Está en la página 1de 1

TABLERO PRINCIPAL TD1

(TIPO EMPOTRADO, 3Ø, 220V, 60Hz, 10KA)


C1 TOMACORRIENTES

2x20A 2x25-30mA CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm

C2 TOMACORRIENTES

2x20A 2x25-30mA CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm


SUBTABLERO TS1
CABLE, 3-1x50mm2 + 1x16mm2, 0.6/1kV - PVC Ø 100mm C3 TOMACORRIENTES (TIPO EMPOTRADO, 2Ø, 220V, 60Hz, 10KA)
2x20A 2x25-30mA CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm
3X125A C1 ILUMINACION

C4 TOMACORRIENTES 2x20A 2x25-30mA CABLE, 2-1x2.5 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm

2x20A 2x25-30mA CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm


C2 ILUMINACION

C5 TOMACORRIENTES 2x20A 2x25-30mA CABLE, 2-1x2.5 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm

2x20A 2x25-30mA CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm


C3 ILUMINACION

C6 TOMACORRIENTES 2x20A 2x25-30mA CABLE, 2-1x2.5 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm


2X40A
2x20A 2x25-30mA CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm
C4 TOMACORRIENTES

C7 TOMACORRIENTES CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm


2x32A 2x32-30mA
2x20A 2x25-30mA CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm
C5 TOMACORRIENTES

C8 TOMACORRIENTES CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm


2x32A 2x32-30mA
2x20A 2x25-30mA CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm TOMACORRIENTES
C6

C9 TOMACORRIENTES 2x20A 2x25-30mA CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm

2x20A 2x25-30mA CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm C7


RESERVA
C10

BORNERA DE TIERRA
2x20A RESERVA C8

C11 RESERVA
2x20A RESERVA

C12 AIRE ACONDICIONADO DE 50,000 BTU/HR.


CABLE, 3-1x6mm2 + 1x4mm2, 0.6/1kV - PVC Ø 25mm
2x50A

C13 AIRE ACONDICIONADO DE 18,000 BTU/HR.

VEHICULAR
2x32A CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm

INGRESO
C14 AIRE ACONDICIONADO DE 18,000 BTU/HR.

2x32A CABLE, 2-1x4 mm2+1x2.5mm2, 0.6/1kV - PVC Ø 20mm

C15 SUBTABLERO TS2


2x20A RESERVA (TIPO EMPOTRADO, 2Ø, 220V, 60Hz, 10KA)

C16
RESERVA
C1

2x20A 2x20-30mA
ILUMINACION
CABLE, 2-1x2.5mm2, 0.6/1kV - PVC Ø 25mm
INGRESO N.P.T.: + - 0.00
2x20A

C17 SUBTABLERO TS1 C2 TOMACORRIENTES


Caja de Registro

Rampa
3X16A 3x16-30mA 2x32A 2x32-30mA CABLE, 2-1x4mm2, 0.6/1kV - PVC Ø 25mm
CABLE, 2-1x6mm2 + 1x4mm2, 0.6/1kV - PVC Ø 25mm
C18 SUBTABLERO TS2 C3 TOMACORRIENTES
3X16A 3x16-30mA 2x32A 2x32-30mA CABLE, 2-1x4mm2, 0.6/1kV - PVC Ø 25mm
CABLE, 2-1x6mm2 + 1x4mm2, 0.6/1kV - PVC Ø 25mm 2X32A
BORNERA DE TIERRA

RESERVA

BORNERA DE TIERRA
C4

1.00 x 2.40

Rampa
1.00 x 2.20
Rampa

0.90 x 2.20

0.90 x 2.20
S.H.
PERSONAL DEPOSITO

Area
SALA DE ESPERA biocontaminada
Rampa

1.28 m2

Máquina de
TS2 hemodiálisis CENTRAL DE
OXIGENO
TS1 REUBICACION
Máquina de
LIMPIEZA Máquina de TP1
hemodiálisis
hemodiálisis
CONSULTORIO
9.20 m2 SALA DE

SALA DE HEMODIÁLISIS
HALL 42.65 m2
HEMODIÁLISIS SECUNDARIA AISLADOS
28.97 m2
4.86 m2 INGRESO
9.50 m2 TS2
TS1 UBICACION ACTUAL
AR TP1
EA Máquina de
EN DE T hemodiálisis GDS-3
FER RA
ME BAJ
RA O Rampa ADMISION
S N.P.T.: + 0.15

S.H. S.H.
PACIENTE PACIENTE
DEP
VESTIDOR CEBADO
4.28 m2 9.78 m2

PLANTA DE
DEP
Máquina de
OSMOSIS
hemodiálisis 11.75 m2

MANTENIMIENTO AREA TRABAJO

1.00 x 2.20
ENFERMERAS