Interface list

Lista de señales

1 x JMS 312 GS-N.L


CUVILAG JMS312 D805 MTY
J AI82

© INNIO Jenbacher GmbH & Co OG


Achenseestr. 1-3
A-6200 Jenbach (Austria)

Index:
Revision reserved!
Index:
Se reserva el derecho de modificación
Interface list | LISTA DE SEÑALES

The target recipients of this document are:

Customers, distribution partners, service partners, commissioning partners, subsidiaries/branches,


Jenbach location

INNIO* proprietary information: CONFIDENTIAL


The information contained in this document is the proprietary information of INNIO Jenbacher GmbH
& Co OG and its subsidiaries and is disclosed in confidence. It is the property of INNIO* and shall not be
used, disclosed to others or reproduced without express written consent. This includes but is not limited
to use for the creation, manufacture, development or derivation of any repairs, modifications, spare
parts, designs or configuration changes, or for obtaining government or regulatory approval to do so.
If consent is given for reproduction in whole or in part, this notice and the notice set forth on each page
of this document shall appear in any such reproduction in whole or in part.

Los destinatarios de este documento son:

Clientes, distribuidores autorizados, servicios técnicos autorizados, servicios de puesta en marcha


autorizados, filiales, Jenbach HQ

Información propiedad de INNIO*: CONFIDENCIAL

La información que recoge este documento es información protegida tanto de INNIO Jenbacher
GmbH & Co OG como de sus filiales y es confidencial. Es propiedad de INNIO* y no se permite su
utilización, distribución a terceros o reproducción sin la previa autorización por escrito. Esta prohibición
incluye también, aunque no exclusivamente, el uso de la información para elaborar, confeccionar,
desarrollar o deducir reparaciones, modificaciones, piezas de repuesto, diseños o modificaciones de
configuración o su presentación ante autoridades nacionales. Cuando se haya autorizado la
reproducción total o parcial, se deberán anotar tanto esta advertencia como la advertencia que sigue
en todas las páginas del documento de manera total o parcial.

*Indicates a trademark
*Señala una marca registrada
KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 2 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

I ENGINE CONTROL AND INTERFACES PER ENGINE_________________________ 6


I MODULO DE CONTROL INTERFACES 1 x POR MOTOR ______________________ 6
IV REMOTE DATA TRANSMISSION WITH myPlant ________________________ 20
IV TRANSMISIÓN DE DATOS CON myPlant _____________________________ 20
V DATA TRANSMISSION TO THE CUSTOMER (DIA.NE XT4) ___________________ 22
V TRANSMISSION DE DATOS AL SISTEME DEL CLIENTE (DIA.NE XT4) _____________ 22
MODBUS-TCPIP 23
MODBUS-TCPIP 24
SEND DATA ITEMS FOR MODULE 38
PUNTOS DATOS DE ENVIO MODUL 38
RECEIVE DATA ITEMS FOR MODULE 56
PUNTOS DATOS DE RECEPCIÓN MODUL 56

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 3 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

- GENERAL:
ALL CONTROL CABLES MUST BE FLEXIBLE.
POWER CABLES MUST BE WITH MULTIPLE-WIRE.
THE CONDUCTORS SHALL BE OF COPPER.

- DIGITAL SIGNAL
1 NO contact = 1 normally open contact
1 NC contact = 1 normally closed contact
1 CO contact = 1 changeover contact
ALL REQUIRED NO AND NC CONTACTS ARE POTENTIALFREE (FLOATING) CONNECTED TO TERMINALS.

Maximum contact rating for:


Standard relays (Finder series 55.33): Part number 1244516
3 CO contacts, breaking capacity
DC1: 30 V 6 A / 110 V 0,1 A,
AC1 250 V 6 A
Interface relays (Finder series 38): Part number 363865
1 CO contact, DC 24 V 50 mA (PLC), breaking capacity
DC1: 30 V 4 A / 110 V 0,1 A,
AC1 250 V 4 A
Power relays (Finder series 62.31): Part number 1233756
1 NO contact, breaking capacity
DC1: 30 V 16 A / 125 V 16 A / 220 V 12 A / 300 V 6 A,
DC13: 30 V 16 A / 125 V 5 A / 220 V 3 A / 300 V 1 A,
AC1 250 V 16 A
============
Option (Finder series 55.34): Part number 1244517
4 CO contacts, breaking capacity
DC1: 30 V 4 A / 110 V 0,1 A,
AC1 250 V 4 A
Option (Finder series 48.P5): Part number 1246274
2 CO contacts, breaking capacity
DC1: 30 V 6 A / 110 V 0,1 A,
AC1 250 V 6 A

PULSE INPUT: PULSE TIME > 1 sec., PAUSE TIME > 1 sec.

- ANALOG SIGNAL
ANALOG INPUT CUSTOMERS TRANSDUCERS POTENTIALFREE (FLOATING)!
ANALOG OUTPUT CUSTOMERS TRANSDUCERS POTENTIALFREE!
MAXIMUM APPARENT OHMIC RESISTANCE 100 OHMS BY mA-SIGNALS (0/4-20 mA).
ANALOG SIGNAL SCREENED CABLES, CABLE SCREEN TO GROUND ON BOTH SIDES!

- SIGNALS FROM OUTSIDE OF THE BUILDING RESPECTIVELY WITH CONTAINERIZED MODULES IF THE SIGNAL CABLES END OUTSIDE
OF THE COMMON GROUNDING SYSTEM:
ON THE BUILDING ENTRANCE | CONTAINER ENTRANCE (AT THE JENBACHER* SIDE AS WELL AS ON THE OPPOSITE CUSTOMER SIDE) ON
THE CUSTOMERS SIDE PROTECTION ELEMENTS AGAINST OVERVOLTAGE SHALL BE PROVIDED BY THE CUSTOMER. FOR ANALOG SIGNALS
USE DOUBLE SCREENED CABLES, FOR DIGITAL SIGNALS USE FOR MINIMUM SINGLE SCREENED CABLES.

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 4 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

GENERAL:
TODOS LOS CABLES DE CONTROL DEBEN SER DE HILOS FINOS.
CABLES DE POTENCIA DEBEN SER POR LO MENOS DE HILOS MULTIPLES.
LOS CONDUCTORES DEBEN SER DE COBRE.

- Señales digitale
1 contacto NA = 1 contacto normalmente abierto
1 contacto NC = 1 contacto normalmente cerrado
1 contacto I = 1 contacto inversor
TODAS LAS SALIDAS NA Y NC SON CONTACTOS LIBRES DE POTENCIAL.

CORRIENTE MÁXIMA PARA LOS CONTACTOS PARA:


Relés estándar (Finder serie 55.33): Número de referencia 1244516
3 contactos I, capacidad de ruptura en
DC1: 30 V 6 A / 110 V 0,1 A,
AC1 250 V 6 A
Relés de interface (Finder serie 38): Número de referencia 363865
1 contacto I, DC 24 V 50 mA (PLC), capacidad de ruptura en
DC1: 30 V 4 A / 110 V 0,1 A,
AC1 250 V 4 A
Relé de potencia (Finder serie 62.31): Número de referencia 1233756
1 contacto NA, capacidad de ruptura en
DC1: 30 V 16 A / 125 V 16 A / 220 V 12 A / 300 V 6 A,
DC13: 30 V 16 A / 125 V 5 A / 220 V 3 A / 300 V 1 A,
AC1 250 V 16 A
============
Opción (Finder serie 55.34): Número de referencia 1244517
4 contactos I, capacidad de ruptura en
DC1: 30 V 4 A / 110 V 0,1 A,
AC1 250 V 4 A
Opción (Finder serie 48.P5): Número de referencia 1246274
2 contactos I, capacidad de ruptura en
DC1: 30 V 6 A / 110 V 0,1 A,
AC1 250 V 6 A

ENTRADAS CON PULSO: DURCIÓN DEL PULSO > 1 seg., PAUSA > 1 seg.

- SEÑALES ANALÓGICA
ENTRADAS ANALÓGICA TRANSDUCTORES DEL CLIENTE; LIBRES DE POTENCIAL, (FLOTANTES)
SALIDAS ANALÓGICA TRANSDUCTORES DEL CLIENTE, LIBRES DE POTENCIAL
RESISTENCIA ÓHMICA APARENTE, MAX. 100 OHM PARA SEÑALES (0/4-20 mA).
SEÑAL ANALÓGICA CABLES APANTALLADOS, APANTALLAMIENTO CONECTADO A TIERRA EN AMBOS LADOS.

- SEÑALES DESDE FUERA DEL EDIFICIO O CUANDO LOS CABLES DE SEÑALIZACIÓN EN CASO DE GRUPOS ELECTRÓGENOS EN
CONTENEDORES TERMINAN FUERA DE LA INSTALACIÓN COMÚN DE PUESTA A TIERRA:
A LA ENTRADA DEBE ENTRADA AL CONTENEDOR (TANTO DEL LADO DE Jenbacher* COMO TAMBIÉN DEL LADO DE LA CLIENTELA)
HABER ELEMENTOS DE PROTECCIÓN CONTRA SOBREVOLTA Jenbacher* POR PARTE DEL CLIENTE.
PARA SEÑALES ANALÓGICAS USE CABLE APANTALLADO, PARA SEÑALES DIGITALES UTILIZE MÍNIMO UN CABLE SIMPLE APANTALADO.

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 5 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

I ENGINE CONTROL AND INTERFACES PER ENGINE


I MODULO DE CONTROL INTERFACES 1 x POR MOTOR

1 Power connection generator Jenbacher* Customer 3/N/PE AC 480/277 V, +/-10 %, 60 Hz ---


Potencia salida alternador Cliente 633 kW 762 A at cos φ = 1
786 kVA 945 A at cos φ = 0,8

2 Service grounding generator Customer Jenbacher* 1


Tierra de funzionamiento del Cliente
generador
3 Equipotential bonding Customer Jenbacher* Cross-sectional area according to 1
Conexión equipotencial Cliente IEC 60364-5-54 and national
standards.
minimum cross-sectional area
16 qmm Cu. connection at the engine
control panel
Sección conforme IEC 60364-5-54 e
normas nacional.
sección mínimo
16 qmm Cu. al armario del módulo de
control

4 Equipotential bonding Customer Jenbacher* Cross-sectional area according to 1


Conexión equipotencial Cliente IEC 60364-5-54 and national
standards. minimum cross-sectional
area
50 qmm Cu. connection at the
genset
Sección conforme IEC 60364-5-54 e
normas nacional.
sección mínimo
50 qmm Cu conexión a la carcasa
del generador

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 6 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

6 Voltage supply module control Customer Jenbacher* TN system, with N conductor 5


panel Cliente 3/N/PE AC 400/230 V, 50 Hz,
Alimentación tensión cuadro max. 5x95 qmm Cu
de control N, PE: max. 95 qmm Cu
fuses:
operation class, rated
current /
rated voltage / rated
breaking capacity / standards
gG 160 A / AC 500 V / 100 kA / IEC
60269
Sistema TN, con conductor N
3/N/PE AC 400/230 V, 50 Hz,
max. 5x95 qmm Cu
N, PE: max. 95 qmm Cu
fusibles:
clase de operacion /
corriente
asignada / tensión asignada /
poder
de corte asignada / normas
gG 160 A / AC 500 V / 100 kA / IEC
60269

6 Customer Jenbacher* Surge protection devices by the ---


Cliente customer, type 2 EN 61643-11 / class II
IEC 61643-1, up max. 2,5 kV.
Pararrayos por el cliente, tipo 2
EN 61643-11 / clase II IEC 61643-1, up
max. 2,5 kV.

