1 2 3 4 5 6 7 8 9 10 11 12

F G/2 G/2 F 10 45°


1+1-BARRA Ø22 CON RESALTES
ACERO A630-420H
CON EPÓXICO HIT-RE500 V3

H/2
A HILTI Ó EQUIVALENTE A
(NOTA 2)

250
TABLA 1
ØA

H/2
Ø NOMINAL DIMENSIONES

Ød
CAÑ. A

Ø8
B C Ød E H PESO (kg) D2

D2 /2
110
3/4" 35 29 1/4" 40 60 0,04
PVC e=5 55 S-202 90

E
1" 42 35 1/4" 40 60 0,04 TIP.

44
ØA 500 (NOTA 4) L 80x7.07 (TABLA 2)
2" 76 64 1/2" 60 109 0,23 S-101 4
(MIN.)

SEGÚN DISEÑO
3" 106 94 1/2" 50 138 0,27 (TABLA 1) L8

L8x7.07 (TIP.)
C d

75
e
4" 136 120 5/8" 60 171 0,71

200
MURO 190 PERFs. Ø27

D1
B CHIMENEA

75
6" 192 176 5/8" 60 217 0,92
(TIPO) P/PERNOS Ø3/4"

30
TIP. 30 130
8" 248 228 3/4" 70 283 1,51 CAÑ. Ø1"
B (NOTA 4)
PL.10 e=10mm
S-101 MORTERO DE

500
B 2-PERF'S Ø27 L 80x7.07
TABLA 2 NIVELACIÓN

190
130
56
PERNO "U" DIMENSIONES
P/BARRAS Ø22
TIP.
B
TIP.

D1 /2
Ø NOMINAL PLACA BASE (NOTA 4)
CAÑ. A Ød Ød SECCIÓN A (NOTA 4)

10
B C e F G H PESO (kg) PB-11C 67 56
B L VARIABLE 500 AGUJERO PERNO PERFIL
(TABLA 1) (MIN.) DET. 1 3/4 32 27 8 1/4" 3 15 80 30 0,13
S/ESC. - L 80x7.07
TIP.
1" 38 33 8 1/4" 3 15 86 30 0,15
PB-11C
PERFIL VAR. VAR.
L10x11.7 1 1/2" 54 48 12 3/8" 3 20 110 35 0,19 MORTERO NIVELACIÓN
e=25
PLACA BASE
2" 66 60 12 3/8" 4 20 120 35 0,31 PESO: 2.80 kg
2 1/2" 78 73 12 3/8" 4 20 146 50 0,53 A SM-06 PERNO QUIM. 3/4"
(TABLA 10)
3" 95 89 14 3/8" 4 20 150 50 0,59
S-101 BARRA Ø 22 4" 120 114 14 1/2" 5 25 184 75 1,39
-
SOPORTE MARCO EN TIRO SE-04
(TABLA 1) ACERO A630-420H ESPACIAMIENTO MÁXIMO: 3m ENTRE SOPORTES
B
SOLDABLE TIPO CAP-SOL
CON EPÓXICO S-202 SOPORTE ESTRUCTURAL TIPO PEDESTAL
HIT RE 500 V3 DE PESO: 9.11 kg
L=2B HILTI O EQUIVALENTE
(NOTA 2)
SOPORTE ABRAZADERA C
SP-419
PERFIL B
SOPORTE PERFIL VOLADIZO EN GALERÍA TIP.
(NOTA 4) TABLA 4
ESPACIAMIENTO MÁXIMO: 3m ENTRE SOPORTES

8
TIP.

Ø1

Ø1
C (NOTA 4) B/2
ØA S-101 ØA
S-101

ØF
DN B PERFIL B

D
PERFIL B BARRA Ø22 ACERO A630-420H
PERFIL B (TABLA 4) ØA
PVC e=5mm TABLA 4 TABLA 4 SOLDABLE TIPO CAP-SOL (S.I.C.)
F
TABLA 4 (NOTA 2)

C
B
DIMENSIONES
20°

B/2
120°
30°

DIA. NOMINAL PERFIL A PERFIL B H e F PESO (kg)


ØA
PL=G 50 B 50 3" A 4" C 12.5x10.1 L 8x7.07 1200 10 300 14,24 50 B 50 TIP. (NOTA 4) D
C

PVC e=5mm C D
H (MAX.)

