REGULACION DE VOLTAJE Y SU MEJORAMIENTO

SE DEFINE COMO LA CAIDA PORCENTUAL DE VOLTAJE EN LA LINEA

SE VERÁ OTRAS FORMAS DE CALCULAR LA REGULACIÓN DE VOLTAJE Y COMO MEJORARLA

SEA EL SIGUIENTE CIRCUITO POR FASE SIMPLIFICADO DE UNA LINEA

V1 : VOLTAJE DE FASE DEL TRANSMISOR

V2 : VOLTAJE DE FASE DEL RECEPTOR ( SE CONSIDERA COMO REFERENCIA)

Z : IMPEDANCIA LINEA , Z=R+JX

I: CORRIENTE TOTAL DEL CONSUMO

CIRCUITO EQUIVALENTE POR FASE

SE CUMPLE QUE V1= ZI + V2 (FASORIALMENTE)

V1= (R+JX)(I*COSØ – JI*SENØ) + V2 LUEGO

V1= RICOSØ – JRISENØ + JXICOSØ + XISENØ +V2


V1 = RICOSØ +XISENØ + J(XICOSØ – RISENØ)+V2

DIAGRAMA FASORIAL CON CARGA INDUCTIVA

SEAN
ΔVX:CAIDA DE VOLTAJE EN EL EJE X
ΔVY:CAIDA DE VOLTAJE EN EL EJE Y
ΔV:CAIDA DE VOLTAJE TOTAL

ΔVX= RICOSØ + XISENØ


ΔVY = XICOSØ – RISENØ
ΔV =√ ΔVX 2 + ΔVY 2

ΔVY ES MENOR A ΔVX


ΔV ΔVX

ΔV =ΔVX + JΔVY =V 1−V 2


CONSIDERANDO SOLO ΔVX

ΔVX =RIcosØ + XIsenØ ( MULTIPLICANDO Y DIVIDIENDO POR V 2)


R∗V 2∗IcosØ + X∗V 2∗IsenØ
ΔVX =
V2

R∗P+ X∗Q
ΔVX =
V2
P : POTENCIA ACTIVA 3 Ø
Q : POTENCIA REACTIVA 3 Ø
V 2:VOLTAJE CARGA ENTRE LINEAS

CONSIDERANDO LA OTRA COMPONENTE


ΔVY =XIcosØ −RIsenØ ( MULTIPLICANDO Y DIVIDIENDO POR V 2)

X∗V 2∗IcosØ−R∗V 2∗IsenØ


ΔVY =
V2

XP−RQ
ΔVY =
V2

P : POTENCIA ACTIVA 3 Ø
Q : POTENCIA REACTIVA 3 Ø
V 2:VOLTAJE CARGA ENTRE LINEAS

GENERALMENTE ΔVY SE DESPRECIA PUES SOLO CONTRIBUYE AL DESFASE


ENTRE V1 Y V2

CALCULO DE V2
R∗P+ X∗Q
| ΔV |=|V 1|-|V 2|=
V2

MULTIPLICANDO CRUZADO
2
V 1V 2−V 2 =RP+ XQ
ORDENANDO TERMINOS
2
V 2 −V 1V 2+ ( RP+ XQ )=0

ECUACION CUADRATICA CUYAS SOLUCIONES SON

V 1+ √V 1 −4( RP+ XQ )
2
V 2= (PRIMERA SOLUCION )
2

V 1−√ V 12−4 ( RP+ XQ )


V 2= (SEGUNDA SOLUCION )
2

P : POTENCIA ACTIVA 3 Ø
Q : POTENCIA REACTIVA 3 Ø
V 2:VOLTAJE CARGA ENTRE LINEAS
R : RESISTENCIA LINEA Ω
X : REACTANCIA LINEA Ω

SE DEBE ELEGIR UNA SOLUCION PARA V2 , SI SE ANALIZA LA SEGUNDA


SOLUCION PARA EL CASO QUE NO EXISTE ALIMENTADOR , ES DECIR R=0 ,
X=0 SE DEBERIA TENER V1=V2 , VEAMOS

V 1−√ V 1 V 1−V 1
2
V 2= = =0
2 2
LO QUE NO ES LOGICO

PERO SI OCURRE PARA LA PRIMERA SOLUCION

V 1+ √V 1 V 1+V 1 2 V 1
2
V 2= = = =V 1
2 2 2

CALCULO DE V1
DEL DIAGRAMA FASORIAL SE TIENE

V 12=(V 2+ ΔVX )2 + ΔVY 2


REEMPLAZANDO LAS CAIDAS DE VOLTAJE

V 12=(V 2+ RIcosØ + XIsenØ )2 +( XIcosØ−RIsenØ )2

2
2 V2
V 1 =(V 2+ ∗(RIcosØ + XIsenØ )) + ¿
V2

2
2 R∗V 2∗IcosØ X∗V 2∗IsenØ
V 1 =(V 2+ + ) +¿
V2 V2

2
2 R∗P X∗Q
V 1 =(V 2+ + ) +¿
V2 V2

2 R∗P+ X∗Q 2
V 1 =(V 2+ ) +¿
V2


2
R∗P+ X∗Q
V 1= (V 2+ ) +¿ ¿
V2

V 1=√ (V 2+ ΔVX ) +¿ ¿
2

LA FORMULA ANTERIOR CONSIDERA LAS DOS CAIDAS DE VOLTAJE

CALCULO DE δ
DEL DIAGRAMA FASORIAL SE TIENE

ΔVY
senδ=
V1

ΔVX +V 2
cosδ=
V1
ΔVY
senδ V1 ΔVY
tgδ= = =
cosδ ΔVX +V 2 ΔVX +V 2
V1
REEMPLAZANDO ΔVX , ΔVY

XP−RQ XP−RQ
V2 V2
tgδ= =
RP+ XQ 2
+V 2 RP+ XQ +V 2
V2 V2

SIMPLIFICANDO POR V2

XP−RQ
tgδ= 2
RP+ XQ +V 2

−1 XP−RQ
δ=tg ( )
RP+ XQ+ V 22

P : POTENCIA ACTIVA 3 Ø
Q : POTENCIA REACTIVA 3 Ø
V 2:VOLTAJE CARGA ENTRE LINEAS
R : RESISTENCIA LINEA Ω
X : REACTANCIA LINEA Ω

CALCULO DE LA CORRIENTE EN LA LINEA

V 1< δ−V 2<0


I=

V 1 ,V 2: VOLTAJES DE FASE
EJEMPLO

UNA LINEA 3Ø , 30 KV , 15 KM , R=0.17 ( kmΩ ) , X=0.36( kmΩ ).¿QUE POTENCIAS


APARENTES Y ACTIVAS PODRAN TRANSPORTARSE CON FP=0.80(i) y FP=1 ,
CONSIDERANDO CONSIDERANDO UNA REG(%)=5%

SOL

FP=0.8 (i)

