Está en la página 1de 121

AMOS REPORT

MAINTENANCE DONE

7/28/2022 1 / 121
AMOS REPORT
MAINTENANCE DONE
SUMMARY OF MAINTENANCE WORK ORDERS

#AMOS Function Last Asset Last Installation


Criticality
1000093090 DD/GG 01 ALTERNATOR 3 609999//609999 Rig 5857 - Heavy Land

#Work Order Work Order Title Completion Hours at


Date Completion Date
4050010005 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 5/20/2022 0 Hours

4050009189 ALELECS03 - 6 MESES / LUBRICACION DE ALTERNADOR 3/26/2022 0 Hours

4050009417 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 2/15/2022 0 Hours

4050009015 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 6/21/2020

4050008325 ALELECS03 - 6 MESES / LUBRICACION DE ALTERNADOR 3/3/2020

4050007793 ASELECBN - 1 A?O / MEDICI?N ANUAL DE ALTERNADOR 1/25/2020

4050008420 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 1/18/2020

4050008018 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 5/8/2019

4050007980 ALELECS03 - 6 MESES / LUBRICACION DE ALTERNADOR 3/30/2019

4050007982 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 11/24/2018

4050007138 ALELECS03 - 6 MESES / LUBRICACION DE ALTERNADOR 7/15/2018

4050007575 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 7/15/2018

4050006555 ASELECBN - 1 A?O / MEDICI?N ANUAL DE ALTERNADOR 6/8/2018

4050007133 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 4/8/2018

4050006556 ALELECS03 - 6 MESES / LUBRICACION DE ALTERNADOR 1/7/2018

4050006557 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 1/7/2018

4050005946 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 8/29/2016

4050005521 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 6/1/2016

4050005157 ALELECS03 - 6 MESES / LUBRICACION DE ALTERNADOR 5/31/2016

4050004624 ASELECBN - 1 AÑO / MEDICIÓN ANUAL DE ALTERNADOR 5/15/2016

4050005162 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 3/1/2016

4050004625 ALELECS03 - 6 MESES / LUBRICACION DE ALTERNADOR 11/29/2015

4050004771 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 11/29/2015

4050004626 ACELECSBR - 3 MESES / REVISION Y LIMPIEZA DE ALTERNA 8/17/2015

7/28/2022 2 / 121
AMOS REPORT
MAINTENANCE DONE
SUMMARY OF MAINTENANCE WORK ORDERS
4050004337 AIELECSIO - 500 HORAS / MANTENIMIENTO DEL ATERNADOR 4/26/2015 2594.00 Hours

4050004142 AIELECSIO - 500 HORAS / MANTENIMIENTO DEL ATERNADOR 1/19/2015 2039.00 Hours

4050003539 AIELECSIR - 20000 HORAS O 3 AÑOS /LIMPIEZA DEL ALTE 12/7/2014 1446.00 Hours

4050004101 AIELECSIO - 500 HORAS / MANTENIMIENTO DEL ATERNADOR 11/29/2014 1440.00 Hours

4050004012 AIELECSIO - 500 HORAS / MANTENIMIENTO DEL ATERNADOR 11/17/2014 -697.00 Hours

4050003664 AIELECSIO - 500 HORAS / MANTENIMIENTO DEL ATERNADOR 10/13/2014 626.00 Hours

4050003536 AIELECSIO - 500 HORAS / MANTENIMIENTO DEL ATERNADOR 8/24/2014 228.00 Hours

4050003537 AIELECSIP - 2000 HORAS /INSPECCION DE ALTERNADOR 8/24/2014 228.00 Hours

4050003538 AIELECSIQ - 8000 HORAS O 1 AÑO/ MEDICION DE AILSAMIE 8/24/2014 228.00 Hours

4050002960 AIELECSIM - 2000 HORAS / ALTERNADOR KATO: INSPECCION 6/29/2014 0 Hours

4050003120 AIELECS70 - 1000 HORAS/ MANTENIMIENTO DE GENERADOR 6/28/2014 0 Hours

4050003202 AIELECSHG - 500 HRS / CHEQUEO DE GENERADOR 6/28/2014 0 Hours

4050003122 AIELECSHG - 500 HRS / CHEQUEO DE GENERADOR 5/25/2014 -530.00 Hours

4050002562 AIELECSH0 - 6 MESES / MANTENIMIENTO SEMESTRAL DE ALT 4/14/2014

4050002961 AIELECS70 - 1000 HORAS/ MANTENIMIENTO DE GENERADOR 4/14/2014 -1503.00 Hours

4050003056 AIELECSHG - 500 HRS / CHEQUEO DE GENERADOR 4/14/2014 -1503.00 Hours

4050002962 AIELECSHG - 500 HRS / CHEQUEO DE GENERADOR 3/22/2014 -2014.00 Hours

4050002914 AIELECSIN - 8000 HORAS / ALTERNADOR KATO: MANTENIMIE 2/21/2014 -2542.00 Hours

4050002915 AIELECSIM - 2000 HORAS / ALTERNADOR KATO: INSPECCION 2/21/2014 -2542.00 Hours

4050002916 AIELECS70 - 1000 HORAS/ MANTENIMIENTO DE GENERADOR 2/21/2014 -2542.00 Hours

4050002917 AIELECSHG - 500 HRS / CHEQUEO DE GENERADOR 2/21/2014 -2542.00 Hours

4050001824 AIELECSHK - 1 AÑO / MANTENIMIENTO ANUAL DE ALTERNADO 8/20/2013

4050002136 AIELECSH0 - 6 MESES / MANTENIMIENTO SEMESTRAL DE ALT 7/28/2013

4050001736 AIELECSH0 - 6 MESES / MANTENIMIENTO SEMESTRAL DE ALTERNADOR 1/30/2013

4050000917 AIELECIR - 2000 HRS / INSPECT GENERATOR/ALTERNATOR 7/21/2010 -13703.00 Hours

4050001731 AIELECSGZ - 1 MES / INSPECCION MENSUAL DE GENERADOR 5/26/2010

4050000418 ACELEC1ET - 1 YEAR / CHECK ROTATING RECTIFIER 5/14/2010

4050000927 AIELECIQ - 1000 HRS / LUBRICATE/ INSPECT BEARINGS 4/30/2010

7/28/2022 3 / 121
AMOS REPORT
MAINTENANCE DONE
SUMMARY OF MAINTENANCE WORK ORDERS
4050000869 AIELECIQ - 1000 HRS / LUBRICATE/ INSPECT BEARINGS 10/10/2009 -16048.43 Hours

4050000704 AIELECIR - 2000 HRS / INSPECT GENERATOR/ALTERNATOR 10/5/2009 -16133.02 Hours

4050000705 AIELECIQ - 1000 HRS / LUBRICATE/ INSPECT BEARINGS 8/22/2009 -16409.78 Hours

4050000666 AIELECIR - 2000 HRS / INSPECT GENERATOR/ALTERNATOR 7/15/2009 -16628.00 Hours

4050000667 AIELECIQ - 1000 HRS / LUBRICATE/ INSPECT BEARINGS 7/15/2009 -16628.00 Hours

7/28/2022 4 / 121
AMOS REPORT
MAINTENANCE DONE

Component
1000093090

Function

0651001A
DD/GG 01 ALTERNATOR

Asset
609999//609999

Last Installation
Rig 5857 - Heavy Land

7/28/2022 5 / 121
AMOS REPORT
MAINTENANCE DONE

WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050010005 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 5/20/2022
Hourmeter Registered: Reported Current Counter Type
Count Value
0 0 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 6 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y.............................................................................Cubiertas y pantallas limpias
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE..........................................................................Tornillos y tapas ajustadas correctamente
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO....................................................... No se perciben ruidos y las temperaturas de
rodamientos y bobinados son normales.
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA............................................................Cables de potencia en buen estado, no
presentan daños mecanicos
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN...........................................Conexiones ajustadas correctamente.
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE............................................................... Cable de tierra ajustado y conectado al
sistema de tierra del RIG.
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

Realizado por: Maikel Soto.

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

Completed Controlled Filed


Date: 5/20/2022 6/13/2022 6/13/2022
By: MAIKEL JOSE SOTO Gonzalo Davila Gonzalo Davila

7/28/2022 7 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050009189 Maintenance Type: //


Title: ALELECS03 - 6 MESES / LUBRICACION DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 3/26/2022
Hourmeter Registered: Reported Current Counter Type
Count Value
0 0 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 8 / 121
AMOS REPORT
MAINTENANCE DONE

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO PRESENTA VIBRACIONES.OK 0,45
MM/S

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE REALIZA LIMPIEZA INTERNA.OK
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONEXIONES EN BUENAS
CONDICIONES.OK
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,ELECMENTOS EN BUEN ESTADO.OK
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONEXIONES CON ESPACIOS
SUFICIENTES.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE APLICA SOLVENTE PARA
LIMPIEZA.OK
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE APLICA GRASA. OK

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

DERWIN PEREIRA
ELECTRONICO
PTX5857

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

Completed Controlled Filed


Date: 3/26/2022 4/8/2022 4/8/2022
By: RODRIGUEZ DANIEL FELIPE Gonzalo Davila Gonzalo Davila

7/28/2022 9 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050009417 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 2/15/2022
Hourmeter Registered: Reported Current Counter Type
Count Value
0 0 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 10 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE REALIZA LIMPIEZA .OK
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,TORNILLOS AJUSTADO.OK
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO SE ENVIDENCIA SOB

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLES EN BUENAS CONDICIONES.OK
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONDICIONES EN BUENAS
CONDICIONES.OK
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO...........................................,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLES TIERRA.OK

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

DERWIN PEREIRA
ELECTRONICO
RIGPTX5857

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

Completed Controlled Filed


Date: 2/15/2022 3/11/2022 3/11/2022
By: RODRIGUEZ DANIEL FELIPE Gonzalo Davila Gonzalo Davila

7/28/2022 11 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050009015 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 6/21/2020
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 12 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y.............................................................................Superficies limpias y en buen estado
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE..........................................................................Tornillos y tapas ajustadas correctamente
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO....................................................... No se perciben ruidos y las temperaturas de
rodamientos y bobinados son normales.
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA............................................................Cables de potencia en buen estado, no
presentan daños mecanicos
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN...........................................Conexiones ajustadas correctamente.
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE............................................................... Cable de tierra ajustado y conectado al
sistema de tierra del RIG.
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

Realizado por: Maikel Soto.

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

Completed Controlled Filed


Date: 6/21/2020 7/5/2020 7/5/2020
By: MAIKEL JOSE SOTO Gonzalo Davila Gonzalo Davila

7/28/2022 13 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050008325 Maintenance Type: //


Title: ALELECS03 - 6 MESES / LUBRICACION DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 3/3/2020
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 14 / 121
AMOS REPORT
MAINTENANCE DONE

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR----------------------------------------------------------------------------DELANTERO 6.45 M/S2
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N TRASERO 3.83 M/S2
EXCESIVA, VERIFICAR EL ALINEAMIENTO.

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.---------------------------------------------------------------------------------------------------------------------------CONDUCTORES EN
BUEN ESTADO.
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.----------------------------------------------CONEXIONES
AJUSTADDAS CORRECTAMENTE.
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.----------------------------------------------------------------------------COMPONENTES
AJUSTADAS Y EN BUEN ESTADO.
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.-------------------------------------------------------------------DISTANCIA ADECUADA.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.---------------------------------------------------------------------------------------------------------------------------------EXCITRATRIZ Y
PLATO DE DIODOS LIMPIO.
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.---------------------------------------SE ENGRASAN CON GRASA
DIELECTRICA.

