ESTRUCTURAL DE TANQUE CIRCULAR DE CONCRETO ARMADO, V = 200 m3.

MEMORIA DE CÁLCULO José Nelson Durón V.


Ingeniero Civil
CONSTANTES DE DISEÑO CICH - 899
Concreto f’c = 280 kg/cm2
Acero de refuerzo fy = 4,200 kg/cm2
Peso volumétrico del concreto wc = 2,400 kg/m3
Peso volumétrico del agua wa = 1,000 kg/m3
Peso volumétrico del suelo ws = 1,800 kg/m3
Carga viva sobre cubierta LL= 100 kg/m2

Cálculo de las dimensiones del tanque.


Diámetro interior del tanque (m) 8.70
Altura útil propuesta (h), metros 3.20
Area fondo (A) m2= Vol/H= 59.45
Volumen útil del tanque (V) m3= 190.23 50,220.65 gal

DIMENSIONES DEL TANQUE


Volumen útil de diseño 190.23 m3
Diámetro interior (D) 8.70 m
Nivel útil de agua 3.20 m
Altura máxima de los muros hasta la losa 3.60 m
Bordo libre 0.40 m

Cálculo de las presiones del agua a diferentes profundidades de fondo hacia arriba
h1 h2 h3
h 3.60 2.00 1.00
P=
2
Para h1 = 3.60 m, h2 = 2.00 m y h3 = 1.00 m considero el tanque lleno totalmente
h1 + h2  P1=(1000x3.6+1000x2.0)/2 2,800.00 kg/m
2

P1 =
2
h2  P2=(1000x2.0+1000x1.0)/2 1,500.00 kg/m
2
P2 =
2
h2
P2 =
2 José Nelson Durón V.
h a ⅓(H)  P2=(1000x3.6/3+1000x0.0)/2 600.00 kg/m
2
Ingeniero Civil
P3 = 3
2 CICH - 899
tensiones perimetrales en bandas
PD
T =
2
banda de la
P1 D 
T1 = resultante T1=(2,800x8.92)/2= 12,180.00 kg/m
2
2
PD  T2=(1,500x8.92)/2= 6,525.00 kg/cm
T2 = 2
2
2
P3 D  T1=(2,600x8.92)/2= 2,610.00 kg/cm
T3 =
2

Por lo tanto T MAX = 12,488.85 kg

Cálculo del espesor mínimo del muro circular.

cEs + fs − nfct
h= T max
100 fs  fct
c fs (kg/cm2) fct (kg/cm2) Es (kg/cm2) n TMAX factorsanit
0.0003 1500 26 2,100,000 9 20,706.00 1.7
esp (h)= 17.1127126 En vista que el CHOC exige dos capas de acero,
\ Espesor = 25cm
Cálculo del acero horizontal en la unión del muro con el fondo.
cant.#4/m #4 a
2
Para T1= 20,706.00 As1= 13.80 cm 10.70 0.09
5.35 0.19

cálculo entre dos y un metro de profundidad


2
Para T2= 11,092.50 As2= 7.40 cm 5.73 0.17
cálculo entre dos y un metro de profundidad José Nelson Durón V.
2
Para T3= 4,437.00 As3= 2.96 cm 2.29 0.44 Ingeniero Civil
USAR #4 a 0.19 m EN CADA CAPA CICH - 899
Nota: Un porcentaje metálico un poco mayor aumenta la vida útil del
acero al proveer mayor resistencia contra la corrosión y, para cumplir con
norma sísmica, se conservará la separación.

Diseño estructural de la losa de cubierta del tanque.


Cargas
2
Peso propio de losa aligerada (20 cm) 380 kg/m
2
Desniveles y repello inferior (interior) 288 kg/m
2
Otras (equipo, tuberías) 100 kg/m
2
Carga muerta 768 kg/m
2
Carga viva 100 kg/m
2
Cálculo del nervio tipo Carga última 1,245.20 kg/m
684.86 wnervio 684.86 kg/m
1,772.08 1,772.08 sección
R 3,544.15 b h d
M 925.66 kg-m 15 20 16.77
M k/F'c w ρ As
925.66 0.116048327 0.125313355 0.009398502 2.36 0.94
1,439.92 0.18051962 0.205414816 0.015406111 3.88 2.46

nervio15x20 2#4

2#3 2#3

2#4 2#3
estribos #2 a 20 estribos #2 a 20
José Nelson Durón V.
columna sección circular Ingeniero Civil
Ø=25cm (10") CICH - 899
6#4,#3 a 18
Cálculo de la viga central Probaré viga de 25x40
w=W*8.70/2+0.25*0.40*2.4*1.4x1.7= 3,550.34 kg/m
M= 7,464.59 kg-m mom negat.
M= 4,798.67 kg-m mom posit.
Rcol= 30,887.97 kg
b h d
25 40 36.77
M k/F'c w ρ As
7,464.59 0.116823018 0.12622305 0.009466729 2#4cont+3#5 acero negat.
8.70
4,798.67 0.075100511 0.0787604 0.00590703 5.43 4#4 acero posit.
Vu= 17,760.58 Vc= 7,060.96 Vs= 10,699.63
s=Avfyd/Vs 13.67 cm usar 4#a12, resto a 18 en cada tramo
Viga 2#4
2#4 3#5 2#4 2#4