R=0.17 ( kmΩ )∗15 km=2.55 Ω , X=0.36 ( kmΩ )∗15 km=5.4 Ω


ΔV
REG ( p .u )=
V2
ΔV =0.05∗30 KV =1.5 KV
ΔVX =RIcosØ + XIsenØ ( MULTIPLICANDO Y DIVIDIENDO POR V 1)
SE MULTIPLICA POR V 1 YA QUE SE PREGUNTA POR LA POTENCIA DEL
TRANSMISOR
R∗V 1∗IcosØ + X∗V 1∗IsenØ
ΔVX ≈ ΔV =
V1
R∗PG + X∗QG
ΔV =
V1
PG : POTENCIA ACTIVA 3 Ø GENERADA

QG : POTENCIA REACTIVA 3 Ø GENERADA

V 1:VOLTAJE TRANSMISOR ENTRE LINEAS

V 1∗ΔV =R∗PG + X∗QG

EXPRESANDO LA POTENCIA REACTIVA EN FUNCION DE LA ACTIVA Y DEL FP


QG
tanØ =
PG

QG =PG∗tanØ

REEMPLAZANDO
V 1∗ΔV =R∗PG + X∗PG∗tanØ

30000∗1500=2.55∗PG +5.4∗PG∗tan 36.86


6
45∗10 =2.55∗PG + 4.12∗P G

PG =6746.62 KW ( TRIFASICOS )

6746.62 KW
SG = =8433.28 KVA( TRIFASICOS)
0.8

FP=1
30000∗1500=2.55∗PG +5.4∗PG∗tan 0
6
45∗10 =2.55∗PG

PG =17647.06 KW (TRIFASICOS)

6746.62 KW
SG = =17647.06 KVA(TRIFASICOS)
1

EJEMPLO

LA CARGA CONECTADA EN DELTA TIENE LAS SIGUIENTES CARACTERISTICAS:

S3 Ø =7.9 KVA , FP=0.707 ( c )


CALCULAR LA REG(%)
P3 Ø =7.9∗0.707=5.58 KW

Q3 Ø =√7.9 −5.58 =5.59 KVAR CAPACITIVOS


2 2


2
R∗P+ X∗Q
V 1= (V 2+ ) +¿ ¿
V2


2
3∗5.58 K+ 4∗(−5.59 K)
V 1= (380+ ) +¿ ¿
380

379.51−380
REG ( % )= ∗100=−0.13 %
380

CALCULAR Z

V 2fase 3802
Z fase = = =54.84 Ω
Sfase 7900
3
FASORIALMENTE
Z fase =54.84← 45Ω

LA CARGA CONECTADA EN DELTA TIENE LAS SIGUIENTES CARACTERISTICAS:

S3 Ø =7.9 KVA , FP=0.707 ( i )

CALCULAR LA REG(%)
P3 Ø =7.9∗0.707=5.58 KW

Q3 Ø =√7.9 2−5.582=5.59 KVAR INDUCTIVOS


2
R∗P+ X∗Q
V 1= (V 2+ ) +¿ ¿
V2


2
3∗5.58 K+ 4∗5.59 K
V 1= (380+ ) +¿ ¿
380
483.10−380
REG ( % )= ∗100=27.13%
380

CALCULAR Z
2
V fase 3802
Z fase = = =54.84 Ω
Sfase 7900
3
FASORIALMENTE
Z fase=54.84< 45 Ω

EJEMPLO

CALCULO DE V2

3300+ √ 33002−4 ( 0.66∗1∗106 + 0.66∗0.75∗106 )


V 2= =2.902 KVLL
2
CALCULO DE LA REGULACION

V 1−V 2 3.3 KV −2.902 KV


REG ( % )= ∗100= ∗100=13.71( %)
V2 2.902 KV

CALCULO DE ΔV

6 6
R∗P+ X∗Q 0.66∗1∗10 +0.66∗0.75∗10
ΔVX = = =398 VLL
V2 2902

6 6
XP−RQ 0.66∗1∗10 −0.66∗0.75∗10
ΔVY = = =56.86 VLL
V2 2902

ΔV =√ ΔVX 2 + ΔVY 2=√ 3982 +56.862=402.40VLL

CALCULO DE δ

( ) ( )
6 6
−1 XP−RQ −1 0.66∗1∗10 −0.66∗0.75∗10
δ=tg 2
=tg 6 6 2
=0.98
RP+ XQ +V 2 0.66∗1∗10 +0.66∗0.75∗10 +2902

CALCULO DE I

3300<0.98 2902<0

I=
V 1< δ−V 2<0
= √ 3 √3 =249.25←36.92 A
Ż 0.66+ J 0.66

−1 Q −1 0.75 MVAR
Ø=tg =tg =36.86 (ANGULO DEL FPCONSUMO)
P 1 MW
CALCULO DEL RENDIMIENTO

P2 3 Ø
η ( % )= ∗100
P1 3 Ø

P1 3 Ø=PP 3 Ø+ P 2 3 Ø
2 2
PP 3 Ø=3 R I =3∗0.66∗249.25 =123 KW
P1 3 Ø=123 KW +1 MW =1.12 MW

1 MW
η ( % )= ∗100=89.29(%)
1.12 MW

EJEMPLO

CALCULAR REGULACION
FORMULA EXACTA


V 1= (V 2+
R∗P+ X∗Q 2
V2
) +¿ ¿

DESPRECIANDO ΔVY

R∗P+ X∗Q 12.16∗30 MW +42.537∗14.52 MVAR


V 1=V 2+ =154000+ =160.38 KVLL
V2 154000
V 1−V 2 160.38 KV −154 KV
REG ( % )= ∗100= ∗100=4.14 (% )
V2 154 KV

CORRIENTE EN LA LINEA

SE PUEDE CALCULAR DE DOS FORMAS


PRIMERO
30 MW
I= =124.97←25.84 A
√3∗154 KV∗0.9

SEGUNDO METODO

δ=tg−1
( XP−RQ
RP+ XQ +V 2 ) (
2
=tg−1 42.537∗30∗106 −12.16∗14.52∗106
6 6
12.16∗30∗10 + 42.537∗14.52∗10 +154000 )
2
=2.55

