SERIE SET FREE FSNM

Catálogo técnico

RAS-8FSNM
RAS-10FSNM
RAS-12FSNM
Contenido

Contenido

Información general 1
Características y ventajas 2
Datos generales 3
Capacidades y datos de selección 4
Curvas acústicas características 5
Margen de funcionamiento 6
Dimensiones generales 7
Ciclo de refrigerante 8
Instalación de las tuberías y carga de refrigerante 9
Cableado eléctrico 10
Funciones opcionales 11
Resolución de problemas 12

III TCES0059 rev.2 - 06/2016


Índice general

Índice general

1. Información general.................................................................................................... 1
1.1 Información general................................................................................................................................. 2
1.1.1  Notas generales............................................................................................................................................... 2
1.1.2 Introducción...................................................................................................................................................... 2

1.2 Seguridad................................................................................................................................................. 3
1.2.1  Simbología aplicada......................................................................................................................................... 3

1.3 Guía del producto..................................................................................................................................... 4


1.3.1  Nomenclatura de los modelos de unidades exteriores.................................................................................... 4
1.3.2  Nomenclatura de los modelos de unidades interiores..................................................................................... 4
1.3.3  Guía del producto: Unidades exteriores........................................................................................................... 4
1.3.4  Lista de códigos de accesorios........................................................................................................................ 5
1.3.5  Línea de producto: unidades interiores............................................................................................................ 6
1.3.6  Línea de producto: Unidad KPI de recuperación de energía / calor.............................................................. 10
1.3.7  Línea de producto: Interfaz DX...................................................................................................................... 10
1.3.8  Línea de producto: Econofresh...................................................................................................................... 10

2. Características y ventajas........................................................................................ 11
2.1 Beneficios de la selección...................................................................................................................... 12
2.1.1  Ventajas de la serie SET FREE FSNM.......................................................................................................... 12
2.1.2  Gama de accesorios...................................................................................................................................... 13
2.1.3  Gama de mandos a distancia......................................................................................................................... 13
2.1.4  Flexibilidad del sistema.................................................................................................................................. 14
2.1.5  Disponibilidad de software de selección Hi-Tool Kit....................................................................................... 15

2.2 Ventajas de la instalación....................................................................................................................... 20


2.2.1  Diseño compacto y ligero de primera clase................................................................................................... 20
2.2.2  Mayor comodidad en la entrega e instalación................................................................................................ 21
2.2.3  Flexibilidad de instalación ampliada............................................................................................................... 22
2.2.4  Instalación eléctrica fácil y flexible................................................................................................................. 24
2.2.5  Conexión de control fácil y flexible (estación central, interfaz BMS, CSNET WEB)...................................... 26

2.3 Ventajas de puesta en marcha............................................................................................................... 26


2.3.1  Prueba automática de puesta en marcha...................................................................................................... 26
2.3.2  Supervisor de servicio.................................................................................................................................... 26

2.4 Ventajas funcionales.............................................................................................................................. 27


2.4.1  Ahorro energético........................................................................................................................................... 27
2.4.2  Tecnologías de ruido bajo.............................................................................................................................. 28
2.4.3  Nuevas funciones........................................................................................................................................... 30
2.4.4  Margen de temperaturas................................................................................................................................ 31
2.4.5  Control electrónico de la capacidad............................................................................................................... 32

2.5 Ventajas de mantenimiento.................................................................................................................... 33

V TCES0059 rev.2 - 06/2016


Índice general

2.5.1  Disponibilidad de herramientas de mantenimiento........................................................................................ 33

2.6 Características principales de las unidades.......................................................................................... 34


2.6.1  Reducción de la capacidad total de la unidad exterior................................................................................... 34
2.6.2  Compresor DC Inverter de alta eficacia ........................................................................................................ 35
2.6.3  Características mejoradas del motor del ventilador para la serie FSNM....................................................... 37

3. Datos generales........................................................................................................ 39
3.1 Datos generales..................................................................................................................................... 40
3.1.1  Condiciones generales................................................................................................................................... 40
3.1.2  RAS-(8-12)FSNM........................................................................................................................................... 41

3.2 Datos de los componentes..................................................................................................................... 42

3.3 Datos eléctricos...................................................................................................................................... 42

4. Capacidades y datos de selección.......................................................................... 43


4.1 Procedimiento de selección del sistema de la Serie SET-FREE FSNM................................................ 44
4.1.1  Posibilidades del sistema SET-FREE............................................................................................................ 44
4.1.2  Parámetros de selección................................................................................................................................ 46
4.1.3  Procedimiento de selección........................................................................................................................... 46

4.2 Tablas de capacidad de enfriamiento..................................................................................................... 53


4.2.1  Curva de capacidad de enfriamiento.............................................................................................................. 53
4.2.2  Tablas de capacidad de enfriamiento nominal............................................................................................... 53
4.2.3  Tablas de capacidad de enfriamiento según potencia total de unidades interiores combinadas................... 54

4.3 Tablas de capacidad de calefacción...................................................................................................... 59


4.3.1  Curva de capacidad de calefacción............................................................................................................... 59
4.3.2  Tablas de capacidad de calefacción nominal................................................................................................. 60
4.3.3  Tablas de capacidad de calefacción según potencia total de unidades interiores combinadas..................... 60

4.4 Factores de corrección........................................................................................................................... 66


4.4.1  Factor de corrección de la longitud de las tuberías........................................................................................ 66
4.4.2  Factor de corrección de descarche................................................................................................................ 68

5. Curvas acústicas características............................................................................ 69


5.1 Nivel acústico total................................................................................................................................. 70

5.2 Curvas de presión acústica.................................................................................................................... 71

5.3 Curvas de potencia acústica.................................................................................................................. 72

6. Margen de funcionamiento...................................................................................... 73
6.1 Fuente de alimentación.......................................................................................................................... 74

6.2 Margen de temperatura.......................................................................................................................... 74

VI TCES0059 rev.2 - 06/2016


Índice general

7. Dimensiones generales............................................................................................ 75
7.1 Gráfico de dimensiones......................................................................................................................... 76

8. Ciclo de refrigerante................................................................................................. 77
8.1 Ciclo de refrigerante de la unidad RAS-(8-12)FSNM............................................................................. 78

9. Instalación de las tuberías y carga de refrigerante............................................... 79


9.1 Selección de las tuberías de refrigerante............................................................................................... 80
9.1.1  Número máximo y mínimo de unidades interiores por unidad exterior.......................................................... 80
9.1.2  Rango de tuberías de refrigerante................................................................................................................. 80
9.1.3  Longitud de la tubería de refrigerante mediante ajuste de conmutadores DIP.............................................. 81
9.1.4  Tamaño de la tubería y kit de conexiones múltiples....................................................................................... 81

9.2 Multi-kits y distribuidores........................................................................................................................ 83


9.2.1 Tamaños......................................................................................................................................................... 83
9.2.2  Método de distribución................................................................................................................................... 84
9.2.3  Tuberías de cobre y tamaños......................................................................................................................... 87

9.3 Cantidad de carga de refrigerante......................................................................................................... 90


9.3.1  Cálculo de la carga de refrigerante adicional (R410A)................................................................................... 90
9.3.2  Ejemplos de cálculo....................................................................................................................................... 92

9.4 Precaución con las fugas de refrigerante............................................................................................... 98


9.4.1  Máxima concentración permisible de gas HCFC/HFC................................................................................... 98
9.4.2  Cálculo de la concentración de refrigerante................................................................................................... 98
9.4.3  Contramedidas en caso de fugas de refrigerante......................................................................................... 98

10. Cableado eléctrico.................................................................................................... 99


10.1 Comprobaciones generales................................................................................................................. 100

10.2 Ajustes y funciones de los conmutadores DIP..................................................................................... 100


10.2.1  DSW1: Prueba de funcionamiento y ajustes de servicio............................................................................ 101

10.3 Cableado común.................................................................................................................................. 105


10.3.1  Cableado eléctrico entre la unidad interior y la exterior............................................................................. 105

10.4 Tamaño del cableado........................................................................................................................... 106

11. Funciones opcionales............................................................................................ 109


11.1 Funciones opcionales disponibles para unidades exteriores............................................................... 110

12. Resolución de problemas...................................................................................... 111


12.1 Indicación de alarma............................................................................................................................ 112

12.2 Códigos de alarma para la serie FSNM............................................................................................... 112

VII TCES0059 rev.2 - 06/2016


1 Información general

1. Información general

Índice 1
1.1 Información general................................................................................................................................. 2
1.1.1  Notas generales............................................................................................................................................... 2
1.1.2 Introducción...................................................................................................................................................... 2

1.2 Seguridad................................................................................................................................................. 3
1.2.1  Simbología aplicada......................................................................................................................................... 3

1.3 Guía del producto..................................................................................................................................... 4


1.3.1  Nomenclatura de los modelos de unidades exteriores.................................................................................... 4
1.3.2  Nomenclatura de los modelos de unidades interiores..................................................................................... 4
1.3.3  Guía del producto: Unidades exteriores........................................................................................................... 4
1.3.4  Lista de códigos de accesorios........................................................................................................................ 5
1.3.5  Línea de producto: unidades interiores............................................................................................................ 6
1.3.6  Línea de producto: Unidad KPI de recuperación de energía / calor.............................................................. 10
1.3.7  Línea de producto: Interfaz DX...................................................................................................................... 10
1.3.8  Línea de producto: Econofresh...................................................................................................................... 10

1 TCES0059 rev.2 - 06/2016


1 Información general

Información general

1.1 Información general


1.1.1  Notas generales

© Copyright 2016 HITACHI Air Conditioning Products Europe, S.A.U. - Todos los derechos reservados.
Ningún fragmento de esta publicación puede ser reproducido, copiado, archivado o transmitido en ninguna forma o
medio sin permiso de HITACHI Air Conditioning Products Europe, S.A.U.
En el marco de una política de mejora continua de la calidad de sus productos, HITACHI Air Conditioning Products
Europe, S.A.U. se reserva el derecho de realizar cambios en cualquier momento, sin comunicación previa y sin incurrir
en la obligación de introducirlas en los productos vendidos con anterioridad. Por lo tanto, este documento puede haber
sufrido modificaciones durante la vida del producto.
HITACHI realiza todos los esfuerzos posibles para ofrecer documentación correcta y actualizada. Pese a ello, los errores
de impresión están fuera del control de HITACHI, que no se hace responsable de ellos.
En consecuencia, algunas de las imágenes o algunos de los datos empleados para ilustrar este documento pueden no
corresponder a modelos concretos. No se admitirán reclamaciones basadas en los datos, ilustraciones y descripciones
de este manual.
No debe hacerse ningún tipo de modificación en el equipo sin la autorización previa y por escrito del fabricante.
1.1.2  Introducción
• El sistema de aire acondicionado SET-FREE es un sistema tipo VRF (Flujo de refrigerante variante) que permite que
múltiples unidades interiores, de distinta potencia y modelo, se ajusten con controles independientes para cada una
de ellas.
• Los sistemas SET-FREE de Hitachi ofrecen una alta eficacia, fiabilidad y confort, características que hacen del
sistema SET-FREE uno de los mejores del mercado.

2 TCES0059 rev.2 - 06/2016


1 Información general

Seguridad

1.2 Seguridad
1.2.1  Simbología aplicada

Durante el diseño del sistema de aire acondicionado y la instalación de los equipos, es necesario prestar mayor atención
en algunas situaciones que requieren especial cuidado, para evitar daños en el equipo, en la instalación o en el edificio

1
o inmueble.
Aquellas situaciones que puedan comprometer la integridad de las personas o que pongan en peligro el equipo se
señalarán de forma clara en este manual.
Para ello se emplearán una serie de símbolos especiales que identificarán claramente estas situaciones.
Preste mucha atención a estos símbolos y a los mensajes que les siguen, pues de ello depende su propia seguridad y la
de los demás.

! PELIGRO
• Los textos precedidos de este símbolo contienen información e indicaciones relacionadas directamente con su seguridad
e integridad física.
• Si no se tienen en cuenta dichas indicaciones tanto usted como otras personas pueden sufrir lesiones graves, muy graves
o incluso mortales.

En los textos precedidos del símbolo de peligro, también puede encontrar información sobre formas seguras de
proceder durante la instalación del equipo.

! PRECAUCIÓN
• Los textos precedidos de este símbolo contienen información e indicaciones relacionadas directamente con su seguridad e integridad
física.
• Si no se tienen en cuenta dichas indicaciones tanto usted como otras personas pueden sufrir lesiones leves.
• No tener en cuenta estas instrucciones puede provocar daños en el equipo.

En los textos precedidos del símbolo de precaución, también puede encontrar información sobre formas seguras de
proceder durante la instalación del equipo.

? N O TA
• Los textos precedidos de este símbolo contienen informaciones o indicaciones que pueden resultar útiles, o que merecen una
explicación más extensa.
• También puede incluir indicaciones acerca de comprobaciones que deben efectuarse sobre elementos o sistemas del equipo.

3 TCES0059 rev.2 - 06/2016


1 Información general

Guía del producto

1.3 Guía del producto


1.3.1  Nomenclatura de los modelos de unidades exteriores

 Unidades exteriores de la serie FSNM


Tipo de unidad (unidad exterior): RAS
Guión separador de posición (fijo)
Capacidad (CV): 8/10/12 CV
FS: Serie SET FREE
N: Refrigerante R410A
Serie
XXX – XX FS N M

1.3.2  Nomenclatura de los modelos de unidades interiores

Tipo de unidad (unidad interior): RCI, RCIM, RCD, RPC, RPI, RPIM, RPK, RPF, RPFI
Guión separador de posición (fijo)
Capacidad (CV): 0,6, 0,8, 1,0, 1,5, 2,0, 2,5, 3,0, 4,0, 5,0, 6,0, 8,0, 10,0
FS = SYSTEM FREE
N = refrigerante R410A
H = Hotel (solo RPK-(0.6-1.5))
2/3/4 = serie
P = Par
E = Fabricado en Europa
M = Fabricado en Malasia
– = Fabricado en Japón
i = Versión mejorada (solo RCI para el panel P-N23NA)
k = Versión mejorada RCI solo para el panel P-AP160NA(1/E)
(-DU) = Desagüe (sólo RPIM)
XXX – X.X FS N (H) X (P) (X) (x) (-DU)

1.3.3  Guía del producto: Unidades exteriores

 Unidades exteriores de la serie FSNM


Unidades exteriores

3N~ 380/415V, 50Hz


RAS-FSNM

Unidad Código
RAS-8FSNM 60288308
RAS-10FSNM 60288309
RAS-12FSNM 60288310

4 TCES0059 rev.2 - 06/2016


1 Información general

Guía del producto

1.3.4  Lista de códigos de accesorios

HITACHI ofrece una amplia gama de accesorios y sistemas de mando a distancia para las unidades exteriores SET
FREE. Consultar el Catálogo Técnico de controles correspondiente.

Nombre Descripción Código Imagen

DBS-26 Conexión de descarga de desagüe 60299192 1


E-102SN4 70524201

Distribuidor en línea

E-162SN4 70524202

MH-84AN1 70522009
Bifurcación de colector
MH-108AN 70522008

5 TCES0059 rev.2 - 06/2016


1 Información general

Guía del producto

1.3.5  Línea de producto: unidades interiores

? N O TA
• Los modelos y códigos de unidad interior son la última actualización en el momento de la publicación de este manual; modelos
anteriores y próximos desarrollos pueden estar disponibles para combinar con esta serie de unidad exterior.
• Verifique la nomenclatura exacta de cada unidad (modelo, tipo, potencia y serie) en “1.3.1 Nomenclatura de los modelos de unidades
exteriores”.

 Unidades interiores RCI y RCIM


RCI RCIM

Cassette de 4 vías Cassette de 4 vías (compacto)


Unidad Código Unidad Código Unidad Código Unidad Código
RCIM-0.8FSN4 60278216
RCI-1.0FSN3Ei 7E403014 RCI-1.0FSN3Ek 7E404001 RCI-1.0FSN3 60278119 RCIM-1.0FSN4 60278217
RCI-1.5FSN3Ei 7E403015 RCI-1.5FSN3Ek 7E404002 RCI-1.5FSN3 60278120 RCIM-1.5FSN4 60278218
RCI-2.0FSN3Ei 7E403016 RCI-2.0FSN3Ek 7E404003 RCI-2.0FSN3 60278121 RCIM-2.0FSN4 60278219
RCI-2.5FSN3Ei 7E403017 RCI-2.5FSN3Ek 7E404004 RCI-2.5FSN3 60278122 RCIM-2.5FSN4 60278220
RCI-3.0FSN3Ei 7E403018 RCI-3.0FSN3Ek 7E404005 RCI-3.0FSN3 60278123

RCI-4.0FSN3Ei 7E403020 RCI-4.0FSN3Ek 7E404007 RCI-4.0FSN3 60278124

RCI-5.0FSN3Ei 7E403021 RCI-5.0FSN3Ek 7E404008 RCI-5.0FSN3 60278125

RCI-6.0FSN3Ei 7E403022 RCI-6.0FSN3Ek 7E404009 RCI-6.0FSN3 60278126

Paneles
RCI RCIM

P-AP160NA1 60297215 P-AP56NAM


P-N23NA 70531000 P-AP160NAE (Sin sensor de 60297297
60297217 presencia)
(Con sensor de presencia)

? N O TA
Los modelos RCI y RCIM deben utilizarse en combinación con los paneles indicados anteriormente.

6 TCES0059 rev.2 - 06/2016


1 Información general

Guía del producto

 Unidades interiores RCD y RPC


RCD RPC

1
Cassette de 2 vías Tipo techo
Unidad Código Unidad Código Unidad Código Unidad Código
RCD-0.8FSN3 60278242

RCD-1.0FSN3 60278243

RCD-1.5FSN3 60278244 RPC-1.5FSN3 60278164

RCD-2.0FSN3 60278245 RPC-2.0FSN3 60278165

RCD-2.5FSN3 60278246 RPC-2.5FSN3 60278166

RCD-3.0FSN3 60278247 RPC-3.0FSN3E 7E443005 RPC-3.0FSN3 60278167

RCD-4.0FSN3 60278248 RPC-4.0FSN3E 7E443007 RPC-4.0FSN3 60278168

RCD-5.0FSN3 60278249 RPC-5.0FSN3E 7E443008 RPC-5.0FSN3 60278169

RCD-6.0FSN3 60278250 RPC-6.0FSN3E 7E443009 RPC-6.0FSN3 60278170

Paneles
RCD

P-AP90DNA 60297300 P-AP160DNA 60297301

? N O TA
Los modelos RCD deben utilizarse en combinación con los paneles indicados anteriormente.

7 TCES0059 rev.2 - 06/2016


1 Información general

Guía del producto

 Unidades interiores RPI y RPIM


RPI RPIM

Unidad interior de conductos Unidad interior de conductos (mini)


Unidad Código Unidad Código Unidad Código
RPIM-0.8FSN4E 7E430013
RPI-0.8FSN4E 7E424013
RPIM-0.8FSN4E -DU 7E431013
RPIM-1.0FSN4E 7E430014
RPI-1.0FSN4E 7E424014
RPIM-1.0FSN4E -DU 7E431014
RPIM-1.5FSN4E 7E430015
RPI-1.5FSN4E 7E424015
RPIM-1.5FSN4E -DU 7E431015
RPI-2.0FSN4E 7E424016

RPI-2.5FSN4E 7E424017

RPI-3.0FSN4E 7E424018

RPI-4.0FSN4E 7E424020

RPI-5.0FSN4E 7E424021

RPI-6.0FSN4E 7E424022

RPI

Unidad interior de conductos


Unidad Código Unidad Código
RPI-8.0FSN3E 7E424010 RPI-8.0FSN3E-f 7E424410
RPI-10.0FSN3E 7E424011 RPI-10.0FSN3E-f 7E424411

8 TCES0059 rev.2 - 06/2016


1 Información general

Guía del producto

 Unidades interiores RPK, RPF y RPFI


RPK RPF RPFI

1
Tipo mural Tipo suelo Tipo consola de suelo sin envolvente
Unidad Código Unidad Código Unidad Código
RPK-0.8FSN3M 60278146

RPK-0.8FSNH3M 60278154

RPK-1.0FSN3M 60278147
RPK-1.0FSNH3M 60278155 RPF-1.0FSN2E 7E450001 RPFI-1.0FSN2E 7E460001
RPK-1.5FSN3M 60278148
RPK-1.5FSNH3M 60278156 RPF-1.5FSN2E 7E450002 RPFI-1.5FSN2E 7E460002
RPK-2.0FSN3M 60278149 RPF-2.0FSN2E 7E450003 RPFI-2.0FSN2E 7E460003
RPK-2.5FSN3M 60278150 RPF-2.5FSN2E 7E450004 RPFI-2.5FSN2E 7E460004
RPK-3.0FSN3M 60278151

RPK-4.0FSN3M 60278152

Kit de la válvula de expansión (1)


EV-1.5N1(1) 60921791

? N O TA
(1)
Sólo para modelos RPK-(0.6-1.5)FSNH3M.

9 TCES0059 rev.2 - 06/2016


1 Información general

Guía del producto

1.3.6  Línea de producto: Unidad KPI de recuperación de energía / calor

KPI

Recuperación de energía Activa (recuperación de energía + sección DX)


Unidad Código Unidad Código
KPI-252E4E 70603000
KPI-502E4E 70603001 KPI-502X4E 70603201
KPI-802E4E 70603002 KPI-802X4E 70603202
KPI-1002E4E 70603003 KPI-1002X4E 70603203
KPI-1502E4E 70603004

KPI-2002E4E 70603005

1.3.7  Línea de producto: Interfaz DX

Interfaz DX
Unidad Código
EXV-2.0E2 7E611000
EXV-2.5E2 7E611001
EXV-3.0E2 7E611002
Caja de control
EXV-4.0E2 7E611003
EXV-5.0E2 7E611004
EXV-6.0E2 7E611005
EXV-8.0E2 7E611006

EXV-10.0E2 7E611007
Caja de la válvula de expansión

1.3.8  Línea de producto: Econofresh

 Kit Econofresh
Econofresh

Unidad Código
EF-456NE 7E560000

? N O TA
La unidad EF-456NE se puede instalar solo en combinación con las siguientes unidades (vendidas a partir de abril de 2014):
• RPI-4.0FSN4E (7E724020)
• RPI-5.0FSN4E (7E724021)
• RPI-6.0FSN4E (7E724022)

10 TCES0059 rev.2 - 06/2016


2 Características y ventajas

2. Características y ventajas

Índice

2.1 Beneficios de la selección...................................................................................................................... 12


2.1.1  Ventajas de la serie SET FREE FSNM.......................................................................................................... 12
2.1.2  Gama de accesorios...................................................................................................................................... 13 2
2.1.3  Gama de mandos a distancia......................................................................................................................... 13
2.1.4  Flexibilidad del sistema.................................................................................................................................. 14
2.1.5  Disponibilidad de software de selección Hi-Tool Kit....................................................................................... 15

2.2 Ventajas de la instalación....................................................................................................................... 20


2.2.1  Diseño compacto y ligero de primera clase................................................................................................... 20
2.2.2  Mayor comodidad en la entrega e instalación................................................................................................ 21
2.2.3  Flexibilidad de instalación ampliada............................................................................................................... 22
2.2.4  Instalación eléctrica fácil y flexible................................................................................................................. 24
2.2.5  Conexión de control fácil y flexible (estación central, interfaz BMS, CSNET WEB)...................................... 26

2.3 Ventajas de puesta en marcha............................................................................................................... 26


2.3.1  Prueba automática de puesta en marcha...................................................................................................... 26
2.3.2  Supervisor de servicio.................................................................................................................................... 26

2.4 Ventajas funcionales.............................................................................................................................. 27


2.4.1  Ahorro energético........................................................................................................................................... 27
2.4.2  Tecnologías de ruido bajo.............................................................................................................................. 28
2.4.3  Nuevas funciones........................................................................................................................................... 30
2.4.4  Margen de temperaturas................................................................................................................................ 31
2.4.5  Control electrónico de la capacidad............................................................................................................... 32

2.5 Ventajas de mantenimiento.................................................................................................................... 33


2.5.1  Disponibilidad de herramientas de mantenimiento........................................................................................ 33

2.6 Características principales de las unidades.......................................................................................... 34


2.6.1  Reducción de la capacidad total de la unidad exterior................................................................................... 34
2.6.2  Compresor DC Inverter de alta eficacia ........................................................................................................ 35
2.6.3  Características mejoradas del motor del ventilador para la serie FSNM....................................................... 37

11 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Beneficios de la selección

2.1 Beneficios de la selección


• El sistema de aire acondicionado SET-FREE aporta una serie de ventajas técnicas que lo hacen uno de los más
atractivos del mercado.
• Desde la selección del tipo de equipamiento ideal en cada caso, hasta su mantenimiento, y pasando por la
instalación, la puesta en marcha y el funcionamiento, SET-FREE siempre proporciona la mejor solución para cada
usuario, y simplifica y facilita en gran medida el proceso de selección del usuario.

El diagrama muestra las múltiples combinaciones de un Sistema SET FREE FSNM

• HITACHI ofrece el mismo tipo de unidades interiores, el sistema SYSTEM-FREE. Hasta ahora, cada gama de
unidades exteriores tenía sus propias unidades interiores. SYSTEM FREE les permite a los usuarios diseñar un
sistema sin tener que pensar qué clase de unidades interiores son necesarias para ello.
• Otra ventaja de este sistema es que permite un mejor control del stock y optimiza el número de referencias. Gracias
a esto, tanto los instaladores como los distribuidores obtienen una significativa reducción en el stock y en los costes
de almacenamiento.
• HITACHI se complace en presentarles la nueva serie SET FREE FSNM, el sistema de aire acondicionado de
alta eficacia y fiabilidad. Actualmente, cada vez más edificios necesitan instalaciones ”inteligentes”, redes de
comunicación y automatización de oficinas en entornos cómodos. Los espacios cómodos son necesarios todos los
días del año en los edificios de oficinas.
El sistema de aire acondicionado multi-split, SET-FREE FSNM, cumple todos estos requisitos. La combinación
del compresor scroll y el inversor proporciona el mejor sistema de aire acondicionado para pequeños y medianos
edificios de oficinas.
• La serie SET FREE FSNM integra el tamaño compacto y la ligereza de un sistema de aire acondicionado multi-split
(con varias unidades interiores) y la facilidad de uso de la serie SET FREE.
2.1.1  Ventajas de la serie SET FREE FSNM
• Se suministra en una estructura compacta. Las condiciones de instalación son comparables a las de un sistema de
aire acondicionado multi-split de alto rendimiento.
• El tamaño y la ligereza de la estructura facilitan la entrega y la instalación.
• La adopción de una estructura estrecha mejora la flexibilidad del montaje permitiendo la instalación en espacios
pequeños y/o inutilizados.
• La nueva serie Set Free SIDE FLOW RAS-FSNM de HITACHI está preparada para someterse al programa de
certificación EUROVENT para unidades VRF.

El programa de certificación EUROVENT para unidades VRF consiste en la certificación del rendimiento de la unidad
exterior. Para ello, tiene en cuenta las capacidades de enfriamiento y calefacción, las eficiencias (EER/COP) y la
potencia acústica.

12 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Beneficios de la selección

2.1.2  Gama de accesorios

Todas las unidades exteriores cuentan con una amplia gama de accesorios que facilitan la instalación, el funcionamiento
y el mantenimiento.
Estos accesorios están diseñados para adaptar la unidad al tipo de instalación que requiere el sistema de aire
acondicionado y mejorar su rendimiento, siempre teniendo en cuenta los parámetros de calidad exigidos.
Las gama de accesorios incluye:
• Mandos a distancia, para la manipulación y el funcionamiento de la instalación.

2
• Kit de conexión de tuberías, para la conexión de tuberías de bifurcación de unidades exteriores.
• Multi-kits y distribuidores para tuberías de bifurcación de las unidades interiores.
• Tuberías de desagüe, para recoger los condensados y canalizarlos.
2.1.3  Gama de mandos a distancia

HITACHI dispone de una gama de sistemas de mando a distancia clasificados según el tipo de gestión y el número de
unidades que gestionan:
• Mando a distancia individual
• Mando a distancia centralizado
• Control del aire acondicionado de edificios (CS-NET WEB / CSNET Manager).
• BMS (sistemas de gestión de edificios).

 Mando a distancia individual


Los sistemas de mando a distancia individuales, ya
sean inalámbricos o conectados directamente por
cable, disponen de una amplia gama de funciones que
facilitan la gestión de la unidad, la programación de
ajustes específicos o la identificación de incidencias.
Recomendable para gestionar un pequeño número de
unidades.

 Mando a distancia centralizado


Los sistemas de mando a distancia centralizados aúnan
las funciones de los mandos a distancia y amplían las
posibilidades de gestión y ajuste para varios sistemas de
aire acondicionado distribuidos por toda la planta de un
edificio.

 Control de aire acondicionado de edificios


Los sistemas de control informatizado incrementan las
posibilidades de gestión y ajuste, y permiten realizarlos
también desde cualquier punto de la red de comunicación
local, a través de un cable de comunicación de dos núcleos
no polarizados, o incluso a través de Internet.
Recomendados para administrar de manera independiente
más de dos plantas en un mismo edificio.
 BMS (sistema de gestión de edificios)
Integración en instalaciones con gestión inteligente. Interfaz
de la Gateway con sistemas LonWorks, KNX, MODBUS y
BACnet BMS.

13 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Beneficios de la selección

2.1.4  Flexibilidad del sistema

 Gran variedad de opciones en los comandos estándares


Las unidades SET-FREE tienen un gran número de comandos estándares. Estas opciones pueden configurarse
fácilmente con una amplia variedad de mandos a distancia HITACHI o a través de las PCBs de las unidades interiores y
exteriores. De esta forma el sistema SET-FREE se adapta a cada instalación.

 Capaz de conectar una unidad exterior con hasta 10 unidades interiores


Utilizando un control inverter, también se encuentra disponible una amplia gama de controles de la capacidad de
funcionamiento. Se puede optar por una potencia total máxima combinada del 130% y una potencia total mínima
combinada del 50% realizando una combinación de unidades interiores, en comparación con la capacidad nominal de
la unidad exterior. De esta forma, el nuevo sistema puede satisfacer todos los requisitos de aire acondicionado en la
mayoría de los edificios de oficinas.

Restricciones de la unidad
Número máximo Número máximo de
RPK-FSNH3M (número
Capacidad recomendado de unidades interiores Gama de
Modelo máximo de unidades
mínima de la unidades interiores conectables (la suma capacidades
de unidad interiores RPK-FSNH3M
unidad interior conectables (solo para de unidades RPK de
exterior combinables con el kit de
conectable unidades interiores de instaladas y otras combinación
la válvula de expansión
0,8 y 1,0) (*) unidades interiores)
EV-1.5N1)
RAS-8FSNM
del 50% al
RAS-10FSNM 0.8 CV (2,2kW) 8 10 8
130%
RAS-12FSNM

(*) La cantidad máxima recomendada es de 8 unidades. Si conecta más de 8 unidades puede haber corrientes de aire
frío durante el funcionamiento con calefacción.

Unidades interiores (Máx. 10)

RAS-(8-12)FSNM

14 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Beneficios de la selección

2.1.5  Disponibilidad de software de selección Hi-Tool Kit

 Asistente para el diseño de instalaciones de aire acondicionado y el cálculo del


rendimiento estacional

Software de selección Hi-ToolKit para la asistencia del diseño


El software de selección Hi-ToolKit es una herramienta que permite diseñar instalaciones de climatización y generar, de
forma automática, toda la información necesaria para completar las especificaciones de la instalación.

Información de la instalación disponible:


• Selección del producto dentro de la extensa gama de HITACHI.
2
• Diagrama de cableado y de enfriamiento conforme al diseño de la instalación.
• Lista completa de los productos necesarios para realizar la instalación.
• Puesta en marcha de la instalación.

 Nuevo software de selección para el cálculo del rendimiento estacional


Hi-ToolKit for Business es un software de Hitachi que ha sido desarrollado especialmente para ayudar a profesionales
que trabajan en la planificación de instalaciones de sistemas de aire acondicionado en edificios no residenciales.
Con solo unos clics, este nuevo software le permite seleccionar rápidamente y con seguridad un sistema Hitachi de la
gama UTOPIA o SET FREE. Hi-ToolKit for Business es una auténtica herramienta que se puede utilizar para realizar
simulaciones de sistemas, orientadas a evaluar la eficiencia en condiciones particulares.
Con Hi-ToolKit for Business tendrá la seguridad de seleccionar el equipo comercial correcto.
Acceso a Hi-ToolKit for Business
Versión web
Al tratarse de una versión web con una estructura flexible y simple, proporciona al usuario una multitud de beneficios:
• El usuario siempre utiliza la última versión del software

NUEVA unidad
Nueva unidad
añadida en
HITACHI
Hi-ToolKit

15 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Beneficios de la selección

• Es accesible desde cualquier sistema operativo (Windows, MacOS, Linux).

Windows MacOS Linux

• Es accesible desde cualquier plataforma de hardware (PC, smartphone o tablet) en forma simultánea (*)

PC (Windows, MAC, Linux) Smartphone Tablet

• (*) Todos los proyectos del usuario están disponibles en la nube.

En el trabajo En cualquier lugar En casa

16 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Beneficios de la selección

Todos los proyectos de su cuenta de usuario


Con el nuevo Hi-ToolKit for Business, el usuario tiene todos sus proyectos en su cuenta, disponibles desde cualquier lugar.
El usuario puede:
• Crear un nuevo proyecto
• Editar un proyecto
• Copiar un proyecto
• Exportar un proyecto

2
• Importar un proyecto
• Borrar un proyecto
• Ver las unidades seleccionadas en un proyecto
• Imprimir un informe de un proyecto

Configuración fácil de usar


La pantalla "Mis preferencias" está compuesta de distintas opciones para definir varios ajustes que aplicarán a todos los
proyectos de Hi-ToolKit for Business.
"Mis preferencias" se divide en dos partes:
• Preferencias de la instalación: todas las opciones relacionadas con la instalación, como la configuración energética.
• Preferencias del usuario: todas las opciones relacionadas con los ajustes del usuario, como el cambio de las
unidades de medida, el idioma del software u otras.

17 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Beneficios de la selección

Creación de proyectos rápida y fácil


En solo seis pasos, el usuario puede crear el informe de las unidades seleccionadas para la instalación. El usuario
puede ver en todo momento el grado de avance del proyecto en el menú del lateral de la pantalla.
Grado de avance
del proyecto

Datos del proyecto Etapa 1 Define la información del nuevo proyecto y del cliente.

Define los criterios de la instalación: composición del sistema,


Instalación Etapa 2 parámetros de instalación, etc.

Define los criterios de diseño: localización de la instalación,


Diseño Etapa 3 condiciones de diseño interior/exterior, uso de marcha y paro, etc.
Una vez configurado el diseño y la instalación, Hi-ToolKit calcula
Eficiencia estacional Etapa 4 el rendimiento estacional de los sistemas seleccionados.
Hi-ToolKit genera información adicional en forma de diferentes
Resultados y gráficas Etapa 5 tipos de gráficos.

Informe Etapa 6 El usuario puede imprimir un informe.

Comparación y selección exhaustiva


Hi-ToolKit puede comparar diversas unidades exteriores para un determinado grupo de unidades interiores, facilitando la
selección de la más adecuada.
Hi-ToolKit calcula, para cada sistema, el rendimiento estacional en enfriamiento y calefacción, con los costes de
funcionamiento relacionados.

18 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Beneficios de la selección

Información detallada con gráficos


Una vez seleccionado el sistema, Hi-ToolKit genera información adicional en forma de gráficos y aclaraciones:

Regulación de carga parcial de la unidad (kWh) Capacidad anual (kWh)

2
Consumo energético anual (kWh) Coste energético mensual (€)

Temperatura media ambiente exterior (ºC) Distribución anual de la temperatura por horas

Informe profesional

19 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas de la instalación

2.2 Ventajas de la instalación


2.2.1  Diseño compacto y ligero de primera clase
• El diseño compacto mejora, en gran medida, la flexibilidad de la instalación.
La instalación resulta más fácil y flexible por el tamaño compacto y ligero de las unidades exteriores.

168 kg ¡Diseño
compacto y ligero!

Tipo side-flow (28,0 kW)

• Con una anchura de tan solo 390 mm, la unidad SET FREE FSNM se puede instalar en el descansillo de la escalera
o en el balcón de cada planta.

El sistema de tipo
front-flow permite
la instalación en
un balcón.

20 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas de la instalación

• El sistema tipo front-flow permite la instalación debajo de los aleros con lo que logra optimizar el espacio.

2
Balcón Descansillo de la escalera Debajo de los aleros del balcón
exterior

2.2.2  Mayor comodidad en la entrega e instalación


• La ligereza y el tamaño compacto de la unidad SET FREE FSNM permiten que se pueda transportar fácilmente en
un ascensor incluso en una zona urbana pequeña.
• No hace falta una grúa

• La unidad se suministra en una sola entrega y puede utilizar el ascensor.

Un cuerpo ligero y compacto facilita la renovación

21 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas de la instalación

2.2.3  Flexibilidad de instalación ampliada

 Instalación flexible
Diseño e instalación flexibles en esta unidad compacta.
• Número máximo de unidades interiores conectables: 10 unidades
• Capacidad mínima de la unidad interior conectable: 0,8 CV (*1)
(Ratio de capacidad combinada: 50-130%
(*1): Si solo se conectan unidades interiores de 0,8 o 1,0 CV, el número máximo recomendado de unidades conectables
es 8. Si conectan más de 8 unidades puede haber corrientes de aire frío durante el funcionamiento con calefacción.
• Longitud total de la tubería: 250 m (Longitud máxima de las tuberías: 100 m)

Longitud máxima de la
tubería: 100m Longitud total de
(Longitud equivalente de las la tubería: 250m
tuberías: 120m)

Longitud máx. de la tubería


entre la UI y la UE
UE más alta: 40m Máx. de unidades
UE más baja: 30m interiores conectables:
10 unidades
(Capacidad mín.
de la unidad interior
conectable: 0,8 CV)

Longitud máx. de la tubería


entre la 1ª bifurcación y
cada UI: 40m

Longitud máx. de la tubería


Longitud máx. de la tubería
entre cada unidad interior: 15m
entre el multi-kit y cada UI: 15m

22 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas de la instalación

 Instalación flexible. Multi-kits y distribuidores


Capacidad para establecer sistemas de aire acondicionado para distintos requisitos. Si la unidad exterior se instala
en una posición más elevada que las unidades interiores, la longitud máxima de las tuberías es de 100 metros y la
distancia máxima entre la unidad exterior y las interiores, 40 metros.
Si la unidad exterior se instala en una posición inferior que las unidades interiores, la distancia máxima entre la unidad
exterior y las interiores es de 30 metros. La distancia máxima entre cada unidad interior es de 15 metros, lo que equivale
a una altura de 4 pisos.
Hitachi proporciona todos los accesorios necesarios para el montaje del sistema de tuberías, como multi-kits y

2
distribuidores. Se pueden realizar instalaciones híbridas entre multi-kits y distribuidores, lo que flexibiliza la instalación y
simplifica en gran medida los problemas que puede crear el uso de un sistema rígido.

Sistema de distribuidor Sistema multi-kit

Sistema híbrido

? N O TA
Para información adicional relacionada con los kits para conexiones múltiples que ofrece Hitachi, consulte el capítulo “9. Instalación de
las tuberías y carga de refrigerante”.

 Control de capacidad múltiple


Para que las unidades interiores funcionen de forma más eficaz, se gestiona en cada momento el volumen de flujo de
refrigerante más apropiado según el número de unidades interiores en funcionamiento.
Al detectar la diferencia de temperatura del aire entre la entrada y la salida de la unidad interior, se controla la apertura
de la válvula de expansión electrónica para proporcionar el volumen de refrigerante más adecuado. Todas las unidades
pueden funcionar según sus condiciones de funcionamiento particulares.
El nuevo método de control admite una diferencia de altura entre unidades interiores de hasta 15 metros (unas 4 plantas
de altura), dando como resultado una flexibilidad de instalación mejorada.

23 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas de la instalación

2.2.4  Instalación eléctrica fácil y flexible

 Correspondiente al sistema H-LINK II


Estas unidades exteriores de la serie SET FREE FSNM corresponden al nuevo sistema de transmisión H-LINK II,
mejorado a partir del actual sistema H-LINK. Un solo dispositivo de control central puede controlar hasta 64 sistemas
de refrigerante y hasta 160 unidades interiores, siempre que todos los equipos (dispositivo de control central, unidades
interiores, mando a distancia) del mismo sistema de transmisión correspondan al mismo H-LINK II.

Ejemplo
Unidad exterior
Cableado de control (Máx. 64
sistemas de
refrigerante)

Unidad interior
Dispositivo de control central (Máx. 160
(1 unidad)* unidades)

* Este ejemplo muestra un caso en el que el dispositivo de control central, las unidades interiores y el
mando a distancia corresponden al sistema H-LINK II

? N O TA
• El uso del sistema H-LINK II requiere el ajuste de los conmutadores DIP. Si no se ajustan correctamente, puede generarse una alarma
debido al un fallo de transmisión.
• La longitud total del cableado para los controladores centrales e individuales se puede ampliar hasta 500 m. Utilizando un cable
alargador de 2 pins para PRC‑(10/15/20/30)E1 puede ampliar hasta más de 30 m su longitud. Si la longitud total del cableado es
inferior a 30 m., podrá utilizar cable normal (0,3 mm²).
• La longitud máxima del cableado eléctrico de la línea H-LINK se puede ampliar de 1.000 a 5.000 metros con hasta cuatro dispositivos
PSC-5HR. Cada PSC‑5HR permite una extensión de cable H-LINK adicional de 1.000 metros.
• El sistema H-LINK II ofrece una excelente flexibilidad para el diseño del sistema, la instalación es sencilla y el coste total es reducido.
Además se pueden controlar de forma centralizada conectando los sistemas de control de la climatización de edificios, CSNET WEB
o CSNET Manager, que pueden controlar instalaciones con gran cantidad de unidades interiores distribuidas en varias plantas que
deben ser controladas por separado:
-- El CSNET WEB es una buena opción en caso de que exista un ordenador en la instalación con control centralizado. En este
caso, conectando el PSC-A160WEB1, se puede tener acceso a todos los parámetros de la instalación desde el ordenador.
-- El CSNET Manager es una buena solución cuando no se dispone de un ordenador en la instalación con control centralizado.
En este caso, con su gateway H-LINK (HC-A64NET), todos los parámetros de la instalación pueden ser fácilmente accesibles
desde la pantalla táctil.
• La instalación se puede controlar también por Internet con el CSNET WEB o el CSNET Manager.

 Comparar con el sistema H-LINK


Elemento H-LINK H-LINK ll
Número máximo de grupos / sistemas de refrigerante 16 64
Intervalo de ajuste de la dirección de unidades interiores /
De 0 a 15 De 0 a 63
Grupo de refrigerante
Número máximo de unidades interiores / sistema 128 160
Cantidad total de dispositivos en el mismo H-LINK 145 200
Longitud máx. del cableado Total 1.000m (5.000m*)
*: En caso de que se usen cuatro unidades de PSC-5HR.

24 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas de la instalación

 La mezcla de H-LINK y H-LINK II


Los modelos correspondientes de H-LINK II se pueden mezclar con los modelos correspondientes de H-LINK en el
mismo sistema sin ningún adaptador.

Unidad exterior Un sistema H-LINK II


Sistema de control
Unidad interior Unidad exterior (Nº del grupo de refrigerante) Unidad interior
H-LINK ll 64 160
H-LINK ll
H-LINK ll / H-LINK Mixto 64 *1) 128
H-LINK ll 16 128

2
H-LINK
H-LINK ll / H-LINK Mixto 16 128
• *1) En un sistema H-LINK pueden estar disponibles un máximo de 16 grupos de refrigerante bajo las siguientes condiciones:
• * La unidad exterior correspondiente al H-LINK
• * La unidad exterior correspondiente al H-LINK II está conectada a una unidad interior correspondiente al H-LINK.
• Dependiendo de la capacidad de la unidad exterior se pueden conectar 17 unidades interiores a una unidad exterior. En ese caso,
son necesarios dos grupos de refrigerante para una unidad exterior.
• *2) Consulte la página siguiente para la función de control cuando se utilicen modelos correspondientes al H-LINK II y al H-LINK.

