
Energia Potencia
Fuente: Electro Oriente S.A.
AREA DE DEMANDA: 4
TOTAL MAT 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
AREA TOTAL AT 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
TOTAL MT 61 64 67 70 73 77 80 84 88 92 97 101 106 111 117 122 128 134 140 147 154 161
TOTAL 69 72 75 78 81 85 88 92 96 100 105 109 114 119 125 130 136 142 148 155 162 169
Del cuadro anterior, la demanda considerada para la SE Moyobamba son las cargas de:
- Moyobamba (MOYO10).
- Nueva Cajamarca (NCAJ22.9).
- Rioja (RIOJA20).
Y el usuario libre:
- Cementos Selva (CESEL60).
Por lo que, se tiene el siguiente resumen de la demanda para la SE Moyobamba:
Cuadro N° 2.5 Proyección de la demanda SE Moyobamba.
SUBESTACIÓN BARRA TENSIÓN
(kV) 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029 2030 2031 2032 2033 2034 2035 2036 2037 2038 2039 2040
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
MOYOBAMBA MOYO10 10 5.6 5.9 6.2 6.5 6.8 7.1 7.4 7.8 8.1 8.5 8.9 9.4 9.8 10.3 10.7 11.3 11.8 12.4 12.9 13.6 14.2 14.9
NUEVA CAJAMARCA NCAJ22.9 20 5.1 5.4 5.6 5.9 6.1 6.4 6.7 7.1 7.4 7.8 8.1 8.5 8.9 9.3 9.8 10.2 10.7 11.2 11.8 12.3 12.9 13.5
RIOJA RIOJA20 20 4.0 4.2 4.4 4.6 4.8 5.1 5.3 5.5 5.8 6.1 6.4 6.7 7.0 7.3 7.7 8.0 8.4 8.8 9.2 9.7 10.1 10.6
CEMENTOS SELVA CESEL60 60 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
TOTAL 22.7 23.4 24.2 24.9 25.7 26.6 27.5 28.4 29.4 30.4 31.4 32.5 33.7 34.9 36.2 37.5 38.9 40.4 42.0 43.6 45.3 47.0
DESCRIPCION /AÑO 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029 2030 2031 2032 2033 2034 2035 2036 2037 2038 2039 2040
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Habitantes electrificados (Pob. Beneficiada) 278,885 289,155 299,805 310,855 322,310 334,195 346,515 359,290 372,545 386,285 400,540 415,330 430,665 446,570 463,065 480,175 497,925 516,335 535,435 544,775 565,150 586,280
Habitantes electrificados (Vegetativa + SER) 278885 289155 299805 310855 322310 334195 346515 359290 372545 386285 400540 415330 430665 446570 463065 480175 497925 516335 535435 544775 565150 586280
Nº de Usuarios Totales 56,103 58,167 60,308 62,529 64,831 67,219 69,694 72,261 74,924 77,684 80,547 83,518 86,598 89,792 93,105 96,541 100,105 103,802 107,637 109,375 113,464 117,704
Número de Usuarios Totales (Vegetativa+SER) 56103 58167 60308 62529 64831 67219 69694 72261 74924 77684 80547 83518 86598 89792 93105 96541 100105 103802 107637 109375 113464 117704
Energía Requerida - Total sin Proyecto (GWh) 122.14 125.92 129.89 134.04 138.39 142.95 147.72 152.72 157.95 163.43 169.17 175.19 181.48 188.08 194.98 202.21 209.79 217.72 226.03 234.73 243.84 253.38
Energía Requerida - (GWh) 122.14 125.92 129.89 134.04 138.39 142.95 147.72 152.72 157.95 163.43 169.17 175.19 181.48 188.08 194.98 202.21 209.79 217.72 226.03 234.73 243.84 253.38
Máxima Demanda MO-S01 -10kV (MW) - Vegetativo ( Ciudad) 2.52 2.64 2.76 2.89 3.03 3.17 3.32 3.48 3.64 3.81 3.99 4.18 4.38 4.58 4.80 5.02 5.26 5.50 5.76 6.03 6.32 6.61
Máxima Demanda MO-S02 -10kV (MW) - Vegetativo (Rural) 1.43 1.49 1.56 1.64 1.71 1.79 1.88 1.97 2.06 2.16 2.26 2.36 2.47 2.59 2.71 2.84 2.97 3.11 3.26 3.41 3.57 3.74