160.38 KV 154 KV
<2.55− <0
I=
V 1< δ−V 2<0
=
√ 3 √ 3
=124.73←25.9 A
Ż 12.16+J 42.537

POTENCIA ACTIVA Y REACTIVA DEL TRANSMISOR


SE PUEDE CALCULAR DE DOS FORMAS
PRIMERO

P1 3 Ø=PP 3 Ø+ P 2 3 Ø

PP 3 Ø=3 R I 2=3∗12.16∗124.732 =0.57 MW


P1 3 Ø=0.57 MW +30 MW =30.57 MW

Q1 3 Ø=QP 3 Ø+Q2 3 Ø
2 2
QP 3 Ø=3 X I =3∗42.537∗124.73 =1.98 MVAR
Q1 3 Ø=1.98 MVAR +14.52 MVAR=16.50 MVAR

SEGUNDO METODO

160.38<2.55 KV
S 1=V 1∗I 1¿ = ∗124.73< 25.9=11.55<28.45 MVA
√3

P1 1 Ø=10.16 MW

P1 3 Ø=30.48 MW

Q1 1 Ø=5.50 MVAR

Q1 3 Ø=16.50 MVAR

FACTOR POTENCIA TRANSMISOR


P1 30.48
FP= = =0.88(i)
√ P 1 +Q 1 √ 30.482+ 16.502
2 2

30 MW
η ( % )= ∗100=98.42(%)
30.48 MW

DE ACUERDO AL CTO POR FASE

V1=RICOSØ +XISENØ +V2

V 1−V 2
SE SABE QUE REG ( % )= ∗100 , (METODO DE LOS VOLTAJES)
V2
O TAMBIEN

ΔV
REG ( % )= ∗100
V2

DONDE

V 1+ √V 1 −4( R∗P 3 Ø + X∗Q 3 Ø )


2
V 2=
2
V2:VOLTAJE ENTRE LINEAS

V1:VOLTAJE ENTRE LINEAS

EJEMPLO

UNA LINEA 3Ø , 15 KM , R=0.17(Ω/KM) , X=0.36(Ω/KM) , ALIMENTA UN CONSUMO EN 30 KVLL.

QUE POTENCIAS APARENTES Y ACTIVAS SE PODRAN TRANSPORTAR CON FP=0.80(I) Y FP=1 ,


CONSIDERANDO UNA REG(%)=5%.

SOL

SE CONSIDERARA PRIMERO DESPRECIANDO ΔVY

FP=0.80(I)


R=0.17( )∗15 KM=2.55(Ω)
KM

X =0.36( )∗15 KM =5.4(Ω)
KM

ΔV
REG ( p .u )=
V2
ΔV =V 2∗REG ( p . u )
30000
ΔV ΔVX= ∗0.05=866.03 V
√3

ΔVX= RICOSØ + XISENØ


−1
Ø=cos 0.8=36.86
sen 36.86=0.60
866.03 V =2.55∗I∗0.8+5.4∗I ∗0.6
I =164.02 A

S 3 Ø=3∗Vfase∗I

3∗30000
S 3 Ø= ∗164.02=8.52 MVA
√3

P 3 Ø =0.8∗8.52 MVA=6.82 MW

FP=1

ΔVX= RICOSØ + XISENØ


866.03 V =2.55∗I∗1+5.4∗I∗0
I =339.62 A
S 3 Ø=3∗Vfase∗I

3∗30000
S 3 Ø= ∗339.62=17.65 MVA
√3

P 3 Ø =1∗17.65 MVA=17.65 MW
CONSIDERANDO ΔVY

ΔVY = XICOSØ – RISENØ

FP=0.8(I)

ΔVY =5.4∗164.02∗0.8−2.55∗164.02∗0.6
ΔVY =457.56 V
LA CAIDA DE VOLTAJE TOTAL ES

ΔV =√ ΔVX 2 + ΔVY 2

ΔV =√ 866.03 +457.56 =979.47 V


2 2

ΔVX REPRESENTA EL 88.42 % DE LA CAIDA TOTAL ΔV


CONSIDERANDO LA CAIDA DE VOLTAJE TOTAL SE CALCULA LA CORRIENTE DE LA EXPRESION

ΔV =√( R∗I∗cosØ+ X∗I ∗senØ )2+(X∗I∗cosØ −R∗I ∗senØ )2


ELEVANDO AL CUADRADO
2 2 2
(ΔV ) =(R∗I∗cosØ + X∗I∗senØ ) +(X∗I∗cosØ −R∗I∗senØ )
REEMPLAZANDO

(979.47)2=(2.55∗I ∗0.8+5.4∗I∗0.6)2 +(5.4∗I ∗0.8−2.55∗I∗0.6)2


DESARROLLANDO

(979.47)2=(5.28∗I )2+(2.79∗I )2

( 979.47 )2 =I 2 (5.282 +2.792 )


I =164.10 A
SE DEMUESTRA QUE LA CORRIENTE ES PRACTICAMENTE LA MISMA CONSIDERANDO LAS DOS
CAIDAS DE VOLTAJE , LUEGO EN ESTE PROBLEMA SE PUEDE DESPRECIAR ΔVY

EJEMPLO

UNA LINEA 36 KM R=0.2 ( KMΩ ) , X=0.4( KMΩ ) V1=132 KV ALIMENTANDO UN CONSUMO


DE 48 MVA , FP=0.95(I) . CALCULAR V2

SOL
R=0.2 ( KMΩ )∗36 KM=7.2 Ω
X =0.4 (
KM )

∗36 KM =14.4 Ω

P=48 MVA∗0.95=45.6 MW

Q= √ 48 −45.6 =15 MVAR


2 2

V 1+ √V 12−4( R∗P 3 Ø + X∗Q 3 Ø )


V 2=
2

132 KV + √ 132 KV −4(7.2∗45.6 MW + 14.4∗15 MVAR )


2
V 2=
2

V 2=127.74 KV

V 1−V 2
REG ( % )= ∗100
V2

132−127.74
REG ( % )= ∗100=3.33(%)
127.74

EJEMPLO

UNA LINEA 3Ø , 6 KM , R=0.198(Ω/KM) , X=0.30(Ω/KM) , ALIMENTA UN CONSUMO EN 23


KVLL , 900 KW , FP=0.80(I)

CALCULAR
REG(%)

Q=P∗tgØ =900 KW∗tg ( cos−1 0.80 ) =675 KVAR

R=0.198 ( kmΩ )∗6 km=1.18 Ω


X =0.30 ( )∗6 km=1.8 Ω

km

R∗P+ X∗Q 1.18∗900 KW +1.8∗675 KVAR


V 1=V 2+ =23000+ =23.10 KVLL
V2 23000

23.10−23
REG ( % )= ∗100=0.43(%)
23

EJEMPLO

UNA LINEA 3Ø , 10 KM , R=0.2(Ω/KM) , X=0.30(Ω/KM) , ALIMENTA UN CONSUMO EN 23 KVLL ,


9 MW , FP=0.80(I)

CALCULAR V1 EN FORMA EXACTA Y APROXIMADA CON SUS RESPECTIVAS REGULACIONES

SOL

Z=( 0.2+J 0.3 ) ( kmΩ )∗10 km=2+ j 3(Ω)


