Está en la página 1de 7

NORMAS TÉCNICAS

ZONAS DE DEMANDA SECTOR RESIDENCIAL URBANO RA8-009


ÁREA METROPOLITANA DEL VALLE DE ABURRÁ

SELECCIÓN DE TRANSFORMADOR DE DISTRIBUCIÓN EN REDES


DE EPM MEDIANTE CURVAS DE DEMANDA DIVERSIFICADA

ZONAS DE DEMANDA SECTOR RESIDENCIAL URBANO


ÁREA METROPOLITANA DEL VALLE DE ABURRÁ

EMPRESAS PÚBLICAS DE MEDELLIN. ESP.


MEDELLÍN, ANTIOQUIA

PRIMERA EDICIÓN: ELABORÓ: AUTORIZÓ:


MAYO-1984 ÁREA INGENIERÍA DISTRIBUCIÓN SUBGERENCIA REDES DISTRIBUCIÓN
DISTRIBUCIÓN
ÚLTIMA PUBLICACIÓN: REVISÓ: Página 1 de 7
MARZO-2012 ÁREA INGENIERÍA DISTRIBUCIÓN
NORMAS TÉCNICAS

ZONAS DE DEMANDA SECTOR RESIDENCIAL URBANO RA8-009


ÁREA METROPOLITANA DEL VALLE DE ABURRÁ

TABLA DE CONTENIDO

1. OBJETIVO ....................................................................................................................................... 3
2. CONSIDERACIONES Y METODOLOGÍA UTILIZADA .................................................................... 3
3. TABLAS (Curvas de demanda diversificada) ................................................................................... 3

PRIMERA EDICIÓN: ELABORÓ: AUTORIZÓ:


MAYO-1984 ÁREA INGENIERÍA DISTRIBUCIÓN SUBGERENCIA REDES DISTRIBUCIÓN
DISTRIBUCIÓN
ÚLTIMA PUBLICACIÓN: REVISÓ: Página 2 de 7
MARZO-2012 ÁREA INGENIERÍA DISTRIBUCIÓN
NORMAS TÉCNICAS

ZONAS DE DEMANDA SECTOR RESIDENCIAL URBANO RA8-009


ÁREA METROPOLITANA DEL VALLE DE ABURRÁ

1. OBJETIVO

Esta norma tiene como propósito establecer las curvas de demanda diversificada para la selección
de transformadores de distribución en el sector residencial, ubicadas en las redes de energía EPM
del sector urbano del Área metropolitana del Valle de Aburrá.

2. CONSIDERACIONES Y METODOLOGÍA UTILIZADA

Existen factores propios de la variabilidad de la demanda que motivaron la actualización de la norma


anterior que tenía una vigencia del año1997 basada en el estudio de caracterización de la carga
realizada por la firma Mejía Villegas, como por ejemplo: el impacto del GLP y el gas natural; el uso
racional de energía eléctrica; los cambios en los hábitos y estilos de vida de los consumidores; el uso
de electrodomésticos más eficientes; entre otros.

El estudio de caracterización de la carga Eléctrica fue realizado para realizar inferencias con un nivel
de confianza del 95%.

Se utilizó la metodología empleada para determinar las curvas de demanda diversificada consistente
en un modelo de regresión lineal múltiple con replicaciones. Se utilizó la función inversa para
obtener la curva de Demanda diversificada donde:

[Y] = B0 + B1 / [X]

En X = 0, la variable tiene un valor indeterminado

En X = Infinito, la variable no es cero y tiende al consumo marginal.

Los resultados aplicados a esta norma fueron tomados del estudio de Caracterización de la carga
realizada por la consultora HMV y liderada por el Área Planeación Transmisión y Distribución Energía
de EPM

3. TABLAS (CURVAS DE DEMANDA DIVERSIFICADA)

Con la metodología utilizada se obtuvo, utilizando el análisis de varianza (tabla Anova), tres curvas
de Demanda Diversificada agrupadas por estratos 1-2, 3-4 y 5-6 (Ver tablas a continuación).

