DE LA ECUACION:
𝑲𝑽𝑨
𝑲𝑽𝑨 = √𝟑 𝑽𝑰 ∴ 𝑰𝒑 =
√𝟑 𝑽
𝑰𝒏𝒐𝒎𝒊𝒏𝒂𝒍 𝒙 𝟔𝟎𝟎%.
𝟏𝟑𝟖. 𝟕𝟐 𝑨 𝒙 𝟔 = 𝟖𝟑𝟐. 𝟑𝟐 𝑨𝒎𝒑 .
PUNTO 4 II 50
𝐼₄ = 0.5 ∗ 𝐼𝑝𝑐
DATOS:
Z= 5.5%
ZT= 0.055
WF=0.58 FACTOR ANSI. (LISTA DE FACTOR ANSI/TRANSFORMADORES
PAG-14)
PUNTO 1. (2 SEG.)
𝐼𝑃𝐶 𝑥 𝑊𝐹
𝐼= ∴
𝑍𝑇
(416.85 𝑥 0.58)
𝐼₁ = = 4,395.8 𝐴.
0.055
𝐼𝑟𝑢𝑠ℎ 4168.5 𝐴
𝑇𝐷 = ∴ 𝑇𝐷 = = 10.42 𝐴 → 0.1 𝑠𝑒𝑔.
𝑀𝑢𝑙𝑡𝑖𝑝𝑙𝑜 𝑇𝑎𝑝 400
TIEMPO
1000 SEG. 15 x 10 = 150AMP.
10 SEG. 150 x 10 = 1500 AMP.
.2 SEG. 3100 x 10 = 31 000 AMP
DATOS:
Z= 5.75%
ZT= 0.0575
WF=0.55
CATEGORIA II
PUNTO 1. (2 SEG.)
𝐼𝑝𝑐 ∗ 𝑤𝑓 (903.17 𝑥 0.55)
𝐼₁ = ∴ 𝐼₁ = = 8,639.01 𝐴.
𝑍𝑡 0.0575
CATEGORIA I
𝐊𝐕𝐀
𝐊𝐕𝐀 = √𝟑 𝐕𝐈 ∴ 𝐈𝐩 =
√𝟑 𝐕
300 x 1000 300,000
Ip = = = 41.68 A.
√3 4160 7,196.8
PUNTO 1. (ZT)2
PUNTO 4. 50 SEG.
𝐼₄ = 0.5 ∗ 𝐼𝑝𝑐 .
𝐼₄ = 0.5 ∗ 361.27 𝐴 = 1806.35
FORMULA:
KVA
KVA = √3 VI ∴ Ipc =
√3 V
500 x 100 500,000
Ipc = = = 602.11 𝐴
√3 x 480 830.4
SUSTITUYENDO:
WF= 0.577
Z= 0.0534
CATERGORIA I
PUNO 1. ZT2
T₁ = 1250 (0.0534)2 = 3.56 seg.
Ipc ∗ wf 602.11 𝑥 0.577
I₁ = ∴ 𝐼₁ = = 6,505.94 𝐴.
Zt 0.0534
PUNTO 4. 50 SEG.
5Ipc ∗ wf. ∴ 5( 602.11)(0.577) = 1,737.08 A.
500 x 1000
Ip = = 69.47 𝐴.
√3 ∗ 4160 𝑣
LA CURVA ANSI
EL PUNTO DE MAGNETIZACION (Inrush)
KVA
KVA = √3 VI ∴ Ip =
√3 V
SUSTITUYENDO:
PUNTO 1. (2 SEG.)
𝐼𝑝𝑐 520.98
𝐼₁ = ∴ 𝐼₁ = = 8,683 𝐴.
𝑍𝑡 0.06
ENCONTRAR:
LA CURVA ANSI
EL PUNTO DE MAGNETIZACION
KVA
KVA = √3 VI ∴ Ip =
√3 V
SUSTITUYENDO:
KVA
KVA = √3 VI ∴ Ip =
√3 V
SUSTITUYENDO:
50 C.P
440V 3𝞥.
𝑯𝒑 𝒙 𝟎.𝟕𝟒𝟔
ROTOR BLOQUEADO LETRA “G” 𝑰𝒑𝒄 =
√𝟑 𝒙 𝑭𝑷.𝑿 𝑬𝑭𝑿𝑲𝑽
460𝑣
𝐼𝑛𝑜𝑚 = (65𝐴) = 67.95𝐴.
440𝑣
IRB = POR TABLA IR TABLA 430- 7 (B). LA LETRA G SE TOMA EN KVA POR
C.P. A ROTOR BLOQUEADO. DONDE G= 5.60 – 6.29 Amp.
𝐼𝑛 = 67.95 𝐴
IRB = 𝐼𝑛 ∗ 6.29
3.-TIEMPO DE ACELERACION.