Q=900 KW ∗tan ( 36.86 )=6.75 MVAR

EN FORMA EXACTA


V 1= (23000+
2∗9∗106 +3∗6.75∗106 2
23000
) +¿ ¿
V 1=24.69 KV
24.69−23
REG ( % )= ∗100=7.35 %
23

EN FORMA APROXIMADA


V 1= (23000+
2∗9∗106 +3∗6.75∗106 2
23000
)

V 1=24.66 KV
24.66−23
REG ( % )= ∗100=7. 22%
23

EJEMPLO

CALCULAR REG(%)

EN FORMA APROXIMADA


V 1= (20 000+
3.82∗3∗106 +5.237∗1.8∗106 2
20 000
)
V 1=21.044 KV
21.044−20
REG ( % )= ∗100=5 . 22 %
20

CALCULAR LA CORRIENTE DE LA LINEA

−1 XP−RQ
δ=tg ( 2
)
RP+ XQ+ V 2

δ=tg−1
( 5.237∗3∗106 −3.82∗1.8∗106
3.82∗3∗106 +5.237∗1.8∗106 +200002 )
=1.2

21044 <1.2 20000< 0



I= √ 3 √ 3 =100.58←30.93 A
3.82+ J 5.237

OTRA FORMA DE CALCULARLA

P
I=
√3∗V ∗FP

EL FACTOR DE POTENCIA DEL CONSUMO ES

3
FP= =0.86(i)
√ 3 + 1.82
2

3 MW
I= =100.70←30.68 A
√3∗20 KV ∗0.86

CALCULAR LAS POTENCIAS DEL TRANSMISOR

P P 3 Ø =3∗3.82∗100.582 =115.93 KW

Q P 3 Ø =3∗5.237∗100.582=158 .93 KW

P 1=3 MW +115.93 KW =3.115 MW


Q 1=1.8 MVAR+ 158.93 KW =1.95 MW

S 1=√ 3.1152 +1.952=3.67 MVA


RECORDEMOS

V1=RICOSØ +XISENØ +V2

REEMPLAZANDO V1 SE TIENE

V1

RICOSØ+ XISENØ +V 2−V 2


REG ( % )= ∗100
V2
RICOSØ+ XISENØ
REG ( % )= ∗100(METODO DE LAS CORRIENTES)
V2
DONDE

Ø: ANGULO DEL FP DEL CONSUMO

V2: VOLTAJE DE FASE DEL RECEPTOR

V2
SI LA EXPRESION ANTERIOR SE MULTIPLICA POR , SE TIENE
V2

REG ( % )=
( R∗V 2∗I∗COSØ + X∗V 2∗I∗SENØ
V2
2
∗100
)
REG ( % )=¿

REG ( % )=¿ (METODO DE LAS POTENCIAS)

V 1+ √V 1 −4( R∗P 3 Ø + X∗Q 3 Ø )


2
V 2=
2
V2:VOLTAJE ENTRE LINEAS

V1:VOLTAJE ENTRE LINEAS

EJEMPLO
SE TIENE UN VOLTAJE EN EL TRANSMISOR DE 380 V , IMPEDANCIA LINEA Z=0.11+J0.23Ω , SE
ALIMENTA UN CONSUMO 3Ø DE 18 KW , FP=0.84(I) . CALCULAR REG(%) USANDO LOS 3
METODOS

METODO DE LOS VOLTAJES

V 1+ √V 1 −4( R∗P 3 Ø + X∗Q 3 Ø )


2
V 2=
2
Q=P*tg(cos-1FP)=18 *tg(cos-10.84)=11.62 KVAR

380+ √ 380 −4(0.11∗18000+0.23∗11620)


2
V 2= =367.33 V
2

380−367.33
REG ( % )= ∗100=3.44( %)
367.33
METODO DE LAS POTENCIAS

REG ( % )=
( 0.11∗18000+0.23∗11620
2
367.33 )∗100=3.44 (%)
METODO DE LAS CORRIENTES

18000
I= =33.68 A
√3∗367.33∗0.84
EN TERMINOS FASORIALES

I =33.68←32.85 A

−1
Ø=cos 0.84=32.85

0.11∗33.68∗cos 32.85+0.23∗33.68∗SEN 32.85


REG ( % )= ∗100=3.44(% )
367.33
√3

EJEMPLO
SE TIENE UN VOLTAJE EN EL TRANSMISOR DE 380 V , IMPEDANCIA LINEA Z=0.13+J0.26Ω , SE
ALIMENTA UN CONSUMO 3Ø DE 25 KVA , FP=0.79(C) . CALCULAR REG(%) USANDO LOS 3
METODOS

METODO DE LOS VOLTAJES

P=FP∗S=0.79∗25=19.75 KW

Q= √25 −19.75 =15.32 KVAR CAPACITIVOS=−15.32 KVAR


2 2

380+ √ 3802−4(0.13∗19750−0.26∗15320)
V 2= =383.68 V
2

380−383.68
REG ( % )= ∗100=−0.95(%)
383.68

METODO DE LAS POTENCIAS

REG ( % )=
( 0.13∗19750+0.26∗−15320
2
383.68 )∗100=−0.96(%)
METODO DE LAS CORRIENTES

19750
I= =37.61 A
√3∗383.68∗0.79

EN TERMINOS FASORIALES

I =37.61<37.81 A

−1
Ø=cos 0.79=−37.81

0.13∗37.61∗cos (−37.81 ) +0.26∗37.61∗SEN (−37.81)


REG ( % )= ∗100=−0.95(%)
383.68
√3
TAREA(SEC 2)

SE TIENE UN VOLTAJE EN EL TRANSMISOR DE 380 V , IMPEDANCIA LINEA Z=0.35<70Ω , SE


ALIMENTA UN CONSUMO 3Ø DE 30 KW , FP=1 . CALCULAR REG(%) USANDO LOS 3 METODOS

SOL

METODO DE LOS VOLTAJES

Q=0 , YA QUE FP=1

Z=0.35<70 Ω = 0.12+J0.33 Ω

380+ √ 380 −4(0.12∗30000+0.33∗0)


2
V 2= =370.27 V
2

380−370.27
REG ( % )= ∗100=2.63( %)
370.27

METODO DE LAS POTENCIAS

REG ( % )=
( 0.12∗30000+0.33∗0
370.27 2 )∗100=2.62( %)

METODO DE LAS CORRIENTES

30000
I= =46.77 A
√3∗370.27∗1

−1
Ø=cos 1=0

0.12∗46.77∗cos ( 0 ) +0.33∗46.77∗SEN (0)


REG ( % )= ∗100=2.62(%)
370.27
√3
EJEMPLO

SE TIENE UN VOLTAJE EN EL TRANSMISOR DE 380 V , IMPEDANCIA LINEA Z=0.10+J0.17 Ω ,


ALIMENTA DOS CONSUMO 3Ø CONECTADOS EN PARALELO .