H (MAX.)
(TABLA 1) 6" A 10" C 15x11.0 L 10x11.70 1200 12 350 17,89 (TABLA 1) E
B
TABLA 5 50 DETALLE 1

Ø18
TIP.
(NOTA 4)
TABLA 5
TABLA 5
PERFIL A TIP.
(NOTA 4)
PERFIL A TIP.
(NOTA 4)
PB-01 S/ESC. -
(TABLA 4) (TABLA 4)

70 60
ØB
PLACA BASE

130
50
TABLA 5
H*

DE NIVELACIÓN

TIP. PL.=e PERNO TABLA 6


MORTERO

F/2
25

20
(NOTA 4) ESPÁRRAGO Ø5/8"
TIP. TIPO ØA B C D E ØF Ø PESO
ØD PLACA BASE (NOTA 4) F (Aguj.) Perno (kg)
EL DISEÑO DE ESTE PLANO, INCLUYENDO PATENTES, INFORMACIÓN DE TECNOLOGÍAS DESARROLLADAS POR CODELCO O SUS ASOCIADOS ES CONFIDENCIAL , SU USO, IMPRESIÓN Y REPRODUCCIÓN DEPENDE DEL ACUERDO CONTRACTUAL DEL PROYECTO DIAMANTE.

PB-01 PB-01 3" 280 220 30 16 18 5/8" 9,9


PERNO QUIM. Ø5/8" PERFIL METÁLICO TABLA 8
SP-208 Ø CAÑERÍA PERFIL S máx.
SP-108
ESTE PLANO NO DEBE SER USADO TOTAL O PARCIALMENTE, NI LOS MATERIALES MENCIONADOS, NI EL DISEÑO PARA NINGÚN PROPÓSITO FUERA DEL PROYECTO DIAMANTE A MENOS QUE SE OBTENGA PERMISO ESCRITO DE CODELCO Y SUS ASOCIADOS.

SOPORTE TIPO PUNTAL 1" L5x2,93 800


E
MORTERO NIVELACIÓN SOPORTE TIPO PUNTAL ESPACIAMIENTO MÁXIMO: 3m ENTRE SOPORTES BARRA Øb (TABLA 10)
2" L5x2,93 800
e=25mm ACERO A630-420H 3" L6,5x3,88 600
CON EPÓXICO HIT-RE500 V3 4" L6,5x4,78 800
PERNO QUIM. Ø5/8" COLUMNA HILTI Ó EQUIVALENTE
PERNO ESPÁRRAGO Øb 6" L6,5x4,78 400
PROYECTADA (NOTA 2)
1+1-BARRA Ø22 CON RESALTES (TABLA 9)
SP-06 ACERO A630-420H PERFIL
(TABLA 8)
8" L8x7,07 450
CON EPÓXICO HIT-RE500 V3 e 10" L10x11,7 600
SOPORTE PUNTAL - APOYO HILTI Ó EQUIVALENTE ØB 50 ØB 12" L10x11,7 450
PILAR /
MARCO REFUERZO *GRAMILES DEBEN SER AL EJE DE LAS ALAS
MURO GALERÍA S-101
TABLA 5
(TABLA 1)
DIMENSIONES S-101 (TIP.) C20x11.7
DN (pulg) ØB C D F H* PESO (kg) (TABLA 1)
S-101 (TIP) TABLA 9
3" 2" 130 1 1/2" 80 x 50 x 6 1000 1,10 PERFIL
(TABLA 1)
VAR.

PERNOS / PLACA BASE


50

4" 3" 165 2 1/2" 107 x 75 x 6 1000 2,60 (TABLA 8) SEGÚN


Ø CAÑERÍA Øb Ø b1 B L e
6" 3" 180 2 1/2" 160 x 75 x 6 1000 2,70 S 200 DISEÑO
F
80

* PESO CALCULADO CON H=1000. (MIN.) 1" 1/2" 16 70 140 6


DISEÑO
SEGÚN

HORIZONTAL
200

25 S B/2 2" 1/2" 16 80 150 6

200
MORTERO 3" 1/2" 16 80 150 6
NIVELACIÓN
COLUMNA
HORIZONTAL 2 CAÑERÍAS 4" 1/2" 16 100 180 6
VAR.

DISEÑO
SEGÚN

EXISTENTE
B/2

50

6" 1/2" 16 100 180 6


50

S-101 (TÍP.) B 8" 5/8" 19 120 200 8


200

C20x11.7 MORTERO (NOTA 4)


(TABLA 1) 10" 5/8" 19 140 220 10
NIVELACIÓN
SEGÚN DISEÑO

ØB 12" 5/8" 19 140 220 10


80

C15x11,0
500
2200 (MAX.)

B (MIN.)

170
L
S-101 Øb1
B/2 B/2 (TABLA 1) TABLA 10
2-PERF'S Ø27 PERNOS ANCLAJE A HORMIGÓN
(NOTA 4) PERNO ESPÁRRAGO PERFIL
P/BARRAS Ø22 Ø5/8" S (TABLA 8) Ø b1 PERF. G
Ø b BARRA HILADA DE ANCLAJE
VAR.