PRIMERA EDICIÓN: ELABORÓ: AUTORIZÓ:


MAYO-1984 ÁREA INGENIERÍA DISTRIBUCIÓN SUBGERENCIA REDES DISTRIBUCIÓN
DISTRIBUCIÓN
ÚLTIMA PUBLICACIÓN: REVISÓ: Página 3 de 7
MARZO-2012 ÁREA INGENIERÍA DISTRIBUCIÓN
NORMAS TÉCNICAS

ZONAS DE DEMANDA SECTOR RESIDENCIAL URBANO RA8-009


ÁREA METROPOLITANA DEL VALLE DE ABURRÁ

Tabla 1 de 4
Clase de Carga 1 - Estratos 1 y 2 Clase de Carga 2 - Estratos 3 y 4 Clase de Carga 3 - Estratos 5 y 6
Trafos Monof Trafos Trif Trafos Monof Trafos Trif Trafos Monof Trafos Trif
N° Usuarios kVA por kVA kVA por kVA kVA por kVA
kVA % de kVA % de kVA % de kVA % de kVA % de kVA % de
Usuario Totales Usuario Totales Usuario Totales
Trafo Uso Trafo Uso Trafo Uso Trafo Uso Trafo Uso Trafo Uso
1 3.22 3.22 5.0 64% - - 6.80 6.80 10.0 68% - - 6.83 6.83 10.0 68% - -
2 1.91 3.81 5.0 76% - - 3.68 7.36 10.0 74% - - 3.81 7.62 10.0 76% 15.0 51%
3 1.47 4.40 5.0 88% - - 2.64 7.93 10.0 79% 15.0 53% 2.81 8.43 10.0 84% 15.0 56%
4 1.25 5.00 5.0 100% - - 2.13 8.51 10.0 85% 15.0 57% 2.31 9.25 10.0 93% 15.0 62%
5 1.12 5.61 5.0 112% - - 1.82 9.09 10.0 91% 15.0 61% 2.02 10.09 10.0 101% 15.0 67%
6 1.04 6.22 10.0 62% - - 1.61 9.68 10.0 97% 15.0 65% 1.82 10.95 10.0 109% 15.0 73%
7 0.98 6.83 10.0 68% - - 1.47 10.27 10.0 103% 15.0 68% 1.69 11.82 15.0 79% 15.0 79%
8 0.93 7.44 10.0 74% 15.0 50% 1.36 10.87 10.0 109% 15.0 72% 1.59 12.70 15.0 85% 15.0 85%
9 0.90 8.06 10.0 81% 15.0 54% 1.27 11.47 10.0 115% 15.0 76% 1.51 13.60 15.0 91% 15.0 91%
10 0.87 8.68 10.0 87% 15.0 58% 1.21 12.08 15.0 81% 15.0 81% 1.45 14.50 15.0 97% 15.0 97%
11 0.85 9.30 10.0 93% 15.0 62% 1.15 12.69 15.0 85% 15.0 85% 1.40 15.40 15.0 103% 15.0 103%
12 0.83 9.93 10.0 99% 15.0 66% 1.11 13.30 15.0 89% 15.0 89% 1.36 16.31 15.0 109% 15.0 109%
13 0.81 10.55 10.0 106% 15.0 70% 1.07 13.92 15.0 93% 15.0 93% 1.32 17.22 25.0 69% 30.0 57%
14 0.80 11.18 10.0 112% 15.0 75% 1.04 14.54 15.0 97% 15.0 97% 1.30 18.14 25.0 73% 30.0 60%
15 0.79 11.80 15.0 79% 15.0 79% 1.01 15.16 15.0 101% 15.0 101% 1.27 19.06 25.0 76% 30.0 64%
16 0.78 12.43 15.0 83% 15.0 83% 0.99 15.78 15.0 105% 15.0 105% 1.25 19.98 25.0 80% 30.0 67%
17 0.77 13.06 15.0 87% 15.0 87% 0.96 16.40 15.0 109% 15.0 109% 1.23 20.90 25.0 84% 30.0 70%
18 0.76 13.68 15.0 91% 15.0 91% 0.95 17.03 15.0 114% 15.0 114% 1.21 21.82 25.0 87% 30.0 73%
19 0.75 14.31 15.0 95% 15.0 95% 0.93 17.65 25.0 71% 30.0 59% 1.20 22.75 25.0 91% 30.0 76%
20 0.75 14.94 15.0 100% 15.0 100% 0.91 18.28 25.0 73% 30.0 61% 1.18 23.67 25.0 95% 30.0 79%
21 0.74 15.56 15.0 104% 15.0 104% 0.90 18.90 25.0 76% 30.0 63% 1.17 24.59 25.0 98% 30.0 82%
22 0.74 16.19 15.0 108% 15.0 108% 0.89 19.53 25.0 78% 30.0 65% 1.16 25.52 25.0 102% 30.0 85%
23 0.73 16.82 15.0 112% 15.0 112% 0.88 20.16 25.0 81% 30.0 67% 1.15 26.45 25.0 106% 30.0 88%
24 0.73 17.45 15.0 116% 15.0 116% 0.87 20.78 25.0 83% 30.0 69% 1.14 27.37 25.0 109% 30.0 91%
25 0.72 18.08 25.0 72% 30.0 60% 0.86 21.41 25.0 86% 30.0 71% 1.13 28.30 25.0 113% 30.0 94%

