CIRCUITO #3: TOMACORRIENTES SALA. CIRCUITO #4: TOMACORRIENTES 1 COCINA.

VOLTIOS = 120V VOLTIOS = 120V

DISTANCIA = 4.35m + 0.90m + 2.20m = 7.45m DISTANCIA = 2.35m + 0.90m + 1.30m = 4.55m

TUBERIA = PVC TUBERIA = PVC

F.P. = 100% F.P. = 100%

POTENCIA = 1500VA POTENCIA = 1500VA

1500𝑉𝐴 1500𝑉𝐴
𝐼= = 12.5 𝐴 𝐼= = 12.5 𝐴
120𝑉 120𝑉

CORRIENTE DE DISEÑO, CONSUMO = 12.5 A CORRIENTE DE DISEÑO, CONSUMO = 12.5 A

PROTECCION: PROTECCION:

(12.5 𝐴) ∙ (1.25) = 15.625 𝐴 (12.5 𝐴) ∙ (1.25) = 15.625 𝐴

DISYUNTOR DE 1/20amp, 120V DISYUNTOR DE 1/20amp, 120V

CONDUCTOR: CONDUCTOR:

(TABLA 3-6) = 20amp →#12-75°C (TABLA 3-6) = 20amp →#12-75°C

(TABLA 310-16) = 30amp →#12 THHN-90°C Cu (TABLA 310-16) = 30amp →#12 THHN-90°C Cu

FACTOR CABLE (CORRECCION): FACTOR CABLE (CORRECCION):

(TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410 (TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410

FACTOR DEL SISTEMA: FACTOR DEL SISTEMA:

MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577 MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577

CAIDA DE TENSION: CAIDA DE TENSION:

(0.3410) ∙ (12.5 𝐴) ∙ (7.45𝑚) ∙ (0.577) (0.3410) ∙ (12.5 𝐴) ∙ (4.55𝑚) ∙ (0.577)


𝐶𝑇 = 𝐶𝑇 =
30.48 30.48

CT = 0.6011V CT = 0.3671V

PORCENTAJE DE CAIDA DE TENSION: PORCENTAJE DE CAIDA DE TENSION:

0.6011𝑉 0.4397𝑉
%𝐶𝑇 = ∙ 100 %𝐶𝑇 = ∙ 100
120𝑉 120𝑉

% CT = 0.5009 % CT = 0.3059

Ø DE CANALIZACION: Ø DE CANALIZACION:

(TABLA 1, CAP9 NEC) CAL #12THHN = 12.70mm = 13mm PVC (TABLA 1, CAP9 NEC) CAL #12THHN = 12.70mm = 13mm PVC
CIRCUITO #5: TOMACORRIENTES 2 COCINA. CIRCUITO #6: SALIDA MICROONDAS.

VOLTIOS = 120V VOLTIOS = 120V

DISTANCIA = 3.25m + 0.90m + 1.30m = 5.45m DISTANCIA = 3.00m + 0.90m + 1.30m = 5.20m

TUBERIA = PVC TUBERIA = PVC

F.P. = 100% F.P. = 100%

POTENCIA = 1500VA POTENCIA = 1200VA

1500𝑉𝐴 1200𝑉𝐴
𝐼= = 12.5 𝐴 𝐼= = 10.0 𝐴
120𝑉 120𝑉

CORRIENTE DE DISEÑO, CONSUMO = 12.5 A CORRIENTE DE DISEÑO, CONSUMO = 10.0 A

PROTECCION: PROTECCION:

(12.5 𝐴) ∙ (1.25) = 15.625 𝐴 (10.0 𝐴) ∙ (1.25) = 12.5 𝐴

DISYUNTOR DE 1/20amp, 120V DISYUNTOR DE 1/15amp, 120V

CONDUCTOR: CONDUCTOR:

(TABLA 3-6) = 20amp →#12-75°C (TABLA 3-6) = 15amp →#14-75°C se aumenta a →#12-75°C

(TABLA 310-16) = 30amp →#12 THHN-90°C Cu (TABLA 310-16) = 30amp →#12 THHN-90°C Cu

FACTOR CABLE (CORRECCION): FACTOR CABLE (CORRECCION):

(TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410 (TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410

FACTOR DEL SISTEMA: FACTOR DEL SISTEMA:

MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577 MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577

CAIDA DE TENSION: CAIDA DE TENSION:

(0.3410) ∙ (12.5 𝐴) ∙ (5.45𝑚) ∙ (0.577) (0.3410) ∙ (10.0 𝐴) ∙ (5.20𝑚) ∙ (0.577)