𝐇. 𝐏. 𝐱 𝟎. 𝟕𝟒𝟔
𝐈𝐩𝐜 =
√𝟑 𝐱 𝐅. 𝐏. 𝐱 𝐄𝐟. 𝐱 𝐊𝐕
PROPOSITO.- ES DETECTAR:
LEY DE OHM:
I1
I3
I2
𝐼₁ + 𝐼₂ = 𝐼₃
CORTOCIRCUITO FUSIBLE > 1.3 I NOMINAL, Y CURVA QUE PERMITA 1.1 VECES LA
CORRIENTE DE ARRANQUE DURANTE 10 SEGUNDOS
1.4 510
2 180
3.3 53
𝐼𝑛 ∗ 125%
16 𝐴.∗ 125% = 20 𝐴.
𝐼𝑛 ∗ 130%
25 C.P.- 68 A -230V
INTERPOLAMOS
230𝑣
𝐼𝑛 = (68) = 71.0 𝐴
220𝑣
𝐼𝑛 ∗ 300%
71 ∗ 300% = 213 𝐴.
TIEMPO CORRIENTE
300 SEG. 300 A.
100 SEG. 380 A
50 SEG. 430 A
12 SEG. 580 A
10 SEG. 600 A
1 SEG. 950 A
GRAFICAR LOS DATOS EN LA HOJA TIEMPO-CORRIENTE
TIEMPO CORRIENTE
50 SEG. 320 A.
12 SEG. 520 A.
10 SEG. 560 A.
1 SEG. 1100 A.
I NOM-71 AMP.
IRB= 3.55-3.99 A.
𝐼𝑐 = 𝐼𝑛 ∗ 125% ∴
𝐼𝑐 = 71 𝐴 ∗ 125% = 88.75 𝐴. ≃ 90 𝐴.
TIEMPO CORRIENTE
𝐼𝑇𝑀 = 𝐼𝑛 ∗ 250%
𝐼𝑇𝑀 = 71 ∗ 250% = 177.5 𝐴.
Inrush 24,060.00
TD = = = 75.18 𝐴.
𝑀𝑢𝑙𝑡. 𝑇𝑎𝑝 320
CALCULO DE Ipick-up
MULT.
TIEMPO
TAP I MULT. TAP*240 A.
1.2 1.2*240= 288 A 4
1.5 1.5*240=480A. 0.18
2 2*240=360 0.78
3 3*240=720A. 0.42
4 3*240=960A. 0.32
5 5*240=1200A. 0.28
6 6*240=1440A. 0.25
7 7*240=1680A. 0.21
8 8*240=1920A. 0.18
9 9*240=2160A. 0.17
10 10*240=2400A. 0.16
20 20*240=4800A. 0.14
= 10 ∗ 400 = 4000 A.
≃ 350E
Inom 𝐼
Ajuste de disparo Termico = ( )( ).
𝐼𝑛𝑜𝑚 𝑅𝑒𝑙𝑒𝑣 𝑅𝑇𝐶
225 1
Ajuste de disparo Termico = ( ) ( ) = 0.46
6 80
400
RTC = = 80 𝐴.
5
In(0.5)(6)(80) = 240 𝐴.
1. LA In 10 s< t <1000s.
In = 120 A.
IA = 720 → T − Seg..
Im = 1.76 ( 720) = 1,267 𝐴. 𝑒𝑛 0.1 𝑠𝑒𝑔
6500 HP, 6600V, FS=10. FP= 0.89 In= 495 A. IRB = 2525 A.
TIEMPO DE ARRANQUE = 3 SEG.
CARACTERISTICAS DE LOSRELEVADORES.
ANSI 50 Mca WESTINGHOUSE TIPO S.C. RANGO: 20-80 A.
ANSI 51 W TIPO CO-5 RANGO: 1-12 A.
ANSI 50G W TIPO ITH RANGO 0.5-10 A.
ANSI 49 W TIPO DT-3 RANGO 50-90°C
RELACION DEL TC QUE ALIMENTA AL REL50/51 In= 495 A.
PARA EVITAR PROBLEMAS DE SATUACION, SE PUEDE
SELECCIONAR UN VALOR DE 150% DE LA In = 𝟒𝟗𝟒 ∗
𝟏𝟓𝟎% = 𝟕𝟒𝟐. 𝟓 𝐀 .
EL VALOR COMERCIAL MAS PROXIMO ES 800/5 POR LO
QUE LA RTC =
800
= 160
5
El TC QUE ALIMENTA AL RELEVADOR 50G SE SELECCIONA DE ACUERDO AL VALOR QUE SE
LIMITE EL VALOR DE LA I FALLA A TIERRA SE TOMA UN VALOR ESTANDAR, SE CONSIDERA
UN DESBALANCE DE CORRIENTE DEL 10% DE LA In DEL MOTOR.
I FALLA A TIERRA= SE SELECCIONA UN TC CON RELACION 50/5 A.
AJUSTE DEL RELEVADOR 50. I DE ARRANQUE DEL MOTOR A TENSION PLENA, SE TOMA
COMO:
Iarranque = 2Irb = 2 ∗ 2525 = 5050 A.