PRIMERA EDICIÓN: ELABORÓ: AUTORIZÓ:


MAYO-1984 ÁREA INGENIERÍA DISTRIBUCIÓN SUBGERENCIA REDES DISTRIBUCIÓN
DISTRIBUCIÓN
ÚLTIMA PUBLICACIÓN: REVISÓ: Página 4 de 7
MARZO-2012 ÁREA INGENIERÍA DISTRIBUCIÓN
NORMAS TÉCNICAS

ZONAS DE DEMANDA SECTOR RESIDENCIAL URBANO RA8-009


ÁREA METROPOLITANA DEL VALLE DE ABURRÁ

Tabla 2 de 4 (continuación)

Clase de Carga 1 - Estratos 1 y 2 Clase de Carga 2 - Estratos 3 y 4 Clase de Carga 3 - Estratos 5 y 6


N° Usuarios kVA por kVA Trafos Monof Trafos Trif kVA por kVA Trafos Monof Trafos Trif kVA por kVA Trafos Monof Trafos Trif
Usuario Totales kVA % de kVA % de Usuario Totales kVA % de kVA % de Usuario Totales kVA % de kVA % de
Trafo Uso Trafo Uso Trafo Uso Trafo Uso Trafo Uso Trafo Uso
26 0.72 18.71 25.0 75% 30.0 62% 0.85 22.04 25.0 88% 30.0 73% 1.12 29.23 37.5 78% 30.0 97%
27 0.72 19.33 25.0 77% 30.0 64% 0.84 22.67 25.0 91% 30.0 76% 1.12 30.15 37.5 80% 30.0 101%
28 0.71 19.96 25.0 80% 30.0 67% 0.83 23.29 25.0 93% 30.0 78% 1.11 31.08 37.5 83% 30.0 104%
29 0.71 20.59 25.0 82% 30.0 69% 0.82 23.92 25.0 96% 30.0 80% 1.10 32.01 37.5 85% 30.0 107%
30 0.71 21.22 25.0 85% 30.0 71% 0.82 24.55 25.0 98% 30.0 82% 1.10 32.94 37.5 88% 30.0 110%
31 0.70 21.85 25.0 87% 30.0 73% 0.81 25.18 25.0 101% 30.0 84% 1.09 33.87 37.5 90% 30.0 113%
32 0.70 22.48 25.0 90% 30.0 75% 0.81 25.81 25.0 103% 30.0 86% 1.09 34.80 37.5 93% 45.0 77%
33 0.70 23.11 25.0 92% 30.0 77% 0.80 26.44 25.0 106% 30.0 88% 1.08 35.72 37.5 95% 45.0 79%
34 0.70 23.74 25.0 95% 30.0 79% 0.80 27.06 25.0 108% 30.0 90% 1.08 36.65 37.5 98% 45.0 81%
35 0.70 24.37 25.0 97% 30.0 81% 0.79 27.69 25.0 111% 30.0 92% 1.07 37.58 45.0 84% 45.0 84%
36 0.69 25.00 25.0 100% 30.0 83% 0.79 28.32 25.0 113% 30.0 94% 1.07 38.51 37.5 103% 45.0 86%
37 0.69 25.62 25.0 102% 30.0 85% 0.78 28.95 25.0 116% 30.0 97% 1.07 39.44 37.5 105% 45.0 88%
38 0.69 26.25 25.0 105% 30.0 88% 0.78 29.58 37.5 79% 30.0 99% 1.06 40.37 37.5 108% 45.0 90%
39 0.69 26.88 25.0 108% 30.0 90% 0.77 30.21 37.5 81% 30.0 101% 1.06 41.30 37.5 110% 45.0 92%
40 0.69 27.51 25.0 110% 30.0 92% 0.77 30.84 37.5 82% 30.0 103% 1.06 42.23 37.5 113% 45.0 94%
41 0.69 28.14 25.0 113% 30.0 94% 0.77 31.47 37.5 84% 30.0 105% 1.05 43.16 37.5 115% 45.0 96%
42 0.69 28.77 25.0 115% 30.0 96% 0.76 32.10 37.5 86% 30.0 107% 1.05 44.09 50.0 88% 45.0 98%
43 0.68 29.40 25.0 118% 30.0 98% 0.76 32.73 37.5 87% 30.0 109% 1.05 45.02 50.0 90% 45.0 100%
44 0.68 30.03 37.5 80% 30.0 100% 0.76 33.36 37.5 89% 30.0 111% 1.04 45.95 50.0 92% 45.0 102%
45 0.68 30.66 37.5 82% 30.0 102% 0.76 33.99 37.5 91% 30.0 113% 1.04 46.88 50.0 94% 45.0 104%
46 0.68 31.29 37.5 83% 30.0 104% 0.75 34.62 37.5 92% 30.0 115% 1.04 47.81 50.0 96% 45.0 106%
47 0.68 31.92 37.5 85% 30.0 106% 0.75 35.25 37.5 94% 30.0 117% 1.04 48.74 50.0 97% 45.0 108%
48 0.68 32.55 37.5 87% 30.0 108% 0.75 35.88 37.5 96% 45.0 80% 1.03 49.67 50.0 99% 45.0 110%
49 0.68 33.18 37.5 88% 30.0 111% 0.75 36.51 37.5 97% 45.0 81% 1.03 50.60 50.0 101% 45.0 112%
50 0.68 33.81 37.5 90% 30.0 113% 0.74 37.13 37.5 99% 45.0 83% 1.03 51.53 50.0 103% 45.0 115%