C1: 15 KW , FP=0.89(I)

C2: 35 KW , FP=0.78(I)

CALCULAR REG(%) USANDO LOS TRES METODOS

SOL

C1: Q1= P*tg(cos-1FP)=15 *tg(cos-10.89)=7.68 KVAR

C2: Q2=P*tg(cos-1FP)=35 *tg(cos-10.78)=28.07 KVAR

PT=15K+35K=50K

QT=7.68K+28.07K=35.75KVAR

ST =√ 50 2+35.75 2=61.46 KVA


METODO DE LOS VOLTAJES

380+ √ 380 −4(0.10∗50000+0.17∗35750)


2
V 2= =348.18 V
2

380−348.18
REG ( % )= ∗100=9.14 (%)
348.18

METODO DE LAS POTENCIAS

REG ( % )=
( 0.10∗50000+0.17∗35750
348.18
2 )
∗100=9.14(%)

METODO DE LAS CORRIENTES


50
FPTOTAL= =0.81(I )
61.46

50000
I= =102.36 A
√3∗348.18∗0.81

−1
Ø=cos 0.81=35.90

0.10∗102.36∗cos ( 35.90 )+ 0.17∗102.36∗SEN (35.90)


REG ( % )= ∗100=9.20 (%)
348.18
√3

TAREA

SE TIENE UN VOLTAJE EN EL TRANSMISOR DE 380 V , IMPEDANCIA LINEA Z=0.18<60 Ω ,


ALIMENTA DOS CONSUMO 3Ø CONECTADOS EN PARALELO .

C1: 50 KVA , FP=0.91(I)

C2: 10 KW , FP=0.81(C)

C3: 6 KW , FP=1

CALCULAR REG(%) USANDO LOS TRES METODOS

SOL

Z=0.18<60=0.09+ J 0.16 Ω
P 1=50∗0.91=45.5 KW

Q 1=√ 502−45.52=20.73 KVAR

P 2=10 KW
Q2=P*tg(cos-1FP)=10 *tg(cos-10.81)= -7.23 KVAR
P3=6 KW

Q3=0

PT= 45.5K+10K+6K= 61.5 KW

QT=20.73K-7.23K+0=13.5 KVAR

METODO DE LOS VOLTAJES

380+ √ 3802−4(0.09∗61500+0.16∗13500)
V 2= =358.54 V
2

380−358.54
REG ( % )= ∗100=5.98( %)
358.54
METODO DE LAS POTENCIAS

REG ( % )=
( 0.09∗61500+0.16∗13500
2
358.54 )∗100=5.98(%)

METODO DE LAS CORRIENTES

61500
FPTOTAL= =0.97(i)
√ 615002+ 135002

61500
I= =102.09←14.07 A
√3∗358.54∗0.97

Ø=cos−1 0.97=14.07

0.09∗102.09∗cos ( 14.07 )+ 0.16∗102.09∗SEN ( 14.07)


REG ( % )= ∗100=6.22(% )
358.54
√3
CALCULO DE REACTIVOS PARA TENER UNA REGULACIÓN DESEADA

EMPLEANDO LA ECUACION DE LA REGULACION METODO DE LAS POTENCIAS

REG ( P .U )=
( R∗P+V X∗QT
2
2 )
DESPEJANDO QT

V 22∗REG ( P .U . )−R∗P
QT =
X

QT : POTENCIA REACTIVA QUE FLUYE EN LA LINEA .


SI QT>0 , ESTA ENTRA A LA BARRA DE CARGA
QC: POTENCIA REACTIVA CAPACITIVA DE LOS CONDENSADORES

QL: POTENCIA REACTIVA INDUCTIVA DEL CONSUMO

QT+QC= QL , QC =QL-QT

SI QT<0 , ESTA SALE DE LA BARRA DE CARGA

QC = QT+QL

EJEMPLO

UNA LINEA CON VOLTAJE EN EL TRANSMISOR DE 380 VLL , Z=0.15+J0.25Ω , ALIMENTA UN


CONSUMO 3Ø , 30 KW , FP=0.89(I) . CALCULAR QUE CANTIDAD REACTIVOS SE DEBEN
INYECTAR EN LA BARRA PARA TENER UNA REG(%)=5%

SOL

PRIMERO SE DEBE CALCULAR V2 PARA COMPROBAR QUE LA REG% ACTUAL SEA > 5%

Q=30000 TG ( cos−1 0.89 )=15.37 KVAR

380+ √ 3802−4(0.15∗30000+0.25∗15370)
V 2= =356.60V
2
380−356.60
REG ( % )= ∗100=6.56 ( % ) >5 %
356.60

CALCULO DE V2 PARA OBTENER 5%

380−V 2
0.05=
V2
0.05∗V 2=380−V 2
0.05∗V 2+ V 2=380
V 2 ( 0.05+ 1 )=380
380
V 2=
0.05+1
V 2=361.90 V
CALCULO DE QT

361.92∗0.05−0.15∗30000
QT = =8.194 KVAR> 0 ENTRA A LA BARRA
0.25

QC=QL−QT =15.37 K−8.194 K =7.176 K

COMPROBACION

380+ √ 380 −4(0.15∗30000+0.25∗8194)


2
V 2= =361.90 V
2

380−361.90
REG ( % )= ∗100=5 %
361.90

EJEMPLO

UNA LINEA 3Ø DE 25 KM ALIMENTA UN CONSUMO 2500 KVA , FP=0.80(I) , 13.2 KV.LOS

PARAMETROS DE LA LINEA SON R=0.4 ( kmΩ ) , X =0.5 ( kmΩ ) .CALCULAR LA CANTIDAD DE


REACTIVO CAPACITIVOS PARA OBTENER UNA REG(%)=10%

SOL
P=2.5 MVA∗0.8=2 MW

Q= √2.52 −22=1.5 MVAR

ZL=( 0.4+ J 0.5 ) ( kmΩ )∗25 ( km )=10+ J 12.5(Ω)


