Documentos de Académico
Documentos de Profesional
Documentos de Cultura
WEG CFW 11 Ip54 Addendum To The Users Manual 10000396310 Manual English
WEG CFW 11 Ip54 Addendum To The Users Manual 10000396310 Manual English
Frequency Inverter
Convertidor de Frecuencia
Inversor de Frequncia
CFW-11 IP54
Addendum to the CFW-11 Users Manual
Adendo al Manual del Usuario CFW-11
Adendo ao Manual do Usurio CFW-11
English / Espaol / Portugus
Summary
1. Introduction.....................................................................................................................5
2. List of Models and Technical Specifications.........................................................................5
3. Installation and Connection...............................................................................................9
3.1 Mechanical Installation...............................................................................................9
3.1.1 Installation Environment.....................................................................................9
3.1.2 Positioning and Mounting..................................................................................9
3.1.3 Access to the Control and Power Terminal Strips and Front Cover Mounting..........10
3.2 Electrical Installation - Grounding Terminals................................................................11
4. Accessories for the CFW-11 IP54 Protection Degree Models...............................................11
5. Mechanical Data.............................................................................................................12
6. Others............................................................................................................................15
ndice
1. Introduccin....................................................................................................................16
2. Relacin de Modelos y Especificaciones Tcnicas...............................................................16
3. Instalacin y Conexin.....................................................................................................20
3.1 Instalacin Mecnica.................................................................................................20
3.1.1 Condiciones Ambientales.................................................................................20
3.1.2 Posicionamiento y Fijacin................................................................................20
3.1.3 Acceso a los Bornes de Control y de Potencia y Montaje de la Tapa Frontal..........21
3.2 Instalacin Elctrica - Puntos de Puesta a la Tierra.......................................................22
4. Accesorios para los Modelos CFW-11 con Grado de Proteccin IP54.................................22
5. Datos Mecnicos.............................................................................................................23
6. Otros.............................................................................................................................26
ndice
1. Introduo......................................................................................................................27
2. Relao de Modelos e Especificaes Tcnicas..................................................................27
3. Instalao e Conexo......................................................................................................31
3.1 Instalao Mecnica.................................................................................................31
3.1.1 Condies Ambientais......................................................................................31
3.1.2 Posicionamento e Fixao.................................................................................31
3.1.3 Acesso aos Bornes de Controle e Potncia e Montagem da Tampa Frontal...........32
3.2 Instalao Eltrica - Pontos de Aterramento.................................................................33
4. Acessrios para os Modelos CFW-11 com Grau de Proteo IP54......................................33
5. Dados Mecnicos............................................................................................................34
6. Outros...........................................................................................................................37
(*) Inverter model with RFI filter option has only single-phase power supply input.
Notes: 1 = single-phase power supply, 3 = three-phase power supply.
1 / 3
7.0
10
13
16
24
28
33.5
45
54
70
86
105
115
7.0
7.0
142
10
5.0
Surrounding air
temperature [C (F)]
-10...40 C (14 ... 104 F)
6.0
Dynamic braking
Optional
(the standard
product does
not have
braking)
Built-in
RFI filter
Built-in
Model
Frame
1 / 3
Yes
Yes (*)
ENGLISH
80
(176)
41
(90)
36
(79)
15
(33)
10
(22)
RFI suppressor
filter
Yes
Dynamic braking
No (braking IGBT available in the standard product)
Number of power
phases
Inverter supply
nominal
voltage range [V]
200...240 V
220...230 V
Safety stop
Yes
Yes
1. INTRODUCTION
This addendum brings information on the CFW11 XXXX X X O 54 ... (CFW-11 models
with IP54 protection degree). Only the differences compared to the standard product (with
IP20 protection degree) are presented. The other information presented in the users guide
is also valid for these models.