PRIMERA EDICIÓN: ELABORÓ: AUTORIZÓ:


MAYO-1984 ÁREA INGENIERÍA DISTRIBUCIÓN SUBGERENCIA REDES DISTRIBUCIÓN
DISTRIBUCIÓN
ÚLTIMA PUBLICACIÓN: REVISÓ: Página 5 de 7
MARZO-2012 ÁREA INGENIERÍA DISTRIBUCIÓN
NORMAS TÉCNICAS

ZONAS DE DEMANDA SECTOR RESIDENCIAL URBANO RA8-009


ÁREA METROPOLITANA DEL VALLE DE ABURRÁ

Tabla 3 de 4 (continuación)

Clase de Carga 1 - Estratos 1 y 2 Clase de Carga 2 - Estratos 3 y 4 Clase de Carga 3 - Estratos 5 y 6


N° Usuarios kVA por kVA Trafos Monof Trafos Trif kVA por kVA Trafos Monof Trafos Trif kVA por kVA Trafos Monof Trafos Trif
Usuario Totales kVA % de kVA % de Usuario Totales kVA % de kVA % de Usuario Totales kVA % de kVA % de
Trafo Uso Trafo Uso Trafo Uso Trafo Uso Trafo Uso Trafo Uso
51 0.68 34.44 37.5 92% 30.0 115% 0.74 37.76 37.5 101% 45.0 84% 1.03 52.46 50.0 105% 75.0 70%
52 0.67 35.07 37.5 94% 30.0 117% 0.74 38.39 37.5 102% 45.0 85% 1.03 53.39 50.0 107% 75.0 71%
53 0.67 35.69 37.5 95% 45.0 79% 0.74 39.02 37.5 104% 45.0 87% 1.02 54.32 50.0 109% 75.0 72%
54 0.67 36.32 37.5 97% 45.0 81% 0.73 39.65 37.5 106% 45.0 88% 1.02 55.25 50.0 110% 75.0 74%
55 0.67 36.95 37.5 99% 45.0 82% 0.73 40.28 37.5 107% 45.0 90% 1.02 56.18 50.0 112% 75.0 75%
56 0.67 37.58 37.5 100% 45.0 84% 0.73 40.91 37.5 109% 45.0 91% 1.02 57.11 50.0 114% 75.0 76%
57 0.67 38.21 37.5 102% 45.0 85% 0.73 41.54 37.5 111% 45.0 92% 1.02 58.04 50.0 116% 75.0 77%
58 0.67 38.84 37.5 104% 45.0 86% 0.73 42.17 37.5 112% 45.0 94% 1.02 58.97 75.0 79% 75.0 79%
59 0.67 39.47 37.5 105% 45.0 88% 0.73 42.80 37.5 114% 45.0 95% 1.02 59.90 75.0 80% 75.0 80%
60 0.67 40.10 37.5 107% 45.0 89% 0.72 43.43 37.5 116% 45.0 97% 1.01 60.83 75.0 81% 75.0 81%
61 0.67 40.73 37.5 109% 45.0 91% 0.72 44.06 37.5 118% 45.0 98% 1.01 61.76 75.0 82% 75.0 82%