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

Completed Controlled Filed


Date: 3/3/2020 4/1/2020 4/1/2020
By: MAIKEL JOSE SOTO Gonzalo Davila Gonzalo Davila

7/28/2022 15 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050007793 Maintenance Type: //


Title: ASELECBN - 1 A?O / MEDICI?N ANUAL DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: 12 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 1/25/2020
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

7/28/2022 16 / 121
AMOS REPORT
MAINTENANCE DONE
1 A?O / MEDICI?N ANUAL DE ALTERNADOR
,,
* COMPROBAR EL FUNCIONAMIENTO ADECUADO DE LOS
CALENTADORES DE ESPACIO.,,
* COMPROBAR FUNCIONAMIENTO DE PLATO DE DIODOS.
* MEDIR Y REGISTRAR ALINEAMIENTO DEL GRUPO ELECTROGENO
* VERIFICAR EL ACOPLAMIENTO ENTRE EL MOTOR Y
EL GENERADOR POR MONTAJE DEFECTUOSO O JUEGO.,,
* SECAR EL GENERADOR.
* INSPECCIONAR EL ACOPLAMIENTO MOTOR-GENERADOR
POR PRESENCIA DE DA?OS. REEMPLAZAR LA GOMA
CENTRAL SI ES NECESARIO.,,
* VERIFICAR CONDICION DE BATERIAS, REEMPLAZAR SI ES NECESARIO [1]

* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR


PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,
U,,_______,,,,,,,,U,,_______
V,,_______,,,,,,,,V,,_______
W,,_______

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,


U,,_______,,,,,,,,U,,_______
V,,_______,,,,,,,,V,,_______
,,,,,,,,,,,,,,W,,_______

* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR


PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,
U-V,,_______,,,,,,,,U-V,,_______
V-W,,_______,,,,,,,,V-W,,_______
U-W,,_______

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,


U-V,,_______,,,,,,,,U-V,,_______
V-W,,_______,,,,,,,,V-W,,_______
,,,,,,,,,,,,,,U-W,,_______
,,
* MEDIR AISLAMIENTO CON RESPECTO A TIERRA Y
RESISTENCIA ENTRE BOBINAS DE PMG (SI APLICA).,,
RESPECTO A TIERRA,,,,ENTRE BOBINAS
PM1,,_______,,,,,,,,PM1-PM2_______
PM4,,_______,,,,,,,,PM3-PM4_______ (SI APLICA)
,,
NOTA: APLICAR 500V AL MEGGER PARA MEDIR AISLAMIENTO. LA
LECTURA M?NIMA DEBE SER: 1 MOHM,,

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.
[1] SE IMPLEMENTO DE ACUERDO A ACCION CORRECTIVA PTX 26

HISTORY

7/28/2022 17 / 121
AMOS REPORT
MAINTENANCE DONE

1 A?O / MEDICI?N ANUAL DE ALTERNADOR


,,
* COMPROBAR EL FUNCIONAMIENTO ADECUADO DE LOS.....................................................CALENTADORES FUNCIONANDO
CORRECTAMENTE.
CALENTADORES DE ESPACIO.,,
* COMPROBAR FUNCIONAMIENTO DE PLATO DE DIODOS......................................................DIODOS EN BUEN ESTADO.
* MEDIR Y REGISTRAR ALINEAMIENTO DEL GRUPO ELECTROGENO....................................ALIMENTACION CORRECTA.
* VERIFICAR EL ACOPLAMIENTO ENTRE EL MOTOR Y.............................................................ACOPLE EN BUEN ESTADO.
EL GENERADOR POR MONTAJE DEFECTUOSO O JUEGO.,,
* SECAR EL GENERADOR.............................................................................................................GENERADOR SECO.
* INSPECCIONAR EL ACOPLAMIENTO MOTOR-GENERADOR....................................................GOMA DE ACOPLE EN BUEN
ESTADO.
POR PRESENCIA DE DA?OS. REEMPLAZAR LA GOMA
CENTRAL SI ES NECESARIO.,,
* VERIFICAR CONDICION DE BATERIAS, REEMPLAZAR SI ES NECESARIO [1].......................N/A

* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR


PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,
U. 500 ,,,,,,,,U. 500
V. 500 ,,,,,,V. 500
W. 500

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,


U,,370 ,,,,,,,,U,, 370
V,, 370 ,,,,,,,,V,, 370
,,,,,,,,,,,,,,W,, 3700

* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR


PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,
U-V,, 0 ,,,,,,,,U-V,, 0
V-W,, 0 ,,,,,,,,V-W,, 0
U-W,, 0

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,


U-V,, 0 ,,,,,,,,U-V,, 0
V-W,,0 ,,,,,,,,V-W,, 0
,,,,,,,,,,,,,,U-W,, 0

* MEDIR AISLAMIENTO CON RESPECTO A TIERRA Y


RESISTENCIA ENTRE BOBINAS DE PMG (SI APLICA).,,.........................................................N/A
RESPECTO A TIERRA,,,,ENTRE BOBINAS
PM1,,_______,,,,,,,,PM1-PM2_______
PM4,,_______,,,,,,,,PM3-PM4_______ (SI APLICA)
,,
NOTA: APLICAR 500V AL MEGGER PARA MEDIR AISLAMIENTO. LA
LECTURA M?NIMA DEBE SER: 1 MOHM,,

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.
[1] SE IMPLEMENTO DE ACUERDO A ACCION CORRECTIVA PTX 26

MAIKEL SOTO..................................................ELECTRONICO.

SPARES USED
DISCIPLINES USED:

ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 1/25/2020 2/19/2020 2/19/2020
By: MAIKEL JOSE SOTO Gonzalo Davila Gonzalo Davila

7/28/2022 18 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050008420 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 1/18/2020
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 19 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR.............G1

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y..........................ok se realiza con aire presurizado
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE.........................ok se verifica en buen estado y ajustado
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO...................ok en buen estado y aislado.
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO............ok en buen estadoy aislado.
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN.............ok se revisa y se observa un cable desajustado,se da ajuste a
todos los terminales en el estator del alternador.
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR....................ok se verifica en buen estado y se da ajuste.
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

Realizado por: Edwin Pedroza.


Electronico Jr.
Franco Soto
Electronico

Inspeccionado por: Franco Soto.


Electronico

SPARES USED
DISCIPLINES USED:

ELEC 1.3 Hour(s)


ELTR 0.45 Hour(s)
Total Duration : 1.30 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.75 Hour(s)

Completed Controlled Filed


Date: 1/18/2020 2/19/2020 2/19/2020
By: CHRISTIAN AXEL GARRIDO CHRISTIAN AXEL GARRIDO Gonzalo Davila

7/28/2022 20 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050008018 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 5/8/2019
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 21 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE REALIZA LIMPIEZA .OK
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,TORNILLOS AJUSTADO.OK
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO SE ENVIDENCIA SOB

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLES EN BUENAS CONDICIONES.OK
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONDICIONES EN BUENAS
CONDICIONES.OK
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO...........................................,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLES TIERRA.OK

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

DERWIN PEREIRA
ELECTRONICO
RIGPTX5857

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

Completed Controlled Filed


Date: 5/8/2019 5/22/2019 5/22/2019
By: DERWIN LEONER PEREIRA DERWIN LEONER PEREIRA ROSAURA DEL VALLE SARMIENTO

7/28/2022 22 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050007980 Maintenance Type: //


Title: ALELECS03 - 6 MESES / LUBRICACION DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 3/30/2019
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 23 / 121
AMOS REPORT
MAINTENANCE DONE

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N.....................................................................
EXCESIVA, VERIFICAR EL ALINEAMIENTO.

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,.............................................PROTECTORES,CONDUCTORES Y
AISLAMIENTO EN BUEN ESTADO.
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.......................................CONEXIONES ELECTRICAS BIEN
AJUSTADAS.
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.......................................................................N/A
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO...............................................................DISTANCIA Y ESPACIO
APROPIADO.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO...........................................................................................................................MANTENIMIENTO REALIZADO.
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO...................................LUBRICACION REALIZADA.

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

REALIZADO POR:

ELECTRONICO.......................................................MAIKEL SOTO

SPARES USED
DISCIPLINES USED:

ELEC 0 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 0 Hour(s)

Completed Controlled Filed


Date: 3/30/2019 4/17/2019 4/17/2019
By: MAIKEL JOSE SOTO MAIKEL JOSE SOTO ROSAURA DEL VALLE SARMIENTO

7/28/2022 24 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050007982 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 11/24/2018
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 25 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE REALIZA LIMPIEZA.OK
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.....................,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE VERIFICA AJUSTE.OK
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS...........,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO PRESENTA RUIDO NI
SOBRECALENTAMIENTO.OK

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLE DE POTENCIA Y PUESTA A
TIERRA EN PERFECTO ESTADO.OK
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONESXIONES ELECTRICA EN
BUENAS CONDICIONES.OK
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLES PRINCIPAL DE PUESTA A
TIERRA CONECTADO.OK

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

DERWIN PEREIRA
ELECTRONICO
RIG PTX 5857

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

Completed Controlled Filed


Date: 11/24/2018 12/4/2018 12/4/2018
By: DERWIN LEONER PEREIRA DERWIN LEONER PEREIRA Gonzalo Davila

7/28/2022 26 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050007138 Maintenance Type: //


Title: ALELECS03 - 6 MESES / LUBRICACION DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 7/15/2018
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 27 / 121
AMOS REPORT
MAINTENANCE DONE

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO PRESENTA VIBRACIONES.OK 0,41
MM/S

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE REALIZA LIMPIEZA INTERNA.OK
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONEXIONES EN BUENAS
CONDICIONES.OK
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,ELECMENTOS EN BUEN ESTADO.OK
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONEXIONES CON ESPACIOS
SUFICIENTES.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE APLICA SOLVENTE PARA
LIMPIEZA.OK
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE APLICA ENGRASE.OK

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

DERWIN PEREIRA
ELECTRONICO
PTX5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 7/15/2018 7/24/2018 7/24/2018
By: DERWIN LEONER PEREIRA ROSAURA DEL VALLE SARMIENTO ROSAURA DEL VALLE SARMIENTO

7/28/2022 28 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050007575 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 7/15/2018
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 29 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE REALIZA LIMPIEZA .OK
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,TORNILLOS AJUSTADO.OK
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO SE ENVIDENCIA SOBRE
CALENTAMIENTO.OK

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLES EN BUENAS CONDICIONES.OK
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONDICIONES EN BUENAS
CONDICIONES.OK
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO...........................................,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLES TIERRA.OK

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

DERWIN PEREIRA
ELECTRONICO
RIGPTX5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 7/15/2018 7/24/2018 7/24/2018
By: DERWIN LEONER PEREIRA ROSAURA DEL VALLE SARMIENTO ROSAURA DEL VALLE SARMIENTO

7/28/2022 30 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050006555 Maintenance Type: //


Title: ASELECBN - 1 A?O / MEDICI?N ANUAL DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 6/8/2018
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

7/28/2022 31 / 121
AMOS REPORT
MAINTENANCE DONE
1 A?O / MEDICI?N ANUAL DE ALTERNADOR
,,
* COMPROBAR EL FUNCIONAMIENTO ADECUADO DE LOS
CALENTADORES DE ESPACIO.,,
* COMPROBAR FUNCIONAMIENTO DE PLATO DE DIODOS.
* MEDIR Y REGISTRAR ALINEAMIENTO DEL GRUPO ELECTROGENO
* VERIFICAR EL ACOPLAMIENTO ENTRE EL MOTOR Y
EL GENERADOR POR MONTAJE DEFECTUOSO O JUEGO.,,
* SECAR EL GENERADOR.
* INSPECCIONAR EL ACOPLAMIENTO MOTOR-GENERADOR
POR PRESENCIA DE DA?OS. REEMPLAZAR LA GOMA
CENTRAL SI ES NECESARIO.,,
,,
* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR
PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,
U,,_______,,,,,,,,U,,_______
V,,_______,,,,,,,,V,,_______
W,,_______

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,


U,,_______,,,,,,,,U,,_______
V,,_______,,,,,,,,V,,_______
,,,,,,,,,,,,,,W,,_______

* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR


PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,
U-V,,_______,,,,,,,,U-V,,_______
V-W,,_______,,,,,,,,V-W,,_______
U-W,,_______

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,


U-V,,_______,,,,,,,,U-V,,_______
V-W,,_______,,,,,,,,V-W,,_______
,,,,,,,,,,,,,,U-W,,_______
,,
* MEDIR AISLAMIENTO CON RESPECTO A TIERRA Y
RESISTENCIA ENTRE BOBINAS DE PMG (SI APLICA).,,
RESPECTO A TIERRA,,,,ENTRE BOBINAS
PM1,,_______,,,,,,,,PM1-PM2_______
PM4,,_______,,,,,,,,PM3-PM4_______ (SI APLICA)
,,
NOTA: APLICAR 500V AL MEGGER PARA MEDIR AISLAMIENTO. LA
LECTURA M?NIMA DEBE SER: 1 MOHM,,

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 32 / 121
AMOS REPORT
MAINTENANCE DONE

1 A?O / MEDICI?N ANUAL DE ALTERNADOR


,,
* COMPROBAR EL FUNCIONAMIENTO ADECUADO DE LOS,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, Calentadores
funcionando correctamente
CALENTADORES DE ESPACIO.,,
* COMPROBAR FUNCIONAMIENTO DE PLATO DE DIODOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, Plato de diodos en
buen estado funcionando bien.
* MEDIR Y REGISTRAR ALINEAMIENTO DEL GRUPO ELECTROGENO,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
* VERIFICAR EL ACOPLAMIENTO ENTRE EL MOTOR Y
EL GENERADOR POR MONTAJE DEFECTUOSO O JUEGO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, Acople en buen
estado no presenta juego ni desajuste
* SECAR EL GENERADOR.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, Generador seco se
limpio con aire comprimido y energizo calentadores.
* INSPECCIONAR EL ACOPLAMIENTO MOTOR-GENERADOR
POR PRESENCIA DE DA?OS. REEMPLAZAR LA GOMA,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, Goma en buen estado.
CENTRAL SI ES NECESARIO.,,
,,
* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR
PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, Rotor principal Megado:
0,1 M-Ohm, Bobinas 2,2 Ohm

MODIFICADO: ENDER CARDOZO


U,,_0,1 M-Ohms_,,,,,,,,U,,_2,2 Ohms_
V,,_ 0,1 M-Ohms _,,,,,,,,V,,_ 2,2 Ohms_
W,,_ 0,1 M-Ohms _,,,,,W,,_ 2,2 Ohms_

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, Estator de la Excitatriz


Megado : 4,4 M-Ohm Bobinas 0,3 Ohm

MODIFICADO: ENDER CARDOZO


U,,_4,4 M-Ohms_,,,,,,,,U,,_0,3 Ohms_
V,,_ 4,4 M-Ohms _,,,,,,,,V,,_ 0,3 Ohms_
W,,_ 4,4 M-Ohms _,,,,,W,,_ 0,3 Ohms_

* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR


PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, Estator principal: 1,57 M-
Ohm Bobinas 0,2 Ohm

MODIFICADO: ENDER CARDOZO


U,,_1,57 M-Ohms_,,,,,,,,U,,_0,2 Ohms_
V,,_ 1,57 M-Ohms _,,,,,,,,V,,_ 0,2 Ohms_
W,,_ 1,57 M-Ohms _,,,,,W,,_ 0,2 Ohms_

* MEDIR AISLAMIENTO CON RESPECTO A TIERRA Y


RESISTENCIA ENTRE BOBINAS DE PMG (SI APLICA).,,
RESPECTO A TIERRA,,,,ENTRE BOBINAS
PM1,,___1,2 M-Ohm____,,,,,,,,PM1-PM2___0,6 Ohm____
PM4,,____1,2 M-Ohm___,,,,,,,,PM3-PM4____0,6 Ohm___

Realizado por: Mauricio Gonzales y Edgar Garcia.