Máxima Demanda MO-S03 -10kV (MW) - Vegetativo (Ciudad) 2.17 2.28 2.38 2.49 2.61 2.73 2.86 3.00 3.14 3.29 3.44 3.60 3.77 3.95 4.13 4.33 4.53 4.74 4.97 5.20 5.45 5.70
Máxima Demanda Barra 10kV (MW) - Vegetativo 6.12 6.41 6.71 7.02 7.35 7.70 8.06 8.44 8.84 9.25 9.69 10.14 10.62 11.12 11.64 12.19 12.76 13.36 13.99 14.65 15.34 16.06
Máxima Demanda Barra 60kV (MW) - Vegetativo 17.12 17.55 18.00 18.48 18.98 19.50 20.04 20.61 21.21 21.84 22.50 23.19 23.91 24.66 25.45 26.28 27.15 28.06 29.01 30.01 31.06 32.15
Máxima Demanda Barra 138kV (MW) - Vegetativo 23.24 23.96 24.71 25.50 26.33 27.20 28.11 29.06 30.05 31.09 32.19 33.33 34.53 35.78 37.10 38.47 39.91 41.42 43.00 44.66 46.39 48.21
Máxima Demanda Cargas Especiales Barra 22.9kV (MW) 3.55 3.58 3.60 3.63 3.66 3.70 3.73 3.77 3.80 3.84 3.88 3.92 3.97 4.02 4.06 4.11 4.17 4.22 4.28 4.34 4.41 4.47
Máxima Demanda Cargas Especiales Barra 60kV (MW) 3.00 6.00 6.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00
Máxima Demanda Cargas Especiales (MW) 6.55 9.58 9.60 12.63 12.66 12.70 12.73 12.77 12.80 12.84 12.88 12.92 12.97 13.02 13.06 13.11 13.17 13.22 13.28 13.34 13.41 13.47
Máxima Demanda Total sin Proyecto (MW) 23.24 23.96 24.71 25.50 26.33 27.20 28.11 29.06 30.05 31.09 32.19 33.33 34.53 35.78 37.10 38.47 39.91 41.42 43.00 44.66 46.39 48.21
Máxima Demanda - (MW) 23.24 23.96 24.71 25.50 26.33 27.20 28.11 29.06 30.05 31.09 32.19 33.33 34.53 35.78 37.10 38.47 39.91 41.42 43.00 44.66 46.39 48.21
Máxima Demanda Barra 22.9kV (MW) - con proyecto 4.98 5.07 5.17 5.27 5.38 5.49 5.61 5.73 5.86 6.00 6.14 6.29 6.44 6.61 6.78 6.95 7.14 7.34 7.54 7.76 7.98 8.21
Máxima Demanda Barra 60kV (MW) - con proyecto 20.12 23.55 24.00 27.48 27.98 28.50 29.04 29.61 30.21 30.84 31.50 32.19 32.91 33.66 34.45 35.28 36.15 37.06 38.01 39.01 40.06 41.15
Máxima Demanda Barra 138kV (MW) - con proyecto 25.09 28.62 29.17 32.75 33.35 33.99 34.65 35.35 36.08 36.84 37.64 38.47 39.35 40.27 41.23 42.24 43.29 44.40 45.55 46.77 48.04 49.37
Energía Requerida - Total con Proyecto (GWh) 131.89 150.42 153.32 172.13 175.31 178.64 182.13 185.78 189.61 193.62 197.82 202.22 206.83 211.65 216.71 222.00 227.54 233.35 239.43 245.81 252.48 259.47
Energía Requerida - (GWh) 131.89 150.42 153.32 172.13 175.31 178.64 182.13 185.78 189.61 193.62 197.82 202.22 206.83 211.65 216.71 222.00 227.54 233.35 239.43 245.81 252.48 259.47
Máxima Demanda Total con Proyecto (MW) 25.09 28.62 29.17 32.75 33.35 33.99 34.65 35.35 36.08 36.84 37.64 38.47 39.35 40.27 41.23 42.24 43.29 44.40 45.55 46.77 48.04 49.37
Máxima Demanda - (MW) 25.09 28.62 29.17 32.75 33.35 33.99 34.65 35.35 36.08 36.84 37.64 38.47 39.35 40.27 41.23 42.24 43.29 44.40 45.55 46.77 48.04 49.37
Máxima Demanda Total Sin Proyecto (MW) ( Vegetativa) 23.24 23.96 24.71 25.50 26.33 27.20 28.11 29.06 30.05 31.09 32.19 33.33 34.53 35.78 37.10 38.47 39.91 41.42 43.00 44.66 46.39 48.21
Máxima Demanda Total Con Proyecto (MW) 25.09 28.62 29.17 32.75 33.35 33.99 34.65 35.35 36.08 36.84 37.64 38.47 39.35 40.27 41.23 42.24 43.29 44.40 45.55 46.77 48.04 49.37
