TECHNICAL GUIDE ®
SINGLE PACKAGE
AIR-TO-AIR
HEAT PUMPS
B3CH 036, 048 & 060 (208/230, 460V)
B5CH 036 & 060 (575V), B6CH 048
3, 4 AND 5 NOMINAL TONS
(10 SEER)
SUNLINE 2000
DESCRIPTION
YORK Sunline 2000 Heat Pumps are convertible single CONVERTIBLE AIRFLOW DESIGN -- Both the side and
package units with a common cabinet and common roof curb bottom duct openings are covered when they leave the factory.
for the 3, 4 and 5 ton sizes. The units were designed for If a side supply/side return is desired, you simply remove the
residential and light commercial applications. They can easily two side duct covers from the outside of the unit and discard
be installed on a roof curb, slab, roof jack or frame. them. If a bottom supply/return is desired, you simply remove
the two bottom duct covers and discard them. No panel cutting
All units are self--contained and assembled on rigid full or swapping is required! Convertible airflow design allows
perimeter base rails allowing for 3--way fork lift access and maximum field flexibility and minimum inventory.
overhead rigging. Every unit is completely charged, wired,
piped and tested at the factory to provide for a quick and easy FACTORY--INSTALLED OPTIONS -- Economizers can be
field installation. installed at the factory. They are shipped installed and wired. The
outdoor air hood needs only to be field assembled and installed.
The units are available with supplemental electric heaters as
field--installed accessories. Adjustable belt--drive blowers are available on most models
from the factory for complete air flow flexibility.
Both down and side discharge airflows are available without
having to swap panels. The installer simply removes the duct FIELD--INSTALLED ACCESSORIES -- Accessories were
covers for the desired configuration. Economizers may be designed for quick and easy installation. The motorized
used on either side or down discharge applications with no damper and economizers simply slide in and electrical
modifications required. connections are made by modular plugs. Electric heaters
mount easily and knockouts are provided in the internal
All models include a 1--year limited warranty on the complete partitions to connect the elements to the control box single
unit. Compressors and electric heater elements each carry an point kit.
additional 4--year warranty.
The motorized air damper includes a slid--in/plug--in damper
assembly with a rainhood and filters. The outdoor air dampers
FEATURES open when the indoor fan motor is energized. The damper is
capable of providing 0% through 100% of outdoor return air
CONTROLS -- These heat pumps utilize a unique time--
opening.
temperature defrost circuit which adjusts the time between
defrost cycles based on the outdoor temperature to provide The manual outdoor damper provides 0% through 35% or 0%
optimal comfort control and ensure reliable operation. The through 100% of return air opening (field adjustable). Designed
ambient--modified, time--temperature defrost control extends the for duct mounted side or bottom supply/return applications.
time below 35°F and shortens the time above 35°F. The nominal Includes rain hood assembly and filter.
defrost times are field adjustable to 50, 80 and 110 minutes. The
defrost time is initiated and terminated by a liquid line control with The 14" high roof curb is shipped knocked down. A roof curb
a 10 minute override limit built into the defrost control. deck is not required because the bottom of the unit is insulated.
COMMON FOOTPRINT/COMMON CABINET -- The 3, 4 and WIDE RANGE OF INDOOR AIRFLOWS -- All models operate
5 ton units all share the exact same cabinet -- and therefore the over a wide range of design conditions with a 3--speed direct--
same roof curb. You now have the flexibility of setting one curb drive fan motor. Belt--drive blowers are also available on all
and, after the internal load has been determined, placing the models.
proper tonnage unit on that curb.
FULL PERIMETER BASE RAILS -- The permanently
HIGH EFFICIENCY -- All units have a minimum SEER of 10, a attached base rails provide a solid foundation for the entire unit
COP of 3.0 (high) and 2.0 (low) and an HSPF as high as 7.3. and protect the unit during shipment. The rails provide fork lift
These efficiencies exceed all legislated minimum levels and access from 3 sides and rigging holes are also provided so that
provide low operating costs. an overhead crane can be used to place the units on a roof.
036-21564-002-A-0404
FEATURES - CONT'D.