7
-
9
10 CT current for differential Customer Jenbacher* 3x 1500/5 A, 15 VA, 10P10 7
protection Cliente
Corriente de transformador
para protección diferencial
11 Mains power consumption ---
control system
Regulación de consumo de
corriente
11.1

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 7 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

11.4 Mains power consumption Customer Jenbacher* 1 NO contact closed = activation 2


control system activation Cliente 1 contacto NA cerrado = activación
Activación de la regulación de
consumo de corriente
11.5

11.6 Actual value mains power Customer Jenbacher* 0-20 mA = - 2000 kW - + 2000 kW 2
consumption Cliente (-… IMPORT/+…EXPORT)
Valore actual consumo de 0-20 mA = - 2000 kW - + 2000 kW
potencia de la red (-… IMPORT/+…EXPORT)

12

13 Measurement: Generator Customer Jenbacher* 3x 480 V / √3 : 120 V / √3 5


voltage power logger and Cliente 50 VA, Cl. 0.5
synchronization converter: 1 pole isolated
Medición: Medición de 3x 480 V / √3 : 120 V / √3
potencia y sincronización de la 50 VA, Cl. 0,5
tensión del generador Transformador: unipolar aislado

14 Status: Ready for Jenbacher* Customer 1 NO contact closed = ready 3


automatic demand Cliente 1 contacto NA cerrado = preparado
Estado: Preparado para
arranque automático
15 Demand module Customer Jenbacher* 1 NO contact closed = demand 2
Arranque remoto del motor Cliente 1 contacto NA cerrado = orden de
arrancar

16 Release Black-Out-Start Customer Jenbacher* 1 NO contact closed = release 2


Liberación arranque Cliente 1 contacto NA cerrado = desbloqueo
autónomo
16.1 Release island operation Customer Jenbacher* 1 NO contact closed = release 2
Liberación funcionamiento en Cliente 1 contacto NA cerrado = desbloqueo
isla
17 Status: Module is demanded Jenbacher* Customer 1 NO contact closed = demanded 3
Estado: Módulo orden de Cliente
arranque recibida 1 contacto NA cerrado = orden de
arrancar

18 Demand for auxiliaries Jenbacher* Customer 2 NO contact closed = demand 4


Orden de arranque de Cliente 2 contacto NA cerrado = arrancar
auxiliares auxiliares

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 8 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

19 Status: Auxiliaries enable Customer Jenbacher* 1 NO contact closed = operation 2


Estado: Liberación de Cliente 1 CNA contacto cerrado = en
operaciones auxiliares funcionamiento

20 Status: engine on Jenbacher* Customer 1 NO contact closed = operation 3


Estado: Funcionamiento del Cliente 1 contacto NA cerrado = en
motor funcionamiento

21 Status: General alarm shut Jenbacher* Customer 1 NO contact open = trip 3


down Cliente 1 contacto NA abierto = parada
Estado: Fallo general detenido
22 Status: General alarm warning Jenbacher* Customer 1 NO contact open = warning 3
Estado: Fallo general atención Cliente 1 contacto NA abierto = advertencia

23 Status Message: Jenbacher* Customer 1 NO contact open = message 2


Emergency stop per engine Cliente emergency stop per engine
Estado: Parada de emergencia 1 contacto NA abierto = mensaje
módulo parada de emergencia por motor

24
-
26
27.0 Command: Utility operator Transmissio Jenbacher* 1 NO contact closed = blockage 2
module blocked n system 1 contacto NA cerrado = bloqueo
Orden: Grupo de bloqueo operator /
operador de red Distribution
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 9 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

27.1 Command: Power limitation by Transmissio Jenbacher* 1 NO contact closed = Max. xx% PN 2
utility operator stage 1 n system xx = Parameter value (50-100 % PN)
Orden: Limitación de potencia operator / 1 contacto NA cerrado = máx. xx % PN
operador de red etapa 1 Distribution xx = valor de parámetro (50-100 % PN)
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución
27.2 Command: Power limitation by Transmissio Jenbacher* 1 NO contact closed = Max. xx% PN 2
utility operator stage 2 n system xx = Parameter value (50-100 % PN)
Orden: Limitación de potencia operator / 1 contacto NA cerrado = máx. xx % PN
operador de red etapa 2 Distribution xx = valor de parámetro (50-100 % PN)
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución
27.3 Command: Power limitation by Transmissio Jenbacher* 1 NO contact closed = Max. xx% PN 2
utility operator stage 3 n system xx = Parameter value (50-100 % PN)
Orden: Limitación de potencia operator / 1 contacto NA cerrado = máx. xx % PN
operador de red etapa 3 Distribution xx = valor de parámetro (50-100 % PN)
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 10 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

27.4 Command: Power limitation by Transmissio Jenbacher* 1 NO contact closed = Max. xx% PN 2
utility operator stage 4 n system xx = Parameter value (50-100 % PN)
Orden: Limitación de potencia operator / 1 contacto NA cerrado = máx. xx % PN
operador de red etapa 4 Distribution xx = valor de parámetro (50-100 % PN)
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución
27.5 Command: Power limitation by Transmissio Jenbacher* 1 NO contact closed = Max. xx% PN 2
utility operator stage 5 n system xx = Parameter value (50-100 % PN)
Orden: Limitación de potencia operator / 1 contacto NA cerrado = máx. xx % PN
operador de red etapa 5 Distribution xx = valor de parámetro (50-100 % PN)
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución
27.11 Status: Power limitation by Jenbacher* Transmissio 1 NO contact closed = Stage 1 power 3
utility operator stage 1 n system limitation message
Estado: Limitación de potencia operator / 1 contacto NA cerrado = mensaje de
operador de red etapa 1 Distribution limitación de potencia nivel 1
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 11 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

27.12 Status: Power limitation by Jenbacher* Transmissio 1 NO contact closed = Stage 2 power 3
utility operator stage 2 n system limitation message
Estado: Limitación de potencia operator / 1 contacto NA cerrado = mensaje de
operador de red etapa 2 Distribution limitación de potencia nivel 2
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución
27.13 Status: Power limitation by Jenbacher* Transmissio 1 NO contact closed = Stage 3 power 3
utility operator stage 3 n system limitation message
Estado: Limitación de potencia operator / 1 contacto NA cerrado = mensaje de
operador de red etapa 3 Distribution limitación de potencia nivel 3
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución
27.14 Status: Power limitation by Jenbacher* Transmissio 1 NO contact closed = Stage 4 power 3
utility operator stage 4 n system limitation message
Estado: Limitación de potencia operator / 1 contacto NA cerrado = mensaje de
operador de red etapa 4 Distribution limitación de potencia nivel 4
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 12 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

27.15 Status: Power limitation by Jenbacher* Transmissio 1 NO contact closed = Stage 5 power 3
utility operator stage 5 n system limitation message
Estado: Limitación de potencia operator / 1 contacto NA cerrado = mensaje de
operador de red etapa 5 Distribution limitación de potencia nivel 5
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución
27.16 Status: Utility operator module Jenbacher* Transmissio 1 NO contact open = blockage 3
blocked n system 1 contacto NA abierto = bloqueo
Estado: Grupo de bloqueo operator /
operador de red Distribution
system
operator
Usuario de
sistemas de
transmisión
/ Usuario de
sistemas de
distribución
28 Set point for generator power Customer Jenbacher* 0(4)-20 mA = 50 - 100% PN 2
Consigna para la potencia Cliente Burden: max. 500 Ohm
generada Signal: is floating
0(4)-20 mA = 50-100% PN
Carga: max 500 Ohm
Señal: libre potencial

29 Signal generator power Jenbacher* Customer 0-20 mA = -175kW - +700kW 2


Señal de medición de la Cliente
potencia activa del generador
30 Signal generator energy Jenbacher* Customer 1 Imp. = 100 kWh 3
Señal potencia del generador Cliente 1 Imp. = 100 kWh

31 Reactive power control at the ---


generator terminals:
Regulación de potencia
reactiva en los bornes del
generador:

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 13 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

31.1
-
31.3

31.4 Setpoint power factor Utility Jenbacher* 0(4)-20 mA = 2


Valor nominal cosφ Cliente cosφ +0,8 [overexcited] … -0,95
[underexcited]
Burden: max. 500 Ohm
Signal: is floating
0(4)-20 mA =
cosφ +0,8 [sobreexcitada] … -0,95
[subexcitado]
Carga: max 500 Ohm
Señal: libre potencial

39 Command: emergency stop Customer Jenbacher* 1 NC contact open = emergency stop 2


per engine Cliente per engine
Comando: parada de emergency stop device according to
emergencia por motor ISO 13850 and IEC/EN 60947-5-5
(TA 1100-0110)
1 contacto NC abierto = parada de
emergencia por motor
dispositivo de parada de
emergencia conforme
ISO 13850 e IEC/ EN 60947-5-5
(TA 1100-0110)

40.1 Gas pre-alarm Customer Jenbacher* 1 NO contact open = pre-alarm 2


Prealarma gas Cliente (TA 1100-0110)
1 contacto NA abierto = alarma
(TA 1100-0110)

40.2 Gas alarm Customer Jenbacher* 1 NO contact open = alarm 2


Alarma gas Cliente (TA 1100-0110)
1 contacto NA abierto = alarma
(TA 1100-0110)

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 14 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

41 Fire alarm Customer Jenbacher* 1 NO contact open = alarm 2


Alarma fuego Cliente (TA 1100-0110)
1 contacto NA abierto = alarma
(TA 1100-0110)

42
-
49
50 High temperature circuit ---
Circuito de alta temperatura

50.1 Status: Heating water flow Customer Jenbacher* 1 NO contact switched over = flow is 2
present Cliente ok
Estado: Existe flujo de agua de 1 contacto NA conmutado= caudal
calefacción ok

50.2 Status: Heating water pressure Customer Jenbacher* 1 CO contact 3


max. Cliente 1 contacto I
Estado: Presíon máxima del
agua caliente
50.3 Status: Heating water Customer Jenbacher* 1 CO contact 3
temperature max. Cliente 1 contacto I
Estado: Temperatura máxima
agua caliente
50.4

52 Activation 3-way valve return Jenbacher* Customer Supply: AC 24 V 3


water temperature Cliente Control signal: DC 0-10 V
Control válvula de tres vias Alimentacion: AC 24 V
para el agua Controle la señal: DC 0-10 V

53 Return water temperature Customer Jenbacher* 3-wire PT100 3


Temperatura de salida del Cliente 3-conductores PT100
agua
54 Low temperature circuit
Circuito de baja temperatura

54.1 Charge cooling water pressure Customer Jenbacher* 1 NO contact open = low 2
low Cliente 1 contacto NA abierto = presión
Presión mínima de agua de mínima.
carga

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 15 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

54.2 Control: Low-temperature Jenbacher* Customer 3/PE AC 480 V, 60 Hz, 6,2. A 4


circuit, pump 1 Cliente
Control: Bomba 1 circuito de
baja temperatura
55 Emergency cooling circuit
Circuito de refrigeración de
emergencia
55.6 Control: Cooling fan 1 Jenbacher* Customer 3/PE AC 480 V, 60 Hz, 4. A 4
Control: Ventilador de Cliente
refrigeración 1
55.7 Control: Cooling fan 1 Jenbacher* Customer 3/PE AC 480 V, 60 Hz, 4. A 4
Control: Ventilador de Cliente
refrigeración 1
56 Room ventilation
Ventilación de la sala de
máquinas
56.0 Room temperature: max Customer Jenbacher* 1 NO contact open = room 2
Temperatura ambiente máx. Cliente temperature max.
1 contacto NA abierto = temperatura
ambiente máx.

56.5 Status: Engine air inlet Customer Jenbacher* 1 NO contact open = failure 2
ventilator 1 failure Cliente 1 contacto NA abierto = avería
Estado: Motor ventilador de
impulsión 1 averiado
56.14 Supply: Air inlet ventilator 1 Jenbacher* Customer 3/PE AC 480 V, 4 kW 4
Alimentacion: Ventilador de Cliente
aire de suministro 1

56.18 Failure: Engine room Customer Jenbacher* 1 NO contact closed = Flow present 2
ventilation, air flow OK Cliente Signal must be realised according to
Fallo: Ventilación de la sala de TA 1100-0110, section 11.1!
máquinas flujo de aire OK 1 contacto NA cerrado = flujo
disponible
La señal se debe diseñar de acuerdo
con TA 1100-0110, cap.11.1.

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 16 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

57
-
74

75 Bus-bar voltage Customer Jenbacher* 3x 480 V / √3 : 120 V / √3 5


Tensión de la barra colectora Cliente 50 VA, Cl. 0.5
converter: 1 pole isolated
3x 480 V / √3 : 120 V / √3
50 VA, Cl. 0,5
Transformador: unipolar aislado

76 Opening failure generator Jenbacher* Customer 1 NO contact closed = 2


circuit breaker Cliente opening failure
Fallo apertura del disyuntor del 1 contacto NA cerrado = fallo
generador apertura

77

78 Command: generator C.B. Jenbacher* Customer 1 NO contact closed = c.b. closed 4


ON|OFF Cliente 1 NO contact closed = c.b. open
Comando : Disyuntor del 1 contacto NA cerrado = cerrar
generador abrir|cerrar interruptor
1 contacto NA cerrado = abrir
interruptor

79 Command undervoltage coil Jenbacher* Customer 1 NO contact closed = energized 2


generator C.B. Cliente 1 contacto NA cerrado = activado
Mando: disparador disyuntor
generador activado por
mínima tensión
80 Status: Generator C.B. closed Customer Jenbacher* 1 NO contact closed = c.b. closed 2
Estado: Interruptor del Cliente 1 contacto NA cerrado = cerrado
generador cerrado
81 Status: Generator C.B. open Customer Jenbacher* 1 NO contact closed = C.B. open 2
Estado: Interruptor del Cliente 1 contacto NA cerrado = abierto
generador abierto
82 Status: Generator C.B. ready for Customer Jenbacher* 1 NO contact closed = ready 2
closure Cliente 1 contacto NA cerrado = preparado
Estado: Disyuntor del
generador preparado para
cerrado

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 17 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

83 Status: Generator C.B. is racked Customer Jenbacher* 1 NO contact closed = racked in 2


in Cliente 1 contacto NA cerrado = encajado
Estado: Disyuntor del
generador encajado
84 Status: Generator overload / Customer Jenbacher* 1 NO contact open = overload / short 2
short circuit Cliente circuit
Estado: Generador sobrecarga 1 contacto NA abierto = sobrecarga /
/ cortocircuito cortocircuito

84.1 Status: Generator protection Customer Jenbacher* 1 NO contact open = protection trip 2
trip Cliente 1 contacto NA abierto = protección
Estado: Protección del activada
generador activada
85 Status: Grid fault Jenbacher* Customer 1 NO contact open = fault 2
Estado: Fallo red Cliente 1 contacto NA abierto = fallo red

86 Mains voltage Customer Jenbacher* 3x 480 V / √3 : 120 V / √3 5


Tensión de red Cliente 50 VA, Cl. 0.5
converter: 1 pole isolated
3x 480 V / √3 : 120 V / √3
50 VA, Cl. 0,5
Transformador: unipolar aislado

87

88.1 Ground current Customer Jenbacher* x/5 A, 1.2 VA, 1FS10 2


Corriente a tierra Cliente

89 Command mains C.B. ON|OFF Jenbacher* Customer 1 NO contact closed = c.b. closed 4
Comando : Disyuntor de la red Cliente 1 NO contact closed = c.b. open
abrir|cerrar 1 contacto NA cerrado = interruptor
cerrado
1 contacto NA cerrado = int abierto

90 Mains circuit breaker control Customer Jenbacher* 1 NO contact closed = pos. remote 2
automatic Cliente 1 contacto NA cerrado = pos. remoto
Control interruptor de red
automatic
91 Status: Mains C.B. closed Customer Jenbacher* 1 NO contact closed = c.b. closed 2
Estado: Disyuntor de la red Cliente 1 contacto NA cerrado = conectado
cerrado

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 18 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

92 Status: Mains C.B. open Customer Jenbacher* 1 NO contact closed = C.B. open 2
Estado: Disyuntor de la red Cliente 1 contacto NA cerrado =
abierto desconectado

93 Status: Mains C.B. ready for Customer Jenbacher* 1 NO contact closed = ready 2
switch on Cliente 1 contacto NA cerrado = preparado
Estado: Disyuntor de la red para conectar
preparado para conectar
94 Status: Mains C.B. is racked in Customer Jenbacher* 1 NO contact closed = racked in 2
Estado: Disyuntor de red Cliente 1 contacto NA cerrado=encajado
encajado
95 Status: Mains C.B. overload / Customer Jenbacher* 1 NO contact open = overload / short 2
short circuit Cliente circuit
Estado: Sobrecarga / 1 contacto NA abierto = sobrecarga /
cortocircuito del disyuntor de cortocircuito
red
96 Command: shed load Jenbacher* Customer 1 NO contact closed = shed load 2
Quitar cargas Cliente 1 contacto NA cerrado=qitar cargas

97
-
108
109 Grid ok Customer Jenbacher* 1 NO contact closed = grid ok 2
Red ok Cliente 1 contacto NA cerrado = red ok

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 19 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

IV REMOTE DATA TRANSMISSION WITH myPlant


IV TRANSMISIÓN DE DATOS CON myPlant

[x] see: DIA.NE WIN User Manual → 5. Network structure and interfaces
[x] véase: DIA.NE WIN Manual de usuario → 5. Estrucura de la res e interfaces

200
-
202
203 Ethernet connection to Jenbacher* Customer Ethernet 100 Mbit, twisted pair, RJ45
customer network for DIA.NE* Cliente Ethernet 100 Mbit, Twisted Pair, RJ45
XT4 client access and/or OPC
Conexión Ethernet a la red del
cliente para el acceso DIA.NE*
XT4 Client y/o OPC
204 Ethernet connection to Internet Customer Jenbacher* Ethernet 100 Mbit, twisted pair, RJ45
for myPlant* connectivity Cliente (TA 2300-0008)
Conexión Ethernet a Internet Ethernet 100 Mbit, Twisted Pair, RJ45
para conectividad myPlant* (TA 2300-0008)

205
-
399

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 20 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

WIRES

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 21 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

V DATA TRANSMISSION TO THE CUSTOMER (DIA.NE XT4)


V TRANSMISSION DE DATOS AL SISTEME DEL CLIENTE (DIA.NE XT4)

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 22 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

MODBUS-TCPIP
in accordance with IEC 61158

See "XT4 MODBUS-TCPIP bus diagram circuit diagram " J AI82 +U

Jenbacher* control system operates as a slave.


The data transfer by the on-site master must take place cyclically.
Communications error monitoring in on-site master.
Register addresses : The corresponding register addresses in the on-site computer (master) can
be the given register address +1, depending on the target system.

MODBUS TCP network parameters


Baud rate: 100 Mbit/s max.
Ethernet port: 502
The following IP address ranges must not be used for Modbus TCP communications:
192.168.137.0 / 255.255.255.0
192.168.123.0 / 255.255.255.0
192.168.0.0 / 255.255.0.0
Arrangement of the send/receive data points: see below
The data point numbers listed refer to the interface numbers.
Data point numbers > 1000: see "Message no." in the "Error message list"
Data bit = 1 if a failure or operational message is present
Measured values: Data size = 2 bytes (= 1 word)
Data format: see the remarks on the interface number

Caution
The data for the MODBUS TCP must not be used for time-critical functions and not for safety
functions!
IEC 61158 must be observed for hardware application and software creation!

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 23 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

MODBUS-TCPIP
conforme a la norma IEC 61158

Ver «Esquema de conexiones; esquema de bus XT4 MODBUS-TCPIP» J +U

El control Jenbacher* trabaja como esclavo


La transferencia de datos a través del maestro del cliente debe efectuarse cíclicamente.
Supervisión de errores de comunicación en el maestro del cliente.
Direcciones de registro
La dirección de registro correspondiente en el ordenador del cliente (maestro) puede, en función
del sistema de destino, ser la dirección de registro +1 indicada.

Parámetros de red MODBUS TCP


Tasa de baudios: máx. 100 MBit/s
Puerto Ethernet: 502
Los siguientes rangos de direcciones IP no pueden utilizarse para la comunicación Modbus TPC:
192.168.137.0 / 255.255.255.0
192.168.123.0 / 255.255.255.0
192.168.0.0 / 255.255.0.0
Disposición de los puntos de datos de envío/recepción: ver abajo
Los números de los puntos de datos facilitados se refieren a los números de interfaz.
Para los números de los puntos de datos >1000, ver «N.º de mensaje» en la «Lista de mensajes de
avería».
Bit de datos = 1 en caso de avería presente o mensaje de funcionamiento presente
Valores medidos: Tamaño de los datos = 2 bytes (= 1 palabra)
Formato de los datos: ver la observación acerca del número de interfaces

Atención
Los datos que se utilicen a través del MODBUS TCP no deben emplearse para funciones urgentes
ni para funciones de seguridad.
Para la aplicación en hardware y la creación de software debe tenerse en cuenta la norma IEC
61158.

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 24 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

SSLno DESIGNATION FROM TO COMMENT


SSLno DESIGNACIÓN DE A COMENTARIO

INDEX
400 Hardwareinterface for MODBUS Jenbacher* Customer's An equipotential bonding must be
TCP: control control produced between the Jenbacher* module
RJ45 Ethernet Port in the cubicle (MASTER) control and the customer's computer by
Jenbacher* control cubicle. (SLAVE) Ordenador the customer!
Interface hardware de conexión Control de del cliente Un potencial de equilibrio se debe producir
MODBUS TCP: Jenbacher* (MAESTRO) entre el control de Jenbacher* y el
RJ45 Ethernet Port en el control (ESCLAVO) ordenador del cliente, por el cliente!
de Jenbacher*.

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 25 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

SEND DATA Register-addresses R000 – R031 (decimal)


ENVIO DE DATOS Dirección de los registros R000 – R031 (decimal)

SOURCE: Jenbacher* module control 1-x = SLAVE 11 (decimal) .... 1x


Fuente: Módulo control 1-x de Jenbacher* = Esclavo 11 (decimal) .... 1x

TARGET SYSTEM: CUSTOMER'S COMPUTER (MASTER)


Destino: Ordenador del CLIENTE (MASTER)

FUNCTION CODE: 03 READ HOLDING REGISTERS (4xxxx references)


Código función: 03 LEER LOS REGISTROS INTERNES (4xxxx referencias)
MSB LSB
R000 1016 1015 1014 1013 1012 1011 1010 1009 1008 1007 1006 1005 1004 1003 1002 1001
R001 1032 1031 1030 1029 1028 1027 1026 1025 1024 1023 1022 1021 1020 1019 1018 1017
R002 1048 1047 1046 1045 1044 1043 1042 1041 1040 1039 1038 1037 1036 1035 1034 1033
R003 1064 1063 1062 1061 1060 1059 1058 1057 1056 1055 1054 1053 1052 1051 1050 1049
R004 1080 1079 1078 1077 1076 1075 1074 1073 1072 1071 1070 1069 1068 1067 1066 1065
R005 1096 1095 1094 1093 1092 1091 1090 1089 1088 1087 1086 1085 1084 1083 1082 1081
R006 1112 1111 1110 1109 1108 1107 1106 1105 1104 1103 1102 1101 1100 1099 1098 1097
R007 1128 1127 1126 1125 1124 1123 1122 1121 1120 1119 1118 1117 1116 1115 1114 1113
R008 1144 1143 1142 1141 1140 1139 *) 1137 1136 1135 1134 1133 1132 1131 1130 1129
R009 1160 1159 1158 1157 1156 1155 1154 1153 1152 1151 1150 1149 1148 1147 1146 1145
R010 1176 1175 1174 1173 1172 1171 1170 1169 1168 1167 1166 1165 1164 1163 1162 1161
R011 1192 1191 1190 1189 1188 1187 1186 1185 1184 1183 1182 1181 1180 1179 1178 1177
R012 1208 1207 1206 1205 1204 1203 1202 1201 1200 1199 1198 1197 1196 1195 1194 1193
R013 1224 1223 1222 1221 1220 1219 1218 1217 1216 1215 1214 1213 1212 1211 1210 1209
R014 440 439 438 437 436 435 434 433 432 431 430 429 428 427 426 425
R015 456 455 454 453 452 451 450 449 448 447 446 445 444 443 442 441
R016 2016 2015 2014 2013 2012 2011 2010 2009 2008 2007 2006 2005 2004 2003 2002 2001
R017 2032 2031 2030 2029 2028 2027 2026 2025 2024 2023 2022 2021 2020 2019 2018 2017
R018 2048 2047 2046 2045 2044 2043 2042 2041 2040 2039 2038 2037 2036 2035 2034 2033
R019 2064 2063 2062 2061 2060 2059 2058 2057 2056 2055 2054 2053 2052 2051 2050 2049
R020 2080 2079 2078 2077 2076 2075 2074 2073 2072 2071 2070 2069 2068 2067 2066 2065
R021 2096 2095 2094 2093 2092 2091 2090 2089 2088 2087 2086 2085 2084 2083 2082 2081
R022 2112 2111 2110 2109 2108 2107 2106 2105 2104 2103 2102 2101 2100 2099 2098 2097
R023 563 562 2573 2572 2571 2501 **) 2119 2118 2117 2116 2115 2114 2113
R024
R025
R026
R027
R028
R029
R030 561 560 559 558 557 556 555 554 553 552 551 550 549 548 547 546

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 26 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

R031 <--- ---- ---- ---- 600 ---- ---- ---> 598 597 596 595 594 593 592 591
*) 1138 or 2295 or 2296 / 1138 o 2295 o 2296
**) 2120 or 2795 or 2796 / 2120 o 2795 o 2796

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 27 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

SEND DATA Register-addresses R032 – R063 (decimal)


ENVIO DE DATOS Dirección de los registros R032 – R063 (dezimal)

SOURCE: Jenbacher* module control 1-x = SLAVE 11 (decimal) .... 1x


Fuente: Módulo control 1-x de Jenbacher* = Esclavo 11 (decimal) .... 1x

TARGET SYSTEM: CUSTOMER'S COMPUTER (MASTER)


Destino: Ordenador del CLIENTE (MASTER)

FUNCTION CODE: 03 READ HOLDING REGISTERS (4xxxx references)


Código función: 03 LEER LOS REGISTROS INTERNES (4xxxx referencias)
MSB LSB
R032 3016 3015 3014 3013 3012 3011 3010 3009 3008 3007 3006 3005 3004 3003 3002 3001
R033 3032 3031 3030 3029 3028 3027 3026 3025 3024 3023 3022 3021 3020 3019 3018 3017
R034 3048 3047 3046 3045 3044 3043 3042 3041 3040 3039 3038 3037 3036 3035 3034 3033
R035 3064 3063 3062 3061 3060 3059 3058 3057 3056 3055 3054 3053 3052 3051 3050 3049
R036 3080 3079 3078 3077 3076 3075 3074 3073 3072 3071 3070 3069 3068 3067 3066 3065
R037 3096 3095 3094 3093 3092 3091 3090 3089 3088 3087 3086 3085 3084 3083 3082 3081
R038 3112 3111 3110 3109 3108 3107 3106 3105 3104 3103 3102 3101 3100 3099 3098 3097
R039 3128 3127 3126 3125 3124 3123 3122 3121 3120 3119 3118 3117 3116 3115 3114 3113
R040 3144 3143 3142 3141 3140 3139 3138 3137 3136 3135 3134 3133 3132 3131 3130 3129
R041 3160 3159 3158 3157 3156 3155 3154 3153 3152 3151 3150 3149 3148 3147 3146 3145
R042 3176 3175 3174 3173 3172 3171 3170 3169 3168 3167 3166 3165 3164 3163 3162 3161
R043 3192 3191 3190 3189 3188 3187 3186 3185 3184 3183 3182 3181 3180 3179 3178 3177
R044 3208 3207 3206 3205 3204 3203 3202 3201 3200 3199 3198 3197 3196 3195 3194 3193
R045 3224 3223 3222 3221 3220 3219 3218 3217 3216 3215 3214 3213 3212 3211 3210 3209
R046 3316 3315 3314 3313 3312 3311 3310 3309 3308 3307 3306 3305 3304 3303 3302 3301
R047 3332 3331 3330 3329 3328 3327 3326 3325 3324 3323 3322 3321 3320 3319 3318 3317
R048 3348 3347 3346 3345 3344 3343 3342 3341 3340 3339 3338 3337 3336 3335 3334 3333
R049 3364 3363 3362 3361 3360 3359 3358 3357 3356 3355 3354 3353 3352 3351 3350 3349
R050 3380 3379 3378 3377 3376 3375 3374 3373 3372 3371 3370 3369 3368 3367 3366 3365
R051 3396 3395 3394 3393 3392 3391 3390 3389 3388 3387 3386 3385 3384 3383 3382 3381
R052 3416 3415 3414 3413 3412 3411 3410 3409 3408 3407 3406 3405 3404 3403 3402 3401
R053 3432 3431 3430 3429 3428 3427 3426 3425 3424 3423 3422 3421 3420 3419 3418 3417
R054 3448 3447 3446 3445 3444 3443 3442 3441 3440 3439 3438 3437 3436 3435 3434 3433
R055 3464 3463 3462 3461 3460 3459 3458 3457 3456 3455 3454 3453 3452 3451 3450 3449
R056 3480 3479 3478 3477 3476 3475 3474 3473 3472 3471 3470 3469 3468 3467 3466 3465
R057 3496 3495 3494 3493 3492 3491 3490 3489 3488 3487 3486 3485 3484 3483 3482 3481
R058 3512 3511 3510 3509 3508 3507 3506 3505 3504 3503 3502 3501 3500 3499 3498 3497
R059 3528 3527 3526 3525 3524 3523 3522 3521 3520 3519 3518 3517 3516 3515 3514 3513
R060 3544 3543 3542 3541 3540 3539 3538 3537 3536 3535 3534 3533 3532 3531 3530 3529
R061 3560 3559 3558 3557 3556 3555 3554 3553 3552 3551 3550 3549 3548 3547 3546 3545
R062 3576 3575 3574 3573 3572 3571 3570 3569 3568 3567 3566 3565 3564 3563 3562 3561

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 28 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

R063 <--- ---- ---- ---- 600 ---- ---- --->

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 29 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

SEND DATA Register-addresses R064 – R095 (decimal)


ENVIO DE DATOS Dirección de los registros R064 – R095 (dezimal)

SOURCE: Jenbacher* module control 1-x = SLAVE 11 (decimal) .... 1x


Fuente: Módulo control 1-x de Jenbacher* = Esclavo 11 (decimal) .... 1x

TARGET SYSTEM: CUSTOMER'S COMPUTER (MASTER)


Destino: Ordenador del CLIENTE (MASTER)

FUNCTION CODE: 03 READ HOLDING REGISTERS (4xxxx references)


Código función: 03 LEER LOS REGISTROS INTERNES (4xxxx referencias)
MSB LSB
R064 <--- ---- ---- ---- ---- ---- ---- 500 ---- ---- ---- ---- ---- ---- ---- --->
R065 <--- ---- ---- ---- ---- ---- ---- 501 ---- ---- ---- ---- ---- ---- ---- --->
R066 <--- ---- ---- ---- ---- ---- ---- 502 ---- ---- ---- ---- ---- ---- ---- --->
R067 <--- ---- ---- ---- ---- ---- ---- 503 ---- ---- ---- ---- ---- ---- ---- --->
R068 <--- ---- ---- ---- ---- ---- ---- 504 ---- ---- ---- ---- ---- ---- ---- --->
R069 <--- ---- ---- ---- ---- ---- ---- 505 ---- ---- ---- ---- ---- ---- ---- --->
R070 <--- ---- ---- ---- ---- ---- ---- 506 ---- ---- ---- ---- ---- ---- ---- --->
R071 <--- ---- ---- ---- ---- ---- ---- 507 ---- ---- ---- ---- ---- ---- ---- --->
R072 <--- ---- ---- ---- ---- ---- ---- 508 ---- ---- ---- ---- ---- ---- ---- --->
R073 <--- ---- ---- ---- ---- ---- ---- 509 ---- ---- ---- ---- ---- ---- ---- --->
R074 <--- ---- ---- ---- ---- ---- ---- 510 ---- ---- ---- ---- ---- ---- ---- --->
R075 <--- ---- ---- ---- ---- ---- ---- 511 ---- ---- ---- ---- ---- ---- ---- --->
R076 <--- ---- ---- ---- ---- ---- ---- 512 ---- ---- ---- ---- ---- ---- ---- --->
R077 <--- ---- ---- ---- ---- ---- ---- 513 ---- ---- ---- ---- ---- ---- ---- --->
R078 <--- ---- ---- ---- ---- ---- ---- 514 ---- ---- ---- ---- ---- ---- ---- --->
R079 <--- ---- ---- ---- ---- ---- ---- 515 ---- ---- ---- ---- ---- ---- ---- --->
R080 <--- ---- ---- ---- ---- ---- ---- 516 ---- ---- ---- ---- ---- ---- ---- --->
R081 <--- ---- ---- ---- ---- ---- ---- 517 ---- ---- ---- ---- ---- ---- ---- --->
R082 <--- ---- ---- ---- ---- ---- ---- 518 ---- ---- ---- ---- ---- ---- ---- --->
R083 <--- ---- ---- ---- ---- ---- ---- 519 ---- ---- ---- ---- ---- ---- ---- --->
R084 <--- ---- ---- ---- ---- ---- ---- 520 ---- ---- ---- ---- ---- ---- ---- --->
R085 <--- ---- ---- ---- ---- ---- ---- 521 ---- ---- ---- ---- ---- ---- ---- --->
R086 <--- ---- ---- ---- ---- ---- ---- 522 ---- ---- ---- ---- ---- ---- ---- --->
R087 <--- ---- ---- ---- ---- ---- ---- 523 ---- ---- ---- ---- ---- ---- ---- --->
R088 <--- ---- ---- ---- ---- ---- ---- 524 ---- ---- ---- ---- ---- ---- ---- --->
R089 <--- ---- ---- ---- ---- ---- ---- 525 ---- ---- ---- ---- ---- ---- ---- --->
R090 <--- ---- ---- ---- ---- ---- ---- 526 ---- ---- ---- ---- ---- ---- ---- --->
R091 <--- ---- ---- ---- ---- ---- ---- 527 ---- ---- ---- ---- ---- ---- ---- --->
R092 <--- ---- ---- ---- ---- ---- ---- 528 ---- ---- ---- ---- ---- ---- ---- --->
R093 <--- ---- ---- ---- ---- ---- ---- 529 ---- ---- ---- ---- ---- ---- ---- --->
R094 <--- ---- ---- ---- ---- ---- ---- 530 ---- ---- ---- ---- ---- ---- ---- --->

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 30 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

R095 <--- ---- ---- ---- ---- ---- ---- 531 ---- ---- ---- ---- ---- ---- ---- --->

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 31 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

SEND DATA Register-addresses R096 – R127 (decimal)


ENVIO DE DATOS Dirección de los registros R096 – R127 (dezimal)

SOURCE: Jenbacher* module control 1-x = SLAVE 11 (decimal) .... 1x


Fuente: Módulo control 1-x de Jenbacher* = Esclavo 11 (decimal) .... 1x

TARGET SYSTEM: CUSTOMER'S COMPUTER (MASTER)


Destino: Ordenador del CLIENTE (MASTER)

FUNCTION CODE: 03 READ HOLDING REGISTERS (4xxxx references)


Código función: 03 LEER LOS REGISTROS INTERNES (4xxxx referencias)
MSB LSB
R096 <--- ---- ---- ---- ---- ---- ---- 532 ---- ---- ---- ---- ---- ---- ---- --->
R097 <--- ---- ---- ---- ---- ---- ---- 533 ---- ---- ---- ---- ---- ---- ---- --->
R098 <--- ---- ---- ---- ---- ---- ---- 534 ---- ---- ---- ---- ---- ---- ---- --->
R099 <--- ---- ---- ---- ---- ---- ---- 535 ---- ---- ---- ---- ---- ---- ---- --->
R100 <--- ---- ---- ---- ---- ---- ---- 536 ---- ---- ---- ---- ---- ---- ---- --->
R101 <--- ---- ---- ---- ---- ---- ---- 537 ---- ---- ---- ---- ---- ---- ---- --->
R102 <--- ---- ---- ---- ---- ---- ---- 538 ---- ---- ---- ---- ---- ---- ---- --->
R103 <--- ---- ---- ---- ---- ---- ---- 539 ---- ---- ---- ---- ---- ---- ---- --->
R104 <--- ---- ---- ---- ---- ---- ---- 540 ---- ---- ---- ---- ---- ---- ---- --->
R105 <--- ---- ---- ---- ---- ---- ---- 541 ---- ---- ---- ---- ---- ---- ---- --->
R106 <--- ---- ---- ---- ---- ---- ---- 542 ---- ---- ---- ---- ---- ---- ---- --->
R107 <--- ---- ---- ---- ---- ---- ---- 543 ---- ---- ---- ---- ---- ---- ---- --->
R108 <--- ---- ---- ---- ---- ---- ---- 544 ---- ---- ---- ---- ---- ---- ---- --->
R109 <--- ---- ---- ---- ---- ---- ---- 545 ---- ---- ---- ---- ---- ---- ---- --->
R110 <--- ---- ---- ---- ---- ---- ---- Res. ---- ---- ---- ---- ---- ---- ---- --->
R111 <--- ---- ---- ---- ---- ---- ---- Res. ---- ---- ---- ---- ---- ---- ---- --->
R112 <--- ---- ---- ---- ---- ---- ---- 601 ---- ---- ---- ---- ---- ---- ---- --->
R113 <--- ---- ---- ---- ---- ---- ---- 602 ---- ---- ---- ---- ---- ---- ---- --->
R114 <--- ---- ---- ---- ---- ---- ---- 603 ---- ---- ---- ---- ---- ---- ---- --->
R115 <--- ---- ---- ---- ---- ---- ---- 604 ---- ---- ---- ---- ---- ---- ---- --->
R116 <--- ---- ---- ---- ---- ---- ---- 605 ---- ---- ---- ---- ---- ---- ---- --->
R117 <--- ---- ---- ---- ---- ---- ---- 606 ---- ---- ---- ---- ---- ---- ---- --->
R118 <--- ---- ---- ---- ---- ---- ---- 607 ---- ---- ---- ---- ---- ---- ---- --->
R119 <--- ---- ---- ---- ---- ---- ---- 608 ---- ---- ---- ---- ---- ---- ---- --->
R120 <--- ---- ---- ---- ---- ---- ---- 609 ---- ---- ---- ---- ---- ---- ---- --->
R121 <--- ---- ---- ---- ---- ---- ---- 610 ---- ---- ---- ---- ---- ---- ---- --->
R122 <--- ---- ---- ---- ---- ---- ---- 611 ---- ---- ---- ---- ---- ---- ---- --->
R123 <--- ---- ---- ---- ---- ---- ---- 612 ---- ---- ---- ---- ---- ---- ---- --->
R124 <--- ---- ---- ---- ---- ---- ---- 613 ---- ---- ---- ---- ---- ---- ---- --->
R125 <--- ---- ---- ---- ---- ---- ---- 614 ---- ---- ---- ---- ---- ---- ---- --->
R126 <--- ---- ---- ---- ---- ---- ---- 615 ---- ---- ---- ---- ---- ---- ---- --->

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 32 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

R127 <--- ---- ---- ---- ---- ---- ---- 616 ---- ---- ---- ---- ---- ---- ---- --->

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 33 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

SEND DATA Register-addresses R128 – R159 (decimal)


ENVIO DE DATOS Dirección de los registros R128 – R159 (dezimal)

SOURCE: Jenbacher* module control 1-x = SLAVE 11 (decimal) .... 1x


Fuente: Módulo control 1-x de Jenbacher* = Esclavo 11 (decimal) .... 1x

TARGET SYSTEM: CUSTOMER'S COMPUTER (MASTER)


Destino: Ordenador del CLIENTE (MASTER)

FUNCTION CODE: 03 READ HOLDING REGISTERS (4xxxx references)


Código función: 03 LEER LOS REGISTROS INTERNES (4xxxx referencias)
MSB LSB
R128 <--- ---- ---- ---- ---- ---- ---- 617 ---- ---- ---- ---- ---- ---- ---- --->
R129 <--- ---- ---- ---- ---- ---- ---- 618 ---- ---- ---- ---- ---- ---- ---- --->
R130 <--- ---- ---- ---- ---- ---- ---- 619 ---- ---- ---- ---- ---- ---- ---- --->
R131 <--- ---- ---- ---- ---- ---- ---- 620 ---- ---- ---- ---- ---- ---- ---- --->
R132 <--- ---- ---- ---- ---- ---- ---- 621 ---- ---- ---- ---- ---- ---- ---- --->
R133 <--- ---- ---- ---- ---- ---- ---- 622 ---- ---- ---- ---- ---- ---- ---- --->
R134 <--- ---- ---- ---- ---- ---- ---- 623 ---- ---- ---- ---- ---- ---- ---- --->
R135 <--- ---- ---- ---- ---- ---- ---- 624 ---- ---- ---- ---- ---- ---- ---- --->
R136 <--- ---- ---- ---- ---- ---- ---- 625 ---- ---- ---- ---- ---- ---- ---- --->
R137 <--- ---- ---- ---- ---- ---- ---- 626 ---- ---- ---- ---- ---- ---- ---- --->
R138 <--- ---- ---- ---- ---- ---- ---- 627 ---- ---- ---- ---- ---- ---- ---- --->
R139 <--- ---- ---- ---- ---- ---- ---- 628 ---- ---- ---- ---- ---- ---- ---- --->
R140 <--- ---- ---- ---- ---- ---- ---- 629 ---- ---- ---- ---- ---- ---- ---- --->
R141 <--- ---- ---- ---- ---- ---- ---- 630 ---- ---- ---- ---- ---- ---- ---- --->
R142 <--- ---- ---- ---- ---- ---- ---- 631 ---- ---- ---- ---- ---- ---- ---- --->
R143 <--- ---- ---- ---- ---- ---- ---- 632 ---- ---- ---- ---- ---- ---- ---- --->
R144 <--- ---- ---- ---- ---- ---- ---- 633 ---- ---- ---- ---- ---- ---- ---- --->
R145 <--- ---- ---- ---- ---- ---- ---- 634 ---- ---- ---- ---- ---- ---- ---- --->
R146 <--- ---- ---- ---- ---- ---- ---- 635 ---- ---- ---- ---- ---- ---- ---- --->
R147 <--- ---- ---- ---- ---- ---- ---- 636 ---- ---- ---- ---- ---- ---- ---- --->
R148 <--- ---- ---- ---- ---- ---- ---- 637 ---- ---- ---- ---- ---- ---- ---- --->
R149 <--- ---- ---- ---- ---- ---- ---- 638 ---- ---- ---- ---- ---- ---- ---- --->
R150 <--- ---- ---- ---- ---- ---- ---- 639 ---- ---- ---- ---- ---- ---- ---- --->
R151 <--- ---- ---- ---- ---- ---- ---- 640 ---- ---- ---- ---- ---- ---- ---- --->
R152 <--- ---- ---- ---- ---- ---- ---- 641 ---- ---- ---- ---- ---- ---- ---- --->
R153 <--- ---- ---- ---- ---- ---- ---- 642 ---- ---- ---- ---- ---- ---- ---- --->
R154 <--- ---- ---- ---- ---- ---- ---- 643 ---- ---- ---- ---- ---- ---- ---- --->
R155 <--- ---- ---- ---- ---- ---- ---- 644 ---- ---- ---- ---- ---- ---- ---- --->
R156 <--- ---- ---- ---- ---- ---- ---- 645 ---- ---- ---- ---- ---- ---- ---- --->
R157 <--- ---- ---- ---- ---- ---- ---- 646 ---- ---- ---- ---- ---- ---- ---- --->
R158 <--- ---- ---- ---- ---- ---- ---- 647 ---- ---- ---- ---- ---- ---- ---- --->

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 34 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

R159 <--- ---- ---- ---- ---- ---- ---- 648 ---- ---- ---- ---- ---- ---- ---- --->

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 35 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

SEND DATA Register-addresses R160 – R191 (decimal)


ENVIO DE DATOS Dirección de los registros R160 – R191 (dezimal)

SOURCE: Jenbacher* module control 1-x = SLAVE 11 (decimal) .... 1x


Fuente: Módulo control 1-x de Jenbacher* = Esclavo 11 (decimal) .... 1x

TARGET SYSTEM: CUSTOMER'S COMPUTER (MASTER)


Destino: Ordenador del CLIENTE (MASTER)

FUNCTION CODE: 03 READ HOLDING REGISTERS (4xxxx references)


Código función: 03 LEER LOS REGISTROS INTERNES (4xxxx referencias)
MSB LSB
R160 <--- ---- ---- ---- ---- ---- ---- 649 ---- ---- ---- ---- ---- ---- ---- --->
R161 <--- ---- ---- ---- ---- ---- ---- 650 ---- ---- ---- ---- ---- ---- ---- --->
R162 <--- ---- ---- ---- ---- ---- ---- 651 ---- ---- ---- ---- ---- ---- ---- --->
R163 <--- ---- ---- ---- ---- ---- ---- 652 ---- ---- ---- ---- ---- ---- ---- --->
R164 <--- ---- ---- ---- ---- ---- ---- 653 ---- ---- ---- ---- ---- ---- ---- --->
R165 <--- ---- ---- ---- ---- ---- ---- 654 ---- ---- ---- ---- ---- ---- ---- --->
R166 <--- ---- ---- ---- ---- ---- ---- 655 ---- ---- ---- ---- ---- ---- ---- --->
R167 <--- ---- ---- ---- ---- ---- ---- 656 ---- ---- ---- ---- ---- ---- ---- --->
R168 <--- ---- ---- ---- ---- ---- ---- 657 ---- ---- ---- ---- ---- ---- ---- --->
R169 <--- ---- ---- ---- ---- ---- ---- 658 ---- ---- ---- ---- ---- ---- ---- --->
R170 <--- ---- ---- ---- ---- ---- ---- 659 ---- ---- ---- ---- ---- ---- ---- --->
R171 <--- ---- ---- ---- ---- ---- ---- 660 ---- ---- ---- ---- ---- ---- ---- --->
R172 <--- ---- ---- ---- ---- ---- ---- 661 ---- ---- ---- ---- ---- ---- ---- --->
R173 <--- ---- ---- ---- ---- ---- ---- 662 ---- ---- ---- ---- ---- ---- ---- --->
R174 <--- ---- ---- ---- ---- ---- ---- 663 ---- ---- ---- ---- ---- ---- ---- --->
R175 <--- ---- ---- ---- ---- ---- ---- 664 ---- ---- ---- ---- ---- ---- ---- --->
R176 <--- ---- ---- ---- ---- ---- ---- 665 ---- ---- ---- ---- ---- ---- ---- --->
R177 <--- ---- ---- ---- ---- ---- ---- 666 ---- ---- ---- ---- ---- ---- ---- --->
R178 <--- ---- ---- ---- ---- ---- ---- 667 ---- ---- ---- ---- ---- ---- ---- --->
R179 <--- ---- ---- ---- ---- ---- ---- 668 ---- ---- ---- ---- ---- ---- ---- --->
R180 <--- ---- ---- ---- ---- ---- ---- 669 ---- ---- ---- ---- ---- ---- ---- --->
R181 <--- ---- ---- ---- ---- ---- ---- 670 ---- ---- ---- ---- ---- ---- ---- --->
R182 <--- ---- ---- ---- ---- ---- ---- 671 ---- ---- ---- ---- ---- ---- ---- --->
R183 <--- ---- ---- ---- ---- ---- ---- 672 ---- ---- ---- ---- ---- ---- ---- --->
R184 <--- ---- ---- ---- ---- ---- ---- 673 ---- ---- ---- ---- ---- ---- ---- --->
R185 <--- ---- ---- ---- ---- ---- ---- 674 ---- ---- ---- ---- ---- ---- ---- --->
R186 <--- ---- ---- ---- ---- ---- ---- 675 ---- ---- ---- ---- ---- ---- ---- --->
R187 <--- ---- ---- ---- ---- ---- ---- 676 ---- ---- ---- ---- ---- ---- ---- --->
R188 <--- ---- ---- ---- ---- ---- ---- 677 ---- ---- ---- ---- ---- ---- ---- --->
R189 <--- ---- ---- ---- ---- ---- ---- 678 ---- ---- ---- ---- ---- ---- ---- --->
R190 <--- ---- ---- ---- ---- ---- ---- 679 ---- ---- ---- ---- ---- ---- ---- --->
R191 <--- ---- ---- ---- ---- ---- ---- 680 ---- ---- ---- ---- ---- ---- ---- --->

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 36 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

END OF SEND DATA


FINAL ENVIO DE DATOS

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 37 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

RECEIVE DATA Register-addresses R192 – R207 (decimal)


RECEPCION DE DATOS Direcion de los registros R192 – R207 (decimal)

SOURCE: CUSTOMER'S COMPUTER (MASTER)


Fuente: Ordenador del cliente (MASTER)

TARGET SYSTEM: Jenbacher* module control 1-x = SLAVE 11 (decimal) .... 1x


Destino: Módulo control 1-x de Jenbacher* = Esclavo 11 (decimal) .... 1x

FUNCTION CODE: 16 PRESET MULTIPLE REGISTERS (4xxxx references)


Código función: 16 ESCRIBIR DE n REGISTROS INTERNES (4xxxx referencias)

MSB LSB
R192 708 707 706 705 704 703 702 701
R193 732 731
R194 <--- ---- ---- ---- ---- ---- ---- 740 ---- ---- ---- ---- ---- ---- ---- --->
R195
R196
R197
R198
R199
R200
R201
R202
R203
R204
R205
R206
R207

END OF RECEIVE DATA


FINAL RECEPCION DE DATOS

SEND DATA ITEMS FOR MODULE


PUNTOS DATOS DE ENVIO MODUL

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 38 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

401 SPARE
- RESERVA
424

425 SERVICE SELECTOR SWITCH IN Jenbacher* CUSTOMER OPERATION MESSAGE


POSITION "OFF" CLIENTE MENSAJE DE SERVICIO
SELECTOR DE SERVICIO EN
POSICION "DESCONECTADO"

426 SERVICE SELECTOR SWITCH IN Jenbacher* CUSTOMER OPERATION MESSAGE


POSITION "MANUAL" CLIENTE IDENTICAL LOGIC WITH No. 450
SELECTOR DE SERVICIO EN MENSAJE DE SERVICIO
POSICION "MANUAL" LOGICA IDENTICA A LA N° 450

427 SERVICE SELECTOR SWITCH IN Jenbacher* CUSTOMER OPERATION MESSAGE


POSITION "AUTOMATIC" CLIENTE IDENTICAL LOGIC WITH No. 451
SELECTOR DE SERVICIO EN MENSAJE DE SERVICIO
POSICION "AUTOMATICA" LOGICA IDENTICA A LA N° 451

428

429 GENERATOR CB CLOSED Jenbacher* CUSTOMER OPERATION MESSAGE


DISYUNTOR DEL GENERADOR CLIENTE IDENTICAL LOGIC WITH No. 446
CERRADO MENSAJE DE SERVICIO
LOGICA IDENTICA A LA N° 446

430 GENERATOR CB OPEN Jenbacher* CUSTOMER OPERATION MESSAGE


DISYUNTOR DEL GENERADOR CLIENTE MENSAJE DE SERVICIO
ABIERTO

431 OPERATION ON Jenbacher* CUSTOMER OPERATION MESSAGE


EN SERVICIO CLIENTE IDENTICAL LOGIC WITH No. 20,449
MENSAJE DE SERVICIO
LOGICA IDENTICA A LA N° 20,449

432 OPERATION OFF Jenbacher* CUSTOMER OPERATION MESSAGE


FUERA DE SERVICIO CLIENTE MENSAJE DE SERVICIO

433 READY FOR AUTOMATIC DEMAND Jenbacher* CUSTOMER OPERATION MESSAGE


ON CLIENTE IDENTICAL LOGIC WITH No. 14,444
PREPARADO PARA ARRANQUE MENSAJE DE SERVICIO
AUTOMATICO CONECTADOS LOGICA IDENTICA A LA N° 14,444

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 39 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

434 READY FOR AUTOMATIC DEMAND Jenbacher* CUSTOMER OPERATION MESSAGE


OFF CLIENTE MENSAJE DE SERVICIO
PREPARADO PARA ARRANQUE
AUTOMATICO DESCONECTADOS

435 MAINS CB CLOSED Jenbacher* CUSTOMER OPERATION MESSAGE


DISYUNTOR DE LA RED CLIENTE IDENTICAL LOGIC WITH No. 447
CONECTADO MENSAJE DE SERVICIO
LOGICA IDENTICA A LA N° 447

436 MAINS CB OPEN Jenbacher* CUSTOMER OPERATION MESSAGE


DISYUNTOR DE LA RED CLIENTE MENSAJE DE SERVICIO
DESCONECTADO

437 SPARE Jenbacher* CUSTOMER FAILURE MESSAGE


RESERVA CLIENTE (General failure message of the turbo
charge unit:
Message No. 2213, 2215-2226, 2233, 2234,
2236-2239, 2258, 2259)
MENSAJE DE FALLO
(Problema general de unidad de
turbocargador:
Aviso Nro. 2213, 2215-2226, 2233, 2234,

438 SPARE Jenbacher* CUSTOMER FAILURE MESSAGE


RESERVA CLIENTE (General failure message of the turbo
charge unit:
Message No. 2514-2523, 2525-2533, 2539-
2541, 2543, 2546-2551, 2554, 2563-2566, 2611,
2612)
MENSAJE DE FALLO
(Problema general de unidad de
turbocargador:
Aviso Nro. 2514-2523, 2525-2533, 2539-2541,
2543, 2546-2551, 2554, 2563-2566, 2611, 2612)

439 SPARE Jenbacher* CUSTOMER FAILURE MESSAGE


RESERVA CLIENTE (General failure message of SAFI/MORIS:
from Message No. 3330 to No. 3345)
MENSAJE DE FALLO
(Problema general de SAFI/MORIS:
de Aviso Nro. 3330 a Nro. 3345)

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 40 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

440 SPARE Jenbacher* CUSTOMER FAILURE MESSAGE


RESERVA CLIENTE (General failure message of SAFI/MORIS:
from Message No. 3530 to No. 3552)
MENSAJE DE FALLO
(Problema general de SAFI/MORIS:
de Aviso Nro. 3530 a Nro. 3552)

441 SYNCHRONIZING GENERATOR Jenbacher* CUSTOMER OPERATION MESSAGE


ACTIVATED CLIENTE MENSAJE DE SERVICIO
SINCRONIZACION DEL GENERADOR
SELECCIONADA

442 RE-SYNCHRONIZING ACTIVATED Jenbacher* CUSTOMER OPERATION MESSAGE


RESINCRONIZACION CLIENTE MENSAJE DE SERVICIO
SELECCIONADA

443 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

444 READY FOR AUTOMATIC DEMAND Jenbacher* CUSTOMER OPERATION MESSAGE


PREPARADO PARA ARRANQUE CLIENTE IDENTICAL LOGIC WITH No. 14,433
AUTOMATICO MENSAJE DE SERVICIO
LOGICA IDENTICA A LA N° 14,433

445 DEMAND FOR AUXILIARIES Jenbacher* CUSTOMER OPERATION MESSAGE


ORDEN DE ARRANQUE DE CLIENTE IDENTICAL LOGIC WITH No. 18
AUXILIARESS MENSAJE DE SERVICIO
LOGICA IDENTICA A LA N° 18

446 GENERATOR CB CLOSED Jenbacher* CUSTOMER OPERATION MESSAGE


DISYUNTOR DEL GENERADOR CLIENTE IDENTICAL LOGIC WITH No. 429
CERRADO MENSAJE DE SERVICIO
LOGICA IDENTICA A LA N° 429

447 MAINS CB CLOSED Jenbacher* CUSTOMER OPERATION MESSAGE


DISYUNTOR DE LA RED CLIENTE IDENTICAL LOGIC WITH No. 435
CONECTADO MENSAJE DE SERVICIO
LOGICA IDENTICA A LA N° 435

448 MODULE IS DEMANDED Jenbacher* CUSTOMER OPERATION MESSAGE


MOTOR HA RECIBIDO ORDEN CLIENTE IDENTICAL LOGIC WITH No. 17
ARRANCAR MENSAJE DE SERVICIO
LOGICA IDENTICA A LA N° 17

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 41 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

449 OPERATION | ENGINE IS RUNNING Jenbacher* CUSTOMER OPERATION MESSAGE


SERVICIO | MOTOR EN MARCHA CLIENTE IDENTICAL LOGIC WITH No. 20,431
MENSAJE DE SERVICIO
LOGICA IDENTICA A LA N° 20,431

450 SERVICE SELECTOR SWITCH IN Jenbacher* CUSTOMER OPERATION MESSAGE


POSITION "MANUAL" CLIENTE IDENTICAL LOGIC WITH No. 426
SELECTOR DE SERVICIO EN MENSAJE DE SERVICIO
POSICION "MANUAL" LOGICA IDENTICA A LA N° 426

451 SERVICE SELECTOR SWITCH IN Jenbacher* CUSTOMER OPERATION MESSAGE


POSITION "AUTOMATIC" CLIENTE IDENTICAL LOGIC WITH No. 427
SELECTOR DE SERVICIO EN MENSAJE DE SERVICIO
POSICION "AUTOMATICA" LOGICA IDENTICA A LA N° 427

452 GENERAL TRIP Jenbacher* CUSTOMER FAILURE MESSAGE


PROBLEMA GENERAL PARADA CLIENTE IDENTICAL LOGIC WITH No. 21
MENSAJE DE FALLO
LOGICA IDENTICA A LA N° 21

453 GENERAL WARNING Jenbacher* CUSTOMER FAILURE MESSAGE


PROBLEMA GENERAL ALARMA CLIENTE IDENTICAL LOGIC WITH No. 22
MENSAJE DE FALLO
LOGICA IDENTICA A LA N° 22

454 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

455 PULSE FOR OPERATION HOURS Jenbacher* CUSTOMER COUNTING PULSE | ON-TIME = 10"
COUNTER CLIENTE IMPULSO | DURACION "ON" = 10"
IMPULSO PARA CONTADOR DE
HORAS DE SERVICIO

456 PULSE FOR START COUNTER Jenbacher* CUSTOMER COUNTING PULSE


IMPULSO PARA CONTADOR DE CLIENTE ON-TIME | OFF-TIME > 10"
ARRANQUES IMPULSO
IMPULSO | DURACION "ON" = 10"

457
-
499

500

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 42 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

501 JACKET WATER TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
TEMPERATURA AGUA DE CAMISAS CLIENTE (1 UNIT = 0,1 °C)
M.04-TI-001 VALOR MEDIDO INT 16 (0,1 °C)

502 JACKET WATER PRESSURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
PRESION AGUA DE CAMISAS CLIENTE (1 UNIT = 0,01 bar)
M.04-PI-001 VALOR MEDIDO INT 16 (0,01 bar)

503 ENGINE OIL TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
TEMPERATURA DEL ACEITE CLIENTE (1 UNIT = 0,1 °C)
M.03-TI-001 VALOR MEDIDO INT 16 (0,1 °C)

504 ENGINE OIL PRESSURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
PRESION DEL ACEITE CLIENTE (1 UNIT = 0,01 bar)
M.03-PI-001 VALOR MEDIDO INT 16 (0,01 bar)

505 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 0,1 °C)
VALOR MEDIDO INT 16 (0,1 °C)

506 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 0,1 °C)
VALOR MEDIDO INT 16 (0,1 °C)

507 SPARE
RESERVA

508 CYLINDER EXHAUST GAS Jenbacher* CUSTOMER CALCULATED VALUE 16 BIT INTEGER
TEMPERATURE AVERAGE VALUE CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA MEDIA DE LOS VALOR CALCULADO INT 16 ( 1,0 °C)
CILINDROS
E.02-TI-001[xx]
509 HEATING WATER RETURN Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
TEMPERATURE CLIENTE (1 UNIT = 0,1 °C)
TEMPERATURA AGUA DE RETORNO VALOR MEDIDO INT 16 (0,1 °C)
P.06-TI-012, P.04-TI-012
510 HEATING WATER SUPPLY Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
TEMPERATURE CLIENTE (1 UNIT = 0,1 °C)
TEMPERATURA AGUA DE SALIDA VALOR MEDIDO INT 16 (0,1 °C)
P.06-TI-014, P.04-TI-014

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 43 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

511 GENERATOR POWER FACTOR Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
COSPHI DEL GENERADOR CLIENTE INT 16 ( -999 ... -1 / 0 ... +1000 =
cosphi -0,999 ... -0,001 [cap.] / 0 ... +1,0 [ind.] )
VALOR MEDIDO
INT 16 ( -999 ... -1 / 0 ... +1000 =
cosphi -0,999 ... -0,001 [cap.] / 0 ... +1,0 [ind.] )

512 GENERATOR FREQUENCY Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


FRECUENCIA DEL GENERADOR CLIENTE (1 UNIT = 0,1 Hz)
VALOR MEDIDO INT 16 (0,1 Hz)

513 GENERATOR CURRENT AVERAGE Jenbacher* CUSTOMER CALCULATED VALUE 16 BIT INTEGER
VALUE CLIENTE (1 UNIT = 1,0A)
NTENSIDAD MEDIA DEL VALOR CALCULADO INT 16 (1,0 A)
GENERADOR

514 GENERATOR VOLTAGE AVERAGE Jenbacher* CUSTOMER CALCULATED VALUE 16 BIT INTEGER
VALUE (PHASE TO PHASE) CLIENTE (1 UNIT = 1,0 V)
TENSION FASE-FASE DEL VALOR CALCULADO INT 16 (1,0 V)
GENERADOR

515

516 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 1 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 1
E.02-TI-001[01]
517 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 2 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 2
E.02-TI-001[02]
518 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 3 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 3
E.02-TI-001[03]
519 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 4 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 4
E.02-TI-001[04]

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 44 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

520 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 5 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 5
E.02-TI-001[05]
521 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 6 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 6
E.02-TI-001[06]
522 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 7 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 7
E.02-TI-001[07]
523 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 8 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 8
E.02-TI-001[08]
524 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 9 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 9
E.02-TI-001[09]
525 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 10 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 10
E.02-TI-001[10]
526 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 11 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 11
E.02-TI-001[11]
527 EXHAUST GAS TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CYLINDER 12 CLIENTE (1 UNIT = 1,0 °C)
TEMPERATURA GAS DE ESCAPE VALOR MEDIDO INT 16 (1,0 °C)
CILINDRO 12
E.02-TI-001[12]
528 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 45 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

529 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

530 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

531 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

532 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

533 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

534 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

535 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

536 TOTAL ACTIVE OUTPUT Jenbacher* CUSTOMER COUNTER READING 32 BIT INTEGER
ENERGIA ACTIVA MAXIMA CLIENTE (1 UNIT = 0,1 MWh)
(HIGH-WORD) LECTURA CONTADOR
INT 32 (0,1 MWh)
(32 bits = 2 words)

537 TOTAL ACTIVE OUTPUT Jenbacher* CUSTOMER SEE No. 536!


ENERGIA ACTIVA MAXIMA CLIENTE ver No. 536!
(LOW-WORD)
538 TOTAL REACTIVE OUTPUT Jenbacher* CUSTOMER COUNTER READING 32 BIT INTEGER
ENERGIA ACTIVA MAXIMA CLIENTE (1 UNIT = 0,1 MVArh)
(HIGH-WORD) LECTURA CONTADOR
INT 32 (0,1 MVArh)
(32 bits = 2 words)

539 TOTAL REACTIVE OUTPUT Jenbacher* CUSTOMER SEE No. 538!


ENERGIA ACTIVA MAXIMA CLIENTE ver No. 538!
(LOW-WORD)

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 46 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

540 SETPOINT POWER CONTROL Jenbacher* CUSTOMER CALCULATED VALUE 16 BIT INTEGER
VALORE CONSIGNA DE CLIENTE (1 UNIT = 1,0 kW)
REGULADOR DE POTENCIA VALOR CALCULADO
INT 16 (1,0 kW)

541 OPERATION HOURS COUNTER Jenbacher* CUSTOMER COUNTER READING 32 BIT INTEGER
CONTADOR DE HORAS DE CLIENTE (1 UNIT = 1 HOUR)
SERVICIO LECTURA CONTADOR
(HIGH-WORD) INT 32 (1 unidad = 1 hora)
(32 bits = 2 words)

542 OPERATION HOURS COUNTER Jenbacher* CUSTOMER SEE No. 541!


CONTADOR DE HORAS DE CLIENTE ver No. 541!
SERVICIO
(LOW-WORD)
543 START COUNTER Jenbacher* CUSTOMER COUNTER READING (1 UNIT = 1 START)
CONTADOR DE HORAS DE CLIENTE LECTURA CONTADOR
SERVICIO INT 32 (1 unidad = 1 arranque)
(HIGH-WORD) (32 bits = 2 words)

544 START COUNTER Jenbacher* CUSTOMER SEE No. 543!


CONTADOR DE HORAS DE CLIENTE ver No. 543!
SERVICIO
(LOW-WORD)
545

546 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

547 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

548 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

549 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

550 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

551 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 47 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

552 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

553 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

554 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

555 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

556 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

557 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

558 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

559 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

560 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

561 SPARE Jenbacher* CUSTOMER OPERATION MESSAGE


RESERVA CLIENTE MENSAJE DE SERVICIO

562 READY FOR FAST START Jenbacher* CUSTOMER OPERATION MESSAGE


Preparado para inicio rápido CLIENTE MENSAJE DE SERVICIO

563 READY FOR VERY FAST START Jenbacher* CUSTOMER OPERATION MESSAGE
Preparado para inicio ultra- CLIENTE MENSAJE DE SERVICIO
rápido
564
-
599

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 48 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

600 CLOCK PULSE Jenbacher* CUSTOMER OPERATION MESSAGE


10" = alle|ALL 8 Bit "1" CLIENTE MENSAJE DE SERVICIO
10" = alle|ALL 8 Bit "0"
PULSOS DE RELOJ
10" = alle|ALL 8 Bit "1"
10" = alle|ALL 8 Bit "0"

601 CHARGE TEMPERATURE (FUEL Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
MIXTURE TEMPERATURE) CLIENTE (1 UNIT = 0,1 °C)
TEMPERATURA DE CARGA VALOR MEDIDO INT 16 (0,1 °C)
(TEMPERATURA DE LA MEZCLA)
E.08-TI-001
602 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
RESERVA CLIENTE (1 UNIT = 0,1 °C)
VALOR MEDIDO INT 16 (0,1 °C)

603 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 0,1 °C)
VALOR MEDIDO INT 16 (0,1 °C)

604 SPARE
RESERVA

605 EXCITATION VOLTAGE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


TENSION DE EXCITACION CLIENTE (1 UNIT = 0,1 V)
VALOR MEDIDO INT 16 (0,1 V)

606 GENERATOR WINDING Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


TEMPERATURE L1 CLIENTE (1 UNIT = 0,1 °C)
TEMPERATURA DE LOS BOBINADOS VALOR MEDIDO INT 16 (0,1 °C)
L1 GENERADOR

607 GENERATOR WINDING Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


TEMPERATURE L2 CLIENTE (1 UNIT = 0,1 °C)
TEMPERATURA DE LOS BOBINADOS VALOR MEDIDO INT 16 (0,1 °C)
L2 GENERADOR

608 GENERATOR WINDING Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


TEMPERATURE L3 CLIENTE (1 UNIT = 0,1 °C)
TEMPERATURA DE LOS BOBINADOS VALOR MEDIDO INT 16 (0,1 °C)
L3 GENERADOR

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 49 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

609 GENERATOR BEARING DRIVE END Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
“DE” CLIENTE (1 UNIT = 0,1 °C)
TEMPERATURA DE LOS COJINETES VALOR MEDIDO INT 16 (0,1 °C)
DEL GENERADOR LADO DE
ACCIONAMIENTO “DE”
G.00-TI-030[01]
610 GENERATOR BEARING NON-DRIVE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
END “NDE” CLIENTE (1 UNIT = 0,1 °C)
TEMPERATURA DE LOS COJINETES VALOR MEDIDO INT 16 (0,1 °C)
DEL GENERADOR LADO OPUESTO
AL ACCIONAMIENTO “NDE”
G.00-TI-030[02]
611 SPEED Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VELOCIDAD CLIENTE (1 UNIT = 1 r.p.m.)
E.00-SI-001 VALOR MEDIDO INT 16 (1/min)
612 GENERATOR VOLTAGE L1-N Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
TENSION GENERADOR L1-N CLIENTE (1 UNIT = 1,0 V)
VALOR MEDIDO INT 16 (1,0 V)

613 GENERATOR VOLTAGE L2-N Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
TENSION GENERADOR L2-N CLIENTE (1 UNIT = 1,0 V)
VALOR MEDIDO INT 16 (1,0 V)

614 GENERATOR VOLTAGE L3-N Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
TENSION GENERADOR L3-N CLIENTE (1 UNIT = 1,0 V)
VALOR MEDIDO INT 16 (1,0 V)

615 GENERATOR VOLTAGE L1-L2 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
TENSION GENERADOR L1-L2 CLIENTE (1 UNIT = 1,0 V)
VALOR MEDIDO INT 16 (1,0 V)

616 GENERATOR VOLTAGE L2-L3 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
TENSION GENERADOR L2-L3 CLIENTE (1 UNIT = 1,0 V)
VALOR MEDIDO INT 16 (1,0 V)

617 GENERATOR VOLTAGE L3-L1 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
TENSION GENERADOR L3 L1 CLIENTE (1 UNIT = 1,0 V)
VALOR MEDIDO INT 16 (1,0 V)

618 GENERATOR POWER Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


POTENCIA GENERADOR CLIENTE (1 UNIT = 1,0 kW)
VALOR MEDIDO INT 16 (1,0 kW)

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 50 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

619 GENERATOR REACTIVE POWER Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
POTENCIA REACTIVA GENERADOR CLIENTE (1 UNIT = 1,0 kVAr)
VALOR MEDIDO INT 16 (1,0 kVAr)

620 GENERATOR APPARENT POWER Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
POTENCIA APARENTE GENERADOR CLIENTE (1 UNIT = 1,0 kVA)
VALOR MEDIDO INT 16 (1,0 kVA)

621 GENERATOR CURRENT L1 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


CORRIENTE GENERADOR L1 CLIENTE (1 UNIT = 1,0 A)
VALOR MEDIDO INT 16 (1,0 A)

622 GENERATOR CURRENT L2 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


CORRIENTE GENERADOR L2 CLIENTE (1 UNIT = 1,0 A)
VALOR MEDIDO INT 16 (1,0 A)

623 GENERATOR CURRENT L3 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


CORRIENTE GENERADOR L3 CLIENTE (1 UNIT = 1,0 A)VALOR MEDIDO INT 16 (1,0 A)

624 GENERATOR NEUTRAL CURRENT Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
CORRIENTE DE NEUTRO DEL CLIENTE (1 UNIT = 1,0 A)
GENERADOR VALOR MEDIDO INT 16 (1,0 A)

625 BOOST PRESSURE ACTUAL VALUE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ACTUAL DE PRESION DE CLIENTE (1 UNIT = 0,01 bar)
CARGA VALOR MEDIDO INT 16 (0,01 bar)
E.08-PI-001, M.08-PI-001
626 GASMIXER POSITION Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
POSICION DEL MEZCLADOR CLIENTE (1 UNIT = 0,1 %)
DE GAS VALOR MEDIDO INT 16 (0,1 %)
E.01-M-00x
627 THROTTLE VALVE POSITION Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
POSICION CLAPETA ENTRADA GAS CLIENTE (1 UNIT = 0,1 %)
E.08-M(YCI)-00x, E.08-M(YCI)- VALOR MEDIDO INT 16 (0,1 %)
00x
628 TURBOCHARGER BYPASS POSITION Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
POSICION VALVULA DEL BYPASS CLIENTE (1 UNIT = 0,1 %)
TURBO VALOR MEDIDO INT 16 (0,1 %)
E.08-YCI-01x, M.08-YCI-01x,
E.08-YCI-10x
629 SPARE
RESERVA

630 SPARE
RESERVA

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 51 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

631 LAMBDA-TECJET Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


LAMBDA-TECJET CLIENTE INT 16 (1000 ... 2000 =
P.01-YCI-xxx Lambda 1,000 ... 2,000 )
VALOR MEDIDO
INT 16 ( 1000 ... 2000 =
Lambda 1,000 ... 2,000 )

632 SPARE
RESERVA

633 RESERVE ANALOGUE VALUE 1 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 1 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

634 RESERVE ANALOGUE VALUE 2 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 2 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

635 RESERVE ANALOGUE VALUE 3 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 3 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

636 RESERVE ANALOGUE VALUE 4 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 4 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

637 RESERVE ANALOGUE VALUE 5 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 5 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

638 RESERVE ANALOGUE VALUE 6 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 6 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

639 RESERVE ANALOGUE VALUE 7 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 7 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

640 RESERVE ANALOGUE VALUE 8 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 8 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

641 RESERVE ANALOGUE VALUE 9 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 9 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 52 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

642 RESERVE ANALOGUE VALUE 10 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 10 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

643 RESERVE ANALOGUE VALUE 11 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 11 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

644 RESERVE ANALOGUE VALUE 12 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 12 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

645 RESERVE ANALOGUE VALUE 13 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 13 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

646 RESERVE ANALOGUE VALUE 14 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 14 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

647 RESERVE ANALOGUE VALUE 15 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 15 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

648 RESERVE ANALOGUE VALUE 16 Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER
VALOR ANÁLOGICO RESERVA 16 CLIENTE (1 UNIT = ...)
VALOR MEDIDO INT 16 (...)

649 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

650 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

651 INTAKE AIR TEMPERATURE Jenbacher* CUSTOMER MEASURED VALUE


TEMPERATURA DE AIRE DE CLIENTE VALOR MEDIDO
ASPIRACION
M.05-TI-001
652 SPARE Jenbacher* CUSTOMER MEASURED VALUE
RESERVA CLIENTE VALOR MEDIDO

653 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 53 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

654 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

655 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

656 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

657 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

658 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

659 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

660 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

661 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

662 SPARE Jenbacher* CUSTOMER MEASURED VALUE


RESERVA CLIENTE VALOR MEDIDO

663 SPARE
- RESERVA
672

673 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

674 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

675 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 54 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

676 SPARE Jenbacher* CUSTOMER MEASURED VALUE 16 BIT INTEGER


RESERVA CLIENTE (1 UNIT = 1,0 °C)
VALOR MEDIDO INT 16 (1,0 °C)

677 SPARE
- RESERVA
680

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 55 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

RECEIVE DATA ITEMS FOR MODULE


Alternatively in place of the signals SSLno 15 + 28
PUNTOS DATOS DE RECEPCIÓN MODUL
Alternativo en lugar de señales SSLno 15 + 28

701

702

703

704

705

706

707

708 CLOCK PULSE CUSTOMER Jenbacher* FOR RELEASE INTERFACE No. 701 !
10" = 1 / 10" = 0 CLIENTE PARA AUTORIZACION SEÑAL N° 701 !
PULSO DE RELOJ
10" = 1 / 10" = 0

709
-
730

731

732

733
-
739

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 56 | 57
Información propiedad de INNIO*: El uso o el reenvío de los datos de esta hoja están sujetos a las limitaciones según la nota que aparece en la página de cubierta o en la segunda página.
INNIO* Proprietary Information: Use or disclosure of data contained on this sheet is subject to the restrictions on the cover or on the second page.
Interface list | LISTA DE SEÑALES

SSLno DESIGNATION FROM TO COMMENT

INDEX
SSLno DESIGNACIÓN DE A COMENTARIO

740

KEYWORD Clave : CUVILAG JMS312 D805 MTY UNIT NO. Núm.Proyect. : J AI82
MODULE TYPE Tipo módulo : 1 x JMS 312 GS-N.L
ISSUE Extendido : TPE | Aichberger, Christoph (INNIO) INDEX Indice : - Creation date Fecha de creación : 29.09.2020
CHECKED Comprobado : PAGE Hoja No : 57 | 57