Está en la página 1de 17

CÁLCULO DE DEMANDA DE AGUA

DEMANDA DE AGUA
VOLUMEN
PISO AMBIENTE UND CANTIDAD DOTACION
PARCIALES
AGUA FRIA:
1 RESTAURANT und. 1.00 1.000 m3/und./día 1.000
AREA VERDE m2. 150.00 0.002 m3/m2/día 0.300
2 OFICINAS
ofic 3,4,5,6,12,13,15,16 m2. 20.00 0.006 m3/m2/día 0.120
ofic 1 m2. 31.00 0.006 m3/m2/día 0.186
ofic 2 m2. 25.00 0.006 m3/m2/día 0.150
ofic 7 m2. 40.00 0.006 m3/m2/día 0.240
ofic 8,9,10,11 m2. 12.00 0.006 m3/m2/día 0.072
ofic 14 m2. 14.00 0.006 m3/m2/día 0.084

3 DEPARTAMENTO 5DORM. und. 3.00 1.500 m3/und./día 4.500

Azotea
AGUA CALIENTE
DEPARTAMENTO 5 DORM. und. 3.00 0.45 m3/und./día 1.350

CALCULO DE LOS VOLUMENES DE CISTERNA Y TANQUE ELEVADO PARA EL RESTAURANT

Volumen de cisterna Vc = 0.98 m3


Volumen del Tanque Elevado VTE = 0.43 m3
Asumimos Vc= 1.00 m3. d=1.20 h=1.55m
Asumimos Vte= 0.45 m3. D 0.85 H=1.00m

CALCULO DE LOS VOLUMENES DE CISTERNA Y TANQUE ELEVADO PARA DEPARTAMENTO 1

Volumen de cisterna Vc = 1.13 m3


Volumen del Tanque Elevado VTE = 0.50 m3
Asumimos Vc= 1.20 m3.
Asumimos Vte= 0.50 m3.
CALCULO DE LOS TANQUES ACUMULADORES DE AGUA CALIENTE:
Según el R.N.E. :
Departamento de 5 dormitorios: 450 lts
Tanque de agua caliente (1/5 de la dotación)= 90
Asumimos: Therma de 100 lts. departamentos de 5 dormitorios.
CALCULO DE LAS UNIDADES DE GASTO:
VOLUMEN PISO APARATO UND CANT. UH

PARCIALES TOTAL LAVATORIOS UND 12 2


INODOROS UND 12 5
1° LAVADEROS DE COCINA UND 2 4
1.300
URINARIO UND 3 3

LAVATORIOS UND 16 2
2° INODOROS UND 16 5

LAVATORIOS UND 7 1
INODOROS UND 9 3
DUCHAS UND 6 2

LAVADEROS DE ROPA UND 3 4
LAVADEROS DE COCINA UND 3 3
6.652
TOTAL U.H (RESTAURANT)
CAUDAL DE DISEÑO Q=
TOTAL U.H (OFICINAS)
1.350 TOTAL U.H (POR CADA OFICINA)
CAUDAL DE DISEÑO Q=
TOTAL U.H (DEPARTAMENTO 1)
PARA EL RESTAURANT CAUDAL DE DISEÑO Q=
TOTAL U.H (DEPARTAMENTO 2)
CAUDAL DE DISEÑO Q=
TOTAL U.H (DEPARTAMENTO 3)
CAUDAL DE DISEÑO Q=

ARA DEPARTAMENTO 1:2:3 TOTAL U.H


CAUDAL DE DISEÑO Q=
CALCULO DEL COLECTOR:
TOTAL UH PISO APARATOS UNIDAD CANTIDAD U.D. TOTAL
24 PISO APARATO UND CANT. UH TOTAL UH

60 LAVATORIOS UND 12 2 24
8 INODOROS UND 12 5 60
9 101 1° LAVADEROS DE COCINA UND 2 4 8
URINARIO UND 3 3 9
32
80 LAVATORIOS UND 16 2 32
2° INODOROS UND 16 5 80
7
27 LAVATORIOS UND 7 1 7
12 INODOROS UND 9 3 27
12 DUCHAS UND 6 2 12

9 LAVADEROS DE ROPA UND 3 4 12
LAVADEROS DE COCINA UND 3 3 9
101
1.68 lts/seg. TOTAL 280
112 lts/seg. Colector Principal 4"
7
0.28 lts/seg.
19
0.52 lts/seg.
22
0.58 lts/seg.
26
0.67 lts/seg.