𝐶𝑇 = 𝐶𝑇 =
30.48 30.48

CT = 0.4397V CT = 0.3356V

PORCENTAJE DE CAIDA DE TENSION: PORCENTAJE DE CAIDA DE TENSION:

0.4397𝑉 0.3356𝑉
%𝐶𝑇 = ∙ 100 %𝐶𝑇 = ∙ 100
120𝑉 120𝑉

% CT = 0.3664 % CT = 0.2796

Ø DE CANALIZACION: Ø DE CANALIZACION:

(TABLA 1, CAP9 NEC) CAL #12THHN = 12.70mm = 13mm PVC (TABLA 1, CAP9 NEC) CAL #12 THHN = 12.70mm = 13mm PVC
CIRCUITO #7: SALIDA REFRIGERADOR. CIRCUITO #8 - 9: SALIDA COCINA.

VOLTIOS = 120V VOLTIOS = 240V

DISTANCIA = 2.00m + 0.90m + 1.30m = 4.20m DISTANCIA = 3.40m + 0.90m + 1.30m = 5.60m

TUBERIA = PVC TUBERIA = PVC

F.P. = 100% F.P. = 100%

POTENCIA = 1200VA POTENCIA = 8000VA

1200𝑉𝐴 8000𝑉𝐴
𝐼= = 10.0 𝐴 𝐼= = 33.33 𝐴
120𝑉 240𝑉

CORRIENTE DE DISEÑO, CONSUMO = 10.0 A CORRIENTE DE DISEÑO, CONSUMO = 33.33 A

PROTECCION: PROTECCION:

(10.0 𝐴) ∙ (1.25) = 12.5 𝐴 (33.33 𝐴) ∙ (1.25) = 41.66 𝐴

DISYUNTOR DE 1/15amp, 120V DISYUNTOR DE 2/50amp, 240V

CONDUCTOR: CONDUCTOR:

(TABLA 3-6) = 15amp →#14-75°C se aumenta a →#12-75°C (TABLA 3-6) = 50amp →#6-75°C

(TABLA 310-16) = 30amp →#12 THHN-90°C Cu (TABLA 310-16) = 75amp →#6 THHN-90°C Cu

FACTOR CABLE (CORRECCION): FACTOR CABLE (CORRECCION):

(TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410 (TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.0849

FACTOR DEL SISTEMA: FACTOR DEL SISTEMA:

MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577 MONOFASICO, 3 CONDUCTORES, FASE-FASE = 1.155

CAIDA DE TENSION: CAIDA DE TENSION:

(0.3410) ∙ (10.0 𝐴) ∙ (4.20𝑚) ∙ (0.577) (0.0849) ∙ (33.33 𝐴) ∙ (5.60𝑚) ∙ (1.155)


𝐶𝑇 = 𝐶𝑇 =
30.48 30.48

CT = 0.2711V CT = 0.6004V

PORCENTAJE DE CAIDA DE TENSION: PORCENTAJE DE CAIDA DE TENSION:

0.2711𝑉 0.6004𝑉
%𝐶𝑇 = ∙ 100 %𝐶𝑇 = ∙ 100
120𝑉 240𝑉

% CT = 0.2259 % CT = 0.2501

Ø DE CANALIZACION: Ø DE CANALIZACION:

(TABLA 1, CAP9 NEC) CAL #12 THHN = 12.70mm = 13mm PVC (TABLA 1, CAP9 NEC) CAL #8 THHN = 19.05mm = 19mm PVC
CIRCUITO #10: TOMACORRIENTES BAÑOS. CIRCUITO #11: TOMACORRIENTES LAVANDERIA.

VOLTIOS = 120V VOLTIOS = 120V

DISTANCIA = 1.80m + 0.90m + 1.20m = 3.90m DISTANCIA = 3.40m + 0.90m + 1.30m = 5.60m

TUBERIA = PVC TUBERIA = PVC

F.P. = 100% F.P. = 100%

POTENCIA = 1200VA POTENCIA = 1200VA

1200𝑉𝐴 1200𝑉𝐴
𝐼= = 10.0 𝐴 𝐼= = 10.0 𝐴
120𝑉 120𝑉

CORRIENTE DE DISEÑO, CONSUMO = 10.0 A CORRIENTE DE DISEÑO, CONSUMO = 10.0 A

PROTECCION: PROTECCION:

(10.0 𝐴) ∙ (1.25) = 12.5 𝐴 (10.0 𝐴) ∙ (1.25) = 12.5 𝐴

DISYUNTOR DE 1/15amp, 120V DISYUNTOR DE 1/15amp, 120V

CONDUCTOR: CONDUCTOR:

(TABLA 3-6) = 15amp →#14-75°C se aumenta a →#12-75°C (TABLA 3-6) = 15amp →#14-75°C se aumenta a →#12-75°C

(TABLA 310-16) = 30amp →#12 THHN-90°C Cu (TABLA 310-16) = 30amp →#12 THHN-90°C Cu

FACTOR CABLE (CORRECCION): FACTOR CABLE (CORRECCION):

(TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410 (TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410

FACTOR DEL SISTEMA: FACTOR DEL SISTEMA:

MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577 MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577

CAIDA DE TENSION: CAIDA DE TENSION:

(0.3410) ∙ (10.0 𝐴) ∙ (3.90𝑚) ∙ (0.577) (0.3410) ∙ (10.0 𝐴) ∙ (5.60𝑚) ∙ (0.577)


𝐶𝑇 = 𝐶𝑇 =
30.48 30.48

CT = 0.2517V CT = 0.3614V

PORCENTAJE DE CAIDA DE TENSION: PORCENTAJE DE CAIDA DE TENSION:

0.2517𝑉 0.3614𝑉
%𝐶𝑇 = ∙ 100 %𝐶𝑇 = ∙ 100
120𝑉 120𝑉

% CT = 0.2097 % CT = 0.3011

Ø DE CANALIZACION: Ø DE CANALIZACION:

(TABLA 1, CAP9 NEC) CAL #12 THHN = 12.70mm = 13mm PVC (TABLA 1, CAP9 NEC) CAL #12 THHN = 12.70mm = 13mm PVC
CIRCUITO #12 - 13: SALIDA CENTRO DE LAVADO. CIRCUITO #14 - 15: SALIDA CALENTADOR DE AGUA.

VOLTIOS = 240V VOLTIOS = 240V

DISTANCIA = 3.60m + 0.90m + 1.30m = 5.80m DISTANCIA = 4.80m + 0.90m + 1.30m = 7.00m

TUBERIA = PVC TUBERIA = PVC

F.P. = 100% F.P. = 100%

POTENCIA = 6000VA POTENCIA = 10000VA

6000𝑉𝐴 10000𝑉𝐴
𝐼= = 25.0 𝐴 𝐼= = 41.66 𝐴
240𝑉 240𝑉

CORRIENTE DE DISEÑO, CONSUMO = 25.0 A CORRIENTE DE DISEÑO, CONSUMO = 41.66 A

PROTECCION: PROTECCION:

(25.0 𝐴) ∙ (1.25) = 31.25 𝐴 (41.66 𝐴) ∙ (1.25) = 52.075 𝐴

DISYUNTOR DE 2/40amp, 240V DISYUNTOR DE 2/60amp, 240V

CONDUCTOR: CONDUCTOR:

(TABLA 3-6) = 40amp →#8-75°C (TABLA 3-6) = 60amp →#6-75°C

(TABLA 310-16) = 55amp →#8 THHN-90°C Cu (TABLA 310-16) = 75amp →#6 THHN-90°C Cu

FACTOR CABLE (CORRECCION): FACTOR CABLE (CORRECCION):

(TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.1350 (TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.0849

FACTOR DEL SISTEMA: FACTOR DEL SISTEMA:

MONOFASICO, 3 CONDUCTORES, FASE-FASE = 1.155 MONOFASICO, 3 CONDUCTORES, FASE-FASE = 1.155

CAIDA DE TENSION: CAIDA DE TENSION:

(0.1350) ∙ (25.0 𝐴) ∙ (5.80𝑚) ∙ (1.155) (0.0849) ∙ (41.66 𝐴) ∙ (7.00𝑚) ∙ (1.155)


𝐶𝑇 = 𝐶𝑇 =
30.48 30.48

CT = 0.7417V CT = 0.9381V

PORCENTAJE DE CAIDA DE TENSION: PORCENTAJE DE CAIDA DE TENSION:

0.7417𝑉 0.9381𝑉
%𝐶𝑇 = ∙ 100 %𝐶𝑇 = ∙ 100
240𝑉 240𝑉

% CT = 0.3090 % CT = 0.3908

Ø DE CANALIZACION: Ø DE CANALIZACION:

(TABLA 1, CAP9 NEC) CAL #8 THHN = 19.05mm = 19mm PVC (TABLA 1, CAP9 NEC) CAL #6 THHN = 25.40mm = 25mm PVC
CIRCUITO #16: TOMACORRIENTES DORMITORIO PRINCIPAL. CIRCUITO #17: TOMACORRIENTES DORMITORIO SECUNDARIO.