SYSTEM PROTECTION -- Crankcase heaters and internal field supplied electrical disconnect switch. Utility connections
compressor protection are standard on all compressors. Every can be made quickly and with a minimum amount of field labor.
unit has a liquid line filter--drier, low pressure switch, high
pressure switch and high temperature switch to protect all SIMPLE CONTROL CIRCUIT -- Mate--n--lock plug connectors
system components. A suction line freezestat is supplied on all are used where line and low voltage wires pass thru internal
three--phase units to protect against loss of charge and coil bulkheads. This allows for easier troubleshooting and
frosting due to low economizer outdoor air temperature while component replacement. The electrical control box is not
the compressor is running. All units will provide cooling at located in the compressor compartment so the access cover
ambient temperatures down to 45°F. can be removed for troubleshooting without affecting the
normal system operating pressures.
UTILITY CONNECTIONS MADE EASY -- Electric utility
knockouts are provided in the unit underside as well as the side AIR FILTERS -- Units come standard with 1" throwaway filters.
of the unit. A clearly identified location is provided to mount a The unit filter racks can accommodate 1" or 2" filters without
any modifications.
DIRECT DRIVE
BLOWER MOTOR
(Belt-Drive Option
also available on some
models)
TABLE OF CONTENTS
RATINGS
CAPACITY RATINGS
ARI RATINGS (SEE NOTE 1) NOMINAL
SOUND HEATING CAPACITY ELECTRIC HEAT CAPACITY
MODEL COOLING (SEE NOTE 3)
BCH PERFORMANCE RATING
HSPF 47°F 17°F KW
(SEE NOTE 2)
MBH SEER EER bels MBH COP MBH COP 240V 480V 600V
036 39 10.00 9.20 8.6 7.3 39.0 3.0 23.0 2.1 5, 7, 10, 15 & 20 7,10,15 & 20 10, 15 & 20
048 48 10.20 9.25 8.6 6.7 48.0 3.0 26.4 2.0 5, 7, 10, 15 & 20 7,10,15 & 20 10, 15 & 20
060 59 10.00 9.20 8.4 7.0 59.0 3.0 36.0 2.1 5,7,10,15,20 & 30 7,10,15,20 & 30 10,15,20 & 30
NOTE: 1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
2. Rated in accordance with ARI Standard 270.
3. Heaters available as accessories - all with single point power supply.
SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input
in watt-hours during the same period.
EER = Energy Efficiency Ratio-the cooling capacity in BTU's per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt
(BTUH/watt).
COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supplementary
resistance (BTU's per hour) divided by the total electric input (watts) x 3.412.
NOTE: These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The dBA values provided are to be used for reference only.
Calculation of dBA values cover matters of system design and the fan manufacturer has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee
requiring a dBA value or sound data in any other form than sound power level ratings.
PHYSICAL DATA
BASIC UNITS
BCH
MODELS
036 048 060
CENTRIFUGAL BLOWER (Dia. x Wd. in.) 12 x 10 12 x 10 12 x 10
SUPPLY AIR 1 3
FAN MOTOR HP (DIRECT-DRIVE) 2 4 1
BLOWER
FAN MOTOR HP (BELT-DRIVE) 1.5 1.5 1.5
ROWS DEEP 4 3 3
INDOOR
FINS PER INCH 16 15 15
COIL
FACE AREA (Sq. Ft.) 4.3 5.1 5.1
PROPELLER DIA. (in.) 22 22 24
OUTDOOR 1 1 1
FAN MOTOR HP 3 2 2
FAN
NOM. CFM TOTAL 4300 4200 4500
ROWS DEEP 1 1 1
OUTDOOR
FINS PER INCH 20 20 20
COIL
FACE AREA (Sq. Ft.) 17.1 17.1 17.1
AIR QUANTITY PER UNIT (15" x 20" x 1") 2 2 2
FILTERS QUANTITY PER UNIT (14" X 25" X 1") 1 1 1
(SEE NOTE) TOTAL FACE AREA (sq. ft.) 6.6 6.6 6.6
CHARGE REFRIGERANT 22 (lbs./oz.) 7/12 9/2 8/4
COMPRESSOR HERMETIC, RECIPROCATING (Qty) 1 1 1
NOTE: Filter racks can accommodate 1" or 2" thick filters.