V 22 REG ( P . U . )−RP
QT =
X

132002∗0.1−10∗2 MW
QT = =−206.08 KVAR
12.5

QC=1.5 MVAR +206.08 KVAR=1.706 MVAR

R∗P+ X∗QT
V 1=V 2+
V2

10∗2 MW +12.5∗−206.08 KVAR


V 1=13.2 KV + =14.52 KV
13.2 KV

14.52−13.2
REG ( % )= ∗100=10 %
13.2

EJEMPLO

UNA LINEA 3Ø , Z=1.7+J3.5(Ω) , VOLTAJE DE 23 KV EN EL TRANSMISOR ALIMENTA DOS


CONSUMOS EN PARALELO

C1: 3.5 MVA , FP=0.83(I)

C2 : 4 MW , FP=0.91(I)
CALCULAR LA CANTIDAD DE CONDENSADORES PARA TENER UNA REG(%)=2.8%

SOL

P 1=0.83∗3.5 MVA=2.91 MW

Q 1=2.91 MW∗tg ( cos−1 0.83 )=1.96 MVAR


P 2=4 MW

Q 2=4 MW∗tg ( cos−1 0.91 )=1.82 MVAR


PT =6.91 MW
QT =3.78 MVAR

23 KV + √23 KV 2−4 (1.7∗6.91 MW +3.5∗3.78 MVAR )


V 2= =21.86 KV
2

23−21.86
REG ( % )= ∗100=5.25 % >2.8 %
21.86

23−V 2
=0.028
V2

V 2=22.37 KV (VOLTAJE REQUERIDO PARA DICHA REGULACION )

2
V 2 REG ( P . U . )−RP
QT =
X

223702∗0.028−1.7∗6.91 MW
QT = =647.05 KVAR
3.5

QC +647.05 KVAR=3.78 MVAR

QC=3.13 MVAR
COMPROBACION

23 KV + √23 KV −4 (1.7∗6.91 MW +3.5∗647.05 KVAR)


2
V 2= =22.37 KV
2

23−22.37
REG ( % )= ∗100=2.8 %
22.37

EJEMPLO


UNA LINEA 3Ø , Z=0.29+ J 0.75( ) , LARGO=10 km , VOLTAJE TRANSMISOR 13.4 KV ,
km
ALIMENTA UN CONSUMO 1.2 MW , FP=0.85(I) . CALCULAR QC PARA OBTENER UNA
REGULACION DE 3.5(%)

SOL

Q=1.2 MW∗tg ( cos 0.85 ) =0.74 MVAR


−1

Z=0.29+ J 0.75 ( kmΩ )∗10 km=2.9+ j7.5(Ω)


13.4 KV + √13.4 KV −4( 2.9∗1.2 MW +7.5∗0.74 MVAR )
2
V 2= =12.68 KV
2

LA REGULACION ACTUAL ES

13.4−12.68
REG ( % )= ∗100=5.67 ( % ) >3.5(% )
12.68

13.4−V 2
=0.035
V2

V 2=12.94 KV (VOLTAJE REQUERIDO PARA DICHA REGULACION )


2
V 2 ∗REG ( P .U . )−R∗P
QT=
X

12.94 KV 2∗0.035−2.9∗1.2 MW
QT = =317.40 KVAR
7.5

QC +317.40 KVAR=0.74 MVAR

QC=422.60 KVAR

COMPROBACION

13.4 KV + √13.4 KV −4( 2.9∗1.2 MW +7.5∗317.40 KVAR)


2
V 2= =12.94 KV
2

13.4−12.94
REG ( % )= ∗100=3.55 %
12.94

CALCULO DE REACTIVOS PARA OBTENER UN VOLTAJE DESEADO EN LA BARRA DE CARGA

DE LA EXPRESION

V 1+ √V 1 −4( R∗P+ X∗QT )


2
V 2=
2

2∗V 2=V 1+ √ V 12−4 (R∗P+ X∗QT )

ELEVANDO AL CUADRADO
2 2
(2∗V 2−V 1) =V 1 −4( R∗P+ X∗QT )

2 2
−4 ( R∗P+ X∗QT ) =( 2∗V 2−V 1 ) −V 1

2 2
V 1 −( 2∗V 2−V 1 )
R∗P+ X∗QT =
4

2 2
V 1 −( 2∗V 2−V 1 )
X∗QT = −R∗P
4

FINALMENTE DESPEJANDO QT

2 2
V 1 −(2∗V 2−V 1) RP
QT= −
4X X

EJEMPLO
UNA LINEA CON VOLTAJE TRANSMISOR DE 13.6 KV , Z=0.75+J1.85(Ω) , SI EL
CONSUMO TIENE 14.5 MW , 5 MVAR , CALCULAR QC PARA OBTENER UN
VOLTAJE DE CARGA DE 13 KV
SOL
CALCULO DE V2

13600+ √ 136002−4 (0.75∗14.5∗10 6+ 1.85∗5∗106 )


V 2= =11.91 KV <13 KV
2

2 2
V 1 −(2∗V 2−V 1) RP
QT = −
4X X
2 2
13.6 KV −( 2∗13 KV −13.6) 0.75∗14.5 MW
QT = − =−1.66 MVAR
4∗1.85 1.85

QC=1.66 MVAR +5 MVAR=6.66 MVAR


VERIFICANDO

13600+ √ 13600 −4 (0.75∗14.5∗10 + 1.85∗−1.66∗10 )


2 6 6
V 2= =13 KV
2

EJEMPLO

UNA LINEA CON VOLTAJE TRANSMISOR DE 23 KV , Z=0.82+J1.94( ) , LARGO
km
LINEA DE 4km , SI EL CONSUMO TIENE 5.1 MW , 3.8 MVAR , CALCULAR QC
PARA OBTENER UN VOLTAJE DE CARGA DE 22.6 KV
RESP
QC=4.79 MVAR

SOL

Z=( 0.82+J 1.94 )∗4 km=3.28+ j 7.76(Ω)

23000+ √ 23000 −4(3.28∗5.1∗10 + 7.76∗3.8∗10 )


2 6 6
V 2= =20.77 KV <22.6 KV
2

2 2
23000 −(2∗22600−23000) 3.28∗5.1∗10 6
QT= − =−990.72 KVAR
4∗7.76 7.76

QC=3.8 MVAR +0.990 MVAR=4.79 MVAR


VERIFICANDO

23000+ √ 23000 −4(3.28∗5.1∗10 + 7.76∗( −990.72∗10 ) )