FORMATO 3 -A
OFERTA DE GENERACION + SEIN SIN PROYECTO
CENTRAL GRUPO PERIODO
2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029 2030 2031 2032 2033 2034 2035 2036 2037 2038 2039 2040
Gera I -T1 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00
C.H. GERA I
Gera I -T2 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00 3.00
C.H. GERA II Gera II 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80
Potencia Efectiva de envio Barra 138kV SET Tingo Maria ( SEIN)40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00 40.00
LT Cajamarca- Caclic- Moyobamba 220 kV 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00
Potencia Efectiva Grupos Hidroeléctricos 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80 7.80
POTENCIA EFECTIVA (MW) 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80 245.80
POTENCIA GARANTIZADA (MW) 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00 198.00
MVA 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00
Oferta Devanado 10kV
MW 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10 8.10
MVA 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00
Oferta Devanado 60 kV
MW 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00
MVA 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00
Oferta Devanado 132 kV
MW 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00
MVA 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00 29.00
Oferta en MT 60kV y 10kV
MW 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10 26.10
MVA 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00
Oferta en AT 132kv
MW 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00
Oferta SET Moyobamba MW 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00
Oferta Optimizada con C.H. GERA MW 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00 24.00
Oferta sin proyecto:
Representa la capacidad actual del transformador de Potencia de la SET Moyobamba,
la cual se mantendrá constante durante todo el periodo de evaluación, siendo la
situación optimizada la operación de la C.H. Gera, para cubrir la demanda.
Oferta con proyecto:
La oferta disponible en la situación “Con Proyecto” está definida con la implementación
de un nuevo Transformador de Potencia.
Sin embargo, el transformador existente será necesario que entre en mantenimiento
por el tiempo de operación; por lo que se estima que, en el segundo semestre del
2021, se retire el transformador existente para mantenimiento y que estaría listo para
su operación en el primer semestre del 2022; pero dependerá de las condiciones de la
demanda, puesto que dicho transformador existente será utilizado cuando la oferta del
lado de 60 kV del transformador del proyecto sea superado por la demanda.
Por lo indicado, la oferta en la situación sin proyecto considera solo la operación del
transformador existente para el año 2020, y como el transformador existente no cuenta
con la tensión de 22.9 kV, es necesario que parte de la demanda de 10 kV sea
trasladado al devanado de 22.9 kV, quedando solo la ciudad de Moyobamba en 10 kV.