Unidad exterior: H-LINK Unidad exterior: H-LINK II


Unidad exterior: H-LINK II
Unidad interior: H-LINK II Unidad interior: H-LINK II
Unidad interior: H-LINK II
Configuración del sistema y H-LINK y H-LINK
Mando a distancia:
Mando a distancia: Mando a distancia:
H-LINK II y H-LINK
H-LINK II y H-LINK H-LINK II y H-LINK
Unidad exterior H-LINK
H-LINK ll H-LINK ll

Unidad interior

H-LINK ll H-LINK ll
and H-LINK H-LINK ll H-LINK ll
and H-LINK H-LINK ll H-LINK
H-LINK

Mando a distancia
A/C Meeting Room FLTR A/C Meeting Room FLTR

MODE SPEED LOUV. TEMP MODE SPEED LOUV. TEMP

A/C Meeting Room FLTR


A/C Meeting Room FLTR A/C Meeting Room FLTR
MODE SPEED LOUV. TEMP MODE SPEED LOUV. TEMP COOL COOL
MODE SPEED LOUV. TEMP HIGH HIGH
A/C Meeting Room FLTR
A/C Meeting Room FLTR A/C Meeting Room FLTR
COOL COOL COOL Motion Sensor is activated Motion Sensor is activated
MODE SPEED LOUV. TEMP MODE SPEED LOUV. TEMP HIGH HIGH
MODE SPEED LOUV. TEMP HIGH
Motion Sensor is activated Motion Sensor is activated LOUV. ADJ LOUV. ADJ
COOL COOL COOL Motion Sensor is activated
HIGH HIGH HIGH
LOUV. ADJ LOUV. ADJ
Motion Sensor is activated Motion Sensor is activated
LOUV. ADJ
Motion Sensor is activated

LOUV. ADJ LOUV. ADJ


LOUV. ADJ

OK OK ?
?
OK OK ? OK ?
?

OK OK ? OK ?
?

H-LINK H-LINK ll H-LINK ll


H-LINK H-LINK ll H-LINK ll H-LINK ll H-LINK

Margen de ajuste de grupo refrigerante *1) De 0 a 15 De 0 a 15 De 0 a 15

Margen de ajuste de dirección *1) De 0 a 15 De 0 a 15 De 0 a 15 De 0 a 15 De 0 a 15 De 0 a 63 De 0 a 15 De 0 a 15


Cruce del cableado del mando a distancia *2) X X X X X X X X
Reinicio automático de la temp. de ajuste *4) X X X
Bloqueo de funcionamiento *4) X X X
Limitación del rango de la temp. de ajuste *5) X X X
Ajuste del temporizador de encendido/apagado
X X X
(72 horas) *4)
Ajuste de la posición del panel de elevación *4) X X X X X X
Indicación de los distintos modos de
X X X X X X
funcionamiento *5)
Indicación de arranque en caliente de la unidad
X X X X X X
interior *5)
Cambio del número y de la dirección del grupo
X X X X X X
de refrigerante de la unidad interior *4)
Compresor de la unidad exterior Indicación/
X X X X X X X
Anulación de pre-calefacción *4)
Control de la temperatura interior para ahorro
X X X X X X X
energético *3)
Funcionamiento de emergencia desde el
X X X X X X X
mando a distancia *6)
*1) El rango de ajuste del grupo de refrigerante y de la dirección es de 0 a 15 si se usa el controlador central correspondiente de H-LINK.
*2) Solo para el inverter UTOPIA en la unidad interior con funcionamiento simultáneo.
*3) Solo para el inverter UTOPIA.
*4) Estas funciones solo se pueden ajustar con un mando a distancia cableado PC-ARFPE.
*5) Estas funciones solo se pueden ajustar con un mando a distancia cableado PC-ARFPE y con un mando a distancia de tamaño medio
(PC-ARH).
*6) Esta función no está disponible dependiendo del tipo de unidad exterior.

25 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas de puesta en marcha

2.2.5  Conexión de control fácil y flexible (estación central, interfaz BMS, CSNET WEB)

 Sin polaridad
Gracias a la ausencia de polaridad, se puede conectar cualquier control centralizado directamente al bus H-LINK II, lo
que significa que no son necesarias líneas especiales.

 Auto Configuración
Aparte de la configuración personalizada, los sistemas de control también son autoconfigurables; por ejemplo, son
capaces de interpretar el tipo de aparato al que están conectados y detectar el tipo de unidad interior o su potencia.

2.3 Ventajas de puesta en marcha


2.3.1  Prueba automática de puesta en marcha

 Prueba de funcionamiento
La prueba de funcionamiento automática se puede activar desde de los conmutadores DIP de la unidad exterior o
desde el mando a distancia de la unidad interior. La pantalla de 7 segmentos de la unidad exterior proporciona toda la
información necesaria para comprobar el correcto funcionamiento del sistema.
• Sistema de identificación de las unidades exteriores conectadas: Usando un mando a distancia puede confirmar la
serie a la que pertenecen las unidades exteriores operativas (por ejemplo, sencilla o múltiple).
• Identificación automática de cada unidad interior. También se pueden asignar manualmente usando el conmutador
DIP giratorio de la unidad.

 Prueba de funcionamiento desde el mando a distancia


Mediante el mando a distancia, se pueden realizar 3 operaciones.
• Autodiagnóstico: Comprobación rápida de las condiciones de funcionamiento de las unidades interiores y la exterior.
• Consulta de los datos de la memoria: si se produce una anomalía, la LCD del mando a distancia muestra un código
de alarma y guarda todos los ajustes de funcionamiento de la unidad en el instante en el que se produce el fallo, de
forma que se pueda realizar un diagnóstico rápido de la instalación.
• Ajuste de funciones opcionales: el mando a distancia permite anular la compensación de 4 grados en el modo de
calefacción y el aumento de la velocidad del ventilador entre 29 opciones posibles.
De este modo, se pueden ajustar varias unidades interiores al mismo tiempo. Además es fácil modificar la
configuración, aunque se haya completado la instalación.

 Prueba de funcionamiento desde la unidad exterior:


La PCB de la unidad exterior está equipada con una pantalla de 7 segmentos que, dependiendo de la posición de los
PSW muestra los siguientes parámetros de forma secuencial
• Temperatura del aire exterior
• Temperatura del gas de descarga
• Temperatura de evaporación en el modo de calefacción
• Temperatura de condensación
• Presión de descarga
• Tiempo de funcionamiento del compresor
• Presión de aspiración
Esto permite un diagnóstico rápido y preciso de la instalación durante el funcionamiento normal o la prueba de
funcionamiento.
2.3.2  Supervisor de servicio

 Hitachi Service Tools


Hitachi también posee una potente herramienta de TI, Hitachi Service Tools. Este software puede funcionar desde
cualquier ordenador portátil mediante una interfaz conectada al bus H-LINK II, y puede recoger diversos parámetros
que influyen en el rendimiento de la unidad. Estos parámetros también se pueden supervisar en distintos formatos,
permitiendo localizar rápidamente los incidentes que tengan lugar durante la puesta en marcha.

26 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas funcionales

2.4 Ventajas funcionales


2.4.1  Ahorro energético

El rendimiento líder en la industria se obtiene mediante la incorporación de las nuevas tecnologías siguientes:

 Compresor DC Inverter de alta eficacia


• Ahorro energético mediante el DC Inverter y el nuevo mecanismo de transmisión
• Reducción del 50% del peso mediante un diseño compacto

Nuevo mecanismo de transmisión


Mecanismo de alimentación de
aceite
2
Disminución significativa de la
pérdida térmica/de la máquina.
Fiabilidad incrementada
Scroll recientemente desarrollado
para 410A. Motor del DC Inverter

Scroll original de Hitachi más Funcionamiento de alta eficacia realizado


desarrollado

 Control de equilibrio inteligente


El rendimiento es el mismo independientemente de la longitud de la tubería de refrigerante.

Temp. habitación Temp. ajustada

Con la unidad
exterior cerca
¡Rendimiento óptimo!

Con la unidad
exterior lejos
¡Rendimiento óptimo!

Detecta rápidamente la diferencia de temperatura del aire para demostrar el rendimiento adecuado.
Funcionamiento de ahorro de energía sin que se produzcan pérdidas.

Temp. habitación Temp. ajustada


La diferencia entre la
temperatura ambiente y
la temperatura ajustada
es de 5ºC

¡Rendimiento óptimo!

La diferencia entre la
temperatura ambiente y
la temperatura ajustada
es de 3ºC

¡Rendimiento óptimo!

27 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas funcionales

2.4.2  Tecnologías de ruido bajo

Motor del ventilador de DC, ventilador de flujo súper alto, protector del ventilador de la pérdida de baja presión. La
unidad exterior líder de ruido bajo se lleva a cabo mediante la aleta del nuevo modelo con poca pérdida de la presión.

Ventilador de Motores de
flujo muy alto ventilador de DC

Nueva aleta
con poca
pérdida de
presión

Rejilla de
salida de aire,
baja pérdida
de presión

 Motor de ventilador de cc
El motor del ventilador de rotación suave con escasa vibración reduce la generación de ruido.

 Ventilador de flujo muy alto


El ventilador de flujo súper alto de 544 mm de Ø reduce el ruido.
Distribución optimizada en
el ángulo de salida del aire

Distribución optimizada en
el ángulo de entrada del aire

Avance angular incrementado

28 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas funcionales

 Rejilla de salida del aire de pérdida de presión baja


La estructura acanalada sincronizada con el flujo de rotación del ventilador reduce la resistencia del aire en la rejilla de
salida del aire.

 Nueva aleta con poca pérdida de presión


La resistencia de corrientes se reduce en un 20%. Tanto el funcionamiento de gran eficacia como el bajo ruido se
satisfacen de forma simultánea.

2
Aire

 Reducción del sonido en funcionamiento nocturno


Mediante la simulación por ordenador de las turbulencias de fluidos, principal fuente de sonido no deseado, y mediante
la observación visual del caudal de fluido, se ha podido analizar completamente el sonido.
Mejorando la estructura del armario y la forma del ventilador, y adoptando un inversor y material nuevo, se ha podido
reducir el sonido.
Se ha obtenido un diseño de funcionamiento silencioso respetuoso con el medio ambiente.

29 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas funcionales

2.4.3  Nuevas funciones

 Control del consumo eléctrico automático


Una función de solicitud automática desarrollada recientemente, ha mejorado en gran medida los efectos de ahorro
energético. Dado que la corriente se detecta de modo automática y el control del consumo eléctrico se realiza de forma
automática, no es necesaria ninguna tarea de cableado de señales. También está disponible el control del consumo
eléctrico convencional usando señales de solicitud, y puede seleccionar diversas operaciones según sea necesario.

Se limita un consumo energético


Consumo energético

superior al margen de capacidades


ajustado

Ajuste de potencia

La eficacia máxima está Seleccionable entre 100%, 80%, 70% y


asegurada dentro del margen 60% del consumo de potencia nominal
de ajuste de energía para el funcionamiento con enfriamiento.

Mañana Día Noche

 Modo onda
El modo onda está equipado para encender o apagar el control del consumo eléctrico alternativamente a intervalos de
unos 20 o 10 minutos. Mientras se ahorra energía sin fallos, los cambios de temperatura también se minimizan para
mantener una temperatura ambiente confortable.
¡Este es el efecto
de la solicitud!
[ Sin control de consumo eléctrico ] [Control
[ del consumo eléctrico automático]
]
Promedio de consumo energético
Promedio de consumo energético
Consumo Consumo
energético energético
Valor de potencia ajustada Valor de potencia ajustada
10 10 10 10 10 10 10 10 min. 10 10 10 10 10 10 10 10 min.

 Protección de corrientes frías para funcionamiento con enfriamiento


Esta función sirve para proteger la corriente fría durante el funcionamiento con enfriamiento en una temporada
intermedia o con una temperatura baja. Esta función proporciona una acondicionamiento de aire confortable.

30 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas funcionales

2.4.4  Margen de temperaturas

 Amplio margen de funcionamiento


La unidad SET FREE FSNM puede operar bajo una amplia gama de condiciones de aire exterior, lo cual amplía la
flexibilidad del espacio de instalación y el entorno climático.
La optimización del ciclo de refrigerante permite trabajar con temperaturas de hasta -5ºC en el modo de enfriamiento.

2
Enfriamiento (DB)

Calefacción (WB)

 Control preciso con el inversor de amplio margen


La velocidad del compresor de la unidad exterior de la serie FSNM está controlada dentro de un amplio margen,
comprendido entre 20 y 100 Hz. Con ello se obtiene un funcionamiento uniforme sin necesidad de utilizar el control de
encendido/apagado de forma frecuente. Gracias a este nuevo control de capacidad de amplio rango se pueden cubrir
no sólo las necesidades de los espacios grandes, sino también de los más reducidos, por ejemplo, salas de espera
o de gestión. El funcionamiento en modo de descarche se realiza rápidamente gracias a una elevada velocidad del
compresor.

Unidad exterior de 10 CV

31 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas funcionales

2.4.5  Control electrónico de la capacidad

La capacidad de la unidad exterior de 8 a 12 CV se controla de forma continua a través del inversor desde el 20%
hasta el 100%. Este amplio margen de funcionamiento se ha obtenido gracias al aumento de la fuerza del eje y a la
circulación de aceite de alta presión en el compresor scroll. Por todo ello, resulta muy sencillo abastecer un sistema de
aire acondicionado en el que la carga de calor cambia mucho a lo largo del día.
La capacidad de cada unidad interior se controla también mediante la detección de las temperaturas de entrada y salida
gracias a una válvula de expansión electrónica. Por lo tanto, es posible refrigerar incluso habitaciones pequeñas con
unidades interiores de hasta 0,8 CV sin necesidad de utilizar el tedioso encendido/apagado, dando como resultado un
cómodo sistema de aire acondicionado.

Control Inverter de la UE de 10 CV
100Hz→20Hz (20%) Amplio
margen de funcionamiento
1. Resistencia del eje mejorada
2. Circulación de aceite de alta presión
Control capacidad del ciclo refrig.
Unidad exterior 10% (8 CV)
8% (10 CV)
RAS-10FSNM 7% (12 CV)

RCI-1.5FSN2 RCI-2.5FSN2 RCI-2.5FSN2 RCI-2.5FSN2


RPI-0.8FSN2 (Recepción) (Oficina) (Oficina) 2 (Oficina)
(Sala de dirección) STOP STOP STOP STOP
Menos encendidos
y apagados para El control de capacidad (10%: 8 CV, 8%: 10 CV, 7%: 12 CV de la capacidad
garantizar el confort de la unidad exterior) de la sala de dirección sigue siendo posible.

• Funcionamiento individual en unidades interiores de 0,8 CV mínimo:


Las válvulas de expansión electrónicas instaladas, no solo en la unidad exterior, sino también en cada unidad
interior, controlan el caudal de refrigerante.

• Control del funcionamiento con deshumidificación:


Este sistema, que combina el control de la velocidad del inversor con el control del volumen de aire interno,
proporciona una eficaz deshumidificación sin realizar prácticamente ningún cambio en la temperatura de la
habitación.

Aire acondicionado Deshumidificación Aire acondicionado


Temperatura de la
habitación
Humedad (%)

32 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Ventajas de mantenimiento

2.5 Ventajas de mantenimiento


• Mantenimiento mínimo
Fieles a la filosofía habitual de Hitachi, las unidades SET FREE se han diseñado para garantizar gran fiabilidad y
solidez a fin de reducir al mínimo las tareas de mantenimiento.
• Fácil acceso
Es fácil acceder a todos los componentes de los sistemas SET FREE. Puede acceder a todos los componentes de la
unidad para llevar a cabo las tareas necesarias a través de una cubierta simple.

2
Todo el sistema está diseñado para facilitar y simplificar el mantenimiento.
• Información sobre alarmas en el mando a distancia a través de la PCB
Las señales de alarma se pueden recibir a través del mando a distancia (individual o centralizo), a través del
software CSNET WEB o CSNET Manager, o mediante la PCB de la unidad exterior, facilitando así los trabajos de
mantenimiento.
• Códigos de alarma
Las alarmas se agrupan por elementos dentro del sistema para facilitar el mantenimiento y optimizar el trabajo del
operario.
• Alarma SMS
Las señales de alarma también se pueden recibir a través de un simple SMS especificando el ciclo afectado y el
código de alarma, permitiendo detectar los incidentes y resolverlos más rápidamente.

2.5.1  Disponibilidad de herramientas de mantenimiento

Todas las funciones del Service Tools de Hitachi se pueden utilizar para el mantenimiento de las unidades, tanto
preventivo como correctivo, con lo que los problemas se pueden detectar y resolver inmediatamente.
El CSNET WEB y CSNET Manager también es útil para las tareas de mantenimiento.

33 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Características principales de las unidades

2.6 Características principales de las unidades


2.6.1  Reducción de la capacidad total de la unidad exterior

El sistema SET FREE FSNM permite reducir la capacidad de la unidad exterior hasta en un 30% si se compara con los
sistemas split de aire acondicionado actuales. El diagrama muestra un edificio típico con una carga de calor de pico
matutino en la zona este equivalente a una unidad de 6 CV.
Por la tarde, se produce un pico en la zona oeste equivalente a una unidad de 7 CV.
Por lo tanto, un sistema convencional necesitaría una instalación de 6 CV + 7 CV = 13 CV. La carga máxima simultánea
en todo el edificio se produce a mediodía y equivale a una capacidad de 10 CV. Por lo tanto, se puede seleccionar el
sistema SET FREE FSNM de 10 CV. Esta capacidad se puede dirigir a la zona este u oeste según lo dictado por los
controles del sistema.

13-10
Ahorro en la instalación = x 100 = 23%
13

 Ejemplo de sistema de aire acondicionado para un edificio


Carga en la zona este Carga total

Carga en la
zona oeste

Carga

 Tiempo

Puesto que se obtiene un funcionamiento parcial gracias a varias unidades interiores, la capacidad de la unidad exterior
se puede seleccionar en función de la carga total del edificio en un día.
La serie Set Free FSNM suministra refrigerante dependiendo de la la carga de cada habitación.

Zona este Área oeste


(6 CV) (7 CV)
Capacidad de las unidades interiores (CV equivalentes)

La potencia total combinada se calcula con la siguiente fórmula:


Potencia total combinada = (potencia total de la unidad interior / potencia de la unidad exterior) x 100 = (13 CV / 10 CV)
x 100 = 130%

Potencia total de la unidad interior 13 CV


Potencia total combinada = x 100 = x 100 = 130%
Potencia de la unidad exterior 10 CV

34 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Características principales de las unidades

2.6.2  Compresor DC Inverter de alta eficacia

5% de aumento
Aspiración del índice de
rendimiento
Recubrimiento
asimétrico

Cojinete de
rodillos

2
Tubería de
Descarga retorno del
aceite
Estructura
del cojinete
Motor síncrono de bolas
inferior

UEVO
NNEW All Rights Reserved, Copyright © 2007 Hitachi, Ltd.

Asymmetric Scroll Lap

AISLAR

NUEVO
Cojinete inferior
AISLAR
ALTA FIABILIDAD
Disminución de la
carga del cojinete ALTO RENDIMIENTO
Minimización de la Disminución de las pérdidas
oscilación del eje en la entrada
Disminución de pérdidas
Tubería de por fugas.
Disminución de las pérdidas
retorno del aceite por sobrecalentamiento
NUEVO
All Rights Reserved, Copyright © 2007 Hitachi, Ltd.

35 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Características principales de las unidades

 Bajo nivel de ruido


• Ruido y vibración
1 El compresor scroll presenta niveles bajos de sonido y vibración puesto que los puntos de compresión están
distribuidos uniformemente por la carrera de compresión, dando lugar a una curva muy plana de par de giro.
2 El número mínimo de componentes utilizados, junto con un revestimiento de alta presión que actúa como un
silenciador, contribuye a reducir incluso más el ruido.
3 Puesto que el patrón de ruido es sonido de alta frecuencia, es fácil de reducir a un nivel muy bajo utilizando un
revestimiento aislante.
4 Reducción del ruido electromagnético del compresor.

Forma de rotor optimizada

Electromagnética

Para el motor del


compresor antes de
cambiar el rotor
Ruido

Frecuencia (Hz)

Reducción del ruido


electromagnético

Para el motor del compresor


Ruido

después de cambiar el rotor

Frecuencia (Hz)

• Protección contra el retorno de líquido


Si el compresor está parado, el scroll móvil descansa en la carcasa. Cuando el compresor se pone en marcha, aumenta
la presión de la cámara situada bajo el scroll a través de dos orificios de purga de la sección de media presión de la
carrera de compresión. Esta presión empuja entonces el scroll hacia arriba y contra el armario y sella la cámara de
compresión. Si el líquido vuelve al compresor, el incremento de presión resultante obliga al scroll a bajar rompiendo
el sello y permitiendo que el líquido vuelva de nuevo al interior del compresor donde hervirá debido a las altas
temperaturas.

 Eficiencia
• Compresor de CC con imán de neodimio.
El uso de un compresor de CC mejora el rendimiento en torno a 30-40 Hz durante largos periodos de funcionamiento
del compresor inverter. Además, para eliminar la interferencia de ruido electromagnético y lograr un bajo nivel sonoro, el
rotor se ha dividido en dos piezas y se ha desplazado el polo eléctrico.
Ha habido mejoras significativas en las características de baja velocidad, lo que afecta a los costes de funcionamiento
anuales.
Forma del rotor Imán de
Motor de gran eficiencia (%)

optimizada neodimio
Motor de CC

Motor de CA
Reducción
del ruido Aumento
electromagnético de la
característico del eficiencia en
compresor de CC. todo el rango
de
rpm

Rotor del compresor


rpm

36 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Características principales de las unidades

 Control de Inverter
El Inverter controla las velocidades del compresor de 30 Hz a 115 Hz, alcanzando rápidamente la temperatura ajustada
y manteniendo un funcionamiento estable que ahorra energía, reduciendo así el ruido ya que el compresor no está
funcionando continuamente.
Diagrama de funcionamiento (en modo de calefacción):
Temperatura de ajuste
Temperatura de la

SET FREE

2
habitación

Aparato con
velocidad constante

Tiempo
• En el caso de Set-Free
Alcanza rápidamente la temperatura ajustada con potencia alta y luego mantiene un funcionamiento estable que
contribuye al ahorro energético.
• En el caso de otros dispositivos de velocidad constante:
Alcanza lentamente la temperatura ajustada y después se enciende y se apaga continuamente para mantener la
temperatura, causando un funcionamiento poco rentable y un derroche energético.
Funcionamiento a alta Funcionamiento con
potencia ahorro energético

Dispositivo de
velocidad constante

SET FREE
En el caso de un aparato existente con velocidad constante,
el encendido y apagado continuos desperdicia energía.
Tiempo

2.6.3  Características mejoradas del motor del ventilador para la serie FSNM

 Motor del ventilador de CC de excelente eficiencia


El motor del ventilador de CC mejora significativamente la eficiencia en comparación con los productos convencionales
que disponen de un motor de CA. Por otra parte, las ráfagas de aire se han reducido mediante el control de la velocidad
de rotación del ventilador. Ofrece un funcionamiento estable frente a fuertes vientos de cara de unos 10m/s en el frontal
de la unidad exterior.

Motor de CC
Eficacia incrementada en un 40%
Eficacia del motor (%)

(consumo energético del motor


reducido a la mitad)

Motor de CA

Revoluciones por minuto (rpm)

• Concepto de control de velocidad PWM (modulación por ancho de pulsos)


El elemento de conmutación (un MOSFET de potencia) se conmuta a una frecuencia de varias decenas de kHz. Esto
controla el régimen de encendido/apagado por ciclo y modifica la tensión aplicada al motor del ventilador para controlar
la velocidad de rotación.

37 TCES0059 rev.2 - 06/2016


2 Características y ventajas

Características principales de las unidades

• Nueva hélice del ventilador


Hitachi utiliza alta tecnología para lograr el nivel más bajo de ruido. El nuevo ventilador tiene tres palas en lugar
de cuatro. Ha sido diseñado con un cuerpo más pequeño que el de los ventiladores tradicionales, y consigue unos
resultados sorprendentes, con una reducción sonora de hasta 4dB (A).

 Amplia variedad de posibilidades de funcionamiento


El empleo de estos equipos junto con CSNET WEB o CSNET Manager puede aumentar, todavía más, el rendimiento de
estas instalaciones con las siguientes características:
• Con un programa que evita el funcionamiento continuo en habitaciones con usuarios y permite la calefacción y el
enfriamiento justo antes de ocupar las habitaciones.
• Limitando las temperaturas de ajuste; los equipos no funcionan a máxima capacidad cuando el confort no lo
requiere.
• Bloqueo de funciones desde el dispositivo de control central, que evita un uso incorrecto o ineficaz de las unidades.
• Todas estas y muchas más funciones suponen optimizar el uso de la instalación como un todo.
• Y vale la pena recordar que debido al amplio rango de unidades interiores, siempre puede encontrar la unidad con la
potencia y el tipo de instalación que mejor se ajuste a sus necesidades.

38 TCES0059 rev.2 - 06/2016


3 Datos generales

3. Datos generales

Índice

3.1 Datos generales..................................................................................................................................... 40


3.1.1  Condiciones generales................................................................................................................................... 40
3.1.2 RAS-(8-12)FSNM........................................................................................................................................... 41

3
3.2 Datos de los componentes..................................................................................................................... 42

3.3 Datos eléctricos...................................................................................................................................... 42

39 TCES0059 rev.2 - 06/2016


3 Datos generales

Datos generales

3.1 Datos generales


3.1.1  Condiciones generales
1 Las capacidades de enfriamiento y calefacción indicadas se refieren a la unidad exterior funcionando con las
unidades interiores al 100% de su capacidad, y están basadas en la norma EN14511.

Condiciones de funcionamiento Enfriamiento Calefacción


DB 27,0ºC 20,0ºC
Temperatura del aire de entrada interior
WB 19,0ºC —
DB 35,0ºC 7,0ºC
Temperatura del aire de entrada exterior
WB — 6,0ºC
DB: bulbo seco; WB: bulbo húmedo.
Longitud de las tuberías: 5 m; altura de las tuberías: 0 m

2 Las capacidades, los EER/COP y los niveles de potencia acústica están certificados por EUROVENT, siguiendo
estándares EUROVENT para el programa de certificación de sistemas VRF.
3 Para el cálculo de la eficiencia de enfriamiento y calefacción no se tiene en cuenta la potencia de entrada de la
unidad interior.
4 El nivel de presión acústica se ha medido basa en las siguientes condiciones:
a. 1 m desde la tapa de servicio de la unidad y 1,5 m desde el nivel del suelo.
b. La información proporcionada corresponde al modo de enfriamiento. En el modo de calefacción, el nivel de
presión acústica aumenta de 1 a 2 dB(A).
c. Los datos indicados se han medido en una cámara anecoica, por lo que el sonido reflejado debe ser tenido en
cuenta para la instalación.
d. La tensión de la fuente de alimentación es de 400V.
e. La información proporcionada corresponde al modo de enfriamiento. En el modo de calefacción, el nivel de
presión acústica aumenta 2 dB(A).
5 En el caso del modo nocturno, el nivel de ruido disminuye 5 dB (A).
6 Los niveles de potencia acústica se han medido en una sala reverberante según la norma EN12102. Las condiciones
ambientales usadas son aquellas especificadas en EN14511 para pruebas de rendimiento.

40 TCES0059 rev.2 - 06/2016


3 Datos generales

Datos generales

3.1.2  RAS-(8-12)FSNM

MODELO RAS RAS-8FSNM RAS-10FSNM RAS-12FSNM


Alimentación eléctrica 3N~ 380/415V, 50Hz
Capacidad de enfriamiento nominal
kW 22,4 28,0 33,5
(Mín./Nom./Máx.)
Capacidad de calefacción nominal
kW 25,0 31,5 37,5
(Mín./Nom./Máx.)
Eficiencia energética en modo enfriamiento
3,56 3,21 2,70
(EER)
Coeficiente de eficiencia energética en
4,24 4,04 3,79
modo de calefacción (COP)
Color (código Munsell) - Gris natural (1.0Y 8.5/0.5)
Nivel de presión acústica frío/calor
(modo nocturno)
Nivel de potencia acústica
dB(A)

dB(A)
53/55

71
56/58

74
59/61

77
3
Alto mm 1.650 1.650 1.650
Medidas exteriores Ancho mm 1.100 1.100 1.100
Fondo mm 390 390 390
Peso neto Kg 170 170 173
Refrigerante - R410A
Control de flujo - Válvula de expansión controlada por microordenador
Compresor - Hermético (scroll)
Cantidad - 1 1 1
Potencia kW 4,80 6,00 7,20
Intercambiador de calor Tubo de aletas cruzadas de paso múltiple
Ventilador de la unidad exterior - Ventilador de hélice
Cantidad - 2 2 2
Caudal de aire m³/min 121 150 163
Potencia (polos) W 170(8)+101(6) 170(8)+115(6) 170(8)+183(6)
Conexión de las tuberías de refrigerante Conexión con tuerca cónica (suministrada de fábrica)
mm ø9,52 ø12,70 ø12,70
Tubería de líquido
(pulg.) (3/8) (1/2) (1/2)
Tamaño
mm ø19,05 ø22,20 ø25,40-ø28,60
Tubería de gas
(pulg.) (3/4) (7/8) (1)-(1-1/8)
Carga de refrigerante Kg 5,0 5,5 6,5
Consumo máximo de energía eléctrica A 14,0 18,0 23,0
Medidas de embalaje m³ 0,71 0,71 0,71

41 TCES0059 rev.2 - 06/2016


3 Datos generales

Datos de los componentes

3.2 Datos de los componentes

Modelo RAS RAS-8FSNM RAS-10FSNM RAS-12FSNM


Tipo - Tubo de aletas cruzadas de paso múltiple
Material - Tubería de cobre
diámetro exterior Ø mm 7,0 7,0 7,0
Intercambiador de calor

Tuberías Filas - 2 2 2
Número de tubos/
- 80 80 80
bobina
Material - Aluminio
Aleta
Inclinación mm 1,9 1,9 1,9
Presión de funcionamiento máxima MPa 4,15 4,15 4,15
Superficie total frontal m² 1,86 1,86 1,86
Número de bobinas/unidad - 2 2 2
Tipo - Ventilador de hélice
Numero/unidad - 2 2 2
diámetro exterior mm 544 544 544
Ventilación
Unidad de ventilación

Revoluciones rpm 399+745 630+772 630+871


Caudal de aire
m /min
3
121 150 163
nominal/ventilador
Tipo - Consola antigoteo
Método de arranque - PSC (condensador permanente)
Motor del ventilador
Motor W 170+120 170+170 170+200
(salida)
Cantidad - 2 2 2
Clase de aislamiento - E E E
Tipo Inverter - E656DHD
Tipo de compresor - Hermético Scroll
Resistencia Descarga MPa 4,20
Compresor

de presión Aspiración MPa 2,21


Método de arranque - Accionado por Inverter
Polos - 4
Motor Clase de aislamiento - E
Tipo de aceite FVC68D
Cantidad de carga 1,9

3.3 Datos eléctricos

Alimentación
Tensión aplicable Motores del compressor y del ventilador
principal
IPT Cor.
Funcionamiento con Funcionamiento con
Modelo U U Máx. Máx.
U f STC enfriamiento calefacción
PH máx. mín. [kW] [A]
[V] [Hz] [A] IPT RNC IPT RNC
[V] [V]
[KW] [A] [KW] [A]
RAS-8FSNM 8/8 6,30 10,3/9,4 5,90 9,6/8,8 8,2 14
RAS-10FSNM 380/415 3N~ 50 457 342 8/8 8,30 13,6/12,4 7,80 12,7/11,7 10,8 18
RAS-12FSNM 8/8 10,70 17,3/15,8 9,90 16,0/14,7 13,9 23
U: Tensión de alimentación
PH: Fase (φ)
? N O TA
1. Los datos de rendimiento anteriores se basan en una combinación al 100%
f: Frecuencia de la capacidad de las unidades interiores y la frecuencia de funcionamiento
nominal del compresor.
STC: Corriente de arranque
2. Los datos de rendimiento anteriores se basan en una longitud equivalente de
RNC: Corriente de funcionamiento tuberías de 5 m y una altura de 0 m.
IPT: Potencia de entrada total 3. El compresor se pone en marcha por un inversor, lo que genera una corriente
de arranque extremadamente baja.
Cor.: Corriente

42 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

4. Capacidades y datos de selección

Índice

4.1 Procedimiento de selección del sistema de la Serie SET-FREE FSNM................................................ 44


4.1.1  Posibilidades del sistema SET-FREE............................................................................................................ 44
4.1.2  Parámetros de selección................................................................................................................................ 46
4.1.3  Procedimiento de selección........................................................................................................................... 46

4.2 Tablas de capacidad de enfriamiento..................................................................................................... 53


4.2.1  Curva de capacidad de enfriamiento.............................................................................................................. 53
4.2.2  Tablas de capacidad de enfriamiento nominal............................................................................................... 53
4.2.3  Tablas de capacidad de enfriamiento según potencia total de unidades interiores combinadas................... 54 4
4.3 Tablas de capacidad de calefacción...................................................................................................... 59
4.3.1  Curva de capacidad de calefacción............................................................................................................... 59
4.3.2  Tablas de capacidad de calefacción nominal................................................................................................. 60
4.3.3  Tablas de capacidad de calefacción según potencia total de unidades interiores combinadas..................... 60

4.4 Factores de corrección........................................................................................................................... 66


4.4.1  Factor de corrección de la longitud de las tuberías........................................................................................ 66
4.4.2  Factor de corrección de descarche................................................................................................................ 68

43 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Procedimiento de selección del sistema de la Serie SET-FREE FSNM

4.1 Procedimiento de selección del sistema de la Serie SET-FREE FSNM


El siguiente procedimiento es un ejemplo de cómo seleccionar las unidades del sistema e indica cómo usar todos los
parámetros indicados en este capítulo.
Considerando la disposición del edificio, la posible ubicación de las unidades interiores y la distribución del flujo de aire,
seleccione las características de la unidad que proporcionan la máxima eficiencia y confort. Decida una posición para la
unidad exterior que facilite las tareas de mantenimiento y servicio, así como la instalación de la tubería de refrigerante.
4.1.1  Posibilidades del sistema SET-FREE

Antes de seleccionar la unidad exterior debe tener en cuenta algunas de las importantes posibilidades que ofrece el
sistema SET FREE.

 Reducción de la capacidad total de la unidad exterior


En primer lugar, se considerará la opción de la “Reducción de la capacidad total de la unidad exterior como resultado del
gran rango disponible para el control de la capacidad de funcionamiento” de los sistemas SET FREE, que permite elegir
en la unidad exterior una potencia total máxima combinada del 130% y una potencia total mínima combinada del 50%
mediante la combinación de unidades interiores, en comparación con la capacidad nominal de la unidad exterior. En la
siguiente tabla se indican las posibilidades de la serie FSNM:

Unidad interior
Restricciones de la
Número máximo de
unidad RPK-FSNH3M
unidades interiores
Unidad Capacidad Capacidad (número máximo de Capacidad de Gama de
conectables (la suma
exterior mínima de la máxima de la unidades interiores funcionamiento capacidades
de unidades RPK
combinación combinación RPK-FSNH3M individual de la
instaladas y otras
(CV) (CV) combinables con el mínima (CV) combinación
unidades interiores)
kit de la válvula de
(*)
expansión EV-1.5N1)
RAS-8FSNM 4,0 10,4
del 50% al
RAS-10FSNM 5,0 13,0 10 (8) 8 0,8
130%
RAS-12FSNM 6,0 13,2

? N O TA
(*) Entre paréntesis se indica el número máximo recomendado de unidades interiores conectables (solo para unidades interiores de 0,8 y
1,0). Si conecta más de 8, puede producirse la percepción de corrientes frías durante el funcionamiento con calefacción.

Este concepto permite que la unidad exterior tenga hasta un 30% menos de capacidad en comparación con otros
sistemas de aire acondicionado, en caso de una potencia total combinada del 130%. Esto se muestra en el siguiente
ejemplo:

Carga en la zona este Carga total

Carga en
la zona
oeste

Carga
Zona este Zona oeste
(6CV) (7CV)
Capacidad de las unidades interiores (CV equivalentes) Tiempo

El diagrama muestra un edificio típico con una carga de calor de pico matutino en la zona este equivalente a una unidad
de 6 CV. Por la tarde, se produce un pico en la zona oeste equivalente a una unidad de 7 CV.
Por lo tanto, un sistema convencional necesitaría una instalación de 6 CV + 7 CV = 13 CV. La carga máxima simultánea
en todo el edificio se produce a mediodía y equivale a una capacidad de 10 CV. Se puede seleccionar el sistema SET
FREE FSNM de 10 CV. Esta capacidad se puede dirigir a la zona este u oeste según lo dictado por los controles del
sistema.

? N O TA
Las cargas máximas requeridas de las zonas este y oeste no deben ser simultáneas.

44 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Procedimiento de selección del sistema de la Serie SET-FREE FSNM

La potencia total combinada se calcula con la siguiente fórmula:

Potencia total de la unidad interior 13 CV


x
Potencia total combinada = x 100 = = 130 %
100
Potencia de la unidad exterior 10 CV

 Ajuste de la capacidad ajustando el conmutador DIP de las unidades interiores


En algunos casos, sería útil ajustar la capacidad de las unidades interiores con el fin de adaptar la unidad a los
requisitos de instalación reales. Esto se logra ajustando el conmutador DIP y está disponible en algunas potencias de
unidades interiores.
A continuación se muestran dos tablas con la capacidad nominal y la capacidad ajustada mediante el ajuste del
conmutador DIP de las unidades interiores.

 Capacidad nominal de las unidades interiores


Potencia
(CV)
0,8 1,0 1,5 2,0 2,5 3,0 4,0 5,0 6,0 8,0 10,0

4
Capacidad

Capacidad de enfriamiento kW 2,2 2,8 4,0 5,6 7,1 8,0 11,2 14,0 16,0 22,4 28,0
Capacidad de calefacción kW 2,5 3,2 4,8 6,3 8,5 9,0 12,5 16,0 18,0 25,0 31,5

? N O TA
La capacidad nominal de enfriamiento y calefacción es la capacidad combinada del sistema SET FREE y se basa en la norma EN14511.

Condiciones de funcionamiento Enfriamiento Calefacción


DB 27ºC 20ºC
Temperatura del aire de entrada interior
WB 19ºC -
DB 35ºC 7ºC
Temperatura del aire de entrada exterior
WB - 6ºC
Longitud de las tuberías: 5 metros; altura de la tubería: 0 metros
DB: Bulbo seco; WB: bulbo húmedo

 Capacidades ajustadas de las unidades interiores


Potencia (CV) 1,3 1,8 2,3
Capacidad variable 1,3 1,5 1,8 2,0 2,3 2,5
Capacidad de enfriamiento kW 3,8 5,2 6,7
Capacidad de calefacción kW 4,2 5,6 7,5

1,3 CV 1,5 CV 1,8 CV 2,0 CV 2,3 CV 2,5 CV


ON ON ON ON ON ON
Ajuste del conmutador DIP de la
unidad interior (DSW3)
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

Disminuido Estándar Disminuido Estándar Disminuido Estándar

45 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Procedimiento de selección del sistema de la Serie SET-FREE FSNM

4.1.2  Parámetros de selección

Para seleccionar las unidades exteriores, será necesario consultar y/o utilizar la serie de parámetros que se muestran
en las tablas y gráficos que aparecen en los distintos capítulos de este catálogo. A continuación se muestra una lista
resumen:

Para información general: capítulo “1. Información general”. Para factores de corrección: capítulo “4.4 Factores de corrección”
Para opciones del espacio operativo: capítulo “7. Dimensiones Para datos acústicos: capítulo “5. Curvas acústicas
generales”. características”
Para capacidades: capítulos “4.2 Tablas de capacidad de Para longitud de las tuberías y alturas: capítulo “9. Instalación de
enfriamiento”, “4.3 Tablas de capacidad de calefacción” las tuberías y carga de refrigerante”.

En caso de una instalación con conductos (unidad exterior con unidad interior RPI) se debe tener en cuenta el
rendimiento del ventilador para los cálculos del conducto. Las unidades RPI están diseñadas con diversos rangos de
presión estática para satisfacer todas las necesidades de instalación.

4.1.3  Procedimiento de selección

Una vez consideradas las posibilidades del sistema SET-FREE, es el momento de empezar con el procedimiento
de selección. Para ello se ha considerado una instalación formada por varias habitaciones con distintas cargas de
enfriamiento y diferentes condiciones de temperatura:

 Condiciones de diseño:
-- Condiciones de temperatura

Enfriamiento Calefacción
Entrada de aire exterior: Entrada de aire exterior:
30ºC DB 5/1ºC (DB/WB)
Entrada de aire interior: Entrada de aire interior:
28/19ºC (DB/WB) 18ºC DB

-- Cargas necesarias en la instalación (*)

Zona este Zona oeste


Elemento
Sala 1 Sala 2 Sala 3 Sala 4
Total 3,40 4,50 4,90 5,40
Carga de enfriamiento estimada kW
Sensible 2,40 3,20 3,50 3,80

Carga de calefacción estimada Total kW 3,80 5,10 5,50 6,10

? N O TA
• (*) En este ejemplo, las cargas máximas requeridas no serán simultáneas.
• Las cargas máximas necesarias para las salas 1, 2 y 3 (zona este) se producen por la mañana
• La carga máxima requerida para la sala 4 (zona oeste) se produce por la tarde.
-- Características de instalación:

Longitud equivalente de las tuberías (L) 50 m

Diferencia de altura entre la unidad exterior y las unidades interiores (H) +20 m

Se ha considerado que la unidad exterior está situada en una posición más alta que las unidades interiores. Por lo tanto,
cuando sea necesario consulte el capítulo “4.4.1 Factor de corrección de la longitud de las tuberías”, se usará el valor
del factor de corrección con una diferencia de altura positiva entre las unidades interiores y la exterior (+H).

46 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Procedimiento de selección del sistema de la Serie SET-FREE FSNM

 Paso 1:
Preselección inicial
Teniendo en cuenta las posibilidades del sistema SET-FREE mencionadas anteriormente, se han ajustado las
capacidades de la unidad interior mediante el conmutador DIP (DSW3).

Elemento Sala 1 Sala 2 Sala 3 Sala 4 1+2+3+4 Unidad exterior


RPK-2.0 RCD-2.5 RAS‑8FSNM
Modelo seleccionado RCI-2.5 RPI-3.0 9,6 CV
(ajustado a 1,8) (ajustado a 2,3) (120%)
Capacidad nominal de
5,2 6,7 7,1 8,0 27,0 22,40
enfriamiento
kW
Capacidad de calefacción
5,6 7,5 8,5 9,0 30,6 24,72
nominal

Para aplicar un factor de seguridad considerando los distintos factores de corrección existentes, que reducirán la
capacidad, la capacidad preseleccionada de las distintas unidades interiores no es la inmediatamente superior en todas
las unidades.
Para determinar las capacidades de enfriamiento y calefacción nominales, consulte los capítulos “4.2.2 Tablas de
capacidad de enfriamiento nominal” y "Tablas de capacidad de calefacción nominal", respectivamente, teniendo en
4
cuenta las condiciones de temperatura y la potencia total combinada (120%).

? N O TA
• Si la temperatura del aire de entrada de la unidad interior o la exterior no se encuentra en las tablas de capacidad, se deberá realizar
una interpolación usando los valores superior e inferior al de la temperatura de entrada del aire.
• Si la potencia total combinada no aparece en las tablas de capacidad (por ejemplo, 114%), debe realizar una interpolación usando
los valores superior e inferior (120% y 110%) a los de la potencia total combinada.

Este es el diagrama de la instalación resultante:

8HP

1.8HP 2.3HP 2.5HP 3.0HP = 9.6HP


Zona este Zona oeste
(6,6 CV) (3,0 CV)
Capacidad de las unidades interiores (CV equivalentes)

En este ejemplo se han considerado cuatro unidades interiores distintas (RPK‑2.0FSN3M, RCD‑2.5FSN2,
RCI‑2.5FSN3Ei y RPI‑3.0FSN3Ei) para ilustrar cómo la selección de la unidad interior puede afectar a los diferentes
factores presentados en este capítulo.
La potencia total resultante de la unidad interior es de 9,6 CV. La unidad exterior con la potencia inmediatamente
superior es el modelo de 10 CV, pero la opción de “Reducción de la capacidad total de la unidad exterior” permite
seleccionar el modelo de 8 CV. De esta forma, la unidad exterior puede tener una capacidad de hasta un 20% menor en
comparación con otros sistemas de aire acondicionado.

La potencia total combinada es la siguiente:

Potencia total de la unidad interior 9,6 CV


Potencia total combinada = x 100 = x 100 = 120 %
Potencia de la unidad exterior 8,0 CV

El siguiente paso será la corrección de la capacidad usando los distintos factores de corrección que se muestran en este
capítulo.
Este procedimiento se divide en dos partes: enfriamiento y calefacción.

47 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Procedimiento de selección del sistema de la Serie SET-FREE FSNM

 Paso 2:
 Modo de enfriamiento
Corrección de la capacidad de enfriamiento
La capacidad de enfriamiento real de la unidad exterior preseleccionada se debe calcular aplicando los factores de
corrección necesarios:

QC= QMC x fLC

QC: Capacidad de enfriamiento de la unidad exterior corregida por la longitud de las tuberías (kW)

QMC: Capacidad de enfriamiento máxima de la unidad exterior (kW)

fLC: Factor de corrección de la longitud de las tuberías para enfriamiento

La capacidad de enfriamiento máxima (QMC) de la unidad RASC-8FSNM es de 22,4 kW.

 Cálculo de f LC
:

Tanto la longitud de la tubería de refrigerante utilizada, como la diferencia de altura


entre la unidad exterior y las unidades interiores afectan directamente al rendimiento
de la unidad. Este concepto se cuantifica en el factor de corrección de la longitud de
las tuberías.
Para determinar este valor consulte el capítulo “4.4.1 Factor de corrección de la
longitud de las tuberías”, en el que podrá comprobar que, para las características de
nuestro ejemplo (longitud de la tubería de 50 metros y diferencia de altura entre la
unidad exterior y las unidades interiores de 20 metros), el factor de corrección de la
longitud de las tuberías para el modo de enfriamiento es de 0,86 aproximadamente.