3
3
Inverter supply
nominal
voltage range [V]
380...480 V
Model
Frame
142
105
88
70.5
58.5
45
38
115
88
73
61
47
38
33
25
19
24
31
11
13.5
10
10
17
5.5
7.0
13.5
3.6
5.0
5.0
Surrounding air
temperature [C (F)]
-10...40 C (14 ...104 F)
Built-in
Optional
(the standard
product does
not have
braking)
Dynamic braking
Built-in
RFI filter
Optional (the standard product does not have RFI filter)
Number of power
phases
41
(90)
36
(79)
15
(33)
10
(22)
RFI suppressor
filter
No (filter
available in
the standard
product)
Yes
Yes
Yes
Yes
Dynamic braking
No (braking IGBT available in the standard product)
Safety stop
6
Yes
Yes
ENGLISH
Table 1 b) - CFW-11 IP54 list of models and technical specifications 380-480 V supply models
Model
Frame
3
Equivalent
IP20 inverter
frame size
E
10
6.0
7.0
7.0
10
13
16
24
28
33.5
45
54
70
86
105
142
3.6
5.0
7.0
10
13.5
17
24
31
38
45
58.5
70.5
88
105
142
Rated
output
current (1)
[Arms]
11.0
6.60
7.70
7.70
11.0
14.3
17.6
26.4
30.8
36.9
49.5
59.4
77.0
94.6
116
156
3.96
5.50
7.7
11.0
14.9
18.7
26.4
34.1
41.8
49.5
64.4
77.6
96.8
116
156
1 min
3s
15.0
9.00
10.5
10.5
15.0
19.5
24.0
36.0
42.0
50.3
67.5
81.0
105
129
158
213
5.40
7.50
10.5
15.0
20.3
25.5
36.0
46.5
57.0
67.5
87.8
106
132
158
213
Overload
current (2)
[Arms]
ENGLISH
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
2.5
5
5
5
5
5
5
5
5
5
5
5
5
5
2.5
2.5
Rated carrier
frequency (3)
[kHz]
3/2.2
1.5/1.1
2/1.5
2/1.5
3/2.2
4/3.0
5/3.7
7.5/5.5
10/7.5
12.5/9.2
15/11
20/15
25/18.5
30/22
40/30
50/37
2/1.5
3/2.2
4/3
6/4.5
7.5/5.5
10/7.5
15/11
20/15
25/18.5
30/22
40/30
50/37
60/45
75/55
100/75
Maximum
motor (4)
[HP/kW]
20.5
12.3/6.0 (5)
14.4/7.0 (5)
7.0
10.0
13.0
16.0
24.0
28.0
33.5
45.0
54.0
70.0
86.0
105
142
3.6
5.0
7.0
10.0
13.5
17.0
24.0
31.0
38.0
45.0
58.5
70.5
88.0
105
142
Rated input
current
[Arms]
180
130
140
140
170
200
230
310
370
430
590
680
900
970
1200
1490
130
140
180
220
280
360
490
560
710
810
1050
1280
1480
1270
1680
Dissipated
power
[W]
Table 2 - CFW-11 IP54 protection degree models electrical specification Normal duty cycle (ND) application
Model
Frame
3
Equivalent
IP20 inverter
frame size
E
10
5.0
7.0
5.5
8.0
11
13
20
24
28
36
45
56
70
86
115
3.6
5.0
5.5
10
11
13.5
19
25
33
38
47
61
73
88
115
Rated
output
current (1)
[Arms]
15.0
7.50
10.5
8.25
12.0
16.5
19.5
30.0
36.0
42.0
54.0
67.5
84.0
105
129
172.5
5.40
7.50
8.25
15.0
16.5
20.3
28.5
37.5
49.5
57.0
70.5
91.5
110
132
173
1 min
3s
20.0
10.0
14.0
11.0
16.0
22.0
26.0
40.0
48.0
56.0
72.0
90.0
112
140
172
230
7.20
10.0
11.0
20.0
22.0
27.0
38.0
50.0
66.0
76.0
94.0
122
146
176
230
Overload
current (2)
[Arms]
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5 (3)
5
5
5
5
5
5
5
5
5
5
5
5
5
2.5
2.5
Rated carrier
frequency (3)
[kHz]
ENGLISH
3/2.2
1.5/1.1
2/1.5
1.5/1.1
2/1.5
3/2.2
4/3.0
6/4.5
7.5/5.5
10/7.5
12.5/9.2
15/11
20/15
25/18.5
30/22
40/30
2/1.5
3/2.2
3/2.2
6/4.5
6/4.5
7.5/5.5
10/7.5
15/11
20/15
25/18.5
30/22
40/30
50/37
60/45
75/55
Maximum
motor (4)
[HP/kW]
20.5
10.3/5.0 (5)
14.4/7.0 (5)
5.5
8.0
11.0
13.0
20.0
24.0
28.0
36.0
45.0
56.0
70.0
86.0
115
3.6
5.0
5.5
10.0
11.0
13.5
19.0
25.0
33.0
38.0
47.0
61.0
73.0
88.0
115
Rated input
current
[Arms]
140
120
140
120
170
170
190
250
290
350
450
540
680
740
920
1280
110
140
140
200
220
270
360
430
590
650
800
1050
1170
1020
1290
Dissipated
power
[W]
Table 3 - CFW-11 IP54 protection degree models electrical specification Heavy duty cycle (HD) application
NOTES!