Estr.#3 4a12, resto a 18,4a12 4a12, resto a 18,4a12

columna sección circular


Cálculo de la columna central
La columna y zapata se calculan por otro medio, solo se indican resultados. 0.003 es el porcentaje de acero vertical mínimo en
Columna de sección circular, diámetro 25 cm,6#4, estribos #3 cada 18 cm. muros de tanque de acuerdo con el ACI 350 artículo
14.3.2.
25cm Como las paredes del reservorio tienen una altura de
Usar tubo PVC 10" como 3.60 m, se ha utilizado el espesor mínimo de e = 0.30 m
encofrado y dejarlo en obra. de acuerdo a la consideracion del ACI 350 (Artículo
Usar anillos de madera u otro soporte para evitar deformación durante colado. 14.6.2).

Cálculo de zapata central


P= 19,927.72 kg fsperm= 2.00 kg/cm2 José Nelson Durón V.
Zapata Areq´d 9,963.86 0.996386023 fs= 1.3743255 Ingeniero Civil
lado lado h d lad-diám col CICH - 899
0.99819138 110 30 25.9125 85
Mu (kg-cm)= 12,528.70 Fsfact= 2.679935
M k/F'c w ρ As # var#5
12,528.70 0.089749642 0.095083789 0.007131284 14.25 7.1259375

usar 8 #5 en cada sentido


Fundir capa de concreto pobre de 7.5cm sobre plástico grueso y rasante
capa concreto pobre 7.5cm espesor

material selecto compactado

30 cm zapata aislada central: 1.10x1.10x0.30, 8#5 a/s


capa concreto pobre 7.5cm espesor
110
½" tamaño mínimo de barra de acero en tanque de
acuerdo al ACI 350 artículo 7.12.2.2.
Cálculo de refuerzo vertical en muro
5.1. Dimensionamiento de las paredes y tapa del reservorio
Luz larga / luz corta = 4.5/3.0 = 1.5 < 2 => Las paredes no tienen comportamiento
bidireccional, entonces, se aplica la norma del espesor mínimo € de las paredes del
reservorio según ACI 350, 14.6.2 es:
• e =L/30
• h = 3.00 m => emin = 0.30 m usaré espesor de 0.30 m
Como las paredes del reservorio tienen una altura de 3.60 m, se utiliza un espesor mínimo
de 30 cm, de acuerdo con ACI 350,14.6.2.
14.1.1 — Provisions of Chapter 14 shall apply for design of planar walls subject to axial
load, with or without flexure; and circular walls with axial load and hoop tension, with or
without flexure.
14.3.2 — Minimum ratio of vertical reinforcement area to gross
concrete area shall be 0.0030.
14.3.2 — Minimum ratio of vertical reinforcement area to gross
concrete area shall be 0.0030. José Nelson Durón V.
14.3.4 — Walls more than 10 in. thick shall have reinforcement for each direction placed in two layers Ingeniero Civil
parallel to faces of wall in accordance with the following: CICH - 899
14.6.1 — Thickness of nonbearing walls that do not receive their vertical stability from curvature shall
not be less than 6 in., nor less than 1/30 the least distance between members that supply lateral
support.
14.6.2 — The minimum thickness of conventionally reinforced cast-in-place concrete walls that are in
contact with liquids and are at least 10 ft high shall be 12 in.

Nos quedamos, entonces, con una pared de 30 cm de espesor


Usaré Factor de seguridad de presión invectiva causada por sismo de 1.3x1.5
2
pw= 3,600.00 kg/m Pw= 6,480.00 lado h d
Mu= 7,776.00 kg-m 100 30 25.9125
M k/F'c w ρ As Núm. var #5 var #5 a
7,776.00 0.061273941 0.063665377 0.004774903 12.37 6.186484037 0.16
o´k 5040
0.30
8.70
Cálculo de losa inferior 0.30
Cálculo de pesos 0.35 25
zapata continua muro losa superior 20,067.87 0.8 anchoreq´d
paredes 145,759.85 1.66E+05 2,932.47 kg/m 33.94981 usaré 0.80 para reducir acero de losa inf.
losa inferior 31,686.10 comprobacion por cortante
volumen agua 214,008.43 Vc=0.53(√f´c)bd 23,041.29 19,201.07
245,694.54 Vu= 6,132.00 o´k
diámetro losa inferior 8.20 usaré 0.25 deespesor
2 2
Área de contacto losa inferior/suelo 52.81 m 528,101.73 cm
2 2
esfuerzo en el suelo 4,652.41 kg/m 0.47 kg/cm 0.3 0.30
kg/cm2
2
usaré viga de cimentación central 4.65 ton/m
4.65 ton/m
4.10 4.10 lado h d
8.20 m 100 30 25.91
M= 8.69 ton-m fundir losa de concreto pobre sobre rasante José Nelson Durón V.
M(-), (+) k/F'c w ρ As Núm. var #4 var #4 a Ingeniero Civil
8.69E+05 0.068473525 0.071488808 0.005361661 13.89 10.77007984 0.09 CICH - 899
5.59E+05 0.044018694 0.045225445 0.003391908 8.79 6.813397421 0.15
José Nelson Durón V.
Ingeniero Civil
CICH - 899
T2
José Nelson Durón V.
#4 a 25
Ingeniero Civil
CICH - 899
1.20 T1
#4 a 19