 Cálculo de Q : C

Una vez determinados los factores de corrección, se puede aplicar la fórmula para
la capacidad en enfriamiento corregida por la longitud de las tuberías de la unidad
RASC-8FSNM:
QC= 22,4 kW x 0,86 = 19,26 kW

 Capacidad de enfriamiento real de la unidad exterior (Q ):


AC

Los datos sobre la capacidad de enfriamiento de la unidad RAS-8FSNM obtenidos de la tabla del capítulo “4.2.2 Tablas
de capacidad de enfriamiento nominal”, se calculan en base a una humedad relativa del 50%, lo que significa que una
temperatura del aire de entrada interior de 19ºC WB, se corresponde a una temperatura de 27ºC DB.
Sin embargo, la diferencia entre la temperatura de bulbo seco de entrada del aire interior requerida por el sistema (28ºC)
y la temperatura de bulbo seco de entrada del aire interior registrada en los datos de la capacidad de enfriamiento
(27ºC) requiere un ajuste de la capacidad.
La siguiente fórmula se usa para aplicar este ajuste:

QAC = QC + (CR x (DBR - DB))

QAC: Capacidad de enfriamiento real de la unidad exterior (kW)

QC: Capacidad de enfriamiento de la unidad exterior corregida por la longitud de las tuberías (kW)
CR: Índice de corrección debido a la humedad

DBR: Temperatura real de bulbo seco del evaporador (°C)


DB: Temperatura de bulbo seco del evaporador (°C) para cada temperatura de bulbo húmedo de la tabla (HR = 50 %).

48 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Procedimiento de selección del sistema de la Serie SET-FREE FSNM

 Cálculo de CR:
El índice de corrección debido a la humedad se muestra en una tabla del capítulo
“4.2.2 Tablas de capacidad de enfriamiento nominal”.
Este coeficiente corrige la capacidad de calor sensible de una unidad de acuerdo
con la humedad relativa del aire que entra en la unidad interior. Cuanto mayor sea la
humedad relativa menor será la capacidad de calor sensible y viceversa.
El índice de corrección de CR para la unidad RAS-8FSNM es 0,74.

 Cálculo de Q AC
:

Una vez identificado el CR para la unidad RAS-8FSNM, se puede calcular la


capacidad de enfriamiento real de la unidad RAS-8FSNM:
QAC = 19,26 kW + (0,74 x (28 - 27)) = 20,00 kW

 Paso 3:
Capacidad de enfriamiento de cada unidad interior
Una vez se conoce la capacidad de enfriamiento real de la unidad exterior, se debe calcular la capacidad de
4
enfriamiento real de cada unidad interior, de acuerdo con la siguiente fórmula:

QNCI
QCI= QAC x
QNCC

QCI: Capacidad de enfriamiento real de la unidad interior (kW)

QAC: Capacidad de enfriamiento real de la unidad exterior (kW)

QNCI: Capacidad de enfriamiento nominal de la unidad interior (kW).

QNCC: Capacidad de enfriamiento nominal de la combinación (kW).

Aplicando esto obtenemos:

nº 1 RPK-2.0 (Ajustado a 1,8) Capacidad de enfriamiento = 20,00 x (5,20 / 27,00) = 3,85 kW

nº 2 RCD-2.5 (Ajustado a 2,3) Capacidad de enfriamiento = 20,00 x (6,70 / 27,00) = 4,96 kW

nº 3 RCI-2.5 Capacidad de enfriamiento = 20,00 x (7,10 / 27,00) = 5,26 kW

nº 4 RPI-3.0 Capacidad de enfriamiento = 20,00 x (8,00 / 27,00) = 5,93 kW

 Paso 4:
Capacidad de calor sensible (SHC)
Los requisitos del sistema establecen una carga de calor sensible para cada unidad interior (consulte el Catálogo
Técnico de la unidad interior).
Una vez finalizado el cálculo de la capacidad de enfriamiento de las unidades interiores, se puede calcular la capacidad
de calor sensible mediante la siguiente fórmula:

SHC = QCI x SHF

SHC: Capacidad de calor sensible (kW)

QCI: Capacidad de enfriamiento real de la unidad interior (kW)


SHF: Factor de calor sensible

49 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Procedimiento de selección del sistema de la Serie SET-FREE FSNM

 Cálculo de SHF:
Para determinar el factor de calor sensible (índice de calor sensible respecto al total)
debe consultar la tabla del apartado “Factor de calor sensible (SHF)”, en la que se
muestran los valores de SHF para las distintas unidades interiores para cada una de
las tres posibles velocidades del ventilador (Alta, Media, Baja). El valor usado es el
relacionado con la velocidad alta del ventilador. Al hacerlo obtenemos:
SHFRPK-2.0 = 0,72

SHFRCD-2.5 = 0,74

SHFRCI-2.5 = 0,73

SHFRPI-3.0 = 0,75

 Cálculo de SHC:
Inicialmente, una vez obtenidos los factores de calor sensible, se puede calcular la
capacidad de calor sensible de cada unidad interior aplicando la fórmula anterior.
SHCRPK-2.0 = 3,85 kW x 0,72 = 2,77 kW

SHCRCD-2.5 = 4,96 kW x 0,74 = 3,67 kW

SHCRCI-2.5 = 5,26 kW x 0,73 = 3,84 kW

SHCRPI-3.0 = 5,93 kW x 0,75 = 4,45 kW

Los resultados del modo de enfriamiento son los siguientes:

Elemento Sala 1 Sala 2 Sala 3 Sala 4 1+2+3+4 Unidad exterior

RPK-2.0 RCD-2.5 RAS‑8FSNM


Modelo seleccionado RCI-2.5 RPI-3.0 9,6 CV
(ajustado a 1,8) (ajustado a 2,3) (120%)

Carga de enfriamiento Total 3,40 4,50 4,90 5,40 18,20


kW
estimada Sensible 2,40 3,20 3,50 3,80 12,90

Capacidad de Total 3,85 4,96 5,26 5,93 20,00


kW
enfriamiento corregida Sensible 2,77 3,67 3,84 4,45 14,73

Tal y como se puede ver, las capacidades de enfriamiento corregidas total y sensible son mayores que la carga de
enfriamiento estimada para las distintas estancias a acondicionar. Por lo tanto, se puede decir que la unidad
RASC-8FSNM cumple con los requisitos de enfriamiento mínimos fijados por el sistema.
Para validar la preselección de la unidad RASC-8FSNM, también se debe comprobar que cumple con los requisitos de
calefacción mínimos.

? N O TA
Si la capacidad de enfriamiento real (total o sensible) calculada es inferior a la proporcionada por la unidad preseleccionada, se debe
volver a realizar el cálculo nuevamente con la unidad inmediatamente superior.

50 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Procedimiento de selección del sistema de la Serie SET-FREE FSNM

 Modo de calefacción
Consultando el paso 1 (Preselección inicial), se pueden ver las capacidades de calefacción nominales seleccionadas
para cada estancia y la capacidad de la unidad exterior a una potencia total combinada del 120%, obteniéndose que la
potencia total de la unidad interior es de 9,6 CV.

Elemento Sala 1 Sala 2 Sala 3 Sala 4 1+2+3+4 Unidad exterior


RPK-2.0 RCD-2.5 RAS‑8FSNM
Modelo seleccionado RCI-2.5 RPI-3.0 9,6 CV
(ajustado a 1,8) (ajustado a 2,3) (120%)
Capacidad de calefacción
kW 5,6 7,5 8,5 9,0 30,6 24,72
nominal

 Paso 5:
Corrección de la capacidad de calefacción
La capacidad de calefacción real de la unidad exterior preseleccionada se debe calcular aplicando los factores de
corrección necesarios:

QAH= QMH x fLH x fD


4
QAH: Capacidad de calefacción real de la unidad exterior (kW)

QMH: Capacidad de calefacción máxima de la unidad exterior (kW)

fLC: Factor de corrección de la longitud de las tuberías para calefacción.

fD: Factor de corrección de descarche

La capacidad de calefacción máxima (QMH) de la unidad RAS-8FSNM es de 24,72 kW.

 Cálculo de f LH
:

Para determinar este valor consulte el capítulo “4.4.1 Factor de corrección de la


longitud de las tuberías”, en el que podrá comprobar que, para las características
de nuestro ejemplo (longitud equivalente de la tubería de 50 metros y una diferencia
de altura entre la unidad exterior y las unidades interiores de +20 metros), el factor
de corrección de la longitud de las tuberías para el modo de calefacción es de 0,963
aproximadamente.

 Cálculo de f : D

En situaciones en las que la temperatura ambiente es inferior a 7ºC DB, se puede


producir escarcha en el intercambiador de calor. En ese caso, la capacidad de
calefacción para la unidad se reduciría debido al tiempo que tarda la unidad en
eliminar la acumulación.
El factor de corrección de descarche tiene en cuenta este tiempo y aplica la
corrección de la capacidad de calefacción.
Para calcular el factor de corrección consulte el apartado “Factor de corrección de
descarche” que muestra una tabla con los distintos valores de fD dependiendo de la
temperatura ambiente (ºC DB). Si el factor de corrección a una temperatura ambiente
de 5ºC DB no aparece en la tabla, deberá realizar una interpolación.
Finalmente, el factor de corrección de descarche resultante es de 0,90.

 Cálculo de Q AH
:

Una vez determinados los factores de corrección, se puede aplicar la fórmula para la
capacidad de calefacción real de la unidad RASC‑8FSNM:
QAH= 24,72 kW x 0,963 x 0,90 = 21,42 kW

51 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Procedimiento de selección del sistema de la Serie SET-FREE FSNM

 Paso 6:
Capacidad de calefacción de cada unidad interior
Una vez se conoce la capacidad de calefacción real de la unidad exterior, se debe calcular la capacidad de calefacción
real de cada unidad interior, de acuerdo con la siguiente fórmula:

QNHI
QHI= QAH x
QNHC

QHI: Capacidad de calefacción real de la unidad interior (kW)

QAH: Capacidad de calefacción real de la unidad exterior (kW)

QNHI: Capacidad de calefacción nominal de la unidad interior (kW)

QNHC: Capacidad de calefacción nominal de la combinación (kW)

Aplicando esto obtenemos:

nº 1 RPK-2.0 (Ajustado a 1,8) Capacidad de calefacción = 21,42 x (5,60 / 30,60) = 3,92 kW

nº 2 RCD-2.5 (Ajustado a 2,3) Capacidad de calefacción = 21,42 x (7,50 / 30,60) = 5,25 kW

nº 3 RCI-2.5 Capacidad de calefacción = 21,42 x (8,50 / 30,60) = 5,95 kW

nº 4 RPI-3.0 Capacidad de calefacción = 21,42 x (9,00 / 30,60) = 6,30 kW

Los resultados del modo de calefacción son los siguientes:

Elemento Sala 1 Sala 2 Sala 3 Sala 4 1+2+3+4 Unidad exterior

RPK-2.0 RCD-2.5 RAS‑8FSNM


Modelo seleccionado RCI-2.5 RPI-3.0 9,6 CV
(ajustado a 1,8) (ajustado a 2,3) (120%)

Carga de calefacción
3,80 5,10 5,50 6,10 20,50
estimada
kW
Capacidad de calefacción
3,92 5,25 5,95 6,30 21,42
corregida

Tal y como se puede ver, la capacidad de calefacción corregida es mayor que la carga de calefacción estimada para
las distintas estancias a acondicionar. Por lo tanto, podemos afirmar que la unidad RASC-8FSNM es válida tanto para
calefacción como para enfriamiento.

? N O TA
Si la capacidad de calefacción real calculada es inferior a la proporcionada por la unidad preseleccionada, se debe realizar de nuevo el
cálculo con la unidad inmediatamente superior.

52 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Tablas de capacidad de enfriamiento

4.2 Tablas de capacidad de enfriamiento


El siguiente diagrama muestra el comportamiento de la capacidad de enfriamiento de la unidad exterior con la potencia
total de las unidades interiores combinadas de hasta el 130%.
Consulte los ejemplos de las combinaciones reales.
4.2.1  Curva de capacidad de enfriamiento

Curva de capacidad de enfriamiento


Capacidad de enfriamiento (kW)

Curvas características de las


100 % distintas unidades exteriores

4
100 % 130 %

Potencia total de las unidades interiores combinadas (CV)

4.2.2  Tablas de capacidad de enfriamiento nominal

Capacidad nominal a 19ºC (bulbo húmedo) y 35ºC (bulbo seco)

(kW)
CV unidades exteriores
Potencia total de las 8 10 12
unidades interiores
Potencia Potencia
combinadas (%) Capacidad Capacidad Capacidad Potencia eléctrica
eléctrica eléctrica
máxima máxima máxima consumida
consumida consumida
130 22,40 6,26 28,00 8,24 33,50 10,59
120 22,40 6,62 28,00 8,78 33,50 11,24
110 22,40 6,63 28,00 8,80 33,50 11,27
100 22,40 6,30 28,00 8,30 33,50 10,70
90 20,16 5,93 25,20 7,75 30,16 10,02
80 17,92 5,44 22,40 7,02 26,82 9,09
70 15,68 4,83 19,60 6,10 23,48 7,90
60 13,44 4,09 16,80 5,00 20,14 6,47
50 11,20 3,22 14,00 3,71 16,80 4,78

53 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Tablas de capacidad de enfriamiento

4.2.3  Tablas de capacidad de enfriamiento según potencia total de unidades interiores


combinadas

? N O TA
• CAP: Capacidad a máxima frecuencia del compresor (kW)
• IPT: Potencia de entrada (kW)
• TEMP: Temperatura del aire de entrada exterior (DB (ºC))
1.1.1 Cooling capacity tables according to Potencia total de las unidades interiores combinadas
 RAS-8FSNM
 RAS-8FSNM1
Potencia total de las unidades interiores combinadas: 50% Potencia total de las unidades interiores combinadas: 60%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 9.30 2.90 10.05 2.93 10.80 2.96 11.20 3.00 11.60 3.00 12.45 3.00 12.85 3.03 11.16 3.11 12.06 3.31 12.96 3.47 13.44 3.56 13.92 3.51 14.94 3.47 15.42 3.43
12 9.30 2.93 10.05 2.96 10.80 3.00 11.20 3.03 11.60 3.03 12.45 3.03 12.85 3.03 11.16 3.15 12.06 3.31 12.96 3.47 13.44 3.56 13.92 3.51 14.94 3.47 15.42 3.43
14 9.30 2.93 10.05 2.96 10.80 3.03 11.20 3.03 11.60 3.03 12.45 3.06 12.85 3.06 11.16 3.15 12.06 3.31 12.96 3.47 13.44 3.56 13.92 3.56 14.94 3.51 15.42 3.43
16 9.30 2.96 10.05 3.00 10.80 3.03 11.20 3.06 11.60 3.06 12.45 3.06 12.85 3.09 11.16 3.15 12.06 3.31 12.96 3.51 13.44 3.56 13.92 3.56 14.94 3.51 15.42 3.47
18 9.30 2.96 10.05 3.03 10.80 3.06 11.20 3.09 11.60 3.09 12.45 3.09 12.85 3.09 11.16 3.19 12.06 3.35 12.96 3.51 13.44 3.60 13.92 3.60 14.94 3.56 15.42 3.51
20 9.30 3.00 10.05 3.03 10.80 3.09 11.20 3.13 11.60 3.13 12.45 3.13 12.85 3.13 11.16 3.23 12.06 3.39 12.96 3.56 13.44 3.64 13.92 3.64 14.94 3.56 15.42 3.51
22 9.30 3.03 10.05 3.06 10.80 3.09 11.20 3.13 11.60 3.13 12.45 3.13 12.85 3.13 11.16 3.23 12.06 3.43 12.96 3.60 13.44 3.68 13.92 3.64 14.94 3.60 15.42 3.56
24 9.30 3.03 10.05 3.09 10.80 3.13 11.20 3.13 11.60 3.16 12.45 3.16 12.85 3.16 11.16 3.31 12.06 3.47 12.96 3.64 13.44 3.72 13.92 3.68 14.94 3.64 15.42 3.64
26 9.30 3.06 10.05 3.09 10.80 3.13 11.20 3.16 11.60 3.16 12.45 3.16 12.85 3.19 11.16 3.31 12.06 3.51 12.96 3.68 13.44 3.76 13.92 3.76 14.94 3.72 15.42 3.68
28 9.30 3.06 10.05 3.13 10.80 3.16 11.20 3.19 11.60 3.19 12.45 3.19 12.85 3.19 11.16 3.39 12.06 3.56 12.96 3.76 13.44 3.84 13.92 3.80 14.94 3.76 15.42 3.72
30 9.30 3.09 10.05 3.13 10.80 3.16 11.20 3.19 11.60 3.19 12.45 3.19 12.85 3.22 11.16 3.43 12.06 3.64 12.96 3.80 13.44 3.88 13.92 3.88 14.94 3.84 15.42 3.80
32 9.30 3.09 10.05 3.13 10.80 3.19 11.20 3.22 11.60 3.22 12.45 3.22 12.85 3.22 11.16 3.51 12.06 3.68 12.96 3.88 13.44 3.96 13.92 3.96 14.94 3.88 15.42 3.84
34 9.30 3.13 10.05 3.16 10.80 3.19 11.20 3.22 11.60 3.22 12.45 3.22 12.85 3.22 11.16 3.56 12.06 3.76 12.96 3.96 13.44 4.05 13.92 4.01 14.94 3.96 15.42 3.92
35 9.30 3.13 10.05 3.16 10.80 3.19 11.20 3.22 11.60 3.22 12.45 3.22 12.85 3.22 11.16 3.60 12.06 3.80 12.96 4.01 13.44 4.09 13.92 4.09 14.94 4.01 15.42 3.96
36 9.16 3.13 9.91 3.16 10.66 3.22 11.05 3.25 11.44 3.22 12.24 3.22 12.58 3.25 10.99 3.64 11.89 3.84 12.79 4.05 13.26 4.01 13.73 4.13 14.69 4.09 15.10 4.01
38 8.88 3.13 9.63 3.16 10.38 3.22 10.75 3.25 11.12 3.25 11.82 3.25 12.04 3.25 10.66 3.72 11.56 3.92 12.46 4.13 12.90 4.09 13.34 4.21 14.18 4.17 14.45 4.09
40 8.60 3.13 9.35 3.19 10.10 3.22 10.45 3.25 10.80 3.25 11.40 3.25 11.50 3.25 10.32 3.84 11.22 4.01 12.12 4.21 12.54 4.21 12.96 4.29 13.68 4.25 13.80 4.21

Potencia total de las unidades interiores combinadas: 70% Potencia total de las unidades interiores combinadas: 80%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 13.02 3.81 14.07 3.96 15.12 4.05 15.68 4.15 16.24 4.15 17.43 4.15 17.99 4.20 14.88 4.52 16.08 4.57 17.28 4.63 17.92 4.68 18.56 4.74 19.92 4.79 20.56 4.90
12 13.02 3.86 14.07 3.96 15.12 4.10 15.68 4.15 16.24 4.15 17.43 4.15 17.99 4.20 14.88 4.52 16.08 4.57 17.28 4.68 17.92 4.68 18.56 4.74 19.92 4.79 20.56 4.90
14 13.02 3.86 14.07 4.01 15.12 4.10 15.68 4.15 16.24 4.15 17.43 4.20 17.99 4.20 14.88 4.57 16.08 4.63 17.28 4.68 17.92 4.74 18.56 4.74 19.92 4.84 20.56 4.90
16 13.02 3.86 14.07 4.01 15.12 4.10 15.68 4.20 16.24 4.20 17.43 4.20 17.99 4.25 14.88 4.57 16.08 4.63 17.28 4.68 17.92 4.74 18.56 4.79 19.92 4.84 20.56 4.95
18 13.02 3.91 14.07 4.01 15.12 4.15 15.68 4.20 16.24 4.25 17.43 4.25 17.99 4.30 14.88 4.57 16.08 4.68 17.28 4.74 17.92 4.79 18.56 4.84 19.92 4.90 20.56 5.01
20 13.02 3.96 14.07 4.05 15.12 4.20 15.68 4.25 16.24 4.25 17.43 4.30 17.99 4.30 14.88 4.63 16.08 4.74 17.28 4.79 17.92 4.84 18.56 4.84 19.92 4.95 20.56 5.06
22 13.02 4.01 14.07 4.10 15.12 4.25 15.68 4.30 16.24 4.30 17.43 4.34 17.99 4.34 14.88 4.68 16.08 4.79 17.28 4.84 17.92 4.84 18.56 4.90 19.92 5.01 20.56 5.12
24 13.02 4.05 14.07 4.15 15.12 4.30 15.68 4.34 16.24 4.39 17.43 4.39 17.99 4.44 14.88 4.79 16.08 4.84 17.28 4.90 17.92 4.95 18.56 4.95 19.92 5.06 20.56 5.17
26 13.02 4.10 14.07 4.25 15.12 4.34 15.68 4.44 16.24 4.44 17.43 4.44 17.99 4.49 14.88 4.84 16.08 4.90 17.28 4.95 17.92 5.01 18.56 5.06 19.92 5.17 20.56 5.22
28 13.02 4.15 14.07 4.30 15.12 4.44 15.68 4.49 16.24 4.54 17.43 4.54 17.99 4.54 14.88 4.90 16.08 4.95 17.28 5.06 17.92 5.06 18.56 5.12 19.92 5.22 20.56 5.33
30 13.02 4.25 14.07 4.39 15.12 4.49 15.68 4.59 16.24 4.59 17.43 4.59 17.99 4.63 14.88 5.01 16.08 5.06 17.28 5.17 17.92 5.17 18.56 5.22 19.92 5.33 20.56 5.44
32 13.02 4.30 14.07 4.44 15.12 4.59 15.68 4.63 16.24 4.68 17.43 4.68 17.99 4.73 14.88 5.06 16.08 5.17 17.28 5.22 17.92 5.28 18.56 5.33 19.92 5.44 20.56 5.50
34 13.02 4.39 14.07 4.54 15.12 4.68 15.68 4.73 16.24 4.78 17.43 4.78 17.99 4.83 14.88 5.17 16.08 5.28 17.28 5.33 17.92 5.39 18.56 5.44 19.92 5.55 20.56 5.61
35 13.02 4.49 14.07 4.59 15.12 4.73 15.68 4.83 16.24 4.83 17.43 4.88 17.99 4.88 14.88 5.22 16.08 5.33 17.28 5.39 17.92 5.44 18.56 5.50 19.92 5.61 20.56 5.71
36 12.82 4.49 13.87 4.63 14.92 4.78 15.47 4.88 16.02 4.88 17.14 4.88 17.61 4.92 14.66 5.28 15.86 5.39 17.06 5.44 17.68 5.55 18.30 5.55 19.58 5.66 20.13 5.77
38 12.43 4.59 13.48 4.73 14.53 4.88 15.05 4.92 15.57 4.97 16.55 5.02 16.86 5.02 14.21 5.44 15.41 5.50 16.61 5.61 17.20 5.77 17.79 5.66 18.91 5.77 19.26 5.88
40 12.04 4.73 13.09 4.88 14.14 5.02 14.63 4.97 15.12 5.12 15.96 5.12 16.10 5.17 13.76 5.55 14.96 5.66 16.16 5.71 16.72 5.88 17.28 5.82 18.24 5.93 18.40 6.04

Potencia total de las unidades interiores combinadas: 90% Potencia total de las unidades interiores combinadas: 100%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 16.74 4.87 18.09 4.92 19.44 5.04 20.16 5.04 20.88 5.04 22.41 5.04 23.13 5.04 18.60 5.17 20.10 5.23 21.60 5.36 22.40 5.36 23.20 5.36 24.90 5.23 25.70 5.10
12 16.74 4.87 18.09 4.98 19.44 5.04 20.16 5.10 20.88 5.10 22.41 5.04 23.13 5.04 18.60 5.17 20.10 5.23 21.60 5.36 22.40 5.42 23.20 5.36 24.90 5.23 25.70 5.10
14 16.74 4.87 18.09 4.98 19.44 5.04 20.16 5.10 20.88 5.10 22.41 5.04 23.13 5.04 18.60 5.17 20.10 5.23 21.60 5.36 22.40 5.42 23.20 5.36 24.90 5.23 25.70 5.10
16 16.74 4.92 18.09 4.98 19.44 5.10 20.16 5.10 20.88 5.10 22.41 5.10 23.13 5.10 18.60 5.23 20.10 5.29 21.60 5.42 22.40 5.42 23.20 5.36 24.90 5.23 25.70 5.17
18 16.74 4.98 18.09 5.04 19.44 5.10 20.16 5.16 20.88 5.16 22.41 5.16 23.13 5.10 18.60 5.23 20.10 5.36 21.60 5.42 22.40 5.48 23.20 5.42 24.90 5.29 25.70 5.17
20 16.74 4.98 18.09 5.10 19.44 5.16 20.16 5.22 20.88 5.22 22.41 5.16 23.13 5.16 18.60 5.29 20.10 5.36 21.60 5.48 22.40 5.54 23.20 5.48 24.90 5.36 25.70 5.23
22 16.74 5.04 18.09 5.16 19.44 5.22 20.16 5.28 20.88 5.28 22.41 5.28 23.13 5.22 18.60 5.36 20.10 5.42 21.60 5.54 22.40 5.61 23.20 5.54 24.90 5.42 25.70 5.29
24 16.74 5.16 18.09 5.22 19.44 5.28 20.16 5.34 20.88 5.34 22.41 5.28 23.13 5.28 18.60 5.42 20.10 5.54 21.60 5.61 22.40 5.67 23.20 5.61 24.90 5.48 25.70 5.36
26 16.74 5.22 18.09 5.28 19.44 5.40 20.16 5.40 20.88 5.40 22.41 5.40 23.13 5.34 18.60 5.48 20.10 5.61 21.60 5.73 22.40 5.73 23.20 5.67 24.90 5.61 25.70 5.48
28 16.74 5.28 18.09 5.40 19.44 5.46 20.16 5.52 20.88 5.52 22.41 5.46 23.13 5.46 18.60 5.61 20.10 5.73 21.60 5.80 22.40 5.86 23.20 5.80 24.90 5.67 25.70 5.54
30 16.74 5.40 18.09 5.46 19.44 5.58 20.16 5.64 20.88 5.64 22.41 5.58 23.13 5.58 18.60 5.73 20.10 5.80 21.60 5.92 22.40 5.99 23.20 5.92 24.90 5.80 25.70 5.67
32 16.74 5.52 18.09 5.58 19.44 5.70 20.16 5.76 20.88 5.76 22.41 5.70 23.13 5.70 18.60 5.80 20.10 5.92 21.60 6.05 22.40 6.11 23.20 6.05 24.90 5.92 25.70 5.80
34 16.74 5.64 18.09 5.70 19.44 5.81 20.16 5.87 20.88 5.87 22.41 5.81 23.13 5.81 18.60 5.92 20.10 6.05 21.60 6.17 22.40 6.24 23.20 6.17 24.90 6.05 25.70 5.92
35 16.74 5.70 18.09 5.81 19.44 5.87 20.16 5.93 20.88 5.93 22.41 5.87 23.13 5.87 18.60 6.05 20.10 6.11 21.60 6.24 22.40 6.30 23.20 6.24 24.90 6.11 25.70 5.99
36 16.49 5.76 17.84 5.87 19.19 5.93 19.89 5.93 20.59 5.99 22.03 5.93 22.64 5.93 18.32 6.11 19.82 6.17 21.32 6.30 22.10 6.43 22.88 6.30 24.48 6.17 25.16 6.05
38 15.98 5.87 17.33 5.99 18.68 6.11 19.35 6.05 20.02 6.11 21.28 6.11 21.67 6.05 17.76 6.24 19.26 6.36 20.76 6.49 21.50 6.62 22.24 6.49 23.64 6.30 24.08 6.17
40 15.48 6.05 16.83 6.11 18.18 6.23 18.81 6.23 19.44 6.29 20.52 6.23 20.70 6.23 17.20 6.43 18.70 6.55 20.20 6.68 20.90 6.62 21.60 6.62 22.80 6.49 23.00 6.36

NOTE
• CAP: Capacity at compressor maximum frequency (kW)
• IPT: Input power (kW)
• TEMP: Outdoor air inlet temperature (DB (ºC))

54 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Tablas de capacidad de enfriamiento

Potencia total de las unidades interiores combinadas: 110% Potencia total de las unidades interiores combinadas: 120%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 18.60 5.04 20.10 5.11 21.60 5.17 22.40 5.24 23.20 5.31 24.90 5.44 25.70 5.51 18.60 5.03 20.10 5.16 21.60 5.30 22.40 5.30 23.20 5.36 24.90 5.56 25.70 5.69
12 18.60 5.04 20.10 5.17 21.60 5.24 22.40 5.31 23.20 5.37 24.90 5.44 25.70 5.57 18.60 5.10 20.10 5.23 21.60 5.30 22.40 5.36 23.20 5.43 24.90 5.56 25.70 5.69
14 18.60 5.11 20.10 5.17 21.60 5.31 22.40 5.31 23.20 5.37 24.90 5.51 25.70 5.57 18.60 5.10 20.10 5.23 21.60 5.36 22.40 5.36 23.20 5.50 24.90 5.63 25.70 5.76
16 18.60 5.17 20.10 5.24 21.60 5.37 22.40 5.37 23.20 5.44 24.90 5.57 25.70 5.64 18.60 5.16 20.10 5.30 21.60 5.36 22.40 5.43 23.20 5.50 24.90 5.63 25.70 5.83
18 18.60 5.17 20.10 5.31 21.60 5.44 22.40 5.44 23.20 5.51 24.90 5.64 25.70 5.77 18.60 5.23 20.10 5.36 21.60 5.43 22.40 5.50 23.20 5.56 24.90 5.76 25.70 5.89
20 18.60 5.31 20.10 5.37 21.60 5.51 22.40 5.57 23.20 5.57 24.90 5.70 25.70 5.84 18.60 5.30 20.10 5.43 21.60 5.56 22.40 5.56 23.20 5.63 24.90 5.83 25.70 5.96
22 18.60 5.37 20.10 5.51 21.60 5.57 22.40 5.64 23.20 5.70 24.90 5.84 25.70 5.90 18.60 5.43 20.10 5.50 21.60 5.63 22.40 5.69 23.20 5.76 24.90 5.89 25.70 6.09
24 18.60 5.51 20.10 5.57 21.60 5.70 22.40 5.77 23.20 5.84 24.90 5.97 25.70 6.04 18.60 5.50 20.10 5.63 21.60 5.76 22.40 5.76 23.20 5.89 24.90 6.03 25.70 6.16
26 18.60 5.64 20.10 5.70 21.60 5.84 22.40 5.90 23.20 5.97 24.90 6.04 25.70 6.17 18.60 5.63 20.10 5.76 21.60 5.83 22.40 5.89 23.20 5.96 24.90 6.16 25.70 6.29
28 18.60 5.77 20.10 5.84 21.60 5.97 22.40 6.04 23.20 6.10 24.90 6.24 25.70 6.30 18.60 5.76 20.10 5.89 21.60 5.96 22.40 6.03 23.20 6.16 24.90 6.29 25.70 6.42
30 18.60 5.90 20.10 6.04 21.60 6.10 22.40 6.17 23.20 6.24 24.90 6.37 25.70 6.50 18.60 5.89 20.10 6.03 21.60 6.16 22.40 6.22 23.20 6.29 24.90 6.42 25.70 6.62
32 18.60 6.04 20.10 6.17 21.60 6.30 22.40 6.37 23.20 6.43 24.90 6.57 25.70 6.70 18.60 6.03 20.10 6.16 21.60 6.29 22.40 6.36 23.20 6.42 24.90 6.62 25.70 6.75
34 18.60 6.24 20.10 6.37 21.60 6.50 22.40 6.50 23.20 6.63 24.90 6.77 25.70 6.83 18.60 6.22 20.10 6.36 21.60 6.49 22.40 6.56 23.20 6.62 24.90 6.82 25.70 6.95
35 18.60 6.30 20.10 6.43 21.60 6.57 22.40 6.63 23.20 6.70 24.90 6.83 25.70 6.97 18.60 6.29 20.10 6.42 21.60 6.56 22.40 6.62 23.20 6.69 24.90 6.89 25.70 7.08
36 18.32 6.43 19.82 6.50 21.32 6.63 22.10 6.77 22.88 6.77 24.48 6.97 25.16 7.10 18.32 6.42 19.82 6.56 21.32 6.69 22.10 6.75 22.88 6.82 24.48 7.02 25.16 7.15
38 17.76 6.63 19.26 6.77 20.76 6.90 21.50 7.03 22.24 7.03 23.64 7.10 24.08 7.30 17.76 6.62 19.26 6.69 20.76 6.89 21.50 6.95 22.24 7.02 23.64 7.22 24.08 7.42
40 17.20 6.83 18.70 6.97 20.20 7.10 20.90 7.16 21.60 7.23 22.80 7.36 23.00 7.50 17.20 6.82 18.70 6.95 20.20 7.08 20.90 7.15 21.60 7.22 22.80 7.42 23.00 7.61

Potencia total de las unidades interiores combinadas: 130%


Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 18.60 4.51 20.10 4.63 21.60 4.70 22.40 4.76 23.20 4.82 24.90 4.95 25.70 5.07
12 18.60 4.51 20.10 4.63 21.60 4.70 22.40 4.76 23.20 4.82 24.90 4.95 25.70 5.07

4
14 18.60 4.57 20.10 4.70 21.60 4.76 22.40 4.82 23.20 4.88 24.90 4.95 25.70 5.14
16 18.60 4.57 20.10 4.70 21.60 4.82 22.40 4.82 23.20 4.88 24.90 5.01 25.70 5.14
18 18.60 4.63 20.10 4.76 21.60 4.88 22.40 4.88 23.20 4.95 24.90 5.14 25.70 5.26
20 18.60 4.76 20.10 4.88 21.60 4.95 22.40 5.01 23.20 5.07 24.90 5.20 25.70 5.32
22 18.60 4.82 20.10 4.95 21.60 5.01 22.40 5.07 23.20 5.14 24.90 5.32 25.70 5.45
24 18.60 4.95 20.10 5.07 21.60 5.14 22.40 5.20 23.20 5.26 24.90 5.45 25.70 5.57
26 18.60 5.07 20.10 5.26 21.60 5.32 22.40 5.39 23.20 5.45 24.90 5.57 25.70 5.70
28 18.60 5.26 20.10 5.39 21.60 5.45 22.40 5.51 23.20 5.57 24.90 5.76 25.70 5.89
30 18.60 5.45 20.10 5.57 21.60 5.64 22.40 5.70 23.20 5.76 24.90 5.95 25.70 6.07
32 18.60 5.64 20.10 5.76 21.60 5.89 22.40 5.89 23.20 6.01 24.90 6.14 25.70 6.33
34 18.60 5.82 20.10 5.95 21.60 6.07 22.40 6.14 23.20 6.20 24.90 6.39 25.70 6.51
35 18.60 5.95 20.10 6.07 21.60 6.20 22.40 6.26 23.20 6.33 24.90 6.51 25.70 6.70
36 18.32 6.07 19.82 6.20 21.32 6.33 22.10 6.83 22.88 6.45 24.48 6.64 25.16 6.83
38 17.76 6.33 19.26 6.45 20.76 6.58 21.50 7.08 22.24 6.70 23.64 6.89 24.08 7.08
40 17.20 6.58 18.70 6.76 20.20 6.83 20.90 7.39 21.60 7.01 22.80 7.20 23.00 7.39

 RAS-10FSNM1
Potencia total de las unidades interiores combinadas: 50% Potencia total de las unidades interiores combinadas: 60%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 11.50 3.34 12.50 3.37 13.50 3.41 14.00 3.45 14.55 3.45 15.50 3.45 16.05 3.48 13.80 3.80 15.00 4.05 16.20 4.25 16.80 4.35 17.46 4.30 18.60 4.25 19.26 4.20
12 11.50 3.37 12.50 3.41 13.50 3.45 14.00 3.48 14.55 3.48 15.50 3.48 16.05 3.48 13.80 3.85 15.00 4.05 16.20 4.25 16.80 4.35 17.46 4.30 18.60 4.25 19.26 4.20
14 11.50 3.37 12.50 3.41 13.50 3.48 14.00 3.48 14.55 3.48 15.50 3.52 16.05 3.52 13.80 3.85 15.00 4.05 16.20 4.25 16.80 4.35 17.46 4.35 18.60 4.30 19.26 4.20
16 11.50 3.41 12.50 3.45 13.50 3.48 14.00 3.52 14.55 3.52 15.50 3.52 16.05 3.56 13.80 3.85 15.00 4.05 16.20 4.30 16.80 4.35 17.46 4.35 18.60 4.30 19.26 4.25
18 11.50 3.41 12.50 3.48 13.50 3.52 14.00 3.56 14.55 3.56 15.50 3.56 16.05 3.56 13.80 3.90 15.00 4.10 16.20 4.30 16.80 4.40 17.46 4.40 18.60 4.35 19.26 4.30
20 11.50 3.45 12.50 3.48 13.50 3.56 14.00 3.59 14.55 3.59 15.50 3.59 16.05 3.59 13.80 3.95 15.00 4.15 16.20 4.35 16.80 4.45 17.46 4.45 18.60 4.35 19.26 4.30
22 11.50 3.48 12.50 3.52 13.50 3.56 14.00 3.59 14.55 3.59 15.50 3.59 16.05 3.59 13.80 3.95 15.00 4.20 16.20 4.40 16.80 4.50 17.46 4.45 18.60 4.40 19.26 4.35
24 11.50 3.48 12.50 3.56 13.50 3.59 14.00 3.59 14.55 3.63 15.50 3.63 16.05 3.63 13.80 4.05 15.00 4.25 16.20 4.45 16.80 4.55 17.46 4.50 18.60 4.45 19.26 4.45
26 11.50 3.52 12.50 3.56 13.50 3.59 14.00 3.63 14.55 3.63 15.50 3.63 16.05 3.67 13.80 4.05 15.00 4.30 16.20 4.50 16.80 4.60 17.46 4.60 18.60 4.55 19.26 4.50
28 11.50 3.52 12.50 3.59 13.50 3.63 14.00 3.67 14.55 3.67 15.50 3.67 16.05 3.67 13.80 4.15 15.00 4.35 16.20 4.60 16.80 4.70 17.46 4.65 18.60 4.60 19.26 4.55
30 11.50 3.56 12.50 3.59 13.50 3.63 14.00 3.67 14.55 3.67 15.50 3.67 16.05 3.71 13.80 4.20 15.00 4.45 16.20 4.65 16.80 4.75 17.46 4.75 18.60 4.70 19.26 4.65
32 11.50 3.56 12.50 3.59 13.50 3.67 14.00 3.71 14.55 3.71 15.50 3.71 16.05 3.71 13.80 4.30 15.00 4.50 16.20 4.75 16.80 4.85 17.46 4.85 18.60 4.75 19.26 4.70
34 11.50 3.59 12.50 3.63 13.50 3.67 14.00 3.71 14.55 3.71 15.50 3.71 16.05 3.71 13.80 4.35 15.00 4.60 16.20 4.85 16.80 4.95 17.46 4.90 18.60 4.85 19.26 4.80
35 11.50 3.59 12.50 3.63 13.50 3.67 14.00 3.71 14.55 3.71 15.50 3.71 16.05 3.71 13.80 4.40 15.00 4.65 16.20 4.90 16.80 5.00 17.46 5.00 18.60 4.90 19.26 4.85
36 11.29 3.59 12.30 3.63 13.31 3.71 13.81 3.74 14.32 3.71 15.21 3.71 15.67 3.74 13.55 4.45 14.76 4.70 15.97 4.95 16.57 4.90 17.18 5.05 18.25 5.00 18.80 4.90
38 10.87 3.59 11.90 3.63 12.93 3.71 13.43 3.74 13.86 3.74 14.63 3.74 14.91 3.74 13.04 4.55 14.28 4.80 15.52 5.05 16.12 5.00 16.63 5.15 17.56 5.10 17.89 5.00
40 10.45 3.59 11.50 3.67 12.55 3.71 13.05 3.74 13.40 3.74 14.05 3.74 14.15 3.74 12.54 4.70 13.80 4.90 15.06 5.15 15.66 5.15 16.08 5.25 16.86 5.20 16.98 5.15

55 TCES0059 rev.2 - 06/2016


28 18.60 5.26 20.10 5.39 21.60 5.45 22.40 5.51 23.20 5.57 24.90 5.76 25.70 5.89
30 18.60 5.45 20.10 5.57 21.60 5.64 22.40 5.70 23.20 5.76 24.90 5.95 25.70 6.07
32 18.60 5.64 20.10 5.76 21.60 5.89 22.40 5.89 23.20 6.01 24.90 6.14 25.70 6.33
4 Capacidades
34 18.60 5.82 y datos
20.10 5.95de21.60
selección
6.07 22.40 6.14 23.20 6.20 24.90 6.39 25.70 6.51
35 18.60 5.95 20.10 6.07 21.60 6.20 22.40 6.26 23.20 6.33 24.90 6.51 25.70 6.70
36 18.32 6.07 19.82 6.20 21.32 6.33 22.10 6.83 22.88 6.45 24.48 6.64 25.16 6.83
Tablas de capacidad de enfriamiento
38 17.76 6.33 19.26 6.45 20.76 6.58 21.50 7.08 22.24 6.70 23.64 6.89 24.08 7.08
40 17.20 6.58 18.70 6.76 20.20 6.83 20.90 7.39 21.60 7.01 22.80 7.20 23.00 7.39

 RAS-10FSNM1
 RAS-10FSNM

Potencia total de las unidades interiores combinadas: 50% Potencia total de las unidades interiores combinadas: 60%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 11.50 3.34 12.50 3.37 13.50 3.41 14.00 3.45 14.55 3.45 15.50 3.45 16.05 3.48 13.80 3.80 15.00 4.05 16.20 4.25 16.80 4.35 17.46 4.30 18.60 4.25 19.26 4.20
12 11.50 3.37 12.50 3.41 13.50 3.45 14.00 3.48 14.55 3.48 15.50 3.48 16.05 3.48 13.80 3.85 15.00 4.05 16.20 4.25 16.80 4.35 17.46 4.30 18.60 4.25 19.26 4.20
14 11.50 3.37 12.50 3.41 13.50 3.48 14.00 3.48 14.55 3.48 15.50 3.52 16.05 3.52 13.80 3.85 15.00 4.05 16.20 4.25 16.80 4.35 17.46 4.35 18.60 4.30 19.26 4.20
16 11.50 3.41 12.50 3.45 13.50 3.48 14.00 3.52 14.55 3.52 15.50 3.52 16.05 3.56 13.80 3.85 15.00 4.05 16.20 4.30 16.80 4.35 17.46 4.35 18.60 4.30 19.26 4.25
18 11.50 3.41 12.50 3.48 13.50 3.52 14.00 3.56 14.55 3.56 15.50 3.56 16.05 3.56 13.80 3.90 15.00 4.10 16.20 4.30 16.80 4.40 17.46 4.40 18.60 4.35 19.26 4.30
20 11.50 3.45 12.50 3.48 13.50 3.56 14.00 3.59 14.55 3.59 15.50 3.59 16.05 3.59 13.80 3.95 15.00 4.15 16.20 4.35 16.80 4.45 17.46 4.45 18.60 4.35 19.26 4.30
22 11.50 3.48 12.50 3.52 13.50 3.56 14.00 3.59 14.55 3.59 15.50 3.59 16.05 3.59 13.80 3.95 15.00 4.20 16.20 4.40 16.80 4.50 17.46 4.45 18.60 4.40 19.26 4.35
24 11.50 3.48 12.50 3.56 13.50 3.59 14.00 3.59 14.55 3.63 15.50 3.63 16.05 3.63 13.80 4.05 15.00 4.25 16.20 4.45 16.80 4.55 17.46 4.50 18.60 4.45 19.26 4.45
26 11.50 3.52 12.50 3.56 13.50 3.59 14.00 3.63 14.55 3.63 15.50 3.63 16.05 3.67 13.80 4.05 15.00 4.30 16.20 4.50 16.80 4.60 17.46 4.60 18.60 4.55 19.26 4.50
28 11.50 3.52 12.50 3.59 13.50 3.63 14.00 3.67 14.55 3.67 15.50 3.67 16.05 3.67 13.80 4.15 15.00 4.35 16.20 4.60 16.80 4.70 17.46 4.65 18.60 4.60 19.26 4.55
30 11.50 3.56 12.50 3.59 13.50 3.63 14.00 3.67 14.55 3.67 15.50 3.67 16.05 3.71 13.80 4.20 15.00 4.45 16.20 4.65 16.80 4.75 17.46 4.75 18.60 4.70 19.26 4.65
32 11.50 3.56 12.50 3.59 13.50 3.67 14.00 3.71 14.55 3.71 15.50 3.71 16.05 3.71 13.80 4.30 15.00 4.50 16.20 4.75 16.80 4.85 17.46 4.85 18.60 4.75 19.26 4.70
34 11.50 3.59 12.50 3.63 13.50 3.67 14.00 3.71 14.55 3.71 15.50 3.71 16.05 3.71 13.80 4.35 15.00 4.60 16.20 4.85 16.80 4.95 17.46 4.90 18.60 4.85 19.26 4.80
35 11.50 3.59 12.50 3.63 13.50 3.67 14.00 3.71 14.55 3.71 15.50 3.71 16.05 3.71 13.80 4.40 15.00 4.65 16.20 4.90 16.80 5.00 17.46 5.00 18.60 4.90 19.26 4.85
36 11.29 3.59 12.30 3.63 13.31 3.71 13.81 3.74 14.32 3.71 15.21 3.71 15.67 3.74 13.55 4.45 14.76 4.70 15.97 4.95 16.57 4.90 17.18 5.05 18.25 5.00 18.80 4.90
38 10.87 3.59 11.90 3.63 12.93 3.71 13.43 3.74 13.86 3.74 14.63 3.74 14.91 3.74 13.04 4.55 14.28 4.80 15.52 5.05 16.12 5.00 16.63 5.15 17.56 5.10 17.89 5.00
40 10.45 3.59 11.50 3.67 12.55 3.71 13.05 3.74 13.40 3.74 14.05 3.74 14.15 3.74 12.54 4.70 13.80 4.90 15.06 5.15 15.66 5.15 16.08 5.25 16.86 5.20 16.98 5.15