280
3.00 lts/seg.
< 180
S = 1%
Cáculo de linea de alimentación y medidor

Datos Variable Calculo


Presion de servicio en la red Pr
Presion minima de agua a la salida en la cisterna Ps
Desnivel entre la red publica y el punto de entrega a la cisterna Ht
Longitud de la linea de servicio
Tiempo de llenado de la cisterna
Volumen de la cisterna
Accesorios en la linea 1 valv comp, 8 codos

Incognitas
Diametro del medidor
Diametro de la linea

Solución
Variable Calculo
Caudal de ingreso a la cisterna Q V/T
Carga disponible H H=Pr - Ps - Ht
Perdida de carga maxima del medidor h 0.50.H

Del abaco de perdidas de carga de medidores para Q= 25.89869 g.p.m.

Diametro Perdida (psi) Perdida (m)


1" 4.10 2.87 medidor tipo disco
hm

Luego el diametro del medidor será 1"

Pr=10 m

Cisterna
V=1 m3
Variable Calculo
Carga disponible con medidor de 1" h h=H - hm
Diametro asumido D
Longitudes equivalentes de accesorios
para D= 1" Cantidad Long Equi
Valvula de comp 1 0.216
Codos de 90 3 1.023

Variable Cálculo
Longitud total L
Pendiente S S
Perdida de carga hf hf=S.L

Carga disponible > hf D = 1"


CÁLCULO DE PÉRDIDAS DE CA

Valor Und DIAMETROS INTERIORES DE TUBERIAS DE PVC


10 m
2m Ø m.
1m 1/2" 0.017
6m 3/4" 0.023
0.17 hr 1" 0.029
1.00 m3 1 1/4" 0.038
p, 8 codos 1 1/2" 0.043
2" 0.054
2 1/2" 0.066
3" 0.080
3 1/2" 0.088
4" 0.098
6" 0.145
Valor Und
5.88 m3/h 1.63 l/s LONGITUDES EQUIVALENTES A PERDIDAS DE CARGA L
7.00 m (exprepadas en metros de longitus)
3.50 m 5.00 psi
Ø codo
1/2" 0.532
3/4" 0.777
1" 1.023
1 1/4" 1.309
1 1/2" 1.554
2" 2.045
2 1/2" 2.577
3" 3.068
3 1/2" 3.600
4" 4.091
6" 6.136

Ps=2 m

Cisterna
V=1 m3
Valor Und
4.13 m
29.40 mm

Long
0.216
3.069

Valor Und
9.285
0.1983 m/m
1.84 m
O DE PÉRDIDAS DE CARGA EN LAS REDES DE A.F.

UBERIAS DE PVC

m. m. A
17.40 0.0002
22.90 0.0004
29.40 0.0007
38.00 0.0011
43.40 0.0015
54.20 0.0023
66.00 0.0034
80.10 0.0050
88.00 0.0061
98.00 0.0075
144.60 0.0164