(MW) (MW)
A B MW
2019 25.09 18.00 -7.09
2020 28.62 18.00 -10.62
2021 29.17 18.00 -11.17
2022 32.75 18.00 -14.75
2023 33.35 18.00 -15.35
2024 33.99 18.00 -15.99
2025 34.65 18.00 -16.65
2026 35.35 18.00 -17.35
2027 36.08 18.00 -18.08
2028 36.84 18.00 -18.84
2029 37.64 18.00 -19.64
2030 38.47 18.00 -20.47
2031 39.35 18.00 -21.35
2032 40.27 18.00 -22.27
2033 41.23 18.00 -23.23
2034 42.24 18.00 -24.24
2035 43.29 18.00 -25.29
2036 44.40 18.00 -26.40
2037 45.55 18.00 -27.55
2038 46.77 18.00 -28.77
2039 48.04 18.00 -30.04
2040 49.37 18.00 -31.37
(M W) (M W)
A B MW
2019 25.09 25.80 0.71
2020 28.62 25.80 -2.82
2021 29.17 25.80 -3.37
2022 32.75 25.80 -6.95
2023 33.35 25.80 -7.55
2024 33.99 25.80 -8.19
2025 34.65 25.80 -8.85
2026 35.35 25.80 -9.55
2027 36.08 25.80 -10.28
2028 36.84 25.80 -11.04
2029 37.64 25.80 -11.84
2030 38.47 25.80 -12.67
2031 39.35 25.80 -13.55
2032 40.27 25.80 -14.47
2033 41.23 25.80 -15.43
2034 42.24 25.80 -16.44
2035 43.29 25.80 -17.49
2036 44.40 25.80 -18.60
2037 45.55 25.80 -19.75
2038 46.77 25.80 -20.97
2039 48.04 25.80 -22.24
2040 49.37 25.80 -23.57
De la figura N° 2.8 podemos ver la máxima demanda sin y con proyecto, llegando a
25.09 MW para el año 0 (año 2020), y 49.37 MW para el año 20, (año 2040) con
proyecto.
Ante estos resultados se concluye que el transformador debe ser de las siguientes
características de potencia:
Año de
Cadena
Tensió puesta
Códig Destin Longitud Conducto Estructura de
Origen n Nom. en Estado
o o [km] r [mm2] s aisladore
[kV] servici
s
o
Belaund
L-1049 Moyob 138 2.5 240 AAAC Celosía Polimérico 1999 Operativa
e
L-6090 Gera Moyob 60 17.5 75 ACSR Celosía Vidrio 1992 Operativa
L-6091 Moyob Rioja 60 21 75 ACSR Celosía Vidrio 1992 Operativa
MARCA : ABB
ENFRIAMIENTO : ONAN/ONAF
Nº DE FASES : 3
CALENTAMIENTO 60/65 °C
AISLAMIENTO CLASE A
ESTADO : OPERATIVO
Fuente: Electro Oriente S.A.
El patio cuenta con dos pórticos tipo celosía de 9.5m de altura para anclaje de las
líneas en 60kV. Estos dos pórticos están montados en el mismo eje.
Asimismo, cuenta con dos pórticos tipo celosía de 7.5m de altura opuestos uno del
otro para montaje de las barras de 60kV. Uno de esos pórticos también sostiene al
seccionador de barra de la bahía de conexión al Transformador de Potencia lado
60kV.
01 Celda 10kV de salida para conexión del alimentador MO-S01 para los
distritos rurales de Moyobamba.
01 Celda 10kV de salida para conexión del alimentador MO-S02 para el distrito
de Yántalo.
01 Celda 10kV de salida para conexión del alimentador MO-S03 para la zona
urbana de Moyobamba.
La subestación Moyobamba cuenta con sala de control que alberga los siguientes
tableros:
4. INSTALACIONES PROYECTADAS
Implementación de una nueva barra de 22.9 kV, con cinco celdas: Una
para conexión al Transformador de Potencia proyectado, tres celdas de salida en
22.9 kV y una celda para medición.
Para la conexión del nuevo transformador de potencia por el lado de alta tensión en
138 kV se deberá implementar el sistema de barras en ese nivel de tensión en la
subestación.
Se han previsto dos bahías en 138 kV: Una para llegada de la línea existente L-1049 y
la otra para conexión a los Transformadores de Potencia del proyecto.
4.4 AMPLIACIÓN EN 60 kV
En el nivel de tensión en 60kV existen barras, por lo que sólo se debe implementar
una bahía que permita conectar a ellas el lado de 60kV del Transformador de potencia
proyectado. En el plano SE-MOY-OE-20-04 se observa la disposición en planta
propuesta para realizar esta conexión.