MODIFICADO Y VERIFICADO POR:


ENDER J. CARDOZO S.
SUPERINTENDENTE ELÉCTRICO

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

7/28/2022 33 / 121
AMOS REPORT
MAINTENANCE DONE
Completed Controlled Filed
Date: 6/8/2018 2/27/2019 2/27/2019
By: MAIKEL JOSE SOTO MAIKEL JOSE SOTO Gonzalo Davila

7/28/2022 34 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050007133 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 4/8/2018
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 35 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y.....................SE REALIZA LIMPIEZA AIRE COMPRIMIDO
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE......................SE REAJUSTARON PERNOS Y TORNILLOS
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO...................SE ENCUENTRAN EN BUEN ESTADO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA.....................SE REAJUSTAN LAS CONEXIONES DE FUERZA Y SE REVISA
LOS DE CONTROL
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN.................SE REAJUSTAN LOS BORNES DE LOS CABLES DE
CONTROL
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE......................SE ENCUENTRA BIEN CONECTADO
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 4/8/2018 5/13/2018 5/13/2018
By: CHRISTIAN AXEL GARRIDO CHRISTIAN AXEL GARRIDO ROSAURA DEL VALLE SARMIENTO

7/28/2022 36 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050006556 Maintenance Type: //


Title: ALELECS03 - 6 MESES / LUBRICACION DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 1/7/2018
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 37 / 121
AMOS REPORT
MAINTENANCE DONE

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO PRESENTA VIBRACIONES.OK 0,27
MM/S

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE REALIZA LIMPIEZA INTERNA.OK
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONEXIONES EN BUENAS
CONDICIONES.OK
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,ELECMENTOS EN BUEN ESTADO.OK
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONEXIONES CON ESPACIOS
SUFICIENTES.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE APLICA SOLVENTE PARA
LIMPIEZA.OK
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE PLICA EMGRASE.OK

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

DERWIN PEREIRA
ELECTRONICO
PTX5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 2.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 1/7/2018 1/9/2018 1/9/2018
By: DERWIN LEONER PEREIRA DERWIN LEONER PEREIRA VICTOR LUIS ROLANDO BUSTAMANTE

7/28/2022 38 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050006557 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 1/7/2018
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 39 / 121
AMOS REPORT
MAINTENANCE DONE

MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE REALIZA LIMPIEZA .OK
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,TORNILLOS AJUSTADO.OK
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO SE ENVIDENCIA SOB

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLES EN BUENAS CONDICIONES.OK
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONDICIONES EN BUENAS
CONDICIONES.OK
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO...........................................,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLES TIERRA.OK

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

DERWIN PEREIRA
ELECTRONICO
RIGPTX5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 1/7/2018 1/9/2018 1/9/2018
By: DERWIN LEONER PEREIRA DERWIN LEONER PEREIRA VICTOR LUIS ROLANDO BUSTAMANTE

7/28/2022 40 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050005946 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 8/29/2016
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 41 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N...........................SUPERFICIE LIMPIA
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES...................TORNILLOS AJUSTADOS OK
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.................RUIDOS NORMALES OK

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO...................................CABLES A 32° C TEMP Y EN BUEN ESTADO OK
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS...........................CONEXION DE CALE AJUSTADA OK
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO..........................................CABLES DE TIERRA CONECTADA A LA CARCASA OK

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

DERWIN PEREIRA
ELECTRONICO RIG 5857

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

Completed Controlled Filed


Date: 8/29/2016 10/5/2016 10/5/2016
By: DERWIN LEONER PEREIRA DERWIN LEONER PEREIRA Churampi Erika

7/28/2022 42 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050005521 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 6/1/2016
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 43 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.----------------------------------------------------------------------------OK, SE REALIZO LIMPIEZA
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.----------------------------------------------------------------------------OK, SE REAJUSTARON
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.-------------------------------------------------------------OK, NO SE OBSERVAN

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO
DA?O MEC?NICO.---------------------------------------------------------------------------------------------------OK, VERIFICADO EN BUEN ESTADO
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.-------------------------------------------------------OK, AJUSTADOS
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.-----------------------------------------------------------------------------------------OK, AJUSTADO.. VALOR 0,29 OHM

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

REALIZADO POR
CLAUDIO MARTINEZ
ELECTRONICO PTX 5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 0 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 6/1/2016 7/5/2016 7/5/2016
By: CLAUDIO GABRIEL MARTINEZ VICTOR LUIS ROLANDO BUSTAMANTE VICTOR LUIS ROLANDO BUSTAMANTE

7/28/2022 44 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050005157 Maintenance Type: //


Title: ALELECS03 - 6 MESES / LUBRICACION DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 5/31/2016
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 45 / 121
AMOS REPORT
MAINTENANCE DONE

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.-------------------------------------------------------------------------------------OK, 6,6 mm/ seg

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.------------------------------------------------------------------------------------------------------------------------------OK, BUEN ESTADO
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.------------------------------------------------OK, SE REAJUSTAN
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.--------------------------------------------------------------------------------OK
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.-----------------------------------------------------------------------OK, VERIFICADO
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.------------------------------------------------------------------------------------------------------------------------------------OK, SE REALIZÓ
LIMPIEZA
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.--------------------------------------------OK, SE ENGRASÓ.

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

REALIZADO POR
CLAUDIO MARTINEZ
ELECTRONICO PTX 5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 0 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 5/31/2016 6/2/2016 6/2/2016
By: CLAUDIO GABRIEL MARTINEZ VICTOR LUIS ROLANDO BUSTAMANTE VICTOR LUIS ROLANDO BUSTAMANTE

7/28/2022 46 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050004624 Maintenance Type: //


Title: ASELECBN - 1 AÑO / MEDICIÓN ANUAL DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 5/15/2016
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

7/28/2022 47 / 121
AMOS REPORT
MAINTENANCE DONE
1 A?O / MEDICI?N ANUAL DE ALTERNADOR
,,
* COMPROBAR EL FUNCIONAMIENTO ADECUADO DE LOS
CALENTADORES DE ESPACIO.,,
* COMPROBAR FUNCIONAMIENTO DE PLATO DE DIODOS.
* MEDIR Y REGISTRAR ALINEAMIENTO DEL GRUPO ELECTROGENO
* VERIFICAR EL ACOPLAMIENTO ENTRE EL MOTOR Y
EL GENERADOR POR MONTAJE DEFECTUOSO O JUEGO.,,
* SECAR EL GENERADOR.
* INSPECCIONAR EL ACOPLAMIENTO MOTOR-GENERADOR
POR PRESENCIA DE DA?OS. REEMPLAZAR LA GOMA
CENTRAL SI ES NECESARIO.,,
,,
* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR
PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,
U,,_______,,,,,,,,U,,_______
V,,_______,,,,,,,,V,,_______
W,,_______

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,


U,,_______,,,,,,,,U,,_______
V,,_______,,,,,,,,V,,_______
,,,,,,,,,,,,,,W,,_______

* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR


PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,
U-V,,_______,,,,,,,,U-V,,_______
V-W,,_______,,,,,,,,V-W,,_______
U-W,,_______

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,


U-V,,_______,,,,,,,,U-V,,_______
V-W,,_______,,,,,,,,V-W,,_______
,,,,,,,,,,,,,,U-W,,_______
,,
* MEDIR AISLAMIENTO CON RESPECTO A TIERRA Y
RESISTENCIA ENTRE BOBINAS DE PMG (SI APLICA).,,
RESPECTO A TIERRA,,,,ENTRE BOBINAS
PM1,,_______,,,,,,,,PM1-PM2_______
PM4,,_______,,,,,,,,PM3-PM4_______ (SI APLICA)
,,
NOTA: APLICAR 500V AL MEGGER PARA MEDIR AISLAMIENTO. LA
LECTURA M?NIMA DEBE SER: 1 MOHM,,

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 48 / 121
AMOS REPORT
MAINTENANCE DONE

1 A?O / MEDICI?N ANUAL DE ALTERNADOR


,,
* COMPROBAR EL FUNCIONAMIENTO ADECUADO DE LOS
CALENTADORES DE ESPACIO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,FUNCIONANDO. OK
* COMPROBAR FUNCIONAMIENTO DE PLATO DE DIODOS.,,,,,,,,,,,,,,,,,,,,,EN BUEN ESTADO.OK
* MEDIR Y REGISTRAR ALINEAMIENTO DEL GRUPO ELECTROGENO,,, DE LA ESPECILIDAD ELECTRICA ESTO NO SE
MANEJA.
* VERIFICAR EL ACOPLAMIENTO ENTRE EL MOTOR Y
EL GENERADOR POR MONTAJE DEFECTUOSO O JUEGO.,,,,,,,,,,,,,,,,,,,,,SE INSPECCIONA VISUALMENTE SIN
DESACOPLAR. OK
* SECAR EL GENERADOR.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE APLICA AIRE SECO COMPRIMIDO PA
LIMPIEZA.OK
* INSPECCIONAR EL ACOPLAMIENTO MOTOR-GENERADOR
POR PRESENCIA DE DA?OS. REEMPLAZAR LA GOMA
CENTRAL SI ES NECESARIO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, SE INSPECCIONA VISUALMENTE SIN
DESACOPLAR.
,,
* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR
PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,
U,,_____,,,,,,,,U,,_______ 410 M M M OHM
V,,_______,,,,,,,,V,,_______ 500 M OHM
W,,_______ 485 M OHM

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,


U,,_______,,,,,,,,U,,_______ 170 M OHM
V,,_______,,,,,,,,V,,_______ 180 M OHM
,,,,,,,,,,,,,,W,,_______ 190 M OHM

* MEDIR AISLAMIENTO ENTRE BOBINAS DE ESTATOR, ROTOR


PRINCIPAL Y EXCITATRIZ.,,
ESTATOR PRINCIPAL,,,,ROTOR PRINCIPAL,,
U-V,,_______,,,,,,,,U-V,,_______455 M OHM
V-W,,_______,,,,,,,,V-W,,_______ 470 M OHM
U-W,,_______

ESTATOR EXCITATRIZ,,,,ROTOR EXCITATRIZ,,


U-V,,_______,,,,,,,,U-V,,_______360 M OHM
V-W,,_______,,,,,,,,V-W,,_______378 M OHM
,,,,,,,,,,,,,,U-W,,_______ 470 MOHM
,,
* MEDIR AISLAMIENTO CON RESPECTO A TIERRA Y
RESISTENCIA ENTRE BOBINAS DE PMG (SI APLICA).,,
RESPECTO A TIERRA,,,,ENTRE BOBINAS
PM1,,_______,,,,,,,,PM1-PM2_______
PM4,,_______,,,,,,,,PM3-PM4_______ (SI APLICA) N/A.
,,
NOTA: APLICAR 500V AL MEGGER PARA MEDIR AISLAMIENTO. LA
LECTURA M?NIMA DEBE SER: 1 MOHM,,

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

DERWIN PEREIRA
ELECTRONICO
RIG 5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 5/15/2016 5/31/2016 5/31/2016
By: DERWIN LEONER PEREIRA VICTOR LUIS ROLANDO BUSTAMANTE VICTOR LUIS ROLANDO BUSTAMANTE

7/28/2022 49 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050005162 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 3/1/2016
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 50 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.------------------------------------------------------------------------------------------------------OK, LIMPIEZA CON
AIRE
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.------------------------------------------------------------------------------------------------------OK, SE REAJUSTAN
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.---------------------------------------------------------------------------------------OK, NO SE OBSERVAN

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.----------------------------------------------------------------------------------------------------------------------------OK, EN BUEN
ESTADO
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.-------------------------------------------------------------------------------OK
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.-----------------------------------------------------------------------------------------------------------------OK, CONECTADO Y
AJUSTADO

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

REALIZADO POR
CLAUDIO MARTINEZ
ELECTRONICO PTX 5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 0 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 3/1/2016 3/4/2016 3/4/2016
By: CLAUDIO GABRIEL MARTINEZ VICTOR LUIS ROLANDO BUSTAMANTE VICTOR LUIS ROLANDO BUSTAMANTE

7/28/2022 51 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050004625 Maintenance Type: //


Title: ALELECS03 - 6 MESES / LUBRICACION DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 11/29/2015
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACI?N
EXCESIVA, VERIFICAR EL ALINEAMIENTO.

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DA?O O GRIETAS.
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DA?O F?SICO. SI APLICA.
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.