A PERDIDAS DE CARGA LOCALIZADAS

tee Valv. Comp. reducc Valv. Comp. reducc Check Pie


1.064 0.112 0.030 0.112 0.030 1.099 3.599
1.554 0.164 0.043 0.164 0.043 1.606 5.260
2.045 0.216 0.057 0.216 0.057 2.114 6.920
2.618 0.278 0.073 0.278 0.073 2.705 8.868
3.109 0.328 0.086 0.328 0.086 3.213 10.519
4.091 0.432 0.114 0.432 0.114 4.227 13.841
5.154 0.544 0.143 0.544 0.143 5.326 17.440
6.136 0.648 0.170 0.648 0.170 6.341 20.761
7.200 0.750 0.200 0.750 0.200 7.440 24.360
8.180 0.864 0.227 0.864 0.227 8.454 27.682
12.273 1.295 0.341 1.295 0.341 12.682 41.523
MEMORIA DE CALCULO
CÁLCULO DE LA ELECTROBOMBA
1 Calculos del caudal de bombeo
Volumen del tanque elevado 0.45 m3
Tiempo de llenado 0.075 hr
Caudal de llenado Qllenado te 1.67 l/seg
Unidades de Gasto 101.00
Qdms 1.68 l/seg
Caudal de bombeo = El mayor Q entre el Qdms y Qllenado te 1.68 l/seg
2 Cálculo de la ADT
Nivel de succion -2.35
Nivel de descarga 17.95
Desnivel geometrico 20.30 m
Accesorios en la succión
1 codo
1 canastilla
Accesorios en la impulsión
1 Valv Check
1 Valv de comp
1 Tee
5 codos de 90
Longitud de la impulsión= 40.00 m
Longitud de la succión = 8.00 m
3 Cálculo del Diámetro económico
Aplicando la formula de Bresse
De = K . Q 1/2 . X1/4
Donde: Q = Caudal en m3/seg
X = N° HB/24
K = 1,3 a 1,9
Para el caso: Q= 0.002 m3/seg
Para el caso: N° HB = 1 horas 0.17 hr
Luego: De = 0.0155 m
Diametro comercial 1 1/2" plg
Diámetro interior 0.0434 m

4 Cálculo de la pérdida de carga unitaria en la impulsión


Aplicando la fórmula de Hazen y Williams
Q= 0.2785 x C x D^2.63 x S^ 0.54
Despejando la pèrdida de carga unitaria
S= ((Q/0.2785CxD^2.63))^(1/0.54)
Material a utilizar en el sistema Fierro Galvanizado
Coeficiente de rugosidad de Hazen y Willimas para fo gdo C= 100
Reemplazando:
Simp= 0.06638 m/m
5 Cálculo de la longitud equivalente de accesorios en la impulsión
Diámetro de la impulsión= 1 1/2" 0.0434 m
Accesorio Cantidad Lon Equi Unit Log Eq par
Valv check 1 3.213 3.213
Valv de comp 1 0.328 0.328
Tee 1 3.109 3.109
Codos de 90 2 1.554 3.108 9.758

6 Cálculo de la longitud equivalente de accesorios en la succión


Diámetro de la succión= 2" 0.0542
Accesorio Cantidad Lon Equi Unit Log Eq par
Canastilla 1 13.841 13.841
Codo de 90 3 2.045 6.135 19.976
7 Cálculo de la pérdida de carga unitaria en la succión
Ssuccion= (0.00275/(0.2785x100x0.00861^2.63))^(1/0.54) 0.02249 m/m
8 Calculo de perdidas de carga hf en tuberias y accesorios
hf en tuberias en la impulsión = SimpxLimp= 2.66 m
hf en tuberias en la succión = SsuccxLsucc= 0.18 m
hf en accesorios en la impulsión = SimpxLequ imp= 0.65 m
hf en accesorios en la succión = SsuccxLequ succ= 1.08 m
9 Cálculo de la velocidad de paso del agua por la impulsión
V= Q/A = 1.14 m
10 Presion de Servicio
Adoptando Ps= 2.00
11 Cálculo de la Altura Dinámica Total
ADT= hgeo+hft +hfacc+ps+v2/2g
ADT= 26.93 m
12 Calculo de la Potencia del equipo de bombeo
Caudal de bombeo 1.68 lts/seg
Altura Dinámica Total 26.93 m
Adoptando una eficiencia de 60% n= 0.60
Potencia = (QxADT/(76xn))*1.15= 1.14 HP
Numero de Unidades: 2
Potencia de la bomba de 1.50 HP
Funcionamiento: Alternado
Ø codo tee Valv. Comp. reducc Check Pie
1/2" 0.532 1.064 0.112 0.030 1.099 3.599
3/4" 0.777 1.554 0.164 0.043 1.606 5.260
1" 1.023 2.045 0.216 0.057 2.114 6.920
1 1/4" 1.309 2.618 0.278 0.073 2.705 8.868
1 1/2" 1.554 3.109 0.328 0.086 3.213 10.519
2" 2.045 4.091 0.432 0.114 4.227 13.841
2 1/2" 2.577 5.154 0.544 0.143 5.326 17.440
3" 3.068 6.136 0.648 0.170 6.341 20.761
3 1/2" 3.600 7.200 0.750 0.200 7.440 24.360
4" 4.091 8.180 0.864 0.227 8.454 27.682
6" 6.136 12.273 1.295 0.341 12.682 41.523