HEATING CAPACITIES
BCH036
RET. AIR CAP OUTDOOR AIR TEMPERATURE, °F (72% RH)
CFM
°F & KW -10 0 10 20 30 40 50 60
MBH 13.1 16.4 23.5 29.1 30.2 41.7 47.0 48.2
55
KW 2.9 3.0 3.2 3.3 3.5 3.7 3.8 3.9
MBH 11.9 15.0 21.5 26.7 27.7 38.2 43.1 44.1
1750 70
KW 3.0 3.1 3.4 3.4 3.6 3.8 3.9 4.1
MBH 10.9 13.6 19.6 24.3 25.2 34.8 39.3 40.2
80
KW 3.1 3.2 3.4 3.5 3.8 3.9 4.1 4.2
MBH 12.4 15.5 22.5 27.7 28.7 39.6 44.7 45.8
55
KW 2.7 2.9 3.0 3.1 3.3 3.5 3.6 3.7
MBH 11.4 14.1 20.3 25.2 26.1 36.1 40.7 41.6
1400 70
KW 2.9 3.0 3.2 3.3 3.5 3.7 3.8 3.9
MBH 10.4 13.1 18.0 23.2 24.2 33.3 37.6 38.5
80
KW 3.0 3.1 3.2 3.4 3.6 3.8 3.9 4.0
MBH 11.8 14.8 21.3 26.5 27.5 37.8 42.7 43.7
55
KW 2.7 2.8 3.0 3.1 3.3 3.4 3.5 3.6
MBH 10.8 13.5 19.4 24.0 24.9 34.4 38.8 39.7
1200 70
KW 2.9 3.0 3.1 3.3 3.4 3.6 3.7 3.8
MBH 9.9 12.4 17.8 22.0 22.9 31.5 35.6 36.5
80
KW 2.9 3.1 3.2 3.4 3.5 3.7 3.8 3.9
MBH 11.2 14.1 20.3 25.2 26.1 35.9 40.6 41.6
55
KW 2.6 2.7 2.9 3.0 3.3 3.3 3.5 3.5
MBH 10.2 12.8 18.5 22.8 23.6 32.7 36.9 37.8
1050 70
KW 2.8 2.9 3.0 3.2 3.3 3.5 3.6 3.7
MBH 9.3 11.7 16.7 20.7 21.5 29.8 33.6 34.4
80
KW 2.8 3.0 3.1 3.3 3.4 3.6 3.7 3.8
BCH048
MBH 12.3 17.3 22.5 28.2 36.3 44.5 53.8 61.6
55
KW 3.4 3.5 3.6 3.6 3.8 4.0 4.6 5.2
MBH 11.8 16.6 21.6 27.1 34.9 42.8 51.7 59.2
2000 70
KW 3.5 3.6 3.8 3.8 4.0 4.2 4.8 5.4
MBH 10.9 15.3 19.9 24.9 32.1 39.4 47.6 54.5
80
KW 3.6 3.7 4.0 4.0 4.1 4.4 5.0 5.7
MBH 12.1 17.0 22.0 27.7 34.5 42.3 51.2 58.6
55
KW 3.3 3.4 3.5 3.6 3.6 3.8 4.4 5.0
MBH 11.6 16.3 21.2 26.6 33.2 40.7 49.2 56.3
1600 70
KW 3.4 3.5 3.6 3.7 3.8 4.0 4.6 5.2
MBH 10.7 15.0 19.5 24.5 30.5 37.4 45.3 51.8
80
KW 3.5 3.6 3.8 3.9 4.0 4.2 4.8 5.4
MBH 10.9 15.3 19.9 24.9 31.7 38.9 47.0 53.8
55
KW 3.1 3.2 3.3 3.4 3.5 3.7 4.2 4.8
MBH 10.5 14.7 19.1 24.0 30.5 37.4 45.2 51.7
1200 70
KW 3.2 3.3 3.4 3.5 3.6 3.8 4.4 5.0
MBH 9.6 13.5 17.6 22.0 28.1 34.4 41.6 47.6
80
KW 3.3 3.4 3.5 3.6 3.8 4.0 4.6 5.2
BCH060
MBH 18.2 24.7 31.1 38.4 45.6 55.4 64.7 75.6
55
KW 5.0 5.1 5.2 5.3 5.3 5.6 5.9 6.5
MBH 17.5 23.7 29.9 37.0 43.9 53.3 62.2 72.7
2500 70
KW 5.2 5.3 5.4 5.5 5.6 5.9 6.2 6.8
MBH 16.1 21.8 27.5 34.0 40.4 49.0 57.2 66.9
80
KW 5.4 5.6 5.7 5.8 5.9 6.0 6.5 7.2
MBH 18.0 24.4 30.8 38.1 45.0 54.7 63.9 74.7
55
KW 4.7 4.8 4.9 5.0 5.3 5.5 5.8 6.4
MBH 17.3 23.5 29.6 36.6 43.3 52.6 61.4 71.8
2000 70
KW 4.9 5.0 5.1 5.2 5.5 5.8 6.1 6.7
MBH 15.9 21.6 27.2 33.7 39.8 48.4 56.5 66.1
80
KW 5.1 5.3 5.4 5.5 5.8 6.1 6.4 7.0
MBH 16.2 22.0 27.8 34.3 41.4 50.2 58.7 68.6
55
KW 4.5 4.6 4.7 4.8 5.0 5.3 5.5 6.1
MBH 15.6 21.2 26.7 33.0 39.8 48.3 56.4 66.0
1500 70
KW 4.7 4.8 4.9 5.0 5.2 5.5 5.8 6.4
MBH 14.4 19.5 24.6 30.4 36.6 44.5 51.9 60.7
80
KW 4.9 5.0 5.1 5.2 5.5 5.8 6.1 6.7
*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER
THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.