NOTA: USAR GRASA PARA RODAMIENTOS QUE CUMPLA CON LA


CLASIFICACI?N NLGI No 2 EVITANDO LA LUBRICACI?N EN
EXCESO. NO USAR GRASA MULTIPROP?SITO EP 2

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 52 / 121
AMOS REPORT
MAINTENANCE DONE

6 MESES / LUBRICACION DE ALTERNADOR

VIBRACION
* COMPROBAR NIVEL DE VIBRACION. UTILIZAR
MEDIDOR PORTATIL.EN CASO DE VIBRACIÓN
EXCESIVA, VERIFICAR EL ALINEAMIENTO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,0,32 M/S, ALINEACION ADECUADA.OK

LIMPIEZA INTERNA, AJUSTES Y LUBRICACION


* DESTAPAR GENERADOR. INSPECCIONAR CONDUCTORES,
PROTECTORES Y AISLAMIENTO POR PRESENCIA DE
DAÑO O GRIETAS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, NO PRESENTA DAÑO.OK
* VERIFICAR AJUSTE EN TODAS LAS CONEXIONES ELECTRICAS.,,,,,,,,,,,,,,AJUSTE ADECUADO.OK
* REVISAR TRANSFORMADORES, FUSIBLES, CAPACITORES;
POR DESAJUSTE O DAÑO FÍSICO. SI APLICA.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, N/A.OK
* VERIFICAR QUE LOS CABLES Y CONEXIONES ELECTRICAS
TENGAN UNA APROPIADA DISTANCIA Y ESPACIO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,ESPACIO ADECUADO.OK
* LIMPIAR CAJA DE CONEXIONES, EXCITATRIZ, PLATO
DE DIODOS USANDO AIRE COMPRIMIDO Y SOLVENTE
DIELECTRICO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE REALIZA LIMPIEZA.OK
* LUBRICAR RODAMIENTOS, EN CASO NO SEAN DE DOBLE SELLO.,,,,,,,,,,,SE REALIZA ENGRASE.OK

DERWIN PEREIRA
ELECTRONICO
RIG 5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 11/29/2015 11/30/2015 11/30/2015
By: DERWIN LEONER PEREIRA DAVID BARRETO DAVID BARRETO

7/28/2022 53 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050004771 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: 3 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 11/29/2015
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISI?N DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACI?N.
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DA?O MEC?NICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.

REFERENCIA: PLAN DE MANTENIMIENTO GENERICO BASADO


EN LAS RECOMENDACIONES DE LOS FABRICANTES: CATERPILLAR<(>,<)>
KATO y BAYLOR.

HISTORY

7/28/2022 54 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISIÓN DE CUBIERTAS


* LIMPIAR SUPERFICIE EXTERNA Y
PANTALLAS DE VENTILACIÓN.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE REALIZA LIMPIEZA.OK
* VERIFICAR TORNILLOS Y MONTAJE
DE TAPAS POR DESAJUSTES.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,TORNILLOS DE LA TAPA
AJUSTADO.OK
* CHEQUEAR RUIDO O SOBRECALENTAMIENTO
EN LOS RODAMIENTOS Y BOBINADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,TEMPERATURA ADECUADA. 35
°C EN LA BOBINAS. RODAMIENTOS 45 °C.OK

CABLES DE POTENCIA Y ATERRAMIENTO


* VERIFICAR QUE LOS CABLES DE POTENCIA
Y SUS CONEXIONES NO PRESENTAN CALENTAMIENTO,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, TEMPERATURA
ADECUADA.OK SIN NINGUN DAÑO.OK
EXCESIVO, BAJO AISLAMIENTO APLASTAMIENTO,
DAÑO MECÁNICO.
* VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN
AJUSTADAS Y LOS CABLES ASEGURADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CONEXIONES AJUSTADA.OK
* VERIFICAR QUE EL CABLE DE TIERRA SE
ENCUENTRA BIEN AJUSTADO AL GENERADOR
Y QUE SE ENCUENTRA CONECTADO AL SISTEMA
A TIERRA DEL EQUIPO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLE DE TIERRA
CONECTADO.OK

DERWIN PEREIRA
ELECTRONICO
RIG 5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 11/29/2015 11/30/2015 11/30/2015
By: DERWIN LEONER PEREIRA DAVID BARRETO DAVID BARRETO

7/28/2022 55 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050004626 Maintenance Type: //


Title: ACELECSBR - 3 MESES / REVISION Y Maintenance Class: //
LIMPIEZA DE ALTERNA Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 8/17/2015
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISIÓN DE CUBIERTAS


- LIMPIAR SUPERFICIE EXTERNA Y PANTALLAS DE VENTILACIÓN.
- VERIFICAR TORNILLOS Y MONTAJE DE TAPAS POR DESAJUSTES.
- CHEQUEAR RUIDO O SOBRECALENTAMIENTO EN LOS RODAMIENTOS Y
BOBINADOS.

CABLES DE POTENCIA Y ATERRAMIENTO


- VERIFICAR QUE LOS CABLES DE POTENCIA Y SUS CONEXIONES NO
PRESENTAN CALENTAMIENTO EXCESIVO, BAJO AISLAMIENTO
APLASTAMIENTO, DAÑO MECÁNICO.
- VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN AJUSTADAS Y
LOS CABLES ASEGURADOS.
- VERIFICAR QUE EL CABLE DE TIERRA SE ENCUENTRA BIEN
AJUSTADO AL GENERADOR Y QUE SE ENCUENTRA
CONECTADO AL SISTEMA A TIERRA DEL EQUIPO.

HISTORY

7/28/2022 56 / 121
AMOS REPORT
MAINTENANCE DONE

3 MESES / REVISION Y LIMPIEZA DE ALTERNADOR

LIMPIEZA GENERAL Y REVISIÓN DE CUBIERTA


- LIMPIAR SUPERFICIE EXTERNA Y PANTALLAS DE VENTILACIÓN.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE
REALIZA LIMPIEZA .OK
- VERIFICAR TORNILLOS Y MONTAJE DE TAPAS POR DESAJUSTES.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE
AJUSTARON LOS TORNILLOS.OK
- CHEQUEAR RUIDO O SOBRECALENTAMIENTO EN LOS RODAMIENTOS Y
BOBINADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO
PRESENTA RUIDOS EXTRALLOS.OK

CABLES DE POTENCIA Y ATERRAMIENTO


- VERIFICAR QUE LOS CABLES DE POTENCIA Y SUS CONEXIONES NO
PRESENTAN CALENTAMIENTO EXCESIVO, BAJO AISLAMIENTO
APLASTAMIENTO, DAÑO
MECÁNICO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,CABLE EN BUENAS
CONDICIONES.OK
- VERIFICAR QUE LAS CONEXIONES SE ENCUENTREN AJUSTADAS Y
LOS CABLES ASEGURADOS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,LAS
CONXIONES ESTAN AJUSTADAS.OK
- VERIFICAR QUE EL CABLE DE TIERRA SE ENCUENTRA BIEN
AJUSTADO AL GENERADOR Y QUE SE ENCUENTRA
CONECTADO AL SISTEMA A TIERRA DEL EQUIPO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,EL
CABLE DE TIERRA DEL GENERADOR ESTA BIEN AJUSTADO.OK
DERWIN PEREIRA
ELECTRONICO
RIG 5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 8/17/2015 9/29/2015 10/2/2015
By: DERWIN LEONER PEREIRA JOHANNA CAROLINA QUEVEDO VICTOR LUIS ROLANDO BUSTAMANTE

7/28/2022 57 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050004337 Maintenance Type: //


Title: AIELECSIO - 500 HORAS / MANTENIMIENTO Maintenance Class: //
DEL ATERNADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 4/26/2015
Hourmeter Registered: Reported Current Counter Type
Count Value
2594.00 21260.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO.
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA.
REGISTRAR TEMPERATURAS.
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

HISTORY

7/28/2022 58 / 121
AMOS REPORT
MAINTENANCE DONE

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO SE EVIDENCIA
GOTEO.OK
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,COJINETES LIMPIOS.OK
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA...........39 °C.OK
REGISTRAR TEMPERATURAS.
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,FILTROS LIMPIOS.OK

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

DERWIN PEREIRA
ELECTRONICO
RIG 5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 4/26/2015 5/6/2015 5/6/2015
By: DERWIN LEONER PEREIRA DIANA MARCELA ARDILA DIANA MARCELA ARDILA

7/28/2022 59 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050004142 Maintenance Type: //


Title: AIELECSIO - 500 HORAS / MANTENIMIENTO Maintenance Class: //
DEL ATERNADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 1/19/2015
Hourmeter Registered: Reported Current Counter Type
Count Value
2039.00 20705.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO.
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA.
REGISTRAR TEMPERATURAS.
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

HISTORY

7/28/2022 60 / 121
AMOS REPORT
MAINTENANCE DONE

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE -------------------------------------------------- INSPECCIONO VISUALMENTE TODO EN BUEN ESTADO
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO ------------------------------------------------------------------- EN BUEN ESTADO
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA.
REGISTRAR TEMPERATURAS ------------------------------------------- TEMP 33oC
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO ----------------------------------------------------------- EN BUEN ESTADO

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

REALIZADO POR:
ENDER CARDOZO
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 1/19/2015 2/4/2015 2/4/2015
By: ENDER JOSE CARDOZO DIANA MARCELA ARDILA DIANA MARCELA ARDILA

7/28/2022 61 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050003539 Maintenance Type: //


Title: AIELECSIR - 20000 HORAS O 3 AÑOS Maintenance Class: //
/LIMPIEZA DEL ALTE Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 12/7/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
1446.00 20112.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

20000 HORAS O 3 AÑOS /LIMPIEZA DEL ALTERNADOR

-RETIRE LAS ETIQUETAS DE CIERRE Y HAGA UNA INSPECCIÓN VISUAL DE LOS


DEVANADOS PARA VERIFICAR LA PRESENCIA DE ACEITE, POLVO O CONTAMINACIÓN
EXCESIVA
-REALIZAR LIMPIEZA CON AIRE COMPRIMIDO Y SOLVENTE ELÉCTRICO.
-INSPECCIONE EL VENTILADOR Y SU EJE PARA VERIFICAR DAÑOS.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 30

HISTORY

20000 HORAS O 3 AÑOS /LIMPIEZA DEL ALTERNADOR

-RETIRE LAS ETIQUETAS DE CIERRE Y HAGA UNA INSPECCIÓN VISUAL DE LOS


DEVANADOS PARA VERIFICAR LA PRESENCIA DE ACEITE, POLVO O CONTAMINACIÓN
EXCESIVA ---------------------------------------------------------------------- NO PRESENTA CONTAMINACION EXCESIVA
-REALIZAR LIMPIEZA CON AIRE COMPRIMIDO Y SOLVENTE ELÉCTRICO ---------------- SE APLICO AIRE COMPRIMIDO
-INSPECCIONE EL VENTILADOR Y SU EJE PARA VERIFICAR DAÑOS ----------------------- NO PRESENTA DAÑOS VISUALES

Realizado por:
Ing. Ender J. Cardozo S.
Electronico
PTX-5857

7/28/2022 62 / 121
AMOS REPORT
MAINTENANCE DONE
SPARES USED
DISCIPLINES USED:

ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 12/7/2014 1/2/2015 1/2/2015
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 63 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050004101 Maintenance Type: //


Title: AIELECSIO - 500 HORAS / MANTENIMIENTO Maintenance Class: //
DEL ATERNADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 11/29/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
1440.00 20106.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO.
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA.
REGISTRAR TEMPERATURAS.
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

HISTORY

7/28/2022 64 / 121
AMOS REPORT
MAINTENANCE DONE

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE -------------------------------------------------- INSPECCIONO VISUALMENTE TODO EN BUEN ESTADO
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO ------------------------------------------------------------------- EN BUEN ESTADO
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA.
REGISTRAR TEMPERATURAS ------------------------------------------- TEMP 30oC
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO ----------------------------------------------------------- EN BUEN ESTADO

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

REALIZADO POR:
ENDER CARDOZO
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 11/29/2014 12/1/2014 12/1/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 65 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050004012 Maintenance Type: //


Title: AIELECSIO - 500 HORAS / MANTENIMIENTO Maintenance Class: //
DEL ATERNADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 11/17/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
-697.00 17969.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO.
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA.
REGISTRAR TEMPERATURAS.
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

HISTORY

7/28/2022 66 / 121
AMOS REPORT
MAINTENANCE DONE

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO SE OBSERVA GOTEO
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,BUENOS, REALIZA
LIMPIEZA.OK
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA.
REGISTRAR TEMPERATURAS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,31. °C.OK
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,FILTROS.OK

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

DERWIN PEREIRA
ELECTRONICO
RIG 5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 11/17/2014 12/1/2014 12/1/2014
By: DERWIN LEONER PEREIRA Victor Bustamante Victor Bustamante

7/28/2022 67 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050003664 Maintenance Type: //


Title: AIELECSIO - 500 HORAS / MANTENIMIENTO Maintenance Class: //
DEL ATERNADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 10/13/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
626.00 19292.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO.
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA.
REGISTRAR TEMPERATURAS.
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

HISTORY

7/28/2022 68 / 121
AMOS REPORT
MAINTENANCE DONE

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE -------------------------------------------------- INSPECCIONO VISUALMENTE TODO EN BUEN ESTADO
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO ------------------------------------------------------------------- EN BUEN ESTADO
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA.
REGISTRAR TEMPERATURAS ------------------------------------------- TEMP 32oC
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO ----------------------------------------------------------- EN BUEN ESTADO

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

SPARES USED
DISCIPLINES USED:

ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 10/13/2014 10/31/2014 10/31/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 69 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050003536 Maintenance Type: //


Title: AIELECSIO - 500 HORAS / MANTENIMIENTO Maintenance Class: //
DEL ATERNADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 8/24/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
228.00 18894.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HORAS / MANTENIMIENTO DEL ATERNADOR

-INSPECCIONAR VISUALMENTE DEL ALOJAMIENTO DE LOS COJINETES POR GOTEO O


EXCESO DE LUBRICANTE
-INSPECCION VISUAL DEL EXTERIOR DE LOS COJINETES, LIMPIE SI ES
NECESARIO.
-CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA.
REGISTRAR TEMPERATURAS.
VERIFIQUE QUE LOS FILTROS DE AIRE SE ENCUENTREN -LIMPIOS, REEMPLAZE DE
SER NECESARIO.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 29

HISTORY

7/28/2022 70 / 121
AMOS REPORT
MAINTENANCE DONE

2000 HORAS /INSPECCION DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR

-INSPECCIONAR VISUAL DE CABLES DE SALIDA DEL ESTATOR POR PRESENCIA DE


FALTA DE AISLAMIENTO O QUIEBRE --------------------------------------------- NO PRESENTA DAÑOS VISIBLES APARENTES.