En ese sentido, se construirá una sala de control con un ambiente para celdas de 10
kV y 22.9 kV.
Este conjunto contará con cinco celdas: Una para conexión del nuevo transformador
de potencia, tres para salidas de línea hacia las zonas de carga y una celda de
medición. El equipamiento de estas bahías será del tipo interior.
Las celdas de salida de línea proyectadas en 22.9 kV estarán cada una compuesta por
el siguiente equipamiento:
Las salidas de líneas serán con cables de energía tipo N2XSY de 18/30 kV y serán
conectadas vía ducto de cables, hasta los postes iniciales de cada línea alimentadora
en 22.9kV (futuras).
4.6 AMPLIACIÓN EN 10 kV
Este nuevo sistema de 10kV estará compuesto con diez celdas tipo interior cuyo uso
será el siguiente:
Las celdas descritas estarán ubicadas en la nueva sala de control, contarán con un
sistema de canaletas para recorrido apropiado de los cables de energía y para los
cables de control. Se ha previsto el espacio para futuras ampliaciones.
En la sala de baterías el piso estará provisto con mayólicas al igual que las paredes
hasta una altura de 1.6m. Asimismo se preverá la instalación de un lavatorio que
será empleado en caso de emergencia ante un contacto con los líquidos internos de
las baterías.
El respaldo de los servicios auxiliares en corriente continua viene dado por el sistema
de banco de baterías y rectificadores. El tablero cargador-rectificador asegurará la
continuidad del servicio en corriente continua por al menos 8 horas.
Con finalidad de mantener en operación los servicios auxiliares existentes, los cuales
brindan las tensiones para los tableros existentes (Tablero de Transformador de
potencia existente, tomacorrientes, iluminación interior y exterior de la sala existente,
control y mando de los equipos en 60 kV), se deberá mantener en operación los
tableros de servicios auxiliares existentes, mediante la conexión del nuevo
transformador de servicios auxiliares instalado en la nueva sala hasta los tableros de
SS.AA. existentes; y la Contratista verificará su adecuada operación.
En 10 kV, los cables de energía serán empleados para alimentación del nuevo sistema
de barras en 10 kV desde el nuevo transformador de potencia hasta la celda de
llegada y para las salidas de alimentación al transformador de servicios auxiliares.
Estos cables serán de cobre electrolítico, unipolares, del tipo N2XSY (con aislamiento
de polietileno reticulado-XLPE), 8.7/15 kV para una temperatura de operación de 90º
C.
En 22.9 kV, los cables de energía serán empleados para salida desde las bahías
proyectadas hacia los postes terminales de los alimentadores previstos en este nivel
Los cables de energías para 22.9 kV serán de cobre electrolítico, unipolares, del tipo
N2XSY (con aislamiento de polietileno reticulado-XLPE), 18/30 kV para una
temperatura de operación de 90º C.
Todos los cables serán habilitados con terminales unipolares del tipo auto contraíbles
seleccionados según niveles de tensión y secciones, para uso exterior e interior según
el lugar de instalación.
El recorrido de los cables será por las canaletas existentes y proyectadas y hasta la
base de los pórticos con tuberías de 1”.
Aislar las fallas tan pronto como sea posible con la finalidad de minimizar las
pérdidas económicas que se pudiesen producir como consecuencia de las fallas.
Alertar sobre el estado inapropiado de los equipos con la finalidad de tomar las
acciones preventivas que permitan evitar pérdidas económicas por posibles
fallas en dichos equipos. De acuerdo a la gravedad de la situación aislar al
equipo del sistema.
La subestación contara con 4 niveles de tensión: 138 kV, 60 kV, 22,9 kV y 10 kV.
Esta filosofía facilita que el sistema de control y mando sea automatizado con la
siguiente jerarquía:
Deben tener incorporado las funciones de control de parámetros en tiempo real (V,
I, Hz, kW, kVA, etc.) de la respectiva bahía y de las barras, posición de equipos de
maniobra en tiempo real (Interruptores, seccionadores, etc.) y el comando local de
todos los equipos de su respectiva bahía. El sistema de alarmas para las líneas de
transmisión será desde estos mismos equipos.