Potencia total de las unidades interiores combinadas: 70% Potencia total de las unidades interiores combinadas: 80%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 16.10 4.82 17.50 5.00 18.90 5.13 19.60 5.25 20.37 5.25 21.70 5.25 22.47 5.31 18.40 5.83 20.00 5.90 21.60 5.97 22.40 6.04 23.28 6.11 24.80 6.18 25.68 6.32
12 16.10 4.88 17.50 5.00 18.90 5.19 19.60 5.25 20.37 5.25 21.70 5.25 22.47 5.31 18.40 5.83 20.00 5.90 21.60 6.04 22.40 6.04 23.28 6.11 24.80 6.18 25.68 6.32
14 16.10 4.88 17.50 5.07 18.90 5.19 19.60 5.25 20.37 5.25 21.70 5.31 22.47 5.31 18.40 5.90 20.00 5.97 21.60 6.04 22.40 6.11 23.28 6.11 24.80 6.25 25.68 6.32
16 16.10 4.88 17.50 5.07 18.90 5.19 19.60 5.31 20.37 5.31 21.70 5.31 22.47 5.37 18.40 5.90 20.00 5.97 21.60 6.04 22.40 6.11 23.28 6.18 24.80 6.25 25.68 6.39
18 16.10 4.94 17.50 5.07 18.90 5.25 19.60 5.31 20.37 5.37 21.70 5.37 22.47 5.43 18.40 5.90 20.00 6.04 21.60 6.11 22.40 6.18 23.28 6.25 24.80 6.32 25.68 6.46
20 16.10 5.00 17.50 5.13 18.90 5.31 19.60 5.37 20.37 5.37 21.70 5.43 22.47 5.43 18.40 5.97 20.00 6.11 21.60 6.18 22.40 6.25 23.28 6.25 24.80 6.39 25.68 6.53
22 16.10 5.07 17.50 5.19 18.90 5.37 19.60 5.43 20.37 5.43 21.70 5.49 22.47 5.49 18.40 6.04 20.00 6.18 21.60 6.25 22.40 6.25 23.28 6.32 24.80 6.46 25.68 6.60
24 16.10 5.13 17.50 5.25 18.90 5.43 19.60 5.49 20.37 5.55 21.70 5.55 22.47 5.61 18.40 6.18 20.00 6.25 21.60 6.32 22.40 6.39 23.28 6.39 24.80 6.53 25.68 6.67
26 16.10 5.19 17.50 5.37 18.90 5.49 19.60 5.61 20.37 5.61 21.70 5.61 22.47 5.68 18.40 6.25 20.00 6.32 21.60 6.39 22.40 6.46 23.28 6.53 24.80 6.67 25.68 6.74
28 16.10 5.25 17.50 5.43 18.90 5.61 19.60 5.68 20.37 5.74 21.70 5.74 22.47 5.74 18.40 6.32 20.00 6.39 21.60 6.53 22.40 6.53 23.28 6.60 24.80 6.74 25.68 6.88
30 16.10 5.37 17.50 5.55 18.90 5.68 19.60 5.80 20.37 5.80 21.70 5.80 22.47 5.86 18.40 6.46 20.00 6.53 21.60 6.67 22.40 6.67 23.28 6.74 24.80 6.88 25.68 7.02
32 16.10 5.43 17.50 5.61 18.90 5.80 19.60 5.86 20.37 5.92 21.70 5.92 22.47 5.98 18.40 6.53 20.00 6.67 21.60 6.74 22.40 6.81 23.28 6.88 24.80 7.02 25.68 7.09
34 16.10 5.55 17.50 5.74 18.90 5.92 19.60 5.98 20.37 6.04 21.70 6.04 22.47 6.10 18.40 6.67 20.00 6.81 21.60 6.88 22.40 6.95 23.28 7.02 24.80 7.16 25.68 7.23
35 16.10 5.68 17.50 5.80 18.90 5.98 19.60 6.10 20.37 6.10 21.70 6.16 22.47 6.16 18.40 6.74 20.00 6.88 21.60 6.95 22.40 7.02 23.28 7.09 24.80 7.23 25.68 7.37
36 15.81 5.68 17.22 5.86 18.63 6.04 19.33 6.16 20.05 6.16 21.29 6.16 21.94 6.23 18.06 6.81 19.68 6.95 21.30 7.02 22.10 7.16 22.91 7.16 24.34 7.30 25.07 7.44
38 15.22 5.80 16.66 5.98 18.10 6.16 18.80 6.23 19.40 6.29 20.48 6.35 20.87 6.35 17.39 7.02 19.04 7.09 20.69 7.23 21.49 7.44 22.18 7.30 23.41 7.44 23.86 7.58
40 14.63 5.98 16.10 6.16 17.57 6.35 18.27 6.29 18.76 6.47 19.67 6.47 19.81 6.53 16.72 7.16 18.40 7.30 20.08 7.37 20.88 7.58 21.44 7.51 22.48 7.65 22.64 7.79

Potencia total de las unidades interiores combinadas: 90% Potencia total de las unidades interiores combinadas: 100%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP 14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 20.70 6.36 22.50 6.44 24.30 6.59 25.20 6.59 26.19 6.59 27.90 6.59 28.89 6.59 23.00 6.81 25.00 6.89 27.00 7.06 28.00 7.06 29.10 7.06 31.00 6.89 32.10 6.72
12 20.70 6.36 22.50 6.51 24.30 6.59 25.20 6.67 26.19 6.67 27.90 6.59 28.89 6.59 23.00 6.81 25.00 6.89 27.00 7.06 28.00 7.14 29.10 7.06 31.00 6.89 32.10 6.72
14 20.70 6.36 22.50 6.51 24.30 6.59 25.20 6.67 26.19 6.67 27.90 6.59 28.89 6.59 23.00 6.81 25.00 6.89 27.00 7.06 28.00 7.14 29.10 7.06 31.00 6.89 32.10 6.72
16 20.70 6.44 22.50 6.51 24.30 6.67 25.20 6.67 26.19 6.67 27.90 6.67 28.89 6.67 23.00 6.89 25.00 6.97 27.00 7.14 28.00 7.14 29.10 7.06 31.00 6.89 32.10 6.81
18 20.70 6.51 22.50 6.59 24.30 6.67 25.20 6.75 26.19 6.75 27.90 6.75 28.89 6.67 23.00 6.89 25.00 7.06 27.00 7.14 28.00 7.22 29.10 7.14 31.00 6.97 32.10 6.81
20 20.70 6.51 22.50 6.67 24.30 6.75 25.20 6.82 26.19 6.82 27.90 6.75 28.89 6.75 23.00 6.97 25.00 7.06 27.00 7.22 28.00 7.30 29.10 7.22 31.00 7.06 32.10 6.89
22 20.70 6.59 22.50 6.75 24.30 6.82 25.20 6.90 26.19 6.90 27.90 6.90 28.89 6.82 23.00 7.06 25.00 7.14 27.00 7.30 28.00 7.39 29.10 7.30 31.00 7.14 32.10 6.97
24 20.70 6.75 22.50 6.82 24.30 6.90 25.20 6.98 26.19 6.98 27.90 6.90 28.89 6.90 23.00 7.14 25.00 7.30 27.00 7.39 28.00 7.47 29.10 7.39 31.00 7.22 32.10 7.06
26 20.70 6.82 22.50 6.90 24.30 7.06 25.20 7.06 26.19 7.06 27.90 7.06 28.89 6.98 23.00 7.22 25.00 7.39 27.00 7.55 28.00 7.55 29.10 7.47 31.00 7.39 32.10 7.22
28 20.70 6.90 22.50 7.06 24.30 7.13 25.20 7.21 26.19 7.21 27.90 7.13 28.89 7.13 23.00 7.39 25.00 7.55 27.00 7.64 28.00 7.72 29.10 7.64 31.00 7.47 32.10 7.30
30 20.70 7.06 22.50 7.13 24.30 7.29 25.20 7.37 26.19 7.37 27.90 7.29 28.89 7.29 23.00 7.55 25.00 7.64 27.00 7.80 28.00 7.89 29.10 7.80 31.00 7.64 32.10 7.47
32 20.70 7.21 22.50 7.29 24.30 7.44 25.20 7.52 26.19 7.52 27.90 7.44 28.89 7.44 23.00 7.64 25.00 7.80 27.00 7.97 28.00 8.05 29.10 7.97 31.00 7.80 32.10 7.64
34 20.70 7.37 22.50 7.44 24.30 7.60 25.20 7.68 26.19 7.68 27.90 7.60 28.89 7.60 23.00 7.80 25.00 7.97 27.00 8.13 28.00 8.22 29.10 8.13 31.00 7.97 32.10 7.80
35 20.70 7.44 22.50 7.60 24.30 7.68 25.20 7.75 26.19 7.75 27.90 7.68 28.89 7.68 23.00 7.97 25.00 8.05 27.00 8.22 28.00 8.30 29.10 8.22 31.00 8.05 32.10 7.89
36 20.32 7.52 22.14 7.68 23.96 7.75 24.86 7.75 25.78 7.83 27.38 7.75 28.21 7.75 22.58 8.05 24.60 8.13 26.62 8.30 27.62 8.47 28.64 8.30 30.42 8.13 31.34 7.97
38 19.57 7.68 21.42 7.83 23.27 7.99 24.17 7.91 24.95 7.99 26.33 7.99 26.84 7.91 21.74 8.22 23.80 8.38 25.86 8.55 26.86 8.72 27.72 8.55 29.26 8.30 29.82 8.13
40 18.81 7.91 20.70 7.99 22.59 8.14 23.49 8.14 24.12 8.22 25.29 8.14 25.47 8.14 20.90 8.47 23.00 8.63 25.10 8.80 26.10 8.72 26.80 8.72 28.10 8.55 28.30 8.38

Potencia total de las unidades interiores combinadas: 110% Potencia total de las unidades interiores combinadas: 120%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 23.00 6.69 25.00 6.77 27.00 6.86 28.00 6.95 29.10 7.04 31.00 7.21 32.10 7.30 23.00 6.67 25.00 6.85 27.00 7.02 28.00 7.02 29.10 7.11 31.00 7.37 32.10 7.55
12 23.00 6.69 25.00 6.86 27.00 6.95 28.00 7.04 29.10 7.13 31.00 7.21 32.10 7.39 23.00 6.76 25.00 6.93 27.00 7.02 28.00 7.11 29.10 7.20 31.00 7.37 32.10 7.55
14 23.00 6.77 25.00 6.86 27.00 7.04 28.00 7.04 29.10 7.13 31.00 7.30 32.10 7.39 23.00 6.76 25.00 6.93 27.00 7.11 28.00 7.11 29.10 7.28 31.00 7.46 32.10 7.64
16 23.00 6.86 25.00 6.95 27.00 7.13 28.00 7.13 29.10 7.21 31.00 7.39 32.10 7.48 23.00 6.85 25.00 7.02 27.00 7.11 28.00 7.20 29.10 7.28 31.00 7.46 32.10 7.72
18 23.00 6.86 25.00 7.04 27.00 7.21 28.00 7.21 29.10 7.30 31.00 7.48 32.10 7.65 23.00 6.93 25.00 7.11 27.00 7.20 28.00 7.28 29.10 7.37 31.00 7.64 32.10 7.81
20 23.00 7.04 25.00 7.13 27.00 7.30 28.00 7.39 29.10 7.39 31.00 7.57 32.10 7.74 23.00 7.02 25.00 7.20 27.00 7.37 28.00 7.37 29.10 7.46 31.00 7.72 32.10 7.90
22 23.00 7.13 25.00 7.30 27.00 7.39 28.00 7.48 29.10 7.57 31.00 7.74 32.10 7.83 23.00 7.20 25.00 7.28 27.00 7.46 28.00 7.55 29.10 7.64 31.00 7.81 32.10 8.07
24 23.00 7.30 25.00 7.39 27.00 7.57 28.00 7.65 29.10 7.74 31.00 7.92 32.10 8.01 23.00 7.28 25.00 7.46 27.00 7.64 28.00 7.64 29.10 7.81 31.00 7.99 32.10 8.16
26 23.00 7.48 25.00 7.57 27.00 7.74 28.00 7.83 29.10 7.92 31.00 8.01 32.10 8.18 23.00 7.46 25.00 7.64 27.00 7.72 28.00 7.81 29.10 7.90 31.00 8.16 32.10 8.34
28 23.00 7.65 25.00 7.74 27.00 7.92 28.00 8.01 29.10 8.09 31.00 8.27 32.10 8.36 23.00 7.64 25.00 7.81 27.00 7.90 28.00 7.99 29.10 8.16 31.00 8.34 32.10 8.51
30 23.00 7.83 25.00 8.01 27.00 8.09 28.00 8.18 29.10 8.27 31.00 8.45 32.10 8.62 23.00 7.81 25.00 7.99 27.00 8.16 28.00 8.25 29.10 8.34 31.00 8.51 32.10 8.78
32 23.00 8.01 25.00 8.18 27.00 8.36 28.00 8.45 29.10 8.53 31.00 8.71 32.10 8.89 23.00 7.99 25.00 8.16 27.00 8.34 28.00 8.43 29.10 8.51 31.00 8.78 32.10 8.95
34 23.00 8.27 25.00 8.45 27.00 8.62 28.00 8.62 29.10 8.80 31.00 8.97 32.10 9.06 23.00 8.25 25.00 8.43 27.00 8.60 28.00 8.69 29.10 8.78 31.00 9.04 32.10 9.22
35 23.00 8.36 25.00 8.53 27.00 8.71 28.00 8.80 29.10 8.89 31.00 9.06 32.10 9.24 23.00 8.34 25.00 8.51 27.00 8.69 28.00 8.78 29.10 8.86 31.00 9.13 32.10 9.39
36 22.58 8.53 24.60 8.62 26.62 8.80 27.62 8.97 28.64 8.97 30.42 9.24 31.34 9.41 22.58 8.51 24.60 8.69 26.62 8.86 27.62 8.95 28.64 9.04 30.42 9.30 31.34 9.48
38 21.74 8.80 23.80 8.97 25.86 9.15 26.86 9.33 27.72 9.33 29.26 9.41 29.82 9.68 21.74 8.78 23.80 8.86 25.86 9.13 26.86 9.22 27.72 9.30 29.26 9.57 29.82 9.83
40 20.90 9.06 23.00 9.24 25.10 9.41 26.10 9.50 26.80 9.59 28.10 9.77 28.30 9.94 20.90 9.04 23.00 9.22 25.10 9.39 26.10 9.48 26.80 9.57 28.10 9.83 28.30 10.09

NOTE
• CAP: Capacity at compressor maximum frequency (kW)
• IPT: Input power (kW)
56 TCES0059 rev.2 - 06/2016
• TEMP: Outdoor air inlet temperature (DB (ºC))
4 Capacidades y datos de selección

Tablas de capacidad de enfriamiento

Potencia total de las unidades interiores combinadas: 130%


Potencia total de las
Temperatura delunidades interiores
aire de entrada combinadas:
interior (WB (ºC)) 130%
TEMP Temperatura
TEMP 14 16 18del aire de19
entrada interior
20 (WB (ºC)) 22 24
CAP 14IPT CAP 16IPT CAP 18IPT CAP 19IPT CAP 20IPT CAP 22IPT CAP 24IPT
10 CAP 5.93
23.00 IPT 25.00
CAP 6.09
IPT 27.00
CAP 6.18
IPT 28.00
CAP 6.26
IPT 29.10
CAP 6.34
IPT 31.00
CAP 6.51IPT 32.10
CAP 6.67
IPT
10
12 23.00
23.00 5.93
5.93 25.00
25.00 6.09
6.09 27.00
27.00 6.18
6.18 28.00
28.00 6.26
6.26 29.10
29.10 6.34
6.34 31.00
31.00 6.51
6.51 32.10
32.10 6.67
6.67
12
14 23.00
23.00 5.93
6.01 25.00
25.00 6.09
6.18 27.00
27.00 6.18
6.26 28.00
28.00 6.26
6.34 29.10
29.10 6.34
6.42 31.00
31.00 6.51
6.51 32.10
32.10 6.67
6.75
14
16 23.00
23.00 6.01
6.01 25.00
25.00 6.18
6.18 27.00
27.00 6.26
6.34 28.00
28.00 6.34
6.34 29.10
29.10 6.42
6.42 31.00
31.00 6.51
6.59 32.10
32.10 6.75
6.75
16
18 23.00
23.00 6.01
6.09 25.00
25.00 6.18
6.26 27.00
27.00 6.34
6.42 28.00
28.00 6.34
6.42 29.10
29.10 6.42
6.51 31.00
31.00 6.59
6.75 32.10
32.10 6.75
6.92
18
20 23.00
23.00 6.09
6.26 25.00
25.00 6.26
6.42 27.00
27.00 6.42
6.51 28.00
28.00 6.42
6.59 29.10
29.10 6.51
6.67 31.00
31.00 6.75
6.84 32.10
32.10 6.92
7.00
20
22 23.00
23.00 6.26
6.34 25.00
25.00 6.42
6.51 27.00
27.00 6.51
6.59 28.00
28.00 6.59
6.67 29.10
29.10 6.67
6.75 31.00
31.00 6.84
7.00 32.10
32.10 7.00
7.17
22
24 23.00
23.00 6.34
6.51 25.00
25.00 6.51
6.67 27.00
27.00 6.59
6.75 28.00
28.00 6.67
6.84 29.10
29.10 6.75
6.92 31.00
31.00 7.00
7.17 32.10
32.10 7.17
7.33
24
26 23.00
23.00 6.51
6.67 25.00
25.00 6.67
6.92 27.00
27.00 6.75
7.00 28.00
28.00 6.84
7.08 29.10
29.10 6.92
7.17 31.00
31.00 7.17
7.33 32.10
32.10 7.33
7.49
26
28 23.00
23.00 6.67
6.92 25.00
25.00 6.92
7.08 27.00
27.00 7.00
7.17 28.00
28.00 7.08
7.25 29.10
29.10 7.17
7.33 31.00
31.00 7.33
7.58 32.10
32.10 7.49
7.74
28
30 23.00
23.00 6.92
7.17 25.00
25.00 7.08
7.33 27.00
27.00 7.17
7.41 28.00
28.00 7.25
7.49 29.10
29.10 7.33
7.58 31.00
31.00 7.58
7.82 32.10
32.10 7.74
7.99
30
32 23.00
23.00 7.17
7.41 25.00
25.00 7.33
7.58 27.00
27.00 7.41
7.74 28.00
28.00 7.49
7.74 29.10
29.10 7.58
7.91 31.00
31.00 7.82
8.07 32.10
32.10 7.99
8.32
32
34 23.00
23.00 7.41
7.66 25.00
25.00 7.58
7.82 27.00
27.00 7.74
7.99 28.00
28.00 7.74
8.07 29.10
29.10 7.91
8.15 31.00
31.00 8.07
8.40 32.10
32.10 8.32
8.57
34
35 23.00
23.00 7.66
7.82 25.00
25.00 7.82
7.99 27.00
27.00 7.99
8.15 28.00
28.00 8.07
8.24 29.10
29.10 8.15
8.32 31.00
31.00 8.40
8.57 32.10
32.10 8.57
8.81
35
36 23.00
22.58 7.82
7.99 25.00
24.60 7.99
8.15 27.00
26.62 8.15
8.32 28.00
27.62 8.24
8.98 29.10
28.64 8.32
8.48 31.00
30.42 8.57
8.73 32.10
31.34 8.81
8.98
36
38 22.58
21.74 7.99
8.32 24.60
23.80 8.15
8.48 26.62
25.86 8.32
8.65 27.62
26.86 8.98
9.31 28.64
27.72 8.48
8.81 30.42
29.26 8.73
9.06 31.34
29.82 8.98
9.31
38
40 21.74
20.90 8.32
8.65 23.80
23.00 8.48
8.90 25.86
25.10 8.65
8.98 26.86
26.10 9.31
9.72 27.72
26.80 8.81
9.22 29.26
28.10 9.06
9.47 29.82
28.30 9.31
9.72
40 20.90 8.65 23.00 8.90 25.10 8.98 26.10 9.72 26.80 9.22 28.10 9.47 28.30 9.72


 RAS-12FSNM1
 RAS-12FSNM
RAS-12FSNM1
Potencia total de las unidades interiores combinadas: 50% Potencia total de las unidades interiores combinadas: 60%
Potencia total de del
Temperatura las aire
unidades interiores
de entrada combinadas:
interior (WB (ºC)) 50% Potencia total de del
Temperatura las aire
unidades interiores
de entrada combinadas:
interior (WB (ºC)) 60%
TEMP

4
14 Temperatura
16 18del aire de19
entrada interior
20 (WB (ºC))
22 24 14 Temperatura
16 18del aire de19
entrada interior
20 (WB (ºC))
22 24
TEMP
CAP14IPT CAP16IPT CAP18IPT CAP19IPT CAP20IPT CAP22IPT CAP24IPT CAP14IPT CAP16IPT CAP18IPT CAP19IPT CAP20IPT CAP22IPT CAP24IPT
10 CAP 4.30
13.79 IPT 14.99
CAP 4.35
IPT 16.20
CAP 4.39
IPT 16.80
CAP 4.44
IPT 17.35
CAP 4.44
IPT 18.25
CAP 4.44
IPT 18.76
CAP 4.49
IPT 16.53
CAP 4.91
IPT 17.98
CAP 5.24
IPT 19.42
CAP 5.50
IPT 20.14
CAP 5.63
IPT 20.80
CAP 5.56
IPT 21.88
CAP 5.50
IPT 22.48
CAP 5.43
IPT
10
12 13.79
13.79 4.30
4.35 14.99
14.99 4.35
4.39 16.20
16.20 4.39
4.44 16.80
16.80 4.44
4.49 17.35
17.35 4.44
4.49 18.25
18.25 4.44
4.49 18.76
18.76 4.49
4.49 16.53
16.53 4.91
4.98 17.98
17.98 5.24
5.24 19.42
19.42 5.50
5.50 20.14
20.14 5.63
5.63 20.80
20.80 5.56
5.56 21.88
21.88 5.50
5.50 22.48
22.48 5.43
5.43
12
14 13.79
13.79 4.35
4.35 14.99
14.99 4.39
4.39 16.20
16.20 4.44
4.49 16.80
16.80 4.49
4.49 17.35
17.35 4.49
4.49 18.25
18.25 4.49
4.54 18.76
18.76 4.49
4.54 16.53
16.53 4.98
4.98 17.98
17.98 5.24
5.24 19.42
19.42 5.50
5.50 20.14
20.14 5.63
5.63 20.80
20.80 5.56
5.63 21.88
21.88 5.50
5.56 22.48
22.48 5.43
5.43
14
16 13.79
13.79 4.35
4.39 14.99
14.99 4.39
4.44 16.20
16.20 4.49
4.49 16.80
16.80 4.49
4.54 17.35
17.35 4.49
4.54 18.25
18.25 4.54
4.54 18.76
18.76 4.54
4.58 16.53
16.53 4.98
4.98 17.98
17.98 5.24
5.24 19.42
19.42 5.50
5.56 20.14
20.14 5.63
5.63 20.80
20.80 5.63
5.63 21.88
21.88 5.56
5.56 22.48
22.48 5.43
5.50
16
18 13.79
13.79 4.39
4.39 14.99
14.99 4.44
4.49 16.20
16.20 4.49
4.54 16.80
16.80 4.54
4.58 17.35
17.35 4.54
4.58 18.25
18.25 4.54
4.58 18.76
18.76 4.58
4.58 16.53
16.53 4.98
5.04 17.98
17.98 5.24
5.30 19.42
19.42 5.56
5.56 20.14
20.14 5.63
5.69 20.80
20.80 5.63
5.69 21.88
21.88 5.56
5.63 22.48
22.48 5.50
5.56
18
20 13.79
13.79 4.39
4.44 14.99
14.99 4.49
4.49 16.20
16.20 4.54
4.58 16.80
16.80 4.58
4.63 17.35
17.35 4.58
4.63 18.25
18.25 4.58
4.63 18.76
18.76 4.58
4.63 16.53
16.53 5.04
5.11 17.98
17.98 5.30
5.37 19.42
19.42 5.56
5.63 20.14
20.14 5.69
5.75 20.80
20.80 5.69
5.75 21.88
21.88 5.63
5.63 22.48
22.48 5.56
5.56
20
22 13.79
13.79 4.44
4.49 14.99
14.99 4.49
4.54 16.20
16.20 4.58
4.58 16.80
16.80 4.63
4.63 17.35
17.35 4.63
4.63 18.25
18.25 4.63
4.63 18.76
18.76 4.63
4.63 16.53
16.53 5.11
5.11 17.98
17.98 5.37
5.43 19.42
19.42 5.63
5.69 20.14
20.14 5.75
5.82 20.80
20.80 5.75
5.75 21.88
21.88 5.63
5.69 22.48
22.48 5.56
5.63
22
24 13.79
13.79 4.49
4.49 14.99
14.99 4.54
4.58 16.20
16.20 4.58
4.63 16.80
16.80 4.63
4.63 17.35
17.35 4.63
4.68 18.25
18.25 4.63
4.68 18.76
18.76 4.63
4.68 16.53
16.53 5.11
5.24 17.98
17.98 5.43
5.50 19.42
19.42 5.69
5.75 20.14
20.14 5.82
5.88 20.80
20.80 5.75
5.82 21.88
21.88 5.69
5.75 22.48
22.48 5.63
5.75
24
26 13.79
13.79 4.49
4.54 14.99
14.99 4.58
4.58 16.20
16.20 4.63
4.63 16.80
16.80 4.63
4.68 17.35
17.35 4.68
4.68 18.25
18.25 4.68
4.68 18.76
18.76 4.68
4.73 16.53
16.53 5.24
5.24 17.98
17.98 5.50
5.56 19.42
19.42 5.75
5.82 20.14
20.14 5.88
5.95 20.80
20.80 5.82
5.95 21.88
21.88 5.75
5.88 22.48
22.48 5.75
5.82
26
28 13.79
13.79 4.54
4.54 14.99
14.99 4.58
4.63 16.20
16.20 4.63
4.68 16.80
16.80 4.68
4.73 17.35
17.35 4.68
4.73 18.25
18.25 4.68
4.73 18.76
18.76 4.73
4.73 16.53
16.53 5.24
5.37 17.98
17.98 5.56
5.63 19.42
19.42 5.82
5.95 20.14
20.14 5.95
6.08 20.80
20.80 5.95
6.01 21.88
21.88 5.88
5.95 22.48
22.48 5.82
5.88
28
30 13.79
13.79 4.54
4.58 14.99
14.99 4.63
4.63 16.20
16.20 4.68
4.68 16.80
16.80 4.73
4.73 17.35
17.35 4.73
4.73 18.25
18.25 4.73
4.73 18.76
18.76 4.73
4.78 16.53
16.53 5.37
5.43 17.98
17.98 5.63
5.75 19.42
19.42 5.95
6.01 20.14
20.14 6.08
6.14 20.80
20.80 6.01
6.14 21.88
21.88 5.95
6.08 22.48
22.48 5.88
6.01
30
32 13.79
13.79 4.58
4.58 14.99
14.99 4.63
4.63 16.20
16.20 4.68
4.73 16.80
16.80 4.73
4.78 17.35
17.35 4.73
4.78 18.25
18.25 4.73
4.78 18.76
18.76 4.78
4.78 16.53
16.53 5.43
5.56 17.98
17.98 5.75
5.82 19.42
19.42 6.01
6.14 20.14
20.14 6.14
6.27 20.80
20.80 6.14
6.27 21.88
21.88 6.08
6.14 22.48
22.48 6.01
6.08
32
34 13.79
13.79 4.58
4.63 14.99
14.99 4.63
4.68 16.20
16.20 4.73
4.73 16.80
16.80 4.78
4.78 17.35
17.35 4.78
4.78 18.25
18.25 4.78
4.78 18.76
18.76 4.78
4.78 16.53
16.53 5.56
5.63 17.98
17.98 5.82
5.95 19.42
19.42 6.14
6.27 20.14
20.14 6.27
6.40 20.80
20.80 6.27
6.34 21.88
21.88 6.14
6.27 22.48
22.48 6.08
6.21
34
35 13.79
13.79 4.63
4.63 14.99
14.99 4.68
4.68 16.20
16.20 4.73
4.73 16.80
16.80 4.78
4.78 17.35
17.35 4.78
4.78 18.25
18.25 4.78
4.78 18.76
18.76 4.78
4.78 16.53
16.53 5.63
5.69 17.98
17.98 5.95
6.01 19.42
19.42 6.27
6.34 20.14
20.14 6.40
6.47 20.80
20.80 6.34
6.47 21.88
21.88 6.27
6.34 22.48
22.48 6.21
6.27
35
36 13.79
13.62 4.63
4.63 14.99
14.69 4.68
4.68 16.20
15.77 4.73
4.78 16.80
16.31 4.78
4.82 17.35
16.77 4.78
4.78 18.25
17.54 4.78
4.78 18.76
17.96 4.78
4.82 16.53
16.33 5.69
5.75 17.98
17.61 6.01
6.08 19.42
18.90 6.34
6.40 20.14
19.55 6.47
6.34 20.80
20.10 6.47
6.53 21.88
21.03 6.34
6.47 22.48
21.53 6.27
6.34
36
38 13.62
13.28 4.63
4.63 14.69
14.09 4.68
4.68 15.77
14.90 4.78
4.78 16.31
15.33 4.82
4.82 16.77
15.61 4.78
4.82 17.54
16.12 4.78
4.82 17.96
16.38 4.82
4.82 16.33
15.92 5.75
5.88 17.61
16.89 6.08
6.21 18.90
17.87 6.40
6.53 19.55
18.37 6.34
6.47 20.10
18.71 6.53
6.66 21.03
19.32 6.47
6.60 21.53
19.63 6.34
6.47
38
40 13.28
12.94 4.63
4.63 14.09
13.49 4.68
4.73 14.90
14.04 4.78
4.78 15.33
14.34 4.82
4.82 15.61
14.44 4.82
4.82 16.12
14.69 4.82
4.82 16.38
14.79 4.82
4.82 15.92
15.51 5.88
6.08 16.89
16.17 6.21
6.34 17.87
16.83 6.53
6.66 18.37
17.19 6.47
6.66 18.71
17.31 6.66
6.79 19.32
17.61 6.60
6.72 19.63
17.74 6.47
6.66
40 12.94 4.63 13.49 4.73 14.04 4.78 14.34 4.82 14.44 4.82 14.69 4.82 14.79 4.82 15.51 6.08 16.17 6.34 16.83 6.66 17.19 6.66 17.31 6.79 17.61 6.72 17.74 6.66

Potencia total de las unidades interiores combinadas: 70% Potencia total de las unidades interiores combinadas: 80%
Potencia total de del
Temperatura las aire
unidades interiores
de entrada combinadas:
interior (WB (ºC)) 70% Potencia total de del
Temperatura las aire
unidades interiores
de entrada combinadas:
interior (WB (ºC)) 80%
TEMP Temperatura del aire de entrada interior (WB (ºC)) Temperatura
TEMP 14 16 18 19 20 22 24 14 16 18del aire de19
entrada interior
20 (WB (ºC))
22 24
CAP14IPT CAP16IPT CAP18IPT CAP19IPT CAP20IPT CAP22IPT CAP24IPT CAP14IPT CAP16IPT CAP18IPT CAP19IPT CAP20IPT CAP22IPT CAP24IPT
10 CAP 6.24
19.27 IPT 20.96
CAP 6.48
IPT 22.64
CAP 6.64
IPT 23.48
CAP 6.80
IPT 24.25
CAP 6.80
IPT 25.51
CAP 6.80
IPT 26.21
CAP 6.88
IPT 22.02
CAP 7.54
IPT 23.94
CAP 7.63
IPT 25.86
CAP 7.73
IPT 26.82
CAP 7.82
IPT 27.70
CAP 7.91
IPT 29.14
CAP 8.00
IPT 29.94
CAP 8.18
IPT
10
12 19.27
19.27 6.24
6.32 20.96
20.96 6.48
6.48 22.64
22.64 6.64
6.72 23.48
23.48 6.80
6.80 24.25
24.25 6.80
6.80 25.51
25.51 6.80
6.80 26.21
26.21 6.88
6.88 22.02
22.02 7.54
7.54 23.94
23.94 7.63
7.63 25.86
25.86 7.73
7.82 26.82
26.82 7.82
7.82 27.70
27.70 7.91
7.91 29.14
29.14 8.00
8.00 29.94
29.94 8.18
8.18
12
14 19.27
19.27 6.32
6.32 20.96
20.96 6.48
6.56 22.64
22.64 6.72
6.72 23.48
23.48 6.80
6.80 24.25
24.25 6.80
6.80 25.51
25.51 6.80
6.88 26.21
26.21 6.88
6.88 22.02
22.02 7.54
7.63 23.94
23.94 7.63
7.73 25.86
25.86 7.82
7.82 26.82
26.82 7.82
7.91 27.70
27.70 7.91
7.91 29.14
29.14 8.00
8.09 29.94
29.94 8.18
8.18
14
16 19.27
19.27 6.32
6.32 20.96
20.96 6.56
6.56 22.64
22.64 6.72
6.72 23.48
23.48 6.80
6.88 24.25
24.25 6.80
6.88 25.51
25.51 6.88
6.88 26.21
26.21 6.88
6.95 22.02
22.02 7.63
7.63 23.94
23.94 7.73
7.73 25.86
25.86 7.82
7.82 26.82
26.82 7.91
7.91 27.70
27.70 7.91
8.00 29.14
29.14 8.09
8.09 29.94
29.94 8.18
8.27
16
18 19.27
19.27 6.32
6.40 20.96
20.96 6.56
6.56 22.64
22.64 6.72
6.80 23.48
23.48 6.88
6.88 24.25
24.25 6.88
6.95 25.51
25.51 6.88
6.95 26.21
26.21 6.95
7.03 22.02
22.02 7.63
7.63 23.94
23.94 7.73
7.82 25.86
25.86 7.82
7.91 26.82
26.82 7.91
8.00 27.70
27.70 8.00
8.09 29.14
29.14 8.09
8.18 29.94
29.94 8.27
8.36
18
20 19.27
19.27 6.40
6.48 20.96
20.96 6.56
6.64 22.64
22.64 6.80
6.88 23.48
23.48 6.88
6.95 24.25
24.25 6.95
6.95 25.51
25.51 6.95
7.03 26.21
26.21 7.03
7.03 22.02
22.02 7.63
7.73 23.94
23.94 7.82
7.91 25.86
25.86 7.91
8.00 26.82
26.82 8.00
8.09 27.70
27.70 8.09
8.09 29.14
29.14 8.18
8.27 29.94
29.94 8.36
8.45
20
22 19.27
19.27 6.48
6.56 20.96
20.96 6.64
6.72 22.64
22.64 6.88
6.95 23.48
23.48 6.95
7.03 24.25
24.25 6.95
7.03 25.51
25.51 7.03
7.11 26.21
26.21 7.03
7.11 22.02
22.02 7.73
7.82 23.94
23.94 7.91
8.00 25.86
25.86 8.00
8.09 26.82
26.82 8.09
8.09 27.70
27.70 8.09
8.18 29.14
29.14 8.27
8.36 29.94
29.94 8.45
8.54
22
24 19.27
19.27 6.56
6.64 20.96
20.96 6.72
6.80 22.64
22.64 6.95
7.03 23.48
23.48 7.03
7.11 24.25
24.25 7.03
7.19 25.51
25.51 7.11
7.19 26.21
26.21 7.11
7.27 22.02
22.02 7.82
8.00 23.94
23.94 8.00
8.09 25.86
25.86 8.09
8.18 26.82
26.82 8.09
8.27 27.70
27.70 8.18
8.27 29.14
29.14 8.36
8.45 29.94
29.94 8.54
8.63
24
26 19.27
19.27 6.64
6.72 20.96
20.96 6.80
6.95 22.64
22.64 7.03
7.11 23.48
23.48 7.11
7.27 24.25
24.25 7.19
7.27 25.51
25.51 7.19
7.27 26.21
26.21 7.27
7.35 22.02
22.02 8.00
8.09 23.94
23.94 8.09
8.18 25.86
25.86 8.18
8.27 26.82
26.82 8.27
8.36 27.70
27.70 8.27
8.45 29.14
29.14 8.45
8.63 29.94
29.94 8.63
8.72
26
28 19.27
19.27 6.72
6.80 20.96
20.96 6.95
7.03 22.64
22.64 7.11
7.27 23.48
23.48 7.27
7.35 24.25
24.25 7.27
7.43 25.51
25.51 7.27
7.43 26.21
26.21 7.35
7.43 22.02
22.02 8.09
8.18 23.94
23.94 8.18
8.27 25.86
25.86 8.27
8.45 26.82
26.82 8.36
8.45 27.70
27.70 8.45
8.54 29.14
29.14 8.63
8.72 29.94
29.94 8.72
8.91
28
30 19.27
19.27 6.80
6.95 20.96
20.96 7.03
7.19 22.64
22.64 7.27
7.35 23.48
23.48 7.35
7.51 24.25
24.25 7.43
7.51 25.51
25.51 7.43
7.51 26.21
26.21 7.43
7.59 22.02
22.02 8.18
8.36 23.94
23.94 8.27
8.45 25.86
25.86 8.45
8.63 26.82
26.82 8.45
8.63 27.70
27.70 8.54
8.72 29.14
29.14 8.72
8.91 29.94
29.94 8.91
9.09
30
32 19.27
19.27 6.95
7.03 20.96
20.96 7.19
7.27 22.64
22.64 7.35
7.51 23.48
23.48 7.51
7.59 24.25
24.25 7.51
7.67 25.51
25.51 7.51
7.67 26.21
26.21 7.59
7.75 22.02
22.02 8.36
8.45 23.94
23.94 8.45
8.63 25.86
25.86 8.63
8.72 26.82
26.82 8.63
8.82 27.70
27.70 8.72
8.91 29.14
29.14 8.91
9.09 29.94
29.94 9.09
9.18
32
34 19.27
19.27 7.03
7.19 20.96
20.96 7.27
7.43 22.64
22.64 7.51
7.67 23.48
23.48 7.59
7.75 24.25
24.25 7.67
7.82 25.51
25.51 7.67
7.82 26.21
26.21 7.75
7.90 22.02
22.02 8.45
8.63 23.94
23.94 8.63
8.82 25.86
25.86 8.72
8.91 26.82
26.82 8.82
9.00 27.70
27.70 8.91
9.09 29.14
29.14 9.09
9.27 29.94
29.94 9.18
9.36
34
35 19.27
19.27 7.19
7.35 20.96
20.96 7.43
7.51 22.64
22.64 7.67
7.75 23.48
23.48 7.75
7.90 24.25
24.25 7.82
7.90 25.51
25.51 7.82
7.98 26.21
26.21 7.90
7.98 22.02
22.02 8.63
8.72 23.94
23.94 8.82
8.91 25.86
25.86 8.91
9.00 26.82
26.82 9.00
9.09 27.70
27.70 9.09
9.18 29.14
29.14 9.27
9.36 29.94
29.94 9.36
9.54
35
36 19.27
19.04 7.35
7.35 20.96
20.54 7.51
7.59 22.64
22.04 7.75
7.82 23.48
22.79 7.90
7.98 24.25
23.44 7.90
7.98 25.51
24.52 7.98
7.98 26.21
25.11 7.98
8.06 22.02
21.74 8.72
8.82 23.94
23.46 8.91
9.00 25.86
25.17 9.00
9.09 26.82
26.04 9.09
9.27 27.70
26.77 9.18
9.27 29.14
28.00 9.36
9.45 29.94
28.68 9.54
9.63
36
38 19.04
18.56 7.35
7.51 20.54
19.70 7.59
7.75 22.04
20.83 7.82
7.98 22.79
21.42 7.98
8.06 23.44
21.81 7.98
8.14 24.52
22.53 7.98
8.22 25.11
22.89 8.06
8.22 21.74
21.20 8.82
9.09 23.46
22.50 9.00
9.18 25.17
23.79 9.09
9.36 26.04
24.47 9.27
9.63 26.77
24.91 9.27
9.45 28.00
25.73 9.45
9.63 28.68
26.15 9.63
9.82
38
40 18.56
18.08 7.51
7.75 19.70
18.85 7.75
7.98 20.83
19.63 7.98
8.22 21.42
20.05 8.06
8.14 21.81
20.19 8.14
8.38 22.53
20.54 8.22
8.38 22.89
20.68 8.22
8.46 21.20
20.66 9.09
9.27 22.50
21.54 9.18
9.45 23.79
22.42 9.36
9.54 24.47
22.90 9.63
9.82 24.91
23.06 9.45
9.72 25.73
23.46 9.63
9.91 26.15
23.62 9.82
10.09
40 18.08 7.75 18.85 7.98 19.63 8.22 20.05 8.14 20.19 8.38 20.54 8.38 20.68 8.46 20.66 9.27 21.54 9.45 22.42 9.54 22.90 9.82 23.06 9.72 23.46 9.91 23.62 10.09

NOTE
NOTE
• CAP: Capacity at compressor maximum frequency (kW)
• CAP: Capacity at compressor maximum frequency (kW)
• IPT: Input power (kW)
• IPT: Input power (kW)
• TEMP: Outdoor air inlet temperature (DB (ºC))
• TEMP: Outdoor air inlet temperature (DB (ºC))

57 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Tablas de capacidad de enfriamiento

Potencia total de las unidades interiores combinadas: 90% Potencia total de las unidades interiores combinadas: 100%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 24.76 8.22 26.92 8.32 29.08 8.52 30.16 8.52 31.15 8.52 32.77 8.52 33.67 8.52 27.50 8.77 29.90 8.88 32.30 9.10 33.50 9.10 34.60 9.10 36.40 8.88 37.40 8.67
12 24.76 8.22 26.92 8.42 29.08 8.52 30.16 8.62 31.15 8.62 32.77 8.52 33.67 8.52 27.50 8.77 29.90 8.88 32.30 9.10 33.50 9.20 34.60 9.10 36.40 8.88 37.40 8.67
14 24.76 8.22 26.92 8.42 29.08 8.52 30.16 8.62 31.15 8.62 32.77 8.52 33.67 8.52 27.50 8.77 29.90 8.88 32.30 9.10 33.50 9.20 34.60 9.10 36.40 8.88 37.40 8.67
16 24.76 8.32 26.92 8.42 29.08 8.62 30.16 8.62 31.15 8.62 32.77 8.62 33.67 8.62 27.50 8.88 29.90 8.99 32.30 9.20 33.50 9.20 34.60 9.10 36.40 8.88 37.40 8.77
18 24.76 8.42 26.92 8.52 29.08 8.62 30.16 8.72 31.15 8.72 32.77 8.72 33.67 8.62 27.50 8.88 29.90 9.10 32.30 9.20 33.50 9.31 34.60 9.20 36.40 8.99 37.40 8.77
20 24.76 8.42 26.92 8.62 29.08 8.72 30.16 8.82 31.15 8.82 32.77 8.72 33.67 8.72 27.50 8.99 29.90 9.10 32.30 9.31 33.50 9.42 34.60 9.31 36.40 9.10 37.40 8.88
22 24.76 8.52 26.92 8.72 29.08 8.82 30.16 8.92 31.15 8.92 32.77 8.92 33.67 8.82 27.50 9.10 29.90 9.20 32.30 9.42 33.50 9.52 34.60 9.42 36.40 9.20 37.40 8.99
24 24.76 8.72 26.92 8.82 29.08 8.92 30.16 9.02 31.15 9.02 32.77 8.92 33.67 8.92 27.50 9.20 29.90 9.42 32.30 9.52 33.50 9.63 34.60 9.52 36.40 9.31 37.40 9.10
26 24.76 8.82 26.92 8.92 29.08 9.12 30.16 9.12 31.15 9.12 32.77 9.12 33.67 9.02 27.50 9.31 29.90 9.52 32.30 9.74 33.50 9.74 34.60 9.63 36.40 9.52 37.40 9.31
28 24.76 8.92 26.92 9.12 29.08 9.22 30.16 9.32 31.15 9.32 32.77 9.22 33.67 9.22 27.50 9.52 29.90 9.74 32.30 9.84 33.50 9.95 34.60 9.84 36.40 9.63 37.40 9.42
30 24.76 9.12 26.92 9.22 29.08 9.42 30.16 9.52 31.15 9.52 32.77 9.42 33.67 9.42 27.50 9.74 29.90 9.84 32.30 10.06 33.50 10.17 34.60 10.06 36.40 9.84 37.40 9.63
32 24.76 9.32 26.92 9.42 29.08 9.62 30.16 9.72 31.15 9.72 32.77 9.62 33.67 9.62 27.50 9.84 29.90 10.06 32.30 10.27 33.50 10.38 34.60 10.27 36.40 10.06 37.40 9.84
34 24.76 9.52 26.92 9.62 29.08 9.82 30.16 9.92 31.15 9.92 32.77 9.82 33.67 9.82 27.50 10.06 29.90 10.27 32.30 10.49 33.50 10.59 34.60 10.49 36.40 10.27 37.40 10.06
35 24.76 9.62 26.92 9.82 29.08 9.92 30.16 10.02 31.15 10.02 32.77 9.92 33.67 9.92 27.50 10.27 29.90 10.38 32.30 10.59 33.50 10.70 34.60 10.59 36.40 10.38 37.40 10.17
36 24.45 9.72 26.38 9.92 28.31 10.02 29.28 10.02 30.11 10.12 31.49 10.02 32.25 10.02 27.16 10.38 29.30 10.49 31.44 10.70 32.52 10.91 33.44 10.70 34.98 10.49 35.82 10.27
38 23.84 9.92 25.30 10.12 26.76 10.32 27.51 10.22 28.02 10.32 28.94 10.32 29.40 10.22 26.48 10.59 28.10 10.81 29.72 11.02 30.56 11.24 31.12 11.02 32.14 10.70 32.66 10.49
40 23.23 10.22 24.22 10.32 25.21 10.52 25.75 10.52 25.93 10.62 26.38 10.52 26.56 10.52 25.80 10.91 26.90 11.13 28.00 11.34 28.60 11.24 28.80 11.24 29.30 11.02 29.50 10.81