480v
I= (156) = 162.78 𝐴.
460v
IA = In ∗ 6 = 162.78 ∗ 6 = 976.69 A en 6 Seg.
≃ 400 A.
o Corriente Nominal In
o Corriente de Magnetización Im
o Curva del daño Térmico del Transf.
o Capacidad del Fus. Lado primario
o Capacidad del ITM lado sec.
o Capacidad del cable lado primario.
𝑲𝑽𝑨
𝑲𝑽𝑨 = √𝟑 𝑽𝑰 ∴ 𝑰𝒑 =
√𝟑 𝑽
PUNTO 1. 2 SEG.
PUNTO 1. 2 SEG.
𝐼𝑟𝑒𝑎𝑙 208.17
𝐼𝑟𝑒𝑙 = 𝑇𝐶 ∗ 𝑇𝐴𝑃 ∴ 𝑇𝐴𝑃 = = = 26 ≈ 3
𝑇𝐶 80
400
𝐼𝑟𝑒𝑎𝑙 = 3 ( ) = 240
5
51 PICK-UP (110-140%* FLA).
110*208.17= 228.98
CAPACIDAD DEL CABLE LADO PRIMARIO
𝐼𝑝 = 208.17 ∗ 125% = 260 .21 𝐴
400/5, TAP-5, DIAL-2-5
TIENE 8 TITULOS
1/𝑅𝑇𝐶
Multp. Tap =
TAP REL.
I pick − up = TAP ∗ RTC
(I real)
REDES DE TIERRA
CABLES DE POTENCIA.
PROTECCION
CALCULAR.
Inominal
IArranque
IMagnetización
El ajuste térmico
Tamaño del TC´S para el R.S
Capacidad del interruptor automático de tiempo inverso
Ajuste de baja tensión
Graficar el perfil de la corriente del motor.
CALCULAR…
o Corriente Nominal IN
o Corriente de Aceleración IA
o Corriente de Magnetización IM
o Tamaño del relevador de sobre carga
requiere
o Protección de sobre corriente por FCRT y
FSRT Determine el calibre del cable
SOLUCION:
DE TABLA 430-150 OBTENEMOS LA CORRIENTE
NOMINAL
𝐼𝑛 = 65 𝐴𝑚𝑝. 𝑎 460𝑣
INTERPOLAMOS
460
𝐼𝑛 = 65 ∗ ( ) = 67.96 𝐴.
440
𝐼𝑛 = 68 𝐴.
IRB = Tabla 430-7(b).Letra G se toma KVA por Cp. Rb. 5.60 - 6.29.
𝐼𝑟𝑏 = 𝐼𝑛 ∗ 6.29
𝐼𝑟𝑏 = 68 ∗ 6.29 = 427.72
𝑅. 𝑠 = 125% 𝐷𝑒 𝑠𝑢 𝐼𝑛𝑜𝑚𝑖𝑛𝑎𝑙 ∴
𝑅. 𝑠 = 68 ∗ 125% = 85 𝐴.
80 ∗ 125% = 100 𝐴.
Tabla 310-18 → 430-22 (a). CABLE CAL-4 120 A. 150°C TIPO Z, SF, COBRE.
𝐼𝑎𝑟𝑟𝑎𝑛𝑞𝑢𝑒 529.25
𝐼𝑎𝑟𝑟𝑎𝑛𝑞𝑢𝑒 𝑠𝑒𝑐 = = = 3.55 𝐴.
𝑅𝑇𝐶 160
EL MARGEN SUP.
𝐼𝑎𝑟𝑟𝑎𝑛𝑞𝑢𝑒 = 125% 𝑑𝑒 𝑠𝑢 𝐼𝑛𝑜𝑚𝑖𝑛𝑎𝑙
𝐼𝑎𝑟𝑟𝑎𝑛𝑞𝑢𝑒 618.75
𝐼𝑎𝑟𝑟𝑎𝑛𝑞𝑢𝑒 𝑠𝑒𝑐. = = = 3.86 𝐴.
𝑅𝑇𝐶 160
El Tap se ajusta al valor de 4, con este valor el relevador arranca con una
corriente de
160
𝐼𝑎𝑟𝑟𝑎𝑛𝑞𝑢𝑒 = 4 ∗ ( ) = 1.29 𝐼𝑛.
495
𝑅𝑇𝐶
𝐼 𝑝𝑖𝑐𝑘 𝑢𝑝 = 𝑇𝑎𝑝 ∗ ( 𝐼𝑛 ) ∴
𝐼𝑝𝑖𝑐𝑘 𝑢𝑝 = 𝑇𝑎𝑝 ∗ 𝑅𝑇𝐶 = 640 𝐼𝑛.
Para el ajuste de tiempo de acuerdo con el instructivo del Relev, el múltiplo del
Tap. Se calcula:
𝐼𝑛 = 495 𝐴
𝐼𝑛 = 495 𝐴
𝐼𝑟𝑏 = 2525 𝐴 − 3 𝑠