VOLTIOS = 120V VOLTIOS = 120V

DISTANCIA = 5.10m + 1.00m + 0.30m = 6.40m DISTANCIA = 5.00m + 1.00m + 0.30m = 6.30m

TUBERIA = PVC TUBERIA = PVC

F.P. = 100% F.P. = 100%

POTENCIA = 1500VA POTENCIA = 1500VA

1500𝑉𝐴 1500𝑉𝐴
𝐼= = 12.5 𝐴 𝐼= = 12.5 𝐴
120𝑉 120𝑉

CORRIENTE DE DISEÑO, CONSUMO = 12.5 A CORRIENTE DE DISEÑO, CONSUMO = 12.5 A

PROTECCION: PROTECCION:

(12.5 𝐴) ∙ (1.25) = 15.625 𝐴 (12.5 𝐴) ∙ (1.25) = 15.625 𝐴

DISYUNTOR DE 1/20amp, 120V DISYUNTOR DE 1/20amp, 120V

CONDUCTOR: CONDUCTOR:

(TABLA 3-6) = 20amp →#12-75°C (TABLA 3-6) = 20amp →#12-75°C

(TABLA 310-16) = 30amp →#12 THHN-90°C Cu (TABLA 310-16) = 30amp →#12 THHN-90°C Cu

FACTOR CABLE (CORRECCION): FACTOR CABLE (CORRECCION):

(TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410 (TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410

FACTOR DEL SISTEMA: FACTOR DEL SISTEMA:

MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577 MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577

CAIDA DE TENSION: CAIDA DE TENSION:

(0.3410) ∙ (12.5 𝐴) ∙ (6.40𝑚) ∙ (0.577) (0.3410) ∙ (12.5 𝐴) ∙ (6.30𝑚) ∙ (0.577)


𝐶𝑇 = 𝐶𝑇 =
30.48 30.48

CT = 0.5164V CT = 0.5083V

PORCENTAJE DE CAIDA DE TENSION: PORCENTAJE DE CAIDA DE TENSION:

0.5164𝑉 0.5083𝑉
%𝐶𝑇 = ∙ 100 %𝐶𝑇 = ∙ 100
120𝑉 120𝑉

% CT = 0.4303 % CT = 0.4235

Ø DE CANALIZACION: Ø DE CANALIZACION:

(TABLA 1, CAP9 NEC) CAL #12THHN = 12.70mm = 13mm PVC (TABLA 1, CAP9 NEC) CAL #12THHN = 12.70mm = 13mm PVC
CIRCUITO #18: TOMACORRIENTES GENERAL SEGUNDO NIVEL. CIRCUITO #19: LUMINARIAS GENERAL PRIMER NIVEL.

VOLTIOS = 120V VOLTIOS = 120V

DISTANCIA = 3.45m + 1.00m + 0.30m = 4.75m DISTANCIA = 3.80m + 0.90m = 4.70m

TUBERIA = PVC TUBERIA = PVC

F.P. = 100% F.P. = 100%

POTENCIA = 1500VA POTENCIA = 360VA

1500𝑉𝐴 360𝑉𝐴
𝐼= = 12.5 𝐴 𝐼= =3𝐴
120𝑉 120𝑉

CORRIENTE DE DISEÑO, CONSUMO = 12.5 A CORRIENTE DE DISEÑO, CONSUMO = 3 A

PROTECCION: PROTECCION:

(12.5 𝐴) ∙ (1.25) = 15.625 𝐴 (3 𝐴) ∙ (1.25) = 3.75 𝐴

DISYUNTOR DE 1/20amp, 120V DISYUNTOR DE 1/20amp, 120V

CONDUCTOR: CONDUCTOR:

(TABLA 3-6) = 20amp →#12-75°C (TABLA 3-6) = 15amp →#14-75°C se aumenta a →#12-75°C

(TABLA 310-16) = 30amp →#12 THHN-90°C Cu (TABLA 310-16) = 30amp →#12 THHN-90°C Cu

FACTOR CABLE (CORRECCION): FACTOR CABLE (CORRECCION):

(TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410 (TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410

FACTOR DEL SISTEMA: FACTOR DEL SISTEMA:

MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577 MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577

CAIDA DE TENSION: CAIDA DE TENSION:

(0.3410) ∙ (12.5 𝐴) ∙ (4.75𝑚) ∙ (0.577) (0.3410) ∙ (3 𝐴) ∙ (4.70𝑚) ∙ (0.577)


𝐶𝑇 = 𝐶𝑇 =
30.48 30.48

CT = 0.3832V CT = 0.0910V

PORCENTAJE DE CAIDA DE TENSION: PORCENTAJE DE CAIDA DE TENSION:

0.3832𝑉 0.0910𝑉
%𝐶𝑇 = ∙ 100 %𝐶𝑇 = ∙ 100
120𝑉 120𝑉

% CT = 0.3193 % CT = 0.0758

Ø DE CANALIZACION: Ø DE CANALIZACION:

(TABLA 1, CAP9 NEC) CAL #12THHN = 12.70mm = 13mm PVC (TABLA 1, CAP9 NEC) CAL #12THHN = 12.70mm = 13mm PVC
CIRCUITO #20: LUMINARIAS SALA – COCINA - LAVANDERIA. CIRCUITO #21: LUMINARIAS GENERAL SEGUNDO NIVEL.