PLACA BASE mm
TABLA 7 PERNO ESPÁRRAGO Øb
SP-202
(TABLA 9 )
VAR.

PERNO QUIM. 3/4" PLACA BASE 16 1/2" L=300 EMP. 200 mm (MIN.)
CARGA MÁX. (TABLA 9)
PB-02 PERFIL (kg) 19 5/8" L=300 EMP. 200 mm (MIN.)
VERTICAL SOPORTE CONSOLA VOLADIZO
C20

200

C20x11.7 6530
TIPO B ESPACIAMIENTO MÁXIMO: 3m ENTRE SOPORTES
NIVELACIÓN
MORTERO

EN ESTRUCTURA
25

VAR.

NOTA IMPORTANTE:
"PARA ELIMINAR O CONTROLAR ACCIDENTES GRAVES Y FATALES, JRI CUMPLE CON INCORPORAR EN SUS ENTREGABLES LOS REQUISITOS
SP-107 SP-114
ESTABLECIDOS EN LA NORMATIVA LEGAL, LOS PRINCIPIOS DE LA POLÍTICA DE SEGURIDAD Y SALUD OCUPACIONAL, LA POLÍTICA DE

TIPO A DESARROLLO SUSTENTABLE, LA CARTA DE VALORES, LOS ESTÁNDARES CODELCO (ECF-EST), Y LOS ESTÁNDARES DE LA GERENCIA DE

SOPORTE PEDESTAL SOPORTE CONSOLA TIPO BANQUILLO


PROYECTOS (EGPRO), ASÍ COMO LOS CONTROLES ESTABLECIDOS EN LOS RIESGOS CRÍTICOS (RC) Y LAS REGLAS QUE SALVAN VIDAS DEL
PROYECTO DIAMANTE, SIN PERJUICIO DE LAS MEDIDAS DE CONTROL QUE SE ADOPTEN EN LAS SIGUIENTES FASES DEL PROYECTO."
EN HORMIGÓN
VERTICAL EN HORMIGÓN ESPACIAMIENTO MÁXIMO: 3m ENTRE SOPORTES
NOMBRE FECHA FIRMA No. CONTRATO

PROY. X. LIRA M. MAY. / 2018 DIVISIÓN EL TENIENTE - GERENCIA DE PROYECTOS


CONTRATISTA
REV. X. LIRA M. MAY. / 2018 PROYECTO DIAMANTE 4501770690
H
. . . . . . . . I. REV. G. ELGUETA G. MAY. / 2018
. . . . 5.- ESTA LÁMINA SE COMPLEMENTA CON LÁMINA 2 DE 2, PLANO N° IM8-64917. Q
2
PROYECCIÓN J.D. L. RODRIGUEZ S. MAY. / 2018
INGENIERÍA BÁSICA INGENIERÍA
No. PLANO CONTRATISTA REV
. . Q 03 / 08 / 2018 EMITIDO PARA SIGUIENTE FASE XLM LRS CBY 4.- TODAS LAS SOLDADURAS INDICADAS EN PLANO SE DEBEN REALIZAR EN TALLER. J.I. C. CABALLERO H. MAY. / 2018 ÁREA MINA P255-SPIA3-PL-02000-PI-001
. . ESCALA S/ESC J.P. C. BRAVO Y. MAY. / 2018
P 04 / 07 / 2018 EMITIDO PARA SIGUIENTE FASE XLM LRS CBY 3.- VARIABLE: AJUSTAR SEGÚN MONTAJE EN TERRENO. SUB ÁREA INFRAESTRUCTURA GENERAL No. PLANO CODELCO DIVISIÓN 2
D. SEPÚLVEDA G.
IM8-64916 Q
TDC CODELCO

. REEMPLAZA ESP.1
1 . B 25 / 05 / 2018 EMITIDO PARA REVISIÓN DE CODELCO XLM LRS CBY 2.- PARA ANCLAJE A ROCA USAR BARRAS Ø22 ACERO A630-420H TIPO CAPSOL O EQUIVALENTE.
IM8-64915 Q P&ID - SIMBOLOGÍA GENERAL MECÁNICA-PIPING A 22 / 05 / 2018 EMITIDO PARA REVISIÓN INTERNA XLM LRS CBY 1.- DIMENSIONES EN MILIMETROS (S.I.C.)
AL PLANO
ESP.2 J. VALDIVIA S.
CONT. ESTÁNDAR DE SOPORTES No. PLANO CODELCO GPRO

REFERENCIAS No. FECHA REVISIONES DIB REV JP NOTAS


REEMPLAZADO
POR PLANO J. ING. J. VIENNE C. TIPO PL (LÁMINA 1 DE 2) 4501770690-02000-103CA-00001