-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS ------ TODAS LAS CONEXIONES AJUSTADAS.

-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES


FUSIBLES, CAPACITORES Y PROTECTOR CONTRA RAYOS ----------------- TODOS EN BUENAS CONDICIONES.

-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES


ELECTRICAS -------------------------------------------------------------------------------- TODOS EN BUENAS CONDICIONES.

-LIMPIAR DENTRO DE LA CAJA DE SALIDA, VENTILACION DE


AIRE, ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO, SI SE REQUIERE ------- SE LIMPIO CON TRAPO Y AIRE COMPRIMIDO.

-EN CASO TENERSE RODAMIENTOS DE BOLA, CHEQUEAR VIBRACIONES


CON UN INSTRUMENTO ADECUADO ------------------------------------------------------- VIBRACION = 3.00 mm/seg

-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES ------------------------------------------------------- SE APLICO GRASA CIPRINA.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 30

REALIZADO POR:
ING. ENDER CARDOZO SALAZAR
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 8/24/2014 9/5/2014 10/31/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 71 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050003537 Maintenance Type: //


Title: AIELECSIP - 2000 HORAS /INSPECCION DE Maintenance Class: //
ALTERNADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 8/24/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
228.00 18894.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

2000 HORAS /INSPECCION DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.


-INSPECCIONAR VISUAL DE CABLES DE SALIDA DEL ESTATOR POR PRESENCIA DE
FALTA DE AISLAMIENTO O QUIEBRE.
-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS.
-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES
FUSIBLES, CAPACITORES Y PROTECTOR CONTRA RAYOS.
-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES
ELECTRICAS.
-LIMPIAR DENTRO DE LA CAJA DE SALIDA, VENTILACION DE
AIRE, ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO, SI SE REQUIERE.
-EN CASO TENERSE RODAMIENTOS DE BOLA, CHEQUEAR VIBRACIONES
CON UN INSTRUMENTO ADECUADO.
-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 30

HISTORY

7/28/2022 72 / 121
AMOS REPORT
MAINTENANCE DONE

2000 HORAS /INSPECCION DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR

-INSPECCIONAR VISUAL DE CABLES DE SALIDA DEL ESTATOR POR PRESENCIA DE


FALTA DE AISLAMIENTO O QUIEBRE --------------------------------------------- NO PRESENTA DAÑOS VISIBLES APARENTES.

-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS ------ TODAS LAS CONEXIONES AJUSTADAS.

-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES


FUSIBLES, CAPACITORES Y PROTECTOR CONTRA RAYOS ----------------- TODOS EN BUENAS CONDICIONES.

-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES


ELECTRICAS -------------------------------------------------------------------------------- TODOS EN BUENAS CONDICIONES.

-LIMPIAR DENTRO DE LA CAJA DE SALIDA, VENTILACION DE


AIRE, ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO, SI SE REQUIERE ------- SE LIMPIO CON TRAPO Y AIRE COMPRIMIDO.

-EN CASO TENERSE RODAMIENTOS DE BOLA, CHEQUEAR VIBRACIONES


CON UN INSTRUMENTO ADECUADO ------------------------------------------------------- VIBRACION = 3.00 mm/seg

-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES ------------------------------------------------------- SE APLICO GRASA CIPRINA.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 30

REALIZADO POR:
ING. ENDER CARDOZO SALAZAR
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 8/24/2014 9/5/2014 10/31/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 73 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050003538 Maintenance Type: //


Title: AIELECSIQ - 8000 HORAS O 1 AÑO/ Maintenance Class: //
MEDICION DE AILSAMIE Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 8/24/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
228.00 18894.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

8000 HORAS O 1 AÑO/ MEDICION DE AILSAMIENTO ALTERNADOR

-CHEQUEAR EL AISLAMIENTO A TIERRA DE TODOS LOS DEVANADOS DEL ALTERNADOR:


ROTOR PRINCIPAL =
ESTATOR PRINCIPAL =
ROTOR EXCITATRIZ DE CAMPO =
ESTATOR DE EXCITATRIZ DE CAMPO =
-PARA GENERADORES CON GENERADOR DE MAGNETO PERMANENTE (PMG):
ROTOR DEL PMG =
ESTATOR DEL PMG =
-COMPRUEBE QUE LOS CALENTADORES DE ESPACIO FUNCIONAN CORRECTAMENTE
-COMPRUEBE EL AJUSTE DE LAS CONEXIONES ELECTRICAS DEL PLATO RECTIFICADOR
ROTATIVO.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 30

HISTORY

7/28/2022 74 / 121
AMOS REPORT
MAINTENANCE DONE

2000 HORAS /INSPECCION DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR

-INSPECCIONAR VISUAL DE CABLES DE SALIDA DEL ESTATOR POR PRESENCIA DE


FALTA DE AISLAMIENTO O QUIEBRE --------------------------------------------- NO PRESENTA DAÑOS VISIBLES APARENTES.

-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS ------ TODAS LAS CONEXIONES AJUSTADAS.

-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES


FUSIBLES, CAPACITORES Y PROTECTOR CONTRA RAYOS ----------------- TODOS EN BUENAS CONDICIONES.

-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES


ELECTRICAS -------------------------------------------------------------------------------- TODOS EN BUENAS CONDICIONES.

-LIMPIAR DENTRO DE LA CAJA DE SALIDA, VENTILACION DE


AIRE, ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO, SI SE REQUIERE ------- SE LIMPIO CON TRAPO Y AIRE COMPRIMIDO.

-EN CASO TENERSE RODAMIENTOS DE BOLA, CHEQUEAR VIBRACIONES


CON UN INSTRUMENTO ADECUADO ------------------------------------------------------- VIBRACION = 3.00 mm/seg

-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES ------------------------------------------------------- SE APLICO GRASA CIPRINA.

REFERENCIA:
INSTRUCTION MANUAL INSTALLATION OPERATION & MAINTENANCE STANDARD AC
GENERATOR
PAGINA: 30

REALIZADO POR:
ING. ENDER CARDOZO SALAZAR
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 8/24/2014 9/5/2014 10/31/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 75 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050002960 Maintenance Type: //


Title: AIELECSIM - 2000 HORAS / ALTERNADOR Maintenance Class: //
KATO: INSPECCION Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 6/29/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
0 18666.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

2000 HORAS / ALTERNADOR KATO: INSPECCION

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.


-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES
DE SALIDA DEL ESTATOR Y EL AISLAMIENTO.
-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS.
-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES
FUSIBLES, CAPACITORES Y PROTECTOR CONTRA RAYOS.
-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES
ELECTRICAS.
-LIMPIAR DENTRO DE LA CAJA DE SALIDA, ENTRADA DE
AIRE, ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO, SI SE REQUIERE.
-EN CASO TENERSE RODAMIENTOS DE BOLA, CHEQUEAR VIBRACIONES
CON UN INSTRUMENTO ADECUADO.
-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES.

HISTORY

7/28/2022 76 / 121
AMOS REPORT
MAINTENANCE DONE

2000 HORAS / ALTERNADOR KATO: INSPECCION

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.


-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES
DE SALIDA DEL ESTATOR Y EL AISLAMIENTO ----------------------------------- TODOS VISUALMENTE EN BUEN ESTADO
-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS ---------- SE VERIFICO AJUSTE DE CONEXIONES OK
-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES
FUSIBLES, CAPACITORES Y PROTECTOR CONTRA RAYOS ----------------- EN BUEN ESTADO, COENXIONES AJUSTADAS
-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES
ELECTRICAS ------------------------------------------------------------------------ TODOS EN BUENAS CONDICIONES
-LIMPIAR DENTRO DE LA CAJA DE SALIDA, ENTRADA DE
AIRE, ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO, SI SE REQUIERE ------------ SE REALIZA LIMPIEZA CON TRAPO Y
AIRE COMPRIMIDO
-EN CASO TENERSE RODAMIENTOS DE BOLA, CHEQUEAR VIBRACIONES
CON UN INSTRUMENTO ADECUADO --------------------------------------------------- VIBRACIÓN 2.4 mm/s
-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES --------------------------- SE ENGRASO

REALIZADO POR:
ENDER J. CARDOZO SALAZAR
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

ELEC 2 Hour(s)
Total Duration : 2.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 2.00 Hour(s)

Completed Controlled Filed


Date: 6/29/2014 7/9/2014 10/31/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 77 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050003120 Maintenance Type: //


Title: AIELECS70 - 1000 HORAS/ MANTENIMIENTO Maintenance Class: //
DE GENERADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 6/28/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
0 18666.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

1000 HORAS/ MANTENIMIENTO DE GENERADOR

1.,,CHEQUEAR LA RESISTENCIA DE AISLAMIENTO A TIERRA DE TODOS LOS


ARROLLAMIENTOS DEL GENERADOR ( MEGADO DE GENERADOR)
2.,,LIMPIAR CON AIRE COMPRIMIDO Y LAVAR CONSOLVENTE DILÉCTRICO

HISTORY

1000 HORAS/ MANTENIMIENTO DE GENERADOR

1.,,CHEQUEAR LA RESISTENCIA DE AISLAMIENTO A TIERRA DE TODOS LOS


ARROLLAMIENTOS DEL GENERADOR ( MEGADO DE GENERADOR) ---------------------- AISLAMIENTO = 62 MEGAOHMS,
CONTINUIDAD = 0.1 OHMS
2.,,LIMPIAR CON AIRE COMPRIMIDO Y LAVAR CONSOLVENTE DILÉCTRICO ------------ SE REALIZA LIMPIEZA

REALIZADO POR:
ENDER J. CARDOZO SALAZAR
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

7/28/2022 78 / 121
AMOS REPORT
MAINTENANCE DONE
ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 6/28/2014 7/9/2014 10/31/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 79 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050003202 Maintenance Type: //


Title: AIELECSHG - 500 HRS / CHEQUEO DE Maintenance Class: //
GENERADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 6/28/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
0 18666.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HRS / CHEQUEO DE GENERADOR

1.,,INSPECCIONAR VISUALMENTE LOS COJINETES POR GOTEO O EXCESO DE


LUBRICANTE
2.,,CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE
POTENCIA. REGISTRAR TEMPERATURAS.
3.,,CHEQUEAR LOS NIVELES DE VIBRACIÓN. REGISTRAR
4.,,VERIFICAR LA PERNERÍA Y EL MONTAJE DE LAS TAPAS

HISTORY

500 HRS / CHEQUEO DE GENERADOR

1.,,INSPECCIONAR VISUALMENTE LOS COJINETES POR GOTEO O EXCESO DE


LUBRICANTE ---------------------------------------------------------------------------------------- INSPECCIONO VISUALMENTE
2.,,CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE
POTENCIA. REGISTRAR TEMPERATURAS ---------------------------------------------------- 30 oC
3.,,CHEQUEAR LOS NIVELES DE VIBRACIÓN. REGISTRAR --------------------------------- VIBRACION = 2.4 mm/s
4.,,VERIFICAR LA PERNERÍA Y EL MONTAJE DE LAS TAPAS ------------------------------ TODOS LOS TORNILLOS/PERNOS
AJUSTADOS, TAPAS EN BUENAS CONDICIONES

REALIZADO POR:
ENDER J. CARDOZO SALAZAR
ELECTRONICO
PTX-5857

7/28/2022 80 / 121
AMOS REPORT
MAINTENANCE DONE
SPARES USED
DISCIPLINES USED:

ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 6/28/2014 7/9/2014 10/31/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 81 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050003122 Maintenance Type: //


Title: AIELECSHG - 500 HRS / CHEQUEO DE Maintenance Class: //
GENERADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 5/25/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
-530.00 18136.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HRS / CHEQUEO DE GENERADOR

1.,,INSPECCIONAR VISUALMENTE LOS COJINETES POR GOTEO O EXCESO DE


LUBRICANTE
2.,,CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE
POTENCIA. REGISTRAR TEMPERATURAS.
3.,,CHEQUEAR LOS NIVELES DE VIBRACIÓN. REGISTRAR
4.,,VERIFICAR LA PERNERÍA Y EL MONTAJE DE LAS TAPAS

HISTORY

0 HRS / CHEQUEO DE GENERADOR

1.,,INSPECCIONAR VISUALMENTE LOS COJINETES POR GOTEO O EXCESO DE


LUBRICANTE,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO SE OBSERVA GOTEO
2.,,CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE
POTENCIA. REGISTRAR TEMPERATURAS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,37 ° C.OK
3.,,CHEQUEAR LOS NIVELES DE VIBRACIÓN. REGISTRAR,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO SE EVIDENCIA VIBRACION
4.,,VERIFICAR LA PERNERÍA Y EL MONTAJE DE LAS TAPAS,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE AJUSTA TORNILLERIA. OK

DERWIN PEREIRA
ELECTRONICO
RIG 5857

SPARES USED
DISCIPLINES USED:
7/28/2022 82 / 121
AMOS REPORT
MAINTENANCE DONE
N.D. 0 Hour(s)
Total Duration : 5.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 5/25/2014 6/16/2014 10/31/2014
By: DERWIN LEONER PEREIRA Victor Bustamante Victor Bustamante

7/28/2022 83 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050002562 Maintenance Type: //


Title: AIELECSH0 - 6 MESES / MANTENIMIENTO Maintenance Class: //
SEMESTRAL DE ALT Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 4/14/2014
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / MANTENIMIENTO SEMESTRAL DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.


