CUADRO DE CARGA SERVICIOS GENERALES

USANDO LA REGLA 050-202(3) Y LA REGLA 050-210


POT. INST. F.D.
ITEM CARGAS AREA = 174.91 m2
(w) (%)
1 SEMISOTANO Y AREAS COMUNES
174.91 m2 x 10 w/m2 1,749 100
2 EQUIPO DE BOMBEO AGUA DOMESTICA
ELECTROBOMBA 1 1.5 HP 1,500 50
ELECTROBOMBA 2 1.5 HP 1,500 50
3 EQUIPO DE BOMBEO DESAGUE
ELECTROBOMBA 1 1 HP 750 50
ELECTROBOMBA 2 1 HP 750 50
5 CENTRAL INTERCOMUNICADOR 300 100
6 CENTRAL ALARMA CONTRA INCENDIO 500 100
7 ASCENSOR 6,000 100

SUMA RESULTANTE 13,049


POTENCIA A CONTRATAR 13,049 w x 1 = 13,049 w.

CUADRO DE CARGAS TIPICO (TD-101)


AREA TECHADA A CONSIDERAR OFICINAS. 101, 102. 89.6

REGLA 050.210 CARGAS POT. INST. F.D.


(w) (%)
(1)(a)(i) CARGA BASICA 89,6x25w./m2 2,240 100
(1)(a)(ii) CARGA ADICIONAL 1,000 100
(1)(a)(iii) CARGA FRACCION

(1)(a)(iv) OTRAS CARGAS > 1500w.


RESERVA A.A. 1,500 w. 1,500 800

SUMA RESULTANTE 4,740


POTENCIA A CONTRATAR 4,740 w x .8 = 3,792 w. ≈ 3000 w.

CUADRO DE CARGAS TIPICO (TD-201,TD-301,TD-401)


AREA TECH. A CONSIDERAR OFICINAS. TD-201,TD-301,TD-401. 88.67
REGLA 050.210 CARGAS POT. INST. F.D.
(w) (%)
TABLA 14 CARGA BASICA 56.47x25w./m2 2,217 100
050.210(a) AVISO LUMINOSO 1,000 100

050.210(b) CARGA ADICIONAL > 1500w.


RESERVA A.A. 1,500 w. 1,500 800

SUMA RESULTANTE 4,717


POTENCIA A CONTRATAR 4,717 w x .8 = 3,773 w. ≈ 3500 w.
S

MAX. DEM.
(w)

1,749

750
750

375
375
300
500
6,000

10,799

m2

MAX. DEM.
(w)
2,240
1,000

1,200

4,440

,TD-401)
m2
MAX. DEM.
(w)
2,217
1,000

1,200

4,417
CUADRO DE CARGA SERVICIOS GENERALES
USANDO LA REGLA 050-202(3)
POT. INST. F.D.
ITEM CARGAS AREA = 568.38 m2
(w) (%)
1 SEMISOTANO Y AREAS COMUNES
568.38 m2 x 10 w/m2 5,684 75
2 EQUIPO DE BOMBEO AGUA DOMESTICA
ELECTROBOMBA 1 2 HP 750 75
ELECTROBOMBA 2 2 HP 750 75
ELECTROBOMBA 2 2 HP NO APLICA
3 EQUIPO DE BOMBEO DESAGUE
ELECTROBOMBA 1 1 HP 375 75
ELECTROBOMBA 2 1 HP NO APLICA
4 PUERTA SECCIONABLE
1 u. x 375 w. c/u 375 75
5 CENTRAL INTERCOMUNICADOR 300 75
6 CENTRAL ALARMA CONTRA INCENDIO 500 75
7 ASCENSOR 6,000 75
8 PLATAFORMA MINUSVALIDO 3,000 75

SUMA RESULTANTE 17,734

DETERMINACION DE LA P.I. Y DE LA M.D. DEL EDIFICIO

REGLA CARGAS POT. INST. F.D.


(w) (%)
O50.212 UNIDAD DE OFICINA TD-101 3,374
O50.212 UNIDAD DE OFICINA TD-102 3,912
O50.212 UNIDAD DE OFICINA TD-201 3,912
O50.212 UNIDAD DE OFICINA TD-202 3,912
O50.212 UNIDAD DE OFICINA TD-301 3,912
O50.212 UNIDAD DE OFICINA TD-302 3,912
O50.212 UNIDAD DE OFICINA TD-401 3,912
O50.212 UNIDAD DE OFICINA TD-402 3,912
O50.212 UNIDAD DE OFICINA TD-501 3,912
O50.212 UNIDAD DE OFICINA TD-502 3,912
O50.212 SERVICIOS GENERALES TGS 13,049

CARGA TOTAL 51,631


050.202(3)(d) TOTAL CARGAS
CON UN FACTOR DE DEMANDA DEL 75% 51,631 75
SUMA RESULTANTE 51,631
S

MAX. DEM.
(w)

4,263

563
563

281

281
225
375
4,500
2,250

13,300

DIFICIO

MAX. DEM.
(w)
3,074
3,612
3,612
3,612
3,612
3,612
3,612
3,612
3,612
3,612
10,779

46,361

38,723
38,723
CALCULO DE LA CAIDA DE TENSION
TABLERO GENERAL T-G
SISTEMA TRIFASICO RESULTADOS
∆v=Id x ρ x Cos Φ x L / Sx0.57
M.D. = MAXIMA DEMANDA 13,925 w.
In = MD / 1.7320xV x Cos Φ 38.47 A.
Id = In x 1,25 48.09 A. > 50 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.95
L = LONGITUD (DESDE EL MEDIDOR) 18.65 m.
S = SECCION DEL CONDUCTOR (p/fase) 10 mm.2 LSOHX-90
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 1.47 v.
∆ = % DE 220 v. 0.67 % < 2.50%

INTERRUPTOR GENERAL 3 x 45 A.

CALCULO DE LA CAIDA DE TENSION


TD-201/202/301/302
SISTEMA MONOFASICO RESULTADOS
∆v=Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 3,612 w.
In = MD / V x Cos Φ 18.24 A.
Id = In x 1,25 22.80 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 45.75 m.
S = SECCION DEL CONDUCTOR (p/fase) 16 mm.2 LSOHX-90
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 1.78 v.
∆ = % DE 220 v. 0.81 % < 2.50%

INTERRUPTOR GENERAL 2 x 40 A.

CALCULO DE LA CAIDA DE TENSION


TD-501/502/
SISTEMA MONOFASICO RESULTADOS
∆v=Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 3,612 w.
In = MD / V x Cos Φ 18.24 A.
Id = In x 1,25 22.80 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 52.45 m.
S = SECCION DEL CONDUCTOR (p/fase) 10 mm.2 LSOHX-90
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 3.27 v.
∆ = % DE 220 v. 1.49 % < 2.50%

INTERRUPTOR GENERAL 2 x 40 A.

CALCULO DE LA CAIDA DE TENSION


TD-401/402/
SISTEMA MONOFASICO RESULTADOS
∆v=Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 3,612 w.
In = MD / V x Cos Φ 18.24 A.
Id = In x 1,25 22.80 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 49.65 m.
S = SECCION DEL CONDUCTOR (p/fase) 1016 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 0.03 v.
∆ = % DE 220 v. 0.01 % < 2.50%

INTERRUPTOR GENERAL 2 x 40 A.

CALCULO DE LA CAIDA DE TENSION TD - 301


SISTEMA MONOFASICO RESULTADOS
∆v=Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 7,750 w.
In = MD / V x Cos Φ 39.14 A.
Id = In x 1,25 48.93 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 45.25 m.
S = SECCION DEL CONDUCTOR (p/fase) 16 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 3.78 v.
∆ = % DE 220 v. 1.72 % < 2.50%

INTERRUPTOR GENERAL 2 x 50 A.
CALCULO DE LA CAIDA DE TENSION TD - 302
SISTEMA MONOFASICO RESULTADOS
∆v=Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 7,750 w.
In = MD / V x Cos Φ 39.14 A.
Id = In x 1,25 48.93 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 51.05 m.
S = SECCION DEL CONDUCTOR (p/fase) 16 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 4.27 v.
∆ = % DE 220 v. 1.94 % < 2.50%

INTERRUPTOR GENERAL 2 x 50 A.

CALCULO DE LA CAIDA DE TENSION TD - 401


SISTEMA MONOFASICO RESULTADOS
∆v=Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 7,000 w.
In = MD / V x Cos Φ 35.35 A.
Id = In x 1,25 44.19 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 47.50 m.
S = SECCION DEL CONDUCTOR (p/fase) 16 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 3.59 v.
∆ = % DE 220 v. 1.63 % < 2.50%

INTERRUPTOR GENERAL 2 x 50 A.

CALCULO DE LA CAIDA DE TENSION TD - 402


SISTEMA MONOFASICO RESULTADOS
∆v=Id x ρ x Cos Φ x L / S
M.D. = MAXIMA DEMANDA 9,000 w.
In = MD / V x Cos Φ 45.45 A.
Id = In x 1,25 56.82 A. > 25 A.
ρ = COEFICIENTE DE RESISTIVIDAD DEL Cu. 0.017535 *mm.2/m.
Cos Φ = FACTOR DE POTENCIA 0.90
L = LONGITUD (DESDE EL MEDIDOR) 54.05 m.
S = SECCION DEL CONDUCTOR (p/fase) 16 mm.2 THW
T = SECCION DEL CONDUCTOR A TIERRA 10 mm.2 TW
∆v. = CAIDA DE TENSION EN VOLTIOS 5.25 v.
∆ = % DE 220 v. 2.38 % < 2.50%

INTERRUPTOR GENERAL 2 x 60 A.