- The notes (1) to (8) mentioned in the tables 1, 2 and 3 are those from the section 8.1 of
the users guide. Observe that the environment temperature specification (surrounding the
inverter) for CFW11 XXXX X X O 54 ... inverters is from -10 C (14 F) to 40 C (104 F). It is
possible to operate this inverter in environments with temperatures surrounding the inverter
up to 50 C (122 F) if a derating of 2 % for each C (1.1 % for each F) is applied to the
output current. This output current derating is valid for all the switching frequencies.
- The tables 1, 2 and 3 replace the table 8.1 of the users guide.
ENGLISH
a2
b2
a2
b2
a2
c2
c2
Air flow
(b) Surface mounting
A1
B1
C1
D1
a2
b2
c2
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
Frame 1
255
(10.04)
410
(16.14)
235
(9.23)
450
(17.72)
200
(7.87)
425
(16.73)
M6
Frame 2
350
(13.78)
625
(24.61)
298
(11.71)
675
(26.57)
250
(9.84)
650
(25.59)
M8
Frame 3
400
(15.75)
825
(32.48)
389
(15.31)
875
(34.45)
150
(5.91)
850
(33.46)
M8
Model
ENGLISH
3.1.3 Access to the Control and Power Terminal Strips and Front Cover Mounting
1
2
3
3
4
2
Note: The tightening sequence for mounting the front cover is: 1-2-3-4-5-6. Torque: 2.5 Nm.
10
ENGLISH
The figure 3 shows the grounding points located inside the product.
Grounding
Figure 3 - Product grounding
Name
10960847
CCS-01
11112774
PCS1-01
Shielding kit for power cables for IP54 frame size 1 models (standard for
option FA).
11112776
11119781
Shielding kit for power cables for frame size D (IP20) inverters and
PCSD-01 CFW110086T2O54..., CFW110105T2O54..., CFW110070T4O54...
and CFW110088T4O54... models - included in the standard product.
10960844
PCSE-01
Description
Shielding kit for power cables for frame size E (IP20) and frame size 3
(IP54) inverters - included in the standard product.
11
* Models of the frame size 1 up to CFW11 0016T2O54 ... and CFW11 0013T4O54 ...
** Models of the frame size 1 beginning from the CFW11 0024T2O54 ... and CFW11 0017T4O54 ...
ENGLISH
5. MECHANICAL DATA
Frame 1
12
Dimensions in mm [in]
* Models of the frame size 2 up to CFW11 0070T2O54 ... and CFW11 0058T4O54 ...
** Models of the frame size 2 beginning from the CFW11 0086T2O54 ... and CFW11 0070T4O54 ...
ENGLISH
Frame 2
Dimensions in mm [in]
13
ENGLISH
Frame 3
Dimensions in mm [in]
6. OTHERS
ATTENTION!
The parameter P0352 (Fan Configuration) must be set at 1 or 4 for the CFW11 XXXX X X
O 54 ... inverters.
NOTES!
ATTENTION!
The following items from the users guide do not apply to the CFW11 XXXX X X O 54 ...
inverters:
- Flange mounting described in the section 3.1.3;
- Figure 3.5 (section 3.1.4) of the CFW-11 inverters frame sizes AD users guide;
- Sections 3.1.4 to 3.1.7 of the CFW-11 inverters frame size E users guide;
- Frame sizes 1 and 2 inverters: values for surrounding air temperature = 50 C (122 F)
of the table 8.2;
- Frame size 3 inverters: values presented in the tables 8.2 and 8.4;
- Protection degree specification of the section 8.2.
ENGLISH
- The CFW11 XXXX X X O 54 ... models are supplied with the parameter P0352 adjusted in
4, i.e., the heatsink fan is controlled based in the IGBT/rectifier temperature and the internal
fan is always activated.
- If the factory settings are loaded (via P0204) and the inverter software version is equal
or prior to V1.6x, the parameter P0352 is adjusted automatically in 2. In this case, for the
CFW11 XXXX X X O 54 ... inverters, adjust this parameter again in 1 or 4.
NOTE!
The CFW11 XXXX X X O 54 ... models are not UL listed.
15
Alimentacin externa de
la electrnica en 24 Vcc
Parada de seguridad
S
No (filtro
disponible en
el producto
padrn)
Opcional
(el producto
80
padrn
Posee
(176)
no posee
frenado)
41
(90)
Frenado reosttico
Posee
8.0
11
13
20
24
28
36
45
56
70
86
7.0
10
13
16
24
28
33.5
45
54
70
86
105
3
CFW11 0142 T 2 O 54 ...
3
CFW11 0105 T 2 O 54 ...