Potencia total de las unidades interiores combinadas: 110% Potencia total de las unidades interiores combinadas: 120%
Temperatura del aire de entrada interior (WB (ºC)) Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24 14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 27.50 8.57 29.90 8.68 32.30 8.79 33.50 8.91 34.60 9.02 36.40 9.24 37.40 9.36 27.50 8.54 29.90 8.76 32.30 9.00 33.50 9.00 34.60 9.10 36.40 9.44 37.40 9.66
12 27.50 8.57 29.90 8.79 32.30 8.91 33.50 9.02 34.60 9.13 36.40 9.24 37.40 9.47 27.50 8.66 29.90 8.88 32.30 9.00 33.50 9.10 34.60 9.22 36.40 9.44 37.40 9.66
14 27.50 8.68 29.90 8.79 32.30 9.02 33.50 9.02 34.60 9.13 36.40 9.36 37.40 9.47 27.50 8.66 29.90 8.88 32.30 9.10 33.50 9.10 34.60 9.34 36.40 9.56 37.40 9.78
16 27.50 8.79 29.90 8.91 32.30 9.13 33.50 9.13 34.60 9.24 36.40 9.47 37.40 9.58 27.50 8.76 29.90 9.00 32.30 9.10 33.50 9.22 34.60 9.34 36.40 9.56 37.40 9.90
18 27.50 8.79 29.90 9.02 32.30 9.24 33.50 9.24 34.60 9.36 36.40 9.58 37.40 9.81 27.50 8.88 29.90 9.10 32.30 9.22 33.50 9.34 34.60 9.44 36.40 9.78 37.40 10.00
20 27.50 9.02 29.90 9.13 32.30 9.36 33.50 9.47 34.60 9.47 36.40 9.70 37.40 9.92 27.50 9.00 29.90 9.22 32.30 9.44 33.50 9.44 34.60 9.56 36.40 9.90 37.40 10.12
22 27.50 9.13 29.90 9.36 32.30 9.47 33.50 9.58 34.60 9.70 36.40 9.92 37.40 10.03 27.50 9.22 29.90 9.34 32.30 9.56 33.50 9.66 34.60 9.78 36.40 10.00 37.40 10.34
24 27.50 9.36 29.90 9.47 32.30 9.70 33.50 9.81 34.60 9.92 36.40 10.15 37.40 10.26 27.50 9.34 29.90 9.56 32.30 9.78 33.50 9.78 34.60 10.00 36.40 10.24 37.40 10.46
26 27.50 9.58 29.90 9.70 32.30 9.92 33.50 10.03 34.60 10.15 36.40 10.26 37.40 10.48 27.50 9.56 29.90 9.78 32.30 9.90 33.50 10.00 34.60 10.12 36.40 10.46 37.40 10.68
28 27.50 9.81 29.90 9.92 32.30 10.15 33.50 10.26 34.60 10.37 36.40 10.60 37.40 10.71 27.50 9.78 29.90 10.00 32.30 10.12 33.50 10.24 34.60 10.46 36.40 10.68 37.40 10.90
30 27.50 10.03 29.90 10.26 32.30 10.37 33.50 10.48 34.60 10.60 36.40 10.82 37.40 11.05 27.50 10.00 29.90 10.24 32.30 10.46 33.50 10.56 34.60 10.68 36.40 10.90 37.40 11.24
32 27.50 10.26 29.90 10.48 32.30 10.71 33.50 10.82 34.60 10.94 36.40 11.16 37.40 11.39 27.50 10.24 29.90 10.46 32.30 10.68 33.50 10.80 34.60 10.90 36.40 11.24 37.40 11.46
34 27.50 10.60 29.90 10.82 32.30 11.05 33.50 11.05 34.60 11.27 36.40 11.50 37.40 11.61 27.50 10.56 29.90 10.80 32.30 11.02 33.50 11.14 34.60 11.24 36.40 11.58 37.40 11.80
35 27.50 10.71 29.90 10.94 32.30 11.16 33.50 11.27 34.60 11.39 36.40 11.61 37.40 11.84 27.50 10.68 29.90 10.90 32.30 11.14 33.50 11.24 34.60 11.36 36.40 11.70 37.40 12.02
36 27.16 10.94 29.30 11.05 31.44 11.27 32.52 11.50 33.44 11.50 34.98 11.84 35.82 12.06 27.16 10.90 29.30 11.14 31.44 11.36 32.52 11.46 33.44 11.58 34.98 11.92 35.82 12.14
38 26.48 11.27 28.10 11.50 29.72 11.72 30.56 11.95 31.12 11.95 32.14 12.06 32.66 12.40 26.48 11.24 28.10 11.36 29.72 11.70 30.56 11.80 31.12 11.92 32.14 12.26 32.66 12.60
40 25.80 11.61 26.90 11.84 28.00 12.06 28.60 12.18 28.80 12.29 29.30 12.51 29.50 12.74 25.80 11.58 26.90 11.80 28.00 12.02 28.60 12.14 28.80 12.26 29.30 12.60 29.50 12.92

Potencia total de las unidades interiores combinadas: 110%


Temperatura del aire de entrada interior (WB (ºC))
TEMP
14 16 18 19 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
10 27,50 7,63 29,90 7,83 32,30 7,95 33,50 8,05 34,60 8,15 36,40 8,37 37,40 8,58
12 27,50 7,63 29,90 7,83 32,30 7,95 33,50 8,05 34,60 8,15 36,40 8,37 37,40 8,58
14 27,50 7,73 29,90 7,95 32,30 8,05 33,50 8,15 34,60 8,26 36,40 8,37 37,40 8,70
16 27,50 7,73 29,90 7,95 32,30 8,15 33,50 8,15 34,60 8,26 36,40 8,48 37,40 8,70
18 27,50 7,83 29,90 8,05 32,30 8,26 33,50 8,26 34,60 8,37 36,40 8,70 37,40 8,90
20 27,50 8,05 29,90 8,26 32,30 8,37 33,50 8,48 34,60 8,58 36,40 8,80 37,40 9,00
22 27,50 8,15 29,90 8,37 32,30 8,48 33,50 8,58 34,60 8,70 36,40 9,00 37,40 9,22
24 27,50 8,37 29,90 8,58 32,30 8,70 33,50 8,80 34,60 8,90 36,40 9,22 37,40 9,42
26 27,50 8,58 29,90 8,90 32,30 9,00 33,50 9,12 34,60 9,22 36,40 9,42 37,40 9,64
28 27,50 8,90 29,90 9,12 32,30 9,22 33,50 9,32 34,60 9,42 36,40 9,74 37,40 9,96
30 27,50 9,22 29,90 9,42 32,30 9,54 33,50 9,64 34,60 9,74 36,40 10,07 37,40 10,27
32 27,50 9,54 29,90 9,74 32,30 9,96 33,50 9,96 34,60 10,17 36,40 10,39 37,40 10,71
34 27,50 9,85 29,90 10,07 32,30 10,27 33,50 10,39 34,60 10,49 36,40 10,81 37,40 11,01
35 27,50 10,07 29,90 10,27 32,30 10,49 33,50 10,59 34,60 10,71 36,40 11,01 37,40 11,33
36 27,16 10,27 29,30 10,49 31,44 10,71 32,52 11,55 33,44 10,91 34,98 11,23 35,82 11,55
38 26,48 10,71 28,10 10,91 29,72 11,13 30,56 11,98 31,12 11,33 32,14 11,66 32,66 11,98
40 25,80 11,13 26,90 11,44 28,00 11,55 28,60 12,50 28,80 11,86 29,30 12,18 29,50 12,50

NOTE
• CAP: Capacity at compressor maximum frequency (kW); IPT: Input power (kW)
• TEMP: Outdoor air inlet temperature (DB (ºC))

58 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Tablas de capacidad de calefacción

 Índice de corrección debido a la humedad (CR)


Los datos de la capacidad de enfriamiento para las unidades exteriores se extraen de la tabla del apartado “4.2.2 Tablas
de capacidad de enfriamiento nominal”, y están calculados en base a una humedad relativa del 50%.
En algunos casos, es posible que la condición de la temperatura del ambiente a acondicionar, especifique otra
humedad relativa distinta, lo que afecta a la temperatura de Bulbo seco. En ese caso, debe calcular la diferencia entre
la temperatura de bulbo seco de entrada de aire interior requerida por el sistema y la temperatura de bulbo seco de
entrada de aire interior que aparece en los datos de la capacidad de enfriamiento.
Esta diferencia de temperatura requiere un ajuste de la capacidad de calor sensible para las unidades interiores.
Este coeficiente corrige la capacidad de calor sensible de una unidad de acuerdo con la humedad relativa del aire que
entra en la unidad interior. Cuanto mayor sea la humedad relativa menor será la capacidad de calor sensible y viceversa.

Unidad exterior CR

RAS-8FSNM 0,74

4
RAS-10FSNM 0,88
RAS-12FSNM 1,01

4.3 Tablas de capacidad de calefacción


El siguiente diagrama muestra el comportamiento de la capacidad de calefacción de la unidad exterior con la potencia
total de las unidades interiores combinadas de hasta el 130%.
Consulte los ejemplos de las combinaciones reales.
4.3.1  Curva de capacidad de calefacción

Curva de capacidad de calefacción

Curvas características
Capacidad de calefacción (kW)

de las distintas
100 %
unidades exteriores

100 % 130 %

Potencia total de las unidades interiores combinadas (CV)

59 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Tablas de capacidad de calefacción

4.3.2  Tablas de capacidad de calefacción nominal

Capacidad nominal a 20ºC (bulbo seco) y 6ºC (bulbo húmedo)


(kW)
CV unidades exteriores
Potencia total de las 8 10 12
unidades interiores
combinadas (%) Capacidad Potencia eléctrica Capacidad Potencia eléctrica Capacidad Potencia eléctrica
máxima consumida máxima consumida máxima consumida
1.1.2 Nominal
130 heating
25,00 capacity 6,18
tables 31,50 7,74 37,50 10,10
Nominal 120
capacity at 20 °C25,00
(Dry Bulb) and 66,39
°C (Wet Bulb) 31,50 8,22 37,50 10,40
110 25,00 6,30 31,50 8,24 37,50 10,34 (kW)
Total 25,00 Outdoor units HP
100 5,90 31,50 7,80 37,50 9,90
horsepower 8 10 12
90 22,50 5,52 28,36 7,32 33,76 9,36
of combined Maximum Electrical power Maximum Electrical power Maximum Electrical power
80 indoor units 20,00
(%) capacity 5,03
consumed 25,22
capacity 6,67
consumed 30,02
capacity 8,62
consumed
70 17,50 4,43 22,08 5,86 26,28 7,67
130 25.00 6.18 31.50 7.74 37.50 10.10
60 15,00 3,72 18,94 4,88 22,54 6,51
120 25.00 6.39 31.50 8.22 37.50 10.40
50 12,50 2,90 15,80 3,74 18,80 5,15
110 25.00 6.30 31.50 8.24 37.50 10.34
100 25.00 5.90 31.50 7.80 37.50 9.90
4.3.3  Tablas de capacidad de calefacción según potencia total de unidades interiores
combinadas 90 22.50 5.52 28.36 7.32 33.76 9.36
80 20.00 5.03 25.22 6.67 30.02 8.62
 RAS-8FSNM 70 17.50 4.43 22.08 5.86 26.28 7.67
60 15.00 3.72 18.94 4.88 22.54 6.51

? N O TA 50 12.50 2.90 15.80 3.74 18.80 5.15

• CAP: Capacidad a máxima frecuencia del compresor (kW)


1.1.3 Heating capacity tables according to Potencia total de las unidades interiores combinadas
• IPT: Potencia de entrada (kW)

 TEMP:
• Temperatura del aire de entrada exterior (WB (ºC))
RAS-8FSNM1
Potencia total de las unidades interiores combinadas: 50% Potencia total de las unidades interiores combinadas: 60%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 7.95 2.67 7.75 2.78 7.70 2.90 7.60 3.07 7.50 3.25 9.54 3.42 9.30 3.57 9.24 3.72 9.12 3.94 9.00 4.16
-17 8.40 2.64 8.23 2.76 8.18 2.87 8.08 3.05 7.98 3.19 10.08 3.38 9.88 3.53 9.82 3.68 9.70 3.90 9.58 4.09
-15 8.70 5.22 8.55 5.25 8.50 5.31 8.40 5.54 8.30 5.77 10.44 6.51 10.26 6.65 10.20 6.77 10.08 7.10 9.96 7.47
-13 9.00 4.82 8.87 4.84 8.82 4.87 8.72 5.11 8.62 5.31 10.80 6.02 10.64 6.13 10.58 6.25 10.46 6.58 10.34 6.88
-11 9.30 4.41 9.19 4.44 9.14 4.47 9.04 4.67 8.94 4.87 11.16 5.50 11.03 5.65 10.97 5.73 10.85 6.02 10.73 6.32
-10 9.45 4.21 9.35 4.23 9.30 4.26 9.20 4.45 9.10 4.64 11.34 5.26 11.22 5.39 11.16 5.47 11.04 5.76 10.92 6.04
-9 9.60 4.00 9.51 4.03 9.46 4.06 9.36 4.23 9.26 4.41 11.52 5.02 11.41 5.13 11.35 5.20 11.23 5.50 11.11 5.76
-7 9.90 3.60 9.83 3.63 9.78 3.63 9.68 3.80 9.58 3.94 11.88 4.54 11.80 4.61 11.74 4.68 11.62 4.94 11.50 5.20
-6 10.05 3.36 9.99 3.39 9.94 3.42 9.84 3.57 9.74 3.71 12.06 4.28 11.99 4.35 11.93 4.42 11.81 4.68 11.69 4.91
-5 10.20 3.31 10.15 3.31 10.10 3.34 10.00 3.51 9.90 3.65 12.24 4.16 12.18 4.24 12.12 4.31 12.00 4.54 11.88 4.76
-3 10.78 3.13 10.71 3.16 10.64 3.16 10.54 3.34 10.40 3.45 12.94 3.90 12.85 3.98 12.77 4.05 12.65 4.28 12.48 4.50
-1 11.36 2.96 11.27 2.99 11.18 3.02 11.08 3.13 10.90 3.28 13.63 3.68 13.52 3.76 13.42 3.79 13.30 4.02 13.08 4.20
0 11.65 2.89 11.55 2.92 11.45 2.93 11.35 3.06 11.15 3.19 13.98 3.55 13.86 3.62 13.74 3.66 13.62 3.89 13.38 4.07
1 12.61 2.81 12.36 2.84 12.08 2.84 11.71 2.99 11.15 3.10 15.13 3.42 14.83 3.49 14.50 3.53 14.05 3.76 13.38 3.94
3 13.25 2.70 12.90 2.73 12.50 2.73 11.95 2.84 11.15 2.99 15.90 3.49 15.48 3.57 15.00 3.61 14.34 3.79 13.38 4.02
5 13.25 2.78 12.90 2.81 12.50 2.84 11.95 2.96 11.15 3.07 15.90 3.57 15.48 3.61 15.00 3.68 14.34 3.87 13.38 4.09
6 13.35 2.84 13.00 2.87 12.50 2.90 11.95 3.02 11.15 3.16 16.02 3.57 15.60 3.64 15.00 3.72 14.34 3.90 13.38 4.09
7 13.55 2.93 13.16 2.96 12.60 2.96 11.96 3.10 11.15 3.22 16.26 3.68 15.80 3.76 15.12 3.83 14.36 4.02 13.38 4.24
9 13.95 3.07 13.49 3.07 12.80 3.10 11.99 3.25 11.15 3.39 16.74 3.90 16.19 3.98 15.36 4.05 14.39 4.28 13.38 4.46
10 14.15 3.13 13.65 3.15 12.90 3.18 12.00 3.32 11.15 3.47 16.98 4.02 16.38 4.09 15.48 4.16 14.40 4.39 13.38 4.59
11 14.15 3.19 13.65 3.22 12.90 3.25 12.00 3.39 11.15 3.54 16.98 4.13 16.38 4.20 15.48 4.28 14.40 4.50 13.38 4.72
14 14.15 3.36 13.65 3.39 12.90 3.39 12.00 3.57 11.15 3.71 16.98 4.39 16.38 4.46 15.48 4.54 14.40 4.80 13.38 5.02
15 14.15 3.45 13.65 3.51 12.90 3.51 12.00 3.65 11.15 3.83 16.98 4.57 16.38 4.65 15.48 4.72 14.40 4.98 13.38 5.20

Potencia total de las unidades interiores combinadas: 70% Potencia total de las unidades interiores combinadas: 80%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 11.13 4.07 10.85 4.25 10.78 4.43 10.64 4.69 10.50 4.96 12.72 4.62 12.40 4.83 12.32 5.03 12.16 5.33 12.00 5.63
-17 11.76 4.03 11.52 4.21 11.45 4.38 11.31 4.65 11.17 4.87 13.44 4.57 13.17 4.77 13.09 4.98 12.93 5.28 12.77 5.53
-15 12.18 7.08 11.97 7.13 11.90 7.13 11.76 7.52 11.62 7.88 13.92 6.89 13.68 6.99 13.60 7.09 13.44 7.49 13.28 7.84
-13 12.60 6.82 12.42 6.82 12.35 6.86 12.21 7.21 12.07 7.57 14.40 6.89 14.19 6.99 14.11 7.09 13.95 7.44 13.79 7.84
-11 13.02 6.51 12.87 6.55 12.80 6.55 12.66 6.91 12.52 7.26 14.88 6.84 14.70 6.94 14.62 7.04 14.46 7.44 14.30 7.79
-10 13.23 6.37 13.09 6.40 13.02 6.42 12.88 6.75 12.74 7.10 15.12 6.84 14.96 6.91 14.88 7.01 14.72 7.41 14.56 7.77
-9 13.44 6.24 13.31 6.24 13.24 6.29 13.10 6.60 12.96 6.95 15.36 6.84 15.22 6.89 15.14 6.99 14.98 7.39 14.82 7.74
-7 13.86 5.98 13.76 5.98 13.69 5.98 13.55 6.29 13.41 6.64 15.84 6.79 15.73 6.89 15.65 6.99 15.49 7.34 15.33 7.76
-6 14.07 5.80 13.99 5.84 13.92 5.84 13.78 6.15 13.64 6.46 16.08 6.79 15.98 6.89 15.90 6.94 15.74 7.34 15.58 7.69
-5 14.28 5.62 14.21 5.62 14.14 5.67 14.00 5.93 13.86 6.24 16.32 6.53 16.24 6.63 16.16 6.74 16.00 7.09 15.84 7.44
-3 15.09 5.22 14.99 5.22 14.90 5.27 14.76 5.53 14.56 5.80 17.25 6.03 17.14 6.13 17.02 6.18 16.86 6.53 16.64 6.84
-1 15.90 4.82 15.78 4.82 15.65 4.87 15.51 5.13 15.26 5.40 18.18 5.53 18.03 5.58 17.89 5.68 17.73 5.98 17.44 6.28
0 16.31 4.65 16.17 4.65 16.03 4.67 15.89 4.94 15.61 5.18 18.64 5.28 18.48 5.33 18.32 5.43 18.16 5.73 17.84 6.01
1 17.65 4.47 17.30 4.47 16.91 4.47 16.39 4.74 15.61 4.96 20.18 5.03 19.78 5.08 19.33 5.18 18.74 5.48 17.84 5.73
3 18.55 4.38 18.06 4.38 17.50 4.43 16.73 4.65 15.61 4.87 21.20 4.83 20.64 4.93 20.00 4.98 19.12 5.28 17.84 5.53
5 18.55 4.34 18.06 4.34 17.50 4.38 16.73 4.60 15.61 4.82 21.20 4.67 20.64 4.72 20.00 4.83 19.12 5.08 17.84 5.33
6 18.69 4.38 18.20 4.43 17.50 4.43 16.73 4.65 15.61 4.87 21.36 4.88 20.80 4.93 20.00 5.03 19.12 5.28 17.84 5.58
7 18.97 4.51 18.43 4.51 17.64 4.56 16.75 4.78 15.61 5.05 21.68 4.88 21.06 4.93 20.16 5.03 19.14 5.28 17.84 5.58
9 19.52 4.78 18.88 4.78 17.92 4.78 16.78 5.05 15.61 5.31 22.32 5.13 21.58 5.23 20.48 5.28 19.18 5.58 17.84 5.83
10 19.81 4.89 19.11 4.89 18.06 4.91 16.80 5.18 15.61 5.44 22.64 5.25 21.84 5.35 20.64 5.40 19.20 5.70 17.84 5.98
11 19.81 5.00 19.11 5.00 18.06 5.05 16.80 5.31 15.61 5.58 22.64 5.38 21.84 5.48 20.64 5.53 19.20 5.83 17.84 6.13
14 19.81 5.31 19.11 5.31 18.06 5.36 16.80 5.62 15.61 5.93 22.64 5.68 21.84 5.78 20.64 5.83 19.20 6.18 17.84 6.48
15 19.81 5.49 19.11 5.53 18.06 5.53 16.80 5.80 15.61 6.11 22.64 5.88 21.84 5.93 20.64 6.03 19.20 6.38 17.84 6.68

60 TCES0059 rev.2 - 06/2016


Potencia total de las unidades interiores combinadas: 90% Potencia total de las unidades interiores combinadas: 100%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
4 Capacidades
CAP yIPT
datosCAPde selección
IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 14.31 5.08 13.95 5.30 13.86 5.52 13.68 5.85 13.50 6.18 15.90 5.43 15.50 5.66 15.40 5.90 15.20 6.25 15.00 6.61
Tablas de capacidad de calefacción
-17 15.12 5.02 14.81 5.24 14.72 5.46 14.54 5.79 14.36 6.07 16.80 5.37 16.46 5.61 16.36 5.84 16.16 6.20 15.96 6.49
-15 15.66 7.56 15.39 7.23 15.30 6.95 15.12 7.28 14.94 7.67 17.40 7.43 17.10 6.96 17.00 6.43 16.80 6.79 16.60 7.08
-13 16.20 7.50 15.97 7.17 15.88 6.90 15.70 7.23 15.52 7.56 18.00 7.32 17.74 6.84 17.64 6.37 17.44 6.67 17.24 6.96
-11 16.74 7.45 16.54 7.12 16.45 6.79 16.27 7.17 16.09 7.50 18.60 7.20 18.38 6.73 18.28 6.25 18.08 6.55 17.88 6.90
-10 17.01 7.39 16.83 7.09 16.74 6.76 16.56 7.15 16.38 7.48 18.90 7.14 18.70 6.70 18.60 6.22 18.40 6.52 18.20 6.84
-9 17.28 Potencia
7.34 total de7.06
17.12 las unidades
17.03 interiores
6.73 combinadas:
16.85 7.12 90%
16.67 7.45 19.20 Potencia
7.08 total de6.67
19.02 las unidades
18.92 interiores
6.20 combinadas:
18.72 6.49 100%
18.52 6.79
-7 17.82 7.28 Temperatura
17.69 del aire
7.01 de entrada
17.60 6.68 interior
17.42 (DB (ºC)) 17.24
7.01 7.34 19.80 7.02 Temperatura
19.66 del aire
6.55 de entrada
19.56 6.08 interior
19.36 (DB (ºC)) 19.16
6.37 6.67
TEMP
-6 18.09 16 7.28 17.98 18 6.95 17.89 20 6.68 17.71 22 7.01 17.53 24 7.34 20.10 16 6.96 19.98 18 6.49 19.88 20 6.02 19.68 22 6.31 19.48 24 6.61
-5 CAP
18.36 IPT
7.17 CAP
18.27 IPT
6.84 CAP
18.18 IPT
6.57 CAP
18.00 IPT
6.90 CAP
17.82 IPT
7.23 CAP
20.40 IPT
7.08 CAP
20.30 IPT
6.61 CAP
20.20 IPT
6.14 CAP
20.00 IPT
6.43 CAP
19.80 IPT
6.73
-20
-3 14.31
19.40 5.08
7.01 13.95
19.28 5.30
6.68 13.86
19.15 5.52
6.40 13.68
18.97 5.85
6.73 13.50
18.72 6.18
7.06 15.90
21.56 5.43
7.32 15.50
21.42 5.66
6.84 15.40
21.28 5.90
6.31 15.20
21.08 6.25
6.67 15.00
20.80 6.61
6.96
-17
-1 15.12
20.45 5.02
6.84 14.81
20.29 5.24
6.57 14.72
20.12 5.46
6.23 14.54
19.94 5.79
6.57 14.36
19.62 6.07
6.90 16.80
22.72 5.37
7.49 16.46
22.54 5.61
7.02 16.36
22.36 5.84
6.55 16.16
22.16 6.20
6.84 15.96
21.80 6.49
7.20
-15
0 15.66
20.97 7.56
6.73 15.39
20.79 7.23
6.46 15.30
20.61 6.95
6.15 15.12
20.43 7.28
6.48 14.94
20.07 7.67
6.79 17.40
23.30 7.43
7.64 17.10
23.10 6.96
7.14 17.00
22.90 6.43
6.64 16.80
22.70 6.79
6.96 16.60
22.30 7.08
7.29
-13
1 16.20
22.70 7.50
6.62 15.97
22.25 7.17
6.35 15.88
21.74 6.90
6.07 15.70
21.08 7.23
6.40 15.52
20.07 7.56
6.68 18.00
25.22 7.32
7.79 17.74
24.72 6.84
7.26 17.64
24.16 6.37
6.73 17.44
23.42 6.67
7.08 17.24
22.30 6.96
7.38
-11
3 16.74
23.85 7.45
6.35 16.54
23.22 7.12
6.07 16.45
22.50 6.79
5.79 16.27
21.51 7.17
6.12 16.09
20.07 7.50
6.40 18.60
26.50 7.20
7.38 18.38
25.80 6.73
6.90 18.28
25.00 6.25
6.43 18.08
23.90 6.55
6.73 17.88
22.30 6.90
7.02
-10
5 17.01
23.85 7.39
6.07 16.83
23.22 7.09
5.79 16.74
22.50 6.76
5.57 16.56
21.51 7.15
5.85 16.38
20.07 7.48
6.12 18.90
26.50 7.14
6.96 18.70
25.80 6.70
6.55 18.60
25.00 6.22
6.08 18.40
23.90 6.52
6.37 18.20
22.30 6.84
6.67
-9
6 17.28
24.03 7.34
6.01 17.12
23.40 7.06
5.52 17.03
22.50 6.73
5.52 16.85
21.51 7.12
5.79 16.67
20.07 7.45
6.07 19.20
26.70 7.08
6.79 19.02
26.00 6.67
6.37 18.92
25.00 6.20
5.90 18.72
23.90 6.49
6.20 18.52
22.30 6.79
6.49
-7
7 17.82
24.39 7.28
6.18 17.69
23.69 7.01
5.74 17.60
22.68 6.68
5.63 17.42
21.53 7.01
5.96 17.24
20.07 7.34
6.23 19.80
27.10 7.02
6.96 19.66
26.33 6.55
6.49 19.56
25.20 6.08
6.02 19.36
23.93 6.37
6.31 19.16
22.30 6.67
6.61
-6
9 18.09
25.11 7.28
6.46 17.98
24.28 6.95
5.90 17.89
23.04 6.68
5.90 17.71
21.58 7.01
6.23 17.53
20.07 7.34
6.51 20.10
27.90 6.96
7.26 19.98
26.98 6.49
6.79 19.88
25.60 6.02
6.31 19.68
23.98 6.31
6.61 19.48
22.30 6.61
6.90
-5
10 18.36
25.47 7.17
6.59 18.27
24.57 6.84
6.04 18.18
23.22 6.57
6.04 18.00
21.60 6.90
6.37 17.82
20.07 7.23
6.65 20.40
28.30 7.08
7.40 20.30
27.30 6.61
6.93 20.20
25.80 6.14
6.43 20.00
24.00 6.43
6.73 19.80
22.30 6.73
7.05
-3
11 19.40
25.47 7.01
6.73 19.28
24.57 6.68
6.18 19.15
23.22 6.40
6.18 18.97
21.60 6.73
6.51 18.72
20.07 7.06
6.79 21.56
28.30 7.32
7.55 21.42
27.30 6.84
7.08 21.28
25.80 6.31
6.55 21.08
24.00 6.67
6.84 20.80
22.30 6.96
7.20
-1
14 20.45
25.47 6.84
7.12 20.29
24.57 6.57
6.79 20.12
23.22 6.23
6.51 19.94
21.60 6.57
6.84 19.62
20.07 6.90
7.17 22.72
28.30 7.49
7.91 22.54
27.30 7.02
7.43 22.36
25.80 6.55
6.90 22.16
24.00 6.84
7.26 21.80
22.30 7.20
7.55
0
15 20.97
25.47 6.73
7.34 20.79
24.57 6.46
7.01 20.61
23.22 6.15
6.73 20.43
21.60 6.48
7.06 20.07
20.07 6.79
7.39 23.30
28.30 7.64
8.14 23.10
27.30 7.14
7.85 22.90
25.80 6.64
7.08 22.70
24.00 6.96
7.43 22.30
22.30 7.29
7.79
1 22.70 6.62 22.25 6.35 21.74 6.07 21.08 6.40 20.07 6.68 25.22 7.79 24.72 7.26 24.16 6.73 23.42 7.08 22.30 7.38
3 23.85 6.35 23.22 6.07 22.50 5.79 21.51 6.12 20.07 6.40 26.50 7.38 25.80 6.90 25.00 6.43 23.90 6.73 22.30 7.02
Potencia total de las unidades interiores combinadas: 110% Potencia total de las unidades interiores combinadas: 120%
5 23.85 6.07 23.22 5.79 22.50 5.57 21.51 5.85 20.07 6.12 26.50 6.96 25.80 6.55 25.00 6.08 23.90 6.37 22.30 6.67
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
6
TEMP 24.03 6.01 23.40 5.52 22.50 5.52 21.51 5.79 20.07 6.07 26.70 6.79 26.00 6.37 25.00 5.90 23.90 6.20 22.30 6.49
16 18 20 22 24 16 18 20 22 24
7 24.39 6.18 23.69 5.74 22.68 5.63 21.53 5.96 20.07 6.23 27.10 6.96 26.33 6.49 25.20 6.02 23.93 6.31 22.30 6.61
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
9 25.11 6.46 24.28 5.90 23.04 5.90 21.58 6.23 20.07 6.51 27.90 7.26 26.98 6.79 25.60 6.31 23.98 6.61 22.30 6.90
-20 15.90 5.79 15.50 6.04 15.40 6.30 15.20 6.67 15.00 7.05 15.90 5.88 15.50 6.13 15.40 6.39 15.20 6.77 15.00 7.16
10 25.47 6.59 24.57 6.04 23.22 6.04 21.60 6.37 20.07 6.65 28.30 7.40 27.30 6.93 25.80 6.43 24.00 6.73 22.30 7.05
-17 16.80 5.73 16.46 5.98 16.36 6.23 16.16 6.61 15.96 6.93 16.80 5.82 16.46 6.07 16.36 6.33 16.16 6.71 15.96 7.03
11 25.47 6.73 24.57 6.18 23.22 6.18 21.60 6.51 20.07 6.79 28.30 7.55 27.30 7.08 25.80 6.55 24.00 6.84 22.30 7.20
-15 17.40 6.74 17.10 6.61 17.00 6.48 16.80 6.86 16.60 7.24 17.40 5.82 17.10 6.07 17.00 6.20 16.80 6.65 16.60 7.09
14 25.47 7.12 24.57 6.79 23.22 6.51 21.60 6.84 20.07 7.17 28.30 7.91 27.30 7.43 25.80 6.90 24.00 7.26 22.30 7.55
-13 18.00 6.61 17.74 6.48 17.64 6.36 17.44 6.74 17.24 7.11 18.00 5.69 17.74 5.88 17.64 6.07 17.44 6.52 17.24 6.90
15 25.47 7.34 24.57 7.01 23.22 6.73 21.60 7.06 20.07 7.39 28.30 8.14 27.30 7.85 25.80 7.08 24.00 7.43 22.30 7.79
-11 18.60 6.48 18.38 6.36 18.28 6.23 18.08 6.61 17.88 6.99 18.60 5.56 18.38 5.75 18.28 5.94 18.08 6.39 17.88 6.71
-10 18.90 6.42 18.70 6.30 18.60 6.17 18.40 6.55 18.20 6.93 18.90 5.46 18.70 5.69 18.60 5.88 18.40 6.29 18.20 6.65

4
-9 19.20 Potencia
6.36 total de6.23
19.02 las unidades
18.92 interiores
6.11 combinadas:
18.72 6.48 110%
18.52 6.86 19.20 Potencia
5.37 total
19.02 de las
5.62 unidades
18.92 interiores
5.82 combinadas:
18.72 6.20 120%
18.52 6.58
-7 19.80 6.23 Temperatura
19.66 del aire
6.11 de entrada
19.56 5.98 interior
19.36 (DB (ºC)) 19.16
6.36 6.74 19.80 5.24 Temperatura
19.66 del aire
5.50 de entrada
19.56 5.62 interior
19.36 (DB (ºC)) 19.16
6.07 6.39
TEMP
-6 20.10 16 6.17 19.98 18 6.04 19.88 20 5.98 19.68 22 6.30 19.48 24 6.67 20.10 16 5.18 19.98 18 5.43 19.88 20 5.56 19.68 22 6.01 19.48 24 6.33
-5 CAP
20.40 IPT
6.30 CAP
20.30 IPT
6.17 CAP
20.20 IPT
6.04 CAP
20.00 IPT
6.42 CAP
19.80 IPT
6.74 CAP
20.40 IPT
5.24 CAP
20.30 IPT
5.50 CAP
20.20 IPT
5.62 CAP
20.00 IPT
6.07 CAP
19.80 IPT
6.39
-20
-3 15.90
21.56 5.79
6.48 15.50
21.42 6.04
6.36 15.40
21.28 6.30
6.23 15.20
21.08 6.67
6.61 15.00
20.80 7.05
6.93 15.90
21.56 5.88
5.37 15.50
21.42 6.13
5.62 15.40
21.28 6.39
5.82 15.20
21.08 6.77
6.20 15.00
20.80 7.16
6.58
-17
-1 16.80
22.72 5.73
6.61 16.46
22.54 5.98
6.48 16.36
22.36 6.23
6.42 16.16
22.16 6.61
6.80 15.96
21.80 6.93
7.11 16.80
22.72 5.82
5.56 16.46
22.54 6.07
5.75 16.36
22.36 6.33
5.94 16.16
22.16 6.71
6.39 15.96
21.80 7.03
6.77
-15
0 17.40
23.30 6.74
6.71 17.10
23.10 6.61
6.58 17.00
22.90 6.48
6.52 16.80
22.70 6.86
6.89 16.60
22.30 7.24
7.24 17.40
23.30 5.82
5.62 17.10
23.10 6.07
5.82 17.00
22.90 6.20
6.01 16.80
22.70 6.65
6.45 16.60
22.30 7.09
6.84
-13
1 18.00
25.22 6.61
6.80 17.74
24.72 6.48
6.67 17.64
24.16 6.36
6.61 17.44
23.42 6.74
6.99 17.24
22.30 7.11
7.37 18.00
25.22 5.69
5.69 17.74
24.72 5.88
5.88 17.64
24.16 6.07
6.07 17.44
23.42 6.52
6.52 17.24
22.30 6.90
6.90
-11
3 18.60
26.50 6.48
6.74 18.38
25.80 6.36
6.61 18.28
25.00 6.23
6.48 18.08
23.90 6.61
6.86 17.88
22.30 6.99
7.24 18.60
26.50 5.56
5.82 18.38
25.80 5.75
6.01 18.28
25.00 5.94
6.20 18.08
23.90 6.39
6.65 17.88
22.30 6.71
7.03
-10
5 18.90
26.50 6.42
6.61 18.70
25.80 6.30
6.48 18.60
25.00 6.17
6.36 18.40
23.90 6.55
6.74 18.20
22.30 6.93
7.11 18.90
26.50 5.46
5.88 18.70
25.80 5.69
6.13 18.60
25.00 5.88
6.33 18.40
23.90 6.29
6.77 18.20
22.30 6.65
7.22
-9
6 19.20
26.70 6.36
6.55 19.02
26.00 6.23
6.42 18.92
25.00 6.11
6.30 18.72
23.90 6.48
6.67 18.52
22.30 6.86
7.05 19.20
26.70 5.37
5.94 19.02
26.00 5.62
6.20 18.92
25.00 5.82
6.39 18.72
23.90 6.20
6.84 18.52
22.30 6.58
7.29
-7
7 19.80
27.10 6.23
6.67 19.66
26.33 6.11
6.55 19.56
25.20 5.98
6.42 19.36
23.93 6.36
6.80 19.16
22.30 6.74
7.24 19.80
27.10 5.24
6.13 19.66
26.33 5.50
6.39 19.56
25.20 5.62
6.58 19.36
23.93 6.07
7.03 19.16
22.30 6.39
7.48
-6
9 20.10
27.90 6.17
6.99 19.98
26.98 6.04
6.86 19.88
25.60 5.98
6.74 19.68
23.98 6.30
7.18 19.48
22.30 6.67
7.56 20.10
27.90 5.18
6.39 19.98
26.98 5.43
6.71 19.88
25.60 5.56
6.90 19.68
23.98 6.01
7.41 19.48
22.30 6.33
7.80
-5
10 20.40
28.30 6.30
7.18 20.30
27.30 6.17
7.02 20.20
25.80 6.04
6.89 20.00
24.00 6.42
7.33 19.80
22.30 6.74
7.71 20.40
28.30 5.24
6.55 20.30
27.30 5.50
6.87 20.20
25.80 5.62
7.06 20.00
24.00 6.07
7.57 19.80
22.30 6.39
7.99
-3
11 21.56
28.30 6.48
7.37 21.42
27.30 6.36
7.18 21.28
25.80 6.23
7.05 21.08
24.00 6.61
7.49 20.80
22.30 6.93
7.87 21.56
28.30 5.37
6.71 21.42
27.30 5.62
7.03 21.28
25.80 5.82
7.22 21.08
24.00 6.20
7.73 20.80
22.30 6.58
8.18
-1
14 22.72
28.30 6.61
7.74 22.54
27.30 6.48
7.56 22.36
25.80 6.42
7.43 22.16
24.00 6.80
7.87 21.80
22.30 7.11
8.31 22.72
28.30 5.56
7.09 22.54
27.30 5.75
7.41 22.36
25.80 5.94
7.60 22.16
24.00 6.39
8.18 21.80
22.30 6.77
8.69
0
15 23.30
28.30 6.71
7.93 23.10
27.30 6.58
7.81 22.90
25.80 6.52
7.68 22.70
24.00 6.89
8.12 22.30
22.30 7.24
8.56 23.30
28.30 5.62
7.35 23.10
27.30 5.82
7.67 22.90
25.80 6.01
7.86 22.70
24.00 6.45
8.44 22.30
22.30 6.84
8.95
1 25.22 6.80 24.72 6.67 24.16 6.61 23.42 6.99 22.30 7.37 25.22 5.69 24.72 5.88 24.16 6.07 23.42 6.52 22.30 6.90
3 26.50 6.74 25.80 6.61 25.00 6.48 23.90 6.86 22.30 7.24 26.50 5.82 25.80 6.01 25.00 6.20 23.90 6.65 22.30 7.03
5 26.50 6.61 25.80 6.48 25.00 6.36 23.90 6.74 22.30 7.11 26.50 5.88 25.80 6.13 25.00 6.33 23.90 6.77 22.30 7.22
6 26.70 6.55 26.00 6.42 25.00 6.30 23.90 6.67 22.30 7.05 26.70 5.94 26.00 6.20 25.00 6.39 23.90 6.84 22.30 7.29
7 27.10 6.67 26.33 6.55 25.20 6.42 23.93 6.80 22.30 7.24 27.10 6.13 26.33 6.39 25.20 6.58 23.93 7.03 22.30 7.48
9 NOTE
27.90 6.99 26.98 6.86 25.60 6.74 23.98 7.18 22.30 7.56 27.90 6.39 26.98 6.71 25.60 6.90 23.98 7.41 22.30 7.80
10 28.30 7.18 27.30 7.02 25.80 6.89 24.00 7.33 22.30 7.71 28.30 6.55 27.30 6.87 25.80 7.06 24.00 7.57 22.30 7.99
• 11CAP: Capacity
28.30 7.37 at compressor
27.30 7.18 25.80 maximum
7.05 frequency
24.00 7.49 (kW)
22.30 7.87 28.30 6.71 27.30 7.03 25.80 7.22 24.00 7.73 22.30 8.18

• 14
28.30 7.74 27.30 7.56 25.80 7.43 24.00 7.87 22.30 8.31 28.30 7.09 27.30 7.41 25.80 7.60 24.00 8.18 22.30 8.69
15
IPT: 28.30
Input 7.93
power27.30(kW)7.81 25.80 7.68 24.00 8.12 22.30 8.56 28.30 7.35 27.30 7.67 25.80 7.86 24.00 8.44 22.30 8.95

• TEMP: Outdoor air inlet temperature (WB (ºC))