62 0.67 41.36 37.5 110% 45.0 92% 0.72 44.69 50.0 89% 45.0 99% 1.01 62.69 75.0 84% 75.0 84%
63 0.67 41.99 37.5 112% 45.0 93% 0.72 45.32 50.0 91% 45.0 101% 1.01 63.62 75.0 85% 75.0 85%
64 0.67 42.62 37.5 114% 45.0 95% 0.72 45.95 50.0 92% 45.0 102% 1.01 64.55 75.0 86% 75.0 86%
65 0.67 43.25 37.5 115% 45.0 96% 0.72 46.58 50.0 93% 45.0 104% 1.01 65.48 75.0 87% 75.0 87%
66 0.66 43.88 37.5 117% 45.0 98% 0.72 47.21 50.0 94% 45.0 105% 1.01 66.41 75.0 89% 75.0 89%
67 0.66 44.51 50.0 89% 45.0 99% 0.71 47.84 50.0 96% 45.0 106% 1.01 67.34 75.0 90% 75.0 90%
68 0.66 45.14 50.0 90% 45.0 100% 0.71 48.47 50.0 97% 45.0 108% 1.00 68.27 75.0 91% 75.0 91%
69 0.66 45.77 50.0 92% 45.0 102% 0.71 49.10 50.0 98% 45.0 109% 1.00 69.20 75.0 92% 75.0 92%
70 0.66 46.40 50.0 93% 45.0 103% 0.71 49.73 50.0 99% 45.0 111% 1.00 70.13 75.0 94% 75.0 94%
71 0.66 47.03 50.0 94% 45.0 105% 0.71 50.36 50.0 101% 45.0 112% 1.00 71.06 75.0 95% 75.0 95%
72 0.66 47.66 50.0 95% 45.0 106% 0.71 50.99 50.0 102% 45.0 113% 1.00 71.99 75.0 96% 75.0 96%
73 0.66 48.29 50.0 97% 45.0 107% 0.71 51.62 50.0 103% 45.0 115% 1.00 72.92 75.0 97% 75.0 97%
74 0.66 48.92 50.0 98% 45.0 109% 0.71 52.25 50.0 105% 45.0 116% 1.00 73.85 75.0 98% 75.0 98%
75 0.66 49.55 50.0 99% 45.0 110% 0.71 52.89 50.0 106% 45.0 118% 1.00 74.78 75.0 100% 75.0 100%

PRIMERA EDICIÓN: ELABORÓ: AUTORIZÓ:


MAYO-1984 ÁREA INGENIERÍA DISTRIBUCIÓN SUBGERENCIA REDES DISTRIBUCIÓN
DISTRIBUCIÓN
ÚLTIMA PUBLICACIÓN: REVISÓ: Página 6 de 7
MARZO-2012 ÁREA INGENIERÍA DISTRIBUCIÓN
NORMAS TÉCNICAS

ZONAS DE DEMANDA SECTOR RESIDENCIAL URBANO RA8-009


ÁREA METROPOLITANA DEL VALLE DE ABURRÁ

Tabla 4 de 4 (continuación)

Clase de Carga 1 - Estratos 1 y 2 Clase de Carga 2 - Estratos 3 y 4 Clase de Carga 3 - Estratos 5 y 6