*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER
THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.
*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER
THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.
SUPPLY AIR BLOWER PERFORMANCE - BCH036, 048 & 060 with Direct-Drive
230 / 460 / 575 VOLTS - SIDE DUCT APPLICATIONS
Available External Static Pressure - IWG*
MODEL MOTOR
0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
BCH SPEED
CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts
HI - - - - - - 1720 825 1665 795 1600 765 1540 735 1490 700 1380 670
036 MED 1660 850 1630 820 1590 780 1550 750 1500 720 1450 690 1400 665 1360 650 1270 610
LOW 1470 750 1440 725 1410 700 1370 675 1330 650 1290 625 1250 610 1220 600 1130 560
HI - - - - 2000 1010 1950 975 1905 945 1840 910 1770 825 1660 825 1530 775
048 MED 1810 910 1780 880 1740 850 1700 825 1665 800 1620 775 1560 740 1480 700 1390 660
LOW 1635 810 1610 780 1580 760 1555 740 1540 730 1510 715 1460 690 1400 660 1300 615
HI - - - - 2500 1400 2420 1350 2340 1300 2260 1250 2160 1190 2060 1135 1925 1065
060 MED 2390 1350 2350 1300 2300 1255 2245 1210 2190 1165 2130 1120 2065 1075 1990 1030 1900 970
LOW 2270 1320 2230 1270 2190 1220 2145 1170 2090 1110 2030 1070 1960 1020 1890 970 1810 920
NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.
*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER
THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.
STATIC RESISTANCES
EXTERNAL STATIC PRESSURE DROP
RESISTANCE, IWG
DESCRIPTION CFM
1000 1200 1400 1600 1800 2000 2200 2400 2600
Economizer1, 2 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23
5 - 15 KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16
Electric Heaters1
20 - 30 KW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20
Bottom Duct Connections1 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.14 0.16
1
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
2
The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM
during full economizer operation.
3
4
1
24-volt thermostat with subbase:
TO REMOTE SENSOR
—2TH11700224 for manual changeover. 2TH04702224 IF USED
—2TH11704124 for automatic changeover.
2
Only required on units with supplemental electric heat.
POWER WIRING
1
Dual element, time delay type
KW Cap
2 Nominal Voltage Voltage
Standard circuit breakers may be used in Canada and on applications Multipier
over 60 amps where the heaters are separately fused.
Electric Heat 208 208 1.00
Correction
240 230 0.92
Factors
* These electric heaters DO NOT include a fuse box. If a fuse box is
480 460 0.92
required to meet a local code ((eg., Chicago), the following fuse
block accessories are available for field installation. 600 575 0.92
OUTDOOR COIL
(Direct-Drive Units)
RETURN AIR
SUPPLY AIR
OUTDOOR
OUTDOOR
AIR
(Economizer)
CLEARANCES
Front 24"
12" (Less Economizer)
Back 36" (With Economizer or Fixed
Air/Motorized Air Damper)
24" (Less Economizer)
Left Side (Filter Access)
36" (With Economizer)
Right Side (OD Coil) 24"
Below Unit1 20"
Above Unit2 72" (For Outdoor Air Discharge)
NOTE:
Units and ductwork are approved for zero clearance to combustible materials when
2 7 -1 /2 1 -5 /8
3 “ CONDENSATE
4
DRAIN
(must be trapped)
2 7 -1 /2
1 9 -3 /4
REAR VIEW 1 9 -1 /2 4 4 -7 /8
DETAIL “A” L.H. END VIEW
UNIT WITH ECONOMIZER RAINHOOD
2 7 -1 /2 7 -1 /4
2 7 -1 /2
1 0 -1 /4
30 7 8 3 -1 /2
1 9 -1 /8
8 -1 /4
"A " 4 4 -7 /8
R E A R V IE W L .H . E N D V IE W 4 -3 /8
D IM E N S IO N "A "
F IX E D
O U T D O O R 1 2
A IR D A M P E R
M O T O R IZ E D
D A M P E R 1 6 -1 /2
DETAIL “B”
UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
DUCT SIZES:
Supply Air = 19" x 19"
Return Air = 19" x 19"
FIELD--INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER -- FUSE BLOCK KITS -- These kits have a fuse box with a fuse
Includes a slide--in/plug--in damper assembly with fully block and fuses. They're available for all 460--3--60 volt
modulating spring return motor actuator capable of introducing heaters and 208/230--3--60 volt heaters 7 KW and smaller.