3
CFW11 0054 T 2 O 54 ...
3
CFW11 0045 T 2 O 54 ...
3
CFW11 0028 T 2 O 54 ...
3
CFW11 0024 T 2 O 54 ...
Corriente de salida
nominal de ND (1)
[Arms] consultar tabla 2
Alimentacin
Mecnica
Mecnica del convertidor
de frecuencia IP20 equivalente
3
CFW11 0007 T 2 O 54 ...
1 / 3
CFW11 0007 B 2 O 54 ...
1 / 3
115
7.0
7.0
Corriente de salida
nominal de HD (1)
[Arms] - consultar tabla 3
Rango de variacin de la tensin
nominal de alimentacin del
convertidor de frecuencia [V]
200...240 V
CFW11 0010 S 2 O 54 ...
220...230 V
142
10
5.0
10
6.0
Modelo
16
36
(79)
15
(33)
10
(22)
ESPAOL
S (*)
Frenado reosttico
S
Tabla 1 a) - Relacin de modelos de la lnea CFW-11 IP54 y especificaciones tcnicas Modelos con alimentacin 200-240 V/220-230 V
(*) El modelo de convertidor de frecuencia con la opcin de filtro RFI posee solamente alimentacin de entrada monofsica.
Obs.: 1 = alimentacin monofsica, 3 = alimentacin trifsica.
24
ESPAOL
142
105
88
70.5
58.5
45
38
115
88
73
61
47
38
33
25
19
17
31
11
13.5
13.5
10
5.5
7.0
10
3.6
5.0
Corriente de salida
nominal de ND (1)
[Arms] consultar tabla 2
3.6
Corriente de salida
nominal de HD (1)
[Arms] - consultar tabla 3
5.0
Modelo
Mecnica
Frenado reosttico
Opcional
(el producto
padrn
no posee
frenado)
Posee
Filtro RFI
Posee
Alimentacin
41
(90)
36
(79)
15
(33)
10
(22)
Frenado reosttico
No (IGBT de frenado
disponible en el producto padrn)
S
Parada de seguridad
S
Alimentacin externa de
la electrnica en 24 Vcc
Tabla 1 b) - Relacin de modelos de la lnea CFW-11 IP54 y especificaciones tcnicas Modelos con alimentacin 380-480 V
17
18
Modelo
Mecnica
3
Mecnica del
convertidor de
frecuencia IP20
equivalente
E
10
6.0
7.0
7.0
10
13
16
24
28
33.5
45
54
70
86
105
142
3.6
5.0
7.0
10
13.5
17
24
31
38
45
58.5
70.5
88
105
142
Corriente
de salida
nominal (1)
[Arms]
ESPAOL
11.0
6.60
7.70
7.70
11.0
14.3
17.6
26.4
30.8
36.9
49.5
59.4
77.0
94.6
116
156
3.96
5.50
7.7
11.0
14.9
18.7
26.4
34.1
41.8
49.5
64.4
77.6
96.8
116
156
1 min
15.0
9.00
10.5
10.5
15.0
19.5
24.0
36.0
42.0
50.3
67.5
81.0
105
129
158
213
5.40
7.50
10.5
15.0
20.3
25.5
36.0
46.5
57.0
67.5
87.8
106
132
158
213
3s
Corriente de
sobrecarga (2)
[Arms]
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
2.5
5
5
5
5
5
5
5
5
5
5
5
5
5
2.5
2.5
Frecuencia de
conmutacin
nominal (3)
[kHz]
3/2.2
1.5/1.1
2/1.5
2/1.5
3/2.2
4/3.0
5/3.7
7.5/5.5
10/7.5
12.5/9.2
15/11
20/15
25/18.5
30/22
40/30
50/37
2/1.5
3/2.2
4/3
6/4.5
7.5/5.5
10/7.5
15/11
20/15
25/18.5
30/22
40/30
50/37
60/45
75/55
100/75
Motor
mximo (4)
[HP/kW]
20.5
12.3/6.0 (5)
14.4/7.0 (5)
7.0
10.0
13.0
16.0
24.0
28.0
33.5
45.0
54.0
70.0
86.0
105
142
3.6
5.0
7.0
10.0
13.5
17.0
24.0
31.0
38.0
45.0
58.5
70.5
88.0
105
142
Corriente de
entrada
nominal
[Arms]
180
130
140
140
170
200
230
310
370
430
590
680
900
970
1200
1490
130
140
180
220
280
360
490
560
710
810
1050
1280
1480
1270
1680
Potencia
disipada
[W]
Tabla 2 - Especificaciones elctricas para los modelos con grado de proteccin IP54 de la lnea
CFW-11 - uso en rgimen de sobrecarga normal (ND)
Modelo