N° Usuarios kVA por kVA Trafos Monof Trafos Trif kVA por kVA Trafos Monof Trafos Trif kVA por kVA Trafos Monof Trafos Trif
Usuario Totales kVA % de kVA % de Usuario Totales kVA % de kVA % de Usuario Totales kVA % de kVA % de
Trafo Uso Trafo Uso Trafo Uso Trafo Uso Trafo Uso Trafo Uso
76 0.66 50.18 50.0 100% 45.0 112% 0.70 53.52 50.0 107% 75.0 71% 1.00 75.71 75.0 101% 75.0 101%
77 0.66 50.81 50.0 102% 45.0 113% 0.70 54.15 50.0 108% 75.0 72% 1.00 76.64 75.0 102% 75.0 102%
78 0.66 51.44 50.0 103% 45.0 114% 0.70 54.78 50.0 110% 75.0 73% 0.99 77.57 75.0 103% 75.0 103%
79 0.66 52.07 50.0 104% 45.0 116% 0.70 55.41 50.0 111% 75.0 74% 0.99 78.50 75.0 105% 75.0 105%
80 0.66 52.69 50.0 105% 45.0 117% 0.70 56.04 50.0 112% 75.0 75% 0.99 79.43 75.0 106% 75.0 106%
81 0.66 53.32 50.0 107% 75.0 71% 0.70 56.67 50.0 113% 75.0 76% 0.99 80.36 75.0 107% 75.0 107%
82 0.66 53.95 50.0 108% 75.0 72% 0.70 57.30 50.0 115% 75.0 76% 0.99 81.29 75.0 108% 75.0 108%
83 0.66 54.58 50.0 109% 75.0 73% 0.70 57.93 50.0 116% 75.0 77% 0.99 82.23 75.0 110% 75.0 110%
84 0.66 55.21 50.0 110% 75.0 74% 0.70 58.56 50.0 117% 75.0 78% 0.99 83.16 75.0 111% 75.0 111%
85 0.66 55.84 50.0 112% 75.0 74% 0.70 59.19 50.0 118% 75.0 79% 0.99 84.09 75.0 112% 75.0 112%
86 0.66 56.47 50.0 113% 75.0 75% 0.70 59.82 75.0 80% 75.0 80% 0.99 85.02 75.0 113% 75.0 113%
87 0.66 57.10 50.0 114% 75.0 76% 0.69 60.45 75.0 81% 75.0 81% 0.99 85.95 75.0 115% 75.0 115%
88 0.66 57.73 50.0 115% 75.0 77% 0.69 61.08 75.0 81% 75.0 81% 0.99 86.88 75.0 116% 75.0 116%
89 0.66 58.36 50.0 117% 75.0 78% 0.69 61.71 75.0 82% 75.0 82% 0.99 87.81 75.0 117% 75.0 117%
90 0.66 58.99 50.0 118% 75.0 79% 0.69 62.34 75.0 83% 75.0 83% 0.99 88.74 100.0 89% 112.5 79%
91 0.66 59.62 75.0 79% 75.0 79% 0.69 62.97 75.0 84% 75.0 84% 0.99 89.67 100.0 90% 112.5 80%
92 0.65 60.25 75.0 80% 75.0 80% 0.69 63.60 75.0 85% 75.0 85% 0.98 90.60 100.0 91% 112.5 81%
93 0.65 60.88 75.0 81% 75.0 81% 0.69 64.23 75.0 86% 75.0 86% 0.98 91.53 100.0 92% 112.5 81%
94 0.65 61.51 75.0 82% 75.0 82% 0.69 64.86 75.0 86% 75.0 86% 0.98 92.46 100.0 92% 112.5 82%
95 0.65 62.17 75.0 83% 75.0 83% 0.69 65.49 75.0 87% 75.0 87% 0.98 93.39 100.0 93% 112.5 83%
96 0.65 62.82 75.0 84% 75.0 84% 0.69 66.12 75.0 88% 75.0 88% 0.98 94.32 100.0 94% 112.5 84%
97 0.65 63.47 75.0 85% 75.0 85% 0.69 66.75 75.0 89% 75.0 89% 0.98 95.25 100.0 95% 112.5 85%
98 0.65 64.13 75.0 86% 75.0 86% 0.69 67.38 75.0 90% 75.0 90% 0.98 96.18 100.0 96% 112.5 85%
99 0.65 64.78 75.0 86% 75.0 86% 0.69 68.07 75.0 91% 75.0 91% 0.98 97.11 100.0 97% 112.5 86%
100 0.65 65.44 75.0 87% 75.0 87% 0.69 68.76 100.0 69% 112.5 61% 0.98 98.04 100.0 98% 112.5 87%
Nota: Para un mayor número de usuarios, utilizar el último valor de kVA por usuario y multiplicarlo por la
cantidad de usuarios requerida

REFERENCIA BIBLIOGRÁFICA

HMV Ingenieros. Estudio de caracterización de la carga en el Valle de Aburrá. Año 2009

IEEE Std C57.91-1995, IEEE Guide for Loading Mineral-Oil-Immersed Transformers. IEEE
Std C57.91-1995-Cor 1-2002

PRIMERA EDICIÓN: ELABORÓ: AUTORIZÓ:


MAYO-1984 ÁREA INGENIERÍA DISTRIBUCIÓN SUBGERENCIA REDES DISTRIBUCIÓN
DISTRIBUCIÓN
ÚLTIMA PUBLICACIÓN: REVISÓ: Página 7 de 7
MARZO-2012 ÁREA INGENIERÍA DISTRIBUCIÓN