up to 100% outdoor air, one outdoor air electronic enthalpy
ROOF CURB -- This 14" high full perimeter roof curb is
sensor and a rainhood with filters. The rainhood is painted to
knocked down for field assembly and contains duct supports
match the basic unit and must be field--assembled before
that can easily be shifted for the desired unit duct arrangement.
installation. Economizer dampers are 2% low leakage type.
No deck is required because the unit underside is insulated.
DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER --
START ASSIST KIT (Standard on 4 ton units) -- Provides
Includes the same damper system and rainhood with filters as increased starting torque for 3 and 5 ton single phase units in
described for a single enthalpy economizer above except this areas with low voltage conditions. It contains a 12.5 OHM
accessory contains two enthalpy sensors. It uses a differential PTCR temperature resistor with a support clip and hardware
enthalpy control that compares the outdoor air versus the for mounting.
return air. The logic module then optimizes the economizer
ANTI--RECYCLE TIMER -- A timer to prevent the unit
operation for additional savings over the single input compressor from short cycling. It assures 5 minutes off time
economizer. between compressor cycles.
MOTORIZED AIR DAMPER -- Includes a slid--in/plug--in OUTDOOR COIL GUARD -- Consists of grille--type sections
damper assembly with a rainhood and filters. The outdoor air for assembling over the outdoor coil to protect it from damage.
dampers open when the indoor fan motor is energized. The
damper is capable of providing 0% through 100% of outdoor WALL THERMOSTAT -- The units are designed to operate
return air opening. with 24--volt electronic and electro--mechanical thermostats.
All units can operate with single stage heat/single stage cool
MANUAL OUTDOOR DAMPER -- Provides 0% through 35% thermostats -- with or without the economizer. To obtain
or 0% through 100% of return air opening (field adjustable). maximum economizer operating savings, a two stage cooling
Designed for duct mounted side or bottom supply/return thermostat should be used. To obtain two stage cooling
applications. Includes rain hood assembly and filter. operation, a jumper wire must be removed on the low voltage
relay board. (See unit wiring diagram.)
ELECTRIC HEATERS -- Include nickel chromium elements, a
terminal block, fuses (where required by UL), all the necessary OUTDOOR THERMOSTAT -- A 24--volt thermostat providing
connectors and hardware. All heaters utilize single point power two stages of control for units equipped with supplemental
supply hookup. Capacities from 5 KW thru 30 KW heating are electric heaters.
available.
TYPICAL APPLICATIONS
ROOF JACK
INSTALLATION
ROOF CURB
INSTALLATION
SLAB ON GROUND
INSTALLATION
FIELD-SUPPLIED
DISCONNECT
SWITCH
ROOF CURB
CONDENSATE
TRAP
SUPPLY AIR
DUCT
TO CONTROL WIRING
POWER TO INDOOR RETURN AIR
SUPPLY THERMOSTAT DUCT
MECHANICAL SPECIFICATIONS
GENERAL DESCRIPTION
Units shall be factory--assembled, single packaged Heat 2. Fan wheel shall be double--inlet type with forward--
Pumps, designed for outdoor mounted installation. Units shall curved blades, dynamically balanced to operate
have minimum SEER ratings of 10.0. They shall have built in smoothly throughout the entire range of operation.
field convertible duct connections for down discharge Airflow design shall be constant air volume.
supply/return or horizontal discharge supply/return, and be
3. Bearings shall be sealed and permanently lubricated for
available with factory installed options or field installed longer life and no maintenance.
accessories.