Mecnica
3
Mecnica del
convertidor de
frecuencia IP20
equivalente
E
ESPAOL
10
5.0
7.0
5.5
8.0
11
13
20
24
28
36
45
56
70
86
115
3.6
5.0
5.5
10
11
13.5
19
25
33
38
47
61
73
88
115
Corriente
de salida
nominal (1)
[Arms]
15.0
7.50
10.5
8.25
12.0
16.5
19.5
30.0
36.0
42.0
54.0
67.5
84.0
105
129
172.5
5.40
7.50
8.25
15.0
16.5
20.3
28.5
37.5
49.5
57.0
70.5
91.5
110
132
173
1 min
20.0
10.0
14.0
11.0
16.0
22.0
26.0
40.0
48.0
56.0
72.0
90.0
112
140
172
230
7.20
10.0
11.0
20.0
22.0
27.0
38.0
50.0
66.0
76.0
94.0
122
146
176
230
3s
Corriente de
sobrecarga (2)
[Arms]
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5 (3)
5
5
5
5
5
5
5
5
5
5
5
5
5
2.5
2.5
Frecuencia de
conmutacin
nominal (3)
[kHz]
3/2.2
1.5/1.1
2/1.5
1.5/1.1
2/1.5
3/2.2
4/3.0
6/4.5
7.5/5.5
10/7.5
12.5/9.2
15/11
20/15
25/18.5
30/22
40/30
2/1.5
3/2.2
3/2.2
6/4.5
6/4.5
7.5/5.5
10/7.5
15/11
20/15
25/18.5
30/22
40/30
50/37
60/45
75/55
Motor
mximo (4)
[HP/kW]
20.5
10.3/5.0 (5)
14.4/7.0 (5)
5.5
8.0
11.0
13.0
20.0
24.0
28.0
36.0
45.0
56.0
70.0
86.0
115
3.6
5.0
5.5
10.0
11.0
13.5
19.0
25.0
33.0
38.0
47.0
61.0
73.0
88.0
115
Corriente de
entrada
nominal
[Arms]
140
120
140
120
170
170
190
250
290
350
450
540
680
740
920
1280
110
140
140
200
220
270
360
430
590
650
800
1050
1170
1020
1290
Potencia
disipada
[W]
Tabla 3 - Especificaciones elctricas para los modelos con grado de proteccin IP54 de la lnea
CFW-11 - uso en rgimen de sobrecarga pesada (HD)
19
NOTAS!
- Las notas (1) a (8) mencionadas en las tablas 1, 2 e 3 son conforme el tem 8.1 del manual
del usuario. Observar que la especificacin de la temperatura ambiente (al rededor del
convertidor de frecuencia) para convertidores de frecuencia CFW11 XXXX X X O 54 ... es
de -10 C (14 F) a 40 C (104 F). Es posible que este convertidor de frecuencia opere
en ambientes con temperatura ambiente al rededor del convertidor de frecuencia hasta
50 C (122 F) si fuera aplicado reduccin de la corriente de salida de 2 % para cada C
arriba de 40 C (104 F). Esa reduccin de la corriente de salida es vlida para todas las
frecuencias de conmutacin.
- Las tablas 1, 2 y 3 de este adendo substituyen la tabla 8.1 del manual del usuario.
3. INSTALACIN Y CONEXIN
3.1 Instalacin Mecnica
ESPAOL
a2
a2
b2
b2
a2
c2
c2
Flujo de Aire
(b) Montaje en Superficie
A1
B1
C1
D1
a2
b2
c2
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
Mecnica 1
255
(10.04)
410
(16.14)
235
(9.23)
450
(17.72)
200
(7.87)
425
(16.73)
M6
Mecnica 2
350
(13.78)
625
(24.61)
298
(11.71)
675
(26.57)
250
(9.84)
650
(25.59)
M8
Mecnica 3
400
(15.75)
825
(32.48)
389
(15.31)
875
(34.45)
150
(5.91)
850
(33.46)
M8
Modelo
2
3
ESPAOL
4
2
Obs.: Para el montaje de la tapa frontal la secuencia de prieto es: 1-2-3-4-5-6. Par (torque): 2,5 Nm.
21
Puesta a Tierra
ESPAOL
Descripcin
CCS-01 Kit para blindaje de los cables de control (incluido en el producto estndar).
22
5. DATOS MECNICOS
Mecnica 1
Dimensiones en mm [in]
23
24
ESPAOL
Mecnica 2
Dimensiones en mm [in]
ESPAOL
Mecnica 3
Dimensiones en mm [in]
6. OTROS
ATENCIN!