VOLTIOS = 120V VOLTIOS = 120V

DISTANCIA = 4.80m + 0.90m = 5.70m DISTANCIA = 2.00m + 0.90m = 2.90m

TUBERIA = PVC TUBERIA = PVC

F.P. = 100% F.P. = 100%

POTENCIA = 480VA POTENCIA = 300VA

480𝑉𝐴 300𝑉𝐴
𝐼= =4𝐴 𝐼= = 2.5 𝐴
120𝑉 120𝑉

CORRIENTE DE DISEÑO, CONSUMO = 4 A CORRIENTE DE DISEÑO, CONSUMO = 2.5 A

PROTECCION: PROTECCION:

(4 𝐴) ∙ (1.25) = 5 𝐴 (2.5 𝐴) ∙ (1.25) = 3.125 𝐴

DISYUNTOR DE 1/20amp, 120V DISYUNTOR DE 1/20amp, 120V

CONDUCTOR: CONDUCTOR:

(TABLA 3-6) = 15amp →#14-75°C se aumenta a →#12-75°C (TABLA 3-6) = 15amp →#14-75°C se aumenta a →#12-75°C

(TABLA 310-16) = 30amp →#12 THHN-90°C Cu (TABLA 310-16) = 30amp →#12 THHN-90°C Cu

FACTOR CABLE (CORRECCION): FACTOR CABLE (CORRECCION):

(TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410 (TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410

FACTOR DEL SISTEMA: FACTOR DEL SISTEMA:

MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577 MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577

CAIDA DE TENSION: CAIDA DE TENSION:

(0.3410) ∙ (4 𝐴) ∙ (5.70𝑚) ∙ (0.577) (0.3410) ∙ (2.5 𝐴) ∙ (2.90𝑚) ∙ (0.577)


𝐶𝑇 = 𝐶𝑇 =
30.48 30.48

CT = 0.1471V CT = 0.0468V

PORCENTAJE DE CAIDA DE TENSION: PORCENTAJE DE CAIDA DE TENSION:

0.1471𝑉 0.0468𝑉
%𝐶𝑇 = ∙ 100 %𝐶𝑇 = ∙ 100
120𝑉 120𝑉

% CT = 0.1225 % CT = 0.0390

Ø DE CANALIZACION: Ø DE CANALIZACION:

(TABLA 1, CAP9 NEC) CAL #12THHN = 12.70mm = 13mm PVC (TABLA 1, CAP9 NEC) CAL #12THHN = 12.70mm = 13mm PVC
CIRCUITO #22: LUMINARIAS DORMITORIOS.

VOLTIOS = 120V

DISTANCIA = 4.60m + 0.90m = 5.50m

TUBERIA = PVC

F.P. = 100%

POTENCIA = 420VA

420𝑉𝐴
𝐼= = 3.5 𝐴
120𝑉

CORRIENTE DE DISEÑO, CONSUMO = 3.5 A

PROTECCION:

(3.5 𝐴) ∙ (1.25) = 4.375 𝐴

DISYUNTOR DE 1/20amp, 120V

CONDUCTOR:

(TABLA 3-6) = 15amp →#14-75°C se aumenta a →#12-75°C

(TABLA 310-16) = 30amp →#12 THHN-90°C Cu

FACTOR CABLE (CORRECCION):

(TABLA 1.3-13) CANALIZADO NO MAGNETICO (PVC) F.P.100 = 0.3410

FACTOR DEL SISTEMA:

MONOFASICO, 3 CONDUCTORES, FASE-NEUTRO = 0.577

CAIDA DE TENSION:

(0.3410) ∙ (3.5 𝐴) ∙ (5.50𝑚) ∙ (0.577)


𝐶𝑇 =
30.48

CT = 0.1242V

PORCENTAJE DE CAIDA DE TENSION:

0.1242𝑉
%𝐶𝑇 = ∙ 100
120𝑉

% CT = 0.1035

Ø DE CANALIZACION:

(TABLA 1, CAP9 NEC) CAL #12THHN = 12.70mm = 13mm PVC