2 6 3
V 2= =22.6 KV
2

EJEMPLO

UNA LINEA CON VOLTAJE TRANSMISOR DE 23 KV , Z=2.7+J4.1Ω , ALIMENTA DOS CONSUMOS


EN PARALELO

C1 : 4 MW , FP=0.85(I)

C2: 3.2 MVA , FP=0.91(I)

CALCULAR QC PARA OBTENER UN V2=22.5 KV

SOL

C1 : Q1=4*tg(cos-10.85)=2.47 MVAR

C2:P2=3.2*0.91=2.91 MW

Q 2=√ 3.2 −2.91 =1.33 MVAR


2 2

PT=4 MW+2.91 MW=6.91 MW

QT=2.47 MVAR+1.33 MVAR=3.80MVAR

23000+ √ 23000 −4(2.7∗6.91∗10 +4.1∗( 3.80 ¿ 10 ) )


2 6 6
V 2= =21.40 KV <22.5 KV
2

2 2
23000 −(2∗22500−23000) 2.7∗6.91∗106
QT= − =−1.80 MVAR
4∗4.1 4.1

QC=3.8 MVAR +1.8 MVAR=5.6 MVAR

VERIFICANDO
V 2=

23000+ 23000 −4 ( 2.7∗6.91∗10 + 4.1∗(−1.80 ¿ 10 ) )
2 6 6
=22.5 KV
2

TAREA
UN ALIMENTADOR Z=0.18+J 0.33Ω , V1=380 V , ALIMENTA UN CONSUMO 39 KW ,
FP=0.86(I) .CALCULAR QC PARA OBTENER UN V2=374 V.
RESP
QT=-14.47 KVAR
QC=37.61 KVAR

SOL

Q=39 tg ( cos 0.86 )=23.14 KVAR


−1

380+ √ 380 −4(0.18∗39000+0.33∗23140)


2
V 2= =336.44 V <374 V
2

3802−(2∗374−380)2 0.18∗39000
QT = − =−14.47 KVAR
4∗0.33 0.33

QT =−14.47 KVAR

QC=14.47 KVAR+ 23.14 VAR=37.61 KVAR

VERIFICANDO

380+ √ 3802−4(0.18∗39000+0.33∗−14470)
V 2= =374 V
2

EJEMPLO

UNA LINEA CON VOLTAJE TRANSMISOR DE 23 KV , Z=1.8+J3.2Ω , ALIMENTA DOS CONSUMOS


EN PARALELO

C1 : 4 MVA , FP=0.89(I)

C2: 4.7 MW , FP=0.94(I)


CALCULAR QC PARA OBTENER UN V2=22.1 KV

SOL

P 1=0.89∗4 MVA=3.56 MW

Q 1=3.56 MW∗tg ( cos−1 0.89 ) =1.82 MVAR


P 2=4.7 MW

Q 2=4.7 MW ∗tg ( cos 0.94 ) =1.71 MVAR


−1

PT =8.26 MW
QT =3.53 MVAR

23 KV + √23 KV −4 (1.8∗8.26 MW +3.2∗3.53 MVAR )


2
V 2= =21.80 KV <22.1 KV
2

2 2
V 1 −(2∗V 2−V 1) RP
QT = −
4X X

2 2
23 KV −(2∗22.1 KV −23 KV ) 1.8∗8.26 MW
QT = −
4∗3.2 3.2

QT =1.57 MVAR

QC=3.53 MVAR−1.57 MVAR =1.96 KVAR

VERIFICANDO

23 KV + √ 23 KV −4 (1.8∗8.26 MW +3.2∗1.57 MVAR)


2
V 2= =22.10 KV
2
EJEMPLO
UNA LINEA 3Ø , V1=66 KV , R=4Ω , X=20Ω ALIMENTA UN CONSUMO DE 30 MW ,
FP=0.90(i)

CALCULAR LA CAIDA DE VOLTAJE

Q=30 MWtg ( cos 0.90 )=14.52 MVAR


−1

66 KV + √66 KV −4( 4∗30 MW +20∗14.52 MVAR )


2
V 2= =59.049 KV
2
ΔV =V 1−V 2=66 KV −59.049 KV =6.95 KV
6.95 KV
REG ( % )= ∗100=11.77 %
59.049

CALCULAR QC TAL QUE V2= 66 KV

2 2
V 1 −(2∗V 2−V 1) RP
QT = −
4X X

2 2
66 KV −(2∗66 KV −66 KV ) 4∗30 MW
QT = − =−6 MVAR
4∗20 20

QC=6 MVAR+14.52 MVAR=20.52 MVAR

VERIFICANDO
66 KV + √66 KV 2−4( 4∗30 MW +20∗−6 MVAR )
V 2= =66 KV
2

CACULAR QC PARA OBTENER UNA REG(%)=5%

2
V 2 REG ( P . U . )−RP
QT =
X

V 1−V 2
=0.05
V2

V 1−V 2=0.05 V 2
V 1=1.05 V 2
66 KV
V 2= =62.85 KV
1.05

62.85 KV 2∗0.05−4∗30 MW
QT = =3.87 MVAR
20

QC=14.52 MVAR−3.87 MVAR=10.65 MVAR

VERIFICANDO

66 KV + √66 KV −4( 4∗30 MW +20∗3.87 MVAR)


2
V 2= =62.85 KV
2

EJEMPLO
EL VOLTAJE EN BARRA 1 ES 13.6 KV
SE REQUIERE UN VOLTAJE EN BARRA 2 DE 12.8 KV Y EN BARRA 3 DE 12.5 KV.
CALCULAR LOS CONDENSADORES A CONECTAR EN DICHAS BARRAS