-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES
DE SALIDA DEL ESTATOR Y EL AISLAMIENTO.
-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS.
-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES<(><<)>(>,<(><<)>)>
FUSIBLES,CAPACITORES Y PROTECTOR CONTRA RAYOS.
-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES
ELECTRICAS.
-LIMPIAR DENTRO DE LA CAJA DE SALIDA,ENTRADA DE
AIRE,ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO,SI SE REQUIERE.
-EN CASO TENERSE RODAMIENTOS DE BOLA,CHEQUEAR VIBRACIONES
CON UN INSTRUMENTO ADECUADO.
-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES.

HISTORY

7/28/2022 84 / 121
AMOS REPORT
MAINTENANCE DONE

6 MESES / MANTENIMIENTO SEMESTRAL DE GENERADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.

-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES


DE SALIDA DEL ESTATOR Y EL AISLAMIENTO.----------------------- TERMINALES SIN DAÑOS VISUALES. AISLAMIENTO = 1
MEGA OHMS

-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS. ------------- CONEXIONES AJUSTADAS

-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES<(>,<)>


FUSIBLES,CAPACITORES Y PROTECTOR CONTRA RAYOS. ------------------------CONEXIONES AJUSTADAS. SIN DAÑOS
FISICOS APARENTES.

-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES


ELECTRICAS. --------------------------------------- EN BUEN ESTADO

-LIMPIAR DENTRO DE LA CAJA DE SALIDA,ENTRADA DE


AIRE,ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO,SI SE REQUIERE. -------- SE LIMPIO CON AIRE COMPRIMIDO.

-EN CASO TENERSE RODAMIENTOS DE BOLA,CHEQUEAR VIBRACIONES


CON UN INSTRUMENTO ADECUADO. ---------------------- NO SE TIENE INSTRUMENTO

-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES. ------------------ SE ENGRASÓ

REALIZADO POR:
ENDER J. CARDOZO S.
ELECTRONICO
PTX-5857

6 MESES / MANTENIMIENTO SEMESTRAL DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.

-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES


DE SALIDA DEL ESTATOR Y EL AISLAMIENTO. ----------------------------- TERMINALES SIN DAÑOS VISIBLES. AISLAMIENTO = 1
MEGA OHMS

-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS. ----- CONEXIONES ELECTRICAS AJUSTADAS.

-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES<(><<)>(>,<(><<)>)>


FUSIBLES,CAPACITORES Y PROTECTOR CONTRA RAYOS. ---------------- CONEXIONES ELECTRICAS AJUSTADAS. NO
PRESENTA DAÑOS FISICOS APARENTES.

-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES


ELECTRICAS. ---------------------------------------------------------- EN BUENAS CONDICIONES.

-LIMPIAR DENTRO DE LA CAJA DE SALIDA,ENTRADA DE


AIRE,ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO,SI SE REQUIERE. ---------------- SE LIMPIO CON AIRE COMPRIMIDO.

-EN CASO TENERSE RODAMIENTOS DE BOLA,CHEQUEAR VIBRACIONES


CON UN INSTRUMENTO ADECUADO. ------------------------------ NO SE TIENE INSTRUMENTO

-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES. --------------------- SE ENGRASO

REALIZADO POR:
ENDER J. CARDOZO S.
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

ELEC 8 Hour(s)
Total Duration : 8.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 8.00 Hour(s)

7/28/2022 85 / 121
AMOS REPORT
MAINTENANCE DONE
Completed Controlled Filed
Date: 4/14/2014 4/28/2014 6/2/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 86 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050002562 Maintenance Type: //


Title: AIELECSH0 - 6 MESES / MANTENIMIENTO Maintenance Class: //
SEMESTRAL DE ALT Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 4/14/2014
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / MANTENIMIENTO SEMESTRAL DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.


-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES
DE SALIDA DEL ESTATOR Y EL AISLAMIENTO.
-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS.
-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES<(><<)>(>,<(><<)>)>
FUSIBLES,CAPACITORES Y PROTECTOR CONTRA RAYOS.
-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES
ELECTRICAS.
-LIMPIAR DENTRO DE LA CAJA DE SALIDA,ENTRADA DE
AIRE,ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO,SI SE REQUIERE.
-EN CASO TENERSE RODAMIENTOS DE BOLA,CHEQUEAR VIBRACIONES
CON UN INSTRUMENTO ADECUADO.
-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES.

HISTORY

7/28/2022 87 / 121
AMOS REPORT
MAINTENANCE DONE

6 MESES / MANTENIMIENTO SEMESTRAL DE GENERADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.

-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES


DE SALIDA DEL ESTATOR Y EL AISLAMIENTO.----------------------- TERMINALES SIN DAÑOS VISUALES. AISLAMIENTO = 1
MEGA OHMS

-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS. ------------- CONEXIONES AJUSTADAS

-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES<(>,<)>


FUSIBLES,CAPACITORES Y PROTECTOR CONTRA RAYOS. ------------------------CONEXIONES AJUSTADAS. SIN DAÑOS
FISICOS APARENTES.

-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES


ELECTRICAS. --------------------------------------- EN BUEN ESTADO

-LIMPIAR DENTRO DE LA CAJA DE SALIDA,ENTRADA DE


AIRE,ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO,SI SE REQUIERE. -------- SE LIMPIO CON AIRE COMPRIMIDO.

-EN CASO TENERSE RODAMIENTOS DE BOLA,CHEQUEAR VIBRACIONES


CON UN INSTRUMENTO ADECUADO. ---------------------- NO SE TIENE INSTRUMENTO

-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES. ------------------ SE ENGRASÓ

REALIZADO POR:
ENDER J. CARDOZO S.
ELECTRONICO
PTX-5857

6 MESES / MANTENIMIENTO SEMESTRAL DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.

-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES


DE SALIDA DEL ESTATOR Y EL AISLAMIENTO. ----------------------------- TERMINALES SIN DAÑOS VISIBLES. AISLAMIENTO = 1
MEGA OHMS

-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS. ----- CONEXIONES ELECTRICAS AJUSTADAS.

-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES<(><<)>(>,<(><<)>)>


FUSIBLES,CAPACITORES Y PROTECTOR CONTRA RAYOS. ---------------- CONEXIONES ELECTRICAS AJUSTADAS. NO
PRESENTA DAÑOS FISICOS APARENTES.

-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES


ELECTRICAS. ---------------------------------------------------------- EN BUENAS CONDICIONES.

-LIMPIAR DENTRO DE LA CAJA DE SALIDA,ENTRADA DE


AIRE,ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO,SI SE REQUIERE. ---------------- SE LIMPIO CON AIRE COMPRIMIDO.

-EN CASO TENERSE RODAMIENTOS DE BOLA,CHEQUEAR VIBRACIONES


CON UN INSTRUMENTO ADECUADO. ------------------------------ NO SE TIENE INSTRUMENTO

-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES. --------------------- SE ENGRASO

REALIZADO POR:
ENDER J. CARDOZO S.
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

ELEC 8 Hour(s)
Total Duration : 8.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 8.00 Hour(s)

7/28/2022 88 / 121
AMOS REPORT
MAINTENANCE DONE
Completed Controlled Filed
Date: 4/14/2014 4/28/2014 6/2/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 89 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050002961 Maintenance Type: //


Title: AIELECS70 - 1000 HORAS/ MANTENIMIENTO Maintenance Class: //
DE GENERADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 4/14/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
-1503.00 17163.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

1000 HORAS/ MANTENIMIENTO DE GENERADOR

1.,,CHEQUEAR LA RESISTENCIA DE AISLAMIENTO A TIERRA DE TODOS LOS


ARROLLAMIENTOS DEL GENERADOR ( MEGADO DE GENERADOR)
2.,,LIMPIAR CON AIRE COMPRIMIDO Y LAVAR CONSOLVENTE DILÉCTRICO

HISTORY

1000 HRS / CHEQUEO DE GENERADOR

1.,CHEQUEAR LA RESISTENCIA DE AISLAMIENTO A TIERRA DE TODOS LOS ARROLLAMIENTOS DEL GENERADOR


(MEGADO DEL GENERADOR).-------------------------------- AISLAMIENTO = 1 MEGA OHMS

2.,,LIMPIAR CON AIRE COMPRIMIDO Y LAVAR CON SOLVENTE DIELECTRICO ------------------ SE LIMPIO CON AIRE
COMPRIMIDO

REALIZADO POR:
ENDER J. CARDOZO S.
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

7/28/2022 90 / 121
AMOS REPORT
MAINTENANCE DONE
ELEC 2 Hour(s)
Total Duration : 2.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 2.00 Hour(s)

Completed Controlled Filed


Date: 4/14/2014 4/28/2014 6/2/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 91 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050003056 Maintenance Type: //


Title: AIELECSHG - 500 HRS / CHEQUEO DE Maintenance Class: //
GENERADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 4/14/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
-1503.00 17163.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HRS / CHEQUEO DE GENERADOR

1.,,INSPECCIONAR VISUALMENTE LOS COJINETES POR GOTEO O EXCESO DE


LUBRICANTE
2.,,CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE
POTENCIA. REGISTRAR TEMPERATURAS.
3.,,CHEQUEAR LOS NIVELES DE VIBRACIÓN. REGISTRAR
4.,,VERIFICAR LA PERNERÍA Y EL MONTAJE DE LAS TAPAS

HISTORY

7/28/2022 92 / 121
AMOS REPORT
MAINTENANCE DONE

500 HRS / CHEQUEO DE GENERADOR

1.,,INSPECCIONAR VISUALMENTE LOS COJINETES POR GOTEO O EXCESO DE


LUBRICANTE ---------------------------------------------------------------- SE INSPECCIONO VISUALMENTE.

2.,,CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE


POTENCIA. REGISTRAR TEMPERATURAS. ------------------------ 33oC

3.,,CHEQUEAR LOS NIVELES DE VIBRACIÓN. REGISTRAR ---- NO SE TIENE INSTRUMENTO.

4.,,VERIFICAR LA PERNERÍA Y EL MONTAJE DE LAS TAPAS ---- PERNOS EN BUEN ESTADO Y AJUSTADOS.

REALIZADO POR:
ENDER J. CARDOZO S.
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

ELEC 2 Hour(s)
Total Duration : 2.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 2.00 Hour(s)

Completed Controlled Filed


Date: 4/14/2014 4/28/2014 6/2/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 93 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050002962 Maintenance Type: //


Title: AIELECSHG - 500 HRS / CHEQUEO DE Maintenance Class: //
GENERADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 3/22/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
-2014.00 16652.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HRS / CHEQUEO DE GENERADOR

1.,,INSPECCIONAR VISUALMENTE LOS COJINETES POR GOTEO O EXCESO DE


LUBRICANTE
2.,,CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE
POTENCIA. REGISTRAR TEMPERATURAS.
3.,,CHEQUEAR LOS NIVELES DE VIBRACIÓN. REGISTRAR
4.,,VERIFICAR LA PERNERÍA Y EL MONTAJE DE LAS TAPAS

HISTORY

500 HRS / CHEQUEO DE GENERADOR

1.,,INSPECCIONAR VISUALMENTE LOS COJINETES POR GOTEO O EXCESO DE


LUBRICANTE,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,NO PRESENTA GOTEO.
2.,,CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE
POTENCIA. REGISTRAR TEMPERATURAS.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,39 ° C.OK
3.,,CHEQUEAR LOS NIVELES DE VIBRACIÓN. REGISTRAR,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,VIBRACION NORMALES.OK
4.,,VERIFICAR LA PERNERÍA Y EL MONTAJE DE LAS TAPAS,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,SE AJUSTA TORNILLERIA.OK

DERWIN PEREIRA
ELECTRONICO
RIG 5857

SPARES USED
DISCIPLINES USED:

7/28/2022 94 / 121
AMOS REPORT
MAINTENANCE DONE
N.D. 0 Hour(s)
Total Duration : 4.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 3/22/2014 3/25/2014 6/2/2014
By: DERWIN LEONER PEREIRA Victor Bustamante Victor Bustamante

7/28/2022 95 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050002914 Maintenance Type: //


Title: AIELECSIN - 8000 HORAS / ALTERNADOR Maintenance Class: //
KATO: MANTENIMIE Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 2/21/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
-2542.00 16124.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

8000 HORAS / ALTERNADOR KATO: MANTENIMIENTO

-CHEQUEAR AISLAMIENTO Y CONEXION A TIERRA.