Potencia total de las unidades interiores combinadas: 130%
Temperatura del aire de entrada interior (DB (ºC))
TEMP
NOT
16 E 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
• -20CAP:15.90
Capacity
5.69 at compressor
15.50 5.94 15.40maximum
6.18 frequency
15.20 6.55 (kW)6.92
15.00
-17 16.80 5.63 16.46 5.87 16.36 6.12 16.16 6.49 15.96 6.80
• -15IPT: Input
17.40 power
5.50 (kW)
17.10 5.81 17.00 6.06 16.80 6.43 16.60 6.74
-13 18.00 5.38 17.74 5.63 17.64 5.94 17.44 6.24 17.24 6.55
• -11TEMP:18.60Outdoor
5.26 air inlet
18.38 5.50temperature
18.28 5.75 (WB18.08 (ºC))
6.06 17.88 6.37
-10 18.90 5.19 18.70 5.44 18.60 5.69 18.40 6.00 18.20 6.31
-9 19.20 Potencia
5.13 total de5.38
19.02 las unidades
18.92 interiores
5.63 combinadas:
18.72 5.94 130%
18.52 6.24
-7 19.80 4.95 Temperatura
19.66 del
5.19 aire de
19.56 entrada
5.44 interior
19.36 (DB (ºC))
5.75 19.16 6.06
TEMP
-6 20.10 16 4.88 19.98 18 5.13 19.88 20 5.38 19.68 22 5.69 19.48 24 5.94
-5 CAP
20.40 IPT
4.95 CAP
20.30 IPT
5.19 CAP
20.20 IPT
5.44 CAP
20.00 IPT
5.75 CAP
19.80 IPT
6.00
-20
-3 15.90
21.56 5.69
5.07 15.50
21.42 5.94
5.32 15.40
21.28 6.18
5.56 15.20
21.08 6.55
5.87 15.00
20.80 6.92
6.18
-17
-1 16.80
22.72 5.63
5.19 16.46
22.54 5.87
5.44 16.36
22.36 6.12
5.69 16.16
22.16 6.49
6.00 15.96
21.80 6.80
6.31
-15
0 17.40
23.30 5.50
5.26 17.10
23.10 5.81
5.50 17.00
22.90 6.06
5.75 16.80
22.70 6.43
6.06 16.60
22.30 6.74
6.37
-13
1 18.00
25.22 5.38
5.32 17.74
24.72 5.63
5.56 17.64
24.16 5.94
5.81 17.44
23.42 6.24
6.12 17.24
22.30 6.55
6.43
-11
3 18.60
26.50 5.26
5.44 18.38
25.80 5.50
5.69 18.28
25.00 5.75
5.94 18.08
23.90 6.06
6.31 17.88
22.30 6.37
6.62
-10
5 18.90
26.50 5.19
5.56 18.70
25.80 5.44
5.81 18.60
25.00 5.69
6.12 18.40
23.90 6.00
6.43 18.20
22.30 6.31
6.74
-9
6 19.20
26.70 5.13
5.63 19.02
26.00 5.38
5.94 18.92
25.00 5.63
6.18 18.72
23.90 5.94
6.49 18.52
22.30 6.24
6.86
-7
7 19.80
27.10 4.95
5.75 19.66
26.33 5.19
6.00 19.56
25.20 5.44
6.31 19.36
23.93 5.75
6.62 19.16
22.30 6.06
6.99
-6
9 20.10
27.90 4.88
5.94 19.98
26.98 5.13
6.24 19.88
25.60 5.38
6.49 19.68
23.98 5.69
6.86 19.48
22.30 5.94
7.23
-5
10 20.40
28.30 4.95
6.03 20.30
27.30 5.19
6.34 20.20
25.80 5.44
6.62 20.00
24.00 5.75
6.99 19.80
22.30 6.00
7.36
-3
11 21.56
28.30 5.07
6.12 21.42
27.30 5.32
6.43 21.28
25.80 5.56
6.74 21.08
24.00 5.87
7.11 20.80
22.30 6.18
7.48
-1
14 22.72
28.30 5.19
6.43 22.54
27.30 5.44
6.68 22.36
25.80 5.69
6.99 22.16
24.00 6.00
7.42 21.80
22.30 6.31
7.73
0
15 23.30
28.30 5.26
6.55 23.10
27.30 5.50
6.86 22.90
25.80 5.75
7.17 22.70
24.00 6.06
7.54 22.30
22.30 6.37
7.98
1 25.22 5.32 24.72 5.56 24.16 5.81 23.42 6.12 22.30 6.43
3 26.50 5.44 25.80 5.69 25.00 5.94 23.90 6.31 22.30 6.62
5 26.50 5.56 25.80 5.81 25.00 6.12 23.90 6.43 22.30 6.74
6 26.70 5.63 26.00 5.94 25.00 6.18 23.90 6.49 22.30 6.86
7 27.10 5.75 26.33 6.00 25.20 6.31 23.93 6.62 22.30 6.99
9 27.90 5.94 26.98 6.24 25.60 6.49 23.98 6.86 22.30 7.23
10 28.30 6.03 27.30 6.34 25.80 6.62 24.00 6.99 22.30 7.36
11 28.30 6.12 27.30 6.43 25.80 6.74 24.00 7.11 22.30 7.48
14 28.30 6.43 27.30 6.68 25.80 6.99 24.00 7.42 22.30 7.73
15 28.30 6.55 27.30 6.86 25.80 7.17 24.00 7.54 22.30 7.98

61 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Tablas de capacidad de calefacción

 RAS-10FSNM
 RAS-10FSNM1
Potencia total de las unidades interiores combinadas: 50% Potencia total de las unidades interiores combinadas: 60%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 8.33 3.44 8.23 3.59 8.18 3.74 8.08 3.96 7.98 4.19 9.98 4.49 9.86 4.68 9.80 4.88 9.68 5.17 9.56 5.47
-17 9.29 3.40 9.19 3.55 9.14 3.70 9.04 3.93 8.94 4.11 11.14 4.44 11.02 4.64 10.96 4.83 10.83 5.12 10.71 5.37
-15 9.93 6.73 9.83 6.77 9.78 6.84 9.68 7.14 9.58 7.44 11.91 8.54 11.78 8.73 11.72 8.88 11.60 9.32 11.48 9.81
-13 10.57 6.21 10.47 6.24 10.42 6.28 10.32 6.58 10.22 6.84 12.67 7.90 12.55 8.05 12.49 8.20 12.37 8.64 12.25 9.03
-11 11.22 5.68 11.12 5.72 11.07 5.76 10.96 6.02 10.86 6.28 13.44 7.22 13.32 7.42 13.26 7.51 13.14 7.90 13.02 8.30
-10 11.54 5.42 11.44 5.46 11.39 5.50 11.29 5.74 11.19 5.98 13.83 6.90 13.71 7.08 13.65 7.17 13.53 7.56 13.41 7.93
-9 11.86 5.16 11.76 5.20 11.71 5.23 11.61 5.46 11.51 5.68 14.21 6.59 14.09 6.73 14.03 6.83 13.91 7.22 13.79 7.56
-7 12.50 4.64 12.40 4.67 12.35 4.67 12.25 4.90 12.15 5.08 14.98 5.95 14.86 6.05 14.80 6.15 14.68 6.49 14.56 6.83
-6 12.82 4.34 12.72 4.37 12.67 4.41 12.57 4.60 12.47 4.78 15.37 5.61 15.25 5.71 15.19 5.81 15.07 6.15 14.95 6.44
-5 13.14 4.26 13.04 4.26 12.99 4.30 12.89 4.52 12.79 4.71 15.75 5.47 15.63 5.56 15.57 5.66 15.45 5.95 15.33 6.25
-3 13.74 4.04 13.64 4.07 13.59 4.07 13.47 4.30 13.29 4.45 16.47 5.12 16.35 5.22 16.29 5.32 16.15 5.61 15.93 5.90
-1 14.35 3.81 14.25 3.85 14.19 3.89 14.05 4.04 13.79 4.22 17.20 4.83 17.08 4.93 17.02 4.98 16.85 5.27 16.53 5.51
0 14.65 3.72 14.55 3.76 14.50 3.78 14.35 3.94 14.04 4.11 17.56 4.66 17.44 4.76 17.38 4.81 17.20 5.10 16.84 5.34
1 15.61 3.63 15.45 3.66 15.28 3.66 14.83 3.85 14.04 4.00 18.71 4.49 18.52 4.59 18.31 4.64 17.77 4.93 16.84 5.17
3 16.25 3.48 16.05 3.51 15.80 3.51 15.15 3.66 14.04 3.85 19.48 4.59 19.24 4.68 18.94 4.73 18.16 4.98 16.84 5.27
5 16.25 3.59 16.05 3.63 15.80 3.66 15.15 3.81 14.04 3.96 19.48 4.68 19.24 4.73 18.94 4.83 18.16 5.07 16.84 5.37
6 16.65 3.66 16.30 3.70 15.80 3.74 15.15 3.89 14.04 4.07 19.96 4.68 19.54 4.78 18.94 4.88 18.16 5.12 16.84 5.37
7 16.95 3.78 16.53 3.81 15.91 3.81 15.15 4.00 14.04 4.15 20.32 4.83 19.81 4.93 19.08 5.03 18.16 5.27 16.84 5.56
9 17.56 3.96 16.98 3.96 16.14 4.00 15.15 4.19 14.04 4.37 21.04 5.12 20.35 5.22 19.35 5.32 18.16 5.61 16.84 5.86
10 17.86 4.04 17.20 4.06 16.25 4.09 15.15 4.28 14.04 4.47 21.41 5.27 20.62 5.37 19.48 5.47 18.16 5.76 16.84 6.03
11 17.86 4.11 17.20 4.15 16.25 4.19 15.15 4.37 14.04 4.56 21.41 5.42 20.62 5.51 19.48 5.61 18.16 5.90 16.84 6.20
14 17.86 4.34 17.20 4.37 16.25 4.37 15.15 4.60 14.04 4.78 21.41 5.76 20.62 5.86 19.48 5.95 18.16 6.29 16.84 6.59
15 17.86 4.45 17.20 4.52 16.25 4.52 15.15 4.71 14.04 4.93 21.41 6.00 20.62 6.10 19.48 6.20 18.16 6.54 16.84 6.83

Potencia total de las unidades interiores combinadas: 70% Potencia total de las unidades interiores combinadas: 80%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 11.64 5.39 11.50 5.62 11.43 5.86 11.29 6.21 11.15 6.56 13.29 6.14 13.13 6.40 13.05 6.67 12.89 7.07 12.73 7.47
-17 12.98 5.33 12.84 5.56 12.77 5.80 12.63 6.15 12.49 6.44 14.83 6.07 14.67 6.34 14.59 6.60 14.43 7.00 14.27 7.34
-15 13.88 9.37 13.74 9.43 13.67 9.43 13.53 9.96 13.39 10.42 15.85 9.14 15.69 9.27 15.61 9.40 15.45 9.94 15.29 10.40
-13 14.78 9.02 14.64 9.02 14.57 9.08 14.43 9.55 14.29 10.01 16.88 9.14 16.72 9.27 16.64 9.40 16.48 9.87 16.32 10.40
-11 15.67 8.61 15.53 8.67 15.46 8.67 15.32 9.14 15.18 9.60 17.90 9.07 17.74 9.20 17.66 9.34 17.50 9.87 17.34 10.34
-10 16.12 8.43 15.98 8.46 15.91 8.49 15.77 8.93 15.63 9.40 18.41 9.07 18.25 9.17 18.17 9.30 18.01 9.84 17.85 10.30
-9 16.57 8.26 16.43 8.26 16.36 8.32 16.22 8.73 16.08 9.19 18.93 9.07 18.77 9.14 18.69 9.27 18.53 9.80 18.37 10.27
-7 17.47 7.91 17.33 7.91 17.26 7.91 17.12 8.32 16.98 8.78 19.95 9.00 19.79 9.14 19.71 9.27 19.55 9.74 19.39 10.29
-6 17.92 7.67 17.78 7.73 17.71 7.73 17.57 8.14 17.43 8.55 20.46 9.00 20.30 9.14 20.22 9.20 20.06 9.74 19.90 10.20
-5 18.36 7.44 18.22 7.44 18.15 7.50 18.01 7.85 17.87 8.26 20.98 8.67 20.82 8.80 20.74 8.94 20.58 9.40 20.42 9.87
-3 19.21 6.91 19.07 6.91 19.00 6.97 18.83 7.32 18.58 7.67 21.94 8.00 21.78 8.14 21.70 8.20 21.51 8.67 21.22 9.07
-1 20.05 6.38 19.91 6.38 19.84 6.44 19.64 6.79 19.28 7.14 22.90 7.34 22.74 7.40 22.66 7.54 22.43 7.94 22.02 8.34
0 20.47 6.15 20.33 6.15 20.26 6.18 20.05 6.53 19.63 6.85 23.38 7.00 23.22 7.07 23.14 7.20 22.90 7.60 22.42 7.97
1 21.81 5.92 21.59 5.92 21.35 5.92 20.72 6.27 19.63 6.56 24.92 6.67 24.66 6.74 24.39 6.87 23.67 7.27 22.42 7.60
3 22.71 5.80 22.43 5.80 22.08 5.86 21.17 6.15 19.63 6.44 25.94 6.40 25.62 6.54 25.22 6.60 24.18 7.00 22.42 7.34
5 22.71 5.74 22.43 5.74 22.08 5.80 21.17 6.09 19.63 6.38 25.94 6.20 25.62 6.27 25.22 6.40 24.18 6.74 22.42 7.07
6 23.27 5.80 22.78 5.86 22.08 5.86 21.17 6.15 19.63 6.44 26.58 6.47 26.02 6.54 25.22 6.67 24.18 7.00 22.42 7.40
7 23.69 5.97 23.10 5.97 22.24 6.03 21.17 6.33 19.63 6.68 27.06 6.47 26.38 6.54 25.40 6.67 24.18 7.00 22.42 7.40
9 24.53 6.33 23.73 6.33 22.55 6.33 21.17 6.68 19.63 7.03 28.02 6.80 27.10 6.94 25.76 7.00 24.18 7.40 22.42 7.74
10 24.95 6.47 24.04 6.47 22.71 6.50 21.17 6.85 19.63 7.20 28.50 6.97 27.46 7.10 25.94 7.17 24.18 7.57 22.42 7.94
11 24.95 6.62 24.04 6.62 22.71 6.68 21.17 7.03 19.63 7.38 28.50 7.14 27.46 7.27 25.94 7.34 24.18 7.74 22.42 8.14
14 24.95 7.03 24.04 7.03 22.71 7.09 21.17 7.44 19.63 7.85 28.50 7.54 27.46 7.67 25.94 7.74 24.18 8.20 22.42 8.60
15 24.95 7.26 24.04 7.32 22.71 7.32 21.17 7.67 19.63 8.08 28.50 7.80 27.46 7.87 25.94 8.00 24.18 8.47 22.42 8.87

Potencia total de las unidades interiores combinadas: 90% Potencia total de las unidades interiores combinadas: 100%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 14.95 6.73 14.77 7.02 14.68 7.32 14.50 7.76 14.32 8.19 16.60 7.18 16.40 7.49 16.30 7.80 16.10 8.27 15.90 8.74
-17 16.67 6.66 16.49 6.95 16.40 7.24 16.22 7.68 16.04 8.05 18.52 7.10 18.32 7.41 18.22 7.72 18.02 8.19 17.82 8.58
-15 17.83 10.02 17.65 9.58 17.56 9.22 17.38 9.66 17.20 10.17 19.80 9.83 19.60 9.20 19.50 8.50 19.30 8.97 19.10 9.36
-13 18.98 9.95 18.80 9.51 18.71 9.15 18.53 9.58 18.35 10.02 21.08 9.67 20.88 9.05 20.78 8.42 20.58 8.81 20.38 9.20
-11 20.13 9.88 19.95 9.44 19.86 9.00 19.68 9.51 19.50 9.95 22.36 9.52 22.16 8.89 22.06 8.27 21.86 8.66 21.66 9.13
-10 20.71 9.80 20.53 9.40 20.44 8.96 20.26 9.47 20.08 9.91 23.00 9.44 22.80 8.85 22.70 8.23 22.50 8.62 22.30 9.05
-9 21.28 9.73 21.10 9.36 21.01 8.93 20.83 9.44 20.65 9.88 23.64 9.36 23.44 8.81 23.34 8.19 23.14 8.58 22.94 8.97
-7 22.44 9.66 22.26 9.29 22.17 8.85 21.99 9.29 21.81 9.73 24.92 9.28 24.72 8.66 24.62 8.03 24.42 8.42 24.22 8.81
-6 23.01 9.66 22.83 9.22 22.74 8.85 22.56 9.29 22.38 9.73 25.56 9.20 25.36 8.58 25.26 7.96 25.06 8.35 24.86 8.74
-5 23.59 9.51 23.41 9.07 23.32 8.71 23.14 9.15 22.96 9.58 26.20 9.36 26.00 8.74 25.90 8.11 25.70 8.50 25.50 8.89
-3 24.67 9.29 24.49 8.85 24.40 8.49 24.18 8.93 23.86 9.36 27.40 9.67 27.20 9.05 27.10 8.35 26.86 8.81 26.50 9.20
-1 25.75 9.07 25.57 8.71 25.48 8.27 25.23 8.71 24.76 9.15 28.60 9.91 28.40 9.28 28.30 8.66 28.02 9.05 27.50 9.52
0 26.29 8.93 26.11 8.56 26.02 8.16 25.75 8.60 25.21 9.00 29.20 10.10 29.00 9.44 28.90 8.78 28.60 9.20 28.00 9.63
1 28.02 8.78 27.73 8.41 27.42 8.05 26.61 8.49 25.21 8.85 31.12 10.30 30.80 9.59 30.46 8.89 29.56 9.36 28.00 9.75
3 29.17 8.41 28.81 8.05 28.36 7.68 27.19 8.12 25.21 8.49 32.40 9.75 32.00 9.13 31.50 8.50 30.20 8.89 28.00 9.28
5 29.17 8.05 28.81 7.68 28.36 7.39 27.19 7.76 25.21 8.12 32.40 9.20 32.00 8.66 31.50 8.03 30.20 8.42 28.00 8.81
6 29.89 7.97 29.26 7.32 28.36 7.32 27.19 7.68 25.21 8.05 33.20 8.97 32.50 8.42 31.50 7.80 30.20 8.19 28.00 8.58
7 30.43 8.19 29.67 7.61 28.56 7.46 27.19 7.90 25.21 8.27 33.80 9.20 32.95 8.58 31.73 7.96 30.20 8.35 28.00 8.74
9 31.51 8.56 30.48 7.83 28.97 7.83 27.19 8.27 25.21 8.63 35.00 9.59 33.85 8.97 32.18 8.35 30.20 8.74 28.00 9.13
10 32.05 8.74 30.88 8.01 29.17 8.01 27.19 8.45 25.21 8.82 35.60 9.79 34.30 9.17 32.40 8.50 30.20 8.89 28.00 9.32
11 32.05 8.93 30.88 8.19 29.17 8.19 27.19 8.63 25.21 9.00 35.60 9.98 34.30 9.36 32.40 8.66 30.20 9.05 28.00 9.52
14 32.05 9.44 30.88 9.00 29.17 8.63 27.19 9.07 25.21 9.51 35.60 10.45 34.30 9.83 32.40 9.13 30.20 9.59 28.00 9.98
15 32.05 9.73 30.88 9.29 29.17 8.93 27.19 9.36 25.21 9.80 35.60 10.76 34.30 10.37 32.40 9.36 30.20 9.83 28.00 10.30

NOTE
• CAP: Capacity at compressor maximum frequency (kW)
• IPT: Input power (kW)
• TEMP: Outdoor air inlet temperature (WB (ºC))
Potencia total de las unidades interiores combinadas: 110% Potencia total de las unidades interiores combinadas: 120%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
62 TCES0059 rev.2 - 06/2016
-20 16.60 7.58 16.40 7.91 16.30 8.24 16.10 8.73 15.90 9.23 16.60 7.56 16.40 7.89 16.30 8.22 16.10 8.71 15.90 9.20
-17 18.52 7.50 18.32 7.83 18.22 8.15 18.02 8.65 17.82 9.06 18.52 7.48 18.32 7.81 18.22 8.14 18.02 8.63 17.82 9.04
4 Capacidades y datos de selección

Tablas de capacidad de calefacción

Potencia total de las unidades interiores combinadas: 110% Potencia total de las unidades interiores combinadas: 120%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 16.60 7.58 16.40 7.91 16.30 8.24 16.10 8.73 15.90 9.23 16.60 7.56 16.40 7.89 16.30 8.22 16.10 8.71 15.90 9.20
-17 18.52 7.50 18.32 7.83 18.22 8.15 18.02 8.65 17.82 9.06 18.52 7.48 18.32 7.81 18.22 8.14 18.02 8.63 17.82 9.04
-15 19.80 8.81 19.60 8.65 19.50 8.48 19.30 8.98 19.10 9.47 19.80 7.48 19.60 7.81 19.50 7.97 19.30 8.55 19.10 9.12
-13 21.08 8.65 20.88 8.48 20.78 8.32 20.58 8.81 20.38 9.31 21.08 7.31 20.88 7.56 20.78 7.81 20.58 8.38 20.38 8.88
-11 22.36 8.48 22.16 8.32 22.06 8.15 21.86 8.65 21.66 9.14 22.36 7.15 22.16 7.40 22.06 7.64 21.86 8.22 21.66 8.63
-10 23.00 8.40 22.80 8.24 22.70 8.07 22.50 8.57 22.30 9.06 23.00 7.03 22.80 7.31 22.70 7.56 22.50 8.09 22.30 8.55
-9 23.64 8.32 23.44 8.15 23.34 7.99 23.14 8.48 22.94 8.98 23.64 6.90 23.44 7.23 23.34 7.48 23.14 7.97 22.94 8.46
-7 24.92 8.15 24.72 7.99 24.62 7.83 24.42 8.32 24.22 8.81 24.92 6.74 24.72 7.07 24.62 7.23 24.42 7.81 24.22 8.22
-6 25.56 8.07 25.36 7.91 25.26 7.83 25.06 8.24 24.86 8.73 25.56 6.66 25.36 6.99 25.26 7.15 25.06 7.72 24.86 8.14
-5 26.20 8.24 26.00 8.07 25.90 7.91 25.70 8.40 25.50 8.81 26.20 6.74 26.00 7.07 25.90 7.23 25.70 7.81 25.50 8.22
-3 27.40 8.48 27.20 8.32 27.10 8.15 26.86 8.65 26.50 9.06 27.40 6.90 27.20 7.23 27.10 7.48 26.86 7.97 26.50 8.46
-1 28.60 8.65 28.40 8.48 28.30 8.40 28.02 8.90 27.50 9.31 28.60 7.15 28.40 7.40 28.30 7.64 28.02 8.22 27.50 8.71
0 29.20 8.77 29.00 8.61 28.90 8.53 28.60 9.02 28.00 9.47 29.20 7.23 29.00 7.48 28.90 7.72 28.60 8.30 28.00 8.79
1 31.12 8.90 30.80 8.73 30.46 8.65 29.56 9.14 28.00 9.64 31.12 7.31 30.80 7.56 30.46 7.81 29.56 8.38 28.00 8.88
3 32.40 8.81 32.00 8.65 31.50 8.48 30.20 8.98 28.00 9.47 32.40 7.48 32.00 7.72 31.50 7.97 30.20 8.55 28.00 9.04
5 32.40 8.65 32.00 8.48 31.50 8.32 30.20 8.81 28.00 9.31 32.40 7.56 32.00 7.89 31.50 8.14 30.20 8.71 28.00 9.29
6 33.20 8.57 32.50 8.40 31.50 8.24 30.20 8.73 28.00 9.23 33.20 7.64 32.50 7.97 31.50 8.22 30.20 8.79 28.00 9.37
7 33.80 8.73 32.95 8.57 31.73 8.40 30.20 8.90 28.00 9.47 33.80 7.89 32.95 8.22 31.73 8.46 30.20 9.04 28.00 9.61
9 35.00 9.14 33.85 8.98 32.18 8.81 30.20 9.39 28.00 9.88 35.00 8.22 33.85 8.63 32.18 8.88 30.20 9.52 28.00 10.03
10 35.60 9.39 34.30 9.18 32.40 9.02 30.20 9.60 28.00 10.09 35.60 8.42 34.30 8.83 32.40 9.08 30.20 9.74 28.00 10.27
11 35.60 9.64 34.30 9.39 32.40 9.23 30.20 9.80 28.00 10.30 35.60 8.63 34.30 9.04 32.40 9.29 30.20 9.94 28.00 10.52
14 35.60 10.13 34.30 9.88 32.40 9.72 30.20 10.30 28.00 10.87 35.60 9.12 34.30 9.52 32.40 9.78 30.20 10.52 28.00 11.18
15 35.60 10.38 34.30 10.21 32.40 10.05 30.20 10.63 28.00 11.20 35.60 9.45 34.30 9.86 32.40 10.11 30.20 10.85 28.00 11.50

4
Potencia total de las unidades interiores combinadas: 130%
Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 16.60 7.12 16.40 7.43 16.30 7.74 16.10 8.21 15.90 8.67
-17 18.52 7.05 18.32 7.35 18.22 7.66 18.02 8.13 17.82 8.52
-15 19.80 6.89 19.60 7.28 19.50 7.59 19.30 8.05 19.10 8.44
-13 21.08 6.74 20.88 7.05 20.78 7.43 20.58 7.82 20.38 8.21
-11 22.36 6.58 22.16 6.89 22.06 7.20 21.86 7.59 21.66 7.97
-10 23.00 6.50 22.80 6.81 22.70 7.12 22.50 7.51 22.30 7.90
-9 23.64 6.43 23.44 6.74 23.34 7.05 23.14 7.43 22.94 7.82
-7 24.92 6.19 24.72 6.50 24.62 6.81 24.42 7.20 24.22 7.59
-6 25.56 6.12 25.36 6.43 25.26 6.74 25.06 7.12 24.86 7.43
-5 26.20 6.19 26.00 6.50 25.90 6.81 25.70 7.20 25.50 7.51
-3 27.40 6.35 27.20 6.66 27.10 6.97 26.86 7.35 26.50 7.74
-1 28.60 6.50 28.40 6.81 28.30 7.12 28.02 7.51 27.50 7.90
0 29.20 6.58 29.00 6.89 28.90 7.20 28.60 7.59 28.00 7.97
1 31.12 6.66 30.80 6.97 30.46 7.28 29.56 7.66 28.00 8.05
3 32.40 6.81 32.00 7.12 31.50 7.43 30.20 7.90 28.00 8.28
5 32.40 6.97 32.00 7.28 31.50 7.66 30.20 8.05 28.00 8.44
6 33.20 7.05 32.50 7.43 31.50 7.74 30.20 8.13 28.00 8.59
7 33.80 7.20 32.95 7.51 31.73 7.90 30.20 8.28 28.00 8.75
9 35.00 7.43 33.85 7.82 32.18 8.13 30.20 8.59 28.00 9.06
10 35.60 7.55 34.30 7.94 32.40 8.28 30.20 8.75 28.00 9.21
11 35.60 7.66 34.30 8.05 32.40 8.44 30.20 8.90 28.00 9.37
14 35.60 8.05 34.30 8.36 32.40 8.75 30.20 9.29 28.00 9.68
15 35.60 8.21 34.30 8.59 32.40 8.98 30.20 9.45 28.00 9.99

NOTE
• CAP: Capacity at compressor maximum frequency (kW)
• IPT: Input power (kW)
• TEMP: Outdoor air inlet temperature (WB (ºC))

 RAS-12FSNM1
Potencia total de las unidades interiores combinadas: 50% Potencia total de las unidades interiores combinadas: 60%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 9.58 4.73 9.48 4.94 9.43 5.15 9.32 5.45 9.22 5.76 11.48 5.99 11.36 6.25 11.30 6.51 11.18 6.90 11.06 7.29
-17 10.75 4.68 10.65 4.89 10.60 5.09 10.50 5.40 10.40 5.66 12.89 5.92 12.77 6.19 12.71 6.45 12.59 6.84 12.47 7.16
-15 11.53 9.26 11.43 9.31 11.38 9.42 11.28 9.83 11.18 10.24 13.82 11.39 13.70 11.65 13.64 11.85 13.52 12.44 13.40 13.09
-13 12.31 8.54 12.21 8.59 12.16 8.64 12.06 9.06 11.96 9.42 14.76 10.55 14.64 10.74 14.58 10.94 14.46 11.52 14.34 12.05
-11 13.09 7.82 12.99 7.87 12.94 7.92 12.84 8.28 12.74 8.64 15.70 9.64 15.58 9.90 15.52 10.03 15.40 10.55 15.28 11.07
-10 13.49 7.46 13.39 7.51 13.34 7.56 13.24 7.90 13.13 8.23 16.17 9.21 16.05 9.44 15.99 9.57 15.87 10.09 15.75 10.58
-9 13.88 7.10 13.78 7.15 13.73 7.20 13.63 7.51 13.53 7.82 16.64 8.79 16.52 8.98 16.46 9.12 16.34 9.64 16.22 10.09
-7 14.66 6.38 14.56 6.43 14.51 6.43 14.41 6.74 14.31 7.00 17.58 7.94 17.45 8.07 17.39 8.20 17.27 8.66 17.15 9.12
-6 15.05 5.97 14.95 6.02 14.90 6.07 14.80 6.33 14.70 6.59 18.04 7.49 17.92 7.62 17.86 7.75 17.74 8.20 17.62 8.59
-5 15.44 5.87 15.34 5.87 15.29 5.92 15.19 6.23 15.09 6.48 18.51 7.29 18.39 7.42 18.33 7.55 18.21 7.94 18.09 8.33
-3 16.22 5.56 16.12 5.61 16.07 5.61 15.97 5.92 15.75 6.12 19.45 6.84 19.33 6.97 19.27 7.10 19.15 7.49 18.89 7.88
-1 17.01 5.25 16.90 5.30 16.85 5.35 16.75 5.56 16.41 5.81 20.39 6.45 20.27 6.58 20.21 6.64 20.09 7.03 19.68 7.36
0 17.40 5.12 17.30 5.17 17.25 5.20 17.15 5.43 16.74 5.66 20.86 6.22 20.74 6.35 20.68 6.41 20.56 6.80 20.08 7.13
1 18.06 4.99 17.96 5.04 17.91 5.04 17.69 5.30 16.74 5.51 21.65 5.99 21.53 6.12 21.47 6.19 21.21 6.58 20.08 6.90
3 18.50 4.79 18.40 4.84 18.35 4.84 18.05 5.04 16.74 5.30 22.18 6.12 22.06 6.25 22.00 6.32 21.64 6.64 20.08 7.03
5 18.50 4.94 18.40 4.99 18.35 5.04 18.05 5.25 16.74 5.45 22.18 6.25 22.06 6.32 22.00 6.45 21.64 6.77 20.08 7.16
6 19.05 5.04 18.95 5.09 18.80 5.15 18.05 5.35 16.74 5.61 22.84 6.25 22.72 6.38 22.54 6.51 21.64 6.84 20.08 7.16
7 19.33 5.20 19.20 5.25 18.94 5.25 18.05 5.51 16.74 5.71 23.17 6.45 23.02 6.58 22.71 6.71 21.64 7.03 20.08 7.42
9 19.88 5.45 19.70 5.45 19.21 5.51 18.05 5.76 16.74 6.02 23.83 6.84 23.62 6.97 23.04 7.10 21.64 7.49 20.08 7.81
10 20.15 5.56 19.95 5.58 19.35 5.63 18.05 5.89 16.74 6.15 24.16 7.03 23.92 7.16 23.20 7.29 21.64 7.68 20.08 8.04
11 21.04 5.66 20.39 5.71 19.35 5.76 18.05 6.02 16.74 6.28 25.22 7.23 24.45 7.36 23.20 7.49 21.64 7.88 20.08 8.27
14 21.26 5.97 20.50 6.02 19.35 6.02 18.05 6.33 16.74 6.59 25.49 7.68 24.58 7.81 23.20 7.94 21.64 8.40 20.08 8.79
15 21.26 6.12 20.50 6.23 19.35 6.23 18.05 6.48 16.74 6.79 25.49 8.01 24.58 8.14 23.20 8.27 21.64 8.72 20.08 9.12

63 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Tablas de capacidad de calefacción

 RAS-12FSNM
Potencia total de las unidades interiores combinadas: 50% Potencia total de las unidades interiores combinadas: 60%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 9.58 4.73 9.48 4.94 9.43 5.15 9.32 5.45 9.22 5.76 11.48 5.99 11.36 6.25 11.30 6.51 11.18 6.90 11.06 7.29
-17 10.75 4.68 10.65 4.89 10.60 5.09 10.50 5.40 10.40 5.66 12.89 5.92 12.77 6.19 12.71 6.45 12.59 6.84 12.47 7.16
-15 11.53 9.26 11.43 9.31 11.38 9.42 11.28 9.83 11.18 10.24 13.82 11.39 13.70 11.65 13.64 11.85 13.52 12.44 13.40 13.09
-13 12.31 8.54 12.21 8.59 12.16 8.64 12.06 9.06 11.96 9.42 14.76 10.55 14.64 10.74 14.58 10.94 14.46 11.52 14.34 12.05
-11 13.09 7.82 12.99 7.87 12.94 7.92 12.84 8.28 12.74 8.64 15.70 9.64 15.58 9.90 15.52 10.03 15.40 10.55 15.28 11.07
-10 13.49 7.46 13.39 7.51 13.34 7.56 13.24 7.90 13.13 8.23 16.17 9.21 16.05 9.44 15.99 9.57 15.87 10.09 15.75 10.58
-9 13.88 7.10 13.78 7.15 13.73 7.20 13.63 7.51 13.53 7.82 16.64 8.79 16.52 8.98 16.46 9.12 16.34 9.64 16.22 10.09
-7 14.66 6.38 14.56 6.43 14.51 6.43 14.41 6.74 14.31 7.00 17.58 7.94 17.45 8.07 17.39 8.20 17.27 8.66 17.15 9.12
-6 15.05 5.97 14.95 6.02 14.90 6.07 14.80 6.33 14.70 6.59 18.04 7.49 17.92 7.62 17.86 7.75 17.74 8.20 17.62 8.59
-5 15.44 5.87 15.34 5.87 15.29 5.92 15.19 6.23 15.09 6.48 18.51 7.29 18.39 7.42 18.33 7.55 18.21 7.94 18.09 8.33
-3 16.22 5.56 16.12 5.61 16.07 5.61 15.97 5.92 15.75 6.12 19.45 6.84 19.33 6.97 19.27 7.10 19.15 7.49 18.89 7.88
-1 17.01 5.25 16.90 5.30 16.85 5.35 16.75 5.56 16.41 5.81 20.39 6.45 20.27 6.58 20.21 6.64 20.09 7.03 19.68 7.36
0 17.40 5.12 17.30 5.17 17.25 5.20 17.15 5.43 16.74 5.66 20.86 6.22 20.74 6.35 20.68 6.41 20.56 6.80 20.08 7.13
1 18.06 4.99 17.96 5.04 17.91 5.04 17.69 5.30 16.74 5.51 21.65 5.99 21.53 6.12 21.47 6.19 21.21 6.58 20.08 6.90
3 18.50 4.79 18.40 4.84 18.35 4.84 18.05 5.04 16.74 5.30 22.18 6.12 22.06 6.25 22.00 6.32 21.64 6.64 20.08 7.03
5 18.50 4.94 18.40 4.99 18.35 5.04 18.05 5.25 16.74 5.45 22.18 6.25 22.06 6.32 22.00 6.45 21.64 6.77 20.08 7.16
6 19.05 5.04 18.95 5.09 18.80 5.15 18.05 5.35 16.74 5.61 22.84 6.25 22.72 6.38 22.54 6.51 21.64 6.84 20.08 7.16
7 19.33 5.20 19.20 5.25 18.94 5.25 18.05 5.51 16.74 5.71 23.17 6.45 23.02 6.58 22.71 6.71 21.64 7.03 20.08 7.42
9 19.88 5.45 19.70 5.45 19.21 5.51 18.05 5.76 16.74 6.02 23.83 6.84 23.62 6.97 23.04 7.10 21.64 7.49 20.08 7.81
10 20.15 5.56 19.95 5.58 19.35 5.63 18.05 5.89 16.74 6.15 24.16 7.03 23.92 7.16 23.20 7.29 21.64 7.68 20.08 8.04
11 21.04 5.66 20.39 5.71 19.35 5.76 18.05 6.02 16.74 6.28 25.22 7.23 24.45 7.36 23.20 7.49 21.64 7.88 20.08 8.27
14 21.26 5.97 20.50 6.02 19.35 6.02 18.05 6.33 16.74 6.59 25.49 7.68 24.58 7.81 23.20 7.94 21.64 8.40 20.08 8.79
15 21.26 6.12 20.50 6.23 19.35 6.23 18.05 6.48 16.74 6.79 25.49 8.01 24.58 8.14 23.20 8.27 21.64 8.72 20.08 9.12

Potencia total de las unidades interiores combinadas: 70% Potencia total de las unidades interiores combinadas: 80%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 13.39 7.06 13.25 7.36 13.18 7.67 13.03 8.13 12.89 8.59 15.29 7.93 15.13 8.27 15.05 8.62 14.89 9.14 14.73 9.65
-17 15.03 6.98 14.88 7.29 14.81 7.59 14.67 8.05 14.53 8.44 17.16 7.84 17.00 8.19 16.92 8.53 16.76 9.05 16.60 9.48
-15 16.12 12.27 15.98 12.35 15.91 12.35 15.77 13.04 15.63 13.65 18.41 11.81 18.25 11.98 18.17 12.15 18.01 12.84 17.85 13.45
-13 17.21 11.81 17.07 11.81 17.00 11.89 16.86 12.50 16.72 13.11 19.66 11.81 19.50 11.98 19.42 12.15 19.26 12.76 19.10 13.45
-11 18.30 11.27 18.16 11.35 18.09 11.35 17.95 11.96 17.81 12.58 20.91 11.72 20.75 11.90 20.67 12.07 20.51 12.76 20.35 13.36
-10 18.85 11.04 18.71 11.08 18.64 11.12 18.50 11.69 18.36 12.31 21.53 11.72 21.37 11.85 21.29 12.02 21.13 12.71 20.97 13.32
-9 19.40 10.81 19.26 10.81 19.19 10.89 19.05 11.43 18.91 12.04 22.16 11.72 22.00 11.81 21.92 11.98 21.76 12.67 21.60 13.27
-7 20.49 10.35 20.35 10.35 20.28 10.35 20.14 10.89 20.00 11.50 23.41 11.64 23.25 11.81 23.17 11.98 23.01 12.58 22.85 13.30
-6 21.04 10.05 20.90 10.12 20.83 10.12 20.69 10.66 20.55 11.20 24.03 11.64 23.87 11.81 23.79 11.90 23.63 12.58 23.47 13.19
-5 21.58 9.74 21.44 9.74 21.37 9.82 21.23 10.28 21.09 10.81 24.66 11.21 24.50 11.38 24.42 11.55 24.26 12.15 24.10 12.76
-3 22.68 9.05 22.54 9.05 22.47 9.13 22.33 9.59 22.02 10.05 25.91 10.34 25.75 10.52 25.67 10.60 25.50 11.21 25.15 11.72
-1 23.77 8.36 23.63 8.36 23.56 8.44 23.42 8.90 22.94 9.36 27.15 9.48 26.99 9.57 26.91 9.74 26.75 10.26 26.21 10.77
0 24.32 8.05 24.18 8.05 24.11 8.09 23.97 8.55 23.41 8.97 27.78 9.05 27.62 9.14 27.54 9.31 27.38 9.83 26.74 10.30
1 25.24 7.75 25.10 7.75 25.03 7.75 24.72 8.21 23.41 8.59 28.84 8.62 28.68 8.71 28.60 8.88 28.24 9.40 26.74 9.83
3 25.86 7.59 25.72 7.59 25.65 7.67 25.23 8.05 23.41 8.44 29.54 8.27 29.38 8.45 29.30 8.53 28.82 9.05 26.74 9.48
5 25.86 7.52 25.72 7.52 25.65 7.59 25.23 7.98 23.41 8.36 29.54 8.02 29.38 8.10 29.30 8.27 28.82 8.71 26.74 9.14
6 26.63 7.59 26.49 7.67 26.28 7.67 25.23 8.05 23.41 8.44 30.42 8.36 30.26 8.45 30.02 8.62 28.82 9.05 26.74 9.57
7 27.02 7.82 26.84 7.82 26.47 7.90 25.23 8.28 23.41 8.74 30.86 8.36 30.66 8.45 30.24 8.62 28.82 9.05 26.74 9.57
9 27.79 8.28 27.54 8.28 26.86 8.28 25.23 8.74 23.41 9.20 31.74 8.79 31.46 8.96 30.68 9.05 28.82 9.57 26.74 10.00
10 28.17 8.47 27.89 8.47 27.05 8.51 25.23 8.97 23.41 9.43 32.18 9.01 31.86 9.18 30.90 9.27 28.82 9.78 26.74 10.26
11 29.41 8.67 28.51 8.67 27.05 8.74 25.23 9.20 23.41 9.66 33.59 9.22 32.57 9.40 30.90 9.48 28.82 10.00 26.74 10.52
14 29.71 9.20 28.66 9.20 27.05 9.28 25.23 9.74 23.41 10.28 33.94 9.74 32.74 9.91 30.90 10.00 28.82 10.60 26.74 11.12
15 29.71 9.51 28.66 9.59 27.05 9.59 25.23 10.05 23.41 10.58 33.94 10.09 32.74 10.17 30.90 10.34 28.82 10.95 26.74 11.46

Potencia total de las unidades interiores combinadas: 90% Potencia total de las unidades interiores combinadas: 100%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 17.20 8.61 17.02 8.99 16.93 9.36 16.74 9.93 16.56 10.49 19.10 9.11 18.90 9.50 18.80 9.90 18.60 10.49 18.40 11.09
-17 19.30 8.52 19.12 8.90 19.03 9.27 18.85 9.83 18.67 10.30 21.44 9.01 21.24 9.41 21.14 9.80 20.94 10.40 20.74 10.89
-15 20.71 12.83 20.53 12.27 20.44 11.80 20.26 12.36 20.08 13.02 23.00 12.47 22.80 11.68 22.70 10.79 22.50 11.39 22.30 11.88
-13 22.11 12.73 21.93 12.17 21.84 11.70 21.66 12.27 21.48 12.83 24.56 12.28 24.36 11.48 24.26 10.69 24.06 11.19 23.86 11.68
-11 23.51 12.64 23.33 12.08 23.24 11.52 23.06 12.17 22.88 12.73 26.12 12.08 25.92 11.29 25.82 10.49 25.62 10.99 25.42 11.58
-10 24.22 12.55 24.04 12.03 23.95 11.47 23.77 12.13 23.59 12.69 26.90 11.98 26.70 11.24 26.60 10.44 26.40 10.94 26.20 11.48
-9 24.92 12.45 24.74 11.99 24.65 11.42 24.47 12.08 24.29 12.64 27.68 11.88 27.48 11.19 27.38 10.40 27.18 10.89 26.98 11.39
-7 26.32 12.36 26.14 11.89 26.05 11.33 25.87 11.89 25.69 12.45 29.24 11.78 29.04 10.99 28.94 10.20 28.74 10.69 28.54 11.19
-6 27.03 12.36 26.85 11.80 26.76 11.33 26.58 11.89 26.40 12.45 30.02 11.68 29.82 10.89 29.72 10.10 29.52 10.59 29.32 11.09
-5 27.73 12.17 27.55 11.61 27.46 11.14 27.28 11.70 27.10 12.27 30.80 11.88 30.60 11.09 30.50 10.30 30.30 10.79 30.10 11.29
-3 29.13 11.89 28.95 11.33 28.86 10.86 28.68 11.42 28.29 11.99 32.36 12.28 32.16 11.48 32.06 10.59 31.86 11.19 31.42 11.68
-1 30.54 11.61 30.36 11.14 30.27 10.58 30.09 11.14 29.47 11.70 33.92 12.57 33.72 11.78 33.62 10.99 33.42 11.48 32.74 12.08
0 31.24 11.42 31.06 10.96 30.97 10.44 30.79 11.00 30.07 11.52 34.70 12.82 34.50 11.98 34.40 11.14 34.20 11.68 33.40 12.23
1 32.43 11.24 32.25 10.77 32.16 10.30 31.76 10.86 30.07 11.33 36.02 13.07 35.82 12.18 35.72 11.29 35.28 11.88 33.40 12.38
3 33.22 10.77 33.04 10.30 32.95 9.83 32.41 10.39 30.07 10.86 36.90 12.38 36.70 11.58 36.60 10.79 36.00 11.29 33.40 11.78
5 33.22 10.30 33.04 9.83 32.95 9.46 32.41 9.93 30.07 10.39 36.90 11.68 36.70 10.99 36.60 10.20 36.00 10.69 33.40 11.19
6 34.21 10.21 34.03 9.36 33.76 9.36 32.41 9.83 30.07 10.30 38.00 11.39 37.80 10.69 37.50 9.90 36.00 10.40 33.40 10.89
7 34.71 10.49 34.48 9.74 34.01 9.55 32.41 10.11 30.07 10.58 38.55 11.68 38.30 10.89 37.78 10.10 36.00 10.59 33.40 11.09
9 35.70 10.96 35.38 10.02 34.50 10.02 32.41 10.58 30.07 11.05 39.65 12.18 39.30 11.39 38.33 10.59 36.00 11.09 33.40 11.58
10 36.19 11.19 35.83 10.25 34.75 10.25 32.41 10.82 30.07 11.28 40.20 12.42 39.80 11.63 38.60 10.79 36.00 11.29 33.40 11.83
11 37.78 11.42 36.62 10.49 34.75 10.49 32.41 11.05 30.07 11.52 41.96 12.67 40.68 11.88 38.60 10.99 36.00 11.48 33.40 12.08
14 38.17 12.08 36.82 11.52 34.75 11.05 32.41 11.61 30.07 12.17 42.40 13.27 40.90 12.47 38.60 11.58 36.00 12.18 33.40 12.67
15 38.17 12.45 36.82 11.89 34.75 11.42 32.41 11.99 30.07 12.55 42.40 13.66 40.90 13.17 38.60 11.88 36.00 12.47 33.40 13.07

64 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Tablas de capacidad de calefacción