SOL
1) SE DEBE CALCULAR VB2 Y VB3 VERIFICANDO QUE LOS VALORES
CALCULADOS SON DIFERENTES A LOS REQUERIDOS

13.6 KV + √ 13.6 KV −4 (0.75∗15.6 MW +1.85∗8 MVAR)


2
VB 2= =11.24 KV <12.8 KV
2

11.24 KV + √11.24 KV 2−4(1.2∗4.2 MW + 3.6∗3.2 MVAR)


VB 3= =9.49 KV <12.5 KV
2

2) CALCULAR LA POTENCIA REACTIVA QUE DEBE CIRCULAR EN L1 PARA


TENER UN VOLTAJE EN BARRA 2 DE 12.8 KV

2 2
V 1 −(2∗V 2−V 1) RP
QT = −
4X X
2 2
13.6 KV −(2∗12.8 KV −13.6 KV ) 0.75∗15.6 MW
QL 1= − =−0.789 MVAR
4∗1.85 1.85

3) CALCULAR LA POTENCIA REACTIVA QUE DEBE CIRCULAR EN L2 PARA


TENER UN VOLTAJE EN BARRA 3 DE 12.5KV

2 2
12.8 KV −(2∗12.5 KV −12.8 KV ) 1.2∗4.2 MW
QL 2= − =−0.358 MVAR
4∗3.6 3.6

4) CALCULO DE LOS CONDENSADORES A CONECTAR EN B2 Y B3


EN BARRA 2
QC 2+0.358 MVAR=0.789 MVAR+ 4.8 MVAR
QC 2=5.23 MVAR

EN BARRA 3
QC 3=0.358 MVAR +3.2 MVAR
QC 3=3.558 MVAR

5) VERIFICAR LOS VOLTAJES

13.6 KV + √ 13.6 KV −4 (0.75∗15.6 MW +1.85∗−0.789 MVAR)


2
VB 2= =12.8 KV
2

12.8 KV + √ 12.8 KV 2 −4 (1.2∗4.2 MW +3.6∗−0.358 MVAR)


VB 3= =12.5 KV
2

13.6−12.8
REG L1 ( % )= ∗100=6.25 %
12.8

12.8−12.5
REG L2 ( % )= ∗100=2.40 %
12.5

EJEMPLO

EL VOLTAJE EN BARRA 1 ES 13.8 KV


SE REQUIERE UN VOLTAJE EN BARRA 2 DE 13.6 KV Y EN BARRA 3 DE 13.1 KV.
CALCULAR LOS CONDENSADORES A CONECTAR EN DICHAS BARRAS
SOL
1) SE DEBE CALCULAR VB2 Y VB3 VERIFICANDO QUE LOS VALORES
CALCULADOS SON DIFERENTES A LOS REQUERIDOS

13.8 KV + √ 13.8 KV −4 (0.92∗19 MW + 2.1∗9.9 MVAR )


2
VB 2= =9.96 KV <13.6 KV
2

9.96 KV + √ 9.96 KV 2−4 (1.7∗5 MW +3.6∗3.9 MVAR)


VB 3= =6.48 KV <13.1 KV
2

2) CALCULAR LA POTENCIA REACTIVA QUE DEBE CIRCULAR EN L1 PARA


TENER UN VOLTAJE EN BARRA 2 DE 13.6 KV

2 2
V 1 −(2∗V 2−V 1) RP
QT = −
4X X

13.8 KV 2 −(2∗13.6 KV −13.8 KV )2 0.92∗19 MW


QL 1= − =−7.03 MVAR
4∗2.1 2.1
3) CALCULAR LA POTENCIA REACTIVA QUE DEBE CIRCULAR EN L2 PARA
TENER UN VOLTAJE EN BARRA 3 DE 13.1KV

2 2
13.6 KV −(2∗13.1 KV −13.6 KV ) 1.7∗5 MW
QL 2= − =−0.541 MVAR
4∗3.6 3.6

4) CALCULO DE LOS CONDENSADORES A CONECTAR EN B2 Y B3

EN BARRA 2
QC 2+0.541 MVAR=7.03 MVAR +6 MVAR
QC 2=12.49 MVAR

EN BARRA 3
QC 3=0.541 MVAR +3.9 MVAR
QC 3=4.44 MVAR

5) VERIFICAR LOS VOLTAJES

13.8 KV + √ 13.8 KV −4 (0.92∗19 MW + 2.1∗−7.03 MVAR)


2
VB 2= =13.6 KV
2

13.6 KV + √ 13.6 KV −4 (1.7∗5 MW +3.6∗−0.541 MVAR)


2
VB 3= =13.1 KV
2

13.8−13.6
REG L1 ( % )= ∗100=1.47 %
13.6

13.6−13.1
REG L2 ( % )= ∗100=3.82%
13.1

EJEMPLO
SE DESEAN 13 KV EN CADA NODO DE CARGA(A,B,C) , CALCULAR LA CANTIDAD
DE CONDENSADORES A CONECTAR EN DICHOS NODOS PARA CUMPLIR ESA
CONDICION

SOL
SE DEBEN CALCULAR VB , VC , VD VERIFICANDO QUE LOS VALORES
CALCULADOS SON DIFERENTES A LOS REQUERIDOS

13.2 KV + √ 13.2 KV −4( 1.14∗5.7 MW +1.53∗4.38 MVAR)


2
VB= =12.11 KV <13 KV
2

12.11 KV + √ 12.11 KV 2−4 (1.1∗3.3 MW + 2.15∗2.27 MVAR )


VC = =11.36 KV <13 KV
2

11.36 KV + √ 11.36 KV −4 (1.5∗1.5 MW +2.6∗0.92 MVAR)


2
VD= =10.93 KV <13 KV
2

CALCULAR LA POTENCIA REACTIVA QUE DEBE CIRCULAR EN OB PARA TENER


VB=13 KV

V 12−(2∗V 2−V 1)2 RP


QT = −
4X X

2 2
13.2 KV −(2∗13 KV −13.2 KV ) 1.14∗5.7 MW
QOB= − =−2.54 MVAR
4∗1.53 1.53

CALCULAR LA POTENCIA REACTIVA QUE DEBE CIRCULAR EN BC PARA TENER


VC=13 KV
2 2
V 1 −(2∗V 2−V 1) RP
QT = −
4X X

2 2
13 KV −(2∗13 KV −13 KV ) 1.1∗3.3 MW
QBC= − =−1.68 MVAR
4∗2.15 2.15

CALCULAR LA POTENCIA REACTIVA QUE DEBE CIRCULAR EN CD PARA TENER


VD=13 KV

V 12−(2∗V 2−V 1)2 RP


QT = −
4X X

2 2
13 KV −( 2∗13 KV −13 KV ) 1.5∗1.5 MW
QCD= − =−0.86 MVAR
4∗2.6 2.6
CALCULO DE LOS CONDENSADORES A CONECTAR EN B , C Y D

EN NODO B
QC 1+ 1.68 MVAR =2.54 MVAR +2.11 MVAR
QC 1=2.97 MVAR

EN NODO C
QC 2+0.86 MVAR=1.68 MVAR+ 1.35 MVAR
QC 2=2.17 MVAR

EN NODO D
QC 3=0.86 MVAR +0.92 MVAR
QC 3=1.78 MVAR

VERIFICAR LOS VOLTAJES

13.2 KV + √ 13.2 KV −4(1.14∗5.7 MW +1.53∗−2.54 MVAR)


2
VB= =13 KV
2
13 KV + √ 13 KV 2−4(1.1∗3.3 MW +2.15∗−1.68 MVAR)
VC = =13 KV
2

13 KV + √13 KV −4 (1.5∗1.5 MW +2.6∗−0.86 MVAR)


2
VD= =13 KV
2