-CHEQUEAR ESPACIAMIENTO ENTRE HEATERS.
-CHEQUEAR ENTREHIERRO.
-PARA GENERADORES CON ENTRADA DE ACEITE: REEMPLAZAR ACEITE.

HISTORY

8000 HORAS / ALTERNADOR KATO: MANTENIMIENTO

-CHEQUEAR AISLAMIENTO Y CONEXION A TIERRA------------------------------ ESTATOR PRINCIPAL = 8.81 MOhms / ROTOR


PRINCIPAL = 0.9 MOhms / ESTATOR SECUNDARIO = 150.8 MOhms / ROTOR SEC = 22.1 MOhms.

-CHEQUEAR ESPACIAMIENTO ENTRE HEATERS------------------------------------- SE VERIFICO “OK”

-CHEQUEAR ENTREHIERRO----------------------------------------------------------------- SE VERIFICO “OK”

-PARA GENERADORES CON ENTRADA DE ACEITE: REEMPLAZAR ACEITE—----NO APLICA

SPARES USED
DISCIPLINES USED:

ELEC 5 Hour(s)
Total Duration : 5.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 5.00 Hour(s)

7/28/2022 96 / 121
AMOS REPORT
MAINTENANCE DONE
Completed Controlled Filed
Date: 2/21/2014 3/3/2014 3/7/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 97 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050002915 Maintenance Type: //


Title: AIELECSIM - 2000 HORAS / ALTERNADOR Maintenance Class: //
KATO: INSPECCION Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 2/21/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
-2542.00 16124.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

2000 HORAS / ALTERNADOR KATO: INSPECCION

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.


-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES
DE SALIDA DEL ESTATOR Y EL AISLAMIENTO.
-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS.
-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES
FUSIBLES, CAPACITORES Y PROTECTOR CONTRA RAYOS.
-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES
ELECTRICAS.
-LIMPIAR DENTRO DE LA CAJA DE SALIDA, ENTRADA DE
AIRE, ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO, SI SE REQUIERE.
-EN CASO TENERSE RODAMIENTOS DE BOLA, CHEQUEAR VIBRACIONES
CON UN INSTRUMENTO ADECUADO.
-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES.

HISTORY

7/28/2022 98 / 121
AMOS REPORT
MAINTENANCE DONE

2000 HORAS / ALTERNADOR KATO: INSPECCION

-REMOVER LA CAJA DE SALIDA DEL GENERADOR ------------------------------------- OK

-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES


DE SALIDA DEL ESTATOR Y EL AISLAMIENTO ------------------------------------------- NO TIENE DAÑOS VISIBLES.

-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS----------------- SE VERIFICO AJUSTE OK.

-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES


FUSIBLES, CAPACITORES Y PROTECTOR CONTRA RAYOS -------------------------- SE VERIFICÓ AJUSTE OK, NO PRESENTAN
DAÑOS VISIBLES.

-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES


ELECTRICAS ----------------------------------------------------------------------------------------- SE VERIFICO OK

-LIMPIAR DENTRO DE LA CAJA DE SALIDA, ENTRADA DE


AIRE, ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO, SI SE REQUIERE ------- SE LIMPIO CON AIRE COMPRIMIDO.

-EN CASO TENERSE RODAMIENTOS DE BOLA, CHEQUEAR VIBRACIONES


CON UN INSTRUMENTO ADECUADO ------------------------------------------------------ NO SE TIENE INSTRUMENTO PARA REALIZAR
MEDICION DE VIBRACIÓN.

-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES --------------------------- SE REENGRASARON.

REALIZADO POR:
ING. ENDER J. CARDOZO S.
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 2/21/2014 3/3/2014 3/7/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 99 / 121
AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050002916 Maintenance Type: //


Title: AIELECS70 - 1000 HORAS/ MANTENIMIENTO Maintenance Class: //
DE GENERADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 2/21/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
-2542.00 16124.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

1000 HORAS/ MANTENIMIENTO DE GENERADOR

1.,,CHEQUEAR LA RESISTENCIA DE AISLAMIENTO A TIERRA DE TODOS LOS


ARROLLAMIENTOS DEL GENERADOR ( MEGADO DE GENERADOR)
2.,,LIMPIAR CON AIRE COMPRIMIDO Y LAVAR CONSOLVENTE DILÉCTRICO

HISTORY

1000 HORAS / MANTENIMIENTO DE GENERADOR

-CHEQUEAR LA RESISTENCIA DE AISLAMIENTO A TIERRA DE TODOS LOS ARROLLAMIENTOS DEL GENERADOR


(MEGADO DE GENERADOR) ----------------- ESTATOR PRINCIPAL = 8.81 MOhms / ROTOR PRINCIPAL = 0.9 MOhms / ESTATOR
SECUNDARIO = 150.8 MOhms / ROTOR SEC = 22.1 MOhms.

-LIMPIAR CON AIRE COMPRIMIDO Y LAVAR CON SOLVENTE DIELECTRICO ---- SE APLICO SOLVENTE DIELECTRICO Y
AIRE COMPRIMIDO.

REALIZADO POR:
ING. ENDER J. CARDOZO S.
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

7/28/2022 100 / 121


AMOS REPORT
MAINTENANCE DONE
ELEC 4 Hour(s)
Total Duration : 4.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 4.00 Hour(s)

Completed Controlled Filed


Date: 2/21/2014 3/3/2014 3/7/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 101 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050002917 Maintenance Type: //


Title: AIELECSHG - 500 HRS / CHEQUEO DE Maintenance Class: //
GENERADOR Maintenance Cause: //
Frequency: 0-I_C_OREMOTORE Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 2/21/2014
Hourmeter Registered: Reported Current Counter Type
Count Value
-2542.00 16124.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

500 HRS / CHEQUEO DE GENERADOR

1.,,INSPECCIONAR VISUALMENTE LOS COJINETES POR GOTEO O EXCESO DE


LUBRICANTE
2.,,CHEQUEAR TEMPERATURAS DE LOS ARROLLAMIENTOS DE LOS CABLES DE
POTENCIA. REGISTRAR TEMPERATURAS.
3.,,CHEQUEAR LOS NIVELES DE VIBRACIÓN. REGISTRAR
4.,,VERIFICAR LA PERNERÍA Y EL MONTAJE DE LAS TAPAS

HISTORY

7/28/2022 102 / 121


AMOS REPORT
MAINTENANCE DONE

500 HORAS / CHEQUEO DE GENERADOR

1.INSPECCIONAR VISUALMENTE LOS COJINETES POR GOTEO O EXCESO DE LUBRICANTE


--------------------------------------------------------------------- N/A

2.CHEQUEAR TEMPERATURA DE LOS ARROLLAMIENTOS DE LOS CABLES DE POTENCIA, REGISTRAR TEMPERATURA


------------------------------- 42 Oc

3.CHEQUEAR LOS NIVELES DE VIBRACION. REGISTRAR ---------- NO SE TIENE INSTRUMENTO PARA REALIZAR MEDICION
DE VIBRACIÓN.

4.VERIFICAR LA PERNERIA Y EL MONTAJE DE TAPAS ------------- SE VERIFICO OK

REALIZADO POR:
ING. ENDER J. CARDOZO S.
ELECTRONICO
PTX-5857

SPARES USED
DISCIPLINES USED:

ELEC 3 Hour(s)
Total Duration : 2.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 2/21/2014 3/3/2014 3/7/2014
By: ENDER JOSE CARDOZO Victor Bustamante Victor Bustamante

7/28/2022 103 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050001824 Maintenance Type: //


Title: AIELECSHK - 1 AÑO / MANTENIMIENTO Maintenance Class: //
ANUAL DE ALTERNADO Maintenance Cause: //
Frequency: 12 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 8/20/2013
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

1 AÑO / MANTENIMIENTO ANUAL DE ALTERNADOR

-CHEQUEAR AISLAMIENTO Y CONEXION A TIERRA.


-CHEQUEAR ESPACIAMIENTO ENTRE HEATERS.
-CHEQUEAR ENTREHIERRO.
-PARA GENERADORES CON ENTRADA DE ACEITE: REEMPLAZAR ACEITE.

HISTORY

1 AÑO / MANTENIMIENTO ANUAL DE ALTERNADOR

-CHEQUEAR AISLAMIENTO Y CONEXION A TIERRA. --------- RESISTENCIA = 0.1 OHMS AISLAMIENTO = 21 MOHMS.

-CHEQUEAR ESPACIAMIENTO ENTRE HEATERS. -------------- HEATERS EN BUEN ESTADO

-CHEQUEAR ENTREHIERRO. ------------------------------------------ ENTREHIERRO EN BUEN ESTADO.

-PARA GENERADORES CON ENTRADA DE ACEITE: REEMPLAZAR ACEITE. --- N/A

Realizado por:
Ender Cardozo
Electrónico
PTX-5857

SPARES USED
DISCIPLINES USED:

7/28/2022 104 / 121


AMOS REPORT
MAINTENANCE DONE
ELEC 3 Hour(s)
Total Duration : 3.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 3.00 Hour(s)

Completed Controlled Filed


Date: 8/20/2013 9/10/2013 4/29/2019
By: ENDER JOSE CARDOZO Chavez Jhohan ROSAURA DEL VALLE SARMIENTO

7/28/2022 105 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050002136 Maintenance Type: //


Title: AIELECSH0 - 6 MESES / MANTENIMIENTO Maintenance Class: //
SEMESTRAL DE ALT Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 7/28/2013
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / MANTENIMIENTO SEMESTRAL DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.


-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES
DE SALIDA DEL ESTATOR Y EL AISLAMIENTO.
-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS.
-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES<(><<)>(>,<(><<)>)>
FUSIBLES,CAPACITORES Y PROTECTOR CONTRA RAYOS.
-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES
ELECTRICAS.
-LIMPIAR DENTRO DE LA CAJA DE SALIDA,ENTRADA DE
AIRE,ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO,SI SE REQUIERE.
-EN CASO TENERSE RODAMIENTOS DE BOLA,CHEQUEAR VIBRACIONES
CON UN INSTRUMENTO ADECUADO.
-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES.

HISTORY

7/28/2022 106 / 121


AMOS REPORT
MAINTENANCE DONE

6 MESES / MANTENIMIENTO SEMESTRAL DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.----------------------------------------------------------------SE DESTAPA OK


-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES
DE SALIDA DEL ESTATOR Y EL AISLAMIENTO.-----------------------------------------------------------------------TERMINALES EN BUENAS
CONDICIONES, ESTATOR = 0.1 OHMIOS / 12 M. OHMIOS
-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS.--------------------------------------CONEXIONES BIEN
AJUSTADAS
-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES<(><<)>(>,<(><<)>)>
FUSIBLES,CAPACITORES Y PROTECTOR CONTRA RAYOS.---------------------------------------------------CONEXIONES EN BUEN
ESTADO
-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES
ELECTRICAS.--------------------------------------------------------------------------------------------------------------------------------TODO EN BUENAS
CONDICIONES
-LIMPIAR DENTRO DE LA CAJA DE SALIDA,ENTRADA DE
AIRE,ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO,SI SE REQUIERE.-------------------------------SE LIMPIA CON AIRE Y
SOLVENTE DIELECTRICO
-EN CASO TENERSE RODAMIENTOS DE BOLA,CHEQUEAR VIBRACIONES
CON UN INSTRUMENTO ADECUADO.----------------------------------------------------------------------------------------NO SE CUENTA CON
MEDIDOR DE VIBRACIONES
-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES.--------------------------------------------------------SE ENGRASAN

REALIZADO POR:

JORGE RODRIGUEZ
ASST ELECTRONICO
PTX 5857

SPARES USED
DISCIPLINES USED:

ELEC 2 Hour(s)
Total Duration : 2.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 2.00 Hour(s)

Completed Controlled Filed


Date: 7/28/2013 8/8/2013 4/29/2019
By: Settimio Fasciani Chavez Jhohan ROSAURA DEL VALLE SARMIENTO

7/28/2022 107 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050001736 Maintenance Type: //


Title: AIELECSH0 - 6 MESES / MANTENIMIENTO Maintenance Class: //
SEMESTRAL DE ALTERNADOR Maintenance Cause: //
Frequency: 6 Month(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 1/30/2013
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

6 MESES / MANTENIMIENTO SEMESTRAL DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.


-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES
DE SALIDA DEL ESTATOR Y EL AISLAMIENTO.
-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS.
-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES<(><<)>(>,<(><<)>)>
FUSIBLES,CAPACITORES Y PROTECTOR CONTRA RAYOS.
-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES
ELECTRICAS.
-LIMPIAR DENTRO DE LA CAJA DE SALIDA,ENTRADA DE
AIRE,ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO,SI SE REQUIERE.
-EN CASO TENERSE RODAMIENTOS DE BOLA,CHEQUEAR VIBRACIONES
CON UN INSTRUMENTO ADECUADO.
-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES.

HISTORY

7/28/2022 108 / 121


AMOS REPORT
MAINTENANCE DONE

6 MESES / MANTENIMIENTO SEMESTRAL DE ALTERNADOR

-REMOVER LA CAJA DE SALIDA DEL GENERADOR.