Potencia total de las unidades interiores combinadas: 110% Potencia total de las unidades interiores combinadas: 120%
Temperatura del aire de entrada interior (DB (ºC)) Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24 16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 19.10 9.51 18.90 9.92 18.80 10.34 18.60 10.96 18.40 11.58 19.10 9.57 18.90 9.98 18.80 10.40 18.60 11.02 18.40 11.65
-17 21.44 9.41 21.24 9.82 21.14 10.23 20.94 10.85 20.74 11.37 21.44 9.47 21.24 9.88 21.14 10.30 20.94 10.92 20.74 11.44
-15 23.00 11.06 22.80 10.85 22.70 10.65 22.50 11.27 22.30 11.89 23.00 9.47 22.80 9.88 22.70 10.09 22.50 10.82 22.30 11.54
-13 24.56 10.85 24.36 10.65 24.26 10.44 24.06 11.06 23.86 11.68 24.56 9.26 24.36 9.57 24.26 9.88 24.06 10.61 23.86 11.23
-11 26.12 10.65 25.92 10.44 25.82 10.23 25.62 10.85 25.42 11.47 26.12 9.05 25.92 9.36 25.82 9.67 25.62 10.40 25.42 10.92
-10 26.90 10.54 26.70 10.34 26.60 10.13 26.40 10.75 26.20 11.37 26.90 8.89 26.70 9.26 26.60 9.57 26.40 10.24 26.20 10.82
-9 27.68 10.44 27.48 10.23 27.38 10.03 27.18 10.65 26.98 11.27 27.68 8.74 27.48 9.15 27.38 9.47 27.18 10.09 26.98 10.71
-7 29.24 10.23 29.04 10.03 28.94 9.82 28.74 10.44 28.54 11.06 29.24 8.53 29.04 8.95 28.94 9.15 28.74 9.88 28.54 10.40
-6 30.02 10.13 29.82 9.92 29.72 9.82 29.52 10.34 29.32 10.96 30.02 8.43 29.82 8.84 29.72 9.05 29.52 9.78 29.32 10.30
-5 30.80 10.34 30.60 10.13 30.50 9.92 30.30 10.54 30.10 11.06 30.80 8.53 30.60 8.95 30.50 9.15 30.30 9.88 30.10 10.40
-3 32.36 10.65 32.16 10.44 32.06 10.23 31.86 10.85 31.42 11.37 32.36 8.74 32.16 9.15 32.06 9.47 31.86 10.09 31.42 10.71
-1 33.92 10.85 33.72 10.65 33.62 10.54 33.42 11.16 32.74 11.68 33.92 9.05 33.72 9.36 33.62 9.67 33.42 10.40 32.74 11.02
0 34.70 11.01 34.50 10.80 34.40 10.70 34.20 11.32 33.40 11.89 34.70 9.15 34.50 9.47 34.40 9.78 34.20 10.50 33.40 11.13
1 36.02 11.16 35.82 10.96 35.72 10.85 35.28 11.47 33.40 12.09 36.02 9.26 35.82 9.57 35.72 9.88 35.28 10.61 33.40 11.23
3 36.90 11.06 36.70 10.85 36.60 10.65 36.00 11.27 33.40 11.89 36.90 9.47 36.70 9.78 36.60 10.09 36.00 10.82 33.40 11.44
5 36.90 10.85 36.70 10.65 36.60 10.44 36.00 11.06 33.40 11.68 36.90 9.57 36.70 9.98 36.60 10.30 36.00 11.02 33.40 11.75
6 38.00 10.75 37.80 10.54 37.50 10.34 36.00 10.96 33.40 11.58 38.00 9.67 37.80 10.09 37.50 10.40 36.00 11.13 33.40 11.86
7 38.55 10.96 38.30 10.75 37.78 10.54 36.00 11.16 33.40 11.89 38.55 9.98 38.30 10.40 37.78 10.71 36.00 11.44 33.40 12.17
9 39.65 11.47 39.30 11.27 38.33 11.06 36.00 11.78 33.40 12.40 39.65 10.40 39.30 10.92 38.33 11.23 36.00 12.06 33.40 12.69
10 40.20 11.78 39.80 11.53 38.60 11.32 36.00 12.04 33.40 12.66 40.20 10.66 39.80 11.18 38.60 11.49 36.00 12.32 33.40 13.00
11 41.96 12.09 40.68 11.78 38.60 11.58 36.00 12.30 33.40 12.92 41.96 10.92 40.68 11.44 38.60 11.75 36.00 12.58 33.40 13.31
14 42.40 12.71 40.90 12.40 38.60 12.20 36.00 12.92 33.40 13.64 42.40 11.54 40.90 12.06 38.60 12.37 36.00 13.31 33.40 14.14
15 42.40 13.02 40.90 12.82 38.60 12.61 36.00 13.33 33.40 14.06 42.40 11.96 40.90 12.48 38.60 12.79 36.00 13.74 33.40 14.57

4
Potencia total de las unidades interiores combinadas: 130%
Temperatura del aire de entrada interior (DB (ºC))
TEMP
16 18 20 22 24
CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT
-20 19.10 9.30 18.90 9.71 18.80 10.10 18.60 10.70 18.40 11.31
-17 21.44 9.20 21.24 9.59 21.14 10.00 20.94 10.61 20.74 11.11
-15 23.00 8.99 22.80 9.50 22.70 9.90 22.50 10.51 22.30 11.02
-13 24.56 8.79 24.36 9.20 24.26 9.71 24.06 10.20 23.86 10.70
-11 26.12 8.60 25.92 8.99 25.82 9.40 25.62 9.90 25.42 10.41
-10 26.90 8.48 26.70 8.89 26.60 9.30 26.40 9.81 26.20 10.31
-9 27.68 8.38 27.48 8.79 27.38 9.20 27.18 9.71 26.98 10.20
-7 29.24 8.09 29.04 8.48 28.94 8.89 28.74 9.40 28.54 9.90
-6 30.02 7.98 29.82 8.38 29.72 8.79 29.52 9.30 29.32 9.71
-5 30.80 8.09 30.60 8.48 30.50 8.89 30.30 9.40 30.10 9.81
-3 32.36 8.29 32.16 8.69 32.06 9.09 31.86 9.59 31.42 10.10
-1 33.92 8.48 33.72 8.89 33.62 9.30 33.42 9.81 32.74 10.31
0 34.70 8.60 34.50 8.99 34.40 9.40 34.20 9.90 33.40 10.41
1 36.02 8.69 35.82 9.09 35.72 9.50 35.28 10.00 33.40 10.51
3 36.90 8.89 36.70 9.30 36.60 9.71 36.00 10.31 33.40 10.82
5 36.90 9.09 36.70 9.50 36.60 10.00 36.00 10.51 33.40 11.02
6 38.00 9.20 37.80 9.71 37.50 10.10 36.00 10.61 33.40 11.21
7 38.55 9.40 38.30 9.81 37.78 10.31 36.00 10.82 33.40 11.42
9 39.65 9.71 39.30 10.20 38.33 10.61 36.00 11.21 33.40 11.82
10 40.20 9.85 39.80 10.36 38.60 10.82 36.00 11.42 33.40 12.03
11 41.96 10.00 40.68 10.51 38.60 11.02 36.00 11.62 33.40 12.22
14 42.40 10.51 40.90 10.92 38.60 11.42 36.00 12.13 33.40 12.63
15 42.40 10.70 40.90 11.21 38.60 11.72 36.00 12.32 33.40 13.04

NOTE
• CAP: Capacity at compressor maximum frequency (kW)
• IPT: Input power (kW)
• TEMP: Outdoor air inlet temperature (WB (ºC))

65 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Factores de corrección

4.4 Factores de corrección


4.4.1  Factor de corrección de la longitud de las tuberías

H:
El factor de corrección se basa en la equivalencia de la longitud Diferencia de altura entre la unidad interior y la
de las tuberías en metros (EL) y la altura entre la unidades exterior (m).
interiores y la exterior en metros (H). • H>0: La unidad exterior está situada por encima
de la unidad interior (m).
• H<0: La unidad exterior está situada por debajo
de la unidad interior (m).

L:
Longitud real de la tubería en una dirección entre la
Unidad exterior Unidad interior
unidad interior y la unidad exterior (m).
Unidad EL:
exterior
Unidad Longitud equivalente de la tubería en una dirección
interior entre la unidad interior y la exterior (m).
• Un ángulo de 90° equivale a 0,5 m.
• Un ángulo de 180° equivale a 1,5 m.
• Un Multi-kit equivale a 0,5 m.

? N O TA
• Para garantizar una correcta selección de la unidad exterior, considere la unidad interior más alejada en las situaciones generales.
• En caso de una instalación con unidades interiores a alturas tanto mayores como menores que la de la unidad exterior, se deben
estudiar todas las situaciones con sus valores correspondientes de altura y longitud de la tubería equivalente y se tiene que considerar
el caso más desfavorable en relación a las gráficas que se muestran en esta sección.
• Si la longitud de las tuberías equivalente de las unidades interiores situadas en una posición mayor o menor en la unidad exterior es
la misma, la altura que se tiene que considerar es la correspondiente a la unidad interior situada en una posición mayor que la de la
unidad exterior, dado que es el caso más desfavorable.

66 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Factores de corrección

 Enfriamiento
RAS-(8-12)FSNM

Enfriamiento

4
 Calefacción
RAS-(8-12)FSNM
Calefacción

67 TCES0059 rev.2 - 06/2016


4 Capacidades y datos de selección

Factores de corrección

4.4.2  Factor de corrección de descarche

La capacidad de calefacción no contempla el funcionamiento con escarcha o descarche.


Cuando se tenga en cuenta este tipo de funcionamiento, la capacidad de calefacción se debe corregir de acuerdo con la
siguiente ecuación:

Capacidad de calefacción corregida = factor de corrección x capacidad de calefacción

Temp. de aire de entrada exterior (ºC DB)


-7 -5 -3 0 3 5 7
(HR = 85%)

Factor de corrección de descarche fD 0,95 0,93 0,88 0,85 0,87 0,90 1,00

? N O TA Capacidad de
El factor de corrección de descarche no es válido en calefacción
condiciones especiales, como por ejemplo, en caso de Capacidad
reducida
nevadas o de funcionamiento en períodos transitorios. debido a la
acumulación
de escarcha Tiempo

Descarche máx. 6 min.


1 ciclo

68 TCES0059 rev.2 - 06/2016


5 Curvas acústicas características

5 . C u r v a s a c ú s t i c a s c a r a c t e r í s t i c a s

Índice

5.1 Nivel acústico total................................................................................................................................. 70

5.2 Curvas de presión acústica.................................................................................................................... 71

5.3 Curvas de potencia acústica.................................................................................................................. 72

69 TCES0059 rev.2 - 06/2016


5 Curvas acústicas características

Nivel acústico total

5.1 Nivel acústico total


El nivel acústico total se ha medido en una cámara anecoica, por lo que debe tenerse en cuenta el sonido reflejado
cuando se instala la unidad.
Condiciones de la prueba:
1 Distancia de la unidad desde punto de medición: 1 metro desde el frente de la unidad; 1,5 metros desde el nivel del
suelo:

Posición para la medición del nivel acústico total

2 Fuente de alimentación:
Unidades trifásicas: 3N~ 380/415V, 50Hz.

? N O TA
Los datos acústicos se han medido en una cámara anecoica, por lo que debe tenerse en cuenta el sonido reflejado cuando se instala la
unidad.

3 La información proporcionada corresponde al modo de enfriamiento. En el modo de calefacción, el nivel de presión


acústica aumenta de 1 a 2 dB(A).
4 Los niveles de potencia acústica se han medido en una sala reverberante según la norma EN12102. Las condiciones
ambientales usadas son aquellas especificadas en EN14511 para pruebas de rendimiento.

70 TCES0059 rev.2 - 06/2016


5 Curvas acústicas características

Curvas de presión acústica

5.2 Curvas de presión acústica


RAS-8FSNM RAS-10FSNM
Modo Enfriamiento/Calefacción/Nocturno: 53/55/50 dB(A) Modo Enfriamiento/Calefacción/Nocturno: 56/58/53 dB(A)
Presión acústica en octavas (dB(C))

Presión acústica en octavas (dB(C))


Umbral Umbral
aproximado de

5
aproximado de
detección del detección del
sonido contínuo sonido contínuo

Frecuencia (Hz) Frecuencia (Hz)

RAS-12FSNM
Modo Enfriamiento/Calefacción/Nocturno: 59/61/55 dB(A)
Presión acústica en octavas (dB(C))

Umbral
aproximado de
detección del
sonido contínuo

Frecuencia (Hz)

71 TCES0059 rev.2 - 06/2016


5 Curvas acústicas características

Curvas de potencia acústica

5.3 Curvas de potencia acústica

RAS-8FSNM RAS-10FSNM
Nivel de potencia acústica en octavas (dB)

Nivel de potencia acústica en octavas (dB)


Umbral Umbral
aproximado de aproximado de
detección del detección del
sonido continuo sonido continuo

Frecuencia (Hz) Frecuencia (Hz)


Nivel de potencia acústica: Global 71 dB(A) Nivel de potencia acústica: Global 74 dB(A)

RAS-12FSNM
Nivel de potencia acústica en octavas (dB)

Umbral
aproximado de
detección del
sonido continuo

Frecuencia (Hz)
Nivel de potencia acústica: Global 77 dB(A)

72 TCES0059 rev.2 - 06/2016


6 Margen de funcionamiento

6 . M a r g e n d e f u n c i o n a m i e n t o

Índice

6.1 Fuente de alimentación.......................................................................................................................... 74

6.2 Margen de temperatura.......................................................................................................................... 74

73 TCES0059 rev.2 - 06/2016


6 Margen de funcionamiento

Fuente de alimentación

6.1 Fuente de alimentación

Tensión de funcionamiento Entre el 90 y el 110% de la tensión nominal

Desequilibrio de tensión Dentro de una desviación del 3% de cada tensión en el terminal principal de la unidad exterior

Tensión de arranque Superior al 85% de la tensión nominal

6.2 Margen de temperatura


En la siguiente tabla se indica el margen de temperaturas:

Funcionamiento con enfriamiento Funcionamiento con calefacción

Mínima 21ºC DB/15ºC WB 15ºC DB


Temperatura interior
Máxima 32ºC DB/25ºC WB 27ºC DB
Mínima -5ºC DB (*) -20º WB (**)
Temperatura exterior
Máxima 43ºC DB 15ºC WB

Diagrama de margen de temperaturas

Funcionamiento con enfriamiento Funcionamiento con calefacción


Temperatura del aire exterior (°C WB)
Temperatura del aire exterior (°C DB)

Temperatura del aire de entrada interior (°C WB) Temperatura del aire de entrada interior (°C DB)

? N O TA
• (*) 10°C DB ~ -5°C DB, margen de control de funcionamiento
• (**) -12°C WB ~ -20°C WB, margen de control de funcionamiento
• DB: bulbo seco; WB: bulbo húmedo.

• Margen de control de funcionamiento

74 TCES0059 rev.2 - 06/2016


7 Dimensiones generales

7. Dimensiones generales

Índice

7.1 Gráfico de dimensiones......................................................................................................................... 76

75 TCES0059 rev.2 - 06/2016


7 Dimensiones generales

Gráfico de dimensiones

7.1 Gráfico de dimensiones

Espacio para mantenimiento

En caso de obstáculos en ambos lados En caso de que no haya obstáculos en


y sin obstáculos en la parte superior. ambos lados, ni en la parte superior.

Unidades: mm

Nº Elemento Observaciones
1 Entrada de aire
2 Salida de aire
3 Tapa de servicio
4 Caja de interruptores eléctricos
5 Orificios para las tuberías de refrigerante y tubos de cableado eléctrico
6 Orificios de desagüe 3 de Ø24
7 Orificios de desagüe 2 de Ø26
8 Orificios para fijación de la unidad a la pared 4-(M5)
9 Tubería de líquido refrigerante Tuerca cónica: Øa
10 Tubería de gas refrigerante Tuerca cónica: Øb

76 TCES0059 rev.2 - 06/2016


8 Ciclo de refrigerante

8 . C i c l o d e r e f r i g e r a n t e

Índice

8.1 Ciclo de refrigerante de la unidad RAS-(8-12)FSNM............................................................................. 78

77 TCES0059 rev.2 - 06/2016


8 Ciclo de refrigerante

Ciclo de refrigerante de la unidad RAS-(8-12)FSNM

8.1 Ciclo de refrigerante de la unidad RAS-(8-12)FSNM

RAS-(8/10/12)FSNM1

8HP-FSNM1: Ø19.05
10HP-FSNM1: Ø22.2
RPI-2.5FSN4E 12HP-FSNM1:Ø25.4 or Ø28.6

Ø9.52

Ø9.52
Ø9.52

Ø9.52
RCD-1.5FSN2
Ø9.52

RPI-2.5FSN4E

8HP-FSNM1: Ø9.52
Ø9.52 10/12HP-FSNM1: Ø12.7

R410A 4,15 MPa


Flujo de Flujo de
Tubería de Presión de
refrigerante refrigerante Conexión con Conexión con Conexión
refrigerante de Refrigerante la prueba de
para para tuerca cónica brida soldada
la instalación hermeticidad
enfriamiento calefacción

Nº Elemento Nº Elemento Nº Elemento


Válvula de expansión controlada Sensor de presión del refrigerante
1 Compresor 9 16
por microordenador (sensor de baja presión)
Presostato de alta presión para
2 Intercambiador de calor 10 Válvula de retención 17
protección
3 Separador de aceite 11 Válvula de solenoide 18 Multi-Kit E-162SN4
4 Acumulador 12 Toma de presión 19 Intercambiador de calor interior
Válvula de servicio para tubería de
5 Filtro 13 20 Filtro interior
líquido
Válvula de servicio para tubería de
6 Distribuidor 14 21 Válvula de expansión interior
gas
Válvula de servicio para tubería de
7 Válvula de inversión 14 22 Distribuidor interior
gas
Sensor de presión del refrigerante
8 Tubo capilar 15 23 Multi-Kit E-102SN4
(sensor de alta presión)

78 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

9 . I n s t a l a c i ó n d e l a s t u b e r í a s y
carga de refrigerante

Índice

9.1 Selección de las tuberías de refrigerante............................................................................................... 80


9.1.1  Número máximo y mínimo de unidades interiores por unidad exterior.......................................................... 80
9.1.2  Rango de tuberías de refrigerante................................................................................................................. 80
9.1.3  Longitud de la tubería de refrigerante mediante ajuste de conmutadores DIP.............................................. 81
9.1.4  Tamaño de la tubería y kit de conexiones múltiples....................................................................................... 81

9.2 Multi-kits y distribuidores........................................................................................................................ 83


9.2.1 Tamaños......................................................................................................................................................... 83
9.2.2  Método de distribución................................................................................................................................... 84
9.2.3  Tuberías de cobre y tamaños......................................................................................................................... 87

9.3 Cantidad de carga de refrigerante......................................................................................................... 90


9.3.1  Cálculo de la carga de refrigerante adicional (R410A)................................................................................... 90
9.3.2  Ejemplos de cálculo....................................................................................................................................... 92

9.4 Precaución con las fugas de refrigerante............................................................................................... 98


9.4.1  Máxima concentración permisible de gas HCFC/HFC................................................................................... 98
9.4.2  Cálculo de la concentración de refrigerante................................................................................................... 98
9.4.3  Contramedidas en caso de fugas de refrigerante......................................................................................... 98

79 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Selección de las tuberías de refrigerante

9.1 Selección de las tuberías de refrigerante

El sistema Set-Free FSNM ha sido diseñado teniendo en cuenta todos los tipos de instalación posibles. Por ello,
HITACHI emplea dos distribuidores de tuberías distintos: Sistema de kits de conexiones múltiples y sistema de
distribuidor.
9.1.1  Número máximo y mínimo de unidades interiores por unidad exterior

Con el sistema Set-Free FSNM es posible conectar una unidad exterior con hasta 10 unidades interiores.
Utilizando un control inverter, también se encuentra disponible una amplia gama de controles de la capacidad de
funcionamiento. Se puede optar por una potencia total máxima combinada del 130% y una potencia total mínima
combinada del 50% realizando una combinación de unidades interiores, en comparación con la capacidad nominal de
la unidad exterior. De esta forma, el nuevo sistema puede satisfacer todos los requisitos de aire acondicionado en la
mayoría de los edificios de oficinas.

Unidad interior
Restricciones de la
Número máximo de
unidad RPK-FSNH3M
unidades interiores
Unidad (número máximo de Capacidad de Gama de
Capacidad de Capacidad de conectables (la suma
exterior unidades interiores funcionamiento capacidades
combinación combinación de unidades RPK
RPK-FSNH3M individual de
mínima (CV) máxima (CV) instaladas y otras
combinables con el mínima (CV) combinación
unidades interiores)
kit de la válvula de
(*)
expansión EV-1.5N1)
RAS-8FSNM 4,0 10,4
del 50% al
RAS-10FSNM 5,0 13,0 10 (8) 8 0,8
130%
RAS-12FSNM 6,0 13,2

? N O TA
(*) Entre paréntesis se indica el número máximo recomendado de unidades interiores conectables (solo para unidades interiores de 0,8 y
1,0). Si conecta más de 8, puede producirse la percepción de corrientes frías durante el funcionamiento con calefacción.

9.1.2  Rango de tuberías de refrigerante

La selección y distribución de las tuberías debe diseñarse de acuerdo con las especificaciones siguientes:
Rango
Elemento
aplicable
Real 100
Longitud entre la UE y la UI más alejada: L (m)
Equivalente 120
Longitud total de las tuberías (m) 250
Longitud de las tuberías entre la 1ª bifurcación y la UI más alejada: Li (m) 40
Longitud de las tuberías desde cada UI (m) 40
U.E. más alta 40
Diferencia de altura entre la UI y la UE: Hi-o (m)
U.E. más baja 30
Diferencia de altura entre U. I.: Hi (m) 15

? N O TA
Las tuberías de líquido y de gas deben tener la misma longitud y el mismo recorrido.

80 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Selección de las tuberías de refrigerante

9.1.3  Longitud de la tubería de refrigerante mediante ajuste de conmutadores DIP

La longitud de las tuberías de refrigerante entre las unidades interiores y las exteriores deben diseñarse de acuerdo con
el diagrama siguiente.
Mantenga el punto de diseño dentro de la zona oscura del diagrama, que muestra la diferencia de altura en función de la
longitud de las tuberías.

Cuando la unidad exterior


está instalada en
una posición más elevada
que la unidad interior Ajuste de
fábrica

Longitud de las
tuberías (m)

Cuando la unidad
exterior está instalada en
una posición inferior que
la unidad interior

9.1.4  Tamaño de la tubería y kit de conexiones múltiples

Además del tradicional sistema “Uni-Piping”, en el que se puede utilizar el mismo tamaño de tubería que la tubería de
refrigerante principal, también se puede usar el sistema "Down-pipe" (tuberías de tamaño reducido), que ofrece un coste
menor.
Tal como se muestra en la siguiente tabla, el sistema "Uni-piping" está disponible para unidades de 8 CV.

Sistemas de tuberías
Unidad
Uni-Piping Tamaño reducido

RAS-(8-12)FSNM

? N O TA
• En el caso del sistema Uni-Piping, el tamaño de la tubería y el multi-kit desde la unidad exterior hasta el último multi-kit son iguales.
• Si el tamaño del multi-kit situado después del 2º kit es superior que el del 1º, use un kit del mismo tamaño que el 1º.
• Si el tamaño de la tubería después de la 1ª bifurcación es superior que el tamaño de la tubería entre la unidad exterior y el 1er kit, use
una tubería del mismo tamaño que el 1er kit.
• Si desea utilizar el sistema “Uni-piping” para configuraciones no incluidas en la tabla, consulte con su distribuidor.

81 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Selección de las tuberías de refrigerante

Tabla 1:
De la unidad exterior al primer multi-kit

Tamaño de las tuberías (Ømm)


Unidad Multi-kit
Gas Líquido
RAS-8FSNM 19,05 9,52 (*) E-102SN4
RAS-10FSNM 22,2 12,7 E-162SN4
RAS-12FSNM 25,4~28,6 12,7 E-162SN4

? N O TA
• (*): Si la longitud equivalente de la tubería de refrigerante es superior a 70 m, utilice una tubería de líquido de Ø12,7.
• (En este caso, utilice el kit MW-162AN).

Tabla 2:
Del primer multi-kit al último multi-kit

Tamaño de la tubería (Ømm)


Unidad Multi-kit
Gas Líquido
12≤CV 25,4-28,6 12,7 E-162SN4
9≤CV<12 22,2 9,52 E-102SN4
6≤CV<9 19,05 9,52 E-102SN4
CV<6 15,88 9,52 E-102SN4

? N O TA
• Si el tamaño del multi-kit es mayor que el de la primera bifurcación, adjuste el tamaño del multi-kit al de la primer bifurcación.
• En caso de que el tamaño de la tubería seleccionada tras la primera bifurcación sea superior al tamaño de la tubería antes de la
primera bifurcación, utilice el mismo tamaño de la tubería antes de la bifurcación.

Tabla 3:
Kit de conexiones múltiples a unidad interior

Capacidad total de Tamaño de la tubería (Ømm) Longitud máxima


la unidad interior de la tubería de
(CV) Gas Líquido líquido (m)
de 0,8 a 2 12,7 6,35 15
De 2,5 a 6 15,88 9,52 15
8 19,05 9,52 15
10 22,2 9,52 15

? N O TA
El tamaño de la tubería del multi-kit debe ser el mismo que el de la tubería de la unidad interior.

Tabla 4:
Sistema de distribuidor

Capacidad total de Tamaño de la tubería (Ømm)


Número de
la unidad interior Distribuidor
bifurcaciones Gas Líquido
(CV)
5~8 4 15,88/19,05 9,52 MH-84N1
5~10 8 15,88/19,05/22,2 9,52 MH-108AN

82 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Multi-kits y distribuidores

9.2 Multi-kits y distribuidores


9.2.1  Tamaños

 Multi-kits - distribuidor en línea


E-102SN4
Línea de gas Línea de líquido

E-162SN4
Línea de gas Línea de líquido

A A la unidad interior
B A la unidad exterior
C A la tubería principal

83 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Multi-kits y distribuidores

 Distribuidores
Tubería de Tubería de
Extensor Extensor
cierre para cierre para
Línea de gas para la línea Línea de líquido para la línea
la línea de la línea de
de gas de líquido
gas líquido

ID9.52
ID12.7 OD9.52
MH-84N1

95
ID 22.2

ID6.35
ID 25.4 OD 19.05
3x60=180
Cant.: 2 ID9.52 ID9.52 Cant.: 2
Cant.: 4

Ø19.05

Ø9.53 ID9.52
ID9.53
MH-108AN

ID9.53

Cant.: 6 Cant.: 6
Cant.: 2 Cant.: 8

Ø9.53
(Para cerrar)

9.2.2  Método de distribución

 Distribución en línea
Se pueden utilizar distribuidores en línea para el primer y segundo nivel de bifurcación desde la tubería de distribución
principal, para el tercer y cuarto nivel no es posible. Consulte a continuación los ejemplos de bifurcaciones correctas e
incorrectas.

Método de la bifurcación

Correcto Incorrecto

Máx. 40m

1ª distribución de tubería principal

Distribuidor en línea
1ª distribución de tubería principal

2ª distribución de tubería principal


Tubería bifurcada de la
tubería principal 3ª distribución de tubería principal
2ª distribución de tubería principal Unidad interior Incorrecto

84 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Multi-kits y distribuidores

Posición de instalación
• Instalación horizontal
Sitúe las bifurcaciones en el mismo plano horizontal. (Inclinación máxima de 30º)
Asegúrese de que la tubería está totalmente recta por lo menos durante 0,5m después de cada codo.

Horizontal
Correcto Incorrecto
Hacia arriba Hacia arriba
Tramo recto de
0,5 m mínimo

Hacia abajo

Hacia abajo

Inclinación
máxima de
±30º
Inclinación
máxima de
±30º

• Instalación vertical
El tramo recto de la conexión de la tubería del lateral de la unidad exterior se realiza como se indica a continuación:
-- La pieza de conexión de la tubería colectiva se instala hacia arriba; el tramo recto debe tener un mínimo de 0,5 m.
-- La pieza de conexión de la tubería colectiva se instala hacia abajo; el tramo recto debe tener un mínimo de 0,3 m.

Vertical
Correcto Correcto

Hacia arriba Hacia arriba

Tramo recto
de 0,5 m
como mínimo

9
Bifurcación hacia arriba

Bifurcación
Tramo recto hacia abajo
de 0,3 m
como mínimo
Hacia abajo Hacia abajo

85 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Multi-kits y distribuidores

 Bifurcación de colector
Método de la bifurcación
No conecte dos bifurcaciones de colector consecutivamente.

Unidad interior Colector INCORRECTO


CORRECTO

Colector
Tubería principal
Tubería principal

Unidad interior

Tubería principal

Colector

Posición de instalación
Realice siempre la instalación de forma horizontal.
(Ej.: en el caso del modelo MH-108AN)

Horizontalmente

Lateral de la tubería de gas


Horizontalmente

Lateral de la tubería de líquido

! PRECAUCIÓN
Selle el extremo de las tuberías de bifurcación que no estén conectadas soldando las tuberías de cierre suministradas.

Combinación de bifurcaciones
• Es posible conectar el colector a la segunda bifurcación cuando la primera sea también la bifurcación en línea.
• No conecte una bifurcación en línea a la bifurcación de colector.

Máx. 40 m
Bifurcación en línea
Bifurcación en línea (primera bifurcación)
(primera bifurcación)

Colector
Segunda bifurcación
Colector

Unidad interior
Distribuidor en
línea

Máx. 40 m
Colector

86 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Multi-kits y distribuidores

9.2.3  Tuberías de cobre y tamaños

1 Prepare las tuberías de cobre suministradas localmente.


2 Seleccione el tamaño de tubería con el grosor y material adecuados. Utilice la siguiente tabla para seleccionarlas.

Diámetro nominal
Grosor (mm) Tipo de cobre
(mm) (pulg.)
6,35 1/4 0,80 Bobina
9,52 3/8 0,80 Bobina
12,70 1/2 0,80 Bobina
15,88 5/8 1,00 Bobina
19,05 3/4 1,00 En barra
22,23 7/8 1,00 En barra
25,40 1 1,00 En barra
28,60 1-1/8 1,00 En barra

? N O TA
• Si se utiliza tubo de cobre para tuberías de más de Ø19,05, no se podrá realizar una conexión cónica.
• Si fuera necesario, utilice un adaptador.
3 Utilice tuberías de cobre limpias. Asegúrese de que no haya polvo ni humedad en el interior. Inyecte nitrógeno sin
oxígeno en las tuberías antes de conectarlas para eliminar el polvo y las partículas que pueda haber en su interior.
4 Después de conectar las tuberías de refrigerante, selle el espacio abierto entre el orificio practicado y las tuberías
utilizando material aislante, como se muestra a continuación:

Material aislante

Tubería de refrigerante
suministrada por el instalador

Material aislante
Material aislante

! PRECAUCIÓN
• No utilice sierras, amoladoras, ni otras herramientas que generen polvo de cobre.


Cuando corte las tuberías, sujete la parte de la soldadura de acuerdo con las normativas locales y nacionales.
Use gafas de seguridad y guantes para cortar o soldar. 9

87 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Multi-kits y distribuidores

 Conexiones de las tuberías


Cuando conecte tuberías de líquido en unidades en las que la longitud de las tuberías supere los 15 metros, utilice
una tubería de Ø9,52. Fije la conexión de las tuberías según la figura siguiente. Utilice el aislamiento en la unión con la
unidad interior.

Utilice la tuerca Aísle esta zona Sujete esta pieza con


cónica de la unidad con el aislante el soporte suministrado
interior suministrado. o con cinta
Tubería de
refrigerante de
la instalación

Unidad
interior

Aislamiento en Soldadura Aislante


la unión con la Realice las conexiones cónicas suministrado
unidad interior después de fijar la tuerca cónica por el instalador
a la tubería de conexión en el kit
de conexiones múltiples

? N O TA
• Con un sistema sin humedad ni contaminación de aceite se obtiene el máximo rendimiento y un mayor ciclo de vida útil en comparación
con el de un sistema mal preparado. Tenga especial cuidado y asegúrese de que el interior de la tubería de cobre está limpio y seco.
• Para asegurarse de ello, inyecte nitrógeno sin oxígeno en las tuberías.

Correcto Incorrecto

! PRECAUCIÓN
• Tape el extremo de la tubería cuando la introduzca a través de un orificio.
• No coloque las tuberías directamente en el suelo sin un tapón o cinta cubriendo el extremo, tal como se muestra en las imágenes.
• Si la instalación no se puede terminar hasta el día siguiente o después, suelde los extremos de la tubería y cárguela con nitrógeno
sin oxígeno usando un dispositivo de acceso de tipo válvula Schrader para evitar la humedad y la contaminación por la entrada de
partículas extrañas.

88 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Multi-kits y distribuidores

 Aislamiento
Conecte el paquete aislante con el kit de conexiones múltiples a cada bifurcación utilizando una cinta de vinilo. Aísle
también las tuberías suministradas para evitar que disminuya la capacidad debido a las condiciones ambientales y al
rocío que se forma en la superficie de la tubería por baja presión.

? N O TA
Si utiliza espuma de polietileno, se recomienda un grosor de 10 mm para la tubería de líquido y entre 15 mm y 20 mm para la de gas.

! PRECAUCIÓN
• No emplee material aislante que contenga NH3 ya que puede dañar la tubería de cobre y convertirse en una futura fuente de fugas.
• Coloque el aislamiento cuando la temperatura de la superficie alcance la temperatura de la habitación. En caso contrario es posible
que el aislamiento se derrita.
• Si los extremos del sistema de tuberías están abiertos después de realizar la instalación, fije firmemente las tapas o bolsas de vinilo
a los extremos de las tuberías para evitar que entre polvo o humedad.

 Kit de desagüe de la unidad exterior (DBS-26) (Accesorio opcional)


En caso de que tenga que recoger el agua de desagüe del intercambiador de calor de la unidad exterior, utilice el kit de
desagüe. Sin embargo, se recomienda no utilizarlo en lugares en los que pueda acumularse la nieve.
Si es preciso recoger por completo el agua del desagüe, coloque bajo la unidad exterior una bandeja suministrada por el
instalador.

Ø32

Cantidad de kits de
CV unidad exterior
desagüe (unidades)
43 mm

8 a 12 CV DBS-26 x 4

89 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Cantidad de carga de refrigerante

9.3 Cantidad de carga de refrigerante


9.3.1  Cálculo de la carga de refrigerante adicional (R410A)

Aunque ya se haya cargado refrigerante en la unidad, puede que sea necesario añadir más refrigerante dependiendo de
la longitud de las tuberías.
• La cantidad adicional de refrigerante se debe determinar y cargar en el sistema de acuerdo con el siguiente
procedimiento:
• Anote la cantidad de refrigerante adicional para facilitar las tareas de servicio y mantenimiento.

Unidad exterior

H1≤40m (la unidad exterior está más alta)


H1≤30m (la unidad exterior está más baja)

Lt real ≤ 100 m
Lt equivalente ≤ 120 m

 Método de cálculo de la carga adicional de refrigerante (W kg)


Calcule la carga de refrigerante adicional de acuerdo con los siguientes pasos:

Paso 1:
Cálculo de la carga de refrigerante adicional para la tubería de líquido (W1 (kg))
(Rellene la siguiente tabla)

Diámetro de la tubería (mm) Longitud total de las tuberías (m) Carga adicional (kg/m) Subtotal (kg)
Ø12,7 x 0,12
Ø9,52 x 0,07
Ø6,35 x 0,03

Paso 2:
Cálculo de la carga de refrigerante adicional para la unidad interior (W2 (kg))
Cuando la unidad exterior está combinada con unidades interiores RPI-8/10FSN3E, es necesaria una carga de
refrigerante adicional (W2) = 1 kg/unidad.
Para unidades interiores de menos de 8 CV no será necesaria una carga de refrigerante adicional.

90 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Cantidad de carga de refrigerante

Paso 3:
Cálculo de la carga adicional de refrigerante total (W (kg))
Coloque los valores de W1 y W2 calculados en el paso 1 y en el paso 2 en la siguiente fórmula:

Carga total de refrigerante adicional: W= W1 + W2

La tabla siguiente muestra la cantidad máxima de refrigerante adicional permitida por unidad.

Carga máxima de
Unidad exterior
refrigerante adicional (kg)
RAS-(8-12)FSNM 13,5

? N O TA
• La cantidad de refrigerante adicional calculada, no debe superar la cantidad de refrigerante adicional máxima permitida.
• Si la carga de refrigerante adicional es superior a la carga adicional máxima permitida, debe ajustar la longitud de las tuberías de la
instalación.

• Carga
Cargue el refrigerante (R410A) en el sistema de acuerdo con las instrucciones del manual "SMES0059_rev0".
• Registro de la carga adicional
La carga total de refrigerante para este sistema se calcula con la siguiente fórmula:

Carga total de refrigerante: WTOT= W + W0

Este sistema = + = kg

La unidad exterior se suministra de fábrica con la carga de refrigerante W0 que se indica en la siguiente tabla:

W0 carga de refrigerante de

9
Unidad exterior
la unidad exterior (kg)
RAS-8FSNM 5,0
RAS-10FSNM 5,5
RAS-12FSNM 6,5

Anote la cantidad de carga de refrigerante para facilitar las tareas de servicio y mantenimiento.

Carga adicional total W kg

Carga de refrigerante total kg

Fecha de la carga de refrigerante

/ /

91 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Cantidad de carga de refrigerante

9.3.2  Ejemplos de cálculo

ELEMENTO SISTEMA DE DISTRIBUIDOR


Unidad exterior
Ejemplo de sistemas
H1≤40m (la unidad exterior está más alta)
1: Instalación simple con distribuidor H1≤30m (la unidad exterior está más baja)

La imagen es un ejemplo de 6 unidades interiores combinadas con una


unidad exterior.
Las tuberías de refrigerante se ilustran como una línea simple.
No obstante, las tuberías para la línea de gas y de líquido son necesarias
en la instalación. Lt real ≤ 100 m
Lt equivalente ≤ 120 m

Longitud total de las tuberías ≤ 250 m


Longitud máxima de las Longitud real Lt ≤ 100 m
tuberías Longitud equivalente Lt ≤ 120 m
Si la unidad exterior está más alta que la
H1 ≤ 40 m
Altura máxima entre la interior
unidad exterior y la interior Si la unidad exterior está más baja que la
H1 ≤ 30 m
interior
Altura máxima entre cada unidad interior, o entre ésta y el multi-kit H2 ≤ 15 m
Longitud máxima de las Entre el kit “a” y la unidad interior más
L ≤ 40 m
tuberías entre el multi-kit y alejada
la unidad interior Entre cada multi-kit y cada unidad interior L0. L1. L2. L3. L4. L5 ≤ 15 m
Ejemplo: Unidad exterior: RAS-8FSNM
Selección del distribuidor. Uso de MH-108AN (8 bifurcaciones)
1) Carga de refrigerante adicional. Ejemplo:
La cantidad se calcula con la siguiente fórmula: Marca Lt-L5 L0 L1 L2 L3 L4 L5

W (kg) = W11+W12+W13+W14+W15+W16+W2 Diam. Ø9,52 Ø6,35 Ø6,35 Ø6,35 Ø6,35 Ø6,35 Ø6,35
1.1) Tubería
de líquido Largo 61 5 3 5 3 3 5

1.1) W11 (kg): (Longitud total (m) de la tubería de líquido W15 = 61 x 0,07 = 4,27 kg
de Ø22,2) x 0,39
W16 = (5+3+5+3+5+3) x 0,03 = 0,72 kg
W12 (kg): (longitud total (m) de la tubería de líquido de
Ejemplo:
Ø19,05) x 0,28
Nº de la unidad interior 0 1 2 3 4 5
W13 (kg): (longitud total (m) de la tubería de líquido de
Ø15,88) x 0,19 Potencia
1.2) Unidad 1,5 1,5 1 1 1,5 1,5
correspondiente (CV)
W14 (kg): (longitud total (m) de la tubería de líquido de interior
Cantidad de refrigerante Unidades interiores que no
Ø12,7) x 0,12 adicional necesitan carga adicional
W15 (kg): (longitud total (m) de la tubería de líquido de
W2 = 0 kg
Ø9,52) x 0,07

W16 (kg): (longitud total (m) de la tubería de líquido de


Ø6,35) x 0,030 W (kg) = W11+W12+W13+W14+W15+W16+W2
Total
1.2) W2 (kg): C
 antidad total de refrigerante adicional de = 0 + 0 + 0 + 0 + 4.27 + 0.72 + 0 = 4,99 kg
cada unidad interior (kg)
2) Comprobación de la cantidad máxima de carga de refrigerante
4,99 kg < 13,5 kg (CORRECTO)
adicional: (W < WMAX)
3) Carga de refrigerante total: WTOT (kg)= W0 + W
WTOT = 5,0 + 4,99 = 9,99 kg
W0 : carga de refrigerante de fábrica de la unidad exterior (kg)

? N O TA
• Consulte el capítulo “9.3 Cantidad de carga de refrigerante” para conocer toda la información necesaria sobre el cálculo de la carga
de refrigerante adicional.
• Consulte el apartado “9.3.1 Cálculo de la carga de refrigerante adicional (R410A)” en este capítulo para conocer la carga de
refrigerante adicional máxima (WMAX) y la carga con la que la unidad exterior se suministra de fábrica (W0).

92 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Cantidad de carga de refrigerante

ELEMENTO SISTEMA UNI-PIPING DE MULTI-KITS

Unidad exterior
Ejemplo de sistemas
2: Instalación sencilla con multi-kits (Uni-piping) H1≤40m (la unidad exterior está más alta)
H1≤30m (la unidad exterior está más baja)

La imagen es un ejemplo de 6 unidades interiores combinadas con una


unidad exterior.
Las tuberías de refrigerante se muestran como una sola línea en los
diagramas.
No obstante, las tuberías para la línea de gas y de líquido son necesarias
Lt real ≤ 100 m
en la instalación. Lt equivalente ≤ 120 m

Longitud total de las tuberías ≤ 250 m


Longitud máxima de las Longitud real Lt ≤ 100 m
tuberías Longitud equivalente Lt ≤ 120 m
Si la unidad exterior está más alta que la
H1 ≤ 40 m
Altura máxima entre la interior
unidad exterior y la interior Si la unidad exterior está más baja que la
H1 ≤ 30 m
interior
Altura máxima entre cada unidad interior, o entre ésta y el multi-kit H2 ≤ 15 m
Longitud máxima de las Entre el kit “a” y la unidad interior más alejada L ≤ 40 m
tuberías entre el multi-kit
y la unidad interior Entre cada multi-kit y cada unidad interior L0. L1. L2. L3. L4. L5 ≤ 15 m
Ejemplo: Unidad exterior: RAS-8FSNM

Marca a,b,c,d,e
Elección de cada multi-kit
Multi-kit E-102SN4
1) Carga de refrigerante adicional. Ejemplo:
La cantidad se calcula con la siguiente fórmula: Marca Lt-L5 L0 L1 L2 L3 L4 L5

1.1) Tubería Diam. Ø9,52 Ø6,35 Ø6,35 Ø6,35 Ø6,35 Ø6,35 Ø6,35
W (kg) = W11+W12+W13+W14+W15+W16+W2
de Largo 60 5 3 5 3 5 3
líquido
W15 = 60 x 0,07 = 4,2 kg
1.1) W11 (kg): (Longitud total (m) de la tubería de líquido de
Ø22,2) x 0,39 W16 = (5+3+5+3+5+3) x 0,03 = 0,72 kg

W12 (kg): (longitud total (m) de la tubería de líquido de Ejemplo:


Ø19,05) x 0,28 Nº de la unidad interior 0 1 2 3 4 5
W13 (kg): (longitud total (m) de la tubería de líquido de Potencia
1.2) Unidad 1 1 1,5 1,5 1,5 1,5
Ø15,88) x 0,19 correspondiente (CV)

9
interior
W14 (kg): (longitud total (m) de la tubería de líquido de Cantidad de refrigerante Unidades interiores que no
Ø12,7) x 0,12 adicional necesitan carga adicional

W15 (kg): (longitud total (m) de la tubería de líquido de W2 = 0 kg


Ø9,52) x 0,07

W16 (kg): (longitud total (m) de la tubería de líquido de


W (kg) = W11+W12+W13+W14+W15+W16+W2
Ø6,35) x 0,030 Total
= 0 + 0 + 0 + 0 + 4.2 + 0.72 + 0 = 4,92 kg
1.2) W2 (kg): Cantidad total de refrigerante adicional de cada
unidad interior (kg)
2) Comprobación de la cantidad máxima de carga de refrigerante
4,92 kg < 13,5 kg (CORRECTO)
adicional: (W < WMAX)

3) Carga de refrigerante total: WTOT (kg)= W0 + W


WTOT = 5,0 + 4,92 = 9,92 kg
W0 : carga de refrigerante de fábrica de la unidad exterior (kg)

? N O TA
• Consulte el capítulo “9.3 Cantidad de carga de refrigerante” para conocer toda la información necesaria sobre el cálculo de la carga
de refrigerante adicional.
• Consulte el apartado “9.3.1 Cálculo de la carga de refrigerante adicional (R410A)” en este capítulo para conocer la carga de
refrigerante adicional máxima (WMAX) y la carga con la que la unidad exterior se suministra de fábrica (W0).