El parmetro P0352 (Configuracin de los Ventiladores) debe estar en 1 o 4 para los
convertidores de frecuencia CFW11 XXXX X X O 54 ....
NOTAS!
- Los modelos CFW11 XXXX X X O 54 ... son suministrados con el parmetro P0352 ajustado
en 4, o sea, el ventilador del disipador es controlado con base en la temperatura de los
IGBTs/rectificador y el ventilador interno est siempre accionado.
- Si se ejecuta un reset padrn de fbrica (va P0204) y la versin de software del convertidor
de frecuencia es igual a V1.6X o inferior, el parmetro P0352 es ajustado automticamente
en 2. En ese caso, ajustar ese parmetro en 1 o en 4 nuevamente para los convertidores
de frecuencia CFW11 XXXX X X O 54 ....
ESPAOL
ATENCIN!
Del manual del usuario no se aplica las siguiente consideraciones para los convertidores
de frecuencia CFW11 XXXX X X O 54 ...:
- Montaje en frange descrita en el tem 3.1.3;
- Figura 3.5 (tem 3.1.4) del manual del usuario de los convertidores de frecuencia CFW-11
de la mecnica A...D;
- tem 3.1.4 a 3.1.7 del manual del usuario de los convertidores de frecuencia CFW-11
de la mecnica E;
- Convertidores de frecuencia de la mecnica 1 y 2: valores para Ta = 50 C de la tabla 8.2;
- Convertidores de frecuencia de la mecnica 3: valores presentados en las tablas 8.2 y 8.4;
- Especificacin del grado de proteccin del tem 8.2.
NOTA!
Los modelos CFW11 XXXX X X O 54 ... no poseen homologacin UL.
26
(*) O modelo de inversor com a opo de filtro RFI tem somente alimentao de entrada monofsica.
Obs.: 1 = alimentao monofsica, 3 = alimentao trifsica.
PORTUGUS
1 / 3
5.5
8.0
11
13
20
24
28
36
45
56
70
86
7.0
10
13
16
24
28
33.5
45
54
70
86
105
115
7.0
7.0
142
10
5.0
Corrente de sada
nominal de ND (1)
[Arms] - ver tabela 2
10
Temperatura ambiente
(ao redor do inversor) [C (F)]
-10...40 C (14 ... 104 F)
Corrente de sada
nominal de HD (1)
[Arms] - ver tabela 3
6.0
Frenagem reosttica
Opcional
(o produto
padro
no possui
frenagem)
Possui
Filtro RFI
Possui
Opcional (o produto
padro no possui filtro RFI)
Modelo
1 / 3
Mecnica
Mecnica do inversor IP20
equivalente
41
(90)
36
(79)
15
(33)
10
(22)
Filtro
supressor de RFI
No (filtro
disponvel no
produto padro)
Sim
Sim (*)
Sim
Frenagem
reosttica
Sim
No (IGBT de frenagem
disponvel no produto padro)
N de fases para
alimentao do inversor
Faixa de variao da
tenso nominal de
alimentao do inversor [V]
200...240 V
220...230 V
Parada de
segurana
Sim
Sim
Alimentao externa da
eletrnica em 24 Vcc
1. INTRODUO
Este adendo traz informaes sobre os inversores CFW11 XXXX X X O 54 ... (modelos
da linha CFW-11 com grau de proteo IP54). Somente so apresentadas as diferenas em
relao ao produto padro (com grau de proteo IP20). As demais informaes apresentadas
no manual do usurio so vlidas tambm para esses modelos.
27
Faixa de variao da
tenso nominal de
alimentao do inversor [V]
380...480 V
Modelo
Mecnica
5.0
7.0
24
142
105
88
70.5
58.5
45
38
115
88
73
61
47
38
33
25
19
17
31
11
13.5
13.5
10
3.6
Corrente de sada
nominal de ND (1)
[Arms] - ver tabela 2
10
Corrente de sada
nominal de HD (1)
[Arms] - ver tabela 3
3.6
Temperatura ambiente
(ao redor do inversor) [C (F)]
-10...40 C (14 ...104 F)
N de fases para
alimentao do inversor
Frenagem reosttica
Opcional
(o produto
padro
no possui
frenagem)
Possui
Filtro RFI
Possui
41
(90)
36
(79)
15
(33)
10
(22)
Filtro
supressor de RFI
No (filtro
disponvel no
produto padro)
Sim
Sim
Sim
Frenagem
reosttica
No (IGBT de frenagem
disponvel no produto padro)
Sim
Parada de
segurana
Sim
Sim
Alimentao externa da
eletrnica em 24 Vcc
28
Opcional (o produto padro no possui filtro RFI)
PORTUGUS
Tabela 1 b) - Relao de modelos da linha CFW-11 IP54 e especificaes tcnicas Modelos com alimentao 380-480 V
PORTUGUS
Modelo
Mecnica
3
Mecnica do
inversor IP20
equivalente
E
10
6.0
7.0
7.0
10
13
16
24
28
33.5
45
54
70
86
105
142
3.6
5.0
7.0
10
13.5
17
24
31
38
45
58.5
70.5
88
105
142
Corrente
de sada
nominal (1)
[Arms]
11.0
6.60
7.70
7.70
11.0
14.3
17.6
26.4
30.8
36.9
49.5
59.4
77.0
94.6
116
156
3.96
5.50
7.7
11.0
14.9
18.7
26.4
34.1
41.8
49.5
64.4
77.6
96.8
116
156
1 min
15.0
9.00
10.5
10.5
15.0
19.5
24.0
36.0
42.0
50.3
67.5
81.0
105
129
158
213
5.40
7.50
10.5
15.0
20.3
25.5
36.0
46.5
57.0
67.5
87.8
106
132
158
213
3s
Corrente de
sobrecarga (2)
[Arms]
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
2.5
5
5
5
5
5
5
5
5
5
5
5
5
5
2.5
2.5
Frequncia de
chaveamento
nominal (3)
[kHz]
3/2.2
1.5/1.1
2/1.5
2/1.5
3/2.2
4/3.0
5/3.7
7.5/5.5
10/7.5
12.5/9.2
15/11
20/15
25/18.5
30/22
40/30
50/37
2/1.5
3/2.2
4/3
6/4.5
7.5/5.5
10/7.5
15/11
20/15
25/18.5
30/22
40/30
50/37
60/45
75/55
100/75
Motor
mximo (4)
[HP/kW]
20.5
12.3/6.0 (5)
14.4/7.0 (5)
7.0
10.0
13.0
16.0
24.0
28.0
33.5
45.0
54.0
70.0
86.0
105
142
3.6
5.0
7.0
10.0
13.5
17.0
24.0
31.0
38.0
45.0
58.5
70.5
88.0
105
142
Corrente de
entrada
nominal
[Arms]
180
130
140
140
170
200
230
310
370
430
590
680
900
970
1200
1490
130
140
180
220
280
360
490
560
710
810
1050
1280
1480
1270
1680
Potncia
dissipada
[W]
Tabela 2 - Especificaes eltricas para os modelos com grau de proteo IP54 da linha CFW-11
- uso em regime de sobrecarga normal (ND)
29
30
Modelo
PORTUGUS
Mecnica
3
Mecnica do
inversor IP20
equivalente
E
10
5.0
7.0
5.5
8.0
11
13
20
24
28
36
45
56
70
86
115
3.6
5.0
5.5
10
11
13.5
19
25
33
38
47
61
73
88
115
Corrente
de sada
nominal (1)
[Arms]
15.0
7.50
10.5
8.25
12.0
16.5
19.5
30.0
36.0
42.0
54.0
67.5
84.0
105
129
172.5
5.40
7.50
8.25
15.0
16.5
20.3
28.5
37.5
49.5
57.0
70.5
91.5
110
132
173
1 min
20.0
10.0
14.0
11.0
16.0
22.0
26.0
40.0
48.0
56.0
72.0
90.0
112
140
172
230
7.20
10.0
11.0
20.0
22.0
27.0
38.0
50.0
66.0
76.0
94.0
122
146
176
230
3s
Corrente de
sobrecarga (2)
[Arms]
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5 (3)
5
5
5
5
5
5
5
5
5
5
5
5
5
2.5
2.5
Frequncia de
chaveamento
nominal (3)
[kHz]
3/2.2
1.5/1.1
2/1.5
1.5/1.1
2/1.5
3/2.2
4/3.0
6/4.5
7.5/5.5
10/7.5
12.5/9.2
15/11
20/15
25/18.5
30/22
40/30
2/1.5
3/2.2
3/2.2
6/4.5
6/4.5
7.5/5.5
10/7.5
15/11
20/15
25/18.5
30/22
40/30
50/37
60/45
75/55
Motor
mximo (4)
[HP/kW]
20.5
10.3/5.0 (5)
14.4/7.0 (5)
5.5
8.0
11.0
13.0
20.0
24.0
28.0
36.0
45.0
56.0
70.0
86.0
115
3.6
5.0
5.5
10.0
11.0
13.5
19.0
25.0
33.0
38.0
47.0
61.0
73.0
88.0
115
Corrente de
entrada
nominal
[Arms]
140
120
140
120
170
170
190
250
290
350
450
540
680
740
920
1280
110
140
140
200
220
270
360
430
590
650
800
1050
1170
1020
1290
Potncia
dissipada
[W]
Tabela 3 - Especificaes eltricas para os modelos com grau de proteo IP54 da linha CFW-11
- uso em regime de sobrecarga pesada (HD)
NOTAS!
- As notas (1) a (8) citadas nas tabelas 1, 2 e 3 so conforme item 8.1 do manual do
usurio. Note que a especificao de temperatura ambiente (ao redor do inversor) para
inversores CFW11 XXXX X X O 54 ... de -10 C (14 F) a 40 C (104 F). possvel que
esse inversor opere em ambientes com temperatura ambiente ao redor do inversor at 50 C
(122 F) se for aplicada reduo da corrente de sada de 2 % para cada C acima de 40 C
(104 F). Essa reduo da corrente de sada vlida para todas frequncias de chaveamento.
- As tabelas 1, 2 e 3 deste adendo substituem a tabela 8.1 do manual do usurio.
3. INSTALAO E CONEXO
3.1 Instalao Mecnica
3.1.1 Condies Ambientais
Condies ambientais permitidas para funcionamento:
- Temperatura: -10 C a 40 C - condies nominais (medida ao redor do inversor).
- De 40 C a 50 C - reduo da corrente de 2 % para cada grau Celsius acima de 40 C.
- Umidade relativa do ar: de 5 % a 90 % sem condensao.
- Altitude mxima: at 1000 m - condies nominais.
- De 1000 m a 4000 m - reduo da corrente de 1 % para cada 100 m acima de 1000 m de altitude.
PORTUGUS
31
a2
a2
b2
b2
a2
c2
c2
Fluxo de ar
(b) Montagem em superfcie
A1
B1
C1
D1
a2
b2
c2
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
Mec 1
255
(10.04)
410
(16.14)
235
(9.23)
450
(17.72)
200
(7.87)
425
(16.73)
M6
Mec 2
350
(13.78)
625
(24.61)
298
(11.71)
675
(26.57)
250
(9.84)
650
(25.59)
M8
Mec 3
400
(15.75)
825
(32.48)
389
(15.31)
875
(34.45)
150
(5.91)
850
(33.46)
M8
Modelo
2
3
PORTUGUS
3
4
2
Obs.: Para a montagem da tampa frontal a sequncia de aperto : 1-2-3-4-5-6. Torque: 2,5 Nm.
32
Aterramento
Figura 3 - Aterramento do produto
10960847
CCS-01
11112774
PCS1-01
Kit para blindagem dos cabos de potncia para inversores CFW-11 com
grau de proteo IP54 da mecnica 1 (padro para opo FA).
11112776
PCSC-02
11119781
10960844
PCSE-01
PORTUGUS
N material Nome do
WEG
acessrio
33
34
PORTUGUS
5. DADOS MECNICOS
Mecnica 1
Dimenses em mm [in]
PORTUGUS
Mecnica 2
Dimenses em mm [in]
35
PORTUGUS
Mecnica 3
Dimenses em mm [in]
6. OUTROS
ATENO!
O parmetro P0352 (Configurao dos Ventiladores) deve estar em 1 ou 4 para os inversores
CFW11 XXXX X X O 54 ... .
NOTAS!
- Os modelos CFW11 XXXX X X O 54 ... so fornecidos com o parmetro P0352 ajustado
em 4, ou seja, o ventilador do dissipador controlado com base na temperatura dos IGBTs/
retificador e o ventilador interno est sempre acionado.
- Se for dado um reset padro de fbrica (via P0204) e a verso de software do inversor for
igual a V1.6X ou inferior, o parmetro P0352 ajustado automaticamente em 2. Nesse caso,
ajustar esse parmetro em 1 ou 4 novamente para os inversores CFW11 XXXX X X O 54 ... .
ATENO!
Do manual do usurio no se aplica o seguinte para os inversores CFW11 XXXX X X O 54 ... :
- Montagem em flange descrita no item 3.1.3;
- Figura 3.5 (item 3.1.4) do manual do usurio dos inversores CFW-11 da mecnica A...D;
- Item 3.1.4 a 3.1.7 do manual do usurio dos inversores CFW-11 da mecnica E;
- Inversores da mecnica 1 e 2: valores para Ta = 50 C da tabela 8.2;
- Inversores da mecnica 3: valores apresentados nas tabelas 8.2 e 8.4;
- Especificao de grau de proteo do item 8.2.