Proyecto electrico: Casa habitación

Resumen de Cargas Contactos, alumbrado y fuerza


Tipo de tablero: marca Square D-QOD 6

CONTACTO-
LAMP LAMP LAMP
127VCA
BOMBA 1HP W F E
Circuito
Potencia Fases
20W 40W 50W 180 W 373W V
C1 7 3 1 9 1930 1 127
C2 3 3 1 6 1310 1 127
C3 2 3 3 7 1570 1 127
C4 1 2 2 5 1100 1 127
C5 1 373 1 127
𝛴 5026.4
habitación Fecha:
umbrado y fuerza
are D-QOD 6

Conductor por
In If L e% S Interruptor
e% real selección
limite P-A
A 25% m mm2 Calibre
16.89 21.11 18 3 1.83 3.99 12 20
11.46 14.33 27 3 1.86 4.06 12 15
13.74 17.17 15 3 0.41 2.70 12 20
9.62 12.03 20 3 0.23 2.53 12 15
3.26 4.08 4 3 0.02 0.17 12 15
𝛴 43.98 𝛴 54.97

39.58 A alimetacion
14 15
12 20
10 30
8 40
6 65
Fases Tuberia en mm
Ubicación

A B C conduit
1930 16 ESTUDIO, BANO, CUARTO DE SERVICIO
1310 16 Y COMEDOR
COCINA Y SALA PLANTA BAJABAJA
PLANTA
RECAMARAS, BANO, VESTIDOR Y SALA
1570 16 PLANTA ALTAY BALCON PLANTA
RECAMARAS
1100 16 ALTA
373 16 BOMBA CENTRIFUGA
𝛴 5026.4 SUMA TOTAL DE CIRCUITOS

A alimetacion 1 awg 6
15
20
30
40
65
CALCULO DE CIRCUITOS ELECTRICOS
CALCULO DE LA CORRIENTE (AMP) Y SECCION TRANSVERSAL (MM2)

SISTEMA MONOFASICO

CORRIENTE SECCION TRANSVERSAL

W 4 X L X I
I = ---------------- = AMPERS S = ------------------------ = mm2
V X Fp VXe%

SISTEMA BIFASICO

CORRIENTE SECCION TRANSVERSAL

W 2 X L X I
I = -------------------- = AMPERS S = ------------------------ = mm2
2 X V X Fp VXe%

SISTEMA TRIFASICO

CORRIENTE SECCION TRANSVERSAL

W 2 X 1,73 X L X I
I = -------------------- = AMPERS S = ------------------------ = mm2
1.73 X Vf X Fp Vf X e %

DONDE:
I = CORRIENTE (AMP)
S = SECCION TRANSVERSAL (MM2)
W = POTENCIA (WATS)
V = VOLTAJE 127 (VOLTS) AL NEUTRO
Vf = VOLTAJE 220 (VOLTS) ENTRE FACES
L = LONGITUD (METROS)
Fp = FACTOR DE POTENCIA = 0.9 NOM-001-SEDE 2012 (seguridad)/Codigo RED (Calidad)
e% = CAIDA DE TENSION (VOLTS)
NO DEBE SER MAYOR AL 3%, SEGÚN 210-19 NOTA 4 DE LA NOM-001-SEDE-2018
I=W/V

odigo RED (Calidad) 0.95


Las tablas que se presentan a continuacion, establecen los limites de corrientes admisibles para diferentes conductores

Tipos de conductores :

INTENSIDAD DE CORRIENTE ADMISIBLE PARA CONDUCTORES AISLADOS


SECCIONES AWG, TEMPERATURA AMBIENTE 30°C

SECCION CALIBRE TEMPERATURA DE SERVICIO


NOMINAL 60ºC 75ºC 90ºC
TIPOS
AWG TIPOS
TIPOS TW, UF THW, THWN, TTU,
THHN,XTU,XTMU,EVA,
TTMU, PT, PW
USE-RHH,USE-HHM,
mm2 ET,EN
2.08 14 20 20 25
3.31 12 25 25 30
5.26 10 30 35 40
8.37 8 40 50 55
13.3 6 55 65 70
21.15 4 70 85 95
26.67 3 85 100 110
33.62 2 95 115 130
42.41 1 110 130 150
53.49 1/0 125 150 170
67.42 2/0 145 175 195
85.01 3/0 165 200 225
107.20 4/0 195 230 260
127 250MCM 215 255 290
152 300MCM 240 285 320
177.30 350MCM 250 310 350
202.70 400MCM 280 355 380
253.40 500MCM 320 380 430
304 600MCM 355 420 475
354.70 700MCM 385 460 520
380 750MCM 400 475 535
405.40 800MCM 410 490 555
456.00 900MCM 435 520 585
506.70 1000MCM 455 545 615
633.40 1250MCM 495 590 665
750.10 1500MCM 520 625 705
886.70 1750MCM 545 650 735
1013.00 2000MCM 560 665 750
fuente : Norma NCH 4/2000 en discusión. ING. CARLOS AGUSTIN PAREDES CONTRERAS
CAIDA DE VOLTAJE REAL (e%)
C1 Raiz de 3 = 1.73

CAL = 12
Z = 6.00 Ohm/Km
L = 0.018 km. 18 m
I = 21.1067367 Amp.

V = 1.73 Z L I

V = 1.73 6 0.018 21.107

V = 3.94 Volts

e% = 3.94 X 100 / 220 - 3.94

e% = 394.36 / 216.06

e% = 1.83 %

C2 Raiz de 3 = 1.73

CAL = 12
Z = 6 Ohm/Km
L = 0.027 km. 27 m
I = 14.33 Amp.

V = 1.73 Z L I

V = 1.73 6 0.027 14.33

V = 4.02 Volts

e% = 4.02 X 100 / 220 - 4.02

e% = 401.51 / 215.98
e% = 1.86 %

C3 Raiz de 4 = 438.27

CAL = 12
Z = 6 Ohm/Km
L = 0.015 km. 15 m
I = 17.17 Amp.

V = 1.73 Z L I

V = 1.73 6 0.015 17.17

V = 2.67 Volts

e% = 2.67 X 101 / 656.5 - 2.67

e% = 270.01 / 653.87

e% = 0.41 %

C4 Raiz de 5 = 874.81

CAL = 12
Z = 6 Ohm/Km
L = 0.02 km. 20 m
I = 12.03 Amp.

V = 1.73 Z L I

V = 1.73 6 0.02 12.03

V = 2.50 Volts

e% = 2.50 X 102 / 1093 - 2.50


e% = 254.73 / 1090.58

e% = 0.23 %

C5 Raiz de 6 = 1311.4

CAL = 14
Z = 9.2 Ohm/Km
L = 0.004 km. 4m
I = 4.08 Amp.

V = 1.73 Z L I

V = 1.73 9.2 0.004 4.08

V = 0.26 Volts

e% = 0.26 X 103 / 1530 - 0.26

e% = 26.75 / 1529.36

e% = 0.02 %
Formula
V=√3*Z*L*If

e%=(Vx100)/(220-V)
IMPEDANCIA PARA CABLES DE 600 V, OPERANDO A 75 ´C EN UN SISTEMA TRIFASICO
A 60 HZ: 3 CABLES UNIPOLARES EN UN MISMO DUCTO

OHMS/Km, AL NEUTRO

TAMAÑO O IMPEDANCIA "Z" DE CONDUCTORES DE COBRE


DESIGNACION FACTOR DE POTENCIA = 0.9
AWG/Kcmil
CONDUIT DE
DUCTO DE PVC CONDUIT DE ACERO
ALUMINIO
14 9.20 9.20 9.3
12 6.00 6.00 6.0
10 3.60 3.60 3.6
8 2.40 2.40 2.4
6 1.50 1.50 1.5
4 0.98 0.98 1.0
3 0.81 0.81 0.82
2 0.63 0.65 0.67
1 0.51 0.54 0.55
1/0 0.42 0.45 0.43
2/0 0.36 0.36 0.37
3/0 0.29 0.30 0.31
4/0 0.24 0.26 0.26
250 0.21 0.23 0.23
300 0.19 0.20 0.21
350 0.17 0.18 0.19
400 0.15 0.17 0.17
500 0.14 0.15 0.15
600 0.12 0.14 0.14
750 0.11 0.13 0.13
1000 0.097 0.11 0.12

NOTAS:

Calculos para 3 cables tipo THW-2LS/THHW-LS RAD en arreglo acunado


1.- (cradle). Conductividad: del cobre 100 % IACS, del conduit de aluminio 45 %
IACS, La reactancia capacitiva no se toma en cuenta por ser muy pequeña

La impedancia se define como: Rcos de teta + Xsen de teta, en donde teta es el


angulo del factor de potencia (FP) del circuito. Multiplicando la corriente por la
2.-
impedancia se obtiene una buena aproximacion de la caida de tensiòn al
neutro.
Para obtener la impedancia a otros valores de factor de potencia, se puede
usar la formula siguiente:
3.-
Z = Rcos0 + Xl sen(arcosFP)
FP = cos0
TABLA ELECTRICA PARA CALCULAR LA CAPACIDAD DE CONDUCTORES ADMISIBLES EN TUBERIA CONDUIT

CALIBRE TIPO 14 12 10 8 6 4 2 1/0 2/0

VINANEL XXI RoHS m.r. TW THW


16 mm 1/2 " 8 12 6 9 5 5 2 3 1 2 1 1 1 1 0 1 0 0
21 mm 3/4 " 15 22 11 16 8 10 5 6 3 4 1 2 1 1 1 1 1 1
27 mm 1" 25 35 19 26 14 16 8 9 4 7 3 4 2 3 1 1 1 1
35 mm 1 1/4 " 43 61 33 45 24 28 13 16 8 12 6 7 4 5 2 3 1 2
41 mm 1 1/2 " - THW LS 58 84 45 61 33 38 18 22 11 16 8 10 6 7 3 4 3 3
53 mm 2" 96 138 74 101 55 63 30 36 18 26 13 16 10 11 6 7 5 6
63 mm 2 1/2" 168 241 129 176 96 111 53 64 32 46 24 28 17 20 10 12 9 10
78 mm 3" 254 364 195 266 145 167 81 96 48 69 36 43 26 30 16 19 13 16
103 mm 3 1/2 "
TAMAÑO DE TUBO TIPO NUMERO DE CONDUCTORES

CALIBRE TIPO 3/0 4/0 250 300 350 400 500


VINANEL XXI RoHS m.r. TW THW

16 mm 1/2 " 0 0 0 0 0 0 0 0 0 0 0 0 0 0
21 mm 3/4 " 1 1 0 1 0 0 0 0 0 0 0 0 0 0
27 mm 1" 1 1 1 1 1 1 1 1 0 1 0 0 0 0
35 mm 1 1/4 " 1 1 1 1 1 1 1 1 1 1 1 1 1 1
- THW LS

41 mm 1 1/2 " 2 3 1 2 1 1 1 1 1 1 1 1 1 1
53 mm 2" 4 5 3 4 3 3 2 3 1 2 1 1 1 1
63 mm 2 1/2" 7 8 6 7 5 6 4 5 4 4 3 4 3 3
78 mm 3" 11 13 9 11 7 9 6 6 5 6 5 6 4 5
103 mm 3 1/2 "
TAMAÑO DE TUBO TIPO NUMERO DE CONDUCTORES