93 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Cantidad de carga de refrigerante

ELEMENTO SISTEMA MULTI-KITS DE TAMAÑO REDUCIDO


Unidad exterior
Ejemplo de sistemas
3: Instalación sencilla con multi-kits (Tamaño reducido) H1≤40m (la unidad exterior está más alta)
H1≤30m (la unidad exterior está más baja)

La imagen es un ejemplo de 6 unidades interiores combinadas con


una unidad exterior.
Las tuberías de refrigerante se muestran como una sola línea en los
diagramas.
No obstante, las tuberías para la línea de gas y de líquido son
necesarias en la instalación.
Lt real ≤ 100 m
Lt equivalente ≤ 120 m

Longitud total de las tuberías ≤ 250 m


Longitud máxima de las Longitud real Lt ≤ 100 m
tuberías Longitud equivalente Lt ≤ 120 m
Si la unidad exterior está más alta que la
Altura máxima entre H1 ≤ 40 m
interior
la unidad exterior y la
interior Si la unidad exterior está más baja que la
H1 ≤ 30 m
interior
Altura máxima entre cada unidad interior, o entre ésta y el multi-kit H2 ≤ 15 m
Longitud máxima de las Entre el kit “a” y la unidad interior más L ≤ 40 m
tuberías entre el multi-kit alejada
y la unidad interior Entre cada multi-kit y cada unidad interior L0. L1. L2. L3. L4. L5 ≤ 15 m
Ejemplo: Unidad exterior: RAS-10FSNM

Marca a b,c,d,e
Elección de cada multi-kit
Multi-kit E-162SN4 E-102SN4
1) Carga de refrigerante adicional. Ejemplo:
La cantidad se calcula con la siguiente fórmula: Marca LM1 LM2 L0 L1 L2 L3 L4 L5
Diam. Ø12,7 Ø9,52 Ø6,35 Ø6,35 Ø6,35 Ø6,35 Ø6,35 Ø6,35
W (kg) = W11+W12+W13+W14+W15+W16+W2
1.1) Tubería Largo 45 20 5 3 5 3 5 3
de
líquido W14 = 45 x 0,12 = 5,4 kg
1.1) W11 (kg): (Longitud total (m) de la tubería de líquido
de Ø22,2) x 0,39 W15 = 20 x 0,07 = 1,4 kg

W12 (kg): (longitud total (m) de la tubería de líquido de W16 = (5+3+5+3+5+3) x 0,03 = 0,72 kg
Ø19,05) x 0,28 Ejemplo:
W13 (kg): (longitud total (m) de la tubería de líquido de Nº de la unidad interior 0 1 2 3 4 5
Ø15,88) x 0,19 Potencia
1.2) Unidad 2 2 1 1 2 2
W14 (kg): (longitud total (m) de la tubería de líquido de correspondiente (CV)
interior
Ø12,7) x 0,12 Cantidad de refrigerante Unidades interiores que no
adicional necesitan carga adicional
W15 (kg): (longitud total (m) de la tubería de líquido de
Ø9,52) x 0,07 W2 = 0 kg
W16 (kg): (longitud total (m) de la tubería de líquido de
Ø6,35) x 0,030 W (kg) = W11+W12+W13+W14+W15+W16+W2
Total
1.2) W2 (kg): Cantidad total de refrigerante adicional de = 0 + 0 + 0 + 5,4+ 1.4 + 0,72 + 0 = 7,52 kg
cada unidad interior (kg)
2) Comprobación de la cantidad máxima de carga de refrigerante
7,52 kg < 13,5 kg (CORRECTO)
adicional: (W < WMAX)

3) Carga de refrigerante total: WTOT (kg)= W0 + W


WTOT = 5,5 + 7,52 = 13,02 kg
W0 : carga de refrigerante de fábrica de la unidad exterior (kg)

? N O TA
• Consulte el capítulo “9.3 Cantidad de carga de refrigerante” para conocer toda la información necesaria sobre el cálculo de la carga
de refrigerante adicional.
• Consulte el apartado “9.3.1 Cálculo de la carga de refrigerante adicional (R410A)” en este capítulo para conocer la carga de
refrigerante adicional máxima (WMAX) y la carga con la que la unidad exterior se suministra de fábrica (W0).

94 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Cantidad de carga de refrigerante

ELEMENTO SISTEMA MULTI-KITS DE TAMAÑO REDUCIDO


Ejemplo de sistemas Unidad exterior

4: Instalación simple en la que la longitud desde la unidad exterior H1≤40m (la unidad exterior está más alta)
(RAS-8FSNM) hasta la primera bifurcación es superior a 70 m H1≤30m (la unidad exterior está más baja)
(tamaño reducido)

La imagen es un ejemplo de 6 unidades interiores combinadas con una


unidad exterior.
Las tuberías de refrigerante se muestran como una sola línea en los
diagramas.
No obstante, las tuberías para la línea de gas y de líquido son Lt real ≤ 100 m
necesarias en la instalación. Lt equivalente ≤ 120 m

Longitud total de las tuberías ≤ 250 m


Longitud máxima de las Longitud real Lt ≤ 100 m
tuberías Longitud equivalente Lt ≤ 120 m
Si la unidad exterior está más alta que la
H1 ≤ 40 m
Altura máxima entre la interior
unidad exterior y la interior Si la unidad exterior está más baja que la
H1 ≤ 30 m
interior
Altura máxima entre cada unidad interior, o entre ésta y el multi-kit H2 ≤ 15 m
Longitud máxima de las Entre el kit “a” y la unidad interior más
L ≤ 40 m
tuberías entre el multi-kit y alejada
la unidad interior Entre cada multi-kit y cada unidad interior L0. L1. L2. L3. L4. L5 ≤ 15 m
Ejemplo: Unidad exterior: RAS-8FSNM

Marca a b,c,d,e
Elección de cada multi-kit
Multi-kit E-162SN4 E-102SN4

1) Carga de refrigerante adicional. Ejemplo:


La cantidad se calcula con la siguiente fórmula: Marca LM1 LM2 L0 L1 L2 L3 L4 L5
Ø12,7
W (kg) = W11+W12+W13+W14+W15+W16+W2 Diam. Ø9,52 Ø6,35 Ø9,52 Ø9,52 Ø6,35 Ø9,52 Ø9,52
(*1)
1.1) Tubería
de Largo 76 15 5 3 5 3 5 3
1.1) W11 (kg): (Longitud total (m) de la tubería de líquido de líquido
W14 = 76 x 0,12 = 9,12 kg
Ø22,2) x 0,39
W15 = 15 x 0,07 = 1,05 kg
W12 (kg): (longitud total (m) de la tubería de líquido de
Ø19,05) x 0,28 W16 = (5+3+5+3+5+3) x 0,03 = 0,72 kg
W13 (kg): (longitud total (m) de la tubería de líquido de Ejemplo:

9
Ø15,88) x 0,19
Nº de la unidad interior 0 1 2 3 4 5
W14 (kg): (longitud total (m) de la tubería de líquido de Potencia
Ø12,7) x 0,12 1.2) Unidad 1,5 1,5 1 1 1,5 1,5
correspondiente (CV)
interior
W15 (kg): (longitud total (m) de la tubería de líquido de Cantidad de refrigerante Unidades interiores que no
Ø9,52) x 0,07 adicional necesitan carga adicional
W16 (kg): (longitud total (m) de la tubería de líquido de W2 = 0 kg
Ø6,35) x 0,030
W (kg) = W11+W12+W13+W14+W15+W16+W2
1.2) W2 (kg): Cantidad total de refrigerante adicional de Total
cada unidad interior (kg) = 0 + 0 +0 + 9,12+ 1,05 + 0,72 + 0 = 10,89 kg
2) Comprobación de la cantidad máxima de carga de refrigerante
10,89 kg < 13,5 kg (CORRECTO)
adicional: (W < WMAX)
3) Carga de refrigerante total: WTOT (kg)= W0 + W
W0 : carga de refrigerante de fábrica de la unidad exterior (kg) WTOT = 5,0 + 10,89 = 15,89 kg

? N O TA
• Consulte el capítulo “9.3 Cantidad de carga de refrigerante” para conocer toda la información necesaria sobre el cálculo de la carga
de refrigerante adicional.
• Consulte el apartado “9.3.1 Cálculo de la carga de refrigerante adicional (R410A)” en este capítulo para conocer la carga de
refrigerante adicional máxima (WMAX) y la carga con la que la unidad exterior se suministra de fábrica (W0).
• (*1): Si la longitud equivalente de la tubería de refrigerante es superior a 70 m en las unidades RAS-8FSNM (76 m en este ejemplo), el
tamaño de la tubería de la línea desde la unidad exterior hasta la primera bifurcación se debe incrementar con el reductor (suministrado
por el instalador) de Ø9,52 a Ø12,7. En este caso, utilice el multi kit E-162SN4.

95 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Cantidad de carga de refrigerante

DISTRIBUIDOR REDUCIDO Y SISTEMA DE MULTI-KITS CON


ELEMENTO
REDUCCIÓN

Ejemplo de sistemas
5: Método de distribución de línea en el que es necesaria
una carga adicional de refrigerante para la unidad interior.
(Tamaño reducido)

La imagen es un ejemplo de 6 unidades interiores combinadas con


una unidad exterior.
Las tuberías de refrigerante se muestran como una sola línea en
los diagramas.
H1≤40m (la unidad
exterior está más alta)
No obstante, las tuberías para la línea de gas y de líquido son
H1≤30m (la unidad
necesarias en la instalación. exterior está más baja) Lt real ≤ 100 m
Lt equivalente ≤ 120 m

Longitud total de las tuberías ≤ 250 m


Longitud máxima de Longitud real Lt ≤ 100 m
las tuberías Longitud equivalente Lt ≤ 120 m
Si la unidad exterior está más alta que la
Altura máxima entre H1 ≤ 40 m
interior
la unidad exterior y la
interior Si la unidad exterior está más baja que la
H1 ≤ 30 m
interior
Altura máxima entre cada unidad interior o entre el multi-kit y la
H2 ≤ 15 m
unidad interior
Longitud máxima de Entre el kit “a” y la unidad interior más
L ≤ 40 m
las tuberías entre el alejada
multi-kit y la unidad
interior Entre cada multi-kit y cada unidad interior L0. L1. L2. L3. L4. L5 ≤ 15 m
Ejemplo: Unidad exterior: RAS-12FSNM
Marca a b, c d
Elección de cada multi-kit
Multi-kit E-162SN4 E-102SN4 MH-84HAN

1) Carga de refrigerante adicional. Ejemplo:


La cantidad se calcula con la siguiente fórmula: Marca LM1 LM2 LM3 L0 L1 L2 L3 L4 L5

W (kg) = W11+W12+W13+W14+W15+W16+W2 1.1) Tubería Diam. Ø12,7 Ø9,52 Ø9,52 Ø9,52 Ø6,35 Ø6,35 Ø6,35 Ø6,35 Ø6,35
de Largo 50 15 10 8 5 3 5 3 3
1.1) W11 (kg): (Longitud total (m) de la tubería de líquido
líquido de Ø22,2) x 0,39 W14 = 50 x 0,12 = 6 kg;
W15 = (15+10+8) x 0,07 = 2,31 kg
W12 (kg): ( longitud total (m) de la tubería de líquido de
W16 = (5+3+5+3+3) x 0,03 = 0,57 kg
Ø19,05) x 0,28
Ejemplo:
W13 (kg): ( longitud total (m) de la tubería de líquido de
Ø15,88) x 0,19 Nº de la unidad interior 0 1 2 3 4 5
Potencia correspondiente
W14 (kg): ( longitud total (m) de la tubería de líquido de 1.2) Unidad 8 (*1) 0,8 0,8 0,8 0,8 0,8
(CV)
Ø12,7) x 0,12 interior Cantidad de refrigerante
Unidad interior número 0: 1 kg
W15 (kg): ( longitud total (m) de la tubería de líquido de adicional
Ø9,52) x 0,07
W2 = 1 kg
W16 (kg): ( longitud total (m) de la tubería de líquido de
Ø6,35) x 0,030 W (kg) = W11+W12+W13+W14+W15+W16+W2
Total
1.2) W2 (kg): C
 antidad total de refrigerante adicional = 0 + 0 + 0 + 6 + 2.31 + 0.57 + 1 = 9,88 kg
de cada unidad interior (kg)
2) Comprobación de la cantidad máxima de carga de refrigerante
adicional: (W < WMAX) 9,88 kg < 13,5 kg (CORRECTO)

3) Carga de refrigerante total: WTOT (kg)= W0 + W


W0 : carga de refrigerante de fábrica de la unidad exterior (kg) WTOT = 6,5 + 9,88 = 16,38 kg

? N O TA
• Consulte el capítulo “9.3 Cantidad de carga de refrigerante” para conocer toda la información necesaria sobre el cálculo de la carga
de refrigerante adicional.
• Consulte el apartado “9.3.1 Cálculo de la carga de refrigerante adicional (R410A)” en este capítulo para conocer la carga de
refrigerante adicional máxima (WMAX) y la carga con la que la unidad exterior se suministra de fábrica (W0).
• (*1): Cuando la unidad exterior está combinada con unidades interiores RPI-(8.0/10.0)FSN3E, es necesaria una carga de refrigerante
adicional (W2) = 1 kg/unidad.

96 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Cantidad de carga de refrigerante

ELEMENTO SISTEMA MULTI-KITS DE TAMAÑO REDUCIDO


Ejemplo de sistemas Unidad exterior

6: Instalación simple en la que la carga de refrigerante adicional es H1≤40m (la unidad exterior está más alta)
superior a la carga máxima de refrigerante adicional permitida H1≤30m (la unidad exterior está más baja)
para la unidad. (Tamaño reducido)

La imagen es un ejemplo de 10 unidades interiores combinadas con


una unidad exterior.
Las tuberías de refrigerante se muestran como una sola línea en los
diagramas.
No obstante, las tuberías para la línea de gas y de líquido son
Lt real ≤ 100 m
necesarias en la instalación. Lt equivalente ≤ 120 m

Longitud total de las tuberías ≤ 250 m


Longitud máxima de las Longitud real Lt ≤ 100 m
tuberías Longitud equivalente Lt ≤ 120 m
Si la unidad exterior está más alta que la
H1 ≤ 40 m
Altura máxima entre la interior
unidad exterior y la interior Si la unidad exterior está más baja que la
H1 ≤ 30 m
interior
Altura máxima entre cada unidad interior o entre el multi-kit y la unidad
H2 ≤ 15 m
interior
Longitud máxima de las Entre el kit “a” y la unidad interior más
L ≤ 40 m
tuberías entre el multi-kit alejada
y la unidad interior Entre cada multi-kit y cada unidad interior L0. L1. L2. L3. L4. L5 ≤ 15 m
Ejemplo: Unidad exterior: RAS-12FSNM
Marca a b, c, d, e
Elección de cada multi-kit
Multi-kit E-162SN4 E-102SN4
1) Carga de refrigerante adicional. Ejemplo:
La cantidad se calcula con la siguiente fórmula: Marca LM1 LM2 L0 L1 L2 L3 L4 L5

W (kg) = W11+W12+W13+W14+W15+W16+W2 1.1) Tubería Diam. Ø12,7 Ø9,52 Ø6,35 Ø6,35 Ø9,52 Ø9,52 Ø9,52 Ø9,52
de Largo 72 15 11 11 13 13 10 12
líquido
1.1) W11 (kg): (Longitud total (m) de la tubería de líquido de W13 = 72 x 0,12 = 8,64 kg;
Ø22,2) x 0,39 W14 = (15+13+13+10+12) x 0,07 = 4,41 kg
W15 = (10+12) x 0,03 = 0,66 kg
W12 (kg): (longitud total (m) de la tubería de líquido de
Ø19,05) x 0,28 Ejemplo:

9
Nº de la unidad interior 0 1 2 3 4 5
W13 (kg): (longitud total (m) de la tubería de líquido de
Ø15,88) x 0,19 Potencia
1.2) Unidad 1 1 2,5 2,5 2,5 2,5
correspondiente (CV)
W14 (kg): (longitud total (m) de la tubería de líquido de interior
Ø12,7) x 0,12 Cantidad de refrigerante Unidades interiores que no
adicional necesitan carga adicional
W15 (kg): (longitud total (m) de la tubería de líquido de
Ø9,52) x 0,07 W2 = 0 kg

W16 (kg): (longitud total (m) de la tubería de líquido de


Ø6,35) x 0,030 W (kg) = W11+W12+W13+W14+W15+W16+W2
Total
1.2) W2 (kg): Cantidad total de refrigerante adicional de = 0 + 0 + 0 + 8,64 + 4.41 + 0.66 + 0 = 13,71 kg
cada unidad interior (kg)
2) Comprobación de la cantidad máxima de carga de refrigerante
adicional: (W < WMAX) 13,71 kg > 13,5 kg (INCORRECTO) *(1)

3) Carga de refrigerante total: WTOT (kg)= W0 + W


WTOT = 6,5 + 13,71 = 20,21 kg
W0 : carga de refrigerante de fábrica de la unidad exterior (kg)

? N O TA
• Consulte el capítulo “9.3 Cantidad de carga de refrigerante” para conocer toda la información necesaria sobre el cálculo de la carga
de refrigerante adicional.
• Consulte el apartado “9.3.1 Cálculo de la carga de refrigerante adicional (R410A)” en este capítulo para conocer la carga de
refrigerante adicional máxima (WMAX) y la carga con la que la unidad exterior se suministra de fábrica (W0).
• (*1): Si la carga de refrigerante adicional es superior a la carga adicional máxima permitida, debe ajustar la longitud de las tuberías
de la instalación.

97 TCES0059 rev.2 - 06/2016


9 Instalación de las tuberías y carga de refrigerante

Precaución con las fugas de refrigerante

9.4 Precaución con las fugas de refrigerante


9.4.1  Máxima concentración permisible de gas HCFC/HFC

El refrigerante R410A cargado en el sistema Set Free FSNM, es un gas incombustible y no tóxico. Sin embargo, si se
produce una fuga y el gas se extiende por la habitación, puede provocar asfixia.
La concentración máxima permisible de gas HCFC/HFC, R410A en el aire es de 0,44 kg/m³, de acuerdo con EN378-1.
Por consiguiente, en caso de fuga, debe adoptarse alguna medida eficaz para reducir la concentración de R410A en el
aire por debajo de 0,44 Kg/m³.

9.4.2  Cálculo de la concentración de refrigerante

1 Calcule la cantidad total de refrigerante R (kg) cargado en el sistema conectando todas las unidades interiores en las
habitaciones que desee acondicionar.
2 Calcule el volumen V (m3) de cada estancia.
3 Calcule la concentración de refrigerante C (kg/m3) de la estancia según la siguiente ecuación:

R R: cantidad total de refrigerante cargado (kg)


≤C V: volumen de la habitación (m³)
V
C: concentración de refrigerante 0,44 kg/m³ para R410A

9.4.3  Contramedidas en caso de fugas de refrigerante

El local debe tener las siguientes características en caso de incendio:


1 Debe disponer de una abertura sin contraventana que permita la circulación de aire fresco.
2 Debe disponer de una abertura sin puerta de un tamaño del 0,15% o superior de la superficie de la estancia.
3 Disponer de un aireador, conectado a un detector de fugas de gas, con una capacidad de aireación de 0,4 m3/minuto
o superior por tonelada de refrigeración japonesa (= volumen desplazado del compresor 5,7 m3/h) del sistema de
aire acondicionado que utiliza refrigerante R410A.

Modelo Toneladas
RAS-(8-12)FSNM 4,11

4 Preste especial atención al lugar, por ejemplo, un sótano, donde puede permanecer el refrigerante, ya que éste pesa
más que el aire.

98 TCES0059 rev.2 - 06/2016


10 Cableado eléctrico

1 0 . C a b l e a d o e l é c t r i c o

Índice

10.1 Comprobaciones generales................................................................................................................. 100

10.2 Ajustes y funciones de los conmutadores DIP..................................................................................... 100


10.2.1  DSW1: Prueba de funcionamiento y ajustes de servicio............................................................................ 101

10.3 Cableado común.................................................................................................................................. 105


10.3.1  Cableado eléctrico entre la unidad interior y la exterior............................................................................. 105

10.4 Tamaño del cableado........................................................................................................................... 106

10

99 TCES0059 rev.2 - 06/2016


10 Cableado eléctrico

Comprobaciones generales

10.1 Comprobaciones generales

! PRECAUCIÓN
• Apague el interruptor de alimentación principal de la unidad interior y la exterior antes de llevar a cabo el cableado eléctrico o las
comprobaciones habituales.
• Asegúrese de que el ventilador de la unidad interior y exterior se han parado antes de realizar tareas de cableado eléctrico o una
comprobación periódica.
• Proteja los cables, el tubo de desagüe, las piezas eléctricas, etc. de las ratas u otros animales pequeños, podrían roerlas y provocar
un incendio.
• Asegúrese de que los cables no están en contacto con las tuberías de refrigerante, los bordes de las placas y las piezas eléctricas en
el interior de la unidad. De lo contrario, los cables resultarán dañados, lo cual podría provocar un incendio.
• Sujete firmemente los cables con la abrazadera en el interior de la unidad.

? N O TA
Fije los casquillos de caucho con adhesivo cuando los conductos de la unidad exterior no se utilicen.
1 Asegúrese de que los componentes eléctricos suministrados por el instalador (interruptores de alimentación principal, disyuntores,
cables, conectores de tuberías y terminales de cables) han sido correctamente seleccionados según los datos eléctricos indicados
en este catálogo técnico. Asegúrese de que los componentes cumplen con el National Electrical Code (NEC).
2 Compruebe que la tensión de alimentación está dentro del ± 10% de la tensión nominal.
3 Compruebe la capacidad del cableado eléctrico. Si la capacidad de la fuente de alimentación es demasiado baja, el sistema no
podrá ponerse en marcha debido a la caída de tensión.
4 Compruebe que el cable de tierra está conectado.
5 Interruptor de alimentación principal. Instale un interruptor principal multipolar con un espacio mínimo de 3,5 mm entre cada fase.

10.2 Ajustes y funciones de los conmutadores DIP


Cantidad y posición de los conmutadores DIP La PCB de la unidad exterior funciona con 6 tipos de conmutadores DIP y
3 tipos de interruptores de pulsación.
PCB1

? N O TA
• La marca “■“ indica la posición de los conmutadores DIP. Las figuras muestran el ajuste de fábrica o tras la selección.
• Al utilizar el conmutador DSW4, la unidad se inicia o se para 10 o 20 segundos después de que se utilice el conmutador.
• Asigne un número a esta unidad exterior para distinguirla de las demás en las tareas de servicio y mantenimiento. Anote este número
en el espacio correspondiente.

! PRECAUCIÓN
Antes de ajustar los conmutadores DIP, apague la fuente de alimentación, de lo contrario los ajustes no serán válidos.

100 TCES0059 rev.2 - 06/2016


10 Cableado eléctrico

Ajustes y funciones de los conmutadores DIP

10.2.1  DSW1: Prueba de funcionamiento y ajustes de servicio

El ajuste es necesario para la prueba de funcionamiento y el funcionamiento del compresor.

 DSW1

Ajuste de fábrica

Prueba de funcionamiento con


enfriamiento

Prueba de funcionamiento con


calefacción

Parada forzada del compresor

 RSW1: Ajuste del nº de ciclo de refrigerante


Es necesario realizar el ajuste.
Realice el ajuste insertando un destornillador en la hendidura.

Posición de ajuste

Ajuste de fábrica

Último dígito

 DSW2: Ajuste de funciones opcionales


El ajuste es necesario cuando se requieren funciones opcionales.

Ajuste de fábrica

Ajuste el pin designado en la posición ON para los elementos de ajuste de la tabla.

Elemento de ajuste Número de pin


- 1
-
-
2
3 10
- 4
Ajuste de funciones 5
Señales de selección de entrada/salida
6
externa

101 TCES0059 rev.2 - 06/2016


10 Cableado eléctrico

Ajustes y funciones de los conmutadores DIP

 DSW3: Ajuste de la capacidad


No es necesario realizar ningún ajuste.

Modelo Posición de ajuste

RAS-8FSNM

RAS-10FSNM

RAS-12FSNM

 DSW4: Ajuste del nº de ciclo de refrigerante


Es necesario realizar el ajuste.

Ajuste de fábrica
(Ajuste para el dígito de las decenas)

 DSW5: Resistencia del terminal final


No es necesario realizar ningún ajuste.

Ajuste de fábrica

 DSW6: Diferencia de altura


Es necesario realizar el ajuste.

Ajuste de fábrica

La unidad interior está situada por


encima de la unidad exterior
(de 20 a 30 m)

Ajuste preciso de la capacidad de


calefacción

PCB2

102 TCES0059 rev.2 - 06/2016


10 Cableado eléctrico

Ajustes y funciones de los conmutadores DIP

 DSW1: (en la PCB2)


No es necesario realizar ningún ajuste.

Cuando se ajusta el pin nº 1 en posición ON, se


cancela la detección de corriente eléctrica. El pin nº 1
debe establecerse de nuevo en OFF después de las
tareas eléctricas.

 JP1~6: Cable de puente


380/415V 380/415V
Nº Nº
50 Hz 50 Hz
JP1 JP4
JP2 JP5
JP3 JP6

El ajuste del cable de puente es diferente según la tensión de la fuente de alimentación. Asegúrese de comprobar el
ajuste del cable de puente antes de intercambiar el PCB1.
Tenga cuidado de no dañar los demás componentes eléctricos al cortar los cables de puente.

! PRECAUCIÓN
Si la fuente de alimentación está en fase abierta, en la pantalla de 7 segmentos de la PCB exterior aparecerá “05”, y el compresor no
funcionará. En ese caso, compruebe la conexión del terminal de la fuente de alimentación.

 Ajuste de la transmisión
Se debe ajustar el número de ciclo de refrigerante y la resistencia del terminal final para este sistema H-LINK o H-LINK II.

 Ajuste del número de ciclo de refrigerante


En el mismo ciclo de refrigerante, establezca el mismo número de ciclo para la unidad exterior y las interiores, tal como
se muestra a continuación.
Para el ajuste del número de ciclo de refrigerante de la unidad interior, ajuste el RSW2 y el DSW5 en la PCB de la
unidad interior.

Ajuste del conmutador Ej.: en caso de ajustar el número del ciclo de


Posición de ajuste refrigerante en 25

Realice el ajuste
Dígito de la insertando un
decenas Dígito de las destornillador en
unidades la hendidura Ajuste el pin 2 en Ajuste el dial número 5

10
posición ON
Unidad exterior DSW4 RSW1
El ajuste de fábrica del DSW y del RSW es 0.
Unidad interior
DSW5 RSW2 El número máximo para el ciclo de refrigerante es 63.
(H-LINK II)

103 TCES0059 rev.2 - 06/2016


10 Cableado eléctrico

Ajustes y funciones de los conmutadores DIP

 Ajuste de la resistencia terminal final


El pin 1 del DSW5 se suministra de fábrica en posición ON. En caso de que haya dos o más unidades exteriores en el
mismo sistema H-LINK o H-LINK II, ajuste el pin nº 1 del DSW5 de la segunda unidad en posición “OFF”. Si sólo se está
utilizando una unidad exterior, no es necesario realizar ningún ajuste.

Ajuste de la resistencia terminal final


DSW5
Suministrado de fábrica Cancelación

SetAjuste
Dip SW not to overlap
el conmutador DIP de the
modosetting
que no of
other
solapeoutdoor
el ajusteunits.
de otras unidades exteriores

These Series
Ciclo de Refrigerant
refrigerante de estasCycle
series
Multi-Type
Unidad exterior
Tipo UTOPIA
Unidades
Outdoorexteriores
Unit Outdoor
de varios Unit
tipos UTOPIA Type
Outdoor
Unidad Unit
exterior

Línea de transmisión
Transmission (2 cables no polares)
Line (Non-Polar 2 Wires)
H-LINKoro H-LINK
H-LINK H-LINK II II
Ajuste el conmutador DIP para
Set Dip SW to the
el mismo número de ciclos de
same Refrigerant
refrigerante
Cycle No.

Unidades
Indoor
interiores
Units

Remote
Mando a distancia
Control Switch Central Controller
Controlador Central

Maximum Units per Refrigerant System Central Station


Estación (PSC-A64S)
central (PSC-A64S)
(In Case of H-LINK II) Centralized ON/OFF Controller (PSC-A16RS)
Controlador centralizado de encendido/apagado (PSC-A16RS)
Outdoor Unit 64 Units NOTE:
Unidades máximas por sistema de refrigerante
If H-LINK II adaptive and non-adaptive indoor and outdoor unit are connected together,
Indoor Unit 160 Units
the maximum indoor units to be connected are 128 units.
(En caso del H-LINK II)

Unidad exterior 64 unidades

Unidad interior 160 unidades

? N O TA
Si las unidades interiores y exteriores adaptables y no adaptables H-LINK II están conectadas entre sí, se pueden conectar hasta 128
unidades.

104 TCES0059 rev.2 - 06/2016


10 Cableado eléctrico

Cableado común

10.3 Cableado común


10.3.1  Cableado eléctrico entre la unidad interior y la exterior
• Conecte los cables eléctricos entre la unidad interior y la exterior, tal y como se muestra a continuación.
• Asegúrese de seguir los códigos y reglamentos locales.
• La tubería de refrigerante y el cableado de control se conectan a las unidades del mismo ciclo de refrigerante.
• Utilice cables de par trenzado (de más de 0,75 mm2) para el cableado de servicio entre la unidad exterior y la
interior, y para el cableado de servicio entre unidades interiores.
• Utilice un cable de 2 núcleos para la línea de servicio (no utilice un cable con más de 3 núcleos).
• Use cables blindados para el cableado intermedio para proteger las unidades de interferencias acústicas en
longitudes inferiores a 300 m. El tamaño debe respetar los reglamentos locales.
• Realice un orificio cerca de la abertura para la conexión del cable de alimentación cuando se conecten varias
unidades exteriores desde una única línea de alimentación.
• Los tamaños recomendados para los disyuntores se muestran en la tabla de datos eléctricos y tamaños
recomendados de cableado y disyuntores / 1 U.E.
• Si no usa un conducto suministrado por el instalador, fije los casquillos de caucho con adhesivo al panel.
• Todo el cableado y el equipamiento de la instalación deben respetar los reglamentos locales y los códigos
internacionales.

! PRECAUCIÓN
Preste atención a la conexión de la línea de servicio. Una conexión incorrecta podría causar un fallo en la PCB.
Máx. 1 unidad exterior / línea de fuente de alimentación
La fuente de alimentación de las unidades exteriores debe ser
individual. De lo contrario podría producirse un incendio

Unidad exterior Unidad exterior Unidad exterior


del sistema nº 0 del sistema nº 1 del sistema nº 3
TB1 TB2 TB1 TB2 TB1 TB2
L1 L2 L3 N 1 2 L1 L2 L3 N 1 2 L1 L2 L3 N 1 2

Línea de servicio (cable de par trenzado blindado)


ELB 5 VCC (transmisión no polar, sistema H-LINK II)
ELB Caja de distribución o Caja de distribución o
FUSE / CB caja de derivación caja de derivación

Interruptor principal
ELB

3N
380/415V 50Hz
L1 L2 N L1 L2 N
TB1 TB1
Unidad interior Cable del Unidad interior

10
Cable del
nº 0 mando a nº 1 mando a
1N TB2
distancia
TB2
distancia
220-240V 50Hz 1 2 A B
(par trenzado
1 2 A B
(par trenzado
230V 50Hz blindado) blindado)
Línea de servicio (cable de par trenzado blindado)
Mando a Mando a
5 V CC (transmisión sin polaridad, sistema H-LINK)
distancia distancia
PC-ARFPE PC-ARFPE
TB Cuadro de terminales
PCB : Tarjeta de circuitos impresos
: Cableado de la instalación
: Suministrado por el instalador
: Accesorio opcional
Unidades interiores del Unidades interiores del
sistema nº 0 sistema nº 1

105 TCES0059 rev.2 - 06/2016


10 Cableado eléctrico

Tamaño del cableado

10.4 Tamaño del cableado


 Cableado de conexión
Mínimo grosor del cableado que debe usarse en la instalación.
Unidades interiores

Tamaño del cable de Tamaño del cable de


Fuente de Corriente máxima alimentación transmisión
Modelo
alimentación (A)
EN60 335-1  EN60 335-1 
Todas las unidades
230V/ 5,0 0,75mm²
interiores (*) 0,75mm²
1 fase/50Hz
RPI-8/10 10,0 1,5mm²

(*) Excepto RPI-8/10

Unidades exteriores

Tamaño del cable de la fuente Tamaño del cable de


Fuente de de alimentación transmisión
Modelo Corriente máxima
alimentación
EN60 335-1 *1 Cable de par trenzado blindado
RAS-8FSNM 14 2,5mm 2

RAS-10FSNM 380/415V 50Hz 18 4,0mm2 0,75mm2


RAS-12FSNM 23 4,0mm2

* Consulte las notas para seleccionar el tamaño del cable de la fuente de alimentación.

? N O TA
• Siga los códigos y reglamentos locales al seleccionar los cables de la instalación.
• Los tamaños de los cable marcados con *1 se han seleccionado con la corriente máxima de la unidad según la norma europea
EN60 335-1. Utilice cables que no sean más ligeros que el cable flexible de caucho duro forrado (designación de código H05RN-F) o
el cable normal flexible de policloropreno forrado (designación de código H05RN-F).
• Los tamaños de cable marcados con *2 en la tabla de esta página se han seleccionado con la corriente máxima de la unidad de
acuerdo con el cable MLFC (cable de poliflex ignífugo) fabricado por Hitachi Cable Ltd., Japón.
• Utilice un cable blindado para el circuito de transmisión y conéctelo a tierra.
• En caso de que los cables de alimentación estén conectados en serie, añada a cada unidad la corriente máxima y seleccione los
cables especificados a continuación.

Selección según EN60 335-1


Corriente i (A) Tamaño del cable
I≤6 0,75mm²
6 < i ≤ 10 1,0mm²
10 < i ≤ 16 1,5mm²
16 < i ≤ 25 2,5mm²
25 < i ≤ 32 4,0mm²
32 < i ≤ 40 6,0mm²
40 < i ≤ 63 10,0mm²
63 < i 

106 TCES0059 rev.2 - 06/2016


10 Cableado eléctrico

Tamaño del cableado

 Interruptor principal de protección


Seleccione los interruptores principales de acuerdo con la tabla siguiente.

Unidades interiores

Fuente de Corriente de servicio máxima ELB


Modelo CB(A)
alimentación (A) nº de polos/A/mA
Todas las unidades
5,0 6
interiores (*) 1~230 V/50 Hz 2/40/30
RPI-(8.0/10.0)FSN3E 10,0 16

(*) Excepto RPI-8/10

Unidades exteriores

Fuente de Corriente de servicio máxima ELB


Modelo CB(A)
alimentación (A) nº de polos/A/mA
RAS-8FSNM 14,0 20 4/20/30
RAS-10FSNM 3N~ 380/415V, 50Hz 18,0 30 4/30/30

RAS-12FSNM 23,0 30 4/30/30

? N O TA
• ELB: Conmutador diferencial.
• CB: Conmutador magnetotérmico.

10

107 TCES0059 rev.2 - 06/2016


11 Funciones opcionales

11 . F u n c i o n e s o p c i o n a l e s

Índice

11.1 Funciones opcionales disponibles para unidades exteriores............................................................... 110

11

109 TCES0059 rev.2 - 06/2016


11 Funciones opcionales

Funciones opcionales disponibles para unidades exteriores

11.1 Funciones opcionales disponibles para unidades exteriores


Funciones opcionales
Función opcional Explicación

Bloqueo del modo de Esta función establece el modo de funcionamiento, calefacción o enfriamiento. Si se ajusta el modo
funcionamiento de calefacción (enfriamiento) en la unidad interior cuando está establecido el modo de enfriamiento
(calefacción/enfriamiento) (calefacción), dicha unidad tendrá el termostato desactivado (thermo-OFF).

Orden de parada Cuando se activa esta función, se detiene el compresor y las unidades interiores adquieren la
termostática. condición de termostato apagado.

Esta función pone en marcha todos los ventiladores de la unidad exterior a la máxima velocidad
Sensor de nieve
durante la parada del compresor si detecta que el sensor de nieve está cubierto.

Esta función genera una parada de emergencia; el compresor y los ventiladores de las unidades
Parada forzada
interiores no funcionan.
Conmutación de la Esta función cambia las condiciones del funcionamiento con descarche. Es especialmente útil en
condición de descarche zonas frías.
Esta función regula la corriente de funcionamiento exterior, 60%, 70%, 80%; si la corriente solicitada
Solicitar control de corriente está por encima de la corriente establecida, la capacidad de la unidad interior se reduce y, si es
necesario, se desactiva el termostato.
Control del ventilador
de la unidad interior Esta función activa los ventiladores de las unidades interiores de forma cíclica (2 minutos encendidos
durante el funcionamiento y 6 apagados) para reducir los aspectos desagradables del funcionamiento con el termostato interior
con calefacción con el desactivado.
termostato desactivado
Cancelación del límite de
Esta función permite el funcionamiento en modo de calefacción sin restricción superior de
temperatura ambiente
temperaturas ambiente.
exterior de calefacción
Cancelación del límite de
Esta función permite el funcionamiento en modo de enfriamiento sin restricción inferior de
temperatura ambiente
temperaturas ambiente.
exterior de calefacción
Funcionamiento en modo
Esta función disminuye el nivel de sonido de las unidades, así como la capacidad de enfriamiento.
nocturno (bajo nivel sonoro)

Cuando se activa esta función, la velocidad del ventilador de la unidad interior en modo de descarche
Ajuste del descarche lento
se cambia a lenta en lugar de detener el ventilador.

Cancelación del límite de


Esta función permite poner en marcha la unidad exterior sin esperar a que la temperatura del
temperatura de arranque
compresor supere los 40 ºC.
exterior

Ajuste de la longitud de las Esta función indica a la unidad que la distancia existente entre la unidad exterior y la interior más
tuberías alejada es superior a 100 m.

Esta función reduce la velocidad máxima del motor del ventilador, con lo que también disminuye el
Ajuste de bajo nivel sonoro
nivel de ruido.

Esta función regula la corriente de funcionamiento exterior; si la corriente solicitada está por encima de
Ajuste del consumo la corriente establecida, la capacidad de la unidad interior se reduce y, si es necesario, se desactiva el
eléctrico termostato. El control de la corriente de funcionamiento no es un valor fijo, sino que varía dentro de un
valor máximo.
Prioridad del modo de
capacidad de enfriamiento
Prioridad del modo de
capacidad de calefacción
La temperatura del aire de descarga de la UI es demasiado baja, la UE está cambiando el estado de
Corriente de aire frío (1/2)
funcionamiento con el fin de evitar esta baja temperatura del aire de descarga
Esta función proporciona información sobre el funcionamiento de las unidades, (funcionamiento,
Captura de señal alarma, compresor encendido, señales de descarche) de forma que se pueden activar los dispositivos
necesarios.
Esta función proporciona información sobre el funcionamiento de la unidad, de forma que se pueden
Captura de señales
activar los dispositivos necesarios.

110 TCES0059 rev.2 - 06/2016


12 Resolución de problemas

1 2 . R e s o l u c i ó n d e p r o b l e m a s

Índice

12.1 Indicación de alarma............................................................................................................................ 112

12.2 Códigos de alarma para la serie FSNM............................................................................................... 112

12

111 TCES0059 rev.2 - 06/2016


12 Resolución de problemas

Indicación de alarma

12.1 Indicación de alarma


Si el indicador de funcionamiento parpadea durante 2 segundos, significa que hay un fallo de transmisión entre la unidad
interior y el mando a distancia. Posibles causas:
• El cable del mando a distancia está roto.
• Fallo de contacto del cable del mando a distancia.
• IC o microordenador defectuoso.
• En cualquier caso, póngase en contacto con el proveedor del servicio.
Si el piloto RUN parpadea 5 veces (5 segundos), mostrando el número de unidad y el código de alarma, anote el código
de alarma (véase la tabla siguiente) y póngase en contacto con su proveedor de servicios.

PC-ARFPE

01-02
Alarm Code: 22
MODEL : b .02 ALM RST
I.U. : RCI-3.0FSN3
ADDR
O.U. : RAS-3HVRNM2
SEL. OP MODE OK ENT.

12.2 Códigos de alarma para la serie FSNM

Código Categoría Contenido de la anomalía Causa principal


Unidad Activación del interruptor de flotador, nivel alto en la
01 Activación del dispositivo de protección
interior bandeja de desagüe
Unidad Activación de PSH, obstrucción de tuberías, refrigerante
02 Activación del dispositivo de protección
exterior excesivo, mezcla de gas inerte
Anomalía entre la unidad interior y la exterior (o Cableado incorrecto, terminales sueltos, cable
03
entre unidades exteriores) desconectado, desconexión del fusible
Transmisión
Anomalía entre la PCB del Inverter y la PCB
04 Fallo de transmisión (conector suelto)
exterior
Fase de Fuente de alimentación incorrecta, fase inversa, fase
05 Fase de la fuente de alimentación anómala
alimentación abierta
Caída de tensión exterior, capacidad de alimentación
06 Tensión Tensión del Inverter anómala
insuficiente
Disminución del sobrecalentamiento del gas de Carga excesiva de refrigerante, fallo del termistor,
07
descarga cableado incorrecto
Ciclo
Aumento de la temperatura del gas de Carga insuficiente de refrigerante, obstrucción de las
08
descarga tuberías, fallo de termistor, cableado incorrecto
11 Termistor de entrada de aire
12 Sensor de Termistor de salida de aire
la unidad Cableado incorrecto o desconectado
13 interior Termistor de protección contra congelación
14 Termistor de la tubería de gas
Motor del Activación del dispositivo de protección del
19 Sobrecalentamiento del motor del ventilador, bloqueo
ventilador ventilador de la unidad interior
21 Sensor de alta presión
22 Termistor de aire exterior
Sensor de
23 la unidad Termistor del gas de descarga Cableado incorrecto o desconectado
exterior
24 Termistor de tubería de evaporación
29 Sensor de baja presión

112 TCES0059 rev.2 - 06/2016


12 Resolución de problemas

Códigos de alarma para la serie FSNM

Código Categoría Contenido de la anomalía Causa principal


Capacidad incorrecta de la unidad exterior e
31 Ajuste incorrecto de la combinación de capacidad
interior
35 Ajuste del número de unidad interior incorrecto Número de la unidad interior duplicado
Sistema Fallo del circuito de detección de protección.
Anomalía del circuito protector de la unidad (Fallo del dispositivo de detección de protección,
38
exterior anomalía de la PCB exterior, cableado de la PCB
incorrecto)
Activación del dispositivo protector contra Compresión defectuosa (Fallo del comprensor del
43
disminución de baja presión Inverter, Conexión suelta de la fuente de alimentación)
Activación del dispositivo protector de aumento Sobrecarga en el enfriamiento, temp. alta en la
44
de la presión baja calefacción, bloqueo (conector suelto)
Operación de sobrecarga (obstrucción, paso breve),
Activación del dispositivo de protección de
45 Dispositivo de obstrucción de las tuberías, refrigerante insuficiente,
aumento de la presión alta
protección mezcla de gas inerte
Activación del dispositivo protector contra
Refrigerante insuficiente, obstrucción de las tuberías de
47 disminución de la presión baja (operación de
refrigerante, bloqueo (conector suelto)
vacío)
Activación del dispositivo de protección contra
48 Operación de sobrecarga, fallo del compresor
sobreintensidad del Inverter
51 Sensor Sensor de corriente anómala Fallo del sensor de corriente
Detección de señal de error de IC de unidad (protección
53 Detección de señal de error del inverter
de sobretensión, baja tensión, cortocircuito)
Inverter Aumento de la temperatura de las aletas del Termistor anómalo de las aletas del Inverter, obstrucción
54
Inverter del intercambiador de calor, ventilador anómalo
55 Fallo del Inverter Fallo de la PCB del inverter
Motor del
Desconexión del cableado o cableado incorrecto entre
ventilador
57 Anomalía del motor del ventilador la PCB de control PCB (PCB1) y la PCB del relé del
de la unidad
ventilador (PCB3, PCB5), fallo del motor del ventilador
exterior
EE Compresor Alarma de protección del compresor Fallo del compresor
Ajuste del
número de Se ha ajustado un número superior a 64 para la dirección
b1 Ajuste del número de unidad exterior incorrecto
la unidad o para el ciclo de refrigerante.
exterior
Ajuste del
Ajuste del número de la unidad interior Se han conectado más de 17 unidades no
b5 número de la
incorrecto correspondientes a H-LINK II en un sistema.
unidad interior

12

113 TCES0059 rev.2 - 06/2016


Hitachi Air Conditioning Products Europe, S.A.U.
Ronda Shimizu, 1 - Polig. Ind. Can Torrella
08233 Vacarisses (Barcelona) España

Hitachi certifica que nuestros productos reúnen los requisitos de seguridad


de salud y ambientales de la UE.

Hitachi Air Conditioning Products Europe, S.A.U. dispone de los certificados:


ISO 9001 por AENOR España por su Gestión de la Calidad según la norma
ISO 14001 por AENOR España por sus sistemas de Gestión
Medioambiental según la norma

Los productos de aire acondicionado Hitachi están fabricados según:


ISO 9001 por JQA Japón por su Gestión de la calidad según la norma.
ISO 14001 por JACO Japón por sus sistemas de Gestión
Medioambiental según la norma.

HITACHI participa en el programa de Certificación EUROVENT; los datos de


certificación de los modelos figuran en el Directorio de Certificación Eurovent
(www.eurovent-certification.com).

TCES0059 rev.2 - 06/2016 Impreso en España

También podría gustarte