Protección principal:
Protección de falla de interruptor, función 50/51, 50N/ 51N, 49, 32, 81, 50 BF,
67N, 79.
Protección de falla de interruptor, función 50/51, 50N/ 51N, 49, 32, 81, 50 BF,
67N, 79, 51V, 86, 60.
Para el control, mando local y protección del nivel de tensión 22.9 kV se define
equipos digitales de última generación para cada celda.
Protección de falla de interruptor, función 50/51, 50N/ 51N, 49, 32, 81, 50 BF,
67N, 79, 51V, 86, 60.
Deberán estar preparados para tener comunicación con la red local del sistema de
control y supervisión principal de subestaciones; de no ser así, se proveerá un
sistema que permita enlazar los medidores y tener acceso a cada uno de ellos a
través de una sola línea dedicada.
El equipo contará con un display local para la lectura directa de los parámetros
eléctricos y servirá de enlace con la unidad de control y supervisión principal, a
través de la red local. Se contará como mínimo con la medición de los siguientes
parámetros eléctricos: Tensión fase – fase y fase – tierra, Corriente por fase,
Potencia activa, Potencia reactiva, Potencia aparente, Factor de potencia
Registrado de fallas.
Estos estudios proporcionan los parámetros del suelo que se emplean en el diseño
de las cimentaciones de soportes de equipos y pórticos.
Para realizar los trabajos del presente proyecto es necesario ampliar la subestación
efectuando movimientos de tierra en la zona que cae fuera de la subestación. Esta
zona se encuentra en un nivel más bajo que los niveles del patio de llaves del área
existente por lo que se deberá efectuar cortes y rellenos a fin de ubicar
adecuadamente los equipos.
Las cargas consideradas para el diseño serán los pesos de los equipos, los tiros de
cortocircuito, las fuerzas generadas por los equipos en su operación (casos de
seccionadores e interruptores), las fuerzas debido a las cargas de sismo y datos
técnicos de los equipos a ser tomados en cuenta en el diseño.
FS= ZSUC / R
Las dimensiones de las bases, se ubicarán al mismo nivel de las existentes que es
entre 20 y 30 cm por encima del nivel de la plataforma de la subestación. Los
rellenos de las estructuras se realizarán con material propio.
Las varillas de acero de refuerzo para el concreto armado, cumplirán las normas
ASTM A615 (Grado 60) con límite de fluencia Fy=4,200 kg/cm 2. Los soportes
metálicos de equipos, son fijados a las bases de fundación mediante pernos de
anclaje los cuales se definirán en la etapa de ingeniería de detalle cuando se tenga
la información final de equipos a instalar.
Base de Pararrayos
Todas las canaletas llevarán un sistema de soportes metálicos para los cables
compuesto por ángulos y pletinas que permitirán un adecuado transporte de los
cables hacia la sala de control.
4.19.8 Drenajes
4.19.10 Demoliciones.
a) Primer Corte:
Con una duración de 12 horas, tiene como finalidad liberar el área de trabajo para
las obras civiles y se recomienda que este corte sea realizado antes del inicio de las
obras civiles, siendo responsabilidad de La Contratista su planificación; debido a
que existen cables de 10 kV energizados que interfieren la ejecución de las obras
civiles; dichos trabajos están considerados en el presupuesto.
Con una duración de 12 horas, tiene como finalidad de realizar la puesta en servicio
del proyecto, para lo cual, se debe tener en consideración lo siguiente:
7. VALOR REFERENCIAL
RESUMEN GENERAL
AMPLIACION DE POTENCIA DE LA SUBESTACION DE TRANSFORMACION DE MOYOBAMBA
PROYECTO :
DISTRITO Y PROVINCIA MOYOBAMBA , REGION SAN MARTIN.
DISTRITO: MOYOBAMBA
PROVINCIA : MOYOBAMBA
REGION : SAN MARTIN
SET: MOYOBAMBA Fecha: Set-20
AMPLIACION TOTAL
ITEM DESCRIPCIÓN
SET MOYOBAMBA S/