-INSPECCIONAR PRESENCIA DE DAÑO O QUIEBRE EN LOS TERMINALES
DE SALIDA DEL ESTATOR Y EL AISLAMIENTO.........SE REALIZO
-CHEQUEAR AJUSTES EN TODAS LAS CONEXIONES ELECTRICAS.......SE REALIZO
-CHEQUEAR SOLTURAS O DAÑO FISICO EN TRANSFORMADORES<(><<)>(>,<(><<)>)>
FUSIBLES,CAPACITORES Y PROTECTOR CONTRA RAYOS........SE REALIZO
-CHEQUEAR ESPACIAMIENTO CABLES CONDUCTORES Y CONEXIONES
ELECTRICAS......SE REALIZO
-LIMPIAR DENTRO DE LA CAJA DE SALIDA,ENTRADA DE
AIRE,ALOJAMIENTOS DE RODAMIENTOS Y BAFLES DE AIRE
CON AIRE COMPRIMIDO Y SOLVENTE DIELECTRICO,SI SE REQUIERE...........SE REALIZO
-EN CASO TENERSE RODAMIENTOS DE BOLA,CHEQUEAR VIBRACIONES
CON UN INSTRUMENTO ADECUADO................SE REALIZO DE FORMA MANUAL
-RE-ENGRASAR LOS RODAMIENTOS RE-ENGRASABLES.......NO SE PUDO ENGRASAR POR NO TENER GRASSA. YA SE
SOLICITO. RIM -13-012

DERWIN PEREIRA
ELECTRONICO

SPARES USED
DISCIPLINES USED:

N.D. 0 Hour(s)
Total Duration : 2.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) :

Completed Controlled Filed


Date: 1/30/2013 2/5/2013 4/29/2019
By: Vincenzo Rana Condor Percy ROSAURA DEL VALLE SARMIENTO

7/28/2022 109 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050000917 Maintenance Type: //


Title: AIELECIR - 2000 HRS / INSPECT Maintenance Class: //
GENERATOR/ALTERNATOR Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 7/21/2010
Hourmeter Registered: Reported Current Counter Type
Count Value
-13703.00 4963.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

2000 HRS / INSPECT GENERATOR/ALTERNATOR

-DRY GENERATOR
-INSPECT GENERATOR SET VIBRATION
-CHECK STATOR LEAD
-LUBRICATE BEARINGS

HISTORY

Effettuate misure del traferro tra statore e rotore che sono risultate pari a: 0,85 ad ore 12:00 ; 0,85 ad ore 03:00 ; 0,75 ad ore 06:00 ;
0,90 ad ore 09:00.

SPARES USED
DISCIPLINES USED:

ABSE 2 Hour(s)
ELEC 2 Hour(s)
Total Duration : 2.00 Hour(s) Total Down Time: 2.00 Hour(s) Total man-hour(s) : 4.00 Hour(s)

Completed Controlled Filed


Date: 7/21/2010
By:

7/28/2022 110 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050001731 Maintenance Type: //


Title: AIELECSGZ - 1 MES / INSPECCION MENSUAL Maintenance Class: //
DE GENERADOR Maintenance Cause: //
Frequency: 4 Week(s) Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 5/26/2010
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

1 MES / INSPECCION MENSUAL DE GENERADOR

-CHEQUEAR DEVANADOS,LIMPIARLOS Y MEGAR (REGISTRAR LECTURAS).


-CON EL GENERADOR AISLADO, RETIRE LAS TAPAS Y RETIRE POLVO Y
LA SUCIEDAD CON AIRE COMPRIMIDO DE BAJA PRESION.
-INSPECCIONE LOS BOBINADOS PARA VER SI HAY DAÑOS Y SEÑALES DE
RECALENTAMIENTO. REVISE LAS CONEXIONES EN LOS ANILLOS DE
DIODOS Y TODOS LOS CABLEADOS INTERNOS PARA VER SI HAY
PELADURAS Y DESGASTES.
-DESCONECTE LOS CABLES DE DIODO Y EL MEGGER DE TODOS LOS
BOBINADOS DE CAMPO Y DE EXCITADOR. REGISTRE LOS RESULTADOS.

NOTA: ESTA RUTINA DEBE REALIZARSE MENSUALMENTE EN TODOS LOS GENERADORES


DE FORMA ESCALONADA, SEGUN LO PERMITAN LAS OPERACIONES.

HISTORY

7/28/2022 111 / 121


AMOS REPORT
MAINTENANCE DONE

1 MES / INSPECCION MENSUAL DE GENERADOR

-CHEQUEAR DEVANADOS,LIMPIARLOS Y MEGAR (REGISTRAR LECTURAS)............DEVANADOS BASTANTES SUCIOS, SE


LIMPIARON CON TRAPO Y SOLVENTE DIELECTRICO, ADICIONALMENTE SE APLICO AIRE COMPRIMIDO.
-CON EL GENERADOR AISLADO, RETIRE LAS TAPAS Y RETIRE POLVO Y
LA SUCIEDAD CON AIRE COMPRIMIDO DE BAJA PRESION.
-INSPECCIONE LOS BOBINADOS PARA VER SI HAY DAÑOS Y SEÑALES DE.............EL SUCIO PEGADO AL DEVANADO NO
PERMITE DIFERENCIAR SUCIO A RECALENTAMIENTO.
RECALENTAMIENTO. REVISE LAS CONEXIONES EN LOS ANILLOS DE
DIODOS Y TODOS LOS CABLEADOS INTERNOS PARA VER SI HAY
PELADURAS Y DESGASTES.
-DESCONECTE LOS CABLES DE DIODO Y EL MEGGER DE TODOS LOS
BOBINADOS DE CAMPO Y DE EXCITADOR. REGISTRE LOS RESULTADOS.

SE DESCONECTARON TODAS LAS CONEXIONES ELECTRICAS, REALIZANDO LAS SIGUIENTES MEDICIONES ELÉCTRICAS:

VOLTAJE DE RUPTURA DE LOS DIODOS DE EXCITATRIZ


POSITIVOS NEGATIVOS
D1 0.34 VDC D4 0.33 VDC
D2 0.34 VDC D5 0.34 VDC
D3 0.34 VDC D6 0.34 VDC

CONTINUIDAD DEL MAGNETO PERMANENTE


PMG1-PMG2 = 0.5 OHMS
PMG3-PMG4 = 0.5 OHMS

DEVANADO PRINCIPAL
ROTOR: 2 OHMS / 231 M OHMS
ESTATOR: 0.2 OHMS / 876 M OHMS

DEVANADO SECUNDARIO
ROTOR: 0.2 OHMS / 266 M OHMS
ESTATOR: 13.1 OHMS / INFINITO M OHMS

TRABAJO REALIZADO POR:


ENDER CARDOZO
ELECTRONICO
5857

SPARES USED
DISCIPLINES USED:

ELEC 5 Hour(s)
Total Duration : 5.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 5.00 Hour(s)

Completed Controlled Filed


Date: 5/26/2010 7/9/2012 7/9/2012
By: ENDER JOSE CARDOZO JOHANNA CAROLINA QUEVEDO JOHANNA CAROLINA QUEVEDO

7/28/2022 112 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050000418 Maintenance Type: //


Title: ACELEC1ET - 1 YEAR / CHECK ROTATING Maintenance Class: //
RECTIFIER Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 5/14/2010
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

1 YEAR / CHECK ROTATING RECTIFIER

-CHECK ROTATING RECTIFIER

HISTORY

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

Completed Controlled Filed


Date: 5/14/2010
By:

7/28/2022 113 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050000927 Maintenance Type: //


Title: AIELECIQ - 1000 HRS / LUBRICATE/ INSPECT Maintenance Class: //
BEARINGS Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 4/30/2010
Hourmeter Registered:

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

1000 HRS / LUBRICATE/ INSPECT BEARINGS

-CHECK BEARINGS FOR NOISE, VIBRATION OR OVERHEATING


REPLACE IF NECESSARY
-CHECK WINDINGS AND RECORD MEGOHMETER READINGS
-INSPECT AND CLEAN WINDINGS

HISTORY

tutto nella norma

SPARES USED
DISCIPLINES USED:

ELEC 2 Hour(s)
ABSE 2 Hour(s)
Total Duration : 2.00 Hour(s) Total Down Time: 2.00 Hour(s) Total man-hour(s) : 4.00 Hour(s)

Completed Controlled Filed


Date: 4/30/2010
By:

7/28/2022 114 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050000869 Maintenance Type: //


Title: AIELECIQ - 1000 HRS / LUBRICATE/ INSPECT Maintenance Class: //
BEARINGS Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 10/10/2009
Hourmeter Registered: Reported Current Counter Type
Count Value
-16048.43 2617.57 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

1000 HRS / LUBRICATE/ INSPECT BEARINGS

-CHECK BEARINGS FOR NOISE, VIBRATION OR OVERHEATING


REPLACE IF NECESSARY
-CHECK WINDINGS AND RECORD MEGOHMETER READINGS
-INSPECT AND CLEAN WINDINGS

HISTORY

SPARES USED
DISCIPLINES USED:

ELEC 6 Hour(s)
Total Duration : 6.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 6.00 Hour(s)

Completed Controlled Filed


Date: 10/10/2009
By:

7/28/2022 115 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050000704 Maintenance Type: //


Title: AIELECIR - 2000 HRS / INSPECT Maintenance Class: //
GENERATOR/ALTERNATOR Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 10/5/2009
Hourmeter Registered: Reported Current Counter Type
Count Value
-16133.02 2532.98 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

2000 HRS / INSPECT GENERATOR/ALTERNATOR

-DRY GENERATOR
-INSPECT GENERATOR SET VIBRATION
-CHECK STATOR LEAD
-LUBRICATE BEARINGS

HISTORY

SPARES USED
DISCIPLINES USED:

ABSE 2 Hour(s)
ELEC 2 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 1.00 Hour(s) Total man-hour(s) : 4.00 Hour(s)

Completed Controlled Filed


Date: 10/5/2009
By:

7/28/2022 116 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050000705 Maintenance Type: //


Title: AIELECIQ - 1000 HRS / LUBRICATE/ INSPECT Maintenance Class: //
BEARINGS Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 8/22/2009
Hourmeter Registered: Reported Current Counter Type
Count Value
-16409.78 2256.22 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

1000 HRS / LUBRICATE/ INSPECT BEARINGS

-CHECK BEARINGS FOR NOISE, VIBRATION OR OVERHEATING


REPLACE IF NECESSARY
-CHECK WINDINGS AND RECORD MEGOHMETER READINGS
-INSPECT AND CLEAN WINDINGS

HISTORY

SPARES USED
DISCIPLINES USED:

ABSE 6 Hour(s)
ELEC 6 Hour(s)
Total Duration : 6.00 Hour(s) Total Down Time: 6.00 Hour(s) Total man-hour(s) : 12.00 Hour(s)

Completed Controlled Filed


Date: 8/22/2009
By:

7/28/2022 117 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050000666 Maintenance Type: //


Title: AIELECIR - 2000 HRS / INSPECT Maintenance Class: //
GENERATOR/ALTERNATOR Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 7/15/2009
Hourmeter Registered: Reported Current Counter Type
Count Value
-16628.00 2038.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

2000 HRS / INSPECT GENERATOR/ALTERNATOR

-DRY GENERATOR
-INSPECT GENERATOR SET VIBRATION
-CHECK STATOR LEAD
-LUBRICATE BEARINGS

HISTORY

-INSPECTED GENERATOR SET VIBRATION


-CHECKED STATOR LEAD
-LUBRICATED BEARINGS

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

7/28/2022 118 / 121


AMOS REPORT
MAINTENANCE DONE
Completed Controlled Filed
Date: 7/15/2009
By:

7/28/2022 119 / 121


AMOS REPORT
MAINTENANCE DONE
WORK ORDER INFORMATION WORK ORDER DETAILS

WO Number: 4050000667 Maintenance Type: //


Title: AIELECIQ - 1000 HRS / LUBRICATE/ INSPECT Maintenance Class: //
BEARINGS Maintenance Cause: //
Frequency: // Maintenance Criteria: //
WO Origin: Periodic
Status: Filed
Fecha de Finalización: 7/15/2009
Hourmeter Registered: Reported Current Counter Type
Count Value
-16628.00 2038.00 Hours

ActionTaken: // Cause: // Effect: //

COMPONENT INFORMATION FUNCTION INFORMATION

Asset Number: 609999//609999 Installation: Rig 5857 - Heavy Land


Component Number: 1000093090 Department: FRS Main Department
Component Description: SINCR.ALTERNATOR 1050KW 600V Function Description: DD/GG 01 ALTERNATOR
60HZ 1200RP
Maker: C0867-KATO
Model: 6P6-2650 AA27675007 Criticality: 3
Serial Number: 20677-01
Machine Code: C0867A38K120A0

JOB DESCRIPTION

1000 HRS / LUBRICATE/ INSPECT BEARINGS

-CHECK BEARINGS FOR NOISE, VIBRATION OR OVERHEATING


REPLACE IF NECESSARY
-CHECK WINDINGS AND RECORD MEGOHMETER READINGS
-INSPECT AND CLEAN WINDINGS

HISTORY

-INSPECTED GENERATOR SET VIBRATION


-CHECKED STATOR LEAD
-LUBRICATED BEARINGS

SPARES USED
DISCIPLINES USED:

ELEC 1 Hour(s)
Total Duration : 1.00 Hour(s) Total Down Time: 0 Hour(s) Total man-hour(s) : 1.00 Hour(s)

7/28/2022 120 / 121


AMOS REPORT
MAINTENANCE DONE
Completed Controlled Filed
Date: 7/15/2009
By:

7/28/2022 121 / 121