OUTDOOR FAN ASSEMBLY
The units shall be factory wired, piped, charged with R--22
refrigerant and factory tested prior to shipment. All unit wiring 1. The outdoor fan shall be of the direct--driven propeller
shall be both numbered and color coded. Enclosed in each unit type, discharge air vertically, have aluminum blades
shall be a factory test log sheet consisting of the unit tested riveted to corrosion resistant steel spider bracket and
pressures, temperatures and amps, as tested prior to shall be dynamically balanced for smooth operation.
shipment.
2. The outdoor fan motor shall be totally enclosed with
All units shall be manufactured in a facility certified to ISO 9001 permanently lubricated bearings and internally protected
standards, and the cooling & heating performance shall be against overload conditions.
rated in accordance with DOE and ARI test procedures. Units REFRIGERANT COMPONENTS
shall be listed under UL 1995/CAN/CSA No. 236--M90
conditions. 1. Compressors:
UNIT CABINET A. Shall be fully hermetic type, direct drive, internally pro-
tected with internal high--pressure relief and over tem-
1. Unit cabinet shall be constructed of G90 galvanized perature protection. The hermetic motor shall be
steel, with exterior surfaces coated with a non--chalking, suction gas cooled and have a voltage range of + or --
powered paint finish, certified at 750 hours salt spray test 10% of the unit nameplate voltage.
per ASTM--B117 standards.
B. Shall have internal isolation and sound muffling to mini-
2. Indoor blower section shall be insulated with up to 1" mize vibration and noise, and be externally isolated on
thick insulation, coated on the air side. Aluminum foil a dedicated, independent mounting.
faced insulation shall be used in the furnace compart-
ment and be fastened with ridged fasteners to prevent in- 2. Coils:
sulation from entering the air stream.
A. Evaporator and condenser coils shall have aluminum
3. Cabinet panels shall be “large” size, easily removable for plate fins mechanically bonded to seamless internally--
enhanced copper tubes with all joints brazed. Special
servicing and maintenance. Phenolic coating shall be available as a factory option.
4. Full perimeter base rails shall be provided to assure reli-
able transit of equipment, overhead rigging, fork truck ac- B. Evaporator and Condenser coils shall be of the direct
expansion, draw--thru design.
cess and proper sealing on roof curb applications.
3. Refrigerant Circuit and Refrigerant Safety Components
5. Disposable 1" filters shall be furnished and be accessible shall include:
through a removable access door, sealed air tight. Units
filter track shall be designed to accommodate either 1" or A. Independent fixed--orifice expansion devices.
2" filters.
B. Filter drier/strainer to eliminate any moisture or foreign
6. Fan performance measuring ports shall be provided on matter.
the outside of the cabinet to allow accurate air measure-
ments of evaporator fan performance without removing C. Accessible service gage connections on both suction
panels or creating air by--pass of the coils. and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
7. Units vertical discharge and return duct configuration troubleshooting, without losing charge.
shall be designed to fit between standard 24" O.C.
beams without modification to building structure, duct D. The refrigeration system shall provide at least 15° F of
work and base unit. liquid sub--cooling at design conditions.
8. Condensate pan shall be internally sloped and conform E. Unit shall have a suction line accumulator.
to ASHARE 62--89 self--draining standards. Condensate
connection shall be a minimum of 3/4" I.D. female and be 4. Unit Controls:
a ridged mount connection.
A. Unit shall be complete with self contained low--voltage
INDOOR (SUPPLY) FAN ASSEMBLY control circuit protected by a resetable circuit breaker
fuse on the 24 volt transformer side.
1. Fan shall be direct drive, multi--speed, or a factory in-
stalled belt drive, adjustable--pitch motor pulley option. B. Unit shall incorporate a lock--out circuit which provides
Job site selected (BHP) brake horse power shall not ex- reset capability at the space thermostat or base unit,
ceed the motors nameplate horse power rating, plus the should any of the following standard safety devices trip
service factor. Units shall be designed not to operate and shut off compressor:
above service factor.
7. ANTI--RECYCLE TIMER -- Assures 5--minute off--time 2. TECHNICOAT PHENOLIC COATED COND. COIL
between compressor cycles.
3. ELECTRONIC ENTHALPY ECONOMIZER
8. ELECTRIC HEAT -- Slide--in design, provides single
point power and ranges from 5 to 30 KW. 4. DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER