PISO 1

P 26144
PD: 26144 (VA ) V:208 I = = =72.57 ( A ) ×1.25=90.71( A)
√3 × V √ 3 ×208
CONDUCTOR DE FASE Y NEUTRO
2(AWG) → 100

FACTOR DE CORRECION A UNA TEMPERATURA DE 37˚ → 0.91

I NOMINAL AJUSTADA =( 100 ) × ( 0.91 ) =91( A)

CONDUCTOR DE TIERRA
6(AWG)
PISO 2
P 44625
PD: 44625 (VA ) V:208 I = = =123.87 (A )× 1.25=154.84 ( A )
√3 × V √ 3 ×208
CONDUCTOR DE FASE Y NEUTRO
3/0(AWG) → 175

FACTOR DE CORRECION A UNA TEMPERATURA DE 37˚ → 0.91

I NOMINAL AJUSTADA =( 175 ) × ( 0.91 ) =159.25( A)

CONDUCTOR DE TIERRA
4(AWG)
PISO 3
P 118024
PD: 118024 (VA) V:208 I = = =327.60 ( A )×1.25=409.5
√3 × V √ 3 ×208
CONDUCTOR DE FASE Y NEUTRO
900(KCM) → 480

FACTOR DE CORRECION A UNA TEMPERATURA DE 37˚ → 0.91

I NOMINAL AJUSTADA =( 480 ) × ( 0.91 )=436.8( A)

CONDUCTOR DE TIERRA
3/0(AWG)

PISO 4
P 118024
PD: 118024 (VA) V:208 I = = =327.60 ( A )×1.25=409.5
√3 × V √ 3 ×208
CONDUCTOR DE FASE Y NEUTRO
900(KCM) → 480

FACTOR DE CORRECION A UNA TEMPERATURA DE 37˚ → 0.91

I NOMINAL AJUSTADA =( 480 ) × ( 0.91 )=436.8( A)

CONDUCTOR DE TIERRA
3/0(AWG)

PISO 5
P 56390
PD: 56390(VA) V:208 I = = =156.52( A) ×1.25=195.65
√3 × V √ 3 ×208
CONDUCTOR DE FASE Y NEUTRO
250(KCM) → 230

FACTOR DE CORRECION A UNA TEMPERATURA DE 37˚ → 0.91

I NOMINAL AJUSTADA =( 230 ) × ( 0.91 ) =209.3( A)

CONDUCTOR DE TIERRA
2(AWG)
POTENCIA DEMANDADA EN EL BLOQUE UNO=BLOQUE DOS = BLOQUE
TRES = 363207 (VA)
P 363207
V=208 I = = =1008.16 ( A ) ×1.25=1260.2( A)
√3 × V √ 3 ×208
CONDUCTOR DE FASE Y NEUTRO
500(KCM) → 350

FACTOR DE CORRECION A UNA TEMPERATURA DE 37˚ → 0.91

I NOMINAL AJUSTADA =5 × ( 350 ) × ( 0.91 )=1592.5( A)


CONDUCTOR DE TIERRA
1/0(AWG)

PISO 1
P 26144
I= = =72.57 ( A ) ×1.25=90.71( A)
√3 × V √ 3 ×208
V = 208
A = 8(MT) = 0.008(KM)
CONDUCTOR DE FASE Y NEUTRO 2(AWG)

√ 3 ∙(1.05)∙(0.008)∙(90.71)
%= × 100=0.63 %
208
PISO 2
P 44625
I= = =123.87 (A )× 1.25=154.84 ( A )
√3 × V √ 3 ×208
V = 208
A = 11.5(MT) = 0.0115 (KM)
CONDUCTOR DE FASE Y NEUTRO 3/0(AWG)

√ 3 ∙( 0.427)∙(0.0115)∙(154.84)
%= ×100=0.63 %
208

PISO 3
P 118024
I= = =327.60 ( A )×1.25=409.5
√3 × V √ 3 ×208
V = 208
A = 15(MT) = 0.015 (KM)
CONDUCTOR DE FASE Y NEUTRO 900(KCM)

√ 3 ∙( 0.075)∙(0.015)∙(409.5)
%= ×100=0.38 %
208

PISO 4
P 118024
I= = =327.60 ( A )×1.25=409.5
√3 × V √ 3 ×208
V = 208
A = 18.5(MT) = 0.0185 (KM)
CONDUCTOR DE FASE Y NEUTRO 900(KCM)

√ 3 ∙( 0.075)∙(0.0185)∙(409.5)
%= ×100=0.47 %
208

PISO 5
P 56390
I= = =156.52( A)×1.25=195.65
√3 × V √ 3 ×208
V = 208
A = 22(MT) = 0.022 (KM)
CONDUCTOR DE FASE Y NEUTRO 250(KCM)

√ 3 ∙( 0.279)∙(0.022)∙(195.65)
%= ×100=1.0 %
208

(%) = (0.63+0.63+ 0.38+0.47+1.0 ¿=3.11 %


COMO EL PORCENTAJE DE REGULACION ES MAYOR AL 3% SE REALIZA
UN CAMBIO DE CONDUCTOR POR UNO QUE TENGA MAYOR SECCION
TRASNVERDAL

√ 3 ∙( 0.233)∙(0.022)∙(195.65)
%= ×100=0.83 %
208

(%) = (0.63+0.63+ 0.38+0.47+0.83 ¿=2.94 %

EL PORCENTAJE DE REGULACION ES MENOR AL 3% POR LO QUE SE


CUMPLE LA NORMA

BLOQUE 1 = BLOQUE 2 = BLOQUE 3


PD: 363207 (VA)
P 363207
I= = =1008.161( A)×1.25=1260.201
√3 × V √ 3 ×208
SE COLOCAN 5 CONDUCTORES EN PARALELO
1260.201
=252.040
5
SE ESCOGE EL CONDUCTOR DE FASE Y NEUTRO
500 MCM → ( 350 A )∗( 0.91 )=318.5( A)
SE ESCOGE EL CONDUCTOR DE TIERRA
1/0 AWG
TIPO DE CANALIZACION
PISO 1
3 F × ( 2 AWG ) +1 T (6 AWG) THWN-2 90
TUBERIA ESCOGIDA: tubo Conduit rígido de PVC Schedule 80 (2 pulgadas)

PISO 2
3 F × ( 3 /0 AWG )+ 1T (4 AWG) THWN-2 90
TUBERIA ESCOGIDA: tubo Conduit rígido de PVC Schedule 80 (3 pulgadas)

PISO 3
3 F × ( 900 KCM )+1 T (3/0 AWG) THWN-2 90

TUBERIA ESCOGIDA: 2 tubos Conduit rígido de PVC Schedule 80 (4 pulgadas)

PISO 4
3 F × ( 900 KCM )+1 T (3/0 AWG) THWN-2 90
TUBERIA ESCOGIDA: 2 tubos Conduit rígido de PVC Schedule 80 (4 pulgadas)

PISO 5
3 F × ( 250 KCM ) +1 T (2 AWG) THWN-2 90
TUBERIA ESCOGIDA: 2 tubos Conduit rígido de PVC Schedule 80 (2 pulgadas)