DETALLE DE ARMADO DEL MURO

T2
#4 a 25

1.20 T1
#4 a 19

DETALLE DE ARMADO DEL MURO


T2 José Nelson Durón V.
#4 a 25 Ingeniero Civil
CICH - 899

1.20 T1
#4 a 19

DETALLE DE ARMADO DEL MURO

nervios

viga central

viga-solera perimetral
35x20; 4#4, #3 a 18
José Nelson Durón V.
Ingeniero Civil
CICH - 899

5.5. Control de fisuras para la condición de carga


única
El control de fisuras se realiza bajo cargas de servicio
para verificar el espaciamiento máximo del acero de
refuerzo y garantizar la impermeabilidad de las pa redes del reservorio.
El máximo momento de flexión vertical empleado
en el diseño es Mux = 3699.54 kg-m, cuyo refuerzo
calculado es Ø 1/2» @ 0.175 m.
Como el diseño es en la etapa elástica, se determina
el máximo momento de flexión en la etapa de ser vicio:
5.5. Control de fisuras para la condición
de carga única
El control de fisuras se realiza bajo
cargas de servicio para verificar el
espaciamiento máximo del acero de
refuerzo y garantizar la impermeabilidad de
las paredes del reservorio.
El máximo momento de flexión vertical
empleado en el diseño es:
Mux = 3699.54 kg-m, cuyo refuerzo calculado
es Ø 1/2" @ 0.175 m.
Como el diseño es en la etapa elástica, se
determina el máximo momento de flexión en la
etapa de servicio:
Ms = Mu
1.3 x 1.7 = 3699.54
1.3 x 1.7 = 1674.00 kg - m
El esfuerzo en el refuerzo calculado para las
cargas de servicio es:
? As = 7.62 cm2
? d = 30 - 6 = 24 cm
s = 1017.06 kg/cm2
Según el ACI 350 (Artículo C 10.6.4), fs se
puede tomar como
fs = 1017.06 kg/cm2
Según el ACI 350 (Artículo C 10.6.4), fs se
puede tomar como el 45 % de fy:
fs = 0.45 x 4200 kg/cm2 = 1890 kg/cm2
Entonces, podemos trabajar con el
promedio: (1017.06 + 1890) / 2 = 1453,53 kg/cm2
El espaciamiento máximo para el control de
grietas es:

? Para condiciones severas z = 17000


kg/cm ancho de fisura de 2 mm José Nelson Durón V.
? dc = r + db/2 = 5 + 1,27/2 = 5,63 cm Ingeniero Civil
dc=r+db/2=5+1.27/2=5.63cm CICH - 899
3
smax=0.5z3/(dc2f0.5z
3
s )=0.5x170003/ 0.5x170003 25.24
2 3
dc2fs3 5,63 x 1453,53
= 25 cm
25 cm > 17,5 cm, por lo tanto, el espaciamiento calculado, controla el ancho
de las grietas.
Figura 10: Detalle del acero en el reservorio
VI.CONCLUSIONES
1. Una manera simple para el análisis y
diseño de las paredes con
comportamiento bidireccional de los
tanques rectangulares es con la ayuda
de las tablas de la PCA, Bares, etc.
2. Para el diseño de tanques
rectangulares, es importante aplicar las
especificaciones del Código Ambiental
ACI 350, lo cual se representa en la
aplicación del diseño por resistencia en
etapa última, amplificado por los
coeficientes sanitarios (para flexión,1,3 y
para tracción, 1,65), además de la
verificación del acero para el control de
fisuras.
3. Un diseño eficiente de los tanques
rectangulares que garanticen su
resistencia, su durabilidad y la
impermeabilidad contribuirá al
mejoramiento del medio ambiente.
4. Para tanques superficiales de
dimensiones pequeñas, las fuerzas
sísmicas no son significativas para el José Nelson Durón V.
diseño; las fuerzas que prevalecen son Ingeniero Civil
las estáticas. CICH - 899
smax=0.5z3/(dc2